Bid_24-13_Drawings_-_Plans_Escalator_Canopies_20250420_TSA_-_SET_C.pdf
PDF 6 MB Posted
- Attached to
- Escalator Canopies, RJS
- Solicitation number
- 24-13
- Issued by
- Florida
About this file
These engineering construction drawings, prepared by Osborn Engineering for the Tampa Sports Authority, detail the canopy restoration project at Raymond James Stadium in Tampa, Florida. The project involves comprehensive restoration of four exterior canopy quadrants, specifically focusing on structural steel deck replacement, metal decking restoration, and ensuring wind load compliance. The drawings provide detailed structural plans, framing layouts, and technical specifications for the NW, NE, SW, and SE quadrants of the stadium's canopy, with a typical restoration approach that includes removing and replacing existing metal roof decking, addressing corrosion issues, and maintaining the existing structural framework.
The technical documents indicate a precise, methodical approach to the restoration, with specific attention to wind loading criteria, deck configuration, and structural integrity. The project requires contractors to verify all existing dimensions, maintain fire ratings, and adhere to strict installation standards. While the drawings do not specify exact pricing, they suggest a complex engineering project that will require specialized structural expertise, particularly in metal deck replacement and wind load engineering. The restoration appears designed to extend the structural life of the stadium's canopy while ensuring safety and compliance with current building standards, with work to be conducted during restricted hours (Monday through Friday, 6am-5pm) and targeted for substantial completion by July 18th, 2025.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABOVE FINISH FLOOR
ACCESS PANEL
ACRE
ADJACENT
ALTERNATE
ALUMINUM
ANCHOR BOLT
AND
ANGLE
APPROXIMATE
ARCHITECT(URAL)
AT
BACK TO BACK
BEAM
BEARING
BITUMINOUS
BLOCKING
BOTTOM
BOTTOM OF
BOTTOM OF STEEL
BRICK
BUILDING
BUILT-UP ROOF
CABINET HEATER
CARD READER
CAST IRON
CEILING
CEMENTITIOUS WOOD FIBER
CENTER LINE
CENTER TO CENTER
CENTIMETER
CLEANOUT
CLEAR
COLD-FORMED FRAMING
COLD WATER
COLUMN
COMPACTED/COMPACTOR
CONCRETE
CONCRETE MASONRY UNIT
CONSTRUCTION
CONTINUOUS/CONTINUE
CONTRACTOR
CONTROL JOINT
DEAD LOAD
DEGREE
DEMOLITION
DEPARTMENT
DETAIL
DEPTH/DEEP
DIAMETER
DIMENSION
DISHWASHER
DIVISION
DOWN
DOWNSPOUT
DRAWING
EACH
EACH FACE
EACH WAY
EAST
EDGE OF SLAB
ELECTRICAL
ELECTRICAL PANEL BOARD
ELEVATION/ELEVATOR
ENGINEER
EQUAL
EQUIPMENT
EXHAUST
EXISTING
EXPANSION
EXPANSION JOINT
EXTENSION
EXTERIOR
EXTERIOR INSULATION FINISH SYSTEM
FIBER REINFORCED PLASTIC
FIRE DEPARTMENT CONNECTION
FIRE EXTINGUISHER AND WALL BRACKET
FIRE EXTINGUISHER BRACKET
FIRE EXTINGUISHER CABINET
FIRE RETARDANT TREATED
FIRE VALVE CONNECTION
FINISH
FINISH FLOOR
FLOOR
FLOOR CLEANOUT
FLOOR DRAIN
FOOT/FEET
FOOTING
FOUNDATION
GALVANIZED
GARBAGE DISPOSAL
GAUGE
GLASS
GROUND FACE CONCRETE MASONRY UNIT
GYPSUM BOARD
HARDWARE
HEATING
HEATING, VENTILATION AND AIR CONDITIONING
HEIGHT
HIGH
HIGH POINT
HOLLOW METAL
HORIZONTAL
HOSE BIB
HOT WATER
HOUR
INCH
INCLUDE(D), (ING)
INFORMATION
INSIDE DIAMETER/IDENTIFICATION
INSULATION
INTERIOR
INVERT
AFF
AP
AC
ADJ
ALT
ALUM
AB
L
APPROX
ARCH
B TO B
BM
BRG
BIT
BLKG
BOT
BO
BOS
BRK
BLDG
BUR
CH
CR
CI
CLG
CWF
CL
C TO C
CM
CO
CLR
CFF
CW
COL
COMP
CONC
CMU
CONSTR
CONT
CONTR
CJ
DL
DEMO
DEPT
DET
D
DIA/Ø
DIM
DW
DIV
DN
SP
DWG
EA
EF
EW
E
EOS
ELEC
EP
ELEV
ENGR
EQ
EQUIP
EXH
EXIST
EXP
EJ
EXTN
EXT
EIFS
FRP
FDC
FE
FEB
FEC
FRT
FVC
FIN
FF/FIN FL
FLR
FCO
FD
FT
FTG
FDN
GALV
GD
GA
GL
GFCMU
GYP BRD
HDWR
HTG
HVAC
HT
H
HP
HM
HORIZ
HB
HW
HR
IN
INCL
INFO
ID
INSUL
INT
INV
JOINT
KNOCK DOWN
LAMINATED
LAVATORY
LENGTH
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONG WAY
LOUVER
MANUFACTURER
MASONRY
MASONRY OPENING
MATERIAL
MAXIMUM
MECHANICAL
METAL
MICROWAVE
MINIMUM
MISCELLANEOUS
MODIFIED
NOMINAL
NORTH
NOT IN CONTRACT
NOT TO SCALE
NUMBER
ON CENTER
OPEN TO BELOW
OPENING
OPPOSITE
OPPOSITE HAND
OUT TO OUT
OUTSIDE DIAMETER
OVERHEAD COILING DOOR
OVERHEAD COILING GRILLE
PAINT
PANEL
PANEL JOINT
PLUMBING
PLYWOOD
POINT OF CONNECTION
POUND
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POWDER ACTUATED FASTENER
PREFABRICATED
PROPERTY LINE
RADIUS
REFERENCE
REFRIGERATOR
REINFORCING
REQUIRED
RETURN AIR
REVISION(S)
RISER
ROOF DRAIN
ROOM
ROUGH OPENING
SANITARY
SCHEDULE
SECTION
SHEET
SIMILAR
SOUTH
SPACE
SPECIFICATION(S)
SQUARE
SQUARE FOOT/FEET
SQUARE INCH(ES)
SQUARE YARD(S)
STAINLESS STEEL
STANDARD
STEEL
STORM DRAIN
STRUCTURE/STRUCTURAL
SUPPLY AIR
SYMMETRY(ICAL)
TELEVISION
THICK/THICKNESS
TREAD
TOILET
TOP AND BOTTOM
TOP OF
TOP OF CONCRETE
TOP OF CURB
TOP OF FOOTING
TOP OF MASONRY
TOP OF STEEL
TWO-WAY COMMUNICATION
TYPICAL
UNIT VENTILATOR
UNLESS NOTED OTHERWISE
VAPOR RETARDER
VENT STACK
VERIFY IN FIELD
VERTICAL
VOLUME
WALL CLEANOUT
WEATHER RESISTANT BARRIER
WELDED WIRE FABRIC
WEST/WIDE/WIDTH
WITH
WITHOUT
WOOD
JT
KD
LAM
LAV
L
LL
LLH
LLV
LW
LVR
MFR
MAS
MO
MATL
MAX
MECH
MTL
MICRO
MIN
MISC
MOD
NOM
N
NIC
NTS
NO/#
OC
OTB
OPNG
OPP
OH
O TO O
OD
OCD
OCG
PT
PNL
PJ
PLUMB
PLYWD
POC
LB/#
PSF
PSI
PAF
PREFAB
PL
RAD/R
REF
REFRIG
REINF
REQD
RA
REV
R
RD
RM
RO
SAN
SCH
SECT
SHT
SIM
S
SP
SPEC(S)
SQ
SF
SI
SY
SS
STD
STL
SD
STRUCT
SA
SYMM
TV
THK
T
TLT
T&B
TO
TOC
TC
TOF
TOM
TOS
TWC
TYP
UV
UNO
VR
VS
VIF
VERT
VOL
WCO
WRB
WWF
W W/
WO
WD
1. GENERAL PROJECT NOTES ARE APPLICABLE TO ALL PROJECT AREAS.
2. THE CONTRACTOR SHALL GIVE NOTICES AND COMPLY WITH LAWS, ORDINANCES, RULES, REGULATIONS AND ORDERS OF ANY PUBLIC AUTHORITY BEARING ON THE WORK. IF THE CONTRACTOR OBSERVES THE CONTRACT DOCUMENTS ARE AT VARIANCE WITH SUCH IN ANY RESPECT; PROMPTLY NOTIFY THE OWNER IN WRITING, SUCH THAT ALL NECESSARY CHANGES CAN BE MADE. IF CONTRACTOR KNOWINGLY PERFORMS ANY WORK CONTRARY TO SUCH WITHOUT NOTICE TO THE OWNER, THEY SHALL ASSUME FULL
RESPONSIBILITY THEREFORE AND SHALL BEAR COST ATTRIBUTED THERETO.
3. ALL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN A NEAT AND ORDERLY MANNER. MATERIALS SHALL BE NEW; SECONDHAND OR DAMAGED MATERIALS SHALL NOT BE USED. CONTRACTOR IS RESPONSIBLE FOR THE SAFETY AND CONDITION OF THE EQUIPMENT, MATERIALS AND SYSTEMS UNTIL FINAL ACCEPTANCE OF THE SYSTEM.
4. THE CONTRACTOR IS TO TAKE APPROPRIATE STEPS TO PROTECT ALL EXISTING FLOORING AND WALLS FROM DIRT AND DAMAGE. THE CONTRACTOR IS TO MAINTAIN A CLEAN WORK AREA THROUGHOUT ALL ADJACENT SPACES DURING CONSTRUCTION, AND BE
RESPONSIBLE FOR CLEANING ALL AREAS AT THE END OF EACH WORK DAY.
5. THE CONTRACTOR IS TO TAKE APPROPRIATE CARE IN REMOVAL OF ITEMS; INCLUDING BUT NOT LIMITED TO LOCKERS, FIXTURES, AND APPLIANCES. MAINTAIN PROPER CONDITION AND RETURN TO OWNER FOR STORAGE. CONTRACTOR TO COORDINATE WITH OWNER FOR THE RETURN OF ALL SALVAGEABLE ITEMS. THE OWNER RESERVES THE RIGHT OF FIRST REFUSAL OF ALL BUILDING MATERIALS BEING REMOVED. IF DECLINED, THE CONTRACTOR SHALL DISPOSE OF MATERIAL IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE, AND LOCAL LAWS AND REGULATIONS.
6. WHEN REFERRING TO SCOPE OF WORK; THE WORDS "PROVIDE", "INSTALL", AND "REPLACE" INDIVIDUALLY SHALL BE ASSUMED TO MEAN THAT THE CONTRACTOR IS TO REMOVE ANY EXISTING ITEMS, PROVIDE NEW ITEMS, AND INSTALL NEW ITEMS - UNLESS
EXPRESSLY INDICATED OTHERWISE.
7. FILL AND PATCH ALL OPENINGS RESULTING FROM DEMOLITION AND CONSTRUCTION TO WALLS, FLOORS, AND CEILINGS. PATCH TO MATCH EXISTING FINISHES. CONTRACTOR TO MAINTAIN ALL FIRE RATINGS REQUIRED BY GOVERNING BUILDING CODE REGARDLESS
OF EXISTING CONDITIONS. TYPICAL ENTIRE PROJECT AREA.
8. ALL EXISTING STRUCTURE TO REMAIN. CONTRACTOR SHALL TAKE APPROPRIATE CARE NOT TO DAMAGE EXISTING STRUCTURE.
9. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CLEARANCES AND ALL EXISTING FIELD CONDITIONS BEFORE STARTING CONSTRUCTION. COMMENCEMENT OF WORK CONSTITUTES ACCEPTANCE OF CONDITIONS. SHOULD DIFFERENT CONDITIONS BE
ENCOUNTERED, CONTACT THE ARCHITECT BEFORE PROCEEDING WITH WORK.
10. ALL DIMENSIONS ARE TO FINISH FACE OF WALL, UNLESS SPECIFICALLY NOTED OTHERWISE.
11. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING
CLARIFICATION FROM HE ARCHITECT BEFORE CONTINUING WITH WORK.
12. WHEN MODIFYING ANY PART OF AN EXISTING WALL OR ANY ITEM ATTACHED TO A WALL, THE ENTIRE SURFACE IS TO BE PAINTED
FROM CORNER TO CORNER, U.N.O.
13. PROVIDE AND INSTALL NEW DOORS AND HARDWARE AS INDICATED ON DRAWINGS.
14. REFER TO PLANS, INTERIOR ELEVATIONS AND WALL TYPE DETAILS FOR NEW WALLS, FLOORS AND CEILING FINISHES AND
CONSTRUCTION.
15. UPON COMPLETION, CONTRACTOR IS RESPONSIBLE TO THOROUGHLY CLEAN ENTIRE PROJECT AREA, IN ORDER TO PREPARE IT FOR
IMMEDIATE USE.
16. IN AREAS WHERE NEW FLOORING AND BASE IS BEING PROVIDED AND INSTALLED (BOTH NEW AND PATCHED AREAS); THE CONTRACTOR IS TO PREPARE SUBSTRATE TO RECEIVE NEW MATERIALS AS RECOMMENDED BY THE MANUFACTURER.
1. SEE SPECIFICATIONS FOR QUALITY OF CONSTRUCTION REQUIRED, QUALITY OF WORK, MANUFACTURING AND INDUSTRY STANDARDS, PHYSICAL PROPERTIES OF MATERIALS, CONFORMANCE TO CODES AND REGULATIONS GUARANTEE AND WARRANTY REQUIREMENTS.
2. SEE ARCHITECTURAL, HVAC, PLUMBING, ELEVATOR, FIRE PROTECTION & ELECTRICAL DRAWINGS FOR OTHER PERTINENT INFORMATION RELATED TO STRUCTURAL WORK AND COORDINATE AS REQUIRED. CONTRACTOR SHALL COORDINATE STRUCTURAL DRAWINGS WITH
ALL OTHER DRAWINGS WITHIN THE CONTRACT DOCUMENTS.
3. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND CONDITIONS RELATED TO EXISTING CONSTRUCTION, EXISTING
SERVICES, AND THE SITE BEFORE BEGINNING WORK.
4. IF MATERIALS, QUANTITIES, STRENGTHS OR SIZES INDICATED BY THE DRAWINGS OR SPECIFICATIONS ARE NOT IN AGREEMENT WITH THESE NOTES, THE BETTER QUALITY AND/OR GREATER QUANTITY, STRENGTH OR SIZE INDICATED, SPECIFIED OR NOTED SHALL BE
PROVIDED.
5. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE FOLLOWING ITEMS THAT WILL NOT BE REVIEWED BY THE OWNER, ARCHITECT OR
ENGINEER.
a. DEVIATIONS FROM CONTRACT DOCUMENTS
b. DIMENSIONS, ELEVATIONS AND CONDITIONS TO BE CONFIRMED AND CORRELATED AT THE SITE
c. FABRICATION PROCESS INFORMATION
d. MEANS, METHODS, TECHNIQUES, PROCEDURES OF CONSTRUCTION AND CONSTRUCTION SAFETY
e. COORDINATION OF THE WORK OF ALL TRADES
f. QUALITY ASSURANCE SUBMITTALS
DETAIL IDENTIFICATION ROOM NAME & NUMBER
DOOR NUMBER
KEYNOTE INDICATOR
PARTITION TYPE INDICATOR
SIM
SHEET ON WHICH
DETAIL IS SHOWN
DETAIL NUMBER
INDICATES DETAIL IS
SIMILAR TO CALL OUT (IF
APPLICABLE)
XXX
DOOR NUMBER
INTERIOR ELEVATION IDENTIFICATION
X-XXX
SHEET ON WHICH
ELEVATION IS SHOWN
ELEVATION NUMBER
DIRECTION FROM WHICH
ELEVATION IS VIEWED
X
X
X X
ROOM
NAME
XXX
XXXX SF
ROOM NUMBER
ROOM NET SQUARE FOOTAGE
(IF APPLICABLE)
XX
XXXX
WALL TYPE
X
X-XXX
SIM
X
X-XXX
NORTH
PLAN
NORTH
TRUE
1111 Superior Avenue - Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
PROJ NO.
This item has been electronically signed and sealed by [LICENSEE NAME] using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
REVISIONS
SHEET NAME:
A B
E F
C D
KEY PLAN
ISSUE DATE:
ISSUED BY:
R A
Y M
O N
D J
A M
E S
M
IN
O
R P
R O
J E
C T
S
C
C A
N O
P Y
R E
S T
O R
A T
IO
N
G-000C
COVER SHEET AND
PROJECTION
INFORMATION
J-20242075
T A
M P
A
F L
100% CD SET
02/24/25
02/24/25
VICINITY MAP
SITE MAP
PROJECT LOCATION
RAYMOND JAMES
STADIUM MINOR
PROJECTS - C
OWNER:
JOSHUA MUNK
DIRECTOR OF FACILITIES
CONTACT: jmunk@tampasportsauthority.com 4201 N Dale Mabry Hwy, Tampa, FL 33607
CONTACT INFORMATION
CANOPY RESTORATION
ARCHITECT:
FIRM: OSPORTS
CONTACT: THOM CHUPARKOFF
ADDRESS: 400 N. TAMPA ST., SUITE 2230 TAMPA, FL 33602
PHONE: (813) 868-4100
ENGINEERS:
FIRM: OSBORN ENGINEERING
CONTACT: JACK KREBS
ADDRESS: 400 N. TAMPA ST., SUITE 2230 TAMPA, FL 33602
PHONE: (813) 868-4100
AREA OF WORK. TYP.
EACH OF (4) AREAS
KEY PLAN
ABBREVIATIONS GENERAL PROJECT NOTES
GENERAL NOTES CONDITION
DRAWING SYMBOL LEGEND
SHEET LIST
DRAWING INDEX - C
DRAWING NO. TITLE
DRAWING ISSUE
DATE
ARCHITECTURAL
G-000C COVER SHEET AND PROJECTION INFORMATION 02/24/25
A-001C OVERALL - BUILDING PLAN 02/24/25
A-102C OVERALL - EXTERIOR CANOPY 02/24/25
STRUCTURAL
S-100C GENERAL CONDITIONS 02/24/25
S-102C QUAD A AND B CANOPY PLANS 02/24/25
S-103C QUAD C AND D CANOPY PLANS 02/24/25
4201 N Dale Mabry Hwy, Tampa, FL 33607
TAG ISSUED DATE
UP
W H
V
IS
IT
O
R 'S
L O
C K
E R
R O
O M
S
S H
E E
T S
A S
B .0
.7
A
S B
.0 .9
A-102C
AREA OF WORK
NORTH
PLAN
NORTH
TRUE
1111 Superior Avenue - Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
PROJ NO.
This item has been electronically signed and sealed by [LICENSEE NAME] using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
REVISIONS
SHEET NAME:
A B
E F
C D
KEY PLAN
ISSUE DATE:
ISSUED BY:
R A
Y M
O N
D J
A M
E S
M
IN
O
R P
R O
J E
C T
S
C
C A
N O
P Y
R E
S T
O R
A T
IO
N
A-001C
OVERALL - BUILDING
PLAN
J-20242075
T A
M P
A
F L
100% CD SET
02/24/25
02/24/25
1" = 40'-0"
OVERALL - BUILDING PLAN
GENERAL CONDITIONS:
1. SEE ARCHITECTURAL, HVAC, PLUMBING, ELEVATOR, FIRE PROTECTION & ELECTRICAL
DRAWINGS FOR OTHER PERTINENT INFORMATION RELATED TO STRUCTURAL WORK
AND COORDINATE AS REQUIRED. CONTRACTOR SHALL COORDINATE STRUCTURAL
DRAWINGS WITH ALL OTHER DRAWINGS WITHIN THE CONTRACT DOCUMENTS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND CONDITIONS
RELATED TO EXISTING CONSTRUCTION, EXISTING SERVICES, AND THE SITE BEFORE
BEGINNING WORK.
3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE FOLLOWING ITEMS THAT WILL
NOT BE REVIEWED BY THE OWNER, ARCHITECT OR ENGINEER:
A. DEVIATIONS FROM CONTRACT DOCUMENTS.
B. DIMENSIONS, ELEVATIONS AND CONDITIONS TO BE CONFIRMED AND CORRELATED
AT THE SITE.
C. FABRICATION PROCESS INFORMATION.
D. MEANS, METHODS, TECHNIQUES, PROCEDURES OF CONSTRUCTION AND
CONSTRUCTION SAFETY.
E. COORDINATION OF THE WORK OF ALL TRADES.
EXISTING CONDITIONS:
1. THE INFORMATION SHOWN ON THE ARCHITECTURAL AND STRUCTURAL
CONSTRUCTION DOCUMENTS IS BASED ON ASSUMPTIONS OF THE EXISTING BUILDING
CONSTRUCTION. ORIGINAL CONSTRUCTION DOCUMENTS WERE NOT AVAILABLE FOR
THE PREPARATION OF THESE DOCUMENTS. THE CONTRACTOR IS TO NOTIFY THE A/E
IF CONDITIONS DIFFERING FROM THOSE STATED ARE UNCOVERED IN THE DEMOLITION
PROCESS.
2. CONTRACTOR IS RESPONSIBLE TO UNCOVER AND VISUALLY FIELD VERIFY THE
EXISTING CONSTRUCTION PRIOR TO THE START OF ANY WORK AFFECTING THE
EXISTING STRUCTURE. CONTRACTOR IS TO REPORT ANY CHANGES OR
DISCREPANCIES FROM THOSE SHOWN TO THE A/E.
DEMOLITION:
1. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE DEMOLITION
PROCEDURE AND SEQUENCE TO ENSURE THE SAFETY OF THE EXISTING BUILDING
AND ITS COMPONENT PARTS DURING DEMOLITION AND FUTURE ERECTION. THIS
INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION OF ANY OR ALL TEMPORARY
BRACING, GUYS OR TIE-DOWNS WHICH MAY BE NECESSARY. SUCH MATERIAL SHALL
BE REMOVED AND SHALL REMAIN THE PROPERTY OF THE CONTRACTOR AFTER
COMPLETION OF THE PROJECT.
2. THE CONTRACTOR SHALL SUPPORT, BRACE AND SECURE EXISTING STRUCTURE AS
REQUIRED. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFETY OF THE EXISTING
BUILDING DURING DEMOLITION AND CONSTRUCTION. FIELD VERIFY ALL EXISTING
DIMENSIONS, ELEVATIONS AND CONDITIONS WHICH AFFECT THE DEMOLITION AND
NEW CONSTRUCTION.
3. THE EXTENT OF THE WORK SHOWN SHALL INCLUDE REMOVAL AND DISPOSAL, OFF
SITE, OF THE ELEMENTS INDICATED WITHIN THESE DEMOLITION DRAWINGS UNO.
4. THE EXISTING STRUCTURE SHALL BE DISASSEMBLED IN A MANNER WHICH DOES NOT
DAMAGE OR DEFORM ANY EXISTING STRUCTURE TO REMAIN. EXISTING SLABS SHALL
BE SAWCUT IN A MANNER WHICH DOES NOT CAUSE THE SLAB SUPPORTING MEMBER
TO BE CUT OR DAMAGED.
5. CONFORM TO ALL APPLICABLE CODES FOR DEMOLITION OF STRUCTURES, SAFETY OF
EXISTING AND ADJACENT STRUCTURES, DUST CONTROL, AND DISPOSAL.
UNIT PRICE REPAIR SCOPE:
1. THE EXISTING CONDITION OF THE TOP SURFACE ON THE ROOF DECK IS UNKNOWN \
BECAUSE IT IS CONCEALED BY A ROOF MEMBRANE SYSTEM. THEREFORE, THE
QUANTITY OF ROOF DECK TO BE REPLACED IS CURRENTLY UNDETERMINED.
2. UPON REMOVAL OF THE ROOF MEMBRANE SYSTEM, THE ENGINEER WILL MAKE A SITE
VISIT TO DOCUMENT EXISTING CONDITIONS AND DETERMINE THE ACTUAL QUANTITY OF
ROOF DECK TO BE REPLACED.
3. THE EXISTING ROOF DECK PANELS ARE ASSUMED TO BE 2'-0” WIDE AND EACH SHEET
EXTENDS OVER THREE SPANS.
4. THE FOLLOWING REPAIR QUANTITY TABLE INCLUDES THE 'TOTAL BASE BID QUANTITY'
TO BE USED BY THE CONTRACTOR IN DEVELOPING THEIR BID. THE ACTUAL REPAIR
QUANTITY MAY DEVIATE UP OR DOWN FROM THOSE SHOWN BASED ON ACTUAL FIELD
CONDITIONS.
5. THE BIDDER SHALL SUBMIT A UNIT PRICE FOR REPLACEMENT OF CORRODED ROOF
DECK. THIS UNIT PRICE WILL BE USED TO ADD OR DEDUCT FROM THE BASE BID
QUANTITY COST AS FIELD CONDITIONS WARRANT.
Canopy Location Repair Description Unit Base Bid Quantity Quad A Quad B Quad C Quad D
Roof Deck Replacement Roof Deck Replacement Roof Deck Replacement Roof Deck Replacement
SF
SF
SF
SF
BASE BID REPAIR QUANTITY TABLE
Total Base Bid Quantity = 1,295 SF
STEEL DECK:
1. CODES AND STANDARDS:
ALL STEEL DECK DETAILING, FABRICATION AND ERECTION SHALL BE GOVERNED BY
CONTRACT DOCUMENTS AND LATEST EDITIONS OF:
A. SDI DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS AND ROOF DECKS.
B. AISI - SPECIFICATION OF THE DESIGN OF COLDFORMED STEEL STRUCTURAL
MEMBERS.
C. AWS D1.3 - STRUCTURAL WELDING CODE.
2. SUBMITTALS:
A. SUBMIT SHOP DRAWINGS FOR REVIEW AND APPROVAL WHICH INCLUDES
ERECTION PLANS, ATTACHMENTS, MATERIAL SPECIFICATIONS, STRENGTHS, AND
FINISHES.
3. ROOF DECK:
a. 3" x 18 GA Deck
b. ATTACH WITH 5/8" PUDDLE WELD WITH A 36/4 PATTERN AND (2) #10 SELF
DRILLING SCREW SIDE LAP FASTENERS.
c. ASTM A653 GRADE C, D OR E, GR 33 OR HIGHER.
d. GALVANIZED G90
e. CONFORM TO FACTORY MUTUAL REQUIREMENTS.
4. CONSTRUCTION:
A. CONFIGURE DECK LAYOUTS TO BE MINIMUM THREE SPAN CONTINUOUS.
B. MINIMUM END BEARING = 1 1/2".
C. BUTT ENDS OVER STRUCTURE SUPPORT.
ROOF ZONE 3
PRESSURE
10 SF
ROOF ZONE 2ROOF ZONE 1
19 -108
SUCTION PRESSURE SUCTION PRESSURE SUCTION
19 -146 -20419
COMPONENT
AREA
WALL ZONE 4
PRESSURE SUCTION
-5858
WALL ZONE 5
PRESSURE SUCTION
-11558
COMPONENT AND CLADDING LOAD CRITERIA
WIND LOADING (PSF) IN ACCORDANCE WITH OBC
20 SF 18 -100 18 -136 -18318 -5848 -11548
50 SF 16 -90 16 -123 -15716 -5444 -10044
100 SF 16 -82 16 -113 -13616 -5139 -8939
23 3
2 2
23 3
45 5
5 4 a a a a h z h
2a 2a
WALL ELEVATION
ROOF PLAN
2a2a a: END ZONE WIDTH, IN FEET = 10 PERCENT OF BUILDINGS LEAST HORIZONTAL DIMENSION OR 0.4h, WHICHEVER IS SMALLER, BUT NOT LESS THAN EITHER 4% OF LEAST HORIZONTAL DIMENSION OR 3 FT.
h: MEAN ROOF HEIGHT, IN FEET, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR EAVE ANGLES < 10° z: HEIGHT ABOVE GROUND IN FEET
CASE A: WINDWARD PARAPET CASE B: LEEWARD PARAPET
S-100C
GENERAL
CONDITIONS
PLAN
NORTH
TRUE
NORTH
1111 Superior Avenue - Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
PROJ NO.
This item has been electronically signed and sealed by [LICENSEE NAME] using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
REVISIONS
SHEET NAME:
A B
E F
C D
KEY PLAN
ISSUE DATE:
ISSUED BY:
J-20242075
R
AY
M O
N D
J
AM
ES
M
IN
O R
P R
O
JE
C
TS
C
C
AN
O
PY
R
ES
TO
R
AT
IO
N
TA
M
PA
, F
L
100% CD SET
02/24/25
02/24/25
K.1
J.1
H.1
G.1
F.1
53.4
54.5
54.8 K.1
J.1
H.1
G.1
F.1
66.6
65.8
65.5
18'-6"±
8'-0"±
8'-0"±
'-0
'-0
'-0
8'- 0"±
8'- 0"±
'-6
8'- 0"±
8'- 0"±
32'-0"±
32'-0"±
32'-0"±
8'-0"±
8'-0"±
SCALE: 3/32" = 1'-0" 20'10'0 5'
SW QUAD D CANOPY FRAMING PLAN1 SCALE: 3/32" = 1'-0" 20'10'0 5'
SE QUAD C CANOPY FRAMING PLAN2
NOT TO SCALE
CANOPY CORROSION (TYPICAL)
P1
EX. TS10x4 EX. TS10x4
EX. TS10x4 EX. TS10x4
EX. TS10x4 EX. TS10x4
EX. TS10x4 EX. TS10x4
EX. TS10x4 EX. TS10x4
EX. TS10x4 EX. TS10x4
EX. TS10x4 EX. TS10x4
EX. TS10x4
EX. W
EX. W
EX. W
EX. W
EX. W
EX. W
EX. W
EX. W
EX. W
EX. W
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EQ.
EQ.
EQ.
EQ.
8'- 8"±
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4
EX. T
S10 x4EX. T S10 x4
EX. W24
EX. W24
EX. W24
EX. W24
EX. W24
EX. W24
EX. W24
EX. W24
EX. W24
EX. W24
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EX. TS10x4
EQ.
EQ.
EQ.
EQ.
8'-8"±
SPANSPAN
PEDESTRIAN RAMP
(TYP. 3 SIDES OF CANOPY)
STADIUM WALL
PEDESTRIAN RAMP
(TYP. 3 SIDES OF CANOPY)
STADIUM WALL
STADIUM WALL
STEEL FRAMING
UPPER CONCOURSE UPPER CONCOURSE
TYPICAL CORROSION
OF METAL DECK
METAL ROOF DECK
TO BE REMOVED
AND REPLACED
S-103C
QUAD C AND D
CANOPY PLANS
PLAN
NORTH
TRUE
NORTH
1111 Superior Avenue - Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
PROJ NO.
This item has been electronically signed and sealed by [LICENSEE NAME] using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
REVISIONS
SHEET NAME:
A B
E F
C D
KEY PLAN
ISSUE DATE:
ISSUED BY:
J-20242075
R
AY
M O
N D
J
AM
ES
M
IN
O R
P R
O
JE
C
TS
C
C
AN
O
PY
R
ES
TO
R
AT
IO
N
TA
M
PA
, F
L
100% CD SET
02/24/25
02/24/25
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
E
EXISTING CANOPY
EXIS
TI
NG P
LA
TFORM B
ELO
W
EXIS
TI
NG P
LA
TFORM B
ELO
W
EXIS
TI
NG P
LA
TFORM B
ELO
W
EXIS
TI
NG R
AMP B
ELO
W
EXIS
TI
NG P
LA
TFORM B
ELO
W
EXISTING PLATFORM BELOW
EXISTING CANOPY
EXIS
TI
NG C
ANOPY
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
21.8
21.5
20.4
K.1
J.1
H.1
G.1
F.1
21.8
21.5
K.1
J.1
H.1
G.1
F.1
E
EXISTING COLUMN, TYP.
NORTH
PLAN
NORTH
TRUE
1111 Superior Avenue - Suite 2100 | Cleveland, OH 44114
(216) 861-2020 www.osborn-eng.com
DRAWING NO.
Unless otherwise stated in Contract, The Osborn Engineering Company retains copyright ownership.
Instruments of Service may only be used for the purpose described in the Contract. The Osborn Engineering Company may grant specific usage rights under license, and/ or may transfer copyright ownership/ assignment in writing. Reproduction, re-use or re-distribution of Instruments of Service is prohibited.
PROJ NO.
This item has been electronically signed and sealed by [LICENSEE NAME] using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
REVISIONS
SHEET NAME:
A B
E F
C D
KEY PLAN
ISSUE DATE:
ISSUED BY:
R A
Y M
O N
D J
A M
E S
M
IN
O
R P
R O
J E
C T
S
C
C A
N O
P Y
R E
S T
O R
A T
IO
N
A-102C
OVERALL - EXTERIOR
CANOPY
J-20242075
T A
M P
A
F L
100% CD SET
02/24/25
02/24/25
1/8" = 1'-0"
CANOPY PLAN
1/8" = 1'-0"
CANOPY RCP
NOTE:
REFER TO STRUCTURAL FOR
WORK AT CANOPY AREA
RE-ROOFING NOTE:
EXISTING ROOF MEMBRANES AND SHEATHING TO BE REMOVED DOWN TO MTL DECK.
PARTIAL REMOVAL OF THE MTL DECK MAY BE REQUIRED, REFER TO STRUCTURAL
DRAWINGS FOR ADDITIONAL DETAIL AND SCOPE.
FOLLOWING THE REMOVAL OF THE EXISTING ROOF MEMBRANES AND SHEATHING, BUT
PRIOR TO REMOVAL OF ANY DECK, PLEASE CONTACT THE ARCHITECT OR STRUCTURAL
ENGINEER TO SCHEDULE A SITE VISIT TO VERIFY THE CONDITION OF THE MTL DECK IN
PREPARATION FOR THE NEW ROOFING AND SHEATHING.
ALL FOUR (4) CANOPY ROOFS TO RECEIVE NEW CARLISLE TPO SELF-ADHERED
ROOFING AND SUBSTRATE AND SHALL COMPLY WITH NOA NO: 19-0521.16 OR
APPROVED EQUAL. CONTRACTOR TO VERIFY SELECTED PRODUCTS COMPLY WITH THE
NOA, AND SHALL PROVIDE A SUBMITTAL TO THE ARCHITECT FOR APPROVAL.
CONTRACTOR TO VERIFY WITH MANUFACTURER THAT THE PRODUCTS, PRESSURES
AND NAILING PATTERNS MEET OR EXCEED THE REQUIREMENTS OF THE STRUCTURAL
DESIGN ENGINEER.
METAL FLASHINGS AND DRIP-EDGE SHALL BE RECONSTRUCTED IN ACCORDANCE WITH
APPROVED MANUFACTURER’S INSTALLATION INSTRUCTIONS OR RAS 111.
THE CONTRACTOR SHALL CONFIRM COMPATIBILITY OF ANY ROOF PAINT OR STICKER
SIGNAGE.
| Sheets |
| G-000A - COVER SHEET AND PROJECTION INFORMATION |
| G-000B - COVER SHEET AND PROJECTION INFORMATION |
| G-000C - COVER SHEET AND PROJECTION INFORMATION |