Bid_Plans.pdf

PDF 8 MB Posted

Attached to
Fleet Management Emergency Generator, Project No. 25143-130
Solicitation number
IFB- 26 - 347
Issued by
Pinellas County, Florida

About this file

This is a 100% design plan document prepared by Hall Engineering Group and Belt Engineering for the City of St. Petersburg, Florida's Fleet Management Emergency Generator project (Project No. 25143-130). The project involves the installation of a new 300 kilowatt emergency backup generator at the Fleet Management Complex located at 701 19th Street North, St. Petersburg, Florida, on an 8.05-acre parcel. The design includes a base bid configuration and an Alternate 1 option featuring a concrete masonry wall enclosure with access gates and lightning protection. The generator is designed to provide full backup power for up to 48 hours during utility outages to support half of the complex buildings. The site plan identifies existing utilities, drainage requirements, tree protection measures, and construction staging areas. All construction is designed in compliance with the Florida Building Code 8th Edition 2023, with structural design based on ASCE 7-22 wind loads of 146 miles per hour ultimate and a Risk Category II exposure category for the enclosed structure.

The design specifications establish a 4,000 psi concrete compressive strength for mat foundation construction with an allowable soil bearing capacity of 2,000 pounds per square foot. The site is located in Flood Zone X per the Federal Insurance Rate Map. Contractor responsibilities are explicitly detailed, including verification of all details and dimensions with existing conditions, submission of shop drawings for engineer review, and compliance with construction sequencing and curing plans. The document was approved for bid on September 25, 2026, by Brejesh Prayman, P.E., Director of Engineering & Capital Improvements Department, with engineering prepared by Joseph S. Guagliardo, P.E., Consulting Engineer Registration Number 80504.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ST PETERSBURG, FL

7th Ave. N

DRAWING INDEX

DESCRIPTIONSheet No.

11677-01

11677-02

11677-03

APPROVED FOR BID

BREJESH PRAYMAN, P.E. DATE

DIRECTOR OF ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

DATE: 09/25/2026

DRAWING No.: 11677

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

100% DESIGN

PROJECT NO. 25143-130

ECID DM

CLIENT DEPT

ECID PM

REVIEWER INITIALS

QA/QC APPROVAL

PLANS PREPARED BY:

KEITH W. HALL, P.E.

FL. REG. #: 55024

HALL ENGINEERING GROUP

3820 GUNN HWY., SUITE 200

TAMPA, FL, USA 33618

Drawing No.

G0

C1

S1

G0Sheet No.:

COVER SHEET & INDEX

SITE PLAN

SPECIFICATIONS & DESIGN CRITERIA

11677-04 S2 FLOOR PLAN AND ELEVATIONS

11677-05 S3 STRUCTURAL PLAN VIEW(S)

11677-06 S4 STRUCTURAL DETAILS

11677-08

11677-09

E1

E2

ELECTRICAL SPECIFICATIONS & LEGEND

ELECTRICAL PLAN

11677-10 E3 POWER ONE-LINE DIAGRAM & LOAD SUMMARY

11677-11 E4 ELECTRICAL DETAILS

11677-12 E5 LIGHTNING PROTECTION NOTES AND DETAILS

701 19TH ST. NORTH

ST. PETERSBURG, FL 33713

10/02/26

SCALE:

SITE PLAN

1/8"=1'-0"

PROTECTIVE BARRICADES SHALL BE PLACED AROUND ALL

PROTECTED TREES AND GRAND TREES DURING SITE CLEARING TO

CREATE A PROTECTIVE ROOT ZONE AND SHALL REMAIN IN PLACE

UNTIL LAND ALTERATION, SITE CLEARING AND CONSTRUCTION

ACTIVITIES ARE COMPLETE. BARRICADES FOR THE PROTECTIVE

ROOT ZONE SHALL BE ERECTED AT A MINIMUM DISTANCE OF: TREES

MEASURING 32" OR GREATER REQUIRE 20' OF PROTECTION, TREES

MEASURING 24-31" REQUIRE 15' OF PROTECTION, PROTECTED TREES

MEASURING 5-23" REQUIRE 10' OF PROTECTION AND PALMS ONLY 3'.

FOUR CORNER UPRIGHT STAKES OF NO LESS THAN 2" X 2" LUMBER

CONNECTED BY HORIZONTAL MEMBERS OF NO LESS THAN 1" X 4"

LUMBER; OR UPRIGHT STAKES SPACED AT 5' INTERVALS OF NO LESS

2" X 2" LUMBER CONNECTED BY SILT SCREEN FABRIC OR MATERIAL

OF COMPARABLE DURABILITY.

BARRIER SPECIFICATIONS FOR TREES

(MIN) SEE ABOVE

SITE ADDRESS: 7TH AVE. N.

ST. PETERSBURG, FL

PARCEL NUMBER: 13-31-16-00000-340-0300

FLOOD ZONE: "X" PER FIRM MAP 12103C0218G

LEGAL DESCRIPTION

FROM NW COR OF SE 1/4 OF SW 1/4 RUN S 430FT FOR POB TH E 419FT

(S) TH SE'LY ALONG W R/W OF RR 683FT (S) TH W 663FT (S) TH N 125FT

TH W 59.2FT TH N 205.2FT TH E 30FT TH N 290 FT (S)TO POB CONT 8.05

AC(C)

SITE DATA:

R401.3DRAINAGE.

SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER

CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT

DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN

SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE

SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10

FEET (3048 MM).

SITE NOTES:

TREE BARRICADE:

GENERAL NOTE

A. THIS SHEET IS FOR INFORMATIONAL PURPOSES ONLY,

COORDINATE WITH CITY PRIOR TO BIDDING AND CONSTRUCTION FOR

ALL CIVIL, DRAINAGE, SURVEY, UTILITIES, COORDINATES, EROSION

CONTROL, PARKING, TRAFFIC REQUIREMENTS, ETC. FIELD

DOCUMENT AS-BUILTS.

B. EXISTING INFORMATION INCLUDING UNDERGROUND SURVEY

INFORMATION WAS PROVIDED BY THE CITY. COORDINATE ALL

LOCATIONS, DIMENSIONS, AND UNDERGROUND OBSTRUCTIONS WITH

THE CITY PRIOR TO COMMENCING WORK AND AS-NEEDED.

GENERAL NOTES:

PARKING/ STAGING/ LIMITS

OF CONSTRUCTION

SCALE:

STAGING AREA

NOT TO SCALE

SCALE:

LOCATION MAP

NOT TO SCALE

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U E

U K

U K

U K

U K

U K

U K

U K

U K

U K

U E

UE UE UE UE UE UE UE UE UE UE UE UE UE UE UE UE

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

UK

UK

UK

UK

UK

UK

UK

UK

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

5' MINIMUM OFFSET

FROM PROPERTY

LINE (BID-ALT #1)

5' MINIMUM OFFSET

FROM PROPERTY LINE

(BASE BID)

EXIST. SAN.

SYSTEM (TYP)

EXIST. GAS SYSTEM

4" REMOVABLE BOLLARD (TYP)

COORDINATE FINAL QTY. AND

LOCATIONS W/ SELECTED BASE

BID OR ADD-ALT#1

EXIST. UTILITY POLE

EXIST. UNDERGROUND

WATER LINE (TYP)

EXIST. UNDERGROUND

GAS LINE (TYP)

FLEET MANAGEMENT

EXTERIOR WALL

EXIST. UTILITY

POLE GUY WIRES

EXIST. UNDERGROUND

ELECTRIC LINE (TYP)

EXIST. UNDERGROUND

SANITARY SEWER (TYP)

EXIST. UNKNOWN UNDERGROUND

UTILITY LINE (TYP)

CONFIRM EXACT NORTH

LOCATION/ALIGNMENT WITH

CITY.

EXIST. UTILITY POLE

MAINTAIN RELATIVE DISTANCE

BETWEEN GENERATOR AND ATS FOR

BOTH BASE BID AND ADD-ALT#1

ADD-ALT. #1

300 kW

GENERATOR

6'-8"

'-1 0"

GEN-FRONT

FR

O

N T

4"

ATS2'

-8

5'-3"

'-7

17'-0"

17'-0"

5'-10"

4' -1

4'-10"

4' -0

5'

-0

REMOVABLE BOLLARD BASE BID ONLY.

REMOVABLE BOLLARD

BASE BID ONLY.

REFER TO SUE FIELD REPORT (APRIL

2, 2026) FOR INFORMATION ON

CAPPED UTILITY. COORDINATE THE

CUT AND CAP (AS REQUIRED) OF

ABANDONED LINE FURTHER NORTH,

OUTSIDE THE FOOTPRINT OF

GENERATOR.

SITE PLAN

ET26-0069_WORKFILE.DWG 21.09.2026

JOSEPH S. GUAGLIARDO P.E. #80504

jguagliardo@beltengineering.com

PH.(813) 961-30751503-A WEST BUSCH BLVD.

TAMPA, FL. 33612

WWW.BELTENGINEERING.COM

FX.(813) 961-1031

CA # 29694

DATE: 9/25/26

SCALE: AS SHOWN

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: JG

DRAWN BY: RRC

CHECKED BY: JG

DATE: 9/25/26

DATE: 9/25/26

DATE: 9/25/26

BY DATER E V I S I O N S

ENGINEER OF RECORD:

SHEET No.

11677

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND

SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1

AUTHENTICATION CODE. PRINTED COPIES OF THIS

DOCUMENT ARE NOT CONSIDERED SIGNED AND

SEALED AND THE SHA-1 AUTHENTICATION CODE MUST

BE VERIFIED ON ANY ELECTRONIC COPIES.

email: jguagliardo@beltengineering.com

PHONE: (813) 961-3075

1503-A WEST BUSCH BLVD.

TAMPA FLORIDA 33612

FAX: (813) 961-1031

CONSULTING ENGINEER

REGISTRATION NUMBER 80504

JOSEPH S. GUAGLIARDO P.E.

I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE

AND BELIEF ALL OF THE STRUCTURAL ELEMENTS

AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN

DESIGNED TO BE IN COMPLIANCE WITH THE

FLORIDA BUILDING CODE 8TH EDITION 2023. ALL

OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES

ARE THE TOTAL RESPONSIBILITY OF OTHERS.

CA # 29694

BELT JOB #ET26-0069

C1

100% DESIGN

PARKING/STAGING/ LIMIT

OF CONSTRUCTION

GENERATOR

GENERATOR

Prel im in ary

N ot F or

Const ruct io n

STRUCTURAL SPECIFICATIONS

DESIGN CRITERIA

BASIS OF DESIGN:

ALL CONSTRUCTION IS DESIGNED AS FOLLOWS:

FLORIDA BUILDING CODE 8TH EDITION 2023 AS FOLLOWED BELOW:

FBC, BUILDING-2023

FBC, EXISTING BUILDING-2023

FBC, RESIDENTIAL-2023

DEAD LOADS

GENERATOR SET 210 PSF

LIVE LOADS

FLOOR 40 PSF

ROOF N/A PSF

PARTITIONS N/A PSF

RAIN LOADS

RAIN LOAD 20 PSF

RAIN INTENSITY 4.04 IN/HR

FLOOD ZONE

FLOOD ZONE X

WIND LOADS

ASCE 7-22, 146 MPH WIND (ULTIMATE), 113 MPH (NOMINAL)

N/A MPH TORNADO (ULTIMATE), N/A MPH TORNADO (NOMINAL)

BUILDINGS OF ALL HEIGHTS ANALYTICAL METHOD

RISK CATEGORY II

EXPOSURE CATEGORY "C"

ROOF SLOPE: N/A

INTERNAL PRESSURE COEFFICIENTS:

GCpi = +/- .18, ENCLOSED STRUCTURE BASIC WIND PRESSURE: q= xx.x P.S.F. (C&C) EDGE DISTANCE: a= x FT.

CONTRACTOR RESPONSIBILITIES:

1. THE FOLLOWING SPECIFICATIONS ARE AN OUTLINE OF MINIMUM MATERIAL REQUIREMENTS AND THEIR APPLICATION. MANUFACTURER SPECIFICATION AND LOCAL CODE REQUIREMENTS, WHEN IN EXCESS OF MINIMUM SPECIFICATION SHALL CONTROL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW AND

SUBMIT ALL SHOP DRAWINGS AND REPORT ALL DOCUMENT DISCREPANCIES TO THE STRUCTURAL

ENGINEER PRIOR TO FABRICATION OR ERECTION.

2. AT CONSTRUCTION ISSUE, THESE DRAWINGS REPRESENT STRUCTURAL COMPONENTS IN THEIR FINAL AND

FINISHED STATE. CONSTRUCTION PROCEDURES, BRACING, METHODS SAFETY PRECAUTIONS OR

MECHANICAL REQUIREMENTS USED TO ERECT THEM ARE THE SOLE RESPONSIBILITY OF THE GENERAL

CONTRACTOR OR SUBCONTRACTOR DOING THE WORK.

3. CONTRACTOR SHALL VERIFY ALL DETAILS AND DIMENSIONS WITH EXISTING CONDITIONS, CITY

DOCUMENTS AND PROPERLY COORDINATED, APPROVED SHOP DRAWINGS.

4. NO COMMENT, NOTE OR DETAIL IN THESE STRUCTURAL DOCUMENTS SHOULD BE MISCONSTRUED AS A DESIGN FOR WATERPROOFING OR DAMPPROOFING. SPECIFIC DESIGN FOR MOISTURE CONTROL AND PERMANENT PROTECTION OF STRUCTURAL MATERIALS FROM THE ELEMENTS IS TO BE COMPLETED BY

THE CONTRACTOR AND COORDINATED WITH THE STRUCTURAL DOCUMENTS.

5. CONTRACTOR SHALL OBTAIN LATEST SET OF DRAWINGS INCLUDING ANY REVISIONS BEFORE STARTING

CONSTRUCTION.

6. IT IS ASSUMED THAT THE CONTRACTOR HAS READ AND UNDERSTANDS THE NOTES, SPECIFICATIONS AND

DESIGN INTENT CONTAINED HEREIN.

7. THE CONTRACTOR SHALL REVIEW DRAWINGS IN THEIR ENTIRETY BEFORE STARTING WORK.

8. THE CONTRACTOR SHALL ACCEPT FULL RESPONSIBILITY FOR ANY ERRORS OR OMISSIONS NOT REPORTED

IMMEDIATELY IN WRITING TO THE ENGINEER OF RECORD.

9. CONTRACTORS WHO DISCOVER DISCREPANCIES, OMISSIONS OR VARIATIONS IN THE CONTRACT DOCUMENTS DURING BIDDING SHALL IMMEDIATELY NOTIFY THE S.E.O.R.. THE S.E.O.R. WILL RESOLVE THE

CONDITION AND ISSUE A WRITTEN CLARIFICATION.

10. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER OF RECORD

IN WRITING PRIOR TO PROCEEDING WITH THE AFFECTED PART OF THE WORK.

11. THE GENERAL CONTRACTOR SHALL COORDINATE ALL CONTRACT DOCUMENTS WITH FIELD

CONDITIONS/DIMENSIONS AND PROJECT SHOP DRAWINGS PRIOR TO CONSTRUCTION.

12. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS, AND JOBSITE

SAFETY INCLUDING ALL OSHA REQUIREMENTS.

13. THE CONTRACTOR SHALL PROTECT ADJACENT PROPERTY, HIS OWN WORK AND THE PUBLIC FROM HARM.

14. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS OR TIEDOWNS. WHEREVER THE CONTRACTOR IS UNSURE OF THESE REQUIREMENTS, THE CONTRACTOR SHALL RETAIN A QUALIFIED STATE LICENSED PROFESSIONAL ENGINEER TO DESIGN AND INSPECT THE TEMPORARY BRACING AND

STABILITY OF THE STRUCTURE.

15. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE STRUCTURE IS COMPLETE. PRIOR TO COMPLETION, THE RESPONSIBILITY FOR STABILITY AND TEMPORARY BRACING IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM

REQUIRED FOUNDATION AND SITE PREPARATION REQUIREMENTS, (INCLUDING SLAB ON GRADE

THICKNESS), TO HANDLE CONSTRUCTION LOADS.

16. THE GENERAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION AND SHORING PROCEDURES AND PROTECTION OF ADJACENT PROPERTY, STREETS AND UTILITIES IN ACCORDANCE WITH

LOCAL BUILDING DEPARTMENT.

17. WHEN PERFORMING WORK BELOW GRADE, CARE SHALL BE TAKEN TO AVOID DAMAGING ANY EXISTING

UTILITIES.

18. ALL UNKNOWN UTILITIES DISCOVERED DURING CONSTRUCTION SHALL BE BROUGHT TO THE ATTENTION OF THE CITY. ANY DAMAGE TO THE EXISTING UTILITIES SHALL BE IMMEDIATELY REPORTED TO ALL AFFECTED

PARTIES INCLUDING THE CITY.

FOUNDATION/SLAB-ON-GRADE:

1. CONCRETE COMPRESSIVE STRENGTH SHALL CONFORM TO THE FOLLOWING:

MAT FOUNDATION f'c = 4,000 psi

2. FOUNDATIONS AND SLAB ON GRADE SHALL COMPLY WITH "CONCRETE NOTES AND SPECIFICATION"

SECTION.

3. FOUNDATION IS TO BE A SHALLOW FOUNDATION SYSTEM.

3.1. FOOTINGS HAVE BEEN DESIGNED WITH THE ALLOWABLE SOIL BEARING OF "2,000 PSF"

4. TOPSOIL, VEGETATION, DEBRIS AND SURFACE SOILS CONTAINING ORGANIC MATERIALS SHALL BE REMOVED FROM THE BUILDING FOOTPRINT. THE BUILDING FOOTPRINT IS ASSUMED TO EXTEND AT

MINIMUM 5' BEYOND THE EXTENTS OF EVERY EXTERIOR BUILDING ELEMENT.

5. FOOTINGS SHALL BE PLACED IMMEDIATELY UPON EXCAVATION.

6. ALL EXTERIOR FOOTINGS SHALL BE EMBEDDED AT MINIMUM 12" BELOW LOWEST ADJACENT GRADE.

7. SEE CONCRETE SPECIFICATIONS FOR ALL CONCRETE COVER REQUIREMENTS.

8. ALL REINFORCEMENT MARKED AS CONTINUOUS SHALL BE LAPPED IN ACCORDANCE WITH "REINFORCING STEEL SPLICE NOTES".THERE SHALL BE NO PLUMBING LINES RUNNING PARALLEL TO, WITHIN OR UNDER

ANY FOUNDATION BEAM.

9. SLAB-ON-GRADE SHALL COMPLY WITH ACI 302 "GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION"

ACI 302.

10. ALL SLAB-ON-GRADE SHALL BE PLACED OVER 10 MIL (MINIMUM) POLYETHYLENE FILM VAPOR BARRIER.

11. MINIMUM ALLOWABLE THICKNESS FOR SLAB-ON-GRADE IS 4".

12. SLAB-ON-GRADE THAT IS ADJACENT TO AN EXISTING HARD SURFACE SHALL HAVE A BOND BREAKING

EXPANSION OR PRE-MOLDED JOINT BETWEEN THE TWO MATERIALS.

13. CONTRACTOR TO SUBMIT TO EOR IN WRITING A SLAB SEQUENCING AND CURING PLAN WHICH ALSO INDICATES ALL PLANNED CONTROL JOINTS. ANY REFERENCE TO CONTROL JOINT LAYOUT IN THIS PLAN SET SHALL BE CONSIDERED SCHEMATIC IN NATURE AND IS INTENDED ONLY TO REFERENCE THE

REQUIREMENTS OF THE CONTRACTOR.

13.1. NO CONTROL JOIN SHALL INTERSECT AN ADJACENT CONTROL JOINT AT AN ANGLE <90°.

13.2. CONTROL JOINTS SHALL ONLY INTERSECT A CURB OR OTHER STRUCTURAL MEMBER AT ANGLE OF 90°.

13.3. PREFERRED ASPECT RATIO FOR CONTROL JOINT SPACING IS 1:1 TO 1.5:1. AT NO TIME SHALL THE

CONTROL JOINT SPACING ASPECT RATIO EXCEED 2:1.

14. SLAB-ON-GRADE SHALL BE REINFORCED SUFFICIENTLY WITH WELDED WIRE REINFORCEMENT (W.W.R.), SEE TABLE, OR FIBER MESH PER MANUFACTURER'S REQUIREMENTS. CONTRACTOR TO SUBMIT USE OF FIBER MESH TO EOR AS AN ALTERNATE DESIGN AND PROVIDE QUANTITY, IN LBS/YD, TO BE USED. NO LESS

THAN 1.5 LBS/YD OF FIBER SHALL BE USED IN SLAB-ON-GRADE APPLICATIONS.

15. BACKFILLING OPERATIONS AGAINST FOUNDATION STEM WALLS SHALL BE COMPLETED WITH CARE USING SMALL, WALK BEHIND, VIBRATORY EQUIPMENT. NO TRUCKS OR OTHER HEAVY MACHINERY SHALL BE

ALLOWED WITHIN 6' OF ANY FOUNDATION STEM WALLS.

16. FOUNDATION WALLS THAT EXCEED 2'-8" IN HEIGHT SHALL BE BRACED AT THE TOP OF WALL PRIOR TO COMMENCING WITH ANY BACKFILLING OR COMPACTION ACTIVITIES. SUBMIT BRACE PLAN TO EOR FOR

APPROVAL.

15. AN INDEPENDENT CERTIFIED TESTING LAB SHALL VERIFY AND PROVIDE REPORTS CERTIFYING THE

FOLLOWING:

15.1. SOIL DENSITY TESTING

MASONRY (CMU):

1. CMU SHALL CONFORM TO THE FOLLOWING:

REINFORCED MASONRY f'm = 1,500 psi (ASTM C90) MASONRY GROUT f'c = 3,000 psi (ASTM 476)

MORTAR TYPE "S" OR "M"

2. THE DESIGN AND CONSTRUCTION MUST CONFORM TO BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES ACI530/ASCE 5, AND THE SPECIFICATIONS FOR MASONRY STRUCTURES ACI 530.1/ASCE 6, CURRENT CODE EDITIONS.

3. VERIFY ALL DETAILS AND DIMENSIONS WITH EXISTING CONDITIONS, ARCHITECTURAL DOCUMENTS AND

PROPERLY COORDINATED APPROVED SHOP DRAWINGS.

4. EXPANSION AND CONTROL JOINTS ARE TO BE PLACED PER A.C.I. RECOMMENDATIONS. PREPARE A CRACK

CONTROL PLAN BASED ON CONSTRUCTION SEQUENCING AND PROPOSED ACTUAL FLOOR AND WALL

FINISHES, AND SUBMIT TO THE ARCHITECT/ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION.

5. THE MASONRY CONTRACTOR MUST EMPLOY A CERTIFIED STRUCTURAL MASONRY INSPECTOR. THE INSPECTOR MUST BE IN ATTENDANCE AND MONITOR ALL REINFORCED MASONRY OPERATIONS INCLUDING

DOWEL PLACEMENT. PROVIDE DAILY REPORTS TO THE ENGINEER OF RECORD.

6. PROVIDE 48 BAR DIAMETER MINIMUM LAP FOR ALL SPLICES, U.N.O.

7. PROVIDE CONTINUOUS TRUSS TYPE OR LADDER TYPE #9 GAUGE GALVANIZED HORIZONTAL JOINT

REINFORCEMENT AT 16" O.C. WITH 8" MINIMUM LAP.

8. ALL CMU TEMPORARILY OR PERMANENTLY RESISTING SOIL SHALL BE FULLY GROUT FILLED.

9. ALL KNOCK OUT BLOCK HORIZONTAL BARS MUST HAVE CORNER CONTINUITY BARS AT ALL CORNERS AND

WALL INTERSECTIONS. SIZE AND NUMBER CORNER BARS MUST BE SAME AS HORIZONTAL BARS.

10. ALL INTERSECTING WALLS AND CORNER WALLS MUST BE LAID IN AN OVERLAPPING MASONRY BONDING

PATTERN.

11. PROVIDE REINFORCED FILLED CELL AT EVERY CORNER, JAMB, INTERSECTION, TERMINATION, TRANSITION

AND AT EACH SIDE OF CONTROL JOINT/EXPANSION JOINT.

12. ALL CONTINUOUS HORIZONTAL BARS SHALL BE LAPPED WITH AN ADDITIONAL CORNER BAR THAT MATCHES

IN SIZE AND QUANTITY IN EACH DIRECTION.

13. NO WATER SHALL BE ADDED TO THE GROUT AT THE JOBSITE. IT SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR TO COORDINATE WITH THE SUPPLIER TO ENSURE A PUMPABLE AND WORKABLE MIX

WITHOUT THE ADDITION OF WATER AT THE JOBSITE. THE USE OF PLASTICIZERS, RETARDANTS AND OTHER ADDITIVES SHALL BE AT THE OPTION OF THE CONTRACTOR SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER. FOLLOW THE RECOMMENDATIONS OF THE MANUFACTURER FOR THE PROPER USE OF ADDITIVES. THE USE OF CALCIUM CHLORIDE OR OTHER CHLORIDE BEARING SALTS SHALL NOT BE

PERMITTED.

14. GROUT SLUMP TESTS SHALL BE MADE BEFORE AND AFTER THE ADDITION OF ADMIXTURES AND MAY BE TAKEN AT THE BACK OF THE TRUCK. GROUT FOR THE PREPARATION OF TEST CYLINDERS SHALL BE TAKEN FROM THE HOSE END FOR GROUT PLACED BY PUMP. GROUT WITH A SLUMP BETWEEN 8 TO 11 INCHES

SHALL BE PROVIDED.

STRUCTURAL STEEL:

1. ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM SPECIFICATIONS, UNLESS NOTES

OTHERWISE ON PLAN:

ROLLED W SHAPES ASTM A992, GRADE 50

ROLLED C & MC SHAPES ASTM A36

ANGLES ASTM A36

ROUND HSS ASTM A500, GR B (Fy=42 KSI) RECTANGULAR HSS ASTM A500, GR B (Fy=46 KSI) PIPE ASTM A53, GR B (Fy=35 KSI)

PLATES ASTM A36

STEEL CONNECTION BOLTS A325

2. ALL SHOP AND FIELD WELDING SHALL CONFORM TO AWS STRUCTURAL WELDING CODE, ANSI/AWS D1.1, AND ALL WELDS SHALL BE PERFORMED USING E70XX U.N.O.

3. DESIGN CONNECTIONS FOR ALL BEAMS TO SUPPORT HALF OF THE UNIFORM CAPACITY SHOWN IN AISC "TABLES FOR ALLOWABLE LOADS ON BEAMS" FOR THE GIVEN SECTION AND SPAN UNLESS OTHERWISE

SHOWN ON PLANS.

4. GROUT BELOW BASE PLATES SHALL BE NON-SHRINK, NON-METALLIC GROUT WITH A MINIMUM

COMPRESSIVE STRENGTH OF 6000 PSI.

5. HOT-DIP GALVANIZE ALL STRUCTURAL STEEL ITEMS AND THEIR CONNECTIONS PERMANENTLY EXPOSED TO WEATHER AFTER FABRICATION. ALL FIELD AND ERECTION MARKS SHALL BE COVERED DURING FIELD

TOUCH-UP PAINTING.

6. CUTS, HOLES, COPING, AND ALL OTHER MODIFICATIONS REQUIRED TO BE MADE FOR THE WORK OF OTHER TRADES SHALL BE SHOWN IN THE STRUCTURAL STEEL SHOP DRAWINGS, AND SHALL BE PERFORMED ONLY BY THE SHOP ISSUING SAID DRAWINGS, OR OTHER FACILITY APPROVED BY THE ENGINEER TO PERFORM SAID WORK. HOLES IN STRUCTURAL ELEMENTS SHALL BE REINFORCED AS REQUIRED BY THE ENGINEER.

7. CUTS, HOLES, COPING, AND ALL OTHER MODIFICATIONS TO STEEL MEMBERS IN THE FIELD IS NOT

PERMITTED WITHOUT THE EXPLICIT APPROVAL OF THE ENGINEER.

SITE WORK:

1. PERFORM EXCAVATION, ACCORDING TO GOOD COMMON CONSTRUCTION PRACTICES, TO THE LINES, GRADES, ELEVATIONS INDICATED ON THE DRAWINGS AND ACCORDING TO RECOMMENDATIONS FOUND IN

SUB SURFACE REPORT BY GEOTECHNICAL ENGINEER.

2. ALL FILL UNDER SLABS AND FOUNDATIONS SHALL BE COMPACTED TO 98% OF MAXIMUM DENSITY (MODIFIED PROCTOR TEST) AT OPTIMUM MOISTURE CONTENT. A COMPACTION REPORT FROM QUALIFIED

SOILS ENGINEER SHALL BE TAKEN AND SUBMITTED TO ENGINEER OF RECORD.

3. PROVIDE SOIL POISONING TO CONTROL TERMITES AS REQUIRED BY GOVERNING CODES.

4. SAFETY NOTE - CALL 811 BEFORE YOU DIG. PURSUANT TO FLORIDA STATUTES, CHAPTER 556, THE CONTRACTOR SHALL NOTIFY SUNSHINE 811 (DIAL 811) AT LEAST TWO (2) FULL BUSINESS DAYS BEFORE BEGINNING ANY EXCAVATION. THE CONTRACTOR SHALL COORDINATE WITH SUNSHINE 811 FOR UTILITY LOCATES AND SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING UTILITIES. NO EXCAVATION SHALL

BEGIN UNTIL UTILITY MARKINGS ARE COMPLETE.

SUBMITTALS:

1. THE GENERAL CONTRACTOR SHALL SUBMIT FOR ENGINEER REVIEW SHOP DRAWINGS FOR THE

FOLLOWING ITEMS:

1.1. REINFORCING STEEL

1.2. CONCRETE MIX DESIGN

1.3. MASONRY PRODUCTS INCLUDING VERIFICATION OF f'm AND CERTIFICATES FOR ALL OTHER MATERIALS

USED IN MASONRY CONSTRUCTION INDICATING THE COMPLIANCE WITH THE CONTRACT DOCUMENTS.

1.4. EMBEDDED ITEMS (PLATES, ANGLES, BOLTS, ETC.)

1.5. CONCRETE CONSTRUCTION JOINT SEQUENCING AND CURING PLAN FOR ALL CONCRETE ELEMENTS

1.6. CONTROL JOINT LOCATIONS (CMU CONSTRUCTION)

ALL ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SIGNED, SEALED, AND DATED BY A REGISTERED

ENGINEER IN THE STATE OF FLORIDA.

2. ALL SHOP DRAWINGS MUST BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTAL TO THE CITY/ENGINEERING. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED

UNCHECKED.

3. ALL SHOP DRAWINGS SHALL BE SUBMITTED AND APPROVED PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL PLAN AND ALLOW (10) WORKING DAYS FOR APPROVAL FROM BELT ENGINEERING'S OFFICE. THIS

SHALL BE FIGURED INTO THE CONTRACTOR'S SCHEDULE BEFORE CONSTRUCTION BEGINS.

4. THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS UNLESS OTHERWISE SPECIFIED IN

WRITING BY THE ENGINEER.

5. CHANGES AND ADDITIONS MADE ON THE RE-SUBMITTALS SHALL BE CLEARLY FLAGGED AND NOTED. THE

PURPOSE OF RE-SUBMITTALS SHALL BE CLEARLY NOTED ON THE LETTER OF TRANSMITTAL.

ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO THOSE ITEMS CAUSING RE-SUBMITTAL.

6. SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.

SPECIFICATIONS &

DESIGN CRITERIA

ET26-0069_WORKFILE.DWG 21.09.2026

JOSEPH S. GUAGLIARDO P.E. #80504

jguagliardo@beltengineering.com

PH.(813) 961-30751503-A WEST BUSCH BLVD.

TAMPA, FL. 33612

WWW.BELTENGINEERING.COM

FX.(813) 961-1031

CA # 29694

DATE: 9/25/26

SCALE: AS SHOWN

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: JG

DRAWN BY: RRC

CHECKED BY: JG

DATE: 9/25/26

DATE: 9/25/26

DATE: 9/25/26

BY DATER E V I S I O N S

ENGINEER OF RECORD:

SHEET No.

11677

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND

SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1

AUTHENTICATION CODE. PRINTED COPIES OF THIS

DOCUMENT ARE NOT CONSIDERED SIGNED AND

SEALED AND THE SHA-1 AUTHENTICATION CODE MUST

BE VERIFIED ON ANY ELECTRONIC COPIES.

email: jguagliardo@beltengineering.com

PHONE: (813) 961-3075

1503-A WEST BUSCH BLVD.

TAMPA FLORIDA 33612

FAX: (813) 961-1031

CONSULTING ENGINEER

REGISTRATION NUMBER 80504

JOSEPH S. GUAGLIARDO P.E.

I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE

AND BELIEF ALL OF THE STRUCTURAL ELEMENTS

AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN

DESIGNED TO BE IN COMPLIANCE WITH THE

FLORIDA BUILDING CODE 8TH EDITION 2023. ALL

OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES

ARE THE TOTAL RESPONSIBILITY OF OTHERS.

CA # 29694

BELT JOB #ET26-0069

S1

100% DESIGN

Prel im in ary

N ot F or

Const ruct

SCALE:

PLAN VIEW (ADD-ALT. #1)

1/4" = 1'-0"

33'-7"

'-0

17'-0"

'-0

ADD-ALT. #1

SCALE:

PLAN VIEW (BASE BID)

1/4" = 1'-0"

CONDUIT STUB-UP

WINDOW

300 kW

GENERATOR

REFER TO

ELECTRICAL

REMOVABLE

BOLLARD SEE

TYP. DETAILS

6'-8"

'-1

0"

GEN-FRONT

FR

O

N T

4"

ATS

4"-6" ALL

AROUND

2' -8

5'-3"

CONDUIT STUB-UP

WINDOW

300 kW

GENERATOR

REFER TO

ELECTRICAL

REMOVABLE

BOLLARD SEE

TYP. DETAILS

6'-8"

'-1

0"

8'-8"

'-1

0"

GEN-FRONT

FR

O

N T

ATS

4" -6

" A

LL

A R

O U

N D

4"-6" ALL

AROUND

PROVIDE ATS

PLATFORM

PROVIDE GENERATOR

PLATFORM

'-7

17'-0"

17'-0" 33'-7"

'-0

" M

AS

O N

R Y

W

AL

L

AD

D -A

LT

SCALE:

WEST ELEVATION (ADD-ALT. #1)

1/4" = 1'-0"

S2

SCALE:

EAST ELEVATION (ADD-ALT. #1)

1/4" = 1'-0"

S2

SCALE:

NORTH ELEVATION (ADD-ALT. #1)

1/4" = 1'-0"

S2

SCALE:

SOUTH ELEVATION (ADD-ALT. #1)

1/4" = 1'-0"

S2

GEN SET

17'-0"

'-0

5'-0" TYP.

MASONRY WALL ADD-ALT. #1 ATS

MASONRY WALL FROM BEHIND ADD-ALT#1

REMOVABLE BOLLARD. TYP.

MASONRY WALL ADD-ALT. #1 MASONRY WALL ADD-ALT. #1

M

AS

O N

R Y

W

AL

L

AD

D -A

LT

GENERATOR SET PLATFORM 4" HIGH

ATS PLATFORM

4" HIGH

30'-0"

15'-0"

30'-0"

GEN SET

15'-0"

5'-0" TYP.

ATS

REMOVABLE BOLLARD. TYP.

GENERATOR SET PLATFORM 4" HIGH

ATS PLATFORM

4" HIGH

SCALE:

WEST ELEVATION (BASE BID)

1/4" = 1'-0"

S2

SCALE:

EAST ELEVATION (BASE BID)

1/4" = 1'-0"

S2

SCALE:

NORTH ELEVATION (BASE BID)

1/4" = 1'-0"

S2

SCALE:

SOUTH ELEVATION (BASE BID)

1/4" = 1'-0"

S2

ATS

REMOVABLE BOLLARD. TYP.

GENERATOR SET PLATFORM 4" HIGH

ATS PLATFORM

4" HIGH

'-0

5'-0" 5'-0" 5'-0"

5' -0

" T

YP

ATS GEN SET

NON-REMOVABLE BOLLARD

SEE TYP. DETAILS

REMOVABLE

BOLLARD SEE

TYP. DETAILS

REMOVABLE

BOLLARD. TYP.

REMOVABLE

BOLLARD. TYP.

5'-10" 4'

-1

4'-10"

4' -0

5' -0

2"

FLOOR PLAN

AND ELEVATIONS

ET26-0069_WORKFILE.DWG 21.09.2026

JOSEPH S. GUAGLIARDO P.E. #80504

jguagliardo@beltengineering.com

PH.(813) 961-30751503-A WEST BUSCH BLVD.

TAMPA, FL. 33612

WWW.BELTENGINEERING.COM

FX.(813) 961-1031

CA # 29694

DATE: 9/25/26

SCALE: AS SHOWN

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: JG

DRAWN BY: RRC

CHECKED BY: JG

DATE: 9/25/26

DATE: 9/25/26

DATE: 9/25/26

BY DATER E V I S I O N S

ENGINEER OF RECORD:

SHEET No.

11677

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND

SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1

AUTHENTICATION CODE. PRINTED COPIES OF THIS

DOCUMENT ARE NOT CONSIDERED SIGNED AND

SEALED AND THE SHA-1 AUTHENTICATION CODE MUST

BE VERIFIED ON ANY ELECTRONIC COPIES.

email: jguagliardo@beltengineering.com

PHONE: (813) 961-3075

1503-A WEST BUSCH BLVD.

TAMPA FLORIDA 33612

FAX: (813) 961-1031

CONSULTING ENGINEER

REGISTRATION NUMBER 80504

JOSEPH S. GUAGLIARDO P.E.

I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE

AND BELIEF ALL OF THE STRUCTURAL ELEMENTS

AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN

DESIGNED TO BE IN COMPLIANCE WITH THE

FLORIDA BUILDING CODE 8TH EDITION 2023. ALL

OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES

ARE THE TOTAL RESPONSIBILITY OF OTHERS.

CA # 29694

BELT JOB #ET26-0069

S2

100% DESIGN

Prel im in ary

N ot F or

Const ruct

MASONRY WALL SCHEDULE (ADD-ALT. #1)

MARK BLOCK

SIZE

VERTICAL

REINFORCEMENT

HORIZONTAL

REINFORCEMENT

GROUT T.O.W.

BOND BEAM

SLAB TIES NOTES

SIZE SPACING SIZE/TYPE SPACING NUMBER OF

COURSES REINFORCEMENT

NUMBER OF

OCCURENCES

(VERTICALLY)

T.O.B.

MW-1 8" #5's 24" O.C.

11 ga.

LADDER

TYPE

EVERY

OTHER

COURSE

FILLED

CELLS ONLY 10'-0" 1 COURSE #5 x CONT. 1 10'-0" N/A

MASONRY WALL SCHEDULE NOTES:

1. ALL CMU WALLS ARE SHEAR WALLS, U.N.O.

2. SEE DESIGN CRITERIA AND TYPICAL DETAILS FOR PLACEMENT, CONSOLIDATION, CONTROL JOINTS, INSPECTION AND OTHER REQUIREMENTS.

3. PROVIDE FILLED CELLS AS SHOWN ON PLAN VIEWS.

3.1. DIMENSIONS FOR SPACING OF FILLED CELLS IN THE FIELD SHALL BE TAKEN FROM THE BUILDING CORNERS.

3.2. FILLED CELLS REQUIRED AT ALL CORNERS, TRANSITIONS, OPENINGS AND TERMINATIONS.

3.3. ALIGN STEM WALL REINFORCEMENT w/ WALLS ABOVE WHEN PRACTICAL TO DO SO. OFFSET AS REQUIRED AT SLAB TIE IN.

3.4. ALIGN LOWER LEVEL WALL REINFORCEMENT W/ UPPER LEVEL WALL REINFORCEMENT WHEN PRACTICAL DO SO. OFFSET AS REQUIRED AT THE BOND BEAM.

3.5. HORIZONTAL OFFSETS IN BOND BEAMS IS ALLOWED, SEE TYPICAL DETAILS.

4. ALL RETAINING AND STEM WALLS (IF ANY) ARE TO BE FULLY GROUTED.

GENERATOR

SET

SCALE:

(ADD-ALT. #1)

1/4" = 1'-0"

SCALE:

FOUNDATION PLAN (BASE BID)

1/4" = 1'-0"

SCALE:

WALL PLAN (ADD-ALT. #1)

1/4" = 1'-0"

PROVIDE ATS

PLATFORM

PROVIDE GENERATOR

PLATFORM

'-0

5'-0" 5'-0" 5'-0"

5' -0

" T

YP

S3

5' -0

" T

YP

S3

4' -1

5'-10"

8'-8"

'-1

0"

4"

PROVIDE 4" HIGH

ATS PLATFORM

NEW 12" MAT FOUNDATION. W/

#5's AT 8" O.C EA WAY TOP

AND BOTTOM. SEE DETAILS.

ATS

1'-0" MIN

ALL

AROUND

4"-6"

ALL

AROUND

FOUNDATIONPLAN

1/4

C O

N

TI

N U

O U

S

BO

LL

AR

D F

O O

TI

N

G

S3

3" C

O N

C R

ET

E

C O

VE

R

A

LL

AR

O

U N

D

3" CONCRETE

COVER ALL

AROUND

CMU WALL FROM BEHIND

4000 PSI CONCRETE PAD

#5's AT 8" O.C. EA WAY. TOP AND

BOTTOM W/ 9O° BENT EA END.

SCALE:

SECTION (ADD-ALT. #1)

1/2" = 1'-0"

S3

FULLY GROUTED SINGLE

COURSE BOND BEAM WITH

#5's.

#5's x 48D REBAR AT 24" O.C.

#5's MAIN VERTICAL

REINFORCEMENT AT 24" O.C.

11 ga. GALVANIZED LADDER

TYPE HORIZONTAL JOINT

REINFORCEMENT EVERY

OTHER COURSE.

4" 4"

8", NORMAL WEIGHT CMU

UNITS. PROVIDE TYPE "S"

MORTAR

FULLY GROUTED CELL AT EA

REBAR LOCATION SEE PLAN

ATS ANCHORED

TO PLATFORM

BY OTHERS

1' -0

11'-4"

1' -4

2'-0" 2'-0"

1' -4

EXISTING ASPHALT PAVEMENT SAW

CUT AND RESTORE LIKE FOR LIKE

4"

4" HIGH PLATFORM W/ #3's PERIMETER BAR AND 6x6 W1.4/W1.4 W.W.F.; SLOPE

FOR DRAINAGE.

EXISTING ASPHALT PAVEMENT SAW

CUT AND RESTORE LIKE FOR LIKE

SCALE:

SECTION (BASE BID)

1/2" = 1'-0"

S3

1'-0" ALL AROUND

GENERATOR SET SEE

ELECTRICAL

4000 PSI

CONCRETE PAD

#5's AT 8" O.C. EA WAY. TOP AND

BOTTOM W/ 90° BENT EA END.

ATS SEE

ELECTRICAL

4"-6" ALL AROUND

VARIES PER

MANUFACTURER

VARIES PER MANUFACTURER

VA

R

IE

S

PE

R

M

AN

U

FA

C

TU

R

ER

VA

R

IE

S

PE

R

M

AN

U

FA

C

TU

R

ER

NOTE:

1. GENERATOR SET AND ATS DIMENSIONS MAY VARIES PER

MANUFACTURER SPECIFICATIONS.

2. CONTRACTOR MUST COORDINATE THE FINAL EQUIPMENT

SPECS FOR FINAL PADS DIMENSIONS.

1' -0

1'-0"

1' -0

1' -4

3" CONCRETE

COVER ALL

AROUND

1'-0" ALL AROUND

1'-0"

4' -0

TY

P.

4" REMOVABLE BOLLARD

BY OTHERS. INSTALL PER

MANUFACTURER SPEC.

2' -5

3"

4" REMOVABLE BOLLARD BY OTHERS.

INSTALL PER MANUFACTURER SPEC.

EXITING ASPHALT

4000 PSI CONCRETE ENCASEMENT

FOOTING. PROVIDE (4) #5 VERTICAL

BARS WITH (4) #3 CLOSED TIES @ 9"

O.C.

2'-0"Ø

CONCRETE ENCASEMENT

FOOTING. SEE DETAILS

4' -0

TY

P.

SCALE:

TYPICAL DETAIL (BASE BID)

1/2" = 1'-0"

S3

BOLLARD

FOUNDATION DETAIL

#5's AT 8" O.C. EA WAY. TOP AND

BOTTOM W/ 90° BENT EA END.

S3

2' -0

EXISTING ASPHALT PAVEMENT SAW

CUT AND RESTORE LIKE FOR LIKE

SCALE:

SECTION (ADD-ALT. #1)

1/2" = 1'-0"

4' -0

TY

P.

4" REMOVABLE BOLLARD BY OTHERS.

INSTALL PER MANUFACTURER SPEC.

1'-9"

4000 PSI CIP CONTINUOUS BOLLARD FTG. W/

(4) #4's, (6) #3's AT 8" O.C. STIRRUPS.

STRUCTURAL PLAN

VIEW(S)

ET26-0069_WORKFILE.DWG 21.09.2026

JOSEPH S. GUAGLIARDO P.E. #80504

jguagliardo@beltengineering.com

PH.(813) 961-30751503-A WEST BUSCH BLVD.

TAMPA, FL. 33612

WWW.BELTENGINEERING.COM

FX.(813) 961-1031

CA # 29694

DATE: 9/25/26

SCALE: AS SHOWN

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: JG

DRAWN BY: RRC

CHECKED BY: JG

DATE: 9/25/26

DATE: 9/25/26

DATE: 9/25/26

BY DATER E V I S I O N S

ENGINEER OF RECORD:

SHEET No.

11677

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND

SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1

AUTHENTICATION CODE. PRINTED COPIES OF THIS

DOCUMENT ARE NOT CONSIDERED SIGNED AND

SEALED AND THE SHA-1 AUTHENTICATION CODE MUST

BE VERIFIED ON ANY ELECTRONIC COPIES.

email: jguagliardo@beltengineering.com

PHONE: (813) 961-3075

1503-A WEST BUSCH BLVD.

TAMPA FLORIDA 33612

FAX: (813) 961-1031

CONSULTING ENGINEER

REGISTRATION NUMBER 80504

JOSEPH S. GUAGLIARDO P.E.

I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE

AND BELIEF ALL OF THE STRUCTURAL ELEMENTS

AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN

DESIGNED TO BE IN COMPLIANCE WITH THE

FLORIDA BUILDING CODE 8TH EDITION 2023. ALL

OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES

ARE THE TOTAL RESPONSIBILITY OF OTHERS.

CA # 29694

BELT JOB #ET26-0069

S3

100% DESIGN

Prel im in ary

N ot F or

Const ruct

S4

SCALE:

DETAIL (ADD-ALT. #1)

3/4" = 1'-0" SCALE:

DETAIL (ADD-ALT. #1)

3/4" = 1'-0"

S4

ADDED "L" BAR

HOOK BAR END

AS SHOWN

ADDED "L" BAR

CONT. REINFORCEMENT CONT. REINFORCEMENT

TYPICAL ALTERNATE

48 db LAP

LENGTH

d b

LA

P

LE

N G

TH

48 db LAP

LENGTH

CORNER CONTINUITY REINFORCEMENT

TYP. REINFORCED MASONRY

WALL CONTROL JOINT

NOTE:

1) CONTINUE ALL BOND BEAMS AND TIE BEAMS REINFORCEMENT THROUGH THE JOINT.

2) SAW CUT BOND BEAMS AND TIE BEAMS 1" DEEP TO CONTINUE WALL CONTROL JOINT TO

TOP OF WALL.

3) CONTROL JOINT SPACING IS NOT TO EXCEED 25'-0" O.C. IN WALLS WITH MORE THAN 25'-0"

OF UNINTERRUPTED MASONRY.

PREFORMED RUBBER

GASKET

1/2"

REINFORCED MASONRY WALL

(REINFORCING NOT SHOWN)

BACKER ROD & CONSTRUCTION

SEALANT

PREFORMED

RUBBER GASKET

SASH

UNITS

RAKE &

CAULK

1/2" TYP.

STRUCTURAL

DETAILS

ET26-0069_WORKFILE.DWG 21.09.2026

JOSEPH S. GUAGLIARDO P.E. #80504

jguagliardo@beltengineering.com

PH.(813) 961-30751503-A WEST BUSCH BLVD.

TAMPA, FL. 33612

WWW.BELTENGINEERING.COM

FX.(813) 961-1031

CA # 29694

DATE: 9/25/26

SCALE: AS SHOWN

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: JG

DRAWN BY: RRC

CHECKED BY: JG

DATE: 9/25/26

DATE: 9/25/26

DATE: 9/25/26

BY DATER E V I S I O N S

ENGINEER OF RECORD:

SHEET No.

11677

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND

SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1

AUTHENTICATION CODE. PRINTED COPIES OF THIS

DOCUMENT ARE NOT CONSIDERED SIGNED AND

SEALED AND THE SHA-1 AUTHENTICATION CODE MUST

BE VERIFIED ON ANY ELECTRONIC COPIES.

email: jguagliardo@beltengineering.com

PHONE: (813) 961-3075

1503-A WEST BUSCH BLVD.

TAMPA FLORIDA 33612

FAX: (813) 961-1031

CONSULTING ENGINEER

REGISTRATION NUMBER 80504

JOSEPH S. GUAGLIARDO P.E.

I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE

AND BELIEF ALL OF THE STRUCTURAL ELEMENTS

AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN

DESIGNED TO BE IN COMPLIANCE WITH THE

FLORIDA BUILDING CODE 8TH EDITION 2023. ALL

OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES

ARE THE TOTAL RESPONSIBILITY OF OTHERS.

CA # 29694

BELT JOB #ET26-0069

S4

100% DESIGN

Prel im in ary

N ot F or

Const ruct

E1Electrical · Lighting · Mechanical · Renewables 3820 Gunn Hwy., Suite 200 | Tampa, FL, USA 33618 www.hallenggroup.com | Tel: 813.374.2121

FL. C.O.A. #: 27620

HAL L

ENGINEERING GROUP

® DATE:

SCALE: SEE BAR SCALE

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: DS

DRAWN BY: GW

CHECKED BY: KH

DATE:09/25/2026

DATE:

DATE:

BY DATER E V I S I O N S

ENGINEER OF RECORD:

KEITH W. HALL

FL P.E. No. 55024

-H

AL

L

EN

G

IN

EE

R

IN

G

R O

U P, C

R

ET

AI

N

S

IN

TE

LL

EC

TU

AL

A

N D

P H

YS

IC

AL

R

IG

H

TS

T

O T

H

IS

D O

C U

M

EN

T

AN

D

IT

S C

O N

TE

N

T

AN

D P

R O

H

IB

IT

S

IT

S

PU

BL

IS

H

IN

G

D

IS

C

LO

SU

R E

O

EP

R

O D

U C

TI

O

N W

IT

H

O U

T C

O N

SE

N

T.

TH

IS

D O

C U

M

EN

T

IS

V

AL

ID

F

O R

M O

N

TH

S

FR

O M

D

AT

E O

F

EN

G

IN

EE

R

'S S

IG

N

AT

U

R E

AN

D

S

EA

L.

SHEET No.

KEITH W. HALL, P.E.; FL. REG. #: 55024

09/25/2026 09/25/2026

09/25/2026

11677

ELECTRICAL LEGEND & SITE PLAN

Z

P ro je ct s\

D

C oS

P Fl ee t

M an ag em en t

N ew

G en er at or D es ig n\ D ra w in gs

\E le ct ri ca l\ S he et S et \2

7D

_E

El ec tr ic al S pe ci fic at io ns

L eg en d.

dw g

S ep

.2 5.

9:

am

300 kW

GENERATOR

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS

300 kW

GENERATOR

300 kW

GENERATOR

E2Electrical · Lighting · Mechanical · Renewables 3820 Gunn Hwy., Suite 200 | Tampa, FL, USA 33618 www.hallenggroup.com | Tel: 813.374.2121

FL. C.O.A. #: 27620

HAL L

ENGINEERING GROUP

® DATE:

SCALE: SEE BAR SCALE

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: DS

DRAWN BY: GW

CHECKED BY: KH

DATE:09/25/2026

DATE:

DATE:

BY DATER E V I S I O N S

ENGINEER OF RECORD:

KEITH W. HALL

FL P.E. No. 55024

-H

AL

L

EN

G

IN

EE

R

O

R

ET

AI

N

S

IN

TE

LL

EC

TU

AL

A

N D

P H

YS

IC

AL

R

IG

H

TS

T

O T

H

IS

D O

C U

M

EN

T

AN

D

IT

S C

O N

TE

N

T

AN

D P

R O

H

IB

IT

S

IT

S

PU

BL

IS

H

IN

G

D

IS

C

LO

SU

R E

R

O D

U C

TI

O

N W

IT

H

O U

T C

O N

SE

N

T.

TH

IS

D O

C U

M

EN

T

IS

V

AL

ID

F

O R

M O

N

TH

S

FR

O M

D

AT

E O

F

EN

G

IN

EE

R

'S S

IG

N

AT

U

R E

AN

D

S

EA

L.

SHEET No.

KEITH W. HALL, P.E.; FL. REG. #: 55024

09/25/2026 09/25/2026

09/25/2026

11677

ELECTRICAL PLAN

Z

P ro je ct s\

D

C oS

P Fl ee t

M an ag em en t

N ew

G en er at or D es ig n\ D ra w in gs

\E le ct ri ca l\ S he et S et \2

7D

_E

El ec tr ic al P la n.

.2

5.

E3Electrical · Lighting · Mechanical · Renewables www.hallenggroup.com | Tel: 813.374.2121

FL. C.O.A. #: 27620

HAL L

ENGINEERING GROUP

® DATE:

SCALE: SEE BAR SCALE

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: DS

DRAWN BY: GW

CHECKED BY: KH

DATE:09/25/2026

DATE:

DATE:

BY DATER E V I S I O N S

ENGINEER OF RECORD:

KEITH W. HALL

FL P.E. No. 55024

-H

AL

L

EN

G

IN

EE

R

O

R

ET

AI

N

S

IN

TE

LL

EC

TU

AL

A

N D

P H

YS

IC

AL

R

IG

H

TS

T

O T

H

IS

D O

C U

M

EN

T

AN

D

IT

S C

O N

TE

N

T

AN

D P

R O

H

IB

IT

S

IT

S

PU

BL

IS

H

IN

G

D

IS

C

LO

SU

R E

R

O D

U C

TI

O

N W

IT

H

O U

T C

O N

SE

N

T.

TH

IS

D O

C U

M

EN

T

IS

V

AL

ID

F

O R

M O

N

TH

S

FR

O M

D

AT

E O

F

EN

G

IN

EE

R

'S S

IG

N

AT

U

R E

AN

D

S

EA

L.

SHEET No.

KEITH W. HALL, P.E.; FL. REG. #: 55024

09/25/2026 09/25/2026

09/25/2026

11677

POWER ONE-LINE DIAGRAM

& LOAD SUMMARY

Z

P ro je ct s\

D

C oS

P Fl ee t

M an ag em en t

N ew

G en er at or D es ig n\ D ra w in gs

\E le ct ri ca l\ S he et S et \2

7D

_E

Po w er O ne -L in e

D ia gr am

L oa d

S um m ar y.

.2 5.

E4Electrical · Lighting · Mechanical · Renewables www.hallenggroup.com | Tel: 813.374.2121

FL. C.O.A. #: 27620

HAL L

ENGINEERING GROUP

® DATE:

SCALE: SEE BAR SCALE

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: DS

DRAWN BY: GW

CHECKED BY: KH

DATE:09/25/2026

DATE:

DATE:

BY DATER E V I S I O N S

ENGINEER OF RECORD:

KEITH W. HALL

FL P.E. No. 55024

-H

AL

L

EN

G

IN

EE

R

O

R

ET

AI

N

S

IN

TE

LL

EC

TU

AL

A

N D

P H

YS

IC

AL

R

IG

H

TS

T

O T

H

IS

D O

C U

M

EN

T

AN

D

IT

S C

O N

TE

N

T

AN

D P

R O

H

IB

IT

S

IT

S

PU

BL

IS

H

IN

G

D

IS

C

LO

SU

R E

R

O D

U C

TI

O

N W

IT

H

O U

T C

O N

SE

N

T.

TH

IS

D O

C U

M

EN

T

IS

V

AL

ID

F

O R

M O

N

TH

S

FR

O M

D

AT

E O

F

EN

G

IN

EE

R

'S S

IG

N

AT

U

R E

AN

D

S

EA

L.

SHEET No.

KEITH W. HALL, P.E.; FL. REG. #: 55024

09/25/2026 09/25/2026

09/25/2026

11677

ELECTRICAL DETAILS

Z

P ro je ct s\

D

C oS

P Fl ee t

M an ag em en t

N ew

G en er at or D es ig n\ D ra w in gs

\E le ct ri ca l\ S he et S et \2

7D

_E

D et ai ls

.d w

.2 5.

Electrical · Lighting · Mechanical · Renewables www.hallenggroup.com | Tel: 813.374.2121

FL. C.O.A. #: 27620

HAL L

ENGINEERING GROUP

® DATE:

SCALE: SEE BAR SCALE

DRAWING No.

ENGINEERING & CAPITAL

IMPROVEMENTS DEPARTMENT

CITY OF ST. PETERSBURG

ST. PETERSBURG FLEET MANAGEMENT

NEW GENERATOR DESIGN

PROJECT No. 25143-130

DESIGNED BY: DS

DRAWN BY: GW

CHECKED BY: KH

DATE:09/25/2026

DATE:

DATE:

BY DATER E V I S I O N S

ENGINEER OF RECORD:

KEITH W. HALL

FL P.E. No. 55024

-H

AL

L

EN

G

IN

EE

R

O

R

ET

AI

N

S

IN

TE

LL

EC

TU

AL

A

N D

P H

YS

IC

AL

R

IG

H

TS

T

O T

H

IS

D O

C U

M

EN

T

AN

D

IT

S C

O N

TE

N

T

AN

D P

R O

H

IB

IT

S

IT

S

PU

BL

IS

H

IN

G

D

IS

C

LO

SU

R E

R

O D

U C

TI

O

N W

IT

H

O U

T C

O N

SE

N

T.

TH

IS

D O

C U

M

EN

T

IS

V

AL

ID

F

O R

M O

N

TH

S

FR

O M

D

AT

E O

F

EN

G

IN

EE

R

'S S

IG

N

AT

U

R E

AN

D

S

EA

L.

SHEET No.

KEITH W. HALL, P.E.; FL. REG. #: 55024

09/25/2026 09/25/2026

09/25/2026

11677 E5

LIGHTNING PROTECTION NOTES

& DETAILS

Z

P ro je ct s\

D

C oS

P Fl ee t

M an ag em en t

N ew

G en er at or D es ig n\ D ra w in gs

\E le ct ri ca l\ S he et S et \2

7D

_E

Li gh tn in g Pr ot ec tio n

N ot es

D et ai ls

.d w

.2 5.

2507D_Sheet Set
2507D_G0 Cover Sheet & Index
2507D_E1 Electrical Legend & Site Plan
2507D_E2 Electrical Plan
2507D_E3 Power One-Line Diagram & Load Summary
2507D_Conduit Trench Detail
2507D_26 41 13.25 Ground Well Detail
2507D_E4 Electrical Details
2507D_E5 Lightning Protection Notes & Details
26 41 13.24 Air Term Roof Top Equipment Detail

2026.09.23_ET26-0069_GENERATOR PAD 100% SUBMITTAL