Main Feeds Schematic for Bradenton Water Reclamation Facility
This document is an electrical infrastructure schematic for the City of Bradenton, Florida's Water Reclamation Facility (WRF) and associated satellite facilities. The WRF receives primary power from Florida Power and Light through a 480V transformer and is supported by three generators with automatic transfer switches. The facility contains seven main motor control centers (MCCs) and multiple subpanels distributed across various operational buildings, including the Generator Building, Sludge Pumping Station, Digester, New Clarifier, Chemical Building, Maintenance Building, Operations Building, Blower Building, and Filter Lift Buildings. The Mixon and Tropicana facilities, located offsite, each maintain independent 480V feeds from FPL with associated MCCs. All circuit breakers throughout the system are molded case configurations with various relays and contactors, and many pumps are controlled by variable frequency drives or adjustable speed drives. The electrical distribution system serves numerous pumps, motors, blowers, air conditioning units, air compressors, hoists, and heating equipment, with transformers providing 120V control power distribution across multiple locations.
The schematic details the specific feeder and load configurations for each MCC and subpanel, documenting main feeder breakers, generator automatic transfer switches, interconnections between boards, and the number of feeds serving various equipment at each location. This documentation serves as the baseline electrical inventory for the City's comprehensive Electrical Capacity and Emergency Power Evaluation project, providing the engineering firm selected through the RFQ process with essential reference material for assessing current electrical loads, available capacity, system reconfiguration recommendations, arc flash hazards, and emergency power adequacy at the facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bradenton Water Reclamation Facility (WRF) is directly fed from Florida Power and Light through a 480V transformer onsite. Mixon and Tropicana, located offsite, are fed similarly.
All MCCs and noted subpanels are 480V.
All breakers are believed to be molded case circuit breakers with various configurations (relays, contactors, etc)
Many of the pumps are VFD/ASD controlled.
FPL Feed
WRF
ATS for Generator #1
MCC "M2"
Generator Bldg
MCC "A"
Sludge Pumping Sta
MCC "MB"
Digester
"MDP1" Panel New Clarifier
Sludge Handling Panel
Chemical Bldg Panel
Maint Bldg Panel
Operations Bldg Panel
ATS for Generator #2
MCC "M1"
Blower Bldg
Panel 2017 Air Compressor
ATS for Generator #3
MCC "3"
Filter Lift Bldg
MCC "4"
Filter Lift Bldg
MCC "6"
Headworks
Panel PP1
FPL Feed Mixon
MCC "A" MCC "B"
FPL Feed Tropicana
MCC "P"
WRF - MCC “M2”
1 main feeder breaker (line side of ATS) 1 generator automatic transfer switch (this board only) 2 feeds to other 480V MCCs o MCC “A” – main feeder breaker, 6 pumps and air conditioner, 1 120V xfmr o MCC “MB” – main feeder breaker, 5 pumps and fans, 1 120V xfmr
5 feeds to other 480V subpanels o Panel “MDP1” – covered by upgrade project o Sludge Handling Panel – main feeder breaker, 8 pumps and control panels, 1 120V xfmr o Chemical Bldg Panel – o Maint Bldg Panel – main, 8 hoists heaters and air handler, 120V xfmr o Operations Bldg Panel –
1 feed to 120V xfmr 11 feeds to various pumps, motors, blowers
WRF - MCC “M1” (Blower Bldg)
1 generator automatic transfer switch (this board only) 1 feed to a 480V subpanel o Panel 2017 – air conditioner, air compressor 18 feeds to various pumps, motors, blowers
1 feed to control power
WRF - MCC “3”
1 main feeder breaker (load side of ATS) 7 feeds to various pumps, motors, blowers 1 tie-breaker to MCC “4”
WRF - MCC “4”
1 generator automatic transfer switch for bds MCC “3” / MCC “4” / MCC “6” 1 main feeder breaker (load side of ATS) 2 feeds to various pumps, motors, blowers
WRF - MCC “6”
1 main feeder breaker (load side of ATS) 12 feeds to pumps or ASD filters 1 feed to a 480V subpanel
Mixon – MCC “A” 1 main feeder breaker 3 feeds to pumps
Mixon – MCC “B”
3 feeds to pumps
Tropicana – MCC “P”
1 120V xfmr 5 feeds to pumps and air compressor