BAISD LLC-Bay Campus Project # 2613 Interior Renovations Drawings.pdf

PDF 2 MB Posted

Attached to
Interior Renovations for Bay Arenac ISD LLC Bay
Solicitation number
RFP BAY 260000002017 1
Issued by
Bay County, Michigan

About this file

This is a set of interior renovation architectural and engineering drawings for Bay Arenac ISD's Living and Learning Center located at 1435 W. Center Road in Essexville, Michigan. The project, designated as Project No. 2613, was prepared by TSSF Architects, Inc. (122 N. Washington Avenue, Saginaw, Michigan) with consulting engineering services provided by KTS Engineering Group. The drawings dated May 1, 2026, include comprehensive architectural, mechanical, plumbing, and electrical plans for interior renovations affecting multiple spaces including classrooms (Room 100), offices (Rooms 103-105), open office (Room 102), and toilet facilities (Room 101). The renovation scope encompasses demolition and reconfiguration of existing partition walls, installation of new HVAC ductwork and diffusers, plumbing modifications for toilet facilities, and compliance with accessibility standards per Michigan Barrier Free Code and ADA requirements. The mechanical work includes supply and return air ductwork sizing, exhaust fan specifications, and thermostat relocation, while plumbing work addresses fixture installations and waste line routing.

The technical specifications establish requirements for mechanical and plumbing contractors to coordinate with all trades, verify field conditions, and maintain compliance with Michigan Building Code, Michigan Plumbing Code, Michigan Mechanical & Energy Code, and applicable OSHA standards. The mechanical contractor is responsible for hiring a licensed fire protection contractor to remove and relocate sprinkler heads in accordance with NFPA 13. Testing and balancing work must be performed by a NEBB or NBI certified firm with submission of final certified reports. All contractors must provide one-year warranties on their work, submit shop drawings for approval, and maintain as-built documentation. The drawings specify detailed duct insulation requirements based on ASHRAE 90.1 (2019 Edition) for Climate Zone 5A, piping insulation thickness standards for heating systems, and fixture schedules including diffuser and exhaust fan specifications. The project requires coordination among multiple trades to resolve conflicts related to mechanical, plumbing, electrical, and structural elements while maintaining headroom and accessibility compliance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INTERIOR RENOVATIONS FOR:

1435 W. CENTER RD.

BAY ARENAC ISD

ESSEXVILLE, MICHIGAN 48732

Architect:

122 N. WASHINGTON AVENUE

TSSF ARCHITECTS, INC.

SAGINAW , MICHIGAN

SITE

LOCATION MAP

DATE: May 1, 2026

PROJECT NO. 2613

DRAWING INDEX:

ARCHITECTURAL

COVER

A2.0

MECHANICAL

M0.0 M0.1

PLUMBING

P0.0

PD1

Mechanical / Electrical:

ELECTRICAL

E0.0 E2.0

A9.0

LIVING AND LEARNING CENTER

E3.0 E5.0 E6.0

CODE COMPLIANCE BLDG DATA

EXIST. OCCUPANT LOAD

BUILDING CODE COMPLIANCE

D2.0

A0.3 A0.4

A0.2

ABBREVIATIONS:

EQ

.E

Q.

INTERIOR ELEVATION LOCATOR

BUILDING SECTION LOCATOR

DETAIL/SECTION LOCATOR

Reference Symbols

DETAIL AND SECTION IDENTIFICATION

SO

AP

D

IS

H

TO

W

EL

B

AR

HO

OK

S

SH

EL

F

SA

NI

TA

RY

NA

PK

IN

V

EN

DO

R

ME

DI

CI

NE

CA

BI

NE

T

HA

ND

D

RY

ER

CU

P

DI

SP

EN

SE

R

FA

CI

AL

TI

SS

UE

DI

SP

EN

SE

R

TO

W

EL

DI

SP

EN

SE

R

RE

CE

PT

AC

LE

W

AS

TE

RE

CE

PT

AC

LE

SH

OW

ER

HE

AD

VA

LV

ES

FIR

E

HO

SE

EX

TIN

GU

IS

HE

R

OR

C

OM

BI

NA

TIO

N

CA

BI

NE

T

SA

FE

TY

S

W

ITC

H

MO

TO

R

ST

AR

TE

RS

EL

EC

TR

IC

PA

NE

L O R

CA

BI

NE

T

FIR

E

HO

SE

RA

CK

O R

VA

LV

E

FIR

E

EX

TIN

GU

IS

HE

R

PO

W

ER

PA

NE

L

MI

N

EW

C

OR

DR

IN

KI

NG

FO

UN

TA

IN

TH

ER

MO

ST

AT

LA

V

ME

DI

CI

NE

CA

BI

NE

T

HA

IR

D

RY

ER

TO

W

EL

B

AR

SH

EL

F

EDGE OF

OUTLET

OR WALL

W/OUTLET

SE

AT

C

OV

ER

DI

SP

EN

SE

R

18" MIN

TO

W

EL

DI

SP

EN

SE

R

OR

M

UL

TI-

PU

RP

OS

E

UN

IT

MO

P

ST

RI

P

SH

EL

F

HA

IR

DR

YE

R

SH

OW

ER

CU

RT

AI

N

RO

D

MI

RR

OR

OR

M

IR

RO

R

SH

EL

F

PU

SH

B

UT

TO

N

SW

ITC

H

OR

W

AL

L O

UT

LE

T

AB

OV

E

CO

UN

TE

R

HO

OK

S

MI

RR

OR

OR

M

IR

RO

R

SH

EL

F

MI

N.

MA

X.

" M

IN

IN

TE

RI

OR

W

AL

L M

TD

RO

OM

SI

GN

AG

E

BL

DG

EN

TR

AN

CE

SY

MB

OL

O

F

AC

CE

SS

IB

ILI

TY

EX

TE

RI

OR

W

AL

L

MT

D

SI

GN

HV

AC

C

ON

TR

OL

S

SI

GN

AG

E

OR

P

LA

QU

E W

/ T

AC

TIL

E

CH

AR

AC

TE

R

MI

N

12"

MIN

MI

NMI

N

MI

N

" M

IN

TO

B

OT

T

" M

AX

TO

TO

P

" T

O

" M

AX 80

MA

X

4"

ME

N)

W

OM

EN

" T

O

" T

O

" M

AX

EW

C

OR

DR

IN

KI

NG

FO

UN

TA

IN

SP

EA

KE

R

OR

FI

RE

AL

AR

M

DE

VI

CE

CL

OC

K

OU

TL

ET

TO

P

OF

C

AB

IN

ET

VA

LV

E C

A B

IN

ET

W

AL

L A

ND

A

LL

EM

ER

GE

NC

Y

PH

ON

ES

EL

EC

TR

IC

, O

UT

LE

T

TE

LE

PH

ON

E

OR

CA

BL

E

JA

CK

FIR

E

AL

AR

M

PU

LL

S

TA

TIO

N

6'- 8"

TO

BO

TT

OM

O F D

EV

IC

E

MI

N.

K

NE

E

SP

AC

E

MI

N.

TO

O

RI

FIC

E

MA

X.

TO

O

RI

FIC

E

HI

GH

/LO

W

E W

C

OR

D

RI

NK

IN

G

FO

UN

TA

IN

"CL

EL

EC

TR

IC

PA

NE

L O R

CA

BI

NE

T

COIN SLOT

MA

X

TO

BO

TT

S

HE

LF

24" MAX - 15" MIN

8" MIN

MA

IL

DR

OP

S

LO

T

IN

TE

RI

OR

HO

SE

B

IB

B

MI

N

12"

MIN

MI

N

EX

TE

RI

OR

PO

ST

M

TD

VA

N

AC

CE

SS

IB

LE

SI

GN

MI

N

12"

MIN

PARKING SPACE SIGNAGE

CL

EX

TE

RI

OR

PO

ST

M

TD

SI

GN

18" MIN

Mounting Dimensions

UT

ILI

TY

SH

EL

F

W

AL

L M

OU

NT

ED

SO

AP

D

IS

PE

NS

ER

TIL

T

MI

RR

OR

ACCESSORIES LEGEND

U.

N.

O.

FIL

M

ILL

UM

IN

AT

OR

SE

E

EL

EC

TR

IC

AL

3"

FIL

M

ILL

UM

IN

AT

OR

VIEWER

OVER

VIEWER

COUNTER

U.

N.

O.

CO

RN

ER

GU

AR

D

X-

RA

Y

VI

EW

B

OX

C

LO

C K

ME

D.

G

AS

AL

AR

M

PA

NE

L

ME

D.

G

AS

A

LA

RM

PA

NE

L A

T

CO

UN

TE

R

ME

D.

G

AS

VA

LV

E

BO

X

ME

D.

G

AS

OU

TL

ET

S

DI

AP

ER

CH

AN

GI

NG

ST

AT

IO

N

SE

E

IN

TE

RI

OR

EL

EV

AT

IO

NS

FO

R

SP

EC

IA

L

CO

ND

ITI

ON

S

X

AX.X

X

AX.X

X

AX.X

Ax.x

KEY NOTE

WINDOW SYMBOL

DOOR SYMBOL

WALL TYPE SYMBOL

CL

773231153029221010

11 12

17 9

9 2 8 18 20

24 25 29 281

20"

42" 12"

4"

" 24

"-3

6"

36"6" 18"

6" 36" 18"

5" MAX

GR

AB

B

AR

MA

X

36" MAX

GR

AB

B

AR

MF

G

ST

AN

D

ST

D

W

AT

ER

C

LO

SE

T W

AL

L M

TD

ST

D

W

AT

ER

C

LO

SE

T

FL

OO

R

MT

D

" 24

36"6" 18"

GR

AB

B

AR

FL

OO

R

MT

D W

AT

ER

C

LO

SE

T

W

AL

L M

TD

W

AT

ER

C

LO

SE

T

20"

42" 12"

4"

36" MAX

GR

AB

B

AR

GR

AB

B

AR

MF

G

ST

AN

D

UN

O

CL

R

CL

R

SA

NI

TA

RY

NA

PK

IN

DI

SP

OS

AL

W

AT

ER

C

LO

SE

T (W

/ D

IV

ER

TE

R

FL

US

H

CO

NT

RO

L)

SA

NI

TA

RY

NA

PK

IN

DI

SP

OS

AL

TO

ILE

T

PA

PE

R

HO

LD

ER

TO

ILE

T

PA

PE

R

HO

LD

ER

3 3 26 17 33 26 17 3

"-4

1"

33" w/ NO TANK

"-4

1"

33" w/ NO TANK

39"-41"39"-41"

"-3

6"

"-3

6"

"-3

6"

BA

Y

AR

EN

AC

IS

D

IN

TE

R

IO

R

R

EN

O

VA

TI

O

N S

FO

R

LI

VI

N G

A N

D L

EA

R

N

IN

G C

EN

TE

R

N

. W

AS

H

IN

G

TO

N A

VE

N

U E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

m ax m ax

>20-25 max20 max

(a) (b) m in m ax

42 min m in

X < 48

42 min

X < 48

36 min 36 min m in

(a) 180 degree turn (b) 180 Degree Turn (Exception) m in

48 min 24 max m in m in m in

24 max

10 max m ax m ax m ax m ax

> 10-24 max

(a) (b)

10 max m ax m in

(f) Latch Approach, Pull Side m in

* 24 min m in

22 min

(e) Hinge Approach, Push Side

42 min m in

(d) Hinge Approach, Pull Side

36 min 60 m in

(c) Hinge Approach, Pull Side m in12 min *

(b) Front Approach, Push Side m in

18 min

(a) Front Approach, Pull Side

(g) Latch Approach, Push Side, 24 min m in m in12 min

X > 8 m in

X > 824 min m in

(c) Stop or Latch Approach

22 min m in

(b) Pocket or Hinge Approach m in

(a) Front Approach

48 min 48 min

(a) (b)

48 min

(c)

60 min

X

36 min

X

30 min

(a) Forward (b) Parallel

48 min m in m in

24 min m in

36 min

12 min 12 min

60 min base ar

60 min 67 min

(a) Forward Approach (b) Parallel Approach

SECTION 305.5: SECTION 305.7:SECTION 304.3: SIZE OF TURNING SPACE

(a) Circular (Existing Buildings)

(b) Circular (New Buildings)

(c) T-shaped (Existing Buildings)

SECTION 305.3:

CLEAR FLOOR SPACE POSITION OF CLEAR FLOOR SPACE MANEUVERING CLEARANCE IN AN ALCOVE

17-25

6 max m in

(a) Elevation (b) Plan

11 min m in

8 min

9 min 30 m in

25 max

SECTION 306.2:

TOE CLEARANCE

SECTION 306.3:

KNEE CLEARANCE

(a) Elevation (b) Plan

SECTION 308.2.1

UNOBSTRUCTED

SECTION 308.2.2

OBSTRUCTED

FORWARD REACH FORWARD REACH

SECTION 308.3.1

UNOBSTRUCTED

SIDE REACH

SECTION 308.3.2

OBSTRUCTED

SIDE REACH

SECTION 403.5

ACCESSIBLE ROUTE

SECTION 403.5.1

CLEAR WIDTH AT 180° TURN

(c) Folding Door(a) Hinged Door (b) Sliding Door

32 min 32 min32 min

SECTION 404.2.2

CLEAR WIDTH OF DOORWAYS

(d) Without Doors

36 min

SECTION 307.2

LIMITS OF PROTRUDING OBJECTS CLEAR WIDTH OF AN

4 max

X ³

X

SECTION 404.2.3.3

MANEUVERING CLEARANCE AT

SLIDING AND FOLDING DOORS

SECTION 404.2.3.2

MANEUVERING CLEARANCE AT MANUAL SWING DOORS

*If both Closer And Latch are provided *If both Closer And Latch are provided ** 48 min If both Closer And Latch are provided

12 min *

*48 min If both Closer And Latch are provided

*54 min If both Closer And Latch are provided

(b) Side Approach m in m in

(a) Front Approach

SECTION 404.2.3.4

MANEUVERING CLEARANCE AT

DOORWAYS W./O DOORS

SECTION 404.2.3.5

MANEUVERING CLEARANCE AT

RECESSED DOORS

m in

18 min

X > 8

(a) Pull Side (b) Push Side (c) Push Side, Door Provided w./ Both Closer and Latch

SECTION 404.2.5

TWO DOORS IN A SERIES

NOTE: THESE DETAILS SUPERCEDE ANY AND

ALL DESIGN LAYOUTS AS SHOWN ON THE

ARCHITECTURAL PLAN VIEWS. SHOULD ANY

DISCREPANCY BE DISCOVERED, NOTIFY

ARCHITECT IMMEDIATELY.

MASONRY WIRE

ANCHOR

MASONRY TEE

ANCHOR

WOOD STUD

ANCHOR

STEEL STUD

ANCHOR

EXISTING WALL

ANCHOR

ADJUSTABLE BASE

ANCHOR

WOOD STUD BASE

ANCHOR

TYPICAL MULLION SECTIONS

WITH BASE ANCHORS

PLASTER PARTITION

ANCHOR (CEILING STRUT

OPTIONAL)

ALSO AVAILABLE

WITH LATCH (OR

BOLT), WHICH IS

AUTOMATICALLY

RETRACTED WHEN

DOOR IS OPEN

TOP CASE

ROD 3/4" OR 1/2"

DIA. OR 3/4"

HALF-OVAL

STILE WIDTH 2" MIN.

(DOUBLE DOOR):

2-1/2" (SINGLE DOOR

WITH 1/2" STOP).

USUALLY 3-1/2" - 5"

1-3/4" MIN.

2-5/8" - 2-3/4"

PROJECTION

FROM STILE

STILE 1-3/4" MIN.;

CONSULT

MANUFACTURER

ALSO AVAILABLE

WITH LATCH (OR

BOLT), WHICH IS

RETRACTED WHEN

DOOR IS OPEN:

MUST USE WHEN

THERE IS NO

THRESHOLD

DOOR

THICKNESS

1-1/4" MIN.

USUAL PROJECTION

FROM DOOR 4-1/2" -

5"

DOOR EDGE (ONE

MANUFACTURER)

DOOR THICKNESS

1-3/4" MIN. LOCK

BACKSET 2-3/4"

USUAL THROW 5/8" (3/4"

THROW REQUIRED FOR

UNDERWRITERS LABEL)

AVAILABLE WITH

2-5/8" PROJECTION

PARALLEL

ARM

COVER

ARM

FASTENED

TO DOOR

TOP-JAMB

APPLICATION

MODERN TYPE

MODERN TYPE W./ COVER PUSH BAR

MORTISE TYPE

RIM TYPE (SURFACE)

SURFACE VERTICAL ROD TYPE CONCEALED VERTICAL ROD TYPE

(HOLLOW METAL DOOR)

54 min m in

(a) New Buildings

(b) Existing Buildings m in

20 min m in

40 min

12 min 12 min

64 min base

(d) T-shaped (New Buildings)

BA

Y

AR

EN

AC

IS

D

IN

TE

R

IO

R

R

EN

O

VA

TI

O

N S

FO

R

LI

VI

N G

A N

D L

EA

R

N

IN

G C

EN

TE

R

N

. W

AS

H

IN

G

TO

N A

VE

N

U E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

5 max 15 min

16-18 17-19

(a) WHEELCHAIR ACCESSIBLE

WATER CLOSETS

(b) AMBULATORY ACCESSIBLE

WATER CLOSETS

m in

18 min

60 min transfer side

36 min m in

60 min

(a) ADULT WALL HUNG

WATER CLOSET

(b) ADULT FLOOR MOUNTED WATER

CLOSETAND CHILDREN'S WATER

CLOSET

60 min m in

(a) ELEVATION

ADULT

9 min

6 min partition

6 min

6 min

6 min

(b) ELEVATION

CHILDREN

12 min partition

35-37 m in m in

17 max

13½ min 13½ min length of bathtub 12 min m in control end wall head end wall back wall control end wall back wall head end wall length of bathtub

48 min m in control wall back wall seat wall

60 min m in m ax m ax

6 max6 max side wall side wall back wall

5 max 15 min m ax C hi ld re n

Ad ul t

SECTION 602.5

DRINKING FOUNTAIN SPOUT

(a) Plan (b) Elevation

SECTION 604.2

WATER CLOSER LOCATION

CL CL

SECTION 604.3

m ax

CL

OTHER FIXTURES NOT

ALLOWED IN THIS

AREA

-1

SECTION 604.4

WATER CLOSET SEAT HEIGHT

-4

SECTION 604.5.1

-3

18 m in

12 42 min

54 min

39-41

CL

CL

SECTION 604.5.2

42 min

6 max

-3

CL

42 max

1/

2" m in m in

SECTION 604.7

DISPENSER OUTLET LOCATION

max min m in m ax

(a) PROTRUDING DISPENSER

BELOW GRAB BAR

(b) PROTRUDING DISPENSER

ABOVE GRAB BAR

max min m ax

(c) RECESSED DISPENSER m in18

SECTION 604.9.2 SECTION 604.9.2.3

60 min.

m in

ALTERNATE WHEELCHAIR

TOILET COMPARTMENT

WHEELCHAIR ACCESSIBLE

TOILET COMPARTMENT

SIZE OF CLEARANCE

FOR WATER CLOSET

SIDE-WALL GRAB BAR

FOR WATER CLOSET

REAR-WALL GRAB BAR

FOR WATER CLOSET

56 min m in

DOOR SHALL NOT

SWING INTO MIN.

AREA OF THE

COMPARTMENT

59 min

(WALL MOUNTED) ADULT

(FLR MOUNTED) ADULT

(WALL & FLR MOUNTED) CHILDREN

SECTION 604.9.2.3

WHEELCHAIR COMPARTMENT

DOORS SWINGING INTO TOILET

COMPARTMENT

4 max m in m ax

56 min

SECTION 604.9.3.1

DOOR OPENING LOCATION

(a) DOOR SWINGING ON FRONT

WALL OF PARTITION

(b) DOOR SWINGING ON SIDE

WALL OF PARTITION

m in m in

W

AL

L M

O U

N

TE

D

FL

O

O R

M O

U N

TE

D

SECTION 604.9.5

TOE CLEARANCE

(c) PLAN

SECTION 604.10.1

AMBULATORY COMPARTMENT

SECTION 604.10.1

AMBULATORY COMPARTMENT

(a) WALL HUNG (b) STALL TYPE m in max m in

CL

(a) PLAN

NOTE: HOT WATER AND

DRAIN PIPES UNDER

ACCESSIBLE LAVATORIES

SHALL BE INSULATED OR

OTHERWISE COVERED.

(b) SIDE

NOTE: THE DIP OF THE

OVERFLOW SHALL NOT BE

CONSIDERED IN

DETERMINING KNEE & TOE

CLEARANCES9

272934 m inm inm inm ax

6 max Toe

Clearance

17 8 min Knee

Clearancemin

SECTION 606.3

LAVATORIES AND SINKS

m in

(a) Removable Seat (b) Permanent Seat

SECTION 607.2

BATHTUBS W./ SEAT AT HEAD WALL

LAV COMPLYING W./

606.3 PERMITTED

LAV COMPLYING W./

606.3 PERMITTED

15 max head end wall

12 max m in control end wall back wall 8-10 control end wall head end wall m in m in

12 max 24 max24 min

8-10 back wall

(a) PLAN (b) ELEVATION

-3

3 - 6 m in m in

SECTION 607.4.1

GRAB BARS FOR BATHTUBS

W./ PERMANENT SEAT

SECTION 607.4.2

GRAB BARS FOR BATHTUBS

W./ REMOVABLE SEATS

(a) PLAN (b) ELEVATION

-3

3 - 6 m in m in control end wall

SECTION 607.5

LOCATION OF BATHTUB CONTROLS

CL

SECTION 608.2.1.2

TRANSFER-TYPE SHOWER

COMPARTMENT SIZE

CL

CLCL

52 min m in control wall back wall seat wall

CL

CLCL

(a) Existing Buildings (b) New Buildings

SECTION 608.2.2.1

ROLL IN-TYPE SHOWER

COMPARTMENT SIZE

(a) Without a Seat (b) With a Seat

LAV COMPLYING W./

606.3 PERMITTED

CL

CLCL

60 min m in m ax

6 max side wall side wall back wall

LAV COMPLYING W./

606.3 PERMITTED

CL

CLCL

NOTE: THESE DETAILS SUPERCEDE ANY AND

ALL DESIGN LAYOUTS AS SHOWN ON THE

ARCHITECTURAL PLAN VIEWS. SHOULD ANY

DISCREPANCY BE DISCOVERED, NOTIFY

ARCHITECT IMMEDIATELY.

BA

Y

AR

EN

AC

IS

D

IN

TE

R

IO

R

R

EN

O

VA

TI

O

N S

FO

R

LI

VI

N G

A N

D L

EA

R

N

IN

G C

EN

TE

R

N

. W

AS

H

IN

G

TO

N A

VE

N

U E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

N . W

AS

H

IN

G

TO

N

A

VE

N U

E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

BA

Y

AR

EN

AC

IS

D

IN

TE

R

IO

R

R

EN

O

VA

TI

O

N S

FO

R

LI

VI

N G

A N

D L

EA

R

N

IN

G C

EN

TE

R

EXIST. OPEN OFFICE

EXIST. CLASSROOM EXIST. CLASSROOMEXIST. TRAININGEXIST. EVALUATIONEXIST. CLASSROOM EXIST. STORAGE

EXIST. MECH.

EXIST. WORK RM. EXIST. EXAM RM.

EXIST. STORAGE

EXIST. KITCHEN EXIST. CAFETERIA

EXIST. STORAGEEXIST. TLT.

EXIST. VEST.

EXIST. EARLY

INFANT CLASSROOM

EXIST. GENERAL

OFFICE

EXIST. MEETING RM.

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

JAN. CL.

EXIST.

IT ROOM

EXIST.

STORAGE

EXIST. MENS

WOMENS

EXIST.

MULTI-PURPOSE

EXIST.

CONFERENCE

EXIST.

EXIST. STORAGE

EXIST. STORAGE

EXIST. CLASSROOM

WOMENS

EXIST.

EXIST. MENS

EXIST. CLASSROOM

STORAGE

EXIST. CLASSROOM

EXIST. CLASSROOMEXIST. CLASSROOMEXIST. CLASSROOMEXIST. OPEN OFFICE

EXIST. CORRIDOR

EXIST. CORRIDOR

EX

IS

T.

C

O R

R

ID

O R

EX

IS

T.

C

O R

R

ID

O R

EXIST. VEST.

EX

IS

T.

V

ES

T.

EXIST.

OFFICE

EXIST.

TLT.

EXIST.

OFFICE

DEMOLITION PLAN

GENERAL DEMO NOTES:

http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com

N . W

AS

H

IN

G

TO

N

A

VE

N U

E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

BA

Y

AR

EN

AC

IS

D

IN

TE

R

IO

R

R

EN

O

VA

TI

O

N S

FO

R

LI

VI

N G

A N

D L

EA

R

N

IN

G C

EN

TE

R

OFFICE

OFFICE

OFFICE

OPEN OFFICE

TOILET

CLASSROOM EXIST. CLASSROOMEXIST. TRAININGEXIST. EVALUATIONEXIST. CLASSROOM EXIST. STORAGE

EXIST. MECH.

EXIST. WORK RM. EXIST. EXAM RM.

EXIST. STORAGE

EXIST. KITCHEN EXIST. CAFETERIA

EXIST. STORAGEEXIST. TLT.

EXIST. VEST.

EXIST. EARLY

INFANT CLASSROOM

EXIST. GENERAL

OFFICE

EXIST. MEETING RM.

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

JAN. CL.

EXIST.

IT ROOM

EXIST.

STORAGE

EXIST. MENS

WOMENS

EXIST.

MULTI-PURPOSE

EXIST.

CONFERENCE

EXIST.

EXIST. STORAGE

EXIST. STORAGE

EXIST. CLASSROOM

WOMENS

EXIST.

EXIST. MENS

EXIST. CLASSROOM

STORAGE

EXIST. CLASSROOM

EXIST. CLASSROOMEXIST. CLASSROOMEXIST. CLASSROOMEXIST. OPEN OFFICE

EXIST. CORRIDOR

EXIST. CORRIDOR

EX

IS

T.

C

O R

R

ID

O R

EX

IS

T.

C

O R

R

ID

O R

EXIST. VEST.

EX

IS

T.

V

ES

T.

EXIST.

OFFICE

EXIST.

TLT.

EXIST.

OFFICE

B

B B

A

A

A C

C

C

A PARTITION WALL

NON-RATED

NON-BEARING WALL

WALL TYPES

B PARTITION WALL

NON-RATED

NON-BEARING WALL

C PARTITION WALL

NON-RATED

NON-BEARING WALL

FLOOR PLAN

GENERAL NOTES:

http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com

N . W

AS

H

IN

G

TO

N

A

VE

N U

E

TS

SF

A

RC

HI

TE

CT

S, I

NC

SA

G

IN

AW

M

IC

H

IG

AN

BA

Y

AR

EN

AC

IS

D

IN

TE

R

IO

R

R

EN

O

VA

TI

O

N S

FO

R

LI

VI

N G

A N

D L

EA

R

N

IN

G C

EN

TE

R

OFFICE

OFFICE

OFFICE

OPEN OFFICE

TOILET

CLASSROOM EXIST. CLASSROOMEXIST. TRAININGEXIST. EVALUATIONEXIST. CLASSROOM EXIST. STORAGE

EXIST. MECH.

EXIST. WORK RM. EXIST. EXAM RM.

EXIST. STORAGE

EXIST. KITCHEN EXIST. CAFETERIA

EXIST. STORAGEEXIST. TLT.

EXIST. VEST.

EXIST. EARLY

INFANT CLASSROOM

EXIST. GENERAL

OFFICE

EXIST. MEETING RM.

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

OFFICE

EXIST.

JAN. CL.

EXIST.

IT ROOM

EXIST.

EXIST. MENS

WOMENS

EXIST.

MULTI-PURPOSE

EXIST.

CONFERENCE

EXIST.

EXIST. STORAGE

EXIST. STORAGE

EXIST. CLASSROOM

WOMENS

EXIST.

EXIST. MENS

EXIST. CLASSROOM

STORAGE

EXIST. CLASSROOM

EXIST. CLASSROOMEXIST. CLASSROOMEXIST. CLASSROOMEXIST. OPEN OFFICE

EXIST. CORRIDOR

EXIST. CORRIDOR

EX

IS

T.

C

O R

R

ID

O R

EX

IS

T.

C

O R

R

ID

O R

EXIST. VEST.

EX

IS

T.

V

ES

T.

EXIST.

OFFICE

EXIST.

TLT.

EXIST.

OFFICE

STORAGE

REFLECTED CEILING PLAN

MECHANICAL SPECIFICATIONS

1. MECHANICAL PLANS ARE DIAGRAMMATIC IN NATURE, INTENDED TO INDICATE DESIGN INTENT ONLY.

THE MECHANICAL CONTRACTOR IS EXCLUSIVELY RESPONSIBLE TO COORDINATE SPECIFIC LOCATIONS OF ITEMS AND ADJUST AS REQUIRED TO ACCOMMODATE CODE REQUIREMENTS, EXISTING CONDITIONS, BUILDING STRUCTURE, LIGHTS, PLUMBING, ELECTRICAL WORK, AND THE WORK OF ALL OTHER TRADES.

DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION.

FIELD MODIFICATIONS (SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.

2. ALL OF THE MECHANICAL INFORMATION IS PRESENTED ON AN X-REFERENCED BACKGROUND FLOOR

PLAN. IN CASE OF CONFLICT BETWEEN BACKGROUND PLAN AND ARCHITECTURAL FLOOR PLAN,

ARCHITECTURAL FLOOR PLAN SHALL GOVERN.

3. THE HVAC CONTRACTOR SHALL PROVIDE ALL ITEMS, ARTICLES, MATERIALS, OPERATIONS OR METHODS MENTIONED, LISTED OR SCHEDULED ON THE DRAWINGS AND IN THESE SPECIFICATIONS, INCLUDING

ALL LABOR, MATERIALS, EQUIPMENT AND ALL INCIDENTALS NECESSARY REQUIRED FOR THE

COMPLETION AND OPERATION OF ALL SYSTEMS.

4. THE ENGINEER WILL NOT HAVE CONTROL OR CHARGE OF CONSTRUCTION MEANS, METHODS,

TECHNIQUES, SEQUENCES, OR PROCEDURES AND IS NOT RESPONSIBLE FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, AND WILL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S

FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THOSE DOCUMENTS PREPARED BY THE

ENGINEER.

5. THE HVAC CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF DRAWINGS REFLECTING "AS-BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT DIMENSIONS AND

ELEVATIONS FOR ALL UNDERGROUND AND/OR CONCEALED WORK. UPON COMPLETION OF THIS

PROJECT, THE CONTRACTOR SHALL DELIVER THE AS-BUILT DRAWINGS TO THE CM OR GC.

6. THE INSTALLATION SHALL BE MADE SO THAT ALL COMPONENT PARTS FUNCTION TOGETHER AS A

WORKABLE SYSTEM; IT SHALL BE COMPLETE WITH ALL ACCESSORIES NECESSARY FOR PROPER

OPERATION. WHEN THE INSTALLATION IS COMPLETE, ALL EQUIPMENT SHALL BE EXECUTED IN

CONFORMITY WITH THE BEST PRACTICE SO AS TO CONTRIBUTE TO EFFICIENCY OF OPERATION, MINIMUM MAINTENANCE, ACCESSIBILITY AND SIGHTLINESS.

7. TO ACCOMPLISH THESE RESULTS, THE HVAC CONTRACTOR SHALL CONSULT THE ARCHITECT'S FIELD LAYOUTS OF THE CONTRACTORS FOR THESE TRADES AND THEIR SHOP DRAWINGS. HE/SHE SHALL

COORDINATE THEIR WORK ACCORDINGLY.

8. DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK

AND ARE PARTLY DIAGRAMMATIC. THEY ARE NOT INTENDED TO BE SCALED FOR ROUGHING-IN

MEASUREMENTS OR TO SERVE AS SHOP DRAWINGS. THE ARCHITECTURAL DRAWINGS AND DETAILS SHALL BE EXAMINED FOR EXACT LOCATION OF FIXTURES AND EQUIPMENT. WHERE THEY ARE NOT

DEFINITELY LOCATED, THIS INFORMATION SHALL BE OBTAINED FROM THE ENGINEER.

9. REFER TO THE ARCHITECTURAL PLANS FOR ALL BUILDING SECTIONS, INTERIOR, AND EXTERIOR

ELEVATIONS. EQUIPMENT AND INSTALLATION METHODS SHOWN ON ARCHITECTURAL

SECTIONS/DETAILS ARE CONSIDERED PART OF THE HVAC DOCUMENTS .

10. MINOR ITEMS AND ACCESSORIES OR DEVICES REASONABLY INFERABLE AS NECESSARY TO THE COMPLETE AND PROPER OPERATION OF ANY SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR OR SUB- CONTRACTOR FOR SUCH SYSTEM WHETHER OR NOT THEY ARE SPECIFICALLY CALLED FOR BY THE

SPECIFICATIONS OR DRAWINGS.

11. WHERE WORK OF THE CONTRACTOR CONNECTS TO THAT OF ANOTHER TRADE, OR TO PIPING OR EQUIPMENT IN PLACE, THE CONTRACTOR SHALL TAKE SUCH MEASUREMENTS IN THE FIELD AS MAY BE

NECESSARY TO MAKE HIS WORK COME TRUE OR LINE UP WITH THAT WORK.

12. ALL CONSTRUCTION SHALL BE DONE IN COMPLIANCE WITH CURRENT CODES, INCLUDING BUT NOT

LIMITED TO:

A. MICHIGAN BUILDING CODES

B. MICHIGAN PLUMBING CODE

C. MICHIGAN MECHANICAL & ENERGY CODES

D. NATIONAL ELEC. CODE

E. MICHIGAN REHABILITATION CODE

F. MICHIGAN BARRIER FREE CODES

G. OSHA REQUIREMENTS

ALL CODES SHALL BE THE STATE OF MI LATEST ADOPTED EDITIONS AT THE TIME OF PLAN REVIEW.

13. HVAC WORK SHALL BE DONE IN ACCORDANCE WITH THE MECHANICAL CODE AS LOCALLY ADOPTED, LOCAL REGULATIONS AND OTHER CODES OR REGULATIONS HAVING LEGAL JURISDICTION IN THE AREA.

THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND CERTIFICATES OF INSPECTIONS AS MAY BE REQUIRED. PROVIDE FINAL CERTIFICATES OF INSPECTION TO THE GC UPON COMPLETION.

14. ANY CHANGES IN THE WORK TO SECURE CERTIFICATES SHALL BE MADE BY THIS CONTRACTOR AT HIS OWN EXPENSE. IN THE EVENT PLANS AND SPECIFICATIONS CONFLICT WITH ANY RULES, REGULATIONS OR CODES APPLYING, SAID RULES, REGULATIONS AND CODES SHALL GOVERN THE CONTRACTOR.

15. ALL HEATING AND COOLING WORK SHALL BE DONE IN FULL ACCORD WITH ASME, SMACNA AND ALL

STATE, FEDERAL AND LOCAL CODES OR ORDINANCES WHICH MAY APPLY IN THE AREA.

16. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED. MAINTAIN MAXIMUM HEADROOM

AND SPACE CONDITIONS AT ALL POINTS. WHERE HEADROOM OR SPACE CONDITIONS APPEAR

INADEQUATE, ENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION.

CONTRACTOR MAY CHANGE SHAPE OF DUCTS AS LONG AS THE FREE AREA NOTED ON PLANS IS

RETAINED.

17. IF DIRECTED BY THE ENGINEER, THE CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE REASONABLE MODIFICATIONS IN THE LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF

OTHER TRADES FOR PROPER EXECUTION OF THE WORK.

18. CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED BY HIM OR SUB-CONTRACTORS TO BE FREE FROM DEFECT IN MATERIAL OR WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF THE WORK, AND HE SHALL REPAIR OR REPLACE AT NO ADDITIONAL COST TO THE

OWNER ANY MATERIAL OR EQUIPMENT DEVELOPING DEFECTS AND SHALL ALSO MAKE GOOD ANY

DAMAGE CAUSED BY SUCH DEFECTS OR THE CORRECTION OF DEFECTS. THIS REQUIREMENT SHALL BE BINDING EVEN THOUGH IT WILL EXCEED PRODUCTS GUARANTEES NORMALLY FURNISHED BY SOME

MANUFACTURERS.

19. CONTRACTOR SHALL SUBMIT HIS OWN AND EACH EQUIPMENT MANUFACTURER'S WRITTEN

CERTIFICATES, WARRANTING THAT EACH ITEM OR EQUIPMENT FURNISHED COMPLIES WITH ALL

REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. NOTE THAT GUARANTEE SHALL RUN FROM THE DATE OF FINAL ACCEPTANCE OF THE WORK, NOT FROM THE DATE OF INSTALLATION OF A DEVICE

OR PIECE OF EQUIPMENT.

20. UNTIL FINAL ACCEPTANCE OF THE WORK, THE CONTRACTOR SHALL PROTECT ALL MATERIALS.

21. ALL MATERIALS AND EQUIPMENT FURNISHED SHALL BE EQUAL IN QUALITY AND CAPACITY TO THAT

SPECIFIED AND HARMONIOUS IN DESIGN AS DETERMINED BY THE ENGINEER.

22. HVAC WORK SHALL BE CAREFULLY EXECUTED BY SKILLED MECHANICS WELL VERSED IN THEIR

PARTICULAR TRADES. IT SHALL ALSO HAVE A CLEAN, NEAT, WELL ARRANGED AND FINISHED

APPEARANCE TO THE COMPLETE SATISFACTION OF THE OWNER AND THE ARCHITECT/ENGINEER.

23. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH THE CONDITIONS WHICH WILL AFFECT THE WORK HE IS TO PERFORM. THE SUBMISSION OF A PROPOSAL BY THIS CONTRACTOR SHALL BE CONCLUSIVE EVIDENCE THAT THIS CONTRACTOR HAS VISITED THE SITE AND HAS GIVEN PROPER CONSIDERATION AND EVALUATION OF THESE CONDITIONS IN THE PREPARATION

OF HIS PROPOSAL. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE IN HIS BEHALF FOR EXTRA

EXPENSE INCURRED DUE TO FAILURE OF NEGLECT ON HIS PART TO MAKE THIS VISIT AND

EXAMINATION.

24. PROVIDE SHOP DRAWINGS FOR APPROVAL FOR HVAC EQUIPMENT, DUCT INSULATION, GRILLES AND REGISTERS, ETC. SHOP DRAWINGS ARE THE BE THOROUGHLY CHECKED (AND NOTED SO ON FRONT

COVER) BY THE CONTRACTOR PRIOR TO SUBMITTING THEM TO THE ENGINEER. REVIEW BY THE

ENGINEER SHALL NOT BE CONSTRUED AS A COMPLETE CHECK, BUT ONLY THAT THE GENERAL METHOD OF CONSTRUCTION AND DETAILING IS SATISFACTORY. REVIEW SHALL NOT RELIEVE THE CONTRACTOR

FROM RESPONSIBILITY FOR ERRORS WHICH MAY EXIST.

25. LOCATE THERMOSTATS AT A HEIGHT PER ADA AND MICHIGAN BARRIER FREE CODES. COORDINATE

LOCATIONS WITH OTHER EQUIPMENT, FURNITURE, AND DOOR SWINGS.

13. ALL LOW VOLTAGE TEMPERATURE CONTROL WIRING SHALL BE PROVIDED BY THE HVAC CONTRACTOR UNLESS OTHERWISE NOTED. ELECTRICAL CONTRACTOR SHALL PROVIDE ANY 120/240/208/480 VOLT

POWER WIRING - CONSULT W/ MC PRIOR TO BIDDING PROJECT.

14. ALL EXHAUST AIR LOUVERS AND GRILLES MUST BE INSTALLED A MINIMUM OF TEN FEET (10'-0") FROM

ANY OUTDOOR AIR INTAKE AND/OR OPERABLE WINDOW OR DOOR.

15. ALL EQUIPMENT, DUCTWORK, ETC. SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE

ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.

16. EXHAUST FANS SHALL BE EQUAL TO PANASONIC, BROAN, PATTON, NUTONE, CARNES, GREENHECK OR

ACME.

17. IF AN ARCHITECTURAL REFLECTIVE CEILING PLAN IS PROVIDED WITH THIS PROJECT, ROUGH IN THE

DIFFUSERS, GRILLES, AND REGISTERS PER THAT PLAN.

18. CHECK THE FINAL LOCATION OF GRILLES, REGISTERS AND DIFFUSERS AGAINST THE ARCHITECTURAL

DRAWINGS. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/

ENGINEER PRIOR TO FABRICATION AND INSTALLATION OF THE DUCTWORK AND AIR OUTLETS.

19. ALL DUCTWORK DIMENSION NOTED ON DRAWINGS ARE INSIDE, CLEAR DIMENSIONS, UNLESS NOTED

OTHERWISE. FOR INTERIOR LINED DUCTWORK, OVERSIZE DUCTWORK DURING FABRICATION AS

REQUIRED TO MAINTAIN INSIDE CLEAR DIMENSIONS.

20. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOW.

21. ALL CONTRACTORS ARE TO COORDINATE THE LOCATIONS OF PLUMBING LINES, DUCTWORK,

EQUIPMENT, GAS LINES, FIRE SUPPRESSION LINES, ETC. AS REQUIRED SO THAT CLEARANCES ABOVE ELECTRICAL PANELS ARE MAINTAINED PER 2023 NEC. REFERENCE ELECTRICAL DRAWINGS FOR PANEL

LOCATIONS.

22. RUN ALL PIPING, CONDUIT, ETC. CONCEALED IN WALLS WHENEVER POSSIBLE. AVOID EXPOSED

INSTALLATION UNLESS SPECIFICALLY REQUIRED AND/OR NOTED ON DRAWINGS. ANY EXPOSED

INSTALLATION SHALL BE APPROVED BY THE ENGINEER PRIOR TO INSTALLATION.

23. DO NOT SUPPORT CEILINGS, OTHER BUILDING STRUCTURES, OR CONDUITS FROM DUCTWORK, PIPES OR CONDUIT. DO NOT ALLOW DUCTS, PIPES OR CONDUITS TO DIRECTLY TOUCH BUILDING WALLS, FLOORS, OR STRUCTURE AT ANY LOCATION.

24. ALL OPENINGS IN CONSTRUCTION, THROUGH WHICH PIPING AND/OR DUCTWORK PASS SHALL BE SEALED UP AIR TIGHT AFTER INSTALLATION OF PIPING/DUCTWORK. PENETRATIONS OF FLOOR/ CEILING ASSEMBLIES REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE PROTECTED IN

ACCORDANCE WITH THE MICHIGAN BUILDING CODE, LATEST ADOPTED EDITION.

25. FAILURE TO DETECT INFERIOR WORK, OR WORK NOT IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND APPLICABLE CODES SHALL NOT BE CONSTRUED AS ACCEPTANCE OF SUCH WORK.

26. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL OPERATING HOURS. SUCH INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR

WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH OTHER

TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.

27. THE HVAC CONTRACTOR SHALL REMOVE FROM THE SITE ALL DEBRIS AND RUBBISH ACCUMULATING AS A RESULT OF THE HVAC INSTALLATION. REMOVE WEEKLY. UPON COMPLETION OF THE WORK, HE/SHE SHALL LEAVE ALL AREAS CLEAN INCLUDING BUT NOT LIMITED TO THE MECHANICAL ROOMS AND THE

HVAC EQUIPMENT IN SAID ROOM.

28. ALL CUTTING AND PATCHING IS THE RESPONSIBILITY OF THE TRADE REQUIRING THE WORK UNLESS

NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS/SPECIFICATIONS.

29. ALL REQUIRED INSURANCE SHALL BE CARRIED BY THE CONTRACTOR FOR THE PROTECTION AGAINST

PUBLIC LIABILITY OR PROPERTY DAMAGE FOR THE DURATION OF THE WORK.

END OF MECHANICAL SPECIFICATIONS

MINIMUM DUCT INSULATION VALUES

TABLE 6.8.2, MINIMUM DUCT INSULATION R-VALUE a (FROM ASHRAE 90.1, 2019 EDITION)

THIS PROJECT IS IN CLIMATE ZONE 5A

DUCT LOCATION

UNCONDITIONED SPACE INDIRECTLY

CLIMATE ZONE EXTERIOR b AND BURIED DUCTS CONDITIONED SPACE c,d

SUPPLY AND RETURN DUCTS FOR HEATING AND COOLING:

0 TO 4 R-8 R-6 R-1.9

5 TO 8 R-12 R-6 R-1.9

SUPPLY AND RETURN DUCTS FOR HEATING ONLY:

0 TO 1 NONE NONE NONE

2 TO 4 R-6 R-6 R-1.9

5 TO 8 R-12 R-6 R-1.9

SUPPLY AND RETURN DUCTS FOR COOLING ONLY:

0 TO 6 R-8 R-6 R-1.9

7 TO 8 R-1.9 R-1.9 R-1.9

a. INSULATION R-VALUES, MEASURED IN H x FT2 x °F/BTU, ARE FOR THE INSULATION AS INSTALLED AND

DO NOT INCLUDE FILM RESISTANCE. THE REQUIRED MINIMUM THICKNESSES DO NOT CONSIDER

WATER VAPOR TRANSMISSION AND POSSIBLE SURFACE CONDENSATION. WHERE PORTIONS OF THE BUILDING ENVELOPE ARE USED AS A PLENUM ENCLOSURE, BUILDING ENVELOPE INSULATION SHALL BE AS REQUIRED BY THE MOST RESTRICTIVE CONDITION OF SECTION 6.4.4.1 OR SECTION 5, DEPENDING ON WHETHER THE PLENUM IS LOCATED IN THE ROOF, WALL, OR FLOOR. INSULATION

RESISTANCE MEASURED ON A HORIZONTAL PLANE IN ACCORDANCE WITH ASTM C518 AT A MEAN

TEMPERATURE OF 75°F AT THE INSTALLED THICKNESS.

b. INCLUDES ATTICS ABOVE INSULATED CEILING, PARKING GARAGES AND CRAWL SPACES.

c. INCLUDES RETURN AIR PLENUMS WITH OR WITHOUT EXPOSED ROOFS ABOVE.

d. RETURN DUCTS IN THIS DUCT LOCATION DO NOT REQUIRE INSULATION.

INSULATED FLEXIBLE DUCT

(SIZE TO MATCH DIFFUSER INLET

SIZE AS SHOWN ON PLANS)

PRE-FABRICATED

ADJUSTABLE 90° SHEET

METAL ELBOW

INSULATION

CEILING GRID T-BAR

CEILING DIFFUSER

CEILING TILE

UNCONFINED CEILING SPACE STRAP HANGERTRAPEZE HANGER

HANGER STRAPSHANGER RODS

41" MAX

MECHANICAL SYMBOL SCHEDULE

EQUIPMENT TAG

MARK

AIR FLOW

CU-1

SA

THERMOSTATT

POINT OF NEW CONNECTION

EA EXHAUST AIR

EF EXHAUST FAN

ETR EXISTING TO REMAIN

MMC MICHIGAN MECHANICAL CODE

OA OUTSIDE AIR

PONC POINT OF NEW CONNECTION

RA RETURN AIR

SA SUPPLY AIR

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

XEA EXISTING EXHAUST AIR

XRA EXISTING RETURN AIR

XSA EXISTING SUPPLY AIR

TEST AND BALANCE SPECIFICATIONS

A. SCOPE OF WORK

1. THIS SECTION COVERS THE TESTING, ADJUSTING AND BALANCING (TAB) OF ENVIRONMENTAL SYSTEMS INCLUDING BUT NOT LIMITED TO: AIR DISTRIBUTION SYSTEMS, HYDRONIC DISTRIBUTION SYSTEMS (AS APPLICABLE), AND THE EQUIPMENT AND

APPARATUS CONNECTED THERETO.

2. THE TAB WORK REQUIRED HEREIN SHALL CONSIST OF SETTING VOLUME (FLOW) AND SPEED ADJUSTING FACILITIES PROVIDED OR SPECIFIED FOR THE SYSTEMS, RECORDING DATA, MAKING TESTS AND PREPARING REPORTS, ALL AS HEREINAFTER SPECIFIED.

B. GENERAL REQUIREMENTS

1. THE WORK DESCRIBED IN THIS SECTION SHALL BE PERFORMED BY A FIRM CERTIFIED FOR TAB WORK BY THE NATIONAL

ENVIRONMENTAL BALANCING BUREAU (NEBB), AND/OR THE NATIONAL BALANCING INSTITUTE (NBI). THE NAME OF THE SELECTED NEBB/ NBI CERTIFIED FIRM SHALL BE SUBMITTED TO THE DESIGN ENGINEER FOR APPROVAL WITHIN 2 WEEKS AFTER CONTRACT

AWARD.

C. PROCEDURES

1. THE ENVIRONMENTAL SYSTEMS INCLUDING ALL EQUIPMENT, APPARATUS, AND DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED IN ACCORDANCE WITH THE 1998 EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS.

2. ALL WORK PERFORMED UNDER THIS SECTION SHALL BE UNDER THE DIRECTION OF THE SUPERVISOR WHO IS DESIGNATED AND

CURRENTLY QUALIFIED UNDER THE CERTIFICATION REQUIREMENTS OF NEBB AND/OR NBI.

3. ALL INSTRUMENTS USED FOR MEASUREMENTS SHALL BE RELIABLE, ACCURATE, AND IN GOOD WORKING ORDER, AND CALIBRATION HISTORIES FOR EACH INSTRUMENTS SHALL BE AVAILABLE FOR EXAMINATION. CALIBRATION AND MAINTENANCE OF ALL

INSTRUMENTS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF NEBB/NBI.

4. ACCURACY OF MEASUREMENTS SHALL BE IN ACCORDANCE WITH THE NEBB/NBI PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS.

D. REPORTS

1. CERTIFIED COPY OF THE FINAL REPORT BEARING THE SEAL OF THE SUPERVISOR OF THE NEBB/NBI CERTIFIED FIRM SHALL BE

SUBMITTED ELECTRONICALLY USING APPLICABLE NEBB/NBI REPORT FORMS FOR REVIEW (IN PDF FORMAT).

2. FINAL REPORT FORM SUBMITTED SHALL BEAR THE NAME OF THE PERSON WHO RECORDED THE DATA.

3. IF MORE THAN ONE NEBB/NBI CERTIFIED FIRM PERFORMS THE WORK, THE FINAL REPORT SHALL BE SUBMITTED BY THAT NEBB/NBI

CERTIFIED FIRM HAVING CONTRACTUAL RESPONSIBILITY.

END OF TESTING AND BALANCING SPECIFICATIONS

MECHANICAL SHEET INDEX

SHEET NO. TITLE

M0.0 MECHANICAL SPECIFICATIONS, SCHEDULES & DETAILS

M1.0 MECHANICAL DUCTWORK PLANS

PROJECT NO.

SHEET NO.

APPROVED

DRAWN BY

DATE

N

W

A S

H

IN

G T

O N

A V

E N

U E

S A

G

IN

A W

M

IC

H

IG

A

N

D A T E

N O

T S

S F

A

R C

H

IT

E C

T S

I

N C

A R C H

IT

E C T S

P L A N N E R S

IN

T E R

IO

R S

CONSULTING ENGINEER

491 E. WRIGHT AVE. SHEPHERD, MI 48883

989-567-1100 | info@KTSEngineeringGroup.com

KTS PROJECT NO.: C

O

PY

R

IG

H T

A

LL

R

IG

H T S

R

ES

ER

V

ED

M0.0

JEE

05/11/2026

26-0312

B A

Y A

R E

N A

C I

S D

B A Y

C

IT

Y M

IC

H

IG

A N

IN

T

E R

IO

R

R E

N O

V A

T

IO

N S

F O

R

L

IV

IN

G

A N

D L

E A

R N

IN

G

C E

N T

E R

NOT TO SCALE

DIFFUSER CONNECTION

A.

B.

ACCEPTABLE MANUFACTURERS EQUAL TO SCHEDULED ITEM: PRICE, KRUEGER, SHOEMAKER, CARNES, T & B.

PRIOR TO ORDERING, CONTRACTOR TO VERIFY THAT STYLE & COLOR OF NEW DIFFUSERS MATCH EXISTING.

1. OPPOSED BLADE VOLUME DAMPER

GENERAL SCHEDULE NOTES: SPECIFIC TAG NOTES:

DIFFUSERS, REGISTERS AND GRILLES SCHEDULE

TAG MANUFACTURER MODEL NECK SIZE FACE SIZE DESCRIPTION BORDER MATERIAL COLOR NOTES

SA1 PRICE SMDA 8"ø 24"x24" LOUVERED FACE, ADJUSTABLE PATTERN DEFLECTORS LAY-IN STEEL WHITE 1

RA1 PRICE SMD 8"ø 24"x24" Perforated Ceiling Return Diffusers LAY-IN STEEL WHITE 1

COMMENTS:

1. REQUIREMENTS BELOW ARE BASED ON MICHIGAN REHABILITATION CODE - 2021, SECTION 807.

2. SPACES THAT ARE EXISTING TO REMAIN OR SPACES THAT REQUIRE EXHAUST ONLY ARE NOT LISTED.

3. EXISTING PLANS INDICATE BOTH EXISTING ROOFTOP UNITS ARE SET TO 27% OUTSIDE AIR.

VENTILATION SCHEDULE (REHAB)

NO. NAME AREA

NO. OF

PEOPLE

MICHIGAN REHAB,

MIN. OA CFM REQ. OA CFM PROVIDED % OA PROVIDED SUPPLY AIRFLOW COMMENTS

100 CLASSROOM 963 ft² 34 SECTION 807 169 324 27 1200 CFM 3

102 OPEN OFFICE 1195 ft² 6 SECTION 807 30 270 27 1200 CFM 3

103 OFFICE 113 ft² 1 SECTION 807 3 34 27 150 CFM 3

104 OFFICE 113 ft² 1 SECTION 807 3 34 27 150 CFM 3

105 OFFICE 113 ft² 1 SECTION 807 3 34 27 150 CFM 3

COMMENTS:

1. CONTINUOUS OPERATION RATED & THERMALLY PROTECTED MOTOR 2. BACKDRAFT DAMPER

EXHAUST FAN SCHEDULE

TAG

BASIS OF DESIGN

CFM

E.S.P.

(in-wg)

DRIVE TYPE SONES

ELECTRICAL DATA

CONTROL COMMENTS

MANUFACTURER MODEL WATTS VOLTAGE

EF-1 PANASONIC FV-0511VKS3S 110 0.25 DIRECT 0.3 12.9 120/1 INTERLOCK WITH TOILET LIGHTS 1 - 2

NOT TO SCALE

DUCT HANGER DETAIL

"x

10"x10"

"x

XEA

T

16"x14" 14"x14"

30"x20" 18"x18"30"x20" 18"x18"

"x

22"x12"

"x

22"x12"

8"x8" 12"x12"

10"x10"

XSA

8" x8

XRA

XRA

XRA

XSA

XSA

XSA

XSA

XSA

XSA

XVB-208

REMOVE DIFFUSER &

REFER TO NEW PLAN

REMOVE DIFFUSER &

REFER TO NEW PLAN

10"x10"

10"x10"

AREA OF WORK

"x

10"x10"

"x

XEA

XRA

XRA

16"x14" 14"x14"

30"x20" 18"x18"30"x20" 18"x18"

"x

22"x12"

"x

22"x12"

8"x8" 12"x12"

10"x10"

XSA

XSA

XSA

XSA

XSA

8" x8

SA1

SA1

SA1

RA1

RA1

RA1

XRA

T

XVB-208

8"ø10"x10"

8"ø

10"x10"

DIFFUSER ETR,

NEW AIRFLOW (TYP)

8"ø 8"ø 8"ø10"x10" 10"x10"

EXISTING

JANITOR

CLOSET

EXISTING IT

ROOM

OFFICE

OFFICE

OFFICE

OPEN OFFICE

EXISTING

STORAGE

AREA OF WORK

T

XSA

XSA

XSA

XRA

XRA

12"x12"

"x

18"x18"

30"x24"

18"x18"

24"x20"

16"x16"

24"x20"

REMOVE & RELOCATE

THERMOSTAT

REMOVE & RELOCATE

EXISTING DIFFUSER

12"x12"

12"x12"

XVB-109

AREA OF WORK

XRA

XSA

XSA

XSA

XRA

12"x12"

18"x18"

30"x24"

18"x18"

24"x20"

16"x16"

24"x20"

CLASSROOM

TOILET

NEW LOCATION FOR

EXISTING DIFFUSER

NEW LOCATION FOR

EXISTING THERMOSTAT

12"x12"

12"x12"

"x

XVB-109

T

EF-1

6"Ø EXHAUST DUCT

UP THRU ROOF

WITH GOOSENECK

& BIRDSCREEN

AREA OF WORK

PROJECT NO.

SHEET NO.

APPROVED

DRAWN BY

DATE

N

W

A S

H

IN

G T

O N

A V

E N

U E

S A

G

IN

A W

M

IC

H

IG

A

N

D A T E

N O

T S

C

H

IT

E C

T S

I

N C

A R C H

IT

E C T S

P L A N N E R S

IN

T E R

IO

R S

CONSULTING ENGINEER

491 E. WRIGHT AVE. SHEPHERD, MI 48883

989-567-1100 | info@KTSEngineeringGroup.com

KTS PROJECT NO.: C

O

PY

R

IG

H T

A

LL

R

IG

H T S

R

ES

ER

V

ED

M1.0

JEE

05/11/2026

26-0312

B A

Y A

R E

N A

C I

S D

B A Y

C

IT

Y M

IC

H

IG

A N

IN

T

E R

IO

R

R E

N O

V A

T

IO

N S

F O

R

L

IV

IN

G

A N

D L

E A

R N

IN

G

C E

N T

E R

1/8" = 1'-0"

OFFICE AREA HVAC DEMO PLAN

1/8" = 1'-0"

OFFICE AREA HVAC PLAN

1/8" = 1'-0"

TOILET ADDITION HVAC DEMO PLAN

1/8" = 1'-0"

TOILET ADDITION HVAC PLAN

1. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR HIRING

THE SERVICES OF A LICENSED FIRE PROTECTION

CONTRACTOR TO REMOVE & RE-LOCATE ALL NECESSARY

SPRINKLER HEADS DUE TO THE RENOVATION OF BOTH THE

OFFICE AREA AND TOILET ADDITION.

2. ALL FIRE SUPPRESSION WORK MUST BE IN COMPLIANCE

WITH NFPA 13 AND THE AUTHORITY HAVING JURISDICTION.

3. ALL PERMITS, LICENSES, FEES, INSPECTIONS AND

ARRANGEMENTS SHALL BE OBTAINED AND PAID FOR BY THE

FIRE PROTECTION CONTRACTOR.

FIRE PROTECTION NOTES

PLUMBING SPECIFICATIONS

1. PLUMBING PLANS ARE DIAGRAMMATIC IN NATURE, INTENDED TO INDICATE DESIGN INTENT ONLY. THE PLUMBING CONTRACTOR IS EXCLUSIVELY RESPONSIBLE TO COORDINATE SPECIFIC LOCATIONS OF ITEMS AND ADJUST AS REQUIRED TO ACCOMMODATE CODE REQUIREMENTS, EXISTING CONDITIONS, BUILDING STRUCTURE, LIGHTS, HVAC, ELECTRICAL WORK, AND THE WORK OF ALL OTHER TRADES.

DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION.

FIELD MODIFICATIONS (SUCH AS OFFSETS IN PIPING) NEEDED DUE TO OBSTRUCTIONS OR

INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.

2. ALL OF THE PLUMBING INFORMATION IS PRESENTED ON AN X-REFERENCED BACKGROUND FLOOR PLAN.

IN CASE OF CONFLICT BETWEEN BACKGROUND PLAN AND ARCHITECTURAL FLOOR PLAN,

ARCHITECTURAL FLOOR PLAN SHALL GOVERN.

3. THE PLUMBING CONTRACTOR SHALL PROVIDE ALL ITEMS, ARTICLES, MATERIALS, OPERATIONS OR METHODS MENTIONED, LISTED OR SCHEDULED ON THE DRAWINGS AND IN THESE SPECIFICATIONS, INCLUDING ALL LABOR, MATERIALS, EQUIPMENT AND ALL INCIDENTALS NECESSARY REQUIRED FOR THE

COMPLETION AND OPERATION OF ALL PLUMBING SYSTEMS.

4. THE ENGINEER WILL NOT HAVE CONTROL OR CHARGE OF CONSTRUCTION MEANS, METHODS,

TECHNIQUES, SEQUENCES, OR PROCEDURES AND IS NOT RESPONSIBLE FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, AND WILL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S

FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THOSE DOCUMENTS PREPARED BY THE

ENGINEER.

5. THE PLUMBING CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF DRAWINGS

REFLECTING "AS-BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT

DIMENSIONS AND ELEVATIONS FOR ALL UNDERGROUND AND/OR CONCEALED WORK. UPON

COMPLETION OF THIS PROJECT, THE CONTRACTOR SHALL DELIVER THE AS-BUILT DRAWINGS TO THE

CM OR GC.

6. THE INSTALLATION SHALL BE MADE SO THAT ALL COMPONENT PARTS FUNCTION TOGETHER AS A

WORKABLE SYSTEM; IT SHALL BE COMPLETE WITH ALL ACCESSORIES NECESSARY FOR PROPER

OPERATION. WHEN THE INSTALLATION IS COMPLETE, ALL EQUIPMENT SHALL BE OPERATIVE AND IN PROPER ADJUSTMENT. ALL WORK SHALL BE EXECUTED IN CONFORMITY WITH THE BEST PRACTICE SO AS TO CONTRIBUTE TO EFFICIENCY OF OPERATION, MINIMUM MAINTENANCE, ACCESSIBILITY AND

SIGHTLINESS.

7. TO ACCOMPLISH THESE RESULTS, THE PLUMBING CONTRACTOR SHALL CONSULT THE ARCHITECT'S FIELD LAYOUTS OF THE CONTRACTORS FOR THESE TRADES AND THEIR SHOP DRAWINGS. HE/SHE

SHALL COORDINATE THEIR WORK ACCORDINGLY.

8. DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK

AND ARE PARTLY DIAGRAMMATIC. THEY ARE NOT INTENDED TO BE SCALED FOR ROUGHING-IN

MEASUREMENTS OR TO SERVE AS SHOP DRAWINGS. THE ARCHITECTURAL DRAWINGS AND DETAILS SHALL BE EXAMINED FOR EXACT LOCATION OF FIXTURES AND EQUIPMENT. WHERE THEY ARE NOT

DEFINITELY LOCATED, THIS INFORMATION SHALL BE OBTAINED FROM THE ENGINEER.

9. REFER THE TO THE ARCHITECTURAL PLANS FOR ALL BUILDING SECTIONS, INTERIOR, AND EXTERIOR

ELEVATIONS. PLUMBING EQUIPMENT AND INSTALLATION METHODS SHOWN ON ARCHITECTURAL

SECTIONS/DETAILS ARE CONSIDERED PART OF THE PLUMBING DOCUMENTS.

10. MINOR ITEMS AND ACCESSORIES OR DEVICES REASONABLY INFERABLE AS NECESSARY TO THE COMPLETE AND PROPER OPERATION OF ANY SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR OR SUB-CONTRACTOR FOR SUCH SYSTEM WHETHER OR NOT THEY ARE SPECIFICALLY CALLED FOR BY THE

SPECIFICATIONS OR DRAWINGS.

11. WHERE WORK OF THE CONTRACTOR CONNECTS TO THAT OF ANOTHER TRADE, OR TO PIPING OR EQUIPMENT IN PLACE, THE CONTRACTOR SHALL TAKE SUCH MEASUREMENTS IN THE FIELD AS MAY BE

NECESSARY TO MAKE HIS WORK COME TRUE OR LINE UP WITH THAT WORK.

12. ALL CONSTRUCTION SHALL BE DONE IN COMPLIANCE WITH CURRENT CODES, INCLUDING BUT NOT

LIMITED TO:

A. MICHIGAN BUILDING CODES

B. MICHIGAN PLUMBING CODE

C. MICHIGAN MECHANICAL & ENERGY CODES

D. NATIONAL ELEC. CODE

E. MICHIGAN REHABILITATION CODE

F. MICHIGAN BARRIER FREE CODES

G. OSHA REQUIREMENTS

ALL CODES SHALL BE THE STATE OF MI LATEST ADOPTED EDITIONS AT THE TIME OF PLAN REVIEW

13. PLUMBING WORK SHALL BE DONE IN ACCORDANCE WITH THE PLUMBING CODE AS LOCALLY ADOPTED, LOCAL REGULATIONS AND OTHER CODES OR REGULATIONS HAVING LEGAL JURISDICTION IN THE AREA.

CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND CERTIFICATES OF INSPECTIONS AS MAY

BE REQUIRED. PROVIDE FINAL CERTIFICATES OF INSPECTION TO THE GC UPON COMPLETION.

14. ANY CHANGES IN THE WORK TO SECURE CERTIFICATES SHALL BE MADE BY THIS CONTRACTOR AT HIS OWN EXPENSE. IN THE EVENT PLANS AND SPECIFICATIONS CONFLICT WITH ANY RULES, REGULATIONS OR CODES APPLYING, SAID RULES, REGULATIONS AND CODES SHALL GOVERN THE CONTRACTOR.

15. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED. MAINTAIN MAXIMUM HEADROOM

AND SPACE CONDITIONS AT ALL POINTS. WHERE HEADROOM OR SPACE CONDITIONS APPEAR

INADEQUATE, ENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION.

16. IF DIRECTED BY THE ENGINEER, THE CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE REASONABLE MODIFICATIONS IN THE LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF

OTHER TRADES FOR PROPER EXECUTION OF THE WORK.

17. CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED BY HIM OR SUB-CONTRACTORS TO BE FREE FROM DEFECT IN MATERIAL OR WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE OF THE WORK, AND HE SHALL REPAIR OR REPLACE AT NO ADDITIONAL COST TO THE

OWNER ANY MATERIAL OR EQUIPMENT DEVELOPING DEFECTS AND SHALL ALSO MAKE GOOD ANY

DAMAGE CAUSED BY SUCH DEFECTS OR THE CORRECTION OF DEFECTS. THIS REQUIREMENT SHALL BE BINDING EVEN THOUGH IT WILL EXCEED PRODUCTS GUARANTEES NORMALLY FURNISHED BY SOME

MANUFACTURERS.

18. CONTRACTOR SHALL SUBMIT HIS OWN AND EACH EQUIPMENT MANUFACTURER'S WRITTEN

CERTIFICATES, WARRANTING THAT EACH ITEM OR EQUIPMENT FURNISHED COMPLIES WITH ALL

REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. NOTE THAT GUARANTEE SHALL RUN FROM THE DATE OF FINAL ACCEPTANCE OF THE WORK, NOT FROM THE DATE OF INSTALLATION…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .