This document package includes construction plans and specifications for repairing the exterior of Building 1812 at the Tennessee Air National Guard base in Alcoa, Tennessee. The project involves replacing exterior stairs, repairing concrete walkways, and installing new landscaping. Specifications provide requirements for concrete mixes and finishes, as well as notes on excavation safety, utility locates, and site stabilization.
The related federal contract opportunity is solicitation number W50S98-23-B-0005 for base-wide repairs to facility exteriors in Tennessee under the Department of the Army Tennessee Army National Guard. The solicitation seeks offers for general construction services including but not limited to concrete work, masonry, carpentry and roofing repairs. Pricing, response dates and potential award dates are not included in the provided information.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TENNESSEE AIR NATIONAL GUARDTENNESSEE AIR NATIONAL GUARD
23 SEPTEMBER 2022
134 ARW/CE
PROJECT REVIEW
DATE
DATE
DATE
DATE
DATE
DATE
ATO
SECURITY
PROJECT MANAGER
USER
ENVIRONMENTAL MANAGEMENT
COMMUNICATIONS
FIRE DEPARTMENT DATE
DATEGROUND SAFETY
DATEWING / CC
DATECIVIL ENGINEER
DATECONTRACTING OFFICER
REPAIR BUILDING 1812REPAIR BUILDING 1812
PSXE182009PSXE182009
AutoCAD SHX Text 240 West Bessemer Street Alcoa, TN 37701 ph. 865 980 3500
R ep ai r
B u ild in g
4t h A ir R ef u el in g W in g
PSXE182009
09.23.22
SCALE: 1" = '
0 20 40 60
20 C1.1
S it e La yo u t Pl an
RJB
CJS
CLEANOUT
SANITARY SEWER LINE
WATER LINE
MANHOLE
IRRIGATION CONTROL VALVE
FIRE HYDRANT
WATER METER
VALVE
GAS LINE
YARD HYDRANT
INTERMEDIATE CONTOUR
INDEX CONTOUR
CHAIN LINK FENCE
WOODEN FENCE
BACKFLOW PREVENTER
LEGEND
EXISTING
POST INDICATOR VALVE
POTENTIAL FUTURE
EXPANSION
FUTURE BUILDING EXPANSION
NEW CONCRETE SIDEWALK
WASHED RIVER ROCK
NEW
EXTEND CONCRETE SIDEWALK
REFER TO SHEET A1.1 FOR
EXACT LIMITS.
BUILDING 1812
BAND FACILITY
6.5'
5'
35'
GENERAL NOTES
1. LOCATIONS OF THE EXISTING ABOVE GROUND AND
UNDERGROUND UTILITIES AND STRUCTURES INDICATED
ARE APPROXIMATE ONLY. AND THOSE INDICATED ARE
NOT NECESSARILY ALL WHICH MAY EXIST ON THE
PROJECT SITE. CONTRACTOR SHALL DETERMINE
ACTUAL LOCATION OF ALL UTILITIES AND STRUCTURES
ON THE PROJECT SITE WHETHER THEY ARE INDICATED
OR NOT. CONTRACTOR SHALL ASSUME
RESPONSIBILITY FOR ANY DAMAGE TO THE UTILITY
LINES, WHETHER SHOWN ON THE CONSTRUCTION
PLANS OR NOT.
2. CONTRACTOR SHALL REQUEST A DIG PERMIT FROM
WORK CONTROL (865)336-4219 PRIOR TO ENGAGING IN
ANY EXCAVATION OR PENETRATING THE GROUND IN
ANY WAY.
3. CONTRACTOR SHALL ALSO CONTACT THE TENNESSEE
ONE CALL CENTER AT 811 FOR LOCATION OF ANY/ALL
ELECTRICAL FACILITIES. THE PRIMARY ELECTRICAL
SERVICE ON BASE IS OWNED AND OPERATED BY THE
CITY OF ALCOA ELECTRICAL DEPARTMENT. CONTACT
PERSON IS MR. MIKE LINDSAY (865)380-4853.
4. ONCE ALL EARTH DISTURBING ACTIVITIES HAVE BEEN
COMPLETED, ALL DISTURBED AREAS SHALL BE
STABILIZED WITH SOD AS SOON AS PRACTICAL.
K1 WASHED RIVER ROCK
NOT TO SCALE
1. ALL HARDSCAPE SHALL BE D50 12" WASHED RIVER SLICKS
OVER FABRIC VEGETATIVE BARRIER. NO STONES SMALLER
THAN 4" IN SMALLEST DIMENSION.
2. HARDSCAPE SHALL BE FLUSH WITH SIDEWALK/CURB
ELEVATION. SEE SECTION 1 & 2 OF DETAIL A1 SHEET C2.1.
NOTES:
PROPEX GEOTEX 801
NON-WOVEN FABRIC
OR EQUIVALENT
WASHED RIVER
SLICKS HARDSCAPE
2" SLOPE FROM FACE OF BLDG
12"
F1 CONCRETE SIDEWALK
NOT TO SCALE
x x x x x x x x x x x x x x x x
4" CONCRETE STOOP
4" MINERAL
INSTALL AGGREGATE BASE
TO 95% COMPACTION
12" (TYP.)
6"x6" W2.9xW2.9 WWF
SEE LAYOUT PLAN
FOR DIMENSION GRADE
1", TYP.
BOTH SIDES
SITE CONCRETE SPECIFICATION
1. THESE SPECIFICATIONS APPLY TO CONCRETE APPEARING ON THE CIVIL DRAWINGS.
2. ALL SITE CONCRETE SHALL BE 4,000 PSI COMPRESSIVE STRENGTH AT 28 DAYS WITH MAXIMUM SLUMP OF 4
TO 5 INCHES AND 6% (+/- 1%) AIR ENTRAINMENT; ASTM C94.
3. USE ACCELERATING ADMIXTURES IN COLD WEATHER ONLY WHEN ACCEPTABLE TO THE COR. USE OF ADMIXTURES SHALL NOT RELAX COLD WEATHER PLACEMENT REQUIREMENTS. DO NOT USE CALCIUM
CHLORIDE.
4. USE SET-RETARDING ADMIXTURES DURING HOT WEATHER ONLY WHEN ACCEPTABLE TO THE COR.
5. DO NOT PLACE CONCRETE WHEN BASE SURFACE TEMPERATURE IS LESS THAN 40 DEGREES F OR SURFACE
IS WET OR FROZEN.
6. PORTLAND CEMENT: ASTM C150; NORMAL - TYPE I.
7. MINERAL AGGREGATE BASE: ASTM C33 COMPACTED TO 95% .
8. WATER: CLEAN AND FREE FROM INJURIOUS AMOUNTS OF OIL, ALKALI, ORGANIC MATTER, OR OTHER
DELETERIOUS MATERIAL.
9. AIR ENTRAINMENT: ASTM C260 OR AASHTO M-154. AIR ENTRAINING ADMIXTURES SHALL BE ADDED TO THE
MIXER IN THE AMOUNT NECESSARY TO PRODUCE THE SPECIFIED AIR CONTENT.
10. CONCRETE SIDEWALK SHALL HAVE TNEMEC 664 DURA A PELL 40 SEALER APPLIED AS A FLOOD COAT AT 150 SQUARE FEET PER GALLON. SEALER SHALL BE APPLIED PER MANUFACTURER'S RECOMMENDATIONS.
11. ANY CONCRETE DAMAGED PRIOR TO FINAL ACCEPTANCE OF THE PROJECT SHALL BE REPLACED AT NO
EXPENSE TO THE GOVERNMENT.
A1 CONCRETE SPECIFICATIONS
NOT TO SCALE
K1 C1.1
F1 C1.1
F1 C1.1
EXISTING CONCRETE STOOP.
5'
NEATLY SAW CUT AND REMOVE
EXISTING EQUIPMENT PAD FOR
CONSTRUCTION OF EXTERIOR
STAIRS.
REFER TO SHEET M1.1 FOR
COORDINATION.
UPON COMPLETION OF STAIR
CONSTRUCTION POUR NEW
EQUIPMENT PAD FOR
CONDENSING UNIT.
SEE SHEET M1.1 FOR COORDINATION.
2'
AutoCAD SHX Text W
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PROJ. NO:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text 240 West Bessemer St. Alcoa, TN. 37701
AutoCAD SHX Text
ph. 865 980 3500 fax. 865 980 3555
AutoCAD SHX Text
COR
AutoCAD SHX Text H:\USPFO\47173 - BAND (BLDG1812) STAIRCASE AND FLOOR PLAN ANALYSIS\02-DRAWINGS\SHEETS\C1.1 SITE LAYOUT PLAN.DWG PLOTTED ON:October 25, 2022 1:14 PM BY:BECKY BOWEPLOTTED ON:October 25, 2022 1:14 PM BY:BECKY BOWEOctober 25, 2022 1:14 PM BY:BECKY BOWE1:14 PM BY:BECKY BOWEBY:BECKY BOWEBECKY BOWE
AutoCAD SHX Text Louisville, Tennessee
AutoCAD SHX Text Louisville, Tennessee
AutoCAD SHX Text
SS
AutoCAD SHX Text W
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text
YH
AutoCAD SHX Text
CO
AutoCAD SHX Text
ICV
AutoCAD SHX Text
BFP
AutoCAD SHX Text
COMPACTED SUBGRADE
| 00-Cover |
| Sheets and Views |
| COVER |
| 01-C1-1 Site Layout |
| Sheets and Views |
| Layout1 |
| 02-A1-1 Floor Plan & Elevations |
| 03-A1-2 Stair Details |
| 04-A1-3 Stair Specifications |
| 05-FP1-1 Floor Plan Fire Protection |
| 06-M1-1 Floor Plan HVAC |
| Sheets and Views |
| Model |
| 07-E1-1 Floor Plan Electrical |
| Sheets and Views |
| 20709-E1.1-Model |
| 08-E1-2 Electrical Specifications |
| Sheets and Views |
| 20709-E2.1-Model |