Bid_#2026-08_Drawings_Fire_Station_#3_HVAC_Replacement.pdf

PDF 3 MB Posted

Attached to
Fire Station #3 HVAC Replacement State and local contract opportunity
Solicitation number
2026-08
Issued by
Mclean County, Illinois

About this file

These construction documents are for the City of Bloomington Fire Station #3 HVAC Replacement project located at 2301 E. Empire Street in Bloomington, Illinois. The comprehensive set of architectural, mechanical, and electrical drawings detail a complete HVAC system replacement, including demolition of existing mechanical systems and installation of new variable refrigerant flow (VRF) equipment, energy recovery ventilation, and associated electrical infrastructure. The drawings are dated July 3, 2025, and are prepared by Dewberry Architects and Engineers, with the project number 50185817.

The project involves replacing the existing HVAC systems in the fire station, which includes removing old mechanical equipment, installing new fan coil units, condensing units, an energy recovery ventilator, and a dedicated outdoor air system. The electrical scope includes modifications to existing electrical panels, installing new circuit breakers, and providing power to new mechanical equipment. The drawings specify equipment from manufacturers like LG for VRF systems and include detailed specifications for mechanical and electrical components. The project appears to be fully documented with demolition plans, new work plans, mechanical and electrical schedules, control diagrams, and technical details to support a comprehensive HVAC system replacement.

View the file

Other files for this state and local contract opportunity

Other files attached to Fire Station #3 HVAC Replacement, newest first.
File Type Posted
Fire_Station_#3_HVAC_Replacement.pdf PDF
Bid_#2026-08_General_Project_Specs_Fire_Station_#3_HVAC_Replacement.pdf PDF
Bid_#2026-08_Specifications_Fire_Station_#3_HVAC_Replacement.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPROVED BY

CHECKED BY

A

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

SEAL

REVISIONS

23456

B

C

D

E

F Dewberry Engineers Inc..

401 SW Water Street Suite 701 Peoria IL 61602

309.282.8000 Phone

IL DESIGN FIRM #184.005007

T0.01

COVER SHEET

07/03/25

50185817

FI

R

E

ST

AT

IO

N

- H

VA

C

R

EP

LA

C

EM

EN

T

C ity o f B lo om in gt on

Is su ed fo r B id di ng

E . E

M

PI

R E

ST

R

EE

T

BL

O

O M

IN

G

TO

N

, I L

No. Description Date

CONTACTS

SITE INFORMATION

DRAWING INDEX CITY OF BLOOMINGTON

FIRE STATION #3 - HVAC

REPLACEMENT

BLOOMINGTON, IL 61704

CONSTRUCTION DOCUMENTS

2301 E. EMPIRE STREET

LOCATION MAP

N O

R

TH

O R

IE

N

TE

D

T O

OWNER: CITY OF BLOOMINGTON

2301 E. EMPIRE STREET

BLOOMINGTON, IL 61704

Dewberry Architects, Inc.401 SW Water Street Suite 701 Peoria IL 61602

309.282.8000 Phone

IL DESIGN FIRM #184000358-001

SEAL

Date:7/8/25

EXP:11/30/2025

I LL I NO I S

062-061703

LICENSED

PROFESSIONAL

ENGINEER

OF

J.

M

LEAH

CI S

McTAV

I H

EXP: 11-30-2025

DATE: 07-03-2025

GENERAL NOTES

1. GENERAL NOTES APPLY TO ALL SHEETS.

2. DO NOT SCALE DRAWINGS, REPORT ANY DISCREPANCIES TO THE ARCHITECT IN

WRITING.

1. VISIT SITE AND VERIFY EXISTING CONDITIONS PRIOR TO BID SUBMISSION.

DISCREPANCIES BETWEEN CONSTRUCTION INDICATED ON DRAWINGS AND

ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO ARCHITECT’S ATTENTION

IMMEDIATELY IN WRITING.

2. DEMOLISHED ITEMS NOT INDICATED TO BE “DELIVERED TO OWNER” OR “TO BE

RELOCATED” SHALL BE REMOVED FROM SITE AS SOON AS POSSIBLE UNLESS THEY

ARE TO BE USED FOR REQUIRED PATCHING AND INFILLING OF EXISTING

CONSTRUCTION THAT IS TO REMAIN. NO OTHER DEMOLISHED ITEMS SHALL BE

STORED ON SITE.

3. DEMOLISHED ITEMS NOTED AS “DELIVER TO OWNER” OR “TO BE RELOCATED”

SHALL BE REMOVED OR DISASSEMBLED IN SUCH A MANNER THAT WILL NOT

DAMAGE THE ITEM AND PREVENT IT FROM BEING RELOCATED. REPAIR OR

REPLACE SUCH ITEMS, IF DAMAGED. NOTIFY OWNER’S REPRESENTATIVE

IMMEDIATELY IF DAMAGE HAS OCCURRED, AND SUBMIT A REPAIR SOLUTION TO

ARCHITECT FOR REVIEW.

4. TEMPORARILY STORE ITEMS INDICATED AS “DELIVER TO THE OWNER” IN ONSITE

LOCATION, DESIGNATED BY THE OWNER. OWNER SHALL MOVE ITEM(S), AS

NECESSARY, TO NOT HINDER OR DELAY PERFORMANCE OF WORK IN AREA.

5. TEMPORARILY STORE ITEMS INDICATED AS “TO BE RELOCATED” IN LOCATION

ONSITE AND PROTECT ITEMS FROM DAMAGE PRIOR TO INSTALLATION IN NEW

LOCATION.

6. ITEMS INDICATED “TO REMAIN” THAT ARE DAMAGED DURING THE PERFORMANCE

OF THE DEMOLITION WORK. SUCH DAMAGE SHALL BE REPORTED TO OWNER’S

REPRESENTATIVE IMMEDIATELY, AND SUBMIT A REPAIR SOLUTION TO ARCHITECT

FOR REVIEW.

7. COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTION WORK IN EACH AREA

OF DEMOLITION. EXISTING CONSTRUCTION IN AREAS ADJACENT TO DEMOLITION

WORK SHALL BE PATCHED AND REPAIRED TO MATCH ORIGINAL EXISTING

CONDITION AS REQUIRED TO PROVIDE FOR NEW CONSTRUCTION WORK IN AREA

OF DEMOLITION.

8. ITEMS INDICATED TO BE REMOVED BY OWNER SHALL BE COMPLETED PRIOR TO

COMMENCEMENT OF WORK.

9. AT LOCATIONS WHERE A PORTION OF EXISTING CONSTRUCTION IS TO BE

REMOVED AND PREPARED FOR NEW INFILL CONSTRUCTION, OR AN OPENING IN A

WALL, ROOF, OR FLOOR IS CREATED BY DEMOLITION WORK, CONSTRUCT INFILL

WITH SAME MATERIALS AND METHOD OF CONSTRUCTION AS EXISTING ADJACENT

CONSTRUCTION, UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL DRAWINGS

FOR INFILL CONSTRUCTION. INFILL CONSTRUCTION SHALL SMOOTHLY BUTT

ADJACENT SURFACES AND MATCH THE FINISH, U.N.O.

10. AT LOCATIONS WHERE AN ITEM IS TO BE REMOVED FROM A SURFACE THAT IS TO

REMAIN, PATCH AND REPAIR EXISTING SURFACE TO MATCH EXISTING ADJACENT

SURFACE, UNLESS INDICATED OTHERWISE.

11. EXISTING ITEMS ANCHORED TO CONSTRUCTION THAT IS INDICATED TO BE

DEMOLISHED SHALL BE CONSIDERED A PART OF DEMOLISHED CONSTRUCTION

AND SHALL BE DEMOLISHED WITH THE INDICATED CONSTRUCTION, UNLESS

NOTED OTHERWISE.

12. CONSTRUCT TEMPORARY DUST PARTITIONS TO CONTAIN DEMOLITION WORK AND

PREVENT CONSTRUCTION DUST FROM ENTERING ADJACENT EXISTING

CONSTRUCTION. SUBMIT LOCATIONS OF THESE PARTITIONS FOR APPROVAL BY

OWNER’S REPRESENTATIVE. PARTITION LOCATIONS SHALL NOT IMPEDE OR

HINDER EMERGENCY EGRESS FROM BUILDING. REFER TO SPECIFICATIONS FOR

CONSTRUCTION OF DUST PARTITIONS.

13. IF EXISTING CONSTRUCTION IS REVEALED NOT CONSTRUCTED OR FINISHED IN A

MANNER THAT MATCHES ADJACENT SURFACES, PATCH AREA AS NECESSARY

WITH APPROPRIATE MATERIALS AND METHODS OF CONSTRUCTION TO MATCH

EXISTING ADJACENT FINISH, OR PREPARE SURFACE FOR INSTALLATION OF NEW

FINISH. CONTACT OWNER’S REPRESENTATIVE AS SOON AS POSSIBLE SO THAT

CONCEALED CONSTRUCTION MAY BE IDENTIFIED AND SCOPE OF POSSIBLE

ADDITIONAL WORK DETERMINED.

14. WHEN EXISTING SURFACE IS INDICATED TO BE “PATCHED AND REPAIRED” OR

“PREPARED” TO RECEIVE NEW FINISH MATERIAL, PROVIDE A CONSTRUCTION

SURFACE THAT IS CAPABLE OF RECEIVING NEW FINISH MATERIAL.

15. WHEN THE TERM ‘ENTIRETY’ IS DIRECTED TO A SPECIFIC ITEM OR ASSEMBLY,

DEMOLISH AND REMOVE IDENTIFIED ITEM AND ASSOCIATED CONSTRUCTION

PERTINENT TO THE ITEM, INCLUDING, BUT NOT LIMITED TO UNDERGROUND AND

CONCEALED CONSTRUCTION, SUCH AS FOOTINGS AND FOUNDATIONS, SEWER,

PLUMBING, AND ELECTRICAL WORK. THIS DEMOLITION WORK SHALL BE

COORDINATED WITH THE CIVIL, STRUCTURAL, PLUMBING, MECHANICAL,

ELECTRICAL, AND TECHNOLOGY DRAWINGS.

16. REMOVE PORTION OF EXISTING GYP BD. CEILING AS REQUIRED TO COMPLETE

MECHANICAL AND ELECTRICAL WORK ABOVE CEILING. PATCH AND REPAIR WITH

LIKE CONSTRUCTION.

DEMOLITION PLAN GENERAL NOTES

1. SITE WORK SHOWN FOR REFERANCE ONLY, REFER TO LANDSCAPE AND CIVIL

DRAWINGS FOR MORE INFORMATION.

2. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL INFORMATION ON MECHANICAL,

ELECTRICAL, AND PLUMBING WORK.

ANNOTATION PLAN GENERAL NOTES

1. REFLECTED CEILING PLAN GENERAL NOTES APPLY TO ALL REFLECTED CEILING

PLAN SHEETS.

2. ELECTRICAL, MECHANICAL, AND TECHNOLOGY FIXTURES AND DEVICES ARE

SHOWN FOR REFERENCE AND TO COORDINATE PLACEMENT. REFER TO

ENGINEERING DRAWINGS FOR INFORMATION REGARDING TYPE AND OTHER

FIXTURE AND DEVICE INFORMATION.

3. ALL CEILING GRIDS/PANELS SHALL BE CENTERED IN EACH ROOM UNLESS NOTED

OTHERWISE. ESTABLISH PRE-INSTALLATION MEETING WITH ARCHITECT TO

REVIEW STARTING POINT OF CEILING GRID IN EACH AREA/ROOM.

4. GYPSUM CEILINGS & SOFFITS TO BE PAINTED, COLOR: PNT-X, U.N.O.

5. EXPOSED STRUCTURE, MECHANICAL, ELECTRICAL, AND FIRE PROTECTION

COMPONENTS (EXCEPT SPRINKLER HEADS) ARE TO BE PAINTED PNT-X, U.N.O.

6. IN ROOMS WITH EXPOSED CEILINGS, MOUNT LIGHT FIXTURES TO UNDERSIDE OF

STRUCTURE. OTHER MEP/FP ITEMS TO MAINTAIN A MINIMUM CLEARANCE OF 9'-0"

A.F.F.

7. CEILING HEIGHTS SHOWN ON REFLECTED CEILING PLANS ARE FROM FINISHED

FLOOR OF PLAN SHOWN.

8. SEE ELECTRICAL LIGHTING PLANS FOR EMERGENCY LIGHT FIXTURE LOCATIONS.

9. CONTRACTOR TO COORDINATE CEILING FIXTURE LOCATIONS WITH ABOVE-

CEILING WORK TO AVOID CONFLICTS.

10. ELECTRICAL, MECHANICAL, AND TECHNOLOGY FIXTURES AND DEVICES ARE

SHOWN FOR REFERENCE AND TO COORDINATE PLACEMENT. REFER TO

ENGINEERING DRAWINGS FOR INFORMATION REGARDING TYPE AND OTHER

FIXTURE AND DEVICE INFORMATION.

11. ALL SUSPENDED CEILING SYSTEMS SHALL BE SUPPORTED FROM STRUCTURE

ABOVE.

CEILING PLAN GENERAL NOTES

A101

SIM

APC-X

8' - 0"

A

X#XX 1HR

SF01

Area Name

150 SF

FIRST FLOOR

100' - 0"

ROOM NAME

A101

SIM

GB-01

Scale:

View Name 1/8" = 1'-0" 1/A101

A101

SIM

CALLOUT

BUILDING/WALL

SECTION

DETAIL SECTION

ROOM TAG

CEILING TAG

DOOR / BORROWED

LITE TAG

WINDOW TAG

WALL TAG

FURNITURE,

CASEWORK, &

EQUIPMENT TAG

REVISION TAG

KEYNOTE TAG00 00 00.A1

AREA TO BE

ENLARGED

SHEET REF.

PLAN / DETAIL REF.

SECTION REF.

SHEET REF.

DETAIL REF.

SHEET REF.

LEVEL LINE

AREA SQUARE

FOOTAGE

ROOM NUMBER

EXTERIOR

ELEVATION

INTERIOR

ELEVATION

ELEVATION REF.

SHEET REF.A101

A101

1 ELEVATION REF.

SHEET REF.

VIEW NAME

VIEW SCALE

VIEW DESIGNATION

VIEW REF/SHEET REF

WHERE VIEW IS REFERENCED

VIEW TITLE

AREA TAG

CEILING TYPE

CEILING HEIGHT

(ABOVE FINISH FLOOR)

LEVEL NAME

LEVEL ELEVATION

GRID LINE

NORTH INDICATOR

GRID NUMBER OR

LETTER

INDICATES PLAN NORTH

INDICATES TRUE NORTH

A101

SPOT ELEVATION

SYMBOL

ANNOTATION LEGEND

RECESSED LIGHT FIXTURE

PENDANT LIGHT FIXTURE

SUPPLY DIFFUSER

RETURN DIFFUSER

EXIT SIGN

S SPEAKER

A FIRE ALARM

HEAT DETECTOR

SMOKE DETECTOR

LINEAR SLOT DIFFUSER

SPRINKLER HEAD

EMERGENCY LIGHT

RECESSED LIGHT FIXTURE

SUSPENDED ACOUSTICAL PANEL CEILING (APC-#)

GYPSUM BOARD CEILING (GYP BD-#)

CEILING FAN

CEILING MOUNTED PROJECTOR

CEILING MOUNTED MOTORIZED PROJECTION SCREEN

ROLLER SHADE

SUSPENDED OPEN GRID CEILING SYSTEM

DROP IN RESIN PANEL ON SUSPENDED OPEN GRID

CEILING SYSTEM

SURFACE MOUNTED LIGHT FIXTURE

STRIP LIGHT FIXTURE

TRACK LIGHTING

CONTROL JOINTCJ

PLASTER CEILING (PLAS-#)

HORN/STROBE DEVICE

EXHAUST AIR DEVICE

OCCUPANCY SENSOR

CEILING ACCESS PANEL (AP-#)

SEE PLAN FOR TYPE

SUSPENDED WOOD PANEL GRILLE DOWELED

CEILING SYSTEM (WD-#)

WOOD PANEL CEILING SYSTEM (WD-#)

FAUX WOOD PANELS (WD-#)

DAYLIGHTING SENSOR

s SPEAKER/STROBE

STROBE

ES EXPOSED STRUCTURE

NOTE: FOR MEPFP DEVICES, REFER TO MEPFP DRAWINGS.

APC-X

8' - 0"

CEILING TYPE

CEILING HEIGHT

CEILING LEGEND

DRAFTING LEGEND

NEW WALL

EXISTING WALL

EXISTING WALL TO BE DEMOLISHED

NEW DOOR

EXISTING DOOR

EXISTING DOOR TO BE DEMOLISHED

CMU (CONCRETE MASONRY UNIT)

CONCRETE

GYPSUM BOARD

PLASTER

RIGID INSULATION

MATERIAL LEGEND

A

54321

B

C

D

E

F

SCALE

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

REVISIONS

SEAL

KEY PLAN

Dewberry Architects Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000

IL DESIGN FIRM #184000358-0001

Dewberry Engineers Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602 309.282.8000

IL DESIGN FIRM #184.005007

/3

/2

:4

:2

A M

GENERAL NOTES

DEW

PHT

PHT

7/3/25

50185817

F

IR

E S

T A

T

IO

N

H V

A C

R E

P L A

C E

M E

N T

C it y o f B lo o m in g to n

Is s u e d f o r

B id d in g

E

E M

P

IR

E S

T R

E E

T

B L O

O M

IN

G

T O

N

IL

A-001

AB ANCHOR BOLT

ACST ACOUSTIC(AL)

ADDL ADDITIONAL

ADDN ADDITION

ADH ADHESIVE

ADJ ADJACENT, ADJOINING,

ADJUSTABLE

AED AUTOMATED EXTERNAL

DEFIBRILLATOR

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ALUM ALUMINUM

ANCH ANCHOR

ANOD ANODIZE(D)

AP ACCESS PANEL

APC ACOUSTICAL PANEL CEILING

APPROX APPROXIMATE

ASPH ASPHALT

AUTO AUTOMATIC

AVE AVERAGE

AWT ACOUSTICAL WALL TREATMENT

BAL SHT BALANCE SHEET

BC BRICK COLOR

BCS BABY CHANGING STATION

BD BOARD

BG BUMPER GUARD

BITUM BITUMINOUS

BLDG BUILDING

BLKG BLOCKING (WOOD)

BOT BOTTOM

BRDG BRIDGING

BRG BEARING

BRK PV BRICK PAVERS

BRKT BRACKET

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT UP ROOFING

CAB CABINET

CB CHALKBOARD

CC CUBICLE CURTAIN

CCT CUBICLE CURTAIN TRACK

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CFMF COLD-FORMED METAL FRAMING

CG CORNER GUARD

CH COAT HOOK

CIP CONC CAST-IN-PLACE CONCRETE

CJ CONTROL JOING, CONSTRUCTION

JOINT

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

CO CLEAN OUT, CASED OPENING

COL COLUMN

COMB COMBINATION, COMBINED

COMP COMPRESSIBLE

COMPT COMPARTMENT

CONC CONCRETE

CONC CTG CONCRETE COATING

COND CONDITION

CONT CONTINUOUS

CONTR CONTRACTOR

CORR CORRIDOR

CPRS COMPRESSIBLE

CPT CARPET

CR CLOSET ROD

CRL CRASH RAIL

CRS COLD-ROLLED STEEL

CTR CENTER(S)

CUH CABINET UNIT HEATER

CUV CABINET UNIT VENTILATOR

CW CURTAINWALL

D DEEP, DEPTH, PENNY NAIL

DC DISPLAY CASE

DET DETAIL

DETN DETENTION

DF DRINKING FOUNTAIN

DIA DIAMETER

DIM DIMENSION

DN DOWN

DP DECORATIVE PANEL

DR DOOR

DS DOWNSPOUT

DWG DRAWING(S)

EHD ELECTRIC HAND DRYER

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EMBED EMBEDMENT

EMER EMERGENCY

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EQ EQUAL

EQUIP EQUIPMENT

ES EXPOSED STRUCTURE

ETR EXISTING TO REMAIN

EW EACH WAY

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

FAB FABRIC

FD FLOOR DRAIN

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISH FLOOR

FHC FIRE HOSE CABINET

FIN FINISH

FLASH FLASHING

FLP FLOOR PATTERN

FLR FLOOR

FRP FIBER REINFORCED PLASTIC

FTG FOOTING

FURG C FURRING CHANNEL

FURN FURNACE

FWC FABRIC WALLCOVERING

GA GAGE, GAUGE

GALV GALVANIZED

GB GRAB BAR

GFRC GLASS-FIBER REINFORCED

CONCRETE

GL GLASS

GL BLK GLASS BLOCK

GLZ CMU GLAZED CONCRETE MASONRY UNIT

GRFG GLASS-FIBER REINFORCED GYPSUM

GT GROUT

GWH GAS FIRED WATER HEATER

GYP BD GYPSUM WALL BOARD

H HIGH, HATCH (ROOF)

HB HOSE BIB

HDNR HARDENER

HDW HARDWARE

HDWD HARDWOOD

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HANDRAIL

HT HEIGHT

HTG HEATING

HVAC HEATING, VENTILATING, AND AIR

CONDITIONING

ID INSIDE DIAMETER, INSIDE

DIMENSION

IF INSIDE FACE

INCL INCLUDED

INSUL INSULATION

INT INTERIOR

INV INVERT

JT JOINT

KD KNOCKED DOWN

KOP KNOCK OUT PANEL

L LONG, ANGLE

LAM LAMINATE(D)

LAV LAVATORY

LH LEFT HAND

LINO LINOLEUM

LKR LOCKER

LL LIVE LOAD, LOW LEVEL

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LT LIGHT

LVL LEVEL

LVR LOUVER

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MB MARKERBOARD

MBH MOB/BROOM HOLDER

MECH MECHANICAL

MED MEDIUM

MEZZ MEZZANINE

MFR MANUFACTURER

MH MANHOLE

MI MIRROR

MIN MINIMUM, MINUTE

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODEL, MODULE, MODULAR

MSB MOP SERVICE BASIN

MT MOUNT

MTL METAL

NDU NEEDLE DISPOSAL UNIT

NIC NOT IN CONTRACT, NOISE ISOLATION

CLASS

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER, OUTSIDE

DIMENSION

OF OUTSIDE FACE

OFCI OWNER FURNISHED CONTRACTOR

INSTALLED

OFD OVERFLOW DRAIN

OFOI OWNER FURNISHED OWNER

INSTALLED

OH OVERHEAD

OH DR OVERHEAD DOOR

OP OPERABLE PARTITION

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OS OVERFLOW SCUPPER

PC PORTLAND CEMENT, POINT

OF CURVE, POLYCARBONATE

PCC PRECAST CONCRETE

PERIM PERIMETER

PJ PROJECTOR

PL PLATE, PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLYWD PLYWOOD

PS PROJECTION SCREEN

PSF POUNDS PER SQUARE FOOT

PT PAINT

PTD PAPER TOWEL DISPENSER

PTDR PAPER TOWEL DISPENSER &

RECEPTACLE

PTN PARTITION

PTR PAPER TOWEL RECEPTACLE

PVC POLYVINYL CHLORIDE

PVG PAVING

R RISER, RADIUS, THERMAL

RESISTANCE (R-VALUE)

RB RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN, ROAD

REF REFERENCE, REFRIGERATOR

REINF REINFORCE

REQD REQUIRED

RF RESILIENT FLOORING

RFG ROOFING

RFM REMOVABLE FLOOR MAT

RH RIGHT HAND

RO ROUGH OPENING

RSF RESINOUS FLOORING

RST REINFORCING STEEL

RTF RESILIENT TILE FLOORING

RV ROOF VENT, ROOF VENTILATOR

SC SEALED CONCRETE

SCHED SCHEDULE

SCR SHOWER CURTAIN ROD

SCWD SOLID CORE WOOD DOOR

SD SOAD DISPENSER

SECT SECTION

SF STOREFRONT

SH SHINGLES, SINGLE HUNG (WINDOW)

SHT SHEET

SHTHG SHEATHING

SHV SHELVING

SLNT SEALANT

SND SANITARY NAPKIN DISPENSER

SNDU SANITARY NAPKIN DISPOSAL UNIT

SOG SLAB ON GRADE

SPCG SPACING

SPEC SPECIFICATION

SPKR SPEAKER

SQ SQUARE

SS SERVICE SINK , SOLID SURFACING

SST STAINLESS STEEL, SHOWER SEAT

STD STANDARD

STL STEEL

STL JST STEEL JOIST

STL LNTL STEEL LINTEL

STL PL STEEL PLATE

STL RF DK STEEL ROOF DECK

STL TR STEEL TRUSS

STN STAIN

STRUCT STRUCTURAL

SUSP SUSPEND

SV SHEET VINYL

SWP SHEET WALL PROTECTION

SYMM SYMMETRICAL

SYNTH SYNTHETIC

T TILE, TREAD

T&G TONGUE AND GROOVE

T/S TUB/SHOWER

TB TOWEL BAR, TACKBOARD

TC TOILET COMPARTMENT

TD TRENCH DRAIN

TER TERRAZZO

THK THICK

TOB TOP OF BEAM

TOC TOP OF CONCRETE, TOP OF CURB

TOF TOP OF FOOTING

TOM TOP OF MASONRY

TOS TOP OF SLAB, TOP OF STEEL

TOW TOP OF WALL

TPH TOILET PAPER HOLDER

TR TOWEL RACK

TS TUBE STEEL, TRANSITION STRIP

UNO UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VIF VERIFY IN FIELD

VWC VINYL WALL COVERING

W WIDE, WEST

WC WALL COVERING

WD WOOD, WOOD DOOR

WDW WINDOW

WP WALL PATTERN, WATERPROOFING

WT WEIGHT, WINDOW TREATMENT

WWF WELDED WIRE FABRIC

STANDARD ABBREVIATIONS

NO. DESCRIPTION DATE

A A

B B

C

C

D

D

E

E

F

F

024119.01024119.01

024119.01024119.01024119.01024119.01

024119.01024119.01

024119.01024119.01

024119.01024119.01

EXIST.

APPARATUS

BAY

EXIST.

ALARM

EXIST. VEST.

EXIST.

OFFICE

EXIST. REC /

DINING

EXIST.

KITCHEN

EXIST. HALL

EXIST. BATH

EXIST. STOR.

EXIST.

LOCKER

EXIST.

DORMITORY

EXIST.

RUBBER

EXIST. STOR.

EXIST. STOR.

EXIST.

MECHANICAL

EXIST. COR.

024119.03

024119.04

024119.03024119.03

024119.03

024119.05

024119.05

024119.05

024119.05

024119.05

024119.05

024119.05

024119.05

024119.05

024119.05

A

54321

B

C

D

E

F

SCALE

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

REVISIONS

SEAL

KEY PLAN

Dewberry Architects Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000

IL DESIGN FIRM #184000358-0001

Dewberry Engineers Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602 309.282.8000

IL DESIGN FIRM #184.005007

/3

/2

:3

:3

A

M

FIRST FLOOR

DEMOLITION RCP

DEW

PHT

PHT

7/3/25

50185817

F

IR

E S

T A

T

IO

N

H V

A C

R E

P L A

C E

M E

N T

C it y o f B lo o m in g to n

Is s u e d f o r

B id d in g

E

E M

P

IR

E S

T R

E E

T

B L O

O M

IN

G

T O

N

IL

AD113

KEYNOTES PER SHEET

NOTE DESCRIPTION

024119.01 REMOVE EXISTING ACOUSTIC PANEL CEILING IN ITS ENTIRETY,

INCLUDING GRID, HANGERS, AND ACCESSORIES.

024119.03 REMOVE EXISTING CEILING FAN IN ITS ENTIRETY, SALVAGE AND

REINSTALL IN ORIGINAL LOCATION.

024119.04 REMOVE EXISTING DIVIDER CURTAIN TRACK IN ITS ENTIRETY.

SALVAGE AND REINSTALL IN ORIGINAL LOCATION.

024119.05 REMOVE PORTION OF EXISTING GYP. BD. CEILING AS REQUIRED FOR

INSTALLATION OF MECHANICAL SCOPE OF WORK. PATCH AND

REPAIR AS REQUIRED, PAINT EXTENTS OF CEILING TO EDGE. REFER

TO FINISH LIST.

Scale: 1/8" = 1'-0"

FIRST FLOOR DEMOLITION RCP

APC-1

10' - 0"

APC-1

10' - 0"

APC-1

10' - 0"

111112

ES

APC-1

10' - 0"

A

54321

B

C

D

E

F

SCALE

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

REVISIONS

SEAL

KEY PLAN

Dewberry Architects Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000

IL DESIGN FIRM #184000358-0001

Dewberry Engineers Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602 309.282.8000

IL DESIGN FIRM #184.005007

/3

/2

:3

:3

A

M

FIRST FLOOR

REFLECTED

CELIING PLAN

DEW

PHT

PHT

7/3/25

50185817

F

IR

E S

T A

T

IO

N

H V

A C

R E

P L A

C E

M E

N T

C it y o f B lo o m in g to n

Is s u e d f o r

B id d in g

E

E M

P

IR

E S

T R

E E

T

B L O

O M

IN

G

T O

N

IL

A-113 Scale: 1/8" = 1'-0"

FIRST FLOOR REFLECTED CEILING PLAN

FINISH LIST

FINISH COMMENTS

CEILING FINISHES

ACOUSTIC CEILING TILE (ACT)

ACT-1 USG MARS HEALTHCARE ACOUSTICAL PANELS - SLT. USG DONN

BRAND DX/DXL ACOUSTICAL SUSPENSION SYSTEM.

PAINT (PNT)

PNT-1 SHERWIN WILLIAMS; SW7007 CEILING BRIGHT WHITE.

F

TS

FLOW SWITCH

HOSE END DRAIN VALVEHED

TEMPERATURE SENSOR

PRESSURE GAUGE

MANUAL DAMPER

MECHANICAL SYMBOLS

FIRE DAMPER

HUMIDISTAT

SYMBOL DESCRIPTION

H

GAS COCK

GAS PRESSURE REGULATING VALVE

CO2

CARBON MONOXIDE SENSOR

T THERMOSTAT/TEMPERATURE SENSOR

MOTOR OPERATED DAMPERM

DUCTWORK SYMBOLSPIPING DESCRIPTION

X" CD

CONDENSATE DRAIN

CHILLED WATER RETURN

CHILLED WATER SUPPLY

NATURAL GAS

HEATING WATER RETURN

HEATING WATER SUPPLY

SMOKE DAMPER

FD

SD

REFRIGERANT PIPES (SUCTION/LIQUID)

X = SECTION DETAIL NUMBER

XX = SHEET REFERENCE

X

XX

X = CALLOUT DETAIL NUMBER

XX = SHEET REFERENCE

X

XX

GENERAL

CONNECT TO EXISTING

DIRECTION OF AIR FLOW

VENTURI FLOW METER

BUTTERFLY VALVE

BACKFLOW PREVENTER

1/8" PIPE SLOPE AS NOTED

PRESSURE REGULATING VALVE

PIPE REDUCER OR INCREASER

CONTROL VALVE (3-WAY)

MECHANICAL SYMBOLS

DIRECTION OF FLOW

GATE VALVE

BALANCING VALVE

GLOBE VALVE

Y-STRAINER

PIPE CAP OR PLUG

CHECK VALVE

UNION

PIPE CONTINUES

SYMBOL DESCRIPTION

CONTROL VALVE (2-WAY)

ELBOW UP

ELBOW DOWN

TOP TAKE-OFF

BOTTOM TAKE-OFF

BALL VALVE

BFP

SUPPLY AIR DEVICE

EXHAUST AIR DEVICE

RETURN AIR DEVICE

EQUIPMENT TAG

XXX = TYPE X = NUMBER

(SEE SCHEDULE)

XXX

X

AIR DEVICE TAG

X = TAG XX = CFM

(SEE SCHEDULE)

X

XX

AIR DEVICE SYMBOLS

WALL AIR DEVICE (SUPPLY/RETURN)

SA

TO SPACE

SQUARE ELBOW (WITH TURNING VANES)

RADIUS ELBOW (1.5 DIA. UNLESS NOTED)

SQUARE TO SQUARE/ROUND DUCT 90 DEGREE TAKEOFF

ROUND TO ROUND DUCT 90 DEGREE TAKEOFF

TRANSITION

RECTANGULAR ELBOW UP (SUPPLY)

RECTANGULAR ELBOW DN (SUPPLY)

ROUND ELBOW UP (SUPPLY)

ROUND ELBOW DN (SUPPLY)

VAV BOX (SIZE MAY VARY)

45 DEGREE DUCT TRANSITION UP/DN

FLEX DUCT

X" CHWR

X" CHWS

X" NG

X" HWR

X" HWS

X" RF

LINEAR SLOT CEILING AIR DEVICE

LINEAR SLOT WALL AIR DEVICE

CO

CARBON DIOXIDE SENSOR

GENERAL NOTES

1. NOT ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS DRAWING MAY

BE USED FOR THIS PROJECT.

2. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS NECESSARY

FOR THE INSTALLATION OF THE WORK AND FOR ALL CERTIFICATES OF

INSPECTION AND APPROVAL REQUIRED BY THE AUTHORITIES HAVING

JURISDICTION. NO WORK IS TO PROCEED WITHOUT BUILDING

DEPARTMENT PERMIT.

3. THE CONTRACTOR SHALL MAINTAIN SUCH INSURANCE AS WILL PROTECT

HIMSELF AND/OR THE OWNER FROM DIRECT, ASSUMED AND CONTINGENT

LIABILITY FROM CLAIMS FOR DAMAGES, FOR PERSONAL INJURIES,

INCLUDING DEATH, AND/OR DAMAGE TO PROPERTY, WHICH MAY ARISE

FROM OPERATION UNDER HIS CONTRACT WHETHER SUCH OPERATIONS

BE BY HIMSELF, OR ANY SUB-CONTRACTOR, OR ANYONE DIRECTLY

EMPLOYED BY EITHER OF THEM.

4. THE MECHANICAL CONTRACTOR SHALL BE FAMILIAR WITH ALL CONTRACT

DOCUMENTS FOR ALL TRADES AND COORDINATE WITH OTHER

CONTRACTORS.

5. WHEN CONFLICTS OCCUR IN THE SPECIFICATIONS OR ON THE DRAWINGS

OR BETWEEN EITHER, PROVIDE THE ITEM OF GREATER QUANTITY OR

HIGHER COST, UNLESS WRITTEN INSTRUCTIONS FROM THE OWNER OR

ENGINEER ARE PROVIDED TO RESOLVE THE SPECIFIC CONFLICT.

6. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION, AS

SPECIFIED, ARE PART OF THIS CONTRACT.

7. THE MECHANICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL

AND PLUMBING REQUIREMENTS WITH THE ELECTRICAL AND PLUMBING

CONTRACTORS.

8. MECHANICAL WORK SHALL BE IN ACCORDANCE WITH APPLICABLE

FEDERAL, STATE AND LOCAL CODES, AND STANDARDS.

9. THE CONTRACTOR WILL BE HELD TO HAVE VISITED THE PREMISES PRIOR

TO SUBMITTING HIS BID AN TO HAVE THOROUGHLY EXAMINED ALL

EXISTING CONDITIONS INCLUDING ENTRANCE AND EXIT FACILITIES,

HOURS PERMITTED BY THE BUILDING FOR THE TRANSPORTATION OF

EQUIPMENT AND MATERIALS, AS WELL AS THE CONTRACTOR SATISFIED

HIMSELF AS TO THE CONDITIONS AND WORK SHOWN ON THE PLANS OF

THE ARCHITECT WHICH WOULD IN ANY MANNER AFFECT THE WORK

UNDER HIS CONTRACT AND ITS COMPLETION DATE. NO LATER CLAIM FOR

EXTRA COMPENSATION FOR WORK WHICH COULD HAVE BEEN FORESEEN

BY SUCH VISIT OR INVESTIGATION SHALL BE RECOGNIZED. SUBMISSION

OF A BID SHALL BE CONSTRUED AS EVIDENCE THAT SUCH A VISIT HAD

OCCURRED. THE CONTRACTOR SHALL EXAMINE ALL EXISTING

STRUCTURAL CONDITIONS, TAKE ALL NECESSARY MEASUREMENTS FOR

HIS WORK AT THE SITE AND SHALL VERIFY ALL DIMENSIONS GIVEN ON THE

DRAWINGS OF THE WORK AND THE REFERENCE DRAWINGS.

10. THE SCOPE OF WORK SHALL INCLUDE PROVIDING HEATING, VENTILATING

AND AIR CONDITIONING FOR THE PREMISES IN ACCORDANCE WITH THESE

DRAWINGS AND SPECIFICATIONS. DRAWINGS AND SPECIFICATIONS

INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN

THIS CONTRACT, WORK SHALL CONSIST OF FURNISHING ALL ASPECTS

NECESSARY FOR AND INCIDENTAL TO THE EXECUTION AND COMPLETION

OF FULLY FUNCTIONAL HVAC SYSTEMS INDICATED ON THE DRAWINGS

AND SPECIFIED HEREIN.

11. MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE

MANUFACTURER'S RECOMMENDATIONS.

12. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. MECHANICAL

DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE BASED ON ONE

MANUFACTURER'S EQUIPMENT. THEY ARE NOT INTENDED TO SHOW

EVERY ITEM IN ITS EXACT LOCATION, THE EXACT DIMENSIONS, OR ALL

THE DETAILS OF THE EQUIPMENT OR DEVICES. THE CONTRACTOR SHALL

VERIFY THE ACTUAL DIMENSIONS OF THE EQUIPMENT PROPOSED TO

ENSURE THAT THE EQUIPMENT WILL FIT IN THE AVAILABLE SPACE; FINAL

ROUTING OF DUCTWORK, PIPING AND EQUIPMENT LOCATIONS SHALL BE

DETERMINED IN THE FIELD. ADDITIONAL OFFSETS, ELBOWS, ETC., SHALL

BE PROVIDED AND INSTALLED WITHOUT ADDITIONAL COST TO THE

OWNER.

13. IN ORDER TO DEFINE REQUIREMENTS FOR CAPACITY, QUALITY,

FUNCTION, SIZE, GAUGES AND GRADES, THESE MATERIAL

SPECIFICATIONS DESIGNATE MANUFACTURERS, BRANDS, AND OTHER

PERTINENT DATA DESCRIBING PRODUCTS THAT CONFORM TO THIS

PROJECT'S REQUIREMENTS, MATERIALS OR PRODUCTS SPECIFIED BY

NAME OF MANUFACTURER, BRAND OR TRADE NAME OR CATALOG

REFERENCE SHALL BE THE BASIS OF THE BID AND FURNISHED UNDER

THIS CONTRACT. SHOULD THE CONTRACTOR WISH TO PROVIDE AN

ALTERNATE PIECE OF EQUIPMENT HE SHALL BEAR ALL BURDEN OF

RESPONSIBILITY GUARANTEEING SUBSTITUTE UNIT IS EQUAL IN ALL

ASPECTS OF PERFORMANCE, DIMENSIONS ETC. WHERE TWO OR MORE

MATERIALS OR PRODUCTS ARE NAMED, THE CHOICE OF THESE SHALL BE

OPTIONAL WITH THE BIDDER, THE BIDDER SHALL SUBMIT HIS BID BASED

ON THE MATERIAL AND PRODUCTS LISTED IN THIS SPECIFICATION.

14. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL

INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE MECHANICAL WORK

COMPLETE AND READY FOR OPERATION.

15. THE CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED AND

MATERIALS INSTALLED BY HIM TO BE FREE FROM INHERENT DEFECTS,

AND SHALL REPAIR OR REPLACE ANY DEFECTIVE MATERIALS OR

WORKMANSHIP, FREE OF COST TO OWNER, FOR A PERIOD OF ONE (1)

YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER. ANY DAMAGE OR

LOSS, EXCLUSIVE OF BUILDING CONTENTS DUE TO SUCH DEFECTS WILL

ALSO BE MADE GOOD AT CONTRACTOR'S EXPENSE. DEFECTS WILL BE

REMEDIED AND DAMAGES OR LOSSES WILL BE MADE GOOD WITHIN A

REASONABLE TIME, AS SPECIFIED IN NOTICE BY THE OWNER.

16. ANY LOSS OF, OR DAMAGE TO ANY EQUIPMENT, OR MATERIALS SUPPLIED

BY THE CONTRACTOR, OR BY OWNER FOR INSTALLATION SHALL BE THE

SOLE RESPONSIBILITY OF THIS CONTRACTOR, UNTIL SUCH TIME AS

COMPLETED JOB HAS BEEN APPROVED AND ACCEPTED BY THE OWNER. IF

LOSS, OR DAMAGE SHOULD OCCUR NO CLAIM MAY BE MADE AGAINST THE

OWNER, NOR SHALL COMPLETION DATES BE AFFECTED BY SUCH LOSS,

OR DAMAGE.

17. THE MECHANICAL CONTRACTOR SHALL FURNISH TO THE GENERAL

CONTRACTOR ALL INFORMATION REQUIRED FOR SETTING OF WALL, ROOF

AND PARTITION OPENINGS FOR MECHANICAL WORK.

18. ALL EXTERIOR OPENINGS TO BE PROPERLY CAULKED AND SEALED WITH A

SEALANT OF HIGH QUALITY AND LONG LIFE, TO PREVENT INFILTRATION OF

OUTSIDE AIR INTO CONDITIONED SPACE.

19. CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS OF THE

EQUIPMENT, DUCTWORK IN 3/8" SCALE, PIPING, TEMPERATURE CONTROLS

AND PROVIDE CUTS OF COMPONENTS TO BE FURNISHED BY HIM. ALL

ITEMS SHALL BE SUBMITTED THE ENGINEER FOR HIS APPROVAL. NO

WORK SHALL PROCEED WITHOUT APPROVED SHOP DRAWINGS.

20. CONTRACTOR SHALL FURNISH "AS BUILT" RECORD DRAWINGS AND

OPERATING AND MAINTENANCE INSTRUCTIONS AT THE COMPLETION OF

THE INSTALLATION. DRAWINGS SHALL SHOW:

A. ALL NEW ELECTRICAL AND MECHANICAL WORK INSTALLED

B. MODIFICATIONS AND ADDITIONS TO ORIGINAL DESIGN

C. DIMENSIONAL INFORMATION NECESSARY TO LOCATE BURIED OR

UNDERGROUND PIPING/UTILITIES

21. TEMPORARY WORK TO KEEP NORMAL BUILDING SERVICES IN OPERATION

SHALL BE PART OF THIS CONTRACT. COORDINATE WITH BUILDING

MANAGEMENT AND OBTAIN PERMISSION FOR ANY ALTERATIONS

AFFECTING BUILDING. COORDINATE ALL BUILDING SHUTDOWNS AND

RELOCATIONS OF EXISTING SYSTEMS WITH OWNER. DO NOT PROCEED

WITH WORK AFFECTING BUILDING SYSTEMS AND OPERATION WITHOUT

WRITTEN APPROVAL.

22. CONTRACTOR SHALL COORDINATE HIS WORK WITH ARCHITECT'S

DRAWINGS, LIGHTING, AND WORK OF ALL OTHER TRADES. CONTRACTOR

SHALL PROVIDE ADDITIONAL DUCTWORK TO MAINTAIN CEILING HEIGHTS

AND AVOID WORK OF OTHER TRADES AND EXISTING CONDITIONS, AS

PART OF HIS BASE BID.

23. FIELD OBSERVATION OF EXISTING SYSTEM AND CONDITIONS WAS

ATTAINED VIA LIMITED FIELD SURVEYS. ONLY SYSTEMS AND CONDITIONS

CLEARLY VISIBLE AT THE TIME OF SURVEY ARE SHOWN. CONTRACTOR

SHALL VERIFY EXACT LOCATION OF CONNECTION OF NEW WORK TO

EXISTING.

24. CONTRACTOR TO PROVIDE PRIME AND FINISH PAINTING AS REQUIRED.

25. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND/OR

DISPOSING OF ALL ITEMS THAT ARE NOT NECESSARY IN THE COMPLETION

OF THE PROJECT AND SHALL CLEAN THE AREA OF CONSTRUCTION AFTER

THE COMPLETION OF THE PROJECT.

26. WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME CARE

SHALL BE TAKEN TO PREVENT DAMAGE DURING THE REMOVAL AND

REINSTALLATION. WHERE DAMAGE OCCURS, THE EQUIPMENT SHALL BE

REPLACED OR REPAIRED TO THE SATISFACTION OF THE ARCHITECT, AT

NO ADDITIONAL COST TO THE OWNER.

27. PROVIDE COMPLETE ACCESS TO ALL NEW OR RELOCATED AIR HANDLING

UNITS, TERMINAL DEVICES, HEATING COILS, AND FANS AND NOTIFY

ENGINEER OF ANY CONFLICTS PRIOR TO INSTALLATION.

28. FIRE STATION #3 IS A CONTROLLED LOCATION. CONTRACTORS WORKING

WITHIN THE FACILITY WILL NEED TO SUBMIT APPLICATION AND BE

GRANTED SITE BADGES TO OPERATE WITHIN THE FACILITY BY THE

AIRPORT AUTHORITY.

GENERAL NOTES - MECHANICAL HVAC

1. MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE

MANUFACTURER'S RECOMMENDATIONS.

2. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS OF

DIFFUSERS, REGISTERS AND GRILLES.

3. VOLUME DAMPERS SHALL BE INSTALLED AT ALL LOW PRESSURE SUPPLY, RETURN

AND EXHAUST DUCTWORK BRANCH TAKE-OFFS.

4. FIRE DAMPERS AND ACCESS PANELS SHALL BE INSTALLED AT FIRE RATED

ASSEMBLIES AND FLOOR PENETRATIONS BY THE GC.

5. SUPPORTS FOR DUCT, FANS, VAV'S, ETC. SHALL BE DIRECTLY FROM BUILDING

STRUCTURE, SUSPENDING ANY OF THE ABOVE FROM ONE ANOTHER IS PROHIBITED.

6. MECHANICAL CONTRACTOR SHALL INSTALL DUCT-MOUNTED SMOKE DETECTORS IN

DUCT AND PROVIDE A 16x16 DUCT ACCESS DOOR FOR EACH. ELECTRICAL

CONTRACTOR WILL FURNISH AND WIRE DETECTORS.

7. THE BUILDING AUTOMATION SYSTEM (BAS) CONTRACTOR SHALL COORDINATE WALL

AND CEILING MOUNTED SENSOR LOCATIONS WITH THE ARCHITECTURAL PLANS. WALL

MOUNTED SENSORS SHALL BE INSTALLED 48" ABOVE FINISHED FLOOR UNLESS

OTHERWISE NOTED.

8. INSULATE THE BACKS OF ALL DIFFUSERS UNLESS NOTED OTHERWISE.

9. PROVIDE ALL NECESSARY DUCT TRANSITIONS FROM THE INDICATED DUCT SIZE TO

THE ACTUAL EQUIPMENT DUCT COLLAR SIZE.

10. EXHAUST AND SUPPLY FANS SHALL BE PROVIDED WITH FLEXIBLE DUCT CONNECTIONS

WHEN ATTACHED TO DUCTWORK.

11. INSTALL EACH FAN WITH THE FAN MOTOR AND DRIVE ORIENTED TO ALLOW ACCESS.

12. ALL DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE

BRAIDED COPPER GROUNDING STRIPS.

13. ALL DUCTWORK DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS. DUCTWORK

SIZES SHOWN DO NOT ACCOUNT FOR DUCTWORK LINER OR INSULATION WRAP

THICKNESS.

14. IN FINISHED AREAS, INSTALL ALL DUCTWORK AT THE MAXIMUM ELEVATION POSSIBLE.

PROVIDE ALL FITTINGS, TRANSITIONS AND MATERIALS REQUIRED TO ACHIEVE

MAXIMUM ELEVATION. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO THE

START OF WORK TO AVOID CONFLICTS. THIS EXCLUDES ALL DUCT NECESSARY TO

KEEP EQUIPMENT AND DAMPERS ACCESSIBLE FOR MAINTENANCE.

15. THE CONTROLS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING POWER TO

THE CONTROL PANELS. ELECTRICAL CONTRACTOR SHALL PROVIDE 120 VOLT CIRCUIT

TO JUNCTION BOX IN EACH MECHANICAL SPACE. THE CONTROLS CONTRACTOR

SHALL BE RESPONSIBLE FOR PULLING WIRING FROM JUNCTION BOX TO CONTROL

PANELS. ALL 120 VOLT WIRING SHALL BE INSTALLED IN ACCORDANCE WITH DIVISION

26.

16. TERMINAL UNITS SHALL ME MOUNTED WITHIN 8" AFC WHERE POSSIBLE.

17. ALL RETURN AIR OPENINGS INDICATED ON DRAWINGS ARE LOCATED ABOVE THE

CEILING UNLESS OTHERWISE NOTED. INSTALL ALL RETURN AIR OPENINGS SO THAT

THERE ARE NO OBSTRUCTIONS BLOCKING THE INDICATED RETURN AIR PATH FREE

AREA.

18. FLEXIBLE DUCTWORK SHALL NOT EXTEND THROUGH FULL HEIGHT PARTITIONS.

CONTRACTOR SHALL EXTEND RIGID ROUND DUCTWORK THROUGH FULL HEIGHT

PARTITIONS BEFORE CONNECTING FLEXIBLE DUCTWORK.

19. THE MAXIMUM LENGTH OF FLEXIBLE DUCTWORK SHALL NOT EXCEED 6'-0". WHERE A

LENGTH GREATER THAN 6'-0" OCCURS, CONTRACTOR SHALL EXTEND THE DUCTWORK

WITH EXTERNALLY INSULATED ROUND SHEET METAL OF THE SAME SIZE AS THE

FLEXIBLE DUCT.

20. THE CONTRACTOR SHALL SEAL ALL LEAKS IN NEW DUCTWORK AND EXISTING

DUCTWORK TO REMAIN. THE CONTRACTOR SHALL CAP AND SEAL ALL UNUSED TAPS

AND OPENINGS IN THE EXISTING DUCTWORK.

21. PROVIDE SPIN COLLAR BRANCH FITTINGS, CONSTRUCTED OF GALVANIZED STEEL,

WITH VOLUME DAMPER AT ALL NEW ROUND BRANCH TAPS SERVING ALL SUPPLY AND

EXHAUST AIR CEILING DIFFUSERS. WHERE THE DEPTH OF THE DUCTWORK WILL NOT

PERMIT A SPIN COLLAR FITTING, PROVIDE AN EQUIVALENT FLAT OVAL CONNECTION

WITH MANUAL VOLUME DAMPER AND AN OVAL TO ROUND TRANSITION FOR EACH

DIFFUSER TAP. REFER TO THE SQUARE CEILING DIFFUSER DETAIL FOR EQUIVALENT

FLAT OVAL SIZES. FLANGED AND GASKETED STYLE OF SPIN COLLAR FITTINGS IS NOT

ACCEPTABLE.

22. PROVIDE SCREWED ON ENGRAVED BLACK LAMICOLD SHEET NAMEPLATES FOR

EQUIPMENT, INSTRUMENTS, GAUGES, CONTROL SWITCHES ETC.

23. ALL AIR SYSTEMS SHALL BE BALANCED AND CERTIFIED READINGS SHALL BE

SUBMITTED FOR APPROVAL. THE CONTRACTOR SHALL ALLOW FOR A SECOND VISIT TO

REBALANCE THE SYSTEM TO PROVIDE AIR QUANTITIES INDICATED ON DRAWINGS AND

TO ADJUST AIR THROW ONCE SPACE IS OCCUPIED. THE WORK WILL NOT BE

CONSIDERED COMPLETE WITHOUT APPROVED BALANCING REPORT.

GENERAL NOTES - MECHANICAL PIPING

1. SUPPORTS FOR, PIPING SHALL BE DIRECTLY FROM BUILDING STRUCTURE, SUSPENDING

PIPING FROM ANOTHER ITEM IS PROHIBITED.

2. MINIMUM SIZE OF HOT WATER SUPPLY, HOT WATER RETURN AND CONDENSATE DRAIN

PIPING SHALL BE 3/4" UNLESS OTHERWISE NOTED.

3. PROVIDE 3/4" MANUAL AIR VENTS WITH BALL VALVES AT ALL HIGH POINTS AND ENDS OF

MAIN PIPE RUNS. PIPE TO FLOOR DRAIN IN MECHANICAL ROOMS OR JANITOR CLOSETS WITH

3/4" COPPER PIPING. ALTERNATE LOCATIONS MUST BE APPROVED BY ENGINEER.

4. ALL WATER SYSTEMS SHALL BE BALANCED AND CERTIFIED READINGS SHALL BE SUBMITTED

FOR APPROVAL. THE CONTRACTOR SHALL ALLOW FOR A SECOND VISIT TO REBALANCE THE

SYSTEM TO PROVIDE WATER QUANTITIES INDICATED ON DRAWINGS. THE WORK WILL NOT

BE CONSIDERED COMPLETE WITHOUT APPROVED BALANCING REPORT. HOT AND CHILLED

WATER SYSTEM SHALL BE BALANCED TO FLOW RATES INDICATED.

5. ISOLATION VALVES SHALL BE INSTALLED IN SUPPLY AND RETURN PIPING ON EACH FLOOR, AND IN BRANCH PIPING SERVING MORE THAN ONE PIECE OF EQUIPMENT.

6. NO BULLHEAD TEES IN PIPING SYSTEMS SHALL BE ALLOWED ON THIS PROJECT.

CONTRACTOR SHALL PROVIDED OFFSETS AS NECESSARY TO MEET THIS REQUIREMENT.

7. CONTRACTOR TO PROVIDE IDENTIFICATION OF PIPING WITH SIZE, PURPOSE AND DIRECTION

OF FLOW. APPLY ASME A13.1 COMPLYING MARKERS TO ALL PIPING WITH NAME OR SERVICE,

SPACE EVERY 20 FEET. COLORING OF ARROWS SHALL BE IN ACCORDANCE WITH AMERICAN

STANDARD ASSOCIATION (A.S.A.) REQUIREMENTS.

8. FURNISH AND INSTALL ON EACH VALVE A 2 INCH DIAMETER NUMBERED TAG, FURNISH AND

INSTALL TWO FRAME, GLASS COVERED VALVE CHARTS, LISTING EACH VALVE BY SYSTEM,

FUNCTION AND NUMBER, AS WELL AS ONE LINE FLOW SCHEMATIC.

9. WHEN INSTALLING VALVES, INSURE THE ABILITY TO ACTUATE THE VALVE HANDLE THROUGH

THE FULL RANGE OF OPERATION.

10. IN FINISHED AREAS, INSTALL ALL PIPING AT THE MAXIMUM ELEVATION POSSIBLE. PROVIDE

ALL FITTINGS, TRANSITIONS AND MATERIALS REQUIRED TO ACHIEVE MAXIMUM ELEVATION.

COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO THE START OF WORK TO AVOID

CONFLICTS. THIS EXCLUDES ALL PIPE NECESSARY TO KEEP EQUIPMENT AND VALVES

ACCESSIBLE FOR MAINTENANCE.

GENERAL NOTES - TEMPERATURE CONTROL

1. THE TEMPERATURE CONTROLS CONTRACTOR (TCC) SHALL BE FULLY RESPONSIBLE FOR

THE AUTOMATIC CONTROL, AS DEFINED BY THE SEQUENCE OF OPERATION, OF

EQUIPMENT DOCUMENTED ON THE TEMPERATURE CONTROLS DRAWINGS. THE TCC SHALL

PROVIDE ALL WIRING TO IMPLEMENT THE SEQUENCE OF CONTROL. WIRING SHALL

CONFORM TO THE DIVISION 26 SPECIFICATIONS.

2. UNLESS EXPLICITLY STATED IN THE EQUIPMENT SPECIFICATIONS, THE TCC SHALL

PROVIDE ALL THERMOSTATS AND/OR SPACE SENSORS REQUIRED FOR AUTOMATIC

CONTROL EQUIPMENT.

3. ALL THERMOSTATS AND/OR SPACE SENSORS SHALL BE OF THE SAME COLOR AND LOOK

SIMILAR IN NATURE UNLESS THE SEQUENCE OF OPERATION REQUIRES A SPECIAL OR

COMBINED FUNCTION OF THE DEVICE.

4. SUBMIT THERMOSTAT OR SENSOR COLOR/MATERIAL TO THE BUILDING ARCHITECT FOR

APPROVAL BEFORE DELIVERY OF THE EQUIPMENT TO THE JOB SITE.

5. UNLESS EXPLICITLY STATED IN THE EQUIPMENT SPECIFICATIONS, THE TCC SHALL

PROVIDE ALL HARDWARE AND SOFTWARE REQUIRED FOR AUTOMATIC CONTROL OF THE

EQUIPMENT.

6. THE TCC IS RESPONSIBLE TO OBTAIN AND THOROUGHLY REVIEW THE HVAC EQUIPMENT

SPECIFICATIONS AND SECTION 230900 (DIGITAL CONTROLS AND INSTRUMENTATION) TO

DETERMINE SCOPE OF WORK.

7. THE TCC IS RESPONSIBLE TO REVIEW ALL HVAC, PLUMBING, ELECTRICAL, AND FIRE

PROTECTION DRAWINGS TO DETERMINE SCOPE OF WORK.

8. THESE GENERAL NOTES SHALL SUPERSEDE ANY CONFLICTING INFORMATION FOUND IN

THE PROJECT DRAWINGS, SPECIFICATIONS, AND ADDENDA.

9. THE TCC SHALL BE RESPONSIBLE TO PROVIDE 120V POWER WIRING, CONDUIT AND

CIRCUIT BREAKERS TO EACH CONTROL PANEL AS REQUIRED. WIRING PROVIDED ON THE

PROJECT SHALL COMPLY WITH THE DIVISION 26 SPECIFICATIONS.

10. THE TCC SHALL PROVIDE ELECTRICAL POWER TO ALL VALVE AND DAMPER ACTUATORS

DESCRIBED IN THE SEQUENCE OF OPERATION OR SHOWN IN THE CONTROL SCHEMATIC.

11. THE TEMPERATURE CONTROLS SYSTEM SHALL MONITOR ALL FACTORY STATUS POINTS

AND ALARMS FROM THE EQUIPMENT MANUFACTURER'S CONTROL PANEL.

A

54321

B

C

D

E

F

SCALE

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

REVISIONS

SEAL

KEY PLAN

Dewberry Architects Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000

IL DESIGN FIRM #184000358-0001

Dewberry Engineers Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602 309.282.8000

IL DESIGN FIRM #184.005007

/8

/2

:2

:3

P M

MECHANICAL

SYMBOLS,

ABBREVIATIONS

& NOTES

JRF

PER

PER

7/3/25

50185817

F

IR

E S

T A

T

IO

N

H V

A C

R E

P L A

C E

M E

N T

C it y o f B lo o m in g to n

Is s u e d f o r

B id d in g

E

E M

P

IR

E S

T R

E E

T

B L O

O M

IN

G

T O

N

IL

M-001

ABBREVIATIONS - MECHANICAL

% PERCENT

(D) DEMOLISH

(E) EXISTING

(R) REMOVE

< LESS THAN

> GREATER THAN

AC AIR CONDITIONING

ACCU AIR COOLED CONDENSING UNIT

ADJ ADJUSTABLE

AF AIRFLOW

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AI ANALOG INPUT

AO ANALOG OUTPUT

ARCH ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATING, AND AIR-CONDITIONING

ENGINEERS

ATC AUTOMATIC TEMPERATURE CONTROL

B BOILER

B&G BELL & GOSSETT

BAS BUILDING AUTOMATION SYSTEM

BHP BRAKE HORSEPOWER

BI BINARY INPUT

BMS BUILDING MANAGEMENT SYSTEM

BO BINARY OUTPUT

BT BUFFER TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

CD CONDENSATE DRAIN

CDWP CONDENSER WATER PUMP

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHW CHILLED WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

CONN CONNECTION

CONT CONTROLS

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

Cv VALVE COEFFICIENT

CW CONDENSER WATER

CWFS CONDENSER WATER FILTRATION SYSTEM

CWP CHILLED WATER PUMP

DB DRY BULB

DBL DOUBLE

DE DISHWASHER EXHAUST

DEF DISHWASHER EXHAUST FAN

DEG DEGREE

DIA DIAMETER

DN DOWN

DOAU DEDICATED OUTDOOR AIR UNIT

DP DIFFERENTIAL PRESSURE (SENSOR)

DPP DUAL PUMP PACKAGE

DRE DRYER EXHAUST

DREF DRYER EXHAUST FAN

DTY DUTY

DWG DRAWING

DWH DOMESTIC WATER HEATER

DX DIRECT EXPANSION

E EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ECM ELECTRICALLY COMMUTATED MOTOR

EF EXHAUST FAN

EHC ELECTRIC HEATING COIL

ELEC ELECTRICAL

EMCS ENERGY MANAGEMENT CONTROL

SYSTEM

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETC ETCETERA

EUH ELECTRIC UNIT HEATER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER TEMPERATURE

EXR EXHAUST REGISTER

Ez ZONE AIR DISTRIBUTION EFFECTIVENESS

F DEGREES FAHRENHEIT

FD FIRE DAMPER OR FLOOR DRAIN

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FP FAN POWERED

FPM FEET PER MINUTE

FS FLOW SWITCH

FT FOOT/FEET

G NATURAL GAS

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GC GENERAL CONTRACTOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GUH GAS FIRED UNIT HEATER

H HUMIDIFIER OR HEIGHT

H2O WATER

HD HEAD

HP HORSEPOWER

HVAC HEATING, VENTILATION, AND

AIR-CONDITIONING

ABBREVIATIONS - MECHANICAL

HVY HEAVY

HW HOT WATER (DOMESTIC)

HWB HOT WATER BOILER

HWP HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWT HOT WATER TEMPERATURE

IN INCH

KEF KITCHEN EXHAUST FAN

KW KILOWATT

L LOUVER

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LD LINEAR DIFFUSER

LF LINEAR FEET

LIN LINEAR

LTDE LOW-LIMIT TEMPERATURE DETECTOR

LWT LEAVING WATER TEMPERATURE

M MOTOR OR MOTORIZED DAMPER OR

METER

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKEUP AIR UNIT

MBH 1,000 BRITISH THERMAL UNITS PER HOUR

MCA MINIMUM CIRCUIT AMPS

MERV MINIMUM EFFICIENCY REPORTING VALUE

MFGR MANUFACTURER

MOCP MAXIMUM OVERCURRENT PROTECTION

N NEW OR NORTH

NC NORMALLY CLOSED OR NOISE CRITERIA

NG NATURAL GAS

NO NORMALLY OPEN OR NUMBER

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTDOOR AIR

OAT OUTDOOR AIR TEMPERATURE

OD OUTSIDE DIAMETER

OS OCCUPANCY SENSOR

P PRESSURE OR PRESSURE SENSOR

P/I PROVIDE AND INSTALL

PA PIPE ANCHOR

PD PRESSURE DROP

PH PHASE

PHC PREHEAT COIL

PPM PARTS PER MILLION

PTAC PACKAGED TERMINAL AIR CONDITIONER

QTY QUANTITY

R RADIUS, RISE, OR REMOVE

RA RETURN AIR

RAD RADIATOR

RAT RETURN AIR TEMPERATURE

RCP REFLECTED CEILING PLAN

RD REFRIGERANT DISCHARGE

RF REFRIGERANT PIPING

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

SA SUPPLY AIR

SAT SUPPLY AIR TEMPERATURE

SCH SCHEDULE

SD SLOT DIFFUSER

SEC SECONDS

SF SUPPLY FAN OR SQUARE FOOT

SP STATIC PRESSURE

SS SPLIT SYSTEM OR STAINLESS STEEL

SVAV SERIES FLOW FAN POWERED BOX

SWR SIDEWALL REGISTER

T OR TEMP TEMPERATURE

T&P TEMPERATURE AND PRESSURE

T-STAT THERMOSTAT

TCP TEMPERATURE CONTROL PANEL

TEF TOILET EXHAUST FAN

TON 12,000 BRITISH THERMAL UNITS PER

HOUR COOLING

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UH UNIT HEATER

V OR VOLT VOLTAGE

VAV VARIABLE AIR VOLUME BOX

VEL VELOCITY

VF VENTILATION FAN

VFD VARIABLE FREQUENCY DRIVE

Voc OUTDOOR AIRFLOW (SPACE)

W WIDTH OR WATTS

W/ WITH

WB WET BULB

WC WATER COLUMN

WCU WATER CHILLING UNIT

WG WATER GAUGE

WH WALL HYDRANT

WHP WATER HEATER PUMP

WL WALL LOUVER

WPD WATER PRESSURE DROP

X UNCORRECTED FRACTION OF OUTDOOR

AIR (SYSTEM)

Y CORRECTED FRACTION OF OUTDOOR AIR

(SYSTEM)

Z FRACTION OF OUTDOOR AIR (CRITICAL

SPACE)

NO. DESCRIPTION DATE

Date:7/8/25

EXP:11/30/2025

EXISTING UFD, ABANDON IN

PLACE (TYP. FOR ALL UFD)

MD101

(E)

(E)

(E)

(E)

EXISTING LOUVER

TO REMAIN

EXISTING HOOD

TO REMAIN

EXISTING HOOD

TO REMAIN

EXISTING WATER

HEATER FLUE

EXISTING UFD, ABANDON IN

PLACE (TYP. FOR ALL UFD)

NG

MD101

A

54321

B

C

D

E

F

SCALE

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

REVISIONS

SEAL

KEY PLAN

Dewberry Architects Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000

IL DESIGN FIRM #184000358-0001

Dewberry Engineers Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602 309.282.8000

IL DESIGN FIRM #184.005007

/8

/2

:2

:4

P M

MECHANICAL

DEMOLITION

PLANS

JRF

PER

PER

7/3/25

50185817

F

IR

E S

T A

T

IO

N

H V

A C

R E

P L A

C E

M E

N T

C it y o f B lo o m in g to n

Is s u e d f o r

B id d in g

E

E M

P

IR

E S

T R

E E

T

B L O

O M

IN

G

T O

N

IL

MD101

NOTES:

1. UNDERFLOOR DUCTWORK TO BE ABANDONED IN PLACE. CONTRACTOR TO

CAP AND SEAL DUCTWORK THROUGH FLOOR PENETRATIONS IN THE

MECHANICAL ROOM 2" ABOVE THE SURROUNDING CONCRETE.

2. EXISTING FLOOR MOUNTED AIR DEVICES ARE TO BE ABANDONED IN PLACE,

TYPICAL FOR ALL.

3. EXISTING CONDENSING UNITS TO BE REMOVED. REMOVE ALL ASSOCIATED

PIPING, CONDUIT AND WIRING. EXISTING ROOFTOP UNIT SUPPORTS SHALL

REMAIN AND BE ABANDONED IN PLACE. EXISTING ROOFTOP PIPING AND

CONDUIT PENETRATION LOCATION/HOUSING TO BE REMOVED ENTIRELY.

CONTRACTOR TO PATCH ROOF TO MATCH EXISTING, REFER TO

ARCHITECTURAL PLANS FOR ADDITIONAL ROOF PATCHING REQUIREMENTS.

4. EXISTING OVERHEAD SUPPLY AIR DUCTWORK TO BE REMOVED.

CONTRACTOR TO REMOVE ALL ASSOCIATED DUCTWORK INSULATION,

ACCESSORIES, FLEX DUCT, HANGERS AND SUPPORTS, AND AIR DEVICES.

5. EXISTING PLENUM RETURN AIR DEVICES ARE TO BE REMOVED, TYPICAL

FOR ALL.

6. EXISTING DUCTWORK SILENCERS AND ALL ASSOCIATED SUPPORTS ARE TO

BE REMOVED.

7. EXISTING EXHAUST AIR DUCTWORK, EXHAUST FAN, AND CONTROLS TO

REMAIN. REFER TO CONTROLS SHEETS FOR ASSOCIATED NEW WORK.

8. EXISTING AIR HANDLING UNIT TO BE REMOVED. CONTRACTOR TO REMOVE

ALL ASSOCIATED PIPING, DUCTWORK, ACCESSORIES, HANGERS AND

SUPPORTS AND CONTROLS.

9. EXISTING FURNACE FLUE DUCTWORK TO BE REMOVED. REMOVE ALL

ASSOCIATED HANGERS AND SUPPORTS. EXISTING ROOFTOP PENETRATION

TO BE REMOVED. CONTRACTOR TO PATCH ROOF TO MATCH EXISTING,

REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL ROOF PATCHING

REQUIREMENTS.

10. EXISTING 1-1/2" NATURAL GAS BRANCH LINE SERVING THE FURNACE TO BE

REMOVED. REMOVE ALL ASSOCIATED HANGERS AND SUPPORTS.

CONTRACTOR TO REMOVE BRANCH LINE BACK TO MAIN IN THE MECHANCIAL

ROOM AND PROVIDE PIPING STUB AND CAP AT THE MAIN LINE.

11. EXISTING EXHAUST FAN TO REMAIN. COORDINATE DEMOLITION AT UPPER

LEVEL WITH ASSOCIATED NEW WORK AND EXISTING EQUIPMENT TO REMAIN.

12. EXISTING COMBUSTION AIR INTAKE DUCTWORK TO BE REMOVED.

CONTRACTOR TO PROVIDE BLANK-OFF PANEL WHERE DUCTWORK AT

LOUVER IS REMOVED, REFER TO NEW WORK PLAN.

13. EXISTING COMBUSTION AIR INTAKE AND MOTORIZED DAMPER TO REMAIN.

GENERAL NOTES:

1. REFER TO SHEET M-001 FOR GENERAL NOTES, SYMBOLS, & ABBREVIATIONS

APPLICABLE TO THIS DRAWING.

2. REFER TO DIVISION 22 & 23 SPECIFICATIONS.

3. BUILDING TO REMAIN FULLY OCCUPIED DURING CONSTRUCTION. PROVIDE

TEMPORARY COOLING/HEATING EQUIPMENT DURING CONSTRUCTION.

CONTRACTOR TO COORDINATE PROJECT PHASING WITH BUILDING OWNER.

4. FIRE STATION #3 IS A CONTROLLED LOCATION. CONTRACTORS WORKING

WITHIN THE FACILITY WILL NEED TO SUBMIT APPLICATION AND BE GRANTED

SITE BADGES TO OPERATE WITHIN THE FACILITY BY THE AIRPORT

AUTHORITY.

Scale: 1/8" = 1'-0"

MECHANCIAL DEMOLITION FLOOR PLAN

Scale: 1/8" = 1'-0"

MECHANICAL DEMOLITION ROOF PLAN

0 4' 8' 16'

0 2' 4' 8'

0 4' 8' 16'

Scale: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM DEMOLTION

Scale: 1/4" = 1'-0"

UPPER LEVEL MECHANICAL ROOM DEMOLTION

0 2' 4' 8'

ASBESTOS ABATEMENT NOTES:

IN 2017, THE CITY OF BLOOMINGTON PERFORMED AN INSPECTION OF FIRE

STATION #3 FOR ACCESSIBLE SUSPECT ASBESTOS-CONTAINING MATERIAL

(ACM). AREA ESTIMATES WERE NOTED IN THE REPORT AND ARE AVAILABLE

FOR REVIEW. PRIOR TO CONSTRUCTION OF THE PROPOSED IMPROVEMENTS,

THE CONTRACTOR IS RESPONSIBLE TO REVIEW THE REPORT AND TO ABATE

AND REMOVE ALL ACM THAT WILL CONFLICT WITH THE PROPOSED

IMPROVEMENTS. THE CONTRACTOR SHALL ADHERE TO ALL STATE OF

ILLINOIS REQUIREMENTS AND REGULATIONS INCLUDING BUT NOT LIMITED TO

THE FOLLOWING:

• THE IEPA’S “STATE OF ILLINOIS DEMOLITION/RENOVATION/ASBESTOS

PROJECT NOTIFICATION FORM” SHALL BE SUBMITTED AND A COPY SENT

TO THE ENGINEER. IT SHALL BE UPDATED IF THERE IS A CHANGE IN THE

START AND/OR FINISH DATE OR IF THE QUANTITY OF ASBESTOS

CHANGES BY MORE THAN 20 PERCENT.

• ASBESTOS ABATEMENT WORK SHALL BE PERFORMED BY AN IDPH

LICENSED CONTRACTOR PREQUALIFIED WITH THE ILLINOIS CAPITAL

DEVELOPMENT BOARD WHO HAS AN ON-SITE SUPERVISOR LICENSED BY

IDPH AND EMPLOYS WORKERS LICENSED BY IDPH. THIS WORK SHALL BE

COMPLETED ACCORDING TO THE REQUIREMENTS OF THE U.S.

ENVIRONMENTAL PROTECTION AGENCY (USEPA), IEPA, OSHA, AND LOCAL

REGULATORY AGENCIES.

• THE CONTRACTOR SHALL PERFORM AIR MONITORING DURING ASBESTOS

ABATEMENT ACTIVITIES. AIR SAMPLING SHALL BE CONDUCTED BY A

QUALIFIED AIR SAMPLING PROFESSIONAL.

• PERSONAL MONITORING SHALL BE CONDUCTED PER APPLICABLE OSHA

REGULATIONS.

• WHEN ASBESTOS IS REMOVED PRIOR TO DEMOLITION, CLEARANCE

TESTING PER IDPH SHALL BE CONDUCTED UPON THE REMOVAL OF

ASBESTOS CONTAINING BUILDING MATERIALS (ACBMS).

THE FOLLOWING SUBMITTALS SHALL BE MADE TO THE ENGINEER PRIOR TO

THE START OF THE ASBESTOS ABATEMENT:

• MANUFACTURER’S CERTIFICATION STATING THAT VACUUMS,

VENTILATION EQUIPMENT, AND OTHER EQUIPMENT REQUIRED TO

CONTAIN AIRBORNE FIBERS CONFORM TO ANSI 29.2.

• A LISTING OF THE BRAND NAME, MANUFACTURER, AND SPECIFICATION OF

ALL SEALANTS OR SURFACTANTS TO BE USED.

• PROOF OF ARRANGEMENTS FOR TRANSPORT AND DISPOSAL OF ACMBS

HAVE BEEN OBTAINED (I.E. A LETTER OF AUTHORIZATION TO UTILIZE

DESIGNATED LANDFILL).

• A DETAILED WORK PLAN OF THE CONTRACTOR’S ANTICIPATED

PROCEDURES INCLUDING THE LOCATION AND LAYOUT OF

DECONTAMINATION UNITS, THE SEQUENCING OF WORK, THE

RESPIRATORY PROTECTION PLAN, A SITE SAFETY PLAN, A DISPOSAL

PLAN, AND A DETAILED DESCRIPTION OF THE METHODS TO BE USED TO

CONTROL POLLUTION.

• PROOF OF THE CONTRACTOR’S PREQUALIFICATION WITH THE CAPITAL

DEVELOPMENT BOARD AND EMPLOYEE CERTIFICATIONS WITH IDPH.

SUBMITTALS THAT SHALL BE MADE UPON COMPLETION OF ABATEMENT

WORK:

• COPIES OF WASTE CHAIN-OF-CUSTODIES, TRIP TICKETS, SHIPPING

MANIFESTS, OR DISPOSAL RECEIPTS FOR ASBESTOS WASTE MATERIALS

REMOVED FROM THE WORK AREA.

• COPIES OF EACH DAY’S WORK SITE ENTRY LOGBOOK WITH INFORMATION

ON WORKER AND VISITOR ACCESS.

• LOGS DOCUMENTING FILTER CHANGES ON RESPIRATORS, HEPA

VACUUMS, NEGATIVE PRESSURE VENTILATION UNITS, AND OTHER

ENGINEERING CONTROLS.

• TEST RESULTS OF ANY BULK MATERIAL ANALYSIS AND AIR SAMPLING

DATA COLLECTED DURING THE ABATEMENT INCLUDING RESULTS OF ANY

ON-SITE TESTING BY ANY FEDERAL, STATE, OR LOCAL AGENCY.

NO. DESCRIPTION DATE

M-101

S1

40 CFM

S1

30 CFM

R2

110 CFM

R2

40 CFM

S2

40 CFM

R1

40 CFM

S1

40 CFM

S1

50 CFM

R1

50 CFM

R2

50 CFM

R1

65 CFM

S1

65 CFM

S2

40 CFM

S2

165 CFM

(E)

(E)

(E)

(E)

(E) (E)

(E)

R2

75 CFM

(E)

S2

50 CFM

12/8

8/8

8/6

6ø

6ø

6ø 6ø

6ø

6ø

8/8

6ø

8ø

6/6 6/6

8/6

6/6

14/8

8/8

6/6

6/6

6/6

6/6

6/6

TEST

CU

CU

(E)

16/8

8ø

R2

50 CFM

8ø 8ø

8ø

S2

80 CFM

6ø

8ø

8ø

6ø

S1

35 CFM

DOAS

ERV

10/10

10/10 14/8

14/12

16/8

14/8

EDH

M-101

M-101

24/24

EXISTING LOUVER AT

UPPER LEVEL, SEE

ELEVATION VIEW

10/10

36/407

EXISTING

MOTORIZED DAMPER

EXISTING

EXHAUST FAN

OA

OA

SA

RA

EA

CU

CU

FCU

FCU

FCU

FCU

FCU

DOAS

ERV

FCU

FCU

FCU

FCU

HRU

HRU

T

T

T

T

T

TT

H

H

H

H

H

H H

CU

CU

FCU

FCU

FCU

FCU

FCU

FCU

FCU

FCU

FCU

DOAS

ERV

1" CD

1" CD 1" CD

1" CD 1" CD

HRU

HRU

ERV

EDH

EXISTING LOUVER

24/24

10/10

PROVIDE BEVELED TAP

INTO 24"x24"

DUCTWORK PLENUM

A

54321

B

C

D

E

F

SCALE

APPROVED BY

CHECKED BY

SHEET NO.

TITLE

DRAWN BY

DATE

PROJECT NO.

REVISIONS

SEAL

KEY PLAN

Dewberry Architects Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602-1585 309.282.8000

IL DESIGN FIRM #184000358-0001

Dewberry Engineers Inc.

401 Southwest Water Street Suite 701 Peoria, IL 61602 309.282.8000

IL DESIGN FIRM #184.005007

/8

/2

:2

:4

P M

MECHANICAL

NEW WORK

PLANS

JRF

PER

PER

7/3/25

50185817

F

IR

E S

T A

T

IO

N

H V

A C

R E

P L A

C E

M E

N T

C it y o f B lo o m in g to n

Is s u e d f o r

B id d in g

E

E M

P

IR

E S

T R

E E

T

B L O

O M

IN

G

T O

N

IL

M-101

Scale: 1/8" = 1'-0"

MECHANICAL NEW WORK FLOOR PLAN - VENTILATION

Scale: 1/4" = 1'-0"

ENLARGED MECHNANICAL ROOM NEW WORK

FLOOR PLAN - VENTILATION

NOTES:

1. PROVIDE CLEANOUT IN CONDENSATE PIPING.

2. TERMINATE CONDENSATE DRAIN LINES IN MOP SINK. JOIN CONDENSATE LINES INTO A

COMMON VERTICAL PIPE FOR DISCHARGE INTO THE MOP SINK, SHOWN SEPARATELY

FOR CLARITY.

3. PROVIDE EXTERNAL CONDENSATE PUMP FOR WALL MOUNTED FAN COIL. CONDENSATE

PUMP SHALL PROVIDE THE REQUIRED LIFT TO ROUTE PIPING AS SCHEMATICALLY

SHOWN. PROVIDE STAINLESS STEEL DRIP PAN BELOW THE CONDENSATE PUMP. MOUNT

CONDENSATE PUMP DIRECTLY BESIDE THE WALL MOUNTED UNIT. MOUNTING LOCATION

SHALL ALLOW FOR GRAVITY DRAINAGE FROM THE FAN COIL TO THE CONDENSATE

PUMP. PROVIDE LEAK DETECTION SENSOR IN THE CONDENSATE PAN THAT SHALL SEND

AN ALARM SIGNAL TO THE BUILDING DDC SYSTEM IN THE EVENT OF LEAK OR

CONDENSATE PUMP FAILURE. FAN COIL SERVED BY A CONDENSATE PUMP SHALL BE

DISABLED UPON DETECTION OF A LEAK.

4. CONTRACTOR TO PROVIDE NEW BLANK-OFF PANEL ACROSS THE ENTIRETY OF THE

EXISTING LOUVER. BLANK-OFF PANEL SHALL BE A MINIMUM OF 2" OF FIBER-BOARD

INSULATION WITH APPROPRIATE EXTERIOR RATED FINISH. CONTRACTOR TO PROVIDE

WEATHER-TIGHT SEALING BETWEEN THE BLANK-OFF PANEL AND LOUVER. REFER TO

PLANS FOR LOCATIONS OF DUCTWORK PENETRATIONS TO THE LOUVER. COORDINATE

THE REQUIRED OPENING SIZES IN THE BLANK-OFF PANELS PRIOR TO FABRICATION.

5. NEW SPACE THERMOSTAT SUPPLIED BY THE VRF EQUIPMENT PROVIDER. INSTALLED

BY THE MECHANICAL CONTRACTOR. THERMOSTAT SHALL BE INSTALLED ADJACENT TO

THE SPACE LIGHTING CONTROLS AT THE SAME ELEVATION. CONTRACTOR TO

COORDINATE DEVICE LOCATION PRIOR TO INSTALLATION. TYPICAL FOR ALL VRF

THERMOSTATS.

6. CONDENSATE PIPING DOWN TO EXISTING SANITARY WASTE PIPING. COORDINATE

CONDENSATE PIPING ELEVATION WITH RESPECT TO DRAIN POINT PRIOR TO

INSTALLATION.

7. PROVIDE NECK SIZE PLENUM DUCTWORK DOWN FROM EXISTING ROOF HOOD. ERV-1

INTAKE DUCTWORK TO TRANSITION INTO NECK SIZE FOR OUTDOOR AIR INTAKE.

8. REFER TO DEMOLITION PLANS FOR REMOVAL OF EXISTING DUCTWORK IN THIS AREA.

PROVIDE 24"x24" PLENUM FROM THE EXISTING LOUVER TO SERVE FOR ERV-1 OUTDOOR AIR INTAKE. INTAKE DUCTWORK TO ERV-1 TO TAP INTO 24"x24" PLENUM. PROVIDE

BEVELED DUCTWORK CONNECTION.

9. WHERE TWO OR MORE FAN COILS SERVE A SINGLE SPACE, THE FAN COILS SHALL BE

CONTROLLED BY A SINGLE SPACE THERMOSTAT. THE FAN COILS' OPERATING MODE

SHALL BE INTERLOCKED SO THE UNITS ARE ALWAYS OPERATING IN THE SAME MODE.

GENERAL NOTES:

1. BUILDING TO REMAIN FULLY OCCUPIED DURING CONSTRUCTION. PROVIDE TEMPORARY

COOLING/HEATING EQUIPMENT DURING CONSTRUCTION. CONTRACTOR TO COORDINATE

PROJECT PHASING WITH BUILDING OWNER.

2. REFER TO SHEET M-001 FOR GENERAL NOTES, SYMBOLS, & ABBREVIATIONS APPLICABLE

TO THIS DRAWING.

3. REFER TO DIVISION 22 & 23 SPECIFICATIONS.

4. INSTALL BOTTOM OF CASSETTES FLUSH WITH CEILING GRID. IN ORDER TO AVOID

OVERHANGIN A LIGHT FIXTURE, 2x2 FAN COILS…