Bldg-F-FireAlarmSystem-BidDwgs.pdf

PDF 10 MB Posted

Attached to
Corrections Mechanical Electrical & Plumbing Upgrades-Building F
Solicitation number
Y23-735
Issued by
Orange County, Orlando City, Florida

About this file

The document is a set of bid drawings prepared by Hanson Professional Services Inc. for the Orange County Government in Florida, specifically for the Fire Alarm System Replacement at Building F of the 33rd Street Correctional Facility. The project involves a comprehensive replacement of the existing fire alarm system, including removal of existing fire alarm panels, devices, wiring, and conduit, and installation of a new standalone digital, addressable system. The new system will be designed per NFPA 72, 101, and 70 (NEC) requirements and must be compatible with existing campus-wide fire alarm systems. The drawings are dated October 14, 2022, and are issued for bidding purposes, covering electrical demolition and fire alarm system plans for all four floors of Building F.

The fire alarm system replacement is part of a larger Mechanical, Electrical, and Plumbing (MEP) upgrade project for the corrections facility, with an estimated project cost of $8,000,000. The project is specifically focused on Building F, which is used for maintaining and housing inmates and is regularly occupied. The new fire alarm system will also be required to interface with and support a new smoke control equipment replacement project being designed by another engineering firm. Bidders are required to submit responses electronically via the OpenGov e-Procurement Platform by 4:00 pm EST on Thursday, February 16, 2023, with no alternative submission methods permitted.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2020

54321 6

E

D

C

B

A

54321 6

MARK DATE DESCRIPTION

SEAL

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022 17G0175A

DLH

DLH

RN/AT

100% BID DOCS

DRAWING INDEX

SHEET

NO. SHEET NAME

G001 PROJECT TITLE SHEET

39th Street, Orlando, FL 32839

100% BIDDING DOCUMENTS

OCTOBER 14, 2022

OC CORRECTIONS FIRE ALARM SYSTEM REPLACEMENT

BUILDING F

HANSON PROFESSIONAL SERVICES INC.

2300 Maitland Center Parkway, Suite 310

Maitland, FL 32751

(407) 622-2050

CODES IN EFFECT AT TIME OF DRAWING SUBMITTAL

FLORIDA BUILDING CODE, SIXTH EDITION (2017)

FLORIDA ENERGY CONSERVATION CODE, SIXTH EDITION (2017)

NEC (NFPA 70) 2014 EDITION

TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS

COMPLY WITH THE 2017 FLORIDA BUILDING CODE WITH ALL CURRENT

AMENDMENTS.

PROJECT INFORMATION

SCOPE OF WORK

The scope of work is for the replacement of the fire alarm systems (FAS) within Building F located at the 33rd Street Correctional Facility in Orange County, FL. Building F at the 33rd Street Correctional Facility is used for maintaining and housing inmates and the building is regularly occupied. The replacement fire alarm system will be required to interface with and support a new smoke control equipment replacement project being designed by another engineering firm.

FIRE ALARM ENGINEERS

ORANGE COUNTY MAYOR

Jerry L. Demings

DISTRICT 1 COMMISSIONER

Nichole H. Wilson

DISTRICT 2 COMMISSIONER

Christine Moore

DISTRICT 5 COMMISSIONER

Emily Bonilla

DISTRICT 6 COMMISSIONER

Victoria P. Siplin

DISTRICT 4 COMMISSIONER

Maribel Gomez Cordero

DISTRICT 3 COMMISSIONER

Mayra Uribe

PROJECT LOCATION

ED-101 BUILDING - F FLOOR PLAN 1ST FLOOR - ELECTRICAL DEMOLITION

ED-102 BUILDING - F FLOOR PLAN 2ND FLOOR - ELECTRICAL DEMOLITION

ED-103 BUILDING - F FLOOR PLAN 3RD FLOOR - ELECTRICAL DEMOLITION

ED-104 BUILDING - F FLOOR PLAN 4TH FLOOR - ELECTRICAL DEMOLITION

E-101 BUILDING - F FLOOR PLAN 1ST FLOOR - FIRE ALARM SYSTEM

E-102 BUILDING - F FLOOR PLAN 2ND FLOOR -FIRE ALARM SYSTEM

E-103 BUILDING - F FLOOR PLAN 3RD FLOOR - FIRE ALARM SYSTEM

E-104 BUILDING - F FLOOR PLAN 4TH FLOOR - FIRE ALARM SYSTEM

E-501 FIRE ALARM DETAILS

The fire alarm system replacement will consist of the removal of the existing fire alarm system including fire alarm panels, fire alarm devices, wiring, and conduit if required, and the installation of a new stand-alone digital, addressable system. The new fire alarm system shall be designed per NFPA 72, 101, and 70 (NEC) requirements and shall be compatible with existing campus wide fire alarm systems.

E-001 FIRE ALARM AND ELECTRICAL LEGEND AND NOTES

E-601 BUILDING - F FIRE ALARM RISER

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

E-011 BUILDING F - FIRE ALARM SYSTEM PROJECT PHASING PLAN

E-012 BUILDING F OVERALL SITE PLAN - FIRE ALARM SYSTEMS

BUILDING F -

FIRE ALARM

SYSTEM

PROJECT

TITLE SHEET

G-001 www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

FIRE ALARM AND

ELECTRICAL

LEGEND AND

NOTES

E-001

AutoCAD SHX Text

HORN/STROBE LIGHT COMBINATION, WALL MOUNT 80" A.F.F.

AutoCAD SHX Text

FIRE ALARM ANNUNCIATOR PANEL

AutoCAD SHX Text

FIRE ALARM CONTROL PANEL

AutoCAD SHX Text

HEAT DETECTOR, CEILING MOUNTED

AutoCAD SHX Text

STROBE LIGHT, WALL MOUNT 80" A.F.F. PROVIDE CODE

AutoCAD SHX Text

TAMPER SWITCH

AutoCAD SHX Text

FLOW SWITCH

AutoCAD SHX Text

%%UFIRE ALARM

AutoCAD SHX Text

SMOKE DETECTOR, CEILING MOUNTED U.O.N.

AutoCAD SHX Text

DOUBLE ACTION MANUAL PULL STATION, WALL MOUNTED

AutoCAD SHX Text

ELECTRICAL PANELBOARD

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text

%%UPOWER

AutoCAD SHX Text

FIRE ALARM ELECTRICAL LEGEND

AutoCAD SHX Text

DUCT MOUNTED SMOKE DETECTOR (PROVIDE SAMPLING TUBE LENGTHS AS REQUIRED)

AutoCAD SHX Text

REQUIRED STROBE INTENSITY (75 CANDELA MINIMUM)

AutoCAD SHX Text

PROVIDE CODE REQUIRED STROBE INTENSITY (75 CANDELA

AutoCAD SHX Text

MINIMUM). WP = WEATHERPROOF DEVICE.

AutoCAD SHX Text

HORN, WALL MOUNT 80" A.F.F. WP = WEATHERPROOF DEVICE

AutoCAD SHX Text

WP

AutoCAD SHX Text 42" A.F.F.

AutoCAD SHX Text

WP

AutoCAD SHX Text

FIRE ALARM TERMINAL CABINET (NUMBER IDENTIFIES CABINET NUMBER/ID)

AutoCAD SHX Text R

AutoCAD SHX Text

DUCT MOUNTED SMOKE DETECTOR AHU SHUT-DOWN RELAY,

AutoCAD SHX Text

MOUNT WITHIN 3'-0" OF MOTOR STARTER

AutoCAD SHX Text

DUCT MOUNTED SMOKE DETECTOR REMOTE TEST STATION

AutoCAD SHX Text

WITH INDICATOR LIGHT, WALL MOUNT 48" A.F.F. TO TOP

AutoCAD SHX Text W

AutoCAD SHX Text

FLASHING ELEVATOR WARNING LIGHT, WALL MOUNT ADJACENT

AutoCAD SHX Text

TO CALL BUTTONS. PROVIDE RED PLASTIC SIGN WITH WHITE

AutoCAD SHX Text

LETTERS TO READ: "DO NOT USE ELEVATOR"

AutoCAD SHX Text

ELECTRICAL GENERAL NOTES

AutoCAD SHX Text CONTRACTOR SHALL COORDINATE ALL PROJECT PHASING AND SCHEDULING REQUIREMENTS WITH OWNER AND ARCHITECT/ENGINEER PRIOR TO BIDDING. THE CONTRACTOR SHALL PROVIDE A COMPLETE AND OPERATIONAL FIRE PROTECTION SYSTEM. THE CONTRACTOR SHALL PROVIDE ALL OPENINGS THROUGH WALLS, FLOORS AND/OR ROOF REQUIRED FOR THE NEW WORK. CONTRACTOR SHALL COORDINATE LOCATIONS AND SIZES OF ALL PENETRATIONS THROUGH WALLS, FLOORS AND/OR ROOF WITH EXISTING FIELD CONDITIONS. CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR REQUIRED TO PROPERLY AND EFFECTIVELY PROTECT SURROUNDING EQUIPMENT, FURNITURE, FINISHES, ETC. LOCATED WITHIN THE PROJECT BOUNDARY THROUGHOUT ENTIRE PROJECT. ANY DAMAGE TO SURROUNDING EQUIPMENT, FURNITURE, FINISHES, ETC. RESULTING FROM FAILURE TO ADHERE TO THIS REQUIREMENT SHALL BE REPAIRED, BY THE CONTRACTOR, TO ORIGINAL CONDITION, TO THE SATISFACTION OF OWNER AND ARCHITECT/ENGINEER, AT NO ADDITIONAL COST TO OWNER. CONTRACTOR SHALL IMMEDIATELY REPORT ANY SUCH OCCURRENCE TO THE OWNER AND ARCHITECT/ENGINEER AND SHALL RECEIVE WRITTEN DIRECTION PRIOR TO PROCEEDING WITH REPAIRS. DEVICE LOCATIONS, EQUIPMENT LOCATIONS AND CIRCUITING ARE DIAGRAMMATIC. FINAL LOCATIONS AND CIRCUITING SHALL BE DETERMINED BY FIELD CONDITIONS AND/OR AS DIRECTED BY ARCHITECT/ ENGINEER. PROJECT MANUAL, ELECTRICAL SPECIFICATIONS, ARE MADE PART OF THE CONTRACT DOCUMENTS. CONDUCT SELECTIVE WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER WHICH ENSURES MINIMUM INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING AREAS, WALKWAYS, AND OTHER ADJACENT OCCUPIED FACILITIES. CONTRACTOR SHALL PROVIDE DUST AND NOISE CONTROL AND PROTECTION FOR ALL WORK. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION. IF HAZARDOUS MATERIALS ARE ENCOUNTERED DURING WORK OPERATIONS, COMPLY WITH ALL APPLICABLE REGULATIONS, LAWS AND ORDINANCES CONCERNING REMOVAL, HANDLING AND PROTECTION AGAINST EXPOSURE, OR ENVIRONMENTAL POLLUTION. CONTRACTOR SHALL PROVIDE FOR PROPER AND LEGAL DISPOSAL, AND SHALL PROVIDE DOCUMENTATION OF SUCH. REMOVE DEBRIS, RUBBISH, ETC. RESULTING FROM WORK OPERATIONS FROM THE PROJECT SITE DAILY. TRANSPORT AND LEGALLY DISPOSE OF MATERIALS OFF-SITE. SUBMIT 1/2" = 1'-0" SCALE EQUIPMENT ROOM COORDINATED AND COMPREHENSIVE SHOP DRAWINGS, INCLUDING INTERIOR ELEVATIONS. SHOW ALL SYSTEMS WITH WORKING CLEARANCES DOCUMENTED. CONTRACTOR IS CAUTIONED TO FIELD VERIFY ALL EXISTING UTILITIES AND EXISTING CONDITIONS PRIOR TO BIDDING. CONTRACTOR SHALL INCLUDE ALL WORK REQUIRED TO SATISFY THE FIELD AND PROJECT REQUIREMENTS. COMMENCEMENT OF WORK SHALL BE CONSTRUED AS EVIDENCE THAT SUCH VERIFICATION HAS BEEN MADE AND FUTURE CLAIMS FOR MATERIAL AND/OR LABOR RESULTING FROM UNFORESEEN DIFFICULTIES WILL NOT BE RECOGNIZED. ALUMINUM CONDUCTORS, MATERIALS, RACEWAYS, BOXES, ETC. ARE EXPRESSLY PROHIBITED. THE CONTRACTOR, THROUGH OWNER AND ARCHITECT/ENGINEER COORDINATION, SHALL BE RESPONSIBLE FOR LOCATING, IDENTIFYING, AS-BUILTING, AND PROTECTING ALL EXISTING UTILITY LINES LOCATED WITHIN PROJECT BOUNDARY LIMITS, INCLUDING ALL COSTS FOR SUCH. THIS PROJECT WILL REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING HIS PROPOSED WORK SEQUENCE WITH THE OWNER AND SHALL PROVIDE IN HIS BID ALL COSTS FOR SUCH. TEMPORARY DOWNTIME FOR SYSTEM TIE-INS THROUGHOUT ENTIRE PROJECT SHALL BE PRE-APPROVED BY THE OWNER AND SCHEDULED IN ADVANCE. THE INFORMATION CONTAINED HEREIN HAS BEEN COORDINATED TO EXISTING OWNER SUPPLIED BUILDING AREA PLANS, OWNER FURNISHED DATA, AND SITE OBSERVATIONS. THE CONTRACTOR SHALL CONFIRM ALL FIELD CONDITIONS, TIE-IN POINTS AND EQUIPMENT SPACE AVAILABILITY PRIOR TO BIDDING. CONTRACTOR SHALL MAINTAIN A SCALED, ACCURATE RECORD OF AS-BUILT DRAWINGS SHOWING DEVICE AND EQUIPMENT LOCATIONS, CONDUCTORS, RACEWAYS, SIZES, BREAKERS, ETC. FOR ALL SYSTEMS AFFECTED BY THIS WORK, THROUGHOUT THE DURATION OF THE PROJECT. AS-BUILT DRAWINGS SHALL BE SUBMITTED TO OWNER AT THE CONCLUSION OF THE WORK. CONTRACTOR'S PROPOSAL SHALL INCLUDE ALL COSTS TO PROVIDE A COMPLETE, FUNCTIONING SYSTEM, INCLUDING ALL DEMOLITION AND SURFACE RESTORATION. WHERE RACEWAYS PENETRATE A FIRE RATED WALL, FLOOR, ETC., FIRESTOPPING SHALL BE PROVIDED. MEET ALL REQUIREMENTS FOR U.L. ASSEMBLY INVOLVED. PROVIDE FIRESTOPPING U.L. LISTED FOR ASSEMBLY AND/OR RACEWAYS INVOLVED. WHERE DRAWINGS INDICATE THE INSTALLATION OF A NEW CIRCUIT BREAKER IN AN EXISTING PANELBOARD, THE AIC RATING OF THE NEW CIRCUIT BREAKER SHALL MATCH THE EXISTING. PROVIDE NEW TYPED PANEL DIRECTORIES FOR ALL PANELBOARDS AFFECTED BY THIS PROJECT. ALL DEVICES LOCATED IN FINISHED SPACES (I.E. OFFICE AREAS, CONFERENCE ROOMS, TOILETS, STORAGE ROOM, OR ANY OTHER NORMALLY OCCUPIED SPACE) SHALL BE FLUSH MOUNTED. ALL RACEWAYS ROUTED IN FINISHED SPACES SHALL BE CONCEALED ABOVE CEILING OR IN WALLS. DEVICES LOCATED IN UNFINISHED SPACES (I.E. MECHANICAL ROOMS, ELECTRICAL ROOMS, JANITORS CLOSETS, BATTERY ROOMS, CHILLER PLANT) MAY BE SURFACE MOUNTED. RACEWAYS ROUTED IN UNFINISHED SPACES MAY BE EXPOSED. WHERE RACEWAYS ROUTED IN FINISHED SPACES CANNOT BE CONCEALED DUE TO FIELD CONDITIONS, USE OF SURFACE METAL RACEWAY MAY BE GRANTED. CONTRACTOR SHALL IMMEDIATELY NOTIFY OWNER AND ARCHITECT/ENGINEER, AND SHALL RECEIVE WRITTEN DIRECTION PRIOR TO PROCEEDING WITH USE OF SURFACE METAL RACEWAY.

AutoCAD SHX Text 5.

AutoCAD SHX Text 4.

AutoCAD SHX Text 3.

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text 6.

AutoCAD SHX Text 7.

AutoCAD SHX Text 8.

AutoCAD SHX Text 9.

AutoCAD SHX Text 10.

AutoCAD SHX Text 11.

AutoCAD SHX Text 12.

AutoCAD SHX Text 13.

AutoCAD SHX Text 14.

AutoCAD SHX Text 15.

AutoCAD SHX Text 16.

AutoCAD SHX Text 17.

AutoCAD SHX Text 18.

AutoCAD SHX Text 19.

AutoCAD SHX Text 20.

AutoCAD SHX Text 21.

AutoCAD SHX Text 22.

AutoCAD SHX Text 23.

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

FACP

AutoCAD SHX Text

FAAP

AutoCAD SHX Text

FATC1

AutoCAD SHX Text J

AutoCAD SHX Text 24.

AutoCAD SHX Text 25.

AutoCAD SHX Text

FIRE ALARM REMOTE DIGITAL COMMUNICATOR

AutoCAD SHX Text

FADC

AutoCAD SHX Text

FIRE ALARM CIRCUIT HOMERUN, "FATC-1" = TERMINAL CABINET NAME

AutoCAD SHX Text

FATC-1

AutoCAD SHX Text

FIRE ALARM AUXILLARY POWER SUPPLY CABINET

AutoCAD SHX Text

FAPS

AutoCAD SHX Text C

AutoCAD SHX Text

LAPTOP/CPU COMPUTER OUTLET/CONNECTION - PROVIDE 2-GANG BOX WITH 1-GANG

AutoCAD SHX Text

RING AT +18" AFF AND RUN (1) 3/4"C. FROM BOX TO FACP. PROVIDE AND INSTALL

AutoCAD SHX Text

WIRING AND OUTLET COMPLETE TO FACP FOR FUTURE COMPUTER ACCESS TO FACP.

www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDINGS D, E,

F - FIRE ALARM

SYSTEM

PROJECT

PHASING PLAN

E-011

AutoCAD SHX Text

%%UOVERALL BUILDING 1ST FLOOR - FIRE ALARM SYSTEM PHASING PLAN

AutoCAD SHX Text

SCALE: 1/16" = 1'-0"

AutoCAD SHX Text NEW FIRE ALARM DEVICES, REFER TO PROJECT SPECIFICATIONS, GENERAL NOTES, AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

%%UCURRENT PHASE BUILDING F

AutoCAD SHX Text

%%UEXISTING BUILDING E

AutoCAD SHX Text

%%UEXISTING BUILDING D

AutoCAD SHX Text

%%USMOKE CONTROL SYSTEM COORDINATION NOTE:

AutoCAD SHX Text FIRE ALARM SYSTEM CONTRACTOR AND EQUIPMENT VENDOR SHALL COORDINATE ALL NEW FIRE ALARM SYSTEM WORK WITH

AutoCAD SHX Text CONCURRENT TLC ENGINEERING SOLUTIONS "ORANGE COUNTY CORRECTIONS BUILDING D, E, F - MECHANICAL AND FIRE

AutoCAD SHX Text PROTECTION UPGRADES PROJECT (Y19-806)" CONTRACT DOCUMENTS PERMIT SET DATED JULY 17, 2021.

AutoCAD SHX Text FIRE ALARM SYSTEM CONTRACTOR AND EQUIPMENT VENDOR SHALL INTERFACE ALL NEW SMOKE CONTROL SYSTEM WORK

AutoCAD SHX Text ALARM AND REPORTING POINTS RECEIVED FROM THE CONCURRENT TLC ENGINEERING SOLUTIONS "ORANGE COUNTY CORRECTIONS

AutoCAD SHX Text BUILDING D, E, F - MECHANICAL AND FIRE PROTECTION UPGRADES PROJECT (Y19-806)" CONTRACT DOCUMENTS NOTED AS

NECESSARY FOR COMPLETE AND INTEGRATED FIRE ALARM SYSTEM AND SMOKE CONTROL SYSTEM.

www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDINGS A, B,

D, E, F OVERALL

SITE PLAN - FIRE

ALARM SYSTEMS

E-012

AutoCAD SHX Text

TO BUILDING-D

AutoCAD SHX Text

TO BUILDING-A

AutoCAD SHX Text

TO BUILDING-B

AutoCAD SHX Text

%%UBUILDINGS A, B, D, E, F OVERALL SITE PLAN - FIRE ALARM SYSTEMS

AutoCAD SHX Text

SCALE: 1" = 20'-0"

AutoCAD SHX Text NEW FIRE ALARM DEVICES, REFER TO PROJECT SPECIFICATIONS, GENERAL NOTES, AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

EXISTING FACP

AutoCAD SHX Text

NEW FACP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

%%UCURRENT PHASE BUILDING F

AutoCAD SHX Text

%%UEXISTING BUILDING E

AutoCAD SHX Text

%%UEXISTING BUILDING D

AutoCAD SHX Text

%%UEXISTING BUILDING B

%%UEXISTING BUILDING A

www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 1ST

FLOOR -

ELECTRICAL

DEMOLITION

ED-101

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 1ST FLOOR - ELECTRICAL DEMOLITION

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text EXISTING FIRE ALARM DEVICES TO BE REMOVED TO ACCOMMODATE INSTALLATION OF NEW FA SYSTEM. VERIFY EXACT LOCATIONS OF DEVICE IN THE FIELD.

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text F119

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F120

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F124

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F166

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F152

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F151

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F150

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F158

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F159

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F153

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F154

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F165

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F155

AutoCAD SHX Text

VISITATION AREA

AutoCAD SHX Text F118

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F117

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F123

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F127

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F142

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F145

AutoCAD SHX Text

STAIR

AutoCAD SHX Text F163

AutoCAD SHX Text

SECURITY VESTIBULE

AutoCAD SHX Text F144

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F143

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F137

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F141

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F140

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F139

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F138

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F136

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F122

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F131

AutoCAD SHX Text

CONTROL STATION

AutoCAD SHX Text F121

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F101

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F102

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F103

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F104

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F105

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F106

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F107

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F108

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F125

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F128

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F129

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F130

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F109

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F110

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F111

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F112

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F113

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F114

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F115

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F116

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F137

AutoCAD SHX Text

CONTROL STATION

AutoCAD SHX Text F135

AutoCAD SHX Text

SECURITY VESTIBULE

AutoCAD SHX Text F160

AutoCAD SHX Text

CONTROL ROOM

AutoCAD SHX Text F157

AutoCAD SHX Text

VISITATION LOBBY

AutoCAD SHX Text F156

AutoCAD SHX Text

VISITATION AREA

AutoCAD SHX Text F149

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F148

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F147

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F146

TOILET

OPEN TO

BELOW

OPEN TO

BELOW

OPEN TO

BELOW

OPEN TO

BELOW

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 2ND

FLOOR -

ELECTRICAL

DEMOLITION

ED-102

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 2ND FLOOR - ELECTRICAL DEMOLISTION

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text EXISTING FIRE ALARM DEVICES TO BE REMOVED TO ACCOMMODATE INSTALLATION OF NEW FA SYSTEM. VERIFY EXACT LOCATIONS OF DEVICE IN THE FIELD.

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text F217

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F218

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F241

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F240

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F218

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F217

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F228

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F245

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F244

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F238

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text F237

AutoCAD SHX Text

CLERICAL

AutoCAD SHX Text F239

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text F243

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F242

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F234

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text F235

AutoCAD SHX Text

EXAMINATION RM.

AutoCAD SHX Text F246

AutoCAD SHX Text

EXAMINATION RM.

AutoCAD SHX Text F227

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F201

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F202

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F203

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F204

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F205

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F206

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F207

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F208

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F229

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F230

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F229

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F230

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F216

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F215

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F214

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F213

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F212

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F211

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F210

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F209

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F226

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F225

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F233

CORRIDOR

www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 3RD

FLOOR -

ELECTRICAL

DEMOLITION

ED-103

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 3RD FLOOR - ELECTRICAL DEMOLITION

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

EXISTING FIRE ALARM DEVICES TO BE REMOVED TO ACCOMMODATE INSTALLATION OF NEW FA SYSTEM. VERIFY EXACT LOCATIONS OF DEVICE IN THE FIELD.

www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 4TH

FLOOR -

ELECTRICAL

DEMOLITION

ED-104

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 4TH FLOOR - ELECTRICAL DEMOLITION

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text EXISTING FIRE ALARM DEVICES TO BE REMOVED TO ACCOMMODATE INSTALLATION OF NEW FA SYSTEM. VERIFY EXACT LOCATIONS OF DEVICE IN THE FIELD.

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text F434

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F412

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F411

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F410

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F409

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F425

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F429

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F426

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F427

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F428

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F433

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text F437

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F422

AutoCAD SHX Text

STAIR

AutoCAD SHX Text F436

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F420

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F408

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F407

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F406

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F405

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F404

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F403

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F402

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F401

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F438

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F431

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F432

AutoCAD SHX Text

MECH.

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

S www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 1ST

FLOOR - FIRE

ALARM SYSTEM

E-101

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 1ST FLOOR - FIRE ALARM SYSTEM

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text NEW FIRE ALARM DEVICES, REFER TO PROJECT SPECIFICATIONS, GENERAL NOTES, AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text F119

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F120

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F124

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F166

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F152

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F151

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F150

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F158

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F159

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F153

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F154

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F165

AutoCAD SHX Text

COUNSELING

AutoCAD SHX Text F155

AutoCAD SHX Text

VISITATION AREA

AutoCAD SHX Text F118

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F117

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F123

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F127

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F142

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F145

AutoCAD SHX Text

STAIR

AutoCAD SHX Text F163

AutoCAD SHX Text

SECURITY VESTIBULE

AutoCAD SHX Text F144

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F143

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F137

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F141

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F140

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F139

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F138

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F136

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F122

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F131

AutoCAD SHX Text

CONTROL STATION

AutoCAD SHX Text F121

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F101

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F102

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F103

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F104

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F105

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F106

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F107

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F108

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F125

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F128

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F129

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F130

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F109

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F110

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F111

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F112

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F113

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F114

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F115

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F116

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F137

AutoCAD SHX Text

CONTROL STATION

AutoCAD SHX Text F135

AutoCAD SHX Text

SECURITY VESTIBULE

AutoCAD SHX Text F160

AutoCAD SHX Text

CONTROL ROOM

AutoCAD SHX Text F157

AutoCAD SHX Text

VISITATION LOBBY

AutoCAD SHX Text F156

AutoCAD SHX Text

VISITATION AREA

AutoCAD SHX Text F149

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F148

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F147

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F146

TOILET

OPEN TO

BELOW

OPEN TO

BELOW

OPEN TO

BELOW

OPEN TO

BELOW

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 2ND

FLOOR - FIRE

ALARM SYSTEM

E-102

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 2ND FLOOR - FIRE ALARM SYSTEM

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text NEW FIRE ALARM DEVICES, REFER TO PROJECT SPECIFICATIONS, GENERAL NOTES, AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text F217

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F218

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F241

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F240

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F218

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F217

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F228

AutoCAD SHX Text

ELEC.

AutoCAD SHX Text F245

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F244

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F238

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text F237

AutoCAD SHX Text

CLERICAL

AutoCAD SHX Text F239

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text F243

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F242

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F234

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text F235

AutoCAD SHX Text

EXAMINATION RM.

AutoCAD SHX Text F246

AutoCAD SHX Text

EXAMINATION RM.

AutoCAD SHX Text F227

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F201

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F202

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F203

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F204

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F205

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F206

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F207

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F208

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F229

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F230

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F229

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F230

AutoCAD SHX Text

MECH. RM,

AutoCAD SHX Text F216

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F215

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F214

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F213

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F212

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F211

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F210

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F209

AutoCAD SHX Text

ONE MAN CELL

AutoCAD SHX Text F226

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F225

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F233

CORRIDOR

www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIRE ALARM SYSTEM

REPLACEMENT

39th Street, Orlando, FL 32839

10/14/2022

DLH

DLH

100% BID DOCS

Engineering | Planning | Allied Services

Offices Nationwide www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751

(407) 622-2050

39th Street, Orlando, FL 32839

17G0175A

RN/AT

ISSUED FOR BIDDING

NOT FOR CONSTRUCTION

BUILDING F

FLOOR PLAN 3RD

FLOOR - FIRE

ALARM SYSTEM

E-103

AutoCAD SHX Text

%%UBUILDING-F FLOOR PLAN 3RD FLOOR - FIRE ALARM SYSTEM

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text NEW FIRE ALARM DEVICES, REFER TO PROJECT SPECIFICATIONS, GENERAL NOTES, AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text F325

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F323

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F327

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F312

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F311

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F318

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F313

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F314

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F315

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F316

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text F301

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F302

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F303

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F304

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F328

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F329

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F305

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F306

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F307

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F308

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F330

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F331

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text F326

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F324

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text F320

AutoCAD SHX Text

ROOM

AutoCAD SHX Text F322

AutoCAD SHX Text

STAIR

AutoCAD SHX Text F310

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F309

AutoCAD SHX Text F317

AutoCAD SHX Text

DAYROOM

AutoCAD SHX Text

FOUR MAN DORMITORY

AutoCAD SHX Text F334

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F335

AutoCAD SHX Text

MECH.

AutoCAD SHX Text F333

AutoCAD SHX Text

PROGRAM AREA

AutoCAD SHX Text F338

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F337

AutoCAD SHX Text

TOILET

AutoCAD SHX Text F339

AutoCAD SHX Text

CONTROL ROOM

AutoCAD SHX Text F340

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S www.hanson-inc.com

Hanson Professional Services Inc.

CONSULTANTS

EB0007061

AA0003116

IB0001058

SHEET TITLE

REVIEWED BY:

DRAWN BY:

DESIGN BY:

PROJECT NO:

ISSUE:

© Copyright Hanson Professional Services Inc. 2022

54321 6

E

D

C

B

A

54321 6

SEAL

MARK DATE DESCRIPTION

STATE OF

S

IG

N SEAL

PROFESSIONAL EN

GIN

EE

R

F L O R I D A

L I C E N S E

No. 00000

This item has been digitally signed and sealed by engineer name, P.E. on the date listed using a digital signature.

Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.

OC CORRECTIONS

BUILDING F

FIR…

This is the start of the file's text. The full file is on GovTribe.