Bid_Plans.pdf
PDF 8 MB Posted
- Solicitation number
- IFB- 26 - 347
- Issued by
- Pinellas County, Florida
About this file
This is a 100% design plan document prepared by Hall Engineering Group and Belt Engineering for the City of St. Petersburg, Florida's Fleet Management Emergency Generator project (Project No. 25143-130). The project involves the installation of a new 300 kilowatt emergency backup generator at the Fleet Management Complex located at 701 19th Street North, St. Petersburg, Florida, on an 8.05-acre parcel. The design includes a base bid configuration and an Alternate 1 option featuring a concrete masonry wall enclosure with access gates and lightning protection. The generator is designed to provide full backup power for up to 48 hours during utility outages to support half of the complex buildings. The site plan identifies existing utilities, drainage requirements, tree protection measures, and construction staging areas. All construction is designed in compliance with the Florida Building Code 8th Edition 2023, with structural design based on ASCE 7-22 wind loads of 146 miles per hour ultimate and a Risk Category II exposure category for the enclosed structure.
The design specifications establish a 4,000 psi concrete compressive strength for mat foundation construction with an allowable soil bearing capacity of 2,000 pounds per square foot. The site is located in Flood Zone X per the Federal Insurance Rate Map. Contractor responsibilities are explicitly detailed, including verification of all details and dimensions with existing conditions, submission of shop drawings for engineer review, and compliance with construction sequencing and curing plans. The document was approved for bid on September 25, 2026, by Brejesh Prayman, P.E., Director of Engineering & Capital Improvements Department, with engineering prepared by Joseph S. Guagliardo, P.E., Consulting Engineer Registration Number 80504.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ST PETERSBURG, FL
7th Ave. N
DRAWING INDEX
DESCRIPTIONSheet No.
11677-01
11677-02
11677-03
APPROVED FOR BID
BREJESH PRAYMAN, P.E. DATE
DIRECTOR OF ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
DATE: 09/25/2026
DRAWING No.: 11677
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
100% DESIGN
PROJECT NO. 25143-130
ECID DM
CLIENT DEPT
ECID PM
REVIEWER INITIALS
QA/QC APPROVAL
PLANS PREPARED BY:
KEITH W. HALL, P.E.
FL. REG. #: 55024
HALL ENGINEERING GROUP
3820 GUNN HWY., SUITE 200
TAMPA, FL, USA 33618
Drawing No.
G0
C1
S1
G0Sheet No.:
COVER SHEET & INDEX
SITE PLAN
SPECIFICATIONS & DESIGN CRITERIA
11677-04 S2 FLOOR PLAN AND ELEVATIONS
11677-05 S3 STRUCTURAL PLAN VIEW(S)
11677-06 S4 STRUCTURAL DETAILS
11677-08
11677-09
E1
E2
ELECTRICAL SPECIFICATIONS & LEGEND
ELECTRICAL PLAN
11677-10 E3 POWER ONE-LINE DIAGRAM & LOAD SUMMARY
11677-11 E4 ELECTRICAL DETAILS
11677-12 E5 LIGHTNING PROTECTION NOTES AND DETAILS
701 19TH ST. NORTH
ST. PETERSBURG, FL 33713
10/02/26
SCALE:
SITE PLAN
1/8"=1'-0"
PROTECTIVE BARRICADES SHALL BE PLACED AROUND ALL
PROTECTED TREES AND GRAND TREES DURING SITE CLEARING TO
CREATE A PROTECTIVE ROOT ZONE AND SHALL REMAIN IN PLACE
UNTIL LAND ALTERATION, SITE CLEARING AND CONSTRUCTION
ACTIVITIES ARE COMPLETE. BARRICADES FOR THE PROTECTIVE
ROOT ZONE SHALL BE ERECTED AT A MINIMUM DISTANCE OF: TREES
MEASURING 32" OR GREATER REQUIRE 20' OF PROTECTION, TREES
MEASURING 24-31" REQUIRE 15' OF PROTECTION, PROTECTED TREES
MEASURING 5-23" REQUIRE 10' OF PROTECTION AND PALMS ONLY 3'.
FOUR CORNER UPRIGHT STAKES OF NO LESS THAN 2" X 2" LUMBER
CONNECTED BY HORIZONTAL MEMBERS OF NO LESS THAN 1" X 4"
LUMBER; OR UPRIGHT STAKES SPACED AT 5' INTERVALS OF NO LESS
2" X 2" LUMBER CONNECTED BY SILT SCREEN FABRIC OR MATERIAL
OF COMPARABLE DURABILITY.
BARRIER SPECIFICATIONS FOR TREES
(MIN) SEE ABOVE
SITE ADDRESS: 7TH AVE. N.
ST. PETERSBURG, FL
PARCEL NUMBER: 13-31-16-00000-340-0300
FLOOD ZONE: "X" PER FIRM MAP 12103C0218G
LEGAL DESCRIPTION
FROM NW COR OF SE 1/4 OF SW 1/4 RUN S 430FT FOR POB TH E 419FT
(S) TH SE'LY ALONG W R/W OF RR 683FT (S) TH W 663FT (S) TH N 125FT
TH W 59.2FT TH N 205.2FT TH E 30FT TH N 290 FT (S)TO POB CONT 8.05
AC(C)
SITE DATA:
R401.3DRAINAGE.
SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10
FEET (3048 MM).
SITE NOTES:
TREE BARRICADE:
GENERAL NOTE
A. THIS SHEET IS FOR INFORMATIONAL PURPOSES ONLY,
COORDINATE WITH CITY PRIOR TO BIDDING AND CONSTRUCTION FOR
ALL CIVIL, DRAINAGE, SURVEY, UTILITIES, COORDINATES, EROSION
CONTROL, PARKING, TRAFFIC REQUIREMENTS, ETC. FIELD
DOCUMENT AS-BUILTS.
B. EXISTING INFORMATION INCLUDING UNDERGROUND SURVEY
INFORMATION WAS PROVIDED BY THE CITY. COORDINATE ALL
LOCATIONS, DIMENSIONS, AND UNDERGROUND OBSTRUCTIONS WITH
THE CITY PRIOR TO COMMENCING WORK AND AS-NEEDED.
GENERAL NOTES:
PARKING/ STAGING/ LIMITS
OF CONSTRUCTION
SCALE:
STAGING AREA
NOT TO SCALE
SCALE:
LOCATION MAP
NOT TO SCALE
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U E
U K
U K
U K
U K
U K
U K
U K
U K
U K
U E
UE UE UE UE UE UE UE UE UE UE UE UE UE UE UE UE
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
UK
UK
UK
UK
UK
UK
UK
UK
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
5' MINIMUM OFFSET
FROM PROPERTY
LINE (BID-ALT #1)
5' MINIMUM OFFSET
FROM PROPERTY LINE
(BASE BID)
EXIST. SAN.
SYSTEM (TYP)
EXIST. GAS SYSTEM
4" REMOVABLE BOLLARD (TYP)
COORDINATE FINAL QTY. AND
LOCATIONS W/ SELECTED BASE
BID OR ADD-ALT#1
EXIST. UTILITY POLE
EXIST. UNDERGROUND
WATER LINE (TYP)
EXIST. UNDERGROUND
GAS LINE (TYP)
FLEET MANAGEMENT
EXTERIOR WALL
EXIST. UTILITY
POLE GUY WIRES
EXIST. UNDERGROUND
ELECTRIC LINE (TYP)
EXIST. UNDERGROUND
SANITARY SEWER (TYP)
EXIST. UNKNOWN UNDERGROUND
UTILITY LINE (TYP)
CONFIRM EXACT NORTH
LOCATION/ALIGNMENT WITH
CITY.
EXIST. UTILITY POLE
MAINTAIN RELATIVE DISTANCE
BETWEEN GENERATOR AND ATS FOR
BOTH BASE BID AND ADD-ALT#1
ADD-ALT. #1
300 kW
GENERATOR
6'-8"
'-1 0"
GEN-FRONT
FR
O
N T
4"
ATS2'
-8
5'-3"
'-7
17'-0"
17'-0"
5'-10"
4' -1
4'-10"
4' -0
5'
-0
REMOVABLE BOLLARD BASE BID ONLY.
REMOVABLE BOLLARD
BASE BID ONLY.
REFER TO SUE FIELD REPORT (APRIL
2, 2026) FOR INFORMATION ON
CAPPED UTILITY. COORDINATE THE
CUT AND CAP (AS REQUIRED) OF
ABANDONED LINE FURTHER NORTH,
OUTSIDE THE FOOTPRINT OF
GENERATOR.
SITE PLAN
ET26-0069_WORKFILE.DWG 21.09.2026
JOSEPH S. GUAGLIARDO P.E. #80504
jguagliardo@beltengineering.com
PH.(813) 961-30751503-A WEST BUSCH BLVD.
TAMPA, FL. 33612
WWW.BELTENGINEERING.COM
FX.(813) 961-1031
CA # 29694
DATE: 9/25/26
SCALE: AS SHOWN
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: JG
DRAWN BY: RRC
CHECKED BY: JG
DATE: 9/25/26
DATE: 9/25/26
DATE: 9/25/26
BY DATER E V I S I O N S
ENGINEER OF RECORD:
SHEET No.
11677
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1
AUTHENTICATION CODE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
BE VERIFIED ON ANY ELECTRONIC COPIES.
email: jguagliardo@beltengineering.com
PHONE: (813) 961-3075
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
FAX: (813) 961-1031
CONSULTING ENGINEER
REGISTRATION NUMBER 80504
JOSEPH S. GUAGLIARDO P.E.
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE STRUCTURAL ELEMENTS
AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN
DESIGNED TO BE IN COMPLIANCE WITH THE
FLORIDA BUILDING CODE 8TH EDITION 2023. ALL
OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES
ARE THE TOTAL RESPONSIBILITY OF OTHERS.
CA # 29694
BELT JOB #ET26-0069
C1
100% DESIGN
PARKING/STAGING/ LIMIT
OF CONSTRUCTION
GENERATOR
GENERATOR
Prel im in ary
N ot F or
Const ruct io n
STRUCTURAL SPECIFICATIONS
DESIGN CRITERIA
BASIS OF DESIGN:
ALL CONSTRUCTION IS DESIGNED AS FOLLOWS:
FLORIDA BUILDING CODE 8TH EDITION 2023 AS FOLLOWED BELOW:
FBC, BUILDING-2023
FBC, EXISTING BUILDING-2023
FBC, RESIDENTIAL-2023
DEAD LOADS
GENERATOR SET 210 PSF
LIVE LOADS
FLOOR 40 PSF
ROOF N/A PSF
PARTITIONS N/A PSF
RAIN LOADS
RAIN LOAD 20 PSF
RAIN INTENSITY 4.04 IN/HR
FLOOD ZONE
FLOOD ZONE X
WIND LOADS
ASCE 7-22, 146 MPH WIND (ULTIMATE), 113 MPH (NOMINAL)
N/A MPH TORNADO (ULTIMATE), N/A MPH TORNADO (NOMINAL)
BUILDINGS OF ALL HEIGHTS ANALYTICAL METHOD
RISK CATEGORY II
EXPOSURE CATEGORY "C"
ROOF SLOPE: N/A
INTERNAL PRESSURE COEFFICIENTS:
GCpi = +/- .18, ENCLOSED STRUCTURE BASIC WIND PRESSURE: q= xx.x P.S.F. (C&C) EDGE DISTANCE: a= x FT.
CONTRACTOR RESPONSIBILITIES:
1. THE FOLLOWING SPECIFICATIONS ARE AN OUTLINE OF MINIMUM MATERIAL REQUIREMENTS AND THEIR APPLICATION. MANUFACTURER SPECIFICATION AND LOCAL CODE REQUIREMENTS, WHEN IN EXCESS OF MINIMUM SPECIFICATION SHALL CONTROL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW AND
SUBMIT ALL SHOP DRAWINGS AND REPORT ALL DOCUMENT DISCREPANCIES TO THE STRUCTURAL
ENGINEER PRIOR TO FABRICATION OR ERECTION.
2. AT CONSTRUCTION ISSUE, THESE DRAWINGS REPRESENT STRUCTURAL COMPONENTS IN THEIR FINAL AND
FINISHED STATE. CONSTRUCTION PROCEDURES, BRACING, METHODS SAFETY PRECAUTIONS OR
MECHANICAL REQUIREMENTS USED TO ERECT THEM ARE THE SOLE RESPONSIBILITY OF THE GENERAL
CONTRACTOR OR SUBCONTRACTOR DOING THE WORK.
3. CONTRACTOR SHALL VERIFY ALL DETAILS AND DIMENSIONS WITH EXISTING CONDITIONS, CITY
DOCUMENTS AND PROPERLY COORDINATED, APPROVED SHOP DRAWINGS.
4. NO COMMENT, NOTE OR DETAIL IN THESE STRUCTURAL DOCUMENTS SHOULD BE MISCONSTRUED AS A DESIGN FOR WATERPROOFING OR DAMPPROOFING. SPECIFIC DESIGN FOR MOISTURE CONTROL AND PERMANENT PROTECTION OF STRUCTURAL MATERIALS FROM THE ELEMENTS IS TO BE COMPLETED BY
THE CONTRACTOR AND COORDINATED WITH THE STRUCTURAL DOCUMENTS.
5. CONTRACTOR SHALL OBTAIN LATEST SET OF DRAWINGS INCLUDING ANY REVISIONS BEFORE STARTING
CONSTRUCTION.
6. IT IS ASSUMED THAT THE CONTRACTOR HAS READ AND UNDERSTANDS THE NOTES, SPECIFICATIONS AND
DESIGN INTENT CONTAINED HEREIN.
7. THE CONTRACTOR SHALL REVIEW DRAWINGS IN THEIR ENTIRETY BEFORE STARTING WORK.
8. THE CONTRACTOR SHALL ACCEPT FULL RESPONSIBILITY FOR ANY ERRORS OR OMISSIONS NOT REPORTED
IMMEDIATELY IN WRITING TO THE ENGINEER OF RECORD.
9. CONTRACTORS WHO DISCOVER DISCREPANCIES, OMISSIONS OR VARIATIONS IN THE CONTRACT DOCUMENTS DURING BIDDING SHALL IMMEDIATELY NOTIFY THE S.E.O.R.. THE S.E.O.R. WILL RESOLVE THE
CONDITION AND ISSUE A WRITTEN CLARIFICATION.
10. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER OF RECORD
IN WRITING PRIOR TO PROCEEDING WITH THE AFFECTED PART OF THE WORK.
11. THE GENERAL CONTRACTOR SHALL COORDINATE ALL CONTRACT DOCUMENTS WITH FIELD
CONDITIONS/DIMENSIONS AND PROJECT SHOP DRAWINGS PRIOR TO CONSTRUCTION.
12. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS, AND JOBSITE
SAFETY INCLUDING ALL OSHA REQUIREMENTS.
13. THE CONTRACTOR SHALL PROTECT ADJACENT PROPERTY, HIS OWN WORK AND THE PUBLIC FROM HARM.
14. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS OR TIEDOWNS. WHEREVER THE CONTRACTOR IS UNSURE OF THESE REQUIREMENTS, THE CONTRACTOR SHALL RETAIN A QUALIFIED STATE LICENSED PROFESSIONAL ENGINEER TO DESIGN AND INSPECT THE TEMPORARY BRACING AND
STABILITY OF THE STRUCTURE.
15. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE STRUCTURE IS COMPLETE. PRIOR TO COMPLETION, THE RESPONSIBILITY FOR STABILITY AND TEMPORARY BRACING IS THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM
REQUIRED FOUNDATION AND SITE PREPARATION REQUIREMENTS, (INCLUDING SLAB ON GRADE
THICKNESS), TO HANDLE CONSTRUCTION LOADS.
16. THE GENERAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION AND SHORING PROCEDURES AND PROTECTION OF ADJACENT PROPERTY, STREETS AND UTILITIES IN ACCORDANCE WITH
LOCAL BUILDING DEPARTMENT.
17. WHEN PERFORMING WORK BELOW GRADE, CARE SHALL BE TAKEN TO AVOID DAMAGING ANY EXISTING
UTILITIES.
18. ALL UNKNOWN UTILITIES DISCOVERED DURING CONSTRUCTION SHALL BE BROUGHT TO THE ATTENTION OF THE CITY. ANY DAMAGE TO THE EXISTING UTILITIES SHALL BE IMMEDIATELY REPORTED TO ALL AFFECTED
PARTIES INCLUDING THE CITY.
FOUNDATION/SLAB-ON-GRADE:
1. CONCRETE COMPRESSIVE STRENGTH SHALL CONFORM TO THE FOLLOWING:
MAT FOUNDATION f'c = 4,000 psi
2. FOUNDATIONS AND SLAB ON GRADE SHALL COMPLY WITH "CONCRETE NOTES AND SPECIFICATION"
SECTION.
3. FOUNDATION IS TO BE A SHALLOW FOUNDATION SYSTEM.
3.1. FOOTINGS HAVE BEEN DESIGNED WITH THE ALLOWABLE SOIL BEARING OF "2,000 PSF"
4. TOPSOIL, VEGETATION, DEBRIS AND SURFACE SOILS CONTAINING ORGANIC MATERIALS SHALL BE REMOVED FROM THE BUILDING FOOTPRINT. THE BUILDING FOOTPRINT IS ASSUMED TO EXTEND AT
MINIMUM 5' BEYOND THE EXTENTS OF EVERY EXTERIOR BUILDING ELEMENT.
5. FOOTINGS SHALL BE PLACED IMMEDIATELY UPON EXCAVATION.
6. ALL EXTERIOR FOOTINGS SHALL BE EMBEDDED AT MINIMUM 12" BELOW LOWEST ADJACENT GRADE.
7. SEE CONCRETE SPECIFICATIONS FOR ALL CONCRETE COVER REQUIREMENTS.
8. ALL REINFORCEMENT MARKED AS CONTINUOUS SHALL BE LAPPED IN ACCORDANCE WITH "REINFORCING STEEL SPLICE NOTES".THERE SHALL BE NO PLUMBING LINES RUNNING PARALLEL TO, WITHIN OR UNDER
ANY FOUNDATION BEAM.
9. SLAB-ON-GRADE SHALL COMPLY WITH ACI 302 "GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION"
ACI 302.
10. ALL SLAB-ON-GRADE SHALL BE PLACED OVER 10 MIL (MINIMUM) POLYETHYLENE FILM VAPOR BARRIER.
11. MINIMUM ALLOWABLE THICKNESS FOR SLAB-ON-GRADE IS 4".
12. SLAB-ON-GRADE THAT IS ADJACENT TO AN EXISTING HARD SURFACE SHALL HAVE A BOND BREAKING
EXPANSION OR PRE-MOLDED JOINT BETWEEN THE TWO MATERIALS.
13. CONTRACTOR TO SUBMIT TO EOR IN WRITING A SLAB SEQUENCING AND CURING PLAN WHICH ALSO INDICATES ALL PLANNED CONTROL JOINTS. ANY REFERENCE TO CONTROL JOINT LAYOUT IN THIS PLAN SET SHALL BE CONSIDERED SCHEMATIC IN NATURE AND IS INTENDED ONLY TO REFERENCE THE
REQUIREMENTS OF THE CONTRACTOR.
13.1. NO CONTROL JOIN SHALL INTERSECT AN ADJACENT CONTROL JOINT AT AN ANGLE <90°.
13.2. CONTROL JOINTS SHALL ONLY INTERSECT A CURB OR OTHER STRUCTURAL MEMBER AT ANGLE OF 90°.
13.3. PREFERRED ASPECT RATIO FOR CONTROL JOINT SPACING IS 1:1 TO 1.5:1. AT NO TIME SHALL THE
CONTROL JOINT SPACING ASPECT RATIO EXCEED 2:1.
14. SLAB-ON-GRADE SHALL BE REINFORCED SUFFICIENTLY WITH WELDED WIRE REINFORCEMENT (W.W.R.), SEE TABLE, OR FIBER MESH PER MANUFACTURER'S REQUIREMENTS. CONTRACTOR TO SUBMIT USE OF FIBER MESH TO EOR AS AN ALTERNATE DESIGN AND PROVIDE QUANTITY, IN LBS/YD, TO BE USED. NO LESS
THAN 1.5 LBS/YD OF FIBER SHALL BE USED IN SLAB-ON-GRADE APPLICATIONS.
15. BACKFILLING OPERATIONS AGAINST FOUNDATION STEM WALLS SHALL BE COMPLETED WITH CARE USING SMALL, WALK BEHIND, VIBRATORY EQUIPMENT. NO TRUCKS OR OTHER HEAVY MACHINERY SHALL BE
ALLOWED WITHIN 6' OF ANY FOUNDATION STEM WALLS.
16. FOUNDATION WALLS THAT EXCEED 2'-8" IN HEIGHT SHALL BE BRACED AT THE TOP OF WALL PRIOR TO COMMENCING WITH ANY BACKFILLING OR COMPACTION ACTIVITIES. SUBMIT BRACE PLAN TO EOR FOR
APPROVAL.
15. AN INDEPENDENT CERTIFIED TESTING LAB SHALL VERIFY AND PROVIDE REPORTS CERTIFYING THE
FOLLOWING:
15.1. SOIL DENSITY TESTING
MASONRY (CMU):
1. CMU SHALL CONFORM TO THE FOLLOWING:
REINFORCED MASONRY f'm = 1,500 psi (ASTM C90) MASONRY GROUT f'c = 3,000 psi (ASTM 476)
MORTAR TYPE "S" OR "M"
2. THE DESIGN AND CONSTRUCTION MUST CONFORM TO BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES ACI530/ASCE 5, AND THE SPECIFICATIONS FOR MASONRY STRUCTURES ACI 530.1/ASCE 6, CURRENT CODE EDITIONS.
3. VERIFY ALL DETAILS AND DIMENSIONS WITH EXISTING CONDITIONS, ARCHITECTURAL DOCUMENTS AND
PROPERLY COORDINATED APPROVED SHOP DRAWINGS.
4. EXPANSION AND CONTROL JOINTS ARE TO BE PLACED PER A.C.I. RECOMMENDATIONS. PREPARE A CRACK
CONTROL PLAN BASED ON CONSTRUCTION SEQUENCING AND PROPOSED ACTUAL FLOOR AND WALL
FINISHES, AND SUBMIT TO THE ARCHITECT/ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION.
5. THE MASONRY CONTRACTOR MUST EMPLOY A CERTIFIED STRUCTURAL MASONRY INSPECTOR. THE INSPECTOR MUST BE IN ATTENDANCE AND MONITOR ALL REINFORCED MASONRY OPERATIONS INCLUDING
DOWEL PLACEMENT. PROVIDE DAILY REPORTS TO THE ENGINEER OF RECORD.
6. PROVIDE 48 BAR DIAMETER MINIMUM LAP FOR ALL SPLICES, U.N.O.
7. PROVIDE CONTINUOUS TRUSS TYPE OR LADDER TYPE #9 GAUGE GALVANIZED HORIZONTAL JOINT
REINFORCEMENT AT 16" O.C. WITH 8" MINIMUM LAP.
8. ALL CMU TEMPORARILY OR PERMANENTLY RESISTING SOIL SHALL BE FULLY GROUT FILLED.
9. ALL KNOCK OUT BLOCK HORIZONTAL BARS MUST HAVE CORNER CONTINUITY BARS AT ALL CORNERS AND
WALL INTERSECTIONS. SIZE AND NUMBER CORNER BARS MUST BE SAME AS HORIZONTAL BARS.
10. ALL INTERSECTING WALLS AND CORNER WALLS MUST BE LAID IN AN OVERLAPPING MASONRY BONDING
PATTERN.
11. PROVIDE REINFORCED FILLED CELL AT EVERY CORNER, JAMB, INTERSECTION, TERMINATION, TRANSITION
AND AT EACH SIDE OF CONTROL JOINT/EXPANSION JOINT.
12. ALL CONTINUOUS HORIZONTAL BARS SHALL BE LAPPED WITH AN ADDITIONAL CORNER BAR THAT MATCHES
IN SIZE AND QUANTITY IN EACH DIRECTION.
13. NO WATER SHALL BE ADDED TO THE GROUT AT THE JOBSITE. IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO COORDINATE WITH THE SUPPLIER TO ENSURE A PUMPABLE AND WORKABLE MIX
WITHOUT THE ADDITION OF WATER AT THE JOBSITE. THE USE OF PLASTICIZERS, RETARDANTS AND OTHER ADDITIVES SHALL BE AT THE OPTION OF THE CONTRACTOR SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER. FOLLOW THE RECOMMENDATIONS OF THE MANUFACTURER FOR THE PROPER USE OF ADDITIVES. THE USE OF CALCIUM CHLORIDE OR OTHER CHLORIDE BEARING SALTS SHALL NOT BE
PERMITTED.
14. GROUT SLUMP TESTS SHALL BE MADE BEFORE AND AFTER THE ADDITION OF ADMIXTURES AND MAY BE TAKEN AT THE BACK OF THE TRUCK. GROUT FOR THE PREPARATION OF TEST CYLINDERS SHALL BE TAKEN FROM THE HOSE END FOR GROUT PLACED BY PUMP. GROUT WITH A SLUMP BETWEEN 8 TO 11 INCHES
SHALL BE PROVIDED.
STRUCTURAL STEEL:
1. ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM SPECIFICATIONS, UNLESS NOTES
OTHERWISE ON PLAN:
ROLLED W SHAPES ASTM A992, GRADE 50
ROLLED C & MC SHAPES ASTM A36
ANGLES ASTM A36
ROUND HSS ASTM A500, GR B (Fy=42 KSI) RECTANGULAR HSS ASTM A500, GR B (Fy=46 KSI) PIPE ASTM A53, GR B (Fy=35 KSI)
PLATES ASTM A36
STEEL CONNECTION BOLTS A325
2. ALL SHOP AND FIELD WELDING SHALL CONFORM TO AWS STRUCTURAL WELDING CODE, ANSI/AWS D1.1, AND ALL WELDS SHALL BE PERFORMED USING E70XX U.N.O.
3. DESIGN CONNECTIONS FOR ALL BEAMS TO SUPPORT HALF OF THE UNIFORM CAPACITY SHOWN IN AISC "TABLES FOR ALLOWABLE LOADS ON BEAMS" FOR THE GIVEN SECTION AND SPAN UNLESS OTHERWISE
SHOWN ON PLANS.
4. GROUT BELOW BASE PLATES SHALL BE NON-SHRINK, NON-METALLIC GROUT WITH A MINIMUM
COMPRESSIVE STRENGTH OF 6000 PSI.
5. HOT-DIP GALVANIZE ALL STRUCTURAL STEEL ITEMS AND THEIR CONNECTIONS PERMANENTLY EXPOSED TO WEATHER AFTER FABRICATION. ALL FIELD AND ERECTION MARKS SHALL BE COVERED DURING FIELD
TOUCH-UP PAINTING.
6. CUTS, HOLES, COPING, AND ALL OTHER MODIFICATIONS REQUIRED TO BE MADE FOR THE WORK OF OTHER TRADES SHALL BE SHOWN IN THE STRUCTURAL STEEL SHOP DRAWINGS, AND SHALL BE PERFORMED ONLY BY THE SHOP ISSUING SAID DRAWINGS, OR OTHER FACILITY APPROVED BY THE ENGINEER TO PERFORM SAID WORK. HOLES IN STRUCTURAL ELEMENTS SHALL BE REINFORCED AS REQUIRED BY THE ENGINEER.
7. CUTS, HOLES, COPING, AND ALL OTHER MODIFICATIONS TO STEEL MEMBERS IN THE FIELD IS NOT
PERMITTED WITHOUT THE EXPLICIT APPROVAL OF THE ENGINEER.
SITE WORK:
1. PERFORM EXCAVATION, ACCORDING TO GOOD COMMON CONSTRUCTION PRACTICES, TO THE LINES, GRADES, ELEVATIONS INDICATED ON THE DRAWINGS AND ACCORDING TO RECOMMENDATIONS FOUND IN
SUB SURFACE REPORT BY GEOTECHNICAL ENGINEER.
2. ALL FILL UNDER SLABS AND FOUNDATIONS SHALL BE COMPACTED TO 98% OF MAXIMUM DENSITY (MODIFIED PROCTOR TEST) AT OPTIMUM MOISTURE CONTENT. A COMPACTION REPORT FROM QUALIFIED
SOILS ENGINEER SHALL BE TAKEN AND SUBMITTED TO ENGINEER OF RECORD.
3. PROVIDE SOIL POISONING TO CONTROL TERMITES AS REQUIRED BY GOVERNING CODES.
4. SAFETY NOTE - CALL 811 BEFORE YOU DIG. PURSUANT TO FLORIDA STATUTES, CHAPTER 556, THE CONTRACTOR SHALL NOTIFY SUNSHINE 811 (DIAL 811) AT LEAST TWO (2) FULL BUSINESS DAYS BEFORE BEGINNING ANY EXCAVATION. THE CONTRACTOR SHALL COORDINATE WITH SUNSHINE 811 FOR UTILITY LOCATES AND SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING UTILITIES. NO EXCAVATION SHALL
BEGIN UNTIL UTILITY MARKINGS ARE COMPLETE.
SUBMITTALS:
1. THE GENERAL CONTRACTOR SHALL SUBMIT FOR ENGINEER REVIEW SHOP DRAWINGS FOR THE
FOLLOWING ITEMS:
1.1. REINFORCING STEEL
1.2. CONCRETE MIX DESIGN
1.3. MASONRY PRODUCTS INCLUDING VERIFICATION OF f'm AND CERTIFICATES FOR ALL OTHER MATERIALS
USED IN MASONRY CONSTRUCTION INDICATING THE COMPLIANCE WITH THE CONTRACT DOCUMENTS.
1.4. EMBEDDED ITEMS (PLATES, ANGLES, BOLTS, ETC.)
1.5. CONCRETE CONSTRUCTION JOINT SEQUENCING AND CURING PLAN FOR ALL CONCRETE ELEMENTS
1.6. CONTROL JOINT LOCATIONS (CMU CONSTRUCTION)
ALL ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SIGNED, SEALED, AND DATED BY A REGISTERED
ENGINEER IN THE STATE OF FLORIDA.
2. ALL SHOP DRAWINGS MUST BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTAL TO THE CITY/ENGINEERING. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED
UNCHECKED.
3. ALL SHOP DRAWINGS SHALL BE SUBMITTED AND APPROVED PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL PLAN AND ALLOW (10) WORKING DAYS FOR APPROVAL FROM BELT ENGINEERING'S OFFICE. THIS
SHALL BE FIGURED INTO THE CONTRACTOR'S SCHEDULE BEFORE CONSTRUCTION BEGINS.
4. THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS UNLESS OTHERWISE SPECIFIED IN
WRITING BY THE ENGINEER.
5. CHANGES AND ADDITIONS MADE ON THE RE-SUBMITTALS SHALL BE CLEARLY FLAGGED AND NOTED. THE
PURPOSE OF RE-SUBMITTALS SHALL BE CLEARLY NOTED ON THE LETTER OF TRANSMITTAL.
ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO THOSE ITEMS CAUSING RE-SUBMITTAL.
6. SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
SPECIFICATIONS &
DESIGN CRITERIA
ET26-0069_WORKFILE.DWG 21.09.2026
JOSEPH S. GUAGLIARDO P.E. #80504
jguagliardo@beltengineering.com
PH.(813) 961-30751503-A WEST BUSCH BLVD.
TAMPA, FL. 33612
WWW.BELTENGINEERING.COM
FX.(813) 961-1031
CA # 29694
DATE: 9/25/26
SCALE: AS SHOWN
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: JG
DRAWN BY: RRC
CHECKED BY: JG
DATE: 9/25/26
DATE: 9/25/26
DATE: 9/25/26
BY DATER E V I S I O N S
ENGINEER OF RECORD:
SHEET No.
11677
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1
AUTHENTICATION CODE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
BE VERIFIED ON ANY ELECTRONIC COPIES.
email: jguagliardo@beltengineering.com
PHONE: (813) 961-3075
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
FAX: (813) 961-1031
CONSULTING ENGINEER
REGISTRATION NUMBER 80504
JOSEPH S. GUAGLIARDO P.E.
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE STRUCTURAL ELEMENTS
AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN
DESIGNED TO BE IN COMPLIANCE WITH THE
FLORIDA BUILDING CODE 8TH EDITION 2023. ALL
OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES
ARE THE TOTAL RESPONSIBILITY OF OTHERS.
CA # 29694
BELT JOB #ET26-0069
S1
100% DESIGN
Prel im in ary
N ot F or
Const ruct
SCALE:
PLAN VIEW (ADD-ALT. #1)
1/4" = 1'-0"
33'-7"
'-0
17'-0"
'-0
ADD-ALT. #1
SCALE:
PLAN VIEW (BASE BID)
1/4" = 1'-0"
CONDUIT STUB-UP
WINDOW
300 kW
GENERATOR
REFER TO
ELECTRICAL
REMOVABLE
BOLLARD SEE
TYP. DETAILS
6'-8"
'-1
0"
GEN-FRONT
FR
O
N T
4"
ATS
4"-6" ALL
AROUND
2' -8
5'-3"
CONDUIT STUB-UP
WINDOW
300 kW
GENERATOR
REFER TO
ELECTRICAL
REMOVABLE
BOLLARD SEE
TYP. DETAILS
6'-8"
'-1
0"
8'-8"
'-1
0"
GEN-FRONT
FR
O
N T
ATS
4" -6
" A
LL
A R
O U
N D
4"-6" ALL
AROUND
PROVIDE ATS
PLATFORM
PROVIDE GENERATOR
PLATFORM
'-7
17'-0"
17'-0" 33'-7"
'-0
" M
AS
O N
R Y
W
AL
L
AD
D -A
LT
SCALE:
WEST ELEVATION (ADD-ALT. #1)
1/4" = 1'-0"
S2
SCALE:
EAST ELEVATION (ADD-ALT. #1)
1/4" = 1'-0"
S2
SCALE:
NORTH ELEVATION (ADD-ALT. #1)
1/4" = 1'-0"
S2
SCALE:
SOUTH ELEVATION (ADD-ALT. #1)
1/4" = 1'-0"
S2
GEN SET
17'-0"
'-0
5'-0" TYP.
MASONRY WALL ADD-ALT. #1 ATS
MASONRY WALL FROM BEHIND ADD-ALT#1
REMOVABLE BOLLARD. TYP.
MASONRY WALL ADD-ALT. #1 MASONRY WALL ADD-ALT. #1
M
AS
O N
R Y
W
AL
L
AD
D -A
LT
GENERATOR SET PLATFORM 4" HIGH
ATS PLATFORM
4" HIGH
30'-0"
15'-0"
30'-0"
GEN SET
15'-0"
5'-0" TYP.
ATS
REMOVABLE BOLLARD. TYP.
GENERATOR SET PLATFORM 4" HIGH
ATS PLATFORM
4" HIGH
SCALE:
WEST ELEVATION (BASE BID)
1/4" = 1'-0"
S2
SCALE:
EAST ELEVATION (BASE BID)
1/4" = 1'-0"
S2
SCALE:
NORTH ELEVATION (BASE BID)
1/4" = 1'-0"
S2
SCALE:
SOUTH ELEVATION (BASE BID)
1/4" = 1'-0"
S2
ATS
REMOVABLE BOLLARD. TYP.
GENERATOR SET PLATFORM 4" HIGH
ATS PLATFORM
4" HIGH
'-0
5'-0" 5'-0" 5'-0"
5' -0
" T
YP
ATS GEN SET
NON-REMOVABLE BOLLARD
SEE TYP. DETAILS
REMOVABLE
BOLLARD SEE
TYP. DETAILS
REMOVABLE
BOLLARD. TYP.
REMOVABLE
BOLLARD. TYP.
5'-10" 4'
-1
4'-10"
4' -0
5' -0
2"
FLOOR PLAN
AND ELEVATIONS
ET26-0069_WORKFILE.DWG 21.09.2026
JOSEPH S. GUAGLIARDO P.E. #80504
jguagliardo@beltengineering.com
PH.(813) 961-30751503-A WEST BUSCH BLVD.
TAMPA, FL. 33612
WWW.BELTENGINEERING.COM
FX.(813) 961-1031
CA # 29694
DATE: 9/25/26
SCALE: AS SHOWN
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: JG
DRAWN BY: RRC
CHECKED BY: JG
DATE: 9/25/26
DATE: 9/25/26
DATE: 9/25/26
BY DATER E V I S I O N S
ENGINEER OF RECORD:
SHEET No.
11677
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1
AUTHENTICATION CODE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
BE VERIFIED ON ANY ELECTRONIC COPIES.
email: jguagliardo@beltengineering.com
PHONE: (813) 961-3075
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
FAX: (813) 961-1031
CONSULTING ENGINEER
REGISTRATION NUMBER 80504
JOSEPH S. GUAGLIARDO P.E.
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE STRUCTURAL ELEMENTS
AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN
DESIGNED TO BE IN COMPLIANCE WITH THE
FLORIDA BUILDING CODE 8TH EDITION 2023. ALL
OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES
ARE THE TOTAL RESPONSIBILITY OF OTHERS.
CA # 29694
BELT JOB #ET26-0069
S2
100% DESIGN
Prel im in ary
N ot F or
Const ruct
MASONRY WALL SCHEDULE (ADD-ALT. #1)
MARK BLOCK
SIZE
VERTICAL
REINFORCEMENT
HORIZONTAL
REINFORCEMENT
GROUT T.O.W.
BOND BEAM
SLAB TIES NOTES
SIZE SPACING SIZE/TYPE SPACING NUMBER OF
COURSES REINFORCEMENT
NUMBER OF
OCCURENCES
(VERTICALLY)
T.O.B.
MW-1 8" #5's 24" O.C.
11 ga.
LADDER
TYPE
EVERY
OTHER
COURSE
FILLED
CELLS ONLY 10'-0" 1 COURSE #5 x CONT. 1 10'-0" N/A
MASONRY WALL SCHEDULE NOTES:
1. ALL CMU WALLS ARE SHEAR WALLS, U.N.O.
2. SEE DESIGN CRITERIA AND TYPICAL DETAILS FOR PLACEMENT, CONSOLIDATION, CONTROL JOINTS, INSPECTION AND OTHER REQUIREMENTS.
3. PROVIDE FILLED CELLS AS SHOWN ON PLAN VIEWS.
3.1. DIMENSIONS FOR SPACING OF FILLED CELLS IN THE FIELD SHALL BE TAKEN FROM THE BUILDING CORNERS.
3.2. FILLED CELLS REQUIRED AT ALL CORNERS, TRANSITIONS, OPENINGS AND TERMINATIONS.
3.3. ALIGN STEM WALL REINFORCEMENT w/ WALLS ABOVE WHEN PRACTICAL TO DO SO. OFFSET AS REQUIRED AT SLAB TIE IN.
3.4. ALIGN LOWER LEVEL WALL REINFORCEMENT W/ UPPER LEVEL WALL REINFORCEMENT WHEN PRACTICAL DO SO. OFFSET AS REQUIRED AT THE BOND BEAM.
3.5. HORIZONTAL OFFSETS IN BOND BEAMS IS ALLOWED, SEE TYPICAL DETAILS.
4. ALL RETAINING AND STEM WALLS (IF ANY) ARE TO BE FULLY GROUTED.
GENERATOR
SET
SCALE:
(ADD-ALT. #1)
1/4" = 1'-0"
SCALE:
FOUNDATION PLAN (BASE BID)
1/4" = 1'-0"
SCALE:
WALL PLAN (ADD-ALT. #1)
1/4" = 1'-0"
PROVIDE ATS
PLATFORM
PROVIDE GENERATOR
PLATFORM
'-0
5'-0" 5'-0" 5'-0"
5' -0
" T
YP
S3
5' -0
" T
YP
S3
4' -1
5'-10"
8'-8"
'-1
0"
4"
PROVIDE 4" HIGH
ATS PLATFORM
NEW 12" MAT FOUNDATION. W/
#5's AT 8" O.C EA WAY TOP
AND BOTTOM. SEE DETAILS.
ATS
1'-0" MIN
ALL
AROUND
4"-6"
ALL
AROUND
FOUNDATIONPLAN
1/4
C O
N
TI
N U
O U
S
BO
LL
AR
D F
O O
TI
N
G
S3
3" C
O N
C R
ET
E
C O
VE
R
A
LL
AR
O
U N
D
3" CONCRETE
COVER ALL
AROUND
CMU WALL FROM BEHIND
4000 PSI CONCRETE PAD
#5's AT 8" O.C. EA WAY. TOP AND
BOTTOM W/ 9O° BENT EA END.
SCALE:
SECTION (ADD-ALT. #1)
1/2" = 1'-0"
S3
FULLY GROUTED SINGLE
COURSE BOND BEAM WITH
#5's.
#5's x 48D REBAR AT 24" O.C.
#5's MAIN VERTICAL
REINFORCEMENT AT 24" O.C.
11 ga. GALVANIZED LADDER
TYPE HORIZONTAL JOINT
REINFORCEMENT EVERY
OTHER COURSE.
4" 4"
8", NORMAL WEIGHT CMU
UNITS. PROVIDE TYPE "S"
MORTAR
FULLY GROUTED CELL AT EA
REBAR LOCATION SEE PLAN
ATS ANCHORED
TO PLATFORM
BY OTHERS
1' -0
11'-4"
1' -4
2'-0" 2'-0"
1' -4
EXISTING ASPHALT PAVEMENT SAW
CUT AND RESTORE LIKE FOR LIKE
4"
4" HIGH PLATFORM W/ #3's PERIMETER BAR AND 6x6 W1.4/W1.4 W.W.F.; SLOPE
FOR DRAINAGE.
EXISTING ASPHALT PAVEMENT SAW
CUT AND RESTORE LIKE FOR LIKE
SCALE:
SECTION (BASE BID)
1/2" = 1'-0"
S3
1'-0" ALL AROUND
GENERATOR SET SEE
ELECTRICAL
4000 PSI
CONCRETE PAD
#5's AT 8" O.C. EA WAY. TOP AND
BOTTOM W/ 90° BENT EA END.
ATS SEE
ELECTRICAL
4"-6" ALL AROUND
VARIES PER
MANUFACTURER
VARIES PER MANUFACTURER
VA
R
IE
S
PE
R
M
AN
U
FA
C
TU
R
ER
VA
R
IE
S
PE
R
M
AN
U
FA
C
TU
R
ER
NOTE:
1. GENERATOR SET AND ATS DIMENSIONS MAY VARIES PER
MANUFACTURER SPECIFICATIONS.
2. CONTRACTOR MUST COORDINATE THE FINAL EQUIPMENT
SPECS FOR FINAL PADS DIMENSIONS.
1' -0
1'-0"
1' -0
1' -4
3" CONCRETE
COVER ALL
AROUND
1'-0" ALL AROUND
1'-0"
4' -0
TY
P.
4" REMOVABLE BOLLARD
BY OTHERS. INSTALL PER
MANUFACTURER SPEC.
2' -5
3"
4" REMOVABLE BOLLARD BY OTHERS.
INSTALL PER MANUFACTURER SPEC.
EXITING ASPHALT
4000 PSI CONCRETE ENCASEMENT
FOOTING. PROVIDE (4) #5 VERTICAL
BARS WITH (4) #3 CLOSED TIES @ 9"
O.C.
2'-0"Ø
CONCRETE ENCASEMENT
FOOTING. SEE DETAILS
4' -0
TY
P.
SCALE:
TYPICAL DETAIL (BASE BID)
1/2" = 1'-0"
S3
BOLLARD
FOUNDATION DETAIL
#5's AT 8" O.C. EA WAY. TOP AND
BOTTOM W/ 90° BENT EA END.
S3
2' -0
EXISTING ASPHALT PAVEMENT SAW
CUT AND RESTORE LIKE FOR LIKE
SCALE:
SECTION (ADD-ALT. #1)
1/2" = 1'-0"
4' -0
TY
P.
4" REMOVABLE BOLLARD BY OTHERS.
INSTALL PER MANUFACTURER SPEC.
1'-9"
4000 PSI CIP CONTINUOUS BOLLARD FTG. W/
(4) #4's, (6) #3's AT 8" O.C. STIRRUPS.
STRUCTURAL PLAN
VIEW(S)
ET26-0069_WORKFILE.DWG 21.09.2026
JOSEPH S. GUAGLIARDO P.E. #80504
jguagliardo@beltengineering.com
PH.(813) 961-30751503-A WEST BUSCH BLVD.
TAMPA, FL. 33612
WWW.BELTENGINEERING.COM
FX.(813) 961-1031
CA # 29694
DATE: 9/25/26
SCALE: AS SHOWN
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: JG
DRAWN BY: RRC
CHECKED BY: JG
DATE: 9/25/26
DATE: 9/25/26
DATE: 9/25/26
BY DATER E V I S I O N S
ENGINEER OF RECORD:
SHEET No.
11677
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1
AUTHENTICATION CODE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
BE VERIFIED ON ANY ELECTRONIC COPIES.
email: jguagliardo@beltengineering.com
PHONE: (813) 961-3075
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
FAX: (813) 961-1031
CONSULTING ENGINEER
REGISTRATION NUMBER 80504
JOSEPH S. GUAGLIARDO P.E.
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE STRUCTURAL ELEMENTS
AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN
DESIGNED TO BE IN COMPLIANCE WITH THE
FLORIDA BUILDING CODE 8TH EDITION 2023. ALL
OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES
ARE THE TOTAL RESPONSIBILITY OF OTHERS.
CA # 29694
BELT JOB #ET26-0069
S3
100% DESIGN
Prel im in ary
N ot F or
Const ruct
S4
SCALE:
DETAIL (ADD-ALT. #1)
3/4" = 1'-0" SCALE:
DETAIL (ADD-ALT. #1)
3/4" = 1'-0"
S4
ADDED "L" BAR
HOOK BAR END
AS SHOWN
ADDED "L" BAR
CONT. REINFORCEMENT CONT. REINFORCEMENT
TYPICAL ALTERNATE
48 db LAP
LENGTH
d b
LA
P
LE
N G
TH
48 db LAP
LENGTH
CORNER CONTINUITY REINFORCEMENT
TYP. REINFORCED MASONRY
WALL CONTROL JOINT
NOTE:
1) CONTINUE ALL BOND BEAMS AND TIE BEAMS REINFORCEMENT THROUGH THE JOINT.
2) SAW CUT BOND BEAMS AND TIE BEAMS 1" DEEP TO CONTINUE WALL CONTROL JOINT TO
TOP OF WALL.
3) CONTROL JOINT SPACING IS NOT TO EXCEED 25'-0" O.C. IN WALLS WITH MORE THAN 25'-0"
OF UNINTERRUPTED MASONRY.
PREFORMED RUBBER
GASKET
1/2"
REINFORCED MASONRY WALL
(REINFORCING NOT SHOWN)
BACKER ROD & CONSTRUCTION
SEALANT
PREFORMED
RUBBER GASKET
SASH
UNITS
RAKE &
CAULK
1/2" TYP.
STRUCTURAL
DETAILS
ET26-0069_WORKFILE.DWG 21.09.2026
JOSEPH S. GUAGLIARDO P.E. #80504
jguagliardo@beltengineering.com
PH.(813) 961-30751503-A WEST BUSCH BLVD.
TAMPA, FL. 33612
WWW.BELTENGINEERING.COM
FX.(813) 961-1031
CA # 29694
DATE: 9/25/26
SCALE: AS SHOWN
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: JG
DRAWN BY: RRC
CHECKED BY: JG
DATE: 9/25/26
DATE: 9/25/26
DATE: 9/25/26
BY DATER E V I S I O N S
ENGINEER OF RECORD:
SHEET No.
11677
THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY JOSEPH GUAGLIARDO, P.E. USING A SHA-1
AUTHENTICATION CODE. PRINTED COPIES OF THIS
DOCUMENT ARE NOT CONSIDERED SIGNED AND
SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
BE VERIFIED ON ANY ELECTRONIC COPIES.
email: jguagliardo@beltengineering.com
PHONE: (813) 961-3075
1503-A WEST BUSCH BLVD.
TAMPA FLORIDA 33612
FAX: (813) 961-1031
CONSULTING ENGINEER
REGISTRATION NUMBER 80504
JOSEPH S. GUAGLIARDO P.E.
I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
AND BELIEF ALL OF THE STRUCTURAL ELEMENTS
AND SYSTEMS FOR THIS STRUCTURE HAVE BEEN
DESIGNED TO BE IN COMPLIANCE WITH THE
FLORIDA BUILDING CODE 8TH EDITION 2023. ALL
OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES
ARE THE TOTAL RESPONSIBILITY OF OTHERS.
CA # 29694
BELT JOB #ET26-0069
S4
100% DESIGN
Prel im in ary
N ot F or
Const ruct
E1Electrical · Lighting · Mechanical · Renewables 3820 Gunn Hwy., Suite 200 | Tampa, FL, USA 33618 www.hallenggroup.com | Tel: 813.374.2121
FL. C.O.A. #: 27620
HAL L
ENGINEERING GROUP
® DATE:
SCALE: SEE BAR SCALE
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: DS
DRAWN BY: GW
CHECKED BY: KH
DATE:09/25/2026
DATE:
DATE:
BY DATER E V I S I O N S
ENGINEER OF RECORD:
KEITH W. HALL
FL P.E. No. 55024
-H
AL
L
EN
G
IN
EE
R
IN
G
R O
U P, C
R
ET
AI
N
S
IN
TE
LL
EC
TU
AL
A
N D
P H
YS
IC
AL
R
IG
H
TS
T
O T
H
IS
D O
C U
M
EN
T
AN
D
IT
S C
O N
TE
N
T
AN
D P
R O
H
IB
IT
S
IT
S
PU
BL
IS
H
IN
G
D
IS
C
LO
SU
R E
O
EP
R
O D
U C
TI
O
N W
IT
H
O U
T C
O N
SE
N
T.
TH
IS
D O
C U
M
EN
T
IS
V
AL
ID
F
O R
M O
N
TH
S
FR
O M
D
AT
E O
F
EN
G
IN
EE
R
'S S
IG
N
AT
U
R E
AN
D
S
EA
L.
SHEET No.
KEITH W. HALL, P.E.; FL. REG. #: 55024
09/25/2026 09/25/2026
09/25/2026
11677
ELECTRICAL LEGEND & SITE PLAN
Z
P ro je ct s\
D
C oS
P Fl ee t
M an ag em en t
N ew
G en er at or D es ig n\ D ra w in gs
\E le ct ri ca l\ S he et S et \2
7D
_E
El ec tr ic al S pe ci fic at io ns
L eg en d.
dw g
S ep
.2 5.
9:
am
300 kW
GENERATOR
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS SS
300 kW
GENERATOR
300 kW
GENERATOR
E2Electrical · Lighting · Mechanical · Renewables 3820 Gunn Hwy., Suite 200 | Tampa, FL, USA 33618 www.hallenggroup.com | Tel: 813.374.2121
FL. C.O.A. #: 27620
HAL L
ENGINEERING GROUP
® DATE:
SCALE: SEE BAR SCALE
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: DS
DRAWN BY: GW
CHECKED BY: KH
DATE:09/25/2026
DATE:
DATE:
BY DATER E V I S I O N S
ENGINEER OF RECORD:
KEITH W. HALL
FL P.E. No. 55024
-H
AL
L
EN
G
IN
EE
R
O
R
ET
AI
N
S
IN
TE
LL
EC
TU
AL
A
N D
P H
YS
IC
AL
R
IG
H
TS
T
O T
H
IS
D O
C U
M
EN
T
AN
D
IT
S C
O N
TE
N
T
AN
D P
R O
H
IB
IT
S
IT
S
PU
BL
IS
H
IN
G
D
IS
C
LO
SU
R E
R
O D
U C
TI
O
N W
IT
H
O U
T C
O N
SE
N
T.
TH
IS
D O
C U
M
EN
T
IS
V
AL
ID
F
O R
M O
N
TH
S
FR
O M
D
AT
E O
F
EN
G
IN
EE
R
'S S
IG
N
AT
U
R E
AN
D
S
EA
L.
SHEET No.
KEITH W. HALL, P.E.; FL. REG. #: 55024
09/25/2026 09/25/2026
09/25/2026
11677
ELECTRICAL PLAN
Z
P ro je ct s\
D
C oS
P Fl ee t
M an ag em en t
N ew
G en er at or D es ig n\ D ra w in gs
\E le ct ri ca l\ S he et S et \2
7D
_E
El ec tr ic al P la n.
.2
5.
E3Electrical · Lighting · Mechanical · Renewables www.hallenggroup.com | Tel: 813.374.2121
FL. C.O.A. #: 27620
HAL L
ENGINEERING GROUP
® DATE:
SCALE: SEE BAR SCALE
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: DS
DRAWN BY: GW
CHECKED BY: KH
DATE:09/25/2026
DATE:
DATE:
BY DATER E V I S I O N S
ENGINEER OF RECORD:
KEITH W. HALL
FL P.E. No. 55024
-H
AL
L
EN
G
IN
EE
R
O
R
ET
AI
N
S
IN
TE
LL
EC
TU
AL
A
N D
P H
YS
IC
AL
R
IG
H
TS
T
O T
H
IS
D O
C U
M
EN
T
AN
D
IT
S C
O N
TE
N
T
AN
D P
R O
H
IB
IT
S
IT
S
PU
BL
IS
H
IN
G
D
IS
C
LO
SU
R E
R
O D
U C
TI
O
N W
IT
H
O U
T C
O N
SE
N
T.
TH
IS
D O
C U
M
EN
T
IS
V
AL
ID
F
O R
M O
N
TH
S
FR
O M
D
AT
E O
F
EN
G
IN
EE
R
'S S
IG
N
AT
U
R E
AN
D
S
EA
L.
SHEET No.
KEITH W. HALL, P.E.; FL. REG. #: 55024
09/25/2026 09/25/2026
09/25/2026
11677
POWER ONE-LINE DIAGRAM
& LOAD SUMMARY
Z
P ro je ct s\
D
C oS
P Fl ee t
M an ag em en t
N ew
G en er at or D es ig n\ D ra w in gs
\E le ct ri ca l\ S he et S et \2
7D
_E
Po w er O ne -L in e
D ia gr am
L oa d
S um m ar y.
.2 5.
E4Electrical · Lighting · Mechanical · Renewables www.hallenggroup.com | Tel: 813.374.2121
FL. C.O.A. #: 27620
HAL L
ENGINEERING GROUP
® DATE:
SCALE: SEE BAR SCALE
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: DS
DRAWN BY: GW
CHECKED BY: KH
DATE:09/25/2026
DATE:
DATE:
BY DATER E V I S I O N S
ENGINEER OF RECORD:
KEITH W. HALL
FL P.E. No. 55024
-H
AL
L
EN
G
IN
EE
R
O
R
ET
AI
N
S
IN
TE
LL
EC
TU
AL
A
N D
P H
YS
IC
AL
R
IG
H
TS
T
O T
H
IS
D O
C U
M
EN
T
AN
D
IT
S C
O N
TE
N
T
AN
D P
R O
H
IB
IT
S
IT
S
PU
BL
IS
H
IN
G
D
IS
C
LO
SU
R E
R
O D
U C
TI
O
N W
IT
H
O U
T C
O N
SE
N
T.
TH
IS
D O
C U
M
EN
T
IS
V
AL
ID
F
O R
M O
N
TH
S
FR
O M
D
AT
E O
F
EN
G
IN
EE
R
'S S
IG
N
AT
U
R E
AN
D
S
EA
L.
SHEET No.
KEITH W. HALL, P.E.; FL. REG. #: 55024
09/25/2026 09/25/2026
09/25/2026
11677
ELECTRICAL DETAILS
Z
P ro je ct s\
D
C oS
P Fl ee t
M an ag em en t
N ew
G en er at or D es ig n\ D ra w in gs
\E le ct ri ca l\ S he et S et \2
7D
_E
D et ai ls
.d w
.2 5.
Electrical · Lighting · Mechanical · Renewables www.hallenggroup.com | Tel: 813.374.2121
FL. C.O.A. #: 27620
HAL L
ENGINEERING GROUP
® DATE:
SCALE: SEE BAR SCALE
DRAWING No.
ENGINEERING & CAPITAL
IMPROVEMENTS DEPARTMENT
CITY OF ST. PETERSBURG
ST. PETERSBURG FLEET MANAGEMENT
NEW GENERATOR DESIGN
PROJECT No. 25143-130
DESIGNED BY: DS
DRAWN BY: GW
CHECKED BY: KH
DATE:09/25/2026
DATE:
DATE:
BY DATER E V I S I O N S
ENGINEER OF RECORD:
KEITH W. HALL
FL P.E. No. 55024
-H
AL
L
EN
G
IN
EE
R
O
R
ET
AI
N
S
IN
TE
LL
EC
TU
AL
A
N D
P H
YS
IC
AL
R
IG
H
TS
T
O T
H
IS
D O
C U
M
EN
T
AN
D
IT
S C
O N
TE
N
T
AN
D P
R O
H
IB
IT
S
IT
S
PU
BL
IS
H
IN
G
D
IS
C
LO
SU
R E
R
O D
U C
TI
O
N W
IT
H
O U
T C
O N
SE
N
T.
TH
IS
D O
C U
M
EN
T
IS
V
AL
ID
F
O R
M O
N
TH
S
FR
O M
D
AT
E O
F
EN
G
IN
EE
R
'S S
IG
N
AT
U
R E
AN
D
S
EA
L.
SHEET No.
KEITH W. HALL, P.E.; FL. REG. #: 55024
09/25/2026 09/25/2026
09/25/2026
11677 E5
LIGHTNING PROTECTION NOTES
& DETAILS
Z
P ro je ct s\
D
C oS
P Fl ee t
M an ag em en t
N ew
G en er at or D es ig n\ D ra w in gs
\E le ct ri ca l\ S he et S et \2
7D
_E
Li gh tn in g Pr ot ec tio n
N ot es
D et ai ls
.d w
.2 5.
| 2507D_Sheet Set |
| 2507D_G0 Cover Sheet & Index |
| 2507D_E1 Electrical Legend & Site Plan |
| 2507D_E2 Electrical Plan |
| 2507D_E3 Power One-Line Diagram & Load Summary |
| 2507D_Conduit Trench Detail |
| 2507D_26 41 13.25 Ground Well Detail |
| 2507D_E4 Electrical Details |
| 2507D_E5 Lightning Protection Notes & Details |
| 26 41 13.24 Air Term Roof Top Equipment Detail |
2026.09.23_ET26-0069_GENERATOR PAD 100% SUBMITTAL
File details come from the government source that posted it. Updated .