BHS Rooftop Reno Bids & Permits 07 02 2026.pdf

PDF 6 MB Posted

Attached to
BHS Rooftop Mechanical Replacement & Renovation State and local contract opportunity
Solicitation number
RFP BRI 260000002317 1
Issued by
Kent County, Michigan

About this file

This is a comprehensive set of mechanical, structural, and electrical design and specification documents for the Brighton High School (BHS) Rooftop Mechanical Replacement and Renovation project, prepared for Brighton Area Schools (BAS) in Brighton, Michigan. The project involves the replacement of existing rooftop HVAC equipment and infrastructure, including the removal of multiple rooftop units (RTUs), an energy recovery ventilator (ERV), and a cooling tower, along with the installation of new mechanical equipment. New equipment includes one air-cooled chiller (ACCH-1) with a capacity of 440 tons and integral primary pump, one cooling tower (CT-1) with a capacity of 434 tons, two energy recovery ventilators (ERV-1 and ERV-2), and fourteen new rooftop units (RTU-C1 through RTU-C22). The project requires structural reinforcement of the existing roof framing to support the new chiller weighing 30,258 pounds and cooling tower weighing 20,858 pounds, including new steel pipe columns, beams, and reinforcement of existing trusses. All work must comply with the 2021 Michigan Building Code, 2023 National Electrical Code, and applicable OSHA standards. The documents are dated June 26, 2026, and are prepared for bids and permits.

The structural design specifies new W10x15 and W12x26 beams, new 3-inch Schedule 40 steel pipe columns with cap and base plates, and field-welded reinforcement to existing structural elements. All structural steel conforms to AISC Load and Resistance Factor Design standards with specified ASTM material grades and E70 series welding. The mechanical system operates in a lead/standby configuration with the new air-cooled chiller as a redundant unit to the existing water-cooled chiller, managed by the building automation system through automated isolation valves. Chilled water piping includes Schedule 40 black steel with threaded, grooved, or welded fittings, with all piping insulated with minimum 2-inch fiberglass insulation featuring a vapor barrier. The electrical work includes disconnection and removal of existing equipment connections, provision of new disconnect switches and service receptacles for new rooftop equipment, and a dedicated feeder from the main switchboard to the new air-cooled chiller with an assumed run length of approximately 550 feet. All mechanical, electrical, and structural contractors are responsible for field verification of existing conditions, coordination with other trades, and compliance with manufacturer recommendations and code requirements prior to final installation and commissioning.

View the file

Other files for this state and local contract opportunity

Other files attached to BHS Rooftop Mechanical Replacement & Renovation, newest first.
File Type Posted
BHS Rooftop Mechanical Replacement RFP Packet 07 02 2026.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P Q Q.5 R R.3O.5

S

- BRIGHTON HIGH SCHOOL -

BRIGHTON AREA SCHOOLS (BAS)

MECHANICAL UNITS REPLACEMENT

conn engineering consultants, inc.

commercial+industrial+institutional+residential structural engineering

107 n. bridge st.

po box 791 linden, mi 48451

p. 810.458.4350

f. 810.458.4592 www.connengineering.com seal:

A B C D E F G H I J job information:

While every attempt has been made to produce error free documents, it is the responsibility of the builder and/or client to verify all existing conditions, dimensions, details, code compliance and specifications preceding commencement of work.

Prior to acceptance of these documents, the engineer takes full responsibility for changes and errors and/or omissions, but is relieved of these responsibilities once these documents have been accepted. The design and original drawings of this project remain the property of Conn Engineering Consultants, Inc. and no additional persons or parties may use this design and/or drawings for any other purpose without the consent of Conn Engineering Consultants, Inc.

c 2026 Conn Engineering Consultants, Inc.

copyright information:

SHEET

ISSUED FOR DATE

JOB NO :

SCALE :

DRAWN :

CHECKED :

DATE :

SHEET TITLE :

K

B R

IG

H

T O

N S

C H

O O

LS

R O

O

FT

O P

F R

A M

E

B

R

IG

T H

T O

N R

D B

R

IG

H T

O N

, M I

APPROVAL 06.25.26

Bids & Permits 6/26/26

06.16.26

JMC

AS NOTED

26-264

X/X = 1'-0"

SHEET TITLE 1

SHEET TITLE 1

EX

. W x1

1.

EX

. W x1

1.

EX

. W x1

1.

EX. W16x26 (BELOW)

EX. W16x26 (BELOW)

EX

. W x4

BE

LO

W

EX

. W x1

1.

EX

. W x4

BE

LO

W

EX

. T

-1 T

RU

SS

B

EL

O W

(R

EI

N

FO

RC

E

PE

R

D

ET

A

IL

4/ S1

EX

. T

-1 T

RU

SS

B

EL

O W

EX. 20HS JOIST @ 5'-0"

O.C. (TYPICAL)

EX. W16x26 BELOW

'-0

T1

C

LE

A R

SP

A

N

'-0

2' -6

'-1 0"

2' -6

5'

-0

'-0

1'

-8

/8

NEW CHILLER

(WEIGHT = 30,258 LBS)

'-6

/8

6'-9"

6'-9" 12'-6"

Scale: 3/16" = 1'-0"

PARTIAL ROOF FRAMING PLAN1 N

O

RT

H

'-8

/8

NEW 3" SCH40

STEEL PIPE

COLUMN

NEW 3" SCH40

STEEL PIPE

COLUMN

22'-3"1'-0"

'-6

'-0

N

EW

W x1

BE

A

M

N

EW

W x1

BE

A

M

NEW W12x26 BEAM (BELOW)

NEW W12x26 BEAM (BELOW)

EX. C10

EX. W14x34 BELOW

EX. W8x10EX. W8x10 EX. W8x10

EX. W8x10EX. W8x10 EX. W8x10

EX. W8x10EX. W8x10 EX. W8x10

EX. W10 BELOW

EX. W10 BELOW

EX

. W x2

EX

. W x2

EX

. W x2

EX

. W x2

EX

. W x2

EX. W8x10EX. W8x10 EX. W8x10

EX. W14x34 BELOW

GENERAL STRUCTURAL NOTES

1. GOVERNING BUILDING CODE - 2021 MICHIGAN BUILDING CODE

2. THE STRUCTURAL NOTES ARE INTENDED TO AUGMENT THE DRAWINGS AND

SPECIFICATIONS. SHOULD CONFLICTS EXIST BETWEEN THE DRAWINGS,

SPECIFICATIONS AND THE STRUCTURAL NOTES, THE STRICTEST PROVISION

SHALL GOVERN.

3. THE STRUCTURAL DRAWINGS FORM AN INTEGRAL PART OF THE CONTRACT

DOCUMENTS, WHICH INCLUDE ARCHITECTURAL, STRUCTURAL,

MECHANICAL, ELECTRICAL, SITE DRAWINGS AND SPECIFICATIONS.

COORDINATE THE STRUCTURAL DRAWINGS WITH THE REQUIREMENTS

SHOWN IN THE OTHER COMPONENTS OF THE CONTRACT DOCUMENTS.

4. TYPICAL DETAILS AND OTHER DETAILS APPLY TO CONDITIONS THAT ARE

SIMILAR TO THE CONDITIONS DESCRIBED IN THE DETAILS, EVEN IF THEY ARE

NOT SPECIFICALLY REFERENCED ON THE PLANS.

5. THE CONTRACTOR IS RESPONSIBLE FOR MEANS, METHODS, SEQUENCES AND

PROCEDURES OF CONSTRUCTION.

6. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE

BUILDING IS FULLY COMPLETED. DETERMINE ERECTION PROCEDURE AND

SEQUENCE, AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS

COMPONENT PARTS DURING ERECTION. THIS INCLUDES THE ADDITION OF

TEMPORARY BRACING, GUYS OR TIE DOWNS IF NECESSARY. RETAIN

OWNERSHIP OF SUCH MATERIAL AFTER COMPLETION OF THE PROJECT.

7. CONSTRUCTION SHALL COMPLY FULLY WITH THE APPLICABLE PROVISIONS

OF OSHA AND THE LOCAL GOVERNING CODES, LATEST EDITION, AND ALL

REQUIREMENTS SPECIFIED IN THE CODES SHALL BE ADHERED TO AS IF THEY

WERE CALLED FOR OR SHOWN ON THE DRAWINGS. THIS SHALL NOT BE

CONSTRUED TO MEAN THAT REQUIREMENTS SET FORTH ON THE DRAWING

MAY BE MODIFIED BECAUSE THEY ARE MORE STRINGENT THAN THE CODE

REQUIREMENTS OR BECAUSE THEY ARE NOT SPECIFICALLY REQUIRED BY

CODE.

DESIGN LOADS

1. THE STRUCTURE IS DESIGNED FOR THE FOLLOWING LIVE LOADS IN ADDITION

TO THE LATERAL LOADS AND SUPERIMPOSED DEAD LOADS AND

SELF-WEIGHT OF THE STRUCTURE. WHERE APPLICABLE, THE LIVE LOADS ARE

REDUCED IN ACCORDANCE WITH THE PROVISIONS OF THE BUILDING CODE.

THE SNOW LOADS ON LOWER ROOFS ADJACENT TO HIGH ROOFS OR

SLOPED ROOFS ARE INCREASED FOR THE EFFECT OF DRIFTING.

2. BUILDING IS NOT DESIGNED FOR FUTURE VERTICAL OR HORIZONTAL

EXPANSION.

LIVE LOAD

ROOF SNOW LOAD:

GROUND SNOW LOAD: 25 PSF

FLAT ROOF SNOW LOAD (MINIMUM ROOF LOAD): 17.5 PSF

SNOW EXPOSURE FACTOR: 1.0

SNOW LOAD IMPORTANCE FACTOR: 1.0

THERMAL FACTOR: 1.0

ADDITIONAL LOADING DUE TO DRIFTING AT CHANGES IN ROOF ELEVATIONS

AND ICE AT OVERHANGS PER APPLICABLE CODE.

DEAD LOAD

EXISTING ROOF: 30 PSF

CHILLER: 25,900 LBS.

OPEN COOLING TOWER: 19,090 LBS.

WIND LOAD

BASIC DESIGN WIND SPEED, V: 115 MPH

ALLOWABLE STRESS DESIGN WIND SPEED, Vasd: 90 MPH

EXPOSURE CATEGORY: C

INTERNAL PRESSURE COEFFICIENT: 0.18

SEISMIC LOAD

DESIGN CATEGORY: B

SITE CLASSIFICATION: D - DEFAULT

SEISMIC IMPORTANCE FACTOR: 1.00

Ss = 0.094 S1 = 0.046 SDs = 0.100

SD1 = 0.073

STRUCTURAL STEEL

1. ALL STRUCTURAL STEEL SHALL CONFORM TO THE 14TH EDITION OF THE LOAD

AND RESISTANCE FACTOR DESIGN (L.R.F.D.) “MANUAL OF STEEL

CONSTRUCTION” OF THE AISC.

2. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM

SPECIFICATIONS AND MINIMUM YIELD STRENGTHS:

MEMBER ASTM MIN. YIELD STRENGTH

W SHAPES A992 50 KSI

HSS TUBES A500 (GRADE B) 46 KSI

ROUND HSS TUBES A500 (GRADE B) 42 KSI

PIPE A53 (GRADE B) 35 KSI

MISC. PLATES/SHAPES A992 50KSI

CONNECTION BOLTS A325 92 KSI

ANCHOR BOLTS F1554 36 KSI

THREADED RODS A36 36 KSI

3. WELDING SHALL BE DONE WITH APPROPRIATE E70 SERIES ELECTRODES

COMPATIBLE WITH THE NEW AND EXISTING STEEL. WELDS AND WELDING

PROCEDURES SHALL CONFORM TO THE "STRUCTURAL WELDING CODE -

STEEL" OF THE AMERICAN WELDING SOCIETY ANSI/AWS D1.1.

4. WHERE FIELD REVISIONS ARE REQUIRED DUE TO UNFORESEEN

CIRCUMSTANCES, SUBMIT ALL CHANGES FOR REVIEW TO THE PROFESSIONAL

ENGINEER.

5. THE LENGTH, DIMENSION AND CONNECTION DETAIL FROM NEW

STRUCTURAL MEMBERS TO THE EXISTING STRUCTURE SHALL BE FIELD VERIFIED

BEFORE FABRICATION. FIELD MODIFICATIONS TO THE FABRICATED MEMBER

OR CONNECTION ARE NOT ALLOWED WITHOUT PRIOR APPROVAL BY THE

ARCHITECT/ENGINEER OF THE CONTRACTOR'S SKETCHES OR SHOP

DRAWINGS REFLECTING THESE MODIFICATIONS.

6. WELDING SHALL BE DONE BY WELDERS QUALIFIED IN ACCORDANCE WITH

THE REQUIREMENTS OF THE CURRENT "STRUCTURAL WELDING CODE - STEEL",

AMERICAN WELDING SOCIETY, AWS D1.1.

EXISTING STEEL JOISTS:

1. EXISTING STEEL JOISTS ARE ASSUMED TO BE A36 STEEL.

2. THE MANUFACTURER OF THE JOISTS IS ASSUMED TO BE A MEMBER OF THE

STEEL JOIST INSTITUTE.

3. FABRICATED TRUSSES ARE ASSUMED TO BE BUILT PER ORIGINAL

CONSTRUCTION DOCUMENTS.

4. REFER TO DETAILS FOR REINFORCEMENT OF EXISTING TRUSSES.

NEW COOLING TOWER

(WEIGHT = 20,858 LBS)

'-0

6'

-6

19'-11"

9' -1

3/

4"

7'-0" 9'-1" 7'-0"

4' -0

5'

-0

5' -4

'-6

2' -8

5'-10"

28'-11"

EX

W

8x

30'-0"

S102

EX. 3"Ø STEEL

COLUMNS

EX. 3"Ø STEEL

COLUMNS

S102

S102

EX

. W

8x

25'-7 1/2"

S102

SIM.

S102

SIM.

conn engineering consultants, inc.

commercial+industrial+institutional+residential structural engineering

107 n. bridge st.

po box 791 linden, mi 48451

p. 810.458.4350

f. 810.458.4592 www.connengineering.com seal:

A B C D E F G H I J job information:

While every attempt has been made to produce error free documents, it is the responsibility of the builder and/or client to verify all existing conditions, dimensions, details, code compliance and specifications preceding commencement of work.

Prior to acceptance of these documents, the engineer takes full responsibility for changes and errors and/or omissions, but is relieved of these responsibilities once these documents have been accepted. The design and original drawings of this project remain the property of Conn Engineering Consultants, Inc. and no additional persons or parties may use this design and/or drawings for any other purpose without the consent of Conn Engineering Consultants, Inc.

c 2026 Conn Engineering Consultants, Inc.

copyright information:

SHEET

ISSUED FOR DATE

JOB NO :

SCALE :

DRAWN :

CHECKED :

DATE :

SHEET TITLE :

K

B R

IG

H

T O

N S

C H

O O

LS

R O

O

FT

O P

F R

A M

E

B

R

IG

T H

T O

N R

D B

R

IG

H T

O N

, M I

APPROVAL 06.25.26

Bids & Permits 6/26/26

06.16.26

JMC

AS NOTED

26-264

SECTIONS & DETAILS

Scale: 3/8" = 1'-0"

CHILLER SECTION DETAIL1

NEW CHILLER

(WEIGHT = 30,258 LBS)

EX. 20HS JOIST @ 5'-0"

O.C. (TYPICAL)

NEW W10x15 BEAM

NEW W12x26 BEAM (BELOW)

EX. T1 STEEL TRUSS

NEW WT6x13 VERTICAL NEW WT6x13 VERTICAL

EX. W10x11.5

EX. W16x26

EX. W16x26

EX. W18x40

S102

Scale: 3/8" = 1'-0"

CHILLER SECTION DETAIL2

EX. 20HS JOIST @ 5'-0"

O.C. (TYPICAL)

NEW 3" SCH40 STEEL PIPE COLUMN

W/ 12" STEEL CAP AND BASE PLATES

ATTACHED W/ (4) 34"Ø A325 STEEL

BOLTS EACH

NEW W10x15 BEAM

NEW W12x26 BEAM (BELOW)

EX. T1 STEEL TRUSS

NEW WT6x13 VERTICAL

NEW CHILLER

(WEIGHT = 30,258 LBS)

NOTES:

1. ALL STEEL REINFORCEMENT TO BE FIELD WELDED TO

EXISTING STEEL.

2. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS

PRIOR TO INSTALLATION OF REINFORCEMENT.

NOTES:

1. ALL STEEL REINFORCEMENT TO BE FIELD WELDED TO

EXISTING STEEL.

2. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS

PRIOR TO INSTALLATION OF REINFORCEMENT.

3/16" TYP.

ATTACH NEW BEAM W/

(3) 34"Ø A325 STEEL BOLTS

Scale: 3/8" = 1'-0"

CHILLER SECTION DETAIL7

EX. C10

EX. W8x10

EX. W16x26

NEW COOLING TOWER

(WEIGHT = 20,858 LBS)

EX. W14x34 BEAM

TOP OF EXISTING ROOF

EX. STEEL RAIL

NEW COOLING TOWER TO

BE PLACED DIRECTLY OVER

STEEL BEAMS BELOW

EX. HSS5x5 COLUMN

EX. W8x10

4" SHEAR PLATE

ATTACHED W/ (3) 34"Ø

A325 STEEL BOLTS

3/16" (3) SIDES

NEW 3" SCH40 STEEL PIPE COLUMN

W/ 12" STEEL CAP AND BASE PLATES

ATTACHED W/ (4) 34"Ø A325 STEEL

BOLTS EACH

NEW 3" SCH40 STEEL PIPE COLUMN

W/ 12" STEEL CAP AND BASE PLATES

ATTACHED W/ (4) 34"Ø A325 STEEL

BOLTS EACH

EX. (2) L2 1/2 x 2 x 3/16

TO BE REINFORCED (SEE

DETAIL 5/S102) EX. (2) L2 1/2 x 2 x 3/16

TO BE REINFORCED (SEE

DETAIL 5/S102)

NEW WT6x13 VERTICAL

Scale: 3/8" = 1'-0"

REINFORCED TRUSS - T14

NEW WT6x13 VERTICAL

EX. (2) L3 1/2 x 3 x 1/4

TO BE REINFORCED (SEE

DETAIL 5/S102)

EX. (2) L2 1/2 x 2 x 5/16

TO BE REINFORCED (SEE

DETAIL 5/S102)

EX. (2) L3 x 2 x 1/4 TO BE

REINFORCED (SEE

DETAIL 5/S102) Scale: 3/8" = 1'-0"

REINFORCED WEB5

NEW 1"Ø A36 STEEL BAR

EACH SIDE OF AS

SHOWN

EXISTING TRUSS WEB

1/4 1-12

Scale: 3/8" = 1'-0"

TRUSS ATTACHMENT DETAIL6

NEW W12x26 BEAM (BELOW)

EX. T1 STEEL TRUSS

NEW WT6x13 VERTICAL

3/16" TYP.

ATTACH NEW BEAM W/

(3) 34"Ø A325 STEEL BOLTS

3/16" TYP.

6/S102

P Q Q.5 R R.3O.5ON.7

S

S

BLBLBLBL

CLR

1. COORDINATE NEW PIPING WITH BUILDING STRUCTURAL CONDITIONS,

EQUIPMENT MANUFACTURER RECOMMENDATIONS AND ALL OTHER

TRADES TO AVOID INTERFERENCES.

2. PROVIDE ACCESS AROUND ALL NEW EQUIPMENT PER

MANUFACTURERS RECOMMENDATIONS.

3. ALL MECHANICAL RELATED CORING THROUGH WALLS AND FLOORS

SHALL BE BY MECHANICAL CONTRACTOR. SEAL ALL PENETRATIONS

THROUGH RATED WALLS AND FLOORS WITH U.L. RATED CAULK

SEALANT IN ACCORDANCE WITH THE SPECIFICATION REQUIREMENTS.

1. COORDINATE SHUT-DOWN OF ANY SYSTEM WITH THE BUILDING

SERVICES PERSONNEL PRIOR TO SYSTEM SHUT-DOWN.

2. REMOVE (INCLUDING DISCONNECTION OF) MECHANICAL SERVICE AS

INDICATED AND/OR DESCRIBED ALONG WITH PIPING, HANGERS,

SUPPORTS, CONTROLS AND ALL RELATED ACCESSORIES.

3. FIELD VERIFY EXACT SIZE AND LOCATION OF ALL EXISTING SERVICES

PRIOR TO DEMOLITION.

4. WHERE DAMAGE OCCURS DURING DEMOLITION, THE CONTRACTOR

SHALL REPAIR AS REQUIRED SO AS TO BE COMPATIBLE WITH

EXISTING.

5. WHERE DUCT AND/OR PIPE INSULATION HAS BEEN DAMAGED, THE

CONTRACTOR SHALL REPAIR AS REQUIRED SO AS TO BE COMPATIBLE

WITH EXISTING.

6. ALL ITEMS DEMOLISHED SHALL BE REMOVED FROM THE SITE AND

DISPOSED OF PROPERLY, UNLESS NOTED OTHERWISE.

7. LIMITS OF DEMOLITION ARE INDICATED ON THE DRAWINGS. SHOULD

EXISTING FIELD CONDITIONS REQUIRE MODIFICATIONS OF THESE

LIMITS FOR THE PROPER INSTALLATION OF NEW WORK, THE

CONTRACTOR SHALL BE RESPONSIBLE FOR SUCH MODIFICATIONS.

8. CAP AND SEAL AIRTIGHT ALL UNUSED OPENINGS ON THE RETURN

AND SUPPLY DUCTWORK.

GENERAL NOTES:

1. PROVIDE MATERIALS AND EQUIPMENT AND EXECUTE THE WORK,

INCLUDING ALL TESTING AND INSPECTIONS, IN COMPLIANCE WITH THE

APPLICABLE PROVISIONS OF FEDERAL, STATE AND LOCAL

GOVERNMENT LAWS, ORDINANCES, REFERENCED CODES AND

STANDARDS CURRENT AS OF THE ISSUE DATE OF THESE DRAWINGS.

ALL MORE STRINGENT REQUIREMENTS OF THE CONTRACT DOCUMENTS

SHALL MODIFY, SUPPLEMENT AND SUPERSEDE APPLICABLE PORTIONS

OF GOVERNING LAWS, ORDINANCES, CODES AND STANDARDS.

2. CONTRACTOR SHALL PRESENT CERTIFICATE TO THE OWNER THAT ALL

APPLICABLE BUILDING PERMITS HAVE BEEN SECURED PRIOR TO

STARTING ANY WORK, AND PROVIDE THE OWNER WITH ALL REQUIRED

CERTIFICATES OF FINAL APPROVAL FROM THE GOVERNING

JURISDICTIONS AT COMPLETION OF THE WORK. PROVIDE ALL SHOP

DRAWINGS AS REQUIRED IN FOLLOWING SECTIONS.

3. MAKE ALL CONNECTIONS TO EXISTING SYSTEMS DURING DESIGNATED

PERIODS UPON APPROVAL OF THE OWNER AND AT NO INCREASE IN

CONTRACT SUM.

4. EXISTING FACILITIES:

A. DO NOT INTERRUPT EXISTING UTILITIES UTILIZED BY THE OWNER

EXCEPT AS SPECIFIED OR WHEN APPROVED IN WRITING, AND THEN

ONLY AFTER TEMPORARY UTILITY SERVICES HAVE BEEN

APPROVED AND PROVIDED. INTERRUPTIONS MUST BE SCHEDULED

TO SUIT THE OWNER'S REQUIREMENTS.

B. VERIFY ALL EXISTING WORK, WHERE EXISTING CONNECTIONS ARE

PARTIAL, PROVIDE ALL NECESSARY MATERIALS, LABOR AND

EQUIPMENT REQUIRED TO MODIFY EXISTING WORK. IN ADDITION,

MAINTAIN INTEGRITY OF THE EXISTING SYSTEMS. RECTIFY ANY

CONTAMINATION, DEGRADATION OF CLEANLINESS OR DAMAGE TO

THE EXISTING SYSTEMS TO THE SATISFACTION OF THE OWNER.

PROVIDE ALL WORK SO REQUIRED AT NO INCREASE IN THE

CONTRACTOR'S ORIGINAL PROPOSAL.

5. COORDINATE EXACT LOCATION OF CONSTRUCTION TO PRECLUDE ANY

INTERFERENCES BETWEEN PIPING, WIRING, LIGHTING FIXTURES,

DUCTWORK, BUILDING EQUIPMENT, PROCESS EQUIPMENT AND OTHER

CONSTRUCTION.

6. PROVIDE LABOR, INCLUDING FIELD ERECTION AND SUPERVISION,

MATERIALS, EQUIPMENT AND ANCILLARIES, AND COORDINATE,

PROCURE, FABRICATE, DELIVER, ERECT OR INSTALL, INTERFACE WITH

EXISTING WORK, START, DEBUG AND TEST ALL SYSTEMS AS

NECESSARY TO PROVIDE THE OWNER WITH A COMPLETE, OPERATING

FACILITY IN CONFORMANCE WITH THE CONSTRUCTION BID

DOCUMENTS.

7. ALL CUTTING AND PATCHING THAT MAY BE NECESSARY FOR THE

INSTALLATION OF THE MECHANICAL CONTRACTOR'S WORK SHALL BE

PERFORMED AND REPAIRED BY THE TRADE WHOM NORMALLY

PERFORMS THAT WORK AND PAID FOR BY THE MECHANICAL

CONTRACTOR. NO CUTTING OF THE BUILDING STRUCTURAL SYSTEM

SHALL BE PERFORMED.

8. THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO

SUBMITTING HIS BID TO FAMILIARIZE HIMSELF WITH THE ACTUAL

PROJECT CONDITIONS AND TO CHECK FOR ANY INTERFERENCES

BETWEEN HIS WORK AND THAT OF THE OTHER TRADES, AND/OR ANY

APPARENT VIOLATIONS OF LOCAL OR STATE CODES, LAWS,

ORDINANCES AND REGULATIONS. SHOULD ANY VIOLATIONS OR

INTERFERENCES APPEAR AND DEPARTURE FROM THE DESIGN INTENT

OF THE CONTRACT DOCUMENTS IS REQUIRED, THE CONTRACTOR

SHALL NOTIFY THE ARCHITECT PRIOR TO ENTERING INTO A CONTRACT

WITH THE OWNER. FAILURE TO PROVIDE THE ARCHITECT WITH THE

AFOREMENTIONED NOTIFICATION SHALL RESULT IN THE CONTRACTOR

BEING HELD RESPONSIBLE TO COMPLETE ALL WORK TO MEET THE

INTENT OF THE CONTRACT DOCUMENTS WITH NO ADDITIONAL

EXPENSES BEING INCURRED BY THE OWNER.

9. THE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL LOCATIONS

AND ARRANGEMENTS OF ALL THE EQUIPMENT AND PIPING. THE

DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS BUILDING

CONSTRUCTION AND ALL OTHER WORK WILL PERMIT. DO NOT SCALE

DRAWINGS FOR EXACT MEASUREMENTS.

10. DEMOLITION OF MECHANICAL EQUIPMENT SHALL INCLUDE ALL EXISTING

PIPING, VALVES, CONTROLS, SUPPORTS, AND EQUIPMENT WHERE SUCH

ITEMS ARE NOT REQUIRED FOR THE PROPER OPERATION OF THE

REVISED SYSTEM. REMOVE, RECONNECT, CAP, PLUG AND REPLACE

EXISTING PIPING AND DUCTWORK.

GENERAL NOTES: PIPING

1. THE PIPING SYSTEMS SHALL BE INSTALLED IN STRICT ACCORDANCE

WITH ALL STATE AND LOCAL CODES. THE PIPING CONTRACTOR SHALL

OBTAIN ALL PERMITS, PAY ALL FEES, AND ARRANGE FOR ALL

INSPECTIONS FOR HIS WORK. AT THE COMPLETION OF THE PROJECT,

THE PIPING CONTRACTOR SHALL FURNISH THE OWNER WITH

CERTIFICATES OF FINAL INSPECTIONS AND APPROVALS.

2. PIPING SHALL BE AS FOLLOWS:

A. CHILLED WATER PIPING:

1) CHILLED WATER PIPING SHALL BE SCHEDULE 40, BLACK STEEL

WITH THREADED, GROOVED OR WELDED FITTINGS.

B. VALVES:

1) BALL VALVES SHALL BE TWO PIECE FULL PORT BRONZE BALL

VALVES WITH STAINLESS STEEL TRIM, TFE SEATS WITH 316

STAINLESS STEEL BALL AND STEM. THREADED BODY PACK NUT

DESIGN WITH ADJUSTABLE STEM PACKING WITH THREADED OR

SOLDERED ENDS. RATED FOR 150 PSIG SWP AND 600 PSIG

CWP.

2) CHECK VALVES SHALL BE SWING CHECK WITH BRONZE DISC,

CLASS 150, ASTM B62. Y PATTERN DESIGN WITH THREADED OR

SOLDERED ENDS. RATED FOR 300 PSIG CWP.

C. PIPING INSULATION:

1) ALL CHILLED WATER PIPING SHALL BE INSULATED WITH

MINIMUM 2" THICK FIBERGLASS INSULATION, WITH A FIRE

RETARDANT JACKET, HAVING AN AVERAGE R VALUE OF 3.45.

CHILLED WATER PIPING INSULATION SHALL BE PROVIDED WITH

A VAPOR BARRIER. PROVIDE PREFORMED SECTIONS WITH PVC

COVERS AT ALL FITTINGS.

2) PIPE INSULATION SHALL HAVE A FLAME SPREAD AND SMOKE

DENSITY RATING NOT EXCEEDING 25/50, AS TESTED PER ASTM

STANDARD E-84.

3. PIPING SHALL BE SUPPORTED FROM HANGERS AT AN ADEQUATE

DISTANCE WITH SUPPORTING HANGER RODS FASTENED TO THE

BUILDING FRAMING WHENEVER POSSIBLE. SUPPORT SPACING SHALL

NOT EXCEED THE HANGER SPACING REQUIREMENTS PER SECTION 308

OF THE LOCAL PLUMBING CODE.

4. ISOLATE PIPING AND EQUIPMENT FROM THE BUILDING STRUCTURE

WITH INSULATING HANGERS AND FITTINGS AS REQUIRED TO PREVENT

GALVANIC CORROSION OF THE BUILDING PIPING SYSTEMS.

5. FURNISH AND INSTALL ISOLATION VALVES AT ALL SERVICE POINTS OR

EQUIPMENT CONNECTIONS.

6. LABEL ALL PIPING SYSTEMS WITH MANUFACTURED SELF ADHESIVE OR

PRE-TENSIONED PIPE MARKERS. MARKERS SHALL INDICATE SERVICE

AND DIRECTION OF FLOW. MARK PIPE NEAR: VALVES, BRANCH

CONNECTIONS, PENETRATIONS, ACCESS DOORS AND NEAR MAJOR

PIECES OF EQUIPMENT.

7. THE PIPING CONTRACTOR SHALL VERIFY EXACT LOCATIONS AND

PROVIDE ROUGH-INS FOR ALL EQUIPMENT FURNISHED BY OTHER

CONTRACTORS. AFTER ALL EQUIPMENT HAS BEEN INSTALLED BY

OTHER CONTRACTORS, THE PIPING CONTRACTOR SHALL MAKE ALL

FINAL CONNECTIONS AND SHALL INCLUDE IN HIS BASE BID ALL VALVES,

UNIONS, COUPLINGS, ETC., THAT ARE REQUIRED TO MAKE FINAL

CONNECTIONS.

8. THE CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS

OF ALL EQUIPMENT FURNISHED BY THIS CONTRACTOR WITH THE

ELECTRICAL CONTRACTOR.

9. THE PIPING CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED

UNDER THIS CONTRACT TO BE FREE FROM DEFECTIVE WORKMANSHIP

AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER THE ACCEPTANCE

OF THE BUILDING BY THE OWNER, AND SHOULD DEFECTS OCCUR

WITHIN THIS PERIOD, REPAIR AND/OR REPLACE DEFECTIVE ITEMS AND

ANY DAMAGE RESULTING FROM FAILURE OF THESE ITEMS, AT NO

EXPENSE TO THE OWNER.

10. THE CONTRACTOR SHALL COORDINATE LOCATIONS OF HIS EQUIPMENT

AND WORK WITH OTHER BUILDING TRADES TO AVOID ANY

INTERFERENCES BETWEEN HIS WORK AND THE WORK OF OTHER

TRADES.

11. CONTRACTOR SHALL MAINTAIN ADEQUATE CLEARANCES (PER N.E.C.)

ABOVE AND AROUND ANY EXISTING ELECTRICAL PANELS, EQUIPMENT

AND TRANSFORMERS WHEN ROUTING OVERHEAD PIPING.

12. CONTRACTOR SHALL PROVIDE PROTECTION FOR PIPING INSTALLED IN

CONCEALED SPACES TO PREVENT DAMAGE FROM FASTENERS.

PIPE TURNED UP

PIPE TURNED DOWN

PIPE OUT BOTTOM

PIPE OUT TOP

UNION

PLUG VALVE

CHECK VALVE

SYMBOL DESCRIPTION

CONNECT NEW TO EXISTING

BUTTERFLY VALVE

CHILLED WATER RETURN PIPING

CHILLED WATER SUPPLY PIPING

CHWR

CHWS

REMOVE / DEMOLISH

ACC-# AIR COOLED CHILLER

CHWP-# CHILLED WATER PUMP

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CTWP-# COOLING TOWER WATER PUMP

C.O. CLEAN OUT

CT-# COOLING TOWER

DIA/Ø DIAMETER

(E) EXISTING

G.P.M. GALLONS PER MINUTE

HHWS HEATING HOT WATER SUPPLY

HHWR HEATING HOT WATER RETURN

(TYP.) TYPICAL

VFD VARIABLE FREQUENCY DRIVE

WCCH-# WATER COOLED CHILLER

WH-# WATER HEATER

SYMBOLS

SPECIFICATIONS ABBREVIATIONS

EXISTING SERVICE TO BE CAPPED

(E) EXISTING

MECHANICAL GENERAL NOTES:

DEMOLITION GENERAL NOTES:

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

A T E O F M I C H I GA N

06/26/26

#DEMOLITION KEY NOTES:

1. REMOVE AND PROPERLY DISPOSE OF THE EXISTING ROOF

TOP UNIT IN ITS ENTIRETY. DISCONNECT ALL ELECTRICAL

AND CONTROL WIRING AND THE HEATING HOT AND

CHILLED WATER PIPING. EXISTING SUPPLY AND RETURN

DUCTWORK CONNECTIONS WITHIN EXISTING CURB TO

REMAIN. EXISTING SUPPORT RAILS ARE TO REMAIN IN

PLACE AND BE PROTECTED DURING REMOVAL

OPERATIONS. EQUIPMENT SHALL BE REMOVED FROM THE

SITE AND REMAIN THE PROPERTY OF THE OWNER OR

DISPOSED OF PROPERLY IF THE OWNER DOES NOT WANT

THEM.

2. REMOVE AND PROPERLY DISPOSE OF THE EXISTING

ENERGY RECOVERY UNIT IN ITS ENTIRETY. DISCONNECT

ALL ELECTRICAL AND CONTROL WIRING AND THE HEATING

HOT AND CHILLED WATER PIPING. EXISTING SUPPORT

RAILS ARE TO REMAIN IN PLACE AND BE REUSED FOR NEW

UNIT SUPPORT. EXISTING DUCTWORK IS ALSO TO REMAIN

AND SHALL BE LEFT INTACT, CLEAN, AND READY FOR

RECONNECTION TO NEW EQUIPMENT. REPAIR ANY MINOR

DAMAGE TO ADJACENT MATERIALS CAUSED BY REMOVAL

WORK. EQUIPMENT SHALL BE REMOVED FROM THE SITE

AND REMAIN THE PROPERTY OF THE OWNER OR

DISPOSED OF PROPERLY IF THE OWNER DOES NOT WANT

THEM.

(E) RTU-C221(E) RTU-C18 1 (E) RTU-C201(E) RTU-C121

(E) RTU-91

(E) RTU-101

(E) RTU-C71

(E) RTU-C51

(E) RTU-C61

(E) RTU-C81

(E) RTU-C31

(E) RTU-C11

(E) RTU-C21

(E) RTU-C41

(E) ERV-B22

(E) ERV-B12

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

C H

W R

C H

W R

C H

W R

C H

W S

C H

W S

C H

W S

H H

W S

H H

W S

H H

W S

H H

W S

H H

W S

H H

W S

H H

W S

H H

W R

H H

W R

H H

W R

H H

W R

H H

W R

H H

W R

HHWR

HHWS

CHWS

CHWR

1 (E)CT

33 3

CHWR CHWR

C H

W R

C H

W R

C H

W R

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

C H

W R

CHWR CHWR CHWR

CHWS CHWS CHWS CHWS

HHWR

HHWS

H H

W S

H H

W S

HHWS HHWS

CHWS

CHWR

HHWS

HHWR

HHWR HHWR HHWR HHWR

H H

W R

H H

W R

HHWR HHWR

H H

W R

H H

W R

CHWS CHWS

CHWR

C H

W S

C H

W R

CHWR CHWR CHWR CHWR CHWR CHWR CHWR

C H

W R

C H

W R

C H

W R

C H

W R

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

CHWS CHWS CHWS CHWS

C H

W R

C H

W R

C H

W S

CHWS

C H

W S

CHWS

CHWS

C H

W S

CHWS

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

CHWS

CHWS

C H

W S

C H

W S

CHWR

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W R

CHWR

CHWR

CHWR

C H

W S

C H

W S

C H

W S

(E )6

"C H

W S

(E)6"

(E)8"

CHWS

(E)10"

C H

W S

(E)6"

(E)6"CHWS

(E)6"CHWS

(E )1

0" C

H W

S H

H W

S H

H W

S H

H W

S

H H

W R

H H

W R

H H

W R

(E)8"HHWS

HHWS HHWS HHWS

(E)CHWP-3

(E)CHWP-4

(E)CHWP-2

(E)CH-1

(E)WH-1

(E)WH-2

(E)6" (E)4"

(E)4"

(E)CHWP-1

(E)CHWP-6

TO ICE TANK

(E)DRY COOLER

CHWR

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

CHWS

CHWS

(E )1

0"

(E)2" TOWER WATER MAKEUP

(E)8" (E)8"

(E)CHWP-5

#KEY NOTES:

1. REMOVE EXISTING COOLING TOWER, INCLUDING ALL ASSOCIATED

PIPING, SUPPORTS, AND ELECTRICAL CONNECTIONS.

CONTRACTOR SHALL PROPERLY DISCONNECT, DRAIN, AND

DISPOSE OF EXISTING EQUIPMENT IN ACCORDANCE WITH

APPLICABLE CODES. PROVIDE AND INSTALL NEW COOLING

TOWER COMPLETE WITH ALL REQUIRED PIPING, VALVES,

CONTROLS, AND ELECTRICAL CONNECTIONS. COORDINATE ALL

WORK WITH EXISTING CONDITIONS. ENSURE PROPER SUPPORT,

ALIGNMENT, AND COMMISSIONING OF THE NEW UNIT PER

MANUFACTURER’S RECOMMENDATIONS.

2. CONTRACTOR SHALL DISCONNECT AND REMOVE THE EXISTING

ENERGY RECOVERY UNIT (ERU) IN ITS ENTIRETY, INCLUDING ALL

ASSOCIATED DUCTWORK, CONTROLS, PIPING, SUPPORTS, AND

APPURTENANCES.

ALL ELECTRICAL, CONTROL WIRING, AND PIPING CONNECTIONS

SHALL BE PROPERLY DISCONNECTED AND MADE SAFE PRIOR TO

REMOVAL.

3. EXISTING STRUCTURAL STEEL BEAM AND STRUCTURAL

SUPPORTS SHALL REMAIN AND BE PROTECTED DURING

DEMOLITION. DO NOT CUT, MODIFY, OR DAMAGE ANY

STRUCTURAL ELEMENTS.

4. DISCONNECT AND REMOVE ASSOCIATED DUCTWORK BACK TO

THE NEAREST MAIN OR AS INDICATED ON THE DRAWINGS, AND

CAP AND PROVIDE A WATERTIGHT SEAL AT ALL ROOF AND WALL

OPENINGS.

5. DISCONNECT AND REMOVE EXISTING PIPING BACK TO THE

NEAREST ACTIVE MAIN AS INDICATED. PROVIDE CAPS AT ALL

OPEN ENDS AND ENSURE A WATERTIGHT SEAL.

6. RELOCATE EXISTING PIPING AS REQUIRED TO ACCOMMODATE

THE NEW CHILLER. FIELD VERIFY FINAL LOCATION PRIOR TO

INSTALLATION ( APPROXIMATELY MINIMUM 10'-0" EAST).

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

A T E O F M I C H I GA N

06/26/26

P Q R

RTU-C8

RTU-C6

RTU-C7

RTU-C5

RTU-C10 RTU-C9

RTU-C4

RTU-C2

RTU-C3

RTU-C1

RTU-C20RTU-C18 RTU-C22

RTU-C18

1 1

#KEY NOTES:

1. CONTRACTOR SHALL FURNISH AND INSTALL A NEW AIR HANDLING UNIT (AHU) ON AN

ADAPTOR CURB THAT ALIGNS WITH THE EXISTING ROOF CURB FROM THE UNIT

THAT WAS REMOVED IN THIS AREA. FIELD MEASURE EXACT EXISTING CURB

DIMENSIONS PRIOR TO FABRICATION OF THE ADAPTOR CURB TO ENSURE PROPER

FIT.

RECONNECT / EXTEND SUPPLY AND RETURN DUCTWORK WITHIN ADAPTOR CURB

AS REQUIRED. MODIFY, EXTEND, OR PROVIDE TRANSITIONS AS REQUIRED TO

MAINTAIN A COMPLETE, AIRTIGHT SYSTEM.

PROVIDE AND INSTALL NEW CHILLED WATER AND HEATING WATER PIPING AS

REQUIRED TO CONNECT TO THE NEW AHU COIL CONNECTION POINTS. PROVIDE

ISOLATION VALVES, BALANCING VALVES, STRAINERS, UNIONS, AND ALL REQUIRED

ACCESSORIES FOR A COMPLETE INSTALLATION.

PROVIDE CONTROL VALVES AT EACH COIL (CHILLED WATER AND HEATING WATER),

COMPLETE WITH ACTUATORS COMPATIBLE WITH THE EXISTING BUILDING

MANAGEMENT SYSTEM (BMS). CONTROL VALVES SHALL BE SIZED AND SELECTED

FOR PROPER MODULATION AND SYSTEM PERFORMANCE.

ALL CONTROLS, SENSORS, ACTUATORS, AND CONTROL WIRING SHALL BE

PROVIDED AND INTEGRATED WITH THE EXISTING BMS. COORDINATE WITH

CONTROLS CONTRACTOR TO ENSURE FULL FUNCTIONALITY, INCLUDING

TEMPERATURE CONTROL, VALVE MODULATION, AND SYSTEM MONITORING.

ALL PIPING SHALL BE PROPERLY SUPPORTED, INSULATED, FLUSHED, AND TESTED.

PROVIDE AIR VENTS AND DRAIN VALVES AS REQUIRED FOR PROPER SYSTEM

OPERATION.

SEAL ANY NEW ROOF PENETRATIONS WATERTIGHT AND COORDINATE WITH

ROOFING CONTRACTOR AS REQUIRED.

CONTRACTOR SHALL VERIFY ALL EXISTING FIELD CONDITIONS AND COORDINATE

WORK WITH ALL TRADES.

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

ERV-B11

ERV-B21

#KEY NOTES:

1. CONTRACTOR SHALL FURNISH AND INSTALL A NEW

ENERGY RECOVERY VENTILATOR UNIT (ERV). UNIT

TO BE MOUNTED ON THE EXISTING STEEL SUPPORT

BEAMS AS INDICATED. SECURE NEW UNIT TO

EXISTING STEEL AS REQUIRED.

ALL CONTROLS, SENSORS, ACTUATORS, AND

CONTROL WIRING SHALL BE PROVIDED AND

INTEGRATED WITH THE EXISTING BMS. COORDINATE

WITH CONTROLS CONTRACTOR TO ENSURE FULL

FUNCTIONALITY, INCLUDING TEMPERATURE

CONTROL VALVE MODULATION, AND SYSTEM

MONITORING. INSTALLING CONTRACTOR SHALL

VERIFY ALL EXISTING FIELD CONDITIONS AND

COORDINATE WORK WITH ALL OTHER TRADES.

2. RECONFIGURE EXISTING DUCTWORK AS REQUIRED

TO CONNECT TO THE NEW UNIT. MODIFY

TRANSITIONS, ADAPTERS, OR OFFSETS AS REQUIRED

TO ALIGN WITH THE NEW ERV DUCT CONNECTION

FLANGES. INSPECT EXISTING DUCT INSULATION AND

REPLACE ANY DAMAGED SECTIONS. ENSURE ALL

REUSED DUCT JOINTS ARE RESEALED TO MEET

CURRENT LEAKAGE REQUIREMENTS. INSULATE ALL

NEW DUCTWORK TO MATCH EXISTING AND SEAL

WATER TIGHT.

3. EXTEND / REWORK CHILLED WATER AND HEATING

WATER PIPING AS REQUIRED TO CONNECT TO THE

NEW ERV COILS CONNECTION LOCATIONS. PROVIDE

ISOLATION BALL VALVES, BALANCING VALVES,

STRAINERS, UNIONS, AND ALL REQUIRED

ACCESSORIES FOR A COMPLETE INSTALLATION. ALL

PIPING SHALL BE PROPERLY SUPPORTED,

INSULATED, FLUSHED, AND TESTED. PROVIDE AIR

VENTS AND DRAIN VALVES AS REQUIRED FOR

PROPER SYSTEM OPERATION.

4. PROVIDE A CONTROL VALVES AT EACH COIL (CHILLED

WATER AND HEATING WATER), COMPLETE WITH

ACTUATORS COMPATIBLE WITH THE BUILDING

MANAGEMENT SYSTEM (BMS). CONTROL VALVES

SHALL BE SIZED AND SELECTED FOR PROPER

MODULATION AND SYSTEM PERFORMANCE.

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

CHWR CHWR

C H

W R

C H

W R

C H

W R

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

C H

W R

CHWR CHWR CHWR

CHWS CHWS CHWS CHWS

HHWR

HHWS

H H

W S

H H

W S

HHWS HHWS

CHWS

CHWR

HHWS

HHWR

HHWR HHWR HHWR HHWR HHWR

H H

W R

H H

W R

HHWR HHWR

H H

W R

H H

W R

CHWS CHWS

CHWR

C H

W S

C H

W R

CHWR CHWR CHWR CHWR CHWR CHWR CHWR

C H

W R

C H

W R

C H

W R

C H

W R

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

CHWS CHWS CHWS CHWS

C H

W R

C H

W R

C H

W S

CHWS

C H

W S

CHWS

CHWS

C H

W S

CHWS

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

CHWS

CHWS

C H

W S

C H

W S

CHWR

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W R

CHWR

CHWR

CHWR

C H

W S

C H

W S

C H

W S

(E )6

"C H

W S

(E)6"

(E)8"

(E)10"

C H

W S

(E)6"

(E)6"CHWS

(E)6"CHWS

(E )1

0" C

H W

S H

H W

S H

H W

S H

H W

S

H H

W R

H H

W R

H H

W R

(E)8"HHWS

HHWS HHWS HHWS

(E)CHWP-3

(E)CHWP-4

(E)CHWP-2

(E)WCCH-1

(E)WH-1

(E)WH-2

(E)6" (E)4"

(E)4"

(E)CHWP-1

(E)CHWP-6

TO ICE TANK

(E)DRY COOLER

CHWR

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

CHWS

CHWS

1 CT-1

EXISTING STEEL

SUPPORT BEAMS

NEW STEEL SUPPORT BEAMS

(BY STRUCTURAL TRADES)

SERVICE CLEARANCE

C H

W R

C H

W R

C H

W R

C H

W R

C H

W R

C H

W R

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W S

C H

W R

CHWR

CHWS

(E )1

0"

6" 6"

EXISTING STEEL

SUPPORT BEAM

ACCH-1

6" 6"

FLEX CONNECTION (TYP.)

TEMPERATURE GAUGE(TYP.)

PRESSURE GAUGE (TYP.)

FLOW SWITCH

STRAINER

BUTTERFLY (TYP.)

(E)2" TOWER WATER MAKEUP

(E)8" (E)8"

PIPE SUPPORT

(TYPICAL)

(E)CHWP-5

(E)CTWP-1

(E)CTWP-2

6"

6"

RELOCATED

PIPING

#KEY NOTES:

1. PROVIDE AND INSTALL NEW COOLING TOWER.

CONNECT NEW COOLING TOWER TO EXISTING

SUPPLY, RETURN AND BYPASS COOLING TOWER

WATER PIPING AS WELL AS TOWER FILL PIPING.

EXISTING VALVES AND STRAINERS SHALL REMAIN.

PROVIDE ANY ADDITIONAL PIPING, CONTROLS, AND

ELECTRICAL CONNECTIONS REQUIRED FOR A

COMPLETE AND OPERATIONAL SYSTEM. COORDINATE

ALL WORK WITH EXISTING CONDITIONS. FIELD VERIFY

EXISTING CONDITIONS PRIOR TO MAKING

CONNECTIONS.

2. STRUCTURAL TRADES TO PROVIDE ADDITIONAL

STRUCTURAL SUPPORT STEEL AND VERIFY THE

CAPACITY OF THE EXISTING SUPPORT STEEL. REFER

TO SPECIFIED CHILLER MANUFACTURER

INSTALLATION MANUAL FOR EXACT REQUIREMENTS

AND POINT WEIGHTS INCLUDING LOCATION OF ALL

VIBRATION ISOLATORS.

3. PROVIDE / REWORK WATER TIGHT SEAL AND SLEEVE

THRU EXISTING WALL AS REQUIRED TO

ACCOMMODATE NEW 6" CHILLED WATER PIPING.

4. CONNECT NEW 6" CHILLED WATER SUPPLY INTO

EXISTING CHILLED WATER PIPING IN THIS AREA.

EXACT CONNECTION LOCATION SHALL BE

FIELD-VERIFIED AND COORDINATED WITH EXISTING

CONDITIONS.

5. PROVIDE (2) NEW 6" 2-POSITION ISOLATION VALVES.

VALVE SHALL MODULATE IN COORDINATION WITH

ACTIVE CHILLER OPERATION. VALVES SHALL BE BRAY

SERIES 70 CONTROLS (120 VOLT) TO MATCH EXISTING

CHILLER CONTROL VALVES.

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VERI F Y A LL W O R K AND SH AL L N OT IF Y TH E A RC HI TEC T

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

A T E O F M I C H I GA N

06/26/26

P Q R

SPREADER TO BE

USED ON PIPE SIZED

ON 10" AND ABOVE

INSULATED PIPE

(COLD)

MIN. 4" INSULATED PIPES

(HOT OR DUEL TEMP.)

(4" AND 5")

INSULATED PIPES

(HOT OR DUEL TEMP.)

(MIN. 6")

SPREADER TO BE

USED ON PIPE SIZED

ON 10" AND ABOVE

INSULATED PIPE

(COLD)

(MIN. 4")

INSULATED SADDLES

AND SHIELDS

STANDARD PIPE

COVERING

INSULATED PIPE

(HOT OR COLD)

(MAX. 4" )

INSULATED PIPE

(MAX. 4" )

HANGER PIPE DETAILS

N.T.S.

PIPE SUPPORT DETAIL

N.T.S.

GALVANIZED SHEET METAL

SHIELD - SEE SCHEDULE FOR

GAUGE THICKNESS AND

LENGTH

"A"

REFRACTORY INSERT (90° WEDGE) SAME

THICKNESS AS INSULATION AND OF

WIDTH "A" SHOWN IN SCHEDULE BELOW

VAPOR BARRIER

LAP CEMENT

CALCIUM SILICATE

INSULATION- SEE

SPECIFICATION FOR

THICKNESS

STEEL BAND AROUND

PERIMETER OF SHIELD

AT EACH END (TYP.)

INSULATION SADDLE AND

SHEILD SCHEDULES

PIPE

SIZE

SHIELD GAUGE

AND LENGTH

INSERT WIDTH "A"

COLD LINES

HOT OR

DUEL TEMP.

LINES

4" - 6" 50 GA. - 6" LG. 4" 4"

PIPE HANGER SCHEDULE

STEEL PIPE

(STANDARD WEIGHT) COPPER TUBING

PIPE SIZE ROD SIZE MAX. SPACING PIPE SIZE ROD SIZE MAX.

SPACING

1" MAX. 3/8" 8'-0" 1" MAX. 3/8" 5'-0"

1" - 2" 3/8" 10'-0" 1 1/4" - 1 1/2 3/8" 7'-0"

2 1/2" - 3" 1/2" 12'-0" 2" 1/2" 10'-0"

4" - 5" 5/8" 16'-0" 2 1/2" - 3" 1/2" 10'-0"

6" - 10" 3/4" 16'-0" 4" 5/8" 10'-0"

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

AIR COOLED CHILLER SCHEDULE

MARK MANUFACTURER MODEL NUMBER TYPE

NOMINAL

CAPACITY

(TONS)

EVAPORATOR ICE BUILD ICE MELT CONDENSER COMPRESSOR PUMPS REFRIGERANT ELECTRICAL

WEIGHT

(LBS) NOTES:

FLOW

GPM FLUID TYPE # OF

PASSES

FOULING

FACTOR

E.W.T.

°F

L.W.T.

°F

CAPACITY

(TONS)

W.P.D.

(FT. HEAD)

E.W.T.

°F

L.W.T.

°F

CAPACITY

(TONS)

W.P.D.

(FT. HEAD)

AMBIENT

ICE BUILD

°F

AMBIENT

ICE MELT

°F

NO. OF

FANS

FAN FLA

(EA) TYPE

NUMBER

OF

COMP.

RLA

(EACH) TYPE FLOW (GPM)

TOTAL HEAD

PRESSURE

(FT H20)

MOTOR

(HP) TYPE NUMBER OF

CIRCUITS

CHARGE PER

CIRCUIT

(LBS)

VOLTS /

PHASE M.C.A. M.O.P.

ACCH-1 TRANE ACR-C-440 AIR COOLED 440 800

30%

ETHYLENE

GLYCOL

2 0.0001 31.72 22.00 294.8 56.3 56.12 42.00 430.9 55.1 85 95 18 2.7 SCREW 3

251.8 195.7 242.1

TACO 800 125 40 R-513A 2 366 / 177 480 / 3 856.8 1,000 30,500 1 - 7

NOTES:

1. PROVIDE WITH LIQUID, DISCHARGE AND SUCTION LINE SHUT-OFF VALVES

2. PROVIDE A SINGLE POINT DISCONNECT SWITCH WITH CIRCUIT PROTECTION

3. PROVIDE WITH PHASE & UNDER/OVER VOLTAGE PROTECTION

4. PROVIDE A FIVE YEAR COMPRESSOR PARTS WARRANTY

5. PROVIDE A RUBBER IN SHEAR ISOLATOR KIT

6. PUMP PACKAGE SHALL BE EQUIPPED WITH:

A. SINGLE TACO 40HP PUMP WITH VFD FOR BALANCING

B. TYPE INLET STRAINER

C. COMBINATION TRIPLE-DUTY OUTLET VALVE HAVING A DRIP-TIGHT DISCHARGE SHUTOFF VALVE, NON-SLAM CHECK VALVE, AND FLOW THROTTLING VALVE D. COMBINATION SUCTION GUIDE WITH FLOW STABILIZING OUTLET VANES AND STAINLESS STEEL STRAINER WITH A DISPOSABLE FINE-MESH STRAINER FOR START-UP E. FACTORY POWER AND CONTROL WIRING FROM THE CHILLER TO THE PUMP PACKAGE CONTROL PANEL

F. THERMAL DISPERSION TYPE FLOW SWITCH MOUNTED AND WIRED

G. INTERCONNECTING SCHEDULE 40 PIPING WITH VICTAULIC COUPLINGS

H. INSULATION OF ALL COLD SURFACES

COOLING TOWER SCHEDULE

MARK MANUFACTURER MODEL NUMBER TYPE

CAPACITY

(TONS)

AIR DATA FAN DATA ELECTRICAL WATER DATA DIMENSIONS

WEIGHT

(LBS) NOTES:

CFM

E.W.B.

(°F) # HP VOLTS /

PHASE FLA MOCP

FLOW

(GPM)

E.W.T.

(°F)

L.W.T.

(°F)

STATIC LIFT

(FT.HD.)

WIDTH

(FT.)

HEIGHT

(FT.) LENGTH (FT.)

CT-1 MARLEY NC8405QAN1 CROSSFLOW 434 113,060 77.2 1 20 460 / 3 33 70 1,300 93.5 84.5 12.3 19'-11" 11'-11" 9'-10" 20,200 1-12

(APPROVED EQUAL: EVAPCO, BALTIMORE AIR COIL, TOWER TECH)

NOTES:

1. PROVIDE WITH WELDED TYPE 304 STAINLESS STEEL WATER BASIN.

2. PROVIDE WITH LOW SOUND FAN ASSEMBLY.

3. PROVIDE WITH 8"Ø BOTTOM INLET AND 14"Ø BOTTOM OUTLET PIPING CONNECTIONS & 10"Ø BYPASS CONNECTION

4. VARIABLE SPEED FAN(S) WITH CONTROLLER(S).

5. PROVIDE AND INSTALL UNIT ON MANUFACTURER RECOMMENDED RESTRAINED SPRING ISOLATORS.

6. UNIT SHALL BE U.L. LISTED.

7. PROVIDE O.S.H.A. APPROVED SERVICE PLATFORM WITH HAND RAIL AND ACCESS LADDER.

8. PROVIDE VIBRATION CUT OUT SWITCH.

9. PROVIDE EXTENDED LUBRICATION LINES.

10. PROVIDE MECHANICAL, ELECTRIC MAKE-UP WATER CONTROL PACKAGE.

11. PROVIDE 5 YEAR FAN, SHAFT, AND INTERIOR WARRANTY.

12. PROVIDE TOTALLY ENCLOSED FAN MOTOR(S).

ENERGY RECOVERY VENTILATOR SCHEDULE

MARK MANUFACTURER MODEL NUMBER

SUPPLY FAN EXHAUST FAN SUMMER HEAT WHEEL

PERFORMANCE

WINTER HEAT WHEEL

PERFORMANCE PRE-HEAT COOLING COIL HOT WATER HEATING COIL FILTERS

WEIGHT

(LBS)

ELECTRICAL

ACCESSORIES

SA / OA

(CFM)

ESP.

(IN WG) BHP HP VFD

EA

(CFM)

ESP.

(IN WG) BHP HP VFD

OA °F

(DB / WB)

RAT °F

(DB / WB)

LAT °F

(DB / WB)

E.A.T.

DB / WB

(°F)

R.A.T.

DB / WB

(°F)

L.A.T.

DB / WB

(°F)

E.A.T.

DB

(°F)

L.A.T.

DB

(°F)

E.W.T.

(°F)

L.W.T.

(°F)

TOTAL

(MBH)

WATER

FLOW

(GPM)

E.A.T.

DB

(°F)

L.A.T.

DB

(°F)

E.W.T.

(°F)

L.W.T.

(°F)

TOTAL

(MBH)

PRE.

SA & EA

FINAL

SA

VOLT /

PHASE MCA MOP

ERV-1 ANNEXAIR ERU-E-05-HW-EW-HW-NC-4-S-B 6,100 1.5 6.54 8.0 YES 6,100 0.75 3.86 4.5 YES 86.2 / 76.7 72 / 63 75.0 / 64.5 0 / -1 70 / 63 40.3 / 40.1 -10 10 42 34 135 37 52.7 90 160 135 251 2"

MERV 10

4"

MERV 13 2,300 460 / 3 17 25 1, 2

ERV-2 ANNEXAIR ERU-E-05-HW-EW-HW-NC-4-S-B 6,100 1.5 6.54 8.0 YES 6,100 0.75 3.86 4.5 YES 86.2 / 76.7 72 / 63 75.0 / 64.5 0 / -1 70 / 63 40.3 / 40.1 -10 10 42 34 135 37 52.7 90 160 135 251 2"

MERV 10

4"

MERV 13 2,300 460 / 3 17 25 1, 2

(APPROVED EQUAL: TRANE, AAON, DAIKIN APPLIED, VALENT, VENMAR)

NOTES:

1. UNIT TO BE MOUNTED ON EXISTING STEEL SUPPORT BEAMS.

2. ENTHALPY WHEEL HAS A 1/4 HP MOTOR AND SHALL MODULATE FOR FROST CONTROL.

ROOF TOP UNIT SCHEDULE

MARK MANUFACTURER MODEL

NUMBER

MINIMUM

OUTSIDE

AIR

(CFM)

SUPPLY FAN SECTION COOLING COIL - (BASED ON 30% ETHYLENE GLYCOL) HEATING COIL FILTERS ELECTRICAL

WEIGHT

(LBS) NOTES

# OF

FANS

TOTAL

FAN

AIRFLOW

(CFM)

E.S.P.

(IN W.G.)

TOTAL

BHP

(EA)

RPM

(EA)

HP

(EA)

FACE

VEL.

(FPM)

COIL

ROWS

ENT

AIR

DB

(°F)

ENT

AIR

WB

(°F)

LVG

AIR

DB

(°F)

LVG

AIR

WB

(°F)

AIR

PD

(IN WG)

SENSIBLE

CAPACITY

(MBH)

TOTAL

CAPACITY

(MBH)

FLOW

RATE

(GPM)

ENT

WATER

TEMP

(°F)

LVG

WATER

TEMP

(°F)

FACE

VEL.

(FPM)

OF

ROWS

ENT

AIR

DB

(°F)

LVG

AIR

DB

(°F)

AIR

PD

(IN WG)

TOTAL

CAPACITY

(MBH)

FLOW

RATE

(GPM)

ENT

WATER

TEMP

(°F)

LVG

WATER

TEMP

(°F)

MAX

FACE

VEL

(FPM)

FILTER EFFICIENCY

CIRCUIT #1 (SUPPLY

FAN+CONTROLS+LIGHTS+SWITCH) CIRCUIT #2 RECEPTACLE

PRE FINAL VOLTS /

PHASE F.L.A. M.C.A. M.O.P. VOLTS /

PHASE F.L.A. M.C.A. M.O.P.

RTU-C1

THRU

RTU-C10

TRANE CSAA004 1,800 1 1,800 3.5" 2.46 4499 3 399 6 85 76 54 53.9 0.6 62.19 136.73 25.5 42 54.2 399 2 0 78 0.113 152.26 13.4 180 157.3 324 (2) 2" PLEATED /

MERV 8

(2) 12" BAG

CARTRIDGE 65%

MERV 13

480 / 3 6.1 A 7.3 15 115 / 1 8.0 A 10.0 15 2,300 1 - 9

RTU-C12,

RTU-C18

RTU-C20,

RTU-C22

TRANE CSAA004 1,800 1 1,800 3.5" 2.46 4499 3 399 6 85 76 54 53.9 0.6 62.19 136.73 25.5 42 54.2 399 2 0 78 0.113 152.26 13.4 180 157.3 324 (2) 2" PLEATED /

MERV 8

(2) 12" BAG

CARTRIDGE 65%

MERV 13

480 / 3 6.1 A 7.3 15 115 / 1 8.0 A 10.0 15 2,300 1 - 9

(APPROVED EQUAL: CARRIER, VENTROL, VENMAR, DAIKIN, SEASONS 4, CLIMATE CRAFT)

NOTES:

1. SUPPLY AIR MOTOR SHALL BE DIRECT DRIVE, CONTROLLED BY A VARIABLE FREQUENCY DRIVE.

2. PROVIDE 5% LINE REACTORS FOR VARIABLE SPEED DRIVE.

3. PROVIDE INDIVIDUAL HOT WATER AND CHILLED WATER COILS.

4. ALL DAMPERS WITHIN THE UNIT ARE TO BE PROVIDED BY UNIT MANUFACTURER.

5. PROVIDE HINGED ACCESS DOORS.

6. HEATING HOT WATER DATA BASED ON (100% WATER) AND CHILLED WATER DATA BASED ON (30% ETHYLENE GLYCOL)

7. DOUBLE WALL, THERMALLY BROKEN INSULATED CABINET WITH 2" FOAM INJECTED r-13 INSULATION.

8. PROVIDE CUSTOM ADAPTOR CURB TO MOUNT NEW UNIT ON EXISTING CURB.

9. PROVIDE MARINE LIGHT IN THE FAN, COILING COIL, HEATING COIL AND MIXING BOX SECTIONS.

THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO

DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD

VER IF Y A LL W O R K AN D S HAL L N O TI FY T HE A RC HI TE CT

IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS

BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE

CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR

SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN

ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING

CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF

WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED

BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.

MEEC JOB # 26-0029

JORDAN

KOENIG

ENGINEER

6201059789 No.

L I C

E N

S E D

P R O F E S S I O N A L E NG

I N

E E

R

S T

DAT (AI)

MAD (AO)

CLG (AO)

HSP ALM (BI)

HSP INTLK (HDW)

SP CO2 (AI)

RAH (AI)

SA SD (HDW)

SA HUM (AI)

OAH (AI)

OAT (AI) MA LLT (BI)MAT (AI)

SAF (BI)

RAT (AI)

SPT (AI)

SPT SP (AI) SPH (AI)

CC LAT (AI)

FIL ALM (AI)

RH LAT (AI)

FIL ALM (AI)

SAF (BO)

RA SD (HDW)

HTG (AO) SAF (AO)

RHW T (AI)

CHW T (AI)

T - 22

ACT - 12

V - 12

D - 13

DPS - 11

CO2 - 2

D - 14

H - 6

SD - 3

OA

H - 9

VFD - 6

H - 7T - 8 LLT - 8

DA

T - 16

RA

DPT- 9

T - 6

T-2

H - 3

T - 18

DPT - 45

T - 20

DPT - 13

R - 3

SD - 1

V - 15

VFD - 7

SKT - 24

TT

Points List: AIR HANDLING UNIT [QTY: 14]

Point Name POINTS ALARMS

G R

A

PH

IC

A

N A

LO

G

H A

R D

W A

R E

IN

PU

T (A

I) B

IN

A

R Y

H A

R D

W A

R E

IN

PU

T (B

I) A

N A

LO

G

H A

R D

W A

R E

O U

TP

U

T (A

O

B

IN

A R

Y H

A R

D W

A R

E O

U

TP

U T

(B O

SO

FT

W

A R

E

PO

IN

T

(S

FT

H

A R

D W

A R

E

IN

TE

R

LO

C

K (H

D W

W

IR

EL

ES

S

(W

LS

N

ET

W

O R

K (N

ET

H

IG

H A

N A

LO

G

L

IM

IT

LO

W A

N A

LO

G

L

IM

IT

B

IN

A

R Y

LA

TC

H D

IA

G

N O

ST

IC

SE

N

SO

R

F A

IL

C

O M

M U

N

IC

A

TI

O N

F A

IL

COIL LEAVING AIR LOW TEMP

CUTOUT ALARM

LLT

X X

COOLING COIL LEAVING

TEMPERATURE

CC LAT

X X X X X

COOLING OUTPUT COMMAND

CLG

X X

DISCHARGE AIR TEMPERATURE

DAT

X X X X X

DISCHARGE AIR STATIC PRESSURE

LOCAL

DA SP

X X X X X

ENERGY WHEEL SPEED COMMAND

EW SPD

X X

FINAL FILTER ALARM

FIL ALM

X X

FILTER ALARM

FIL ALM

X X

HEATING OUTPUT COMMAND

HTG

X X

HIGH STATIC ALARM

HSP ALM

X X X X

HIGH STATIC ALARM INTERLOCK

HSP INTLK

X

MIXED AIR DAMPER COMMAND

MAD

X X

MIXED AIR LOW TEMPERATURE

CUTOUT ALARM

MA LLT

X X

MIXED AIR TEMPERATURE LOCAL

MAT

X X X X

OUTDOOR AIR RELATIVE HUMIDITY

LOCAL

OAH

X X

OUTDOOR AIR TEMPERATURE

LOCAL

OAT

X X

REHEAT LEAVING COIL

TEMPERATURE LOCAL

RH LAT

X X X X X

REHEAT OUTPUT COMMAND

RH

X X

RETURN AIR HUMIDITY LOCAL

RAH

X X X

RETURN AIR TEMPERATURE LOCAL

RAT

X X

RETURN SMOKE DETECTOR INPUT

RA SD

X

SPACE CO2 CONCENTRATION LOCAL

SP CO2

X X X

SPACE HUMIDITY LOCAL

SPH

X X X

SPACE TEMPERATURE LOCAL

SPT

X X X X X

SPACE TEMPERATURE SETPOINT

LOCAL

SPT SP

X X

SUPPLY AIR HUMIDITY LOCAL

SA HUM

X X X X X

SUPPLY FAN SPEED COMMAND

SAF

X X

SUPPLY FAN START STOP COMMAND

SAF

X X

SUPPLY FAN STATUS

SAF

X X

SUPPLY SMOKE DETECTOR INPUT

SA SD

X

BAS COMMUNICATION STATE

BAS COM

X X

DISCHARGE AIR COOLING SETPOINT

DA CL SP

X

DISCHARGE AIR HEATING SETPOINT

DA HT SP

X

MAINTENANCE REQUIRED

MNT REQ

X X

MIXED AIR TEMPERATURE LOW LIMIT

SETPOINT

MA LLT STPT

X

OCCUPIED COOLING SETPOINT

OCC CLG STPT

X X

OCCUPIED HEATING SETPOINT

OCC HTG STPT

X X

SUPPLY FAN FAILURE

SF FAIL

X X X

UNOCCUPIED COOLING SETPOINT

UNOCC CLG STPT

X X

UNOCCUPIED HEATING SETPOINT

UNOCC HTG STPT

X X

LEAVING CHILLED WATER

TEMPERATURE

CHW T

X X

LEAVING PREHEAT WATER

TEMPERATURE

PHW T

X X

LEAVING REHEAT WATER

TEMPERATURE

RHW T

X X

SEQUENCE OF OPERATION: ROOF TOP UNITS (RTU-C1, RTU-C2, RTU-C3, RTU-C4, RTU-C5, RTU-C6, RTU-C7, RTU-C8, RTU-C9, RTU-C10, RTU-12, RTU-C18, RTU-C20, RTU-C22)

BUILDING AUTOMATION SYSTEM INTERFACE:

THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED BYPASS, MORNING WARM-UP/PRE-COOL, OCCUPIED/UNOCCUPIED AND HEAT/COOL MODES. IF A BAS IS NOT PRESENT, OR COMMUNICATION IS LOST WITH THE BAS THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND

SETPOINTS.

OCCUPIED:

DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY AND THE MIXED AIR DAMPERS SHALL OPEN TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS. IN THE COOLING MODE THE CHILLED WATER VALVE SHALL MODULATE TO CONTROL THE ACTIVE SPACE TEMPERATURE SETPOINT. IN THE HEATING MODE THE HOT WATER VALVE SHALL MODULATE TO CONTROL THE ACTIVE SPACE TEMPERATURE SETPOINT. IF THE SPACE TEMPERATURE SENSOR FAILS, THE COOLING AND HEATING SHALL FALLBACK TO CONTROL TO THE DISCHARGE AIR TEMPERATURE SETPOINT OF 70 DEG F (ADJ.) AND AN ALARM SHALL BE ANNUNCIATED AT THE BAS. THE SUPPLY FAN SHALL BE DISABLED, THE CHILLED WATER VALVE SHOULD CLOSE, THE HEATING VALVE SHOULD CLOSE, THE OUTDOOR AIR SHOULD CLOSE, AND AN ALARM SHOULD ANNUNCIATE AT THE BAS.

UNOCCUPIED:

DURING THE UNOCCUPIED PERIODS, THE SUPPLY FAN SHALL BE DISABLED, THE OUTSIDE AIR DAMPER SHALL CLOSE, THE MECHANICAL COOLING SHALL BE DISABLED, THE MECHANICAL HEATING SHALL BE DISABLED, TO CONSERVE ENERGY. WHEN THE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED COOLING SETPOINT OF 85

DEG F (ADJ.) THE SUPPLY FAN SHALL START, THE OUTDOOR DAMPER SHALL REMAIN CLOSED,

THE OUTDOOR DAMPER SHALL MODULATE IF ECONOMIZING IS ENABLED AND REMAIN CLOSED IF NOT ECONOMIZING, AND THE MECHANICAL COOLING SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED COOLING SETPOINT OF 85.0 DEG. F (ADJ.) MINUS THE UNOCCUPIED DIFFERENTIAL OF

4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE OUTDOOR DAMPER SHALL REMAIN CLOSED, AND THE MECHANICAL COOLING SHALL BE DISABLED. WHEN THE SPACE TEMPERATURE IS BELOW THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL START, THE OUTDOOR DAMPER SHALL REMAIN CLOSED, AND THE MECHANICAL HEATING SHALL BE ENABLED. WHEN THE SPACE TEMPERATURE IS ABOVE THE UNOCCUPIED HEATING SETPOINT OF 60.0 DEG. F (ADJ.) PLUS THE UNOCCUPIED DIFFERENTIAL OF

4.0 DEG. F (ADJ.) THE SUPPLY FAN SHALL STOP, THE OUTDOOR DAMPER SHALL REMAIN CLOSED, AND THE

MECHANICAL HEATING SHALL BE DISABLED.

OPTIMAL START:

THE BAS SHALL MONITOR THE SCHEDULED OCCUPIED TIME, OCCUPIED SPACE SETPOINTS AND SPACE

TEMPERATURE TO CALCULATE WHEN THE OPTIMAL START OCCURS.

OPTIMAL STOP:

THE BAS SHALL MONITOR THE SCHEDULED UNOCCUPIED TIME, OCCUPIED SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL STOP OCCURS. WHEN THE OPTIMAL STOP MODE IS ACTIVE THE UNIT CONTROLLER SHALL SWITCH TO THE UNOCCUPIED MODE. OUTSIDE AIR DAMPER SHALL REMAIN

ENABLED TO PROVIDE MINIMUM VENTILATION.

OCCUPIED BYPASS:

THE BAS SHALL MONITOR THE STATUS OF THE ON AND CANCEL BUTTONS OF THE SPACE TEMPERATURE SENSOR. WHEN AN OCCUPIED BYPASS REQUEST IS RECEIVED FROM A SPACE SENSOR, THE UNIT SHALL TRANSITION FROM ITS CURRENT OCCUPANCY MODE TO OCCUPIED BYPASS MODE AND THE UNIT SHALL

MAINTAIN THE SPACE TEMPERATURE TO THE OCCUPIED SETPOINTS (ADJ.).

HEAT/COOL MODE:

WHEN THE SPACE TEMPERATURE RISES ABOVE THE OCCUPIED COOLING SETPOINT THE MODE SHALL TRANSITION TO COOLING. WHEN THE SPACE TEMPERATURE FALLS BELOW THE OCCUPIED HEATING SETPOINT THE MODE SHALL TRANSITION TO HEATING. WHEN THE SPACE TEMPERATURE IS BELOW THE OCCUPIED COOLING SETPOINT AND ABOVE THE OCCUPIED HEATING SETPOINT THE MODE SHALL REMAIN IN ITS LAST STATE. IF THE SPACE TEMPERATURE SENSOR FAILS, THE MODE SHALL DEFAULT TO HEATING AND AN ALARM

SHALL ANNUNCIATE AT THE BAS.

MORNING WARM-UP MODE:

DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING SETPOINT A MORNING WARM-UP MODE SHALL BE ACTIVATED. WHEN MORNING WARM-UP IS INITIATED THE UNIT SHALL ENABLE THE HEATING AND FAN(S). THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED. WHEN THE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO THE

OCCUPIED MODE.

DAYTIME WARM-UP CONTROL:

DURING OCCUPIED PERIODS, WHEN THE SPACE TEMPERATURE IS BELOW THE DAYTIME WARM-UP INITIATE SETPOINT, A DAYTIME WARM-UP SEQUENCE SHALL BE ACTIVATED. THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS, AND THE HEATING SHALL ENABLE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE HEATING SETPOINT. DAYTIME WARM-UP SHALL TERMINATE

WHEN THE AVERAGE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT.

PRE-COOL MODE:

DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT, PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL IS INITIATED THE UNIT SHALL ENABLE THE FAN AND COOLING OR ECONOMIZER. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE SPACE TEMPERATURE REACHES OCCUPIED COOLING SETPOINT (ADJ.), THE UNIT SHALL TRANSITION TO

THE OCCUPIED MODE.

SUPPLY FAN:

THE SUPPLY FAN SHALL BE OFF IN THE UNOCCUPIED MODE. WHEN THE CONTROLLER IS IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY. THE UNIT CONTROLLER SHALL VARY THE SUPPLY FAN SPEED TO OPTIMIZE MINIMUM FAN SPEED IN ALL COOLING AND HEATING MODES. IF THE SUPPLY FAN FAILS TO PROVE STATUS FOR 30 SECONDS (ADJ.), THE FAN SHALL BE COMMANDED OFF, THE OUTSIDE AIR DAMPER SHALL CLOSE, COOLING SHALL BE DISABLED, ALL HEATING SHALL BE DISABLED, AND AN ALARM SHALL

ANNUNCIATE AT THE BAS. A MANUAL RESET SHALL BE REQUIRED TO RESTART THE FAN.

A HARDWIRED, HIGH STATIC PRESSURE CUT-OFF SWITCH SHALL BE ELECTRICALLY INTERLOCKED WITH THE VARIABLE SPEED DRIVE. IF THE HIGH STATIC PRESSURE CUT-OFF SWITCH IS TRIPPED THE FAN SHALL BE COMMANDED OFF, HEATING SHALL BE DISABLED, COOLING SHOULD BE DISABLED, THE OUTSIDE AIR DAMPER

SHALL CLOSE,

AND AN ALARM SHALL ANNUNCIATE AT THE BAS. A MANUAL RESET OF THE HIGH STATIC PRESSURE CUT-OFF

SWITCH SHALL BE REQUIRED TO RESTART THE FAN.

LOW LIMIT TEMPERATURE CONTROL:

THE INITIAL DAMPER OPENING RATE SHALL BE LIMITED TO 2% PER MINUTE (ADJ.) UNTIL THE DAMPER HAS REACHED ITS MINIMUM VENTILATION POSITION. THE OUTSIDE AIR DAMPER SHALL MODULATE TO A POSITION LESS THAN THE MINIMUM DAMPER POSITION IF THE MIXED AIR TEMPERATURE DROPS BELOW 45.0 DEG. F (ADJ.).

IF THE MIXED AIR TEMPERATURE SENSOR FAILS AN ALARM SHALL ANNUNCIATE AT THE BAS AND THE OUTSIDE

AIR DAMPER SHALL CLOSE.

DISCHARGE AIR TEMPERATURE CONTROL: