This is Addendum No. 2 to Bid 2026-05 for the Town of Montville in Connecticut, issued on October 20, 2025, modifying the original Project Manual & Specifications and Drawings dated September 26, 2025. The project involves procurement and installation of a 100KW generator for an Animal Control Facility. Key modifications include construction of a 4.5' by 16' concrete slab as the generator foundation, with the generator contractor responsible for anchoring the unit and installing all required grounding in accordance with code requirements. The Animal Control Facility Contractor will install a 400A automatic transfer switch (ATS) within the facility, with a minimum 2-inch PVC conduit connecting the ATS to the generator pad and a 2-inch PVC stub left above grade for wire pulling. The generator contractor must utilize this conduit to run wires between the ATS and the new generator. Drawings are not available; however, an aerial project map is included with the addendum. Bidders must acknowledge receipt of this addendum in their bid proposal to avoid disqualification.
The diesel fuel tank shall be sized by the manufacturer to provide sufficient fuel for 24-hour runtime at 100 percent load. The Animal Control Facility electrical service is 400A, 120/208 Volt Wye, 3-Phase. No pricing terms, set-asides, incumbents, funding sources, or contract term information is provided in this addendum document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid 2026-05 - ACF Generator - Addendum 1.pdf | ||
| ER_CON_ASB_0028-0109_Scanned.zip | ZIP file | |
| 32732_Jan_28_26_solicitation_doc.pdf | ||
| Bid 2026-05 Animal Control Facility Generator.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum No. 2
ADDENDUM NO. 2
Notice to Bidders for
Town of Montville
Bid No. 2026-05
Animal Control Facility Generator
ADDENDUM ISSUED: October 20, 2025
This Addendum forms part of the Contract Documents and modifies the original Project Manual &
Specifications and Drawings dated September 26, 2025. Acknowledge receipt of this Addendum in the Bid
Proposal, failure to do so may subject the Bidder to disqualification.
This Addendum is a modification to the Contract Documents as follows:
Overall modification throughout the Project Manual and Specifications:
1. References to 100A generator shall be deleted. Generator shall be 100KW.
2. Drawings are not available. An aerial project map is included with this Addendum.
Scope of Work Modifications:
1. A 4.5’x16’ concrete slab shall be constructed with the Animal Control Facility. The Generator
Contractor shall install the new generator on the concrete slab. The Generator Contractor shall be responsible for anchoring the new generator to the existing slab.
2. The Generator Contractor shall install grounding as needed and in accordance with code requirements for the new generator.
3. The Animal Control Facility Contractor will install a 400A automatic transfer switch (ATS) within the facility. A minimum 2” PVC conduit will be installed between the ATS and the generator concrete pad. A 2” PVC stub will be left above grade at the concrete pad for pulling wires through the conduit. The Generator Contractor shall utilize the conduit to run wires between the existing
ATS within the facility and the new generator.
Advertisement to Bid: Delete reference to a 400 V Automatic Transfer Switch. The automatic transfer switch will be installed by the Animal Control Facility Contractor.
Technical Specifications: Engine Generators: 2.7 Fuel Supply System: Add the following:
B. Diesel fuel tank shall be sized by the Manufacturer to provide enough fuel for 24-hour run time at 100% load.
The following are responses to potential bidders questions to date:
• Will all grounding be installed with poured concrete pad? i.e., There will be a bare wire stubbed thru concrete. To tie Generator too.
Response: See Scope of Work Modifications above. The Generator Contractor shall install grounding as needed and in accordance with code requirements for the new generator.
• What size is the electrical service being installed in the building? i.e., 100amp 480 volt
Response: The Animal Control Facility electrical service is 400A, 120/208 Volt Wye, 3-Phase