BA26-007 Exhibits 1-3.pdf

PDF 498 KB Posted

Attached to
Oil Water Separator Cleaning
Solicitation number
2137188
Issued by
Albany County, Albany City, New York

About this file

This file comprises three exhibits supporting the New York State Department of Transportation (NYSDOT) solicitation BA26-007 for Oil Water Separator Cleaning services. Exhibit 1 provides a comprehensive inventory of 28 oil water separators (OWS) located across three regional zones within New York State, including specific addresses, installation years, equipment types, and maintenance histories. The separators range from 1000-gallon capacity units installed between 1984 and 2023, with manufacturers including Mohawk, Highland, Ecosep, Aquarius, and Fluid Containment systems. Recent cleaning and maintenance activities are documented, with most units having been serviced between October 2023 and November 2025. Exhibit 2 establishes mandatory safety protocols aligned with OSHA Permit-Required Confined Spaces (PRCS) standards (29 CFR 1910.146), requiring contractors to implement comprehensive written plans, atmospheric monitoring, personal protective equipment, rescue provisions, and specialized training before entry into any OWS. Exhibit 3 provides the OWS Cleaning Completion Worksheet, a standardized form for documenting contractor work including pre-cleaning inspections, maintenance activities performed, visual structural observations, and post-cleaning sign-offs by both contractor and NYSDOT resident engineers.

The contract requires contractors to comply with all OSHA confined space entry requirements, including written entry permits, designated entry supervisors and attendants, calibrated atmospheric monitoring equipment, and mechanical retrieval systems for vertical entries exceeding five feet. Bidders must provide evidence of their own Confined Space Written Plan and demonstrate training in confined space protocols, atmospheric monitoring, and rescue procedures. All cleaning activities must be documented on completion worksheets submitted with photographic evidence to the Maintenance Environmental Coordinator. The solicitation does not indicate pricing terms, set-asides, or specific contract duration within these exhibits, though inquiries regarding bid package availability should be directed to Purch-Assist@dot.ny.gov with reference to BA26-007.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table of Region One Oil Water Separators (typically 1000 gallon) Zone Location Name

Address Link Year

Installed Type Last

Cleaned Recent work Zo ne

Voorheesville 16 Maple Road

1999 Mohawk 6/2022 Vac & media

Latham 695 Watervliet Shaker Road

2023 Highland 12/2025 Vacuumed

Coxsackie Route 81@Vandenburgh Road

1999 Ecosep Unk

Cairo (1) 107 DOT Road

1984 Highland 11/2025 Vac, New media and plates

Cairo (2) 107 DOT Road

1984 Highland 11/2025 Vac, New media and plates

Tannersville 5749 Route 23A

1999 Ecosep Unk

Duanesburg 4005 Western Turnpike

1996 Highland 11/2025 Vac, New media and plates

Schenectady 3008 Chrisler Ave.

1996 Highland

HTG-2

11/2025 New media

Defreestville 288 Troy Road (Route 4)

In construction

Highland

North Petersburg 20166 Route 22

1995 Highland 7/2022 Vac & media

Zo ne

Clifton Park 14 Crew Road

1999 Mohawk 10/2024 Only vacuumed

Waterford (Fleet) 21 9th Street

Unk Unk 2023 Vac & media

Saratoga Springs 351 West Ave.

Unk Unk Unk

S. Glens Falls 1284 Rt.9 Gansevoort NY

2019 Highland 4/2023 Vac & media

Hudson Falls (1) 3716 Burgoyne

1997 Fluid Containment

10/2023

Hudson Falls (2) 3716 Burgoyne

1997 Fluid Containment

10/2023

East Greenwich

17 CR 49

1998 Mohawk 10/2023

Whitehall 9760 Route 4

1998 Mohawk 10/2023

Zone 3 is on the next page.

EXHIBIT 1

OWS Location and Specs https://goo.gl/maps/t35nHBKcNH62jJwJ7 https://goo.gl/maps/VgFikPkgCPpCu4nn7 https://goo.gl/maps/6wCrK9e68d94pv5HA https://goo.gl/maps/6wCrK9e68d94pv5HA https://goo.gl/maps/woxTH5GsoYT2vfdJ8 https://goo.gl/maps/woxTH5GsoYT2vfdJ8 https://goo.gl/maps/pavXvAwu1ur3Ur828 https://goo.gl/maps/udrNjBmnmYt7A22CA https://goo.gl/maps/E6AtEeVq37Sysy918 https://goo.gl/maps/NEcfmKVaJrw1BrTz9 https://goo.gl/maps/XaMqLxUpSPRDV5VP8 https://goo.gl/maps/9ZK5D9d2cN6nbKK96 https://goo.gl/maps/S4ccxNLcqGnHyc9a9 https://goo.gl/maps/R8AaMjRfqPbZPgB98 https://goo.gl/maps/p3oJegeZt2of1vM58 https://goo.gl/maps/DE98BJxgE11se8CN8 https://goo.gl/maps/DE98BJxgE11se8CN8 https://goo.gl/maps/1Tg6abTB3fVnyRfC6 https://goo.gl/maps/io8TTYpKewnAQ8ih8

Zo ne

Warrensburg (1) 4021 Main St.

2009 Aquarius 11/2024 Only vacuumed

Warrensburg (2) 4021 Main St.

2009 Aquarius 11/2024 Only vacuumed

Chestertown 6186 Route 8

2019 Mohawk 11/2024 Only vacuumed

Ray Brook 111 Rt 86

10/2024 Highland New

Elizabethtown 7735 Route 9

2017 Mohawk Unk

Crown Point 368 Factoryville Road

1999 Highland

Unk

Severance 9 Route 74

1996 Fluid Containment

Unk https://goo.gl/maps/iLy1uKPacbQfUuHn6 https://goo.gl/maps/iLy1uKPacbQfUuHn6 https://goo.gl/maps/Efv4bnYXUC77dZpd8 https://goo.gl/maps/37yizQKTTvRzdQgX7 https://goo.gl/maps/iLy1uKPacbQfUuHn6 https://goo.gl/maps/bqyccMwxhEWHwPtX6 https://goo.gl/maps/bqyccMwxhEWHwPtX6 https://goo.gl/maps/rLMCd53gCc5q5YFi6

SAFETY BULLETIN

SUPERSEDES: Permit-Required Confined Spaces, Dated: 12/26/2012, 3/16/2023

TITLE: PERMIT-REQUIRED CONFINED SPACES

APPROVED:

/s/ Cody Baker 06/27/2025 Director, Employee Safety & Health DATE

ORGANIZATION RESPONSIBLE FOR INTERPRETATION:

Administrative Services Division/ Employee Safety & Health Bureau

Working in a Permit Required Confined Space (PRCS) involves potential significant risks, injuries, and fatalities due to various conditions that may occur in these spaces. These conditions may include:

• Atmospheric (flammable gas, vapor, mist, combustible dust, oxygen deficiency)

• Engulfment (capture by liquid or flowable solid)

• Entrapment (internal configuration or asphyxiated hazard by entering into smaller areas)

• Physical (electrical, mechanical, other safety hazards)

• Insufficient Training

The NYS Department of Transportation (NYSDOT) shall conform to the requirements in the Occupational Safety and Health Administration (OSHA) Permit-Required Confined Spaces (PRCS) Standard (29CFR1910.146). Nothing in this Safety Bulletin is intended to add additional requirements or abridge OSHA requirements. NYSDOT has a Confined Space Written Plan which details further the compliance to the OSHA PRCS Standard and is located on the NYSDOT SharePoint under the Safety and Health Resource page.

Confined spaces have the following stated properties:

• Large enough for a person to bodily enter and perform work

• Limited or restricted means of entry or exit

• Not designed for continuous occupancy

These three factors alone can exist in a general environment, such as a home attic or crawl space. However, when one of the following factors are present, along with a potentially hazardous condition that can exist, it would then be identified as a permit-required confined space such as:

• Hazardous atmosphere

• Engulfment

• Internal configuration that could trap or asphyxiate by progressively smaller areas

• Serious physical hazards such as electrical or mechanical

EXHIBIT 2

NYSDOT Safety Bulletin

Safety Bulletin Date: 6/27/2025 Page 2 Subject: PERMIT-REQUIRED CONFINED SPACES

Some spaces within a NYSDOT facility or location to consider would be: oil water separators, pits, manholes, silos, tanks, vessels, catch basins, drop inlets, and bridge compartments are, unless otherwise classified, to be regarded as a PRCS. Culverts, depending upon diameter, length, internal configuration, and other potential hazards may be deemed as a PRCS (see Culvert/Subsurface Entry Safety Bulletin). Entry into a PRCS occurs when any part of the entrant's body breaks the plane of the opening into the space.

Program management shall identify all PRCSs at their facility. PRCS spaces must be marked, using stenciling or posted signage, and an inventory list is to be maintained and placed within the Written Plan. The Written Plan will be reviewed and all facilities where Department employees enter a PRCS shall maintain a copy. Management shall notify employees or contractors of the existence of PRCS and requirements for working in them. Contractors working in NYSDOT facilities and locations shall have their own Confined Space Written Plan. Only employees or contractors who are trained and provided with appropriate equipment such as personal protective equipment, confined space equipment, and atmospheric monitoring equipment may enter a PRCS. The NYSDOT Confined Space Written Plan and any relevant documentation shall be readily available and accessible and placed in a conspicuous location within a facility and on the NYSDOT SharePoint Safety and Health resources section.

Facilities with an oil water separator must (as a minimum) mark or post a sign the opening as a PRCS and include it on the written list with any other facility PRCSs. In addition, where management has decided to have Department employees enter the oil water separator; entries must meet all requirements of the NYSDOT Confined Space Written Plan and this Safety Bulletin.

Contractors working on oil water separators must provide a copy of their Written Plan and be provided at least this Safety Bulletin and any other relevant confined space NYSDOT protocols.

It may be possible to work in a PRCS without entering it by using tools like a shepherd’s crook or if inspecting from the outside. In such instances, only this Safety Bulletin’s provisions for marking the opening, listing the PRCS, and basic instruction not to enter would be applicable.

Employee Safety and Health shall assist in identification of PRCSs; conduct confined space training; review the NYSDOT Confined Space Written Plan, any associated policies/procedures;

recommend personal protective equipment, confined space equipment, discuss about rescue procedures, and provide any other assistance as necessary. Air monitoring equipment will also be on hand to assess PRCS spaces.

PROCEDURE

Requirements necessary to be in place before entry by Department employees:

Written Plan addresses prevention of unauthorized entry, type(s) of hazard, work practices, air monitoring, roles and responsibilities, provision for entry supervisor, attendant, and entrant, rescue and emergency medical services, multi-employer operations (contractors), and provisions for review procedures. Hazardous operations within PRCS’s (such as hot work and painting) require special procedures/plans and permits are specifically prohibited without those provisions in place.

Safety Bulletin Date: 6/27/2025 Page 3

Written Entry Permit meets requirements of the OSHA Permit-Required Confined Space Standard ( 29CFR1910.146(f)). The entry permit authorizes entry into the permit space. It is to be reviewed and completed prior to entering PRCS spaces. The permit receives a numerical identification number from the Regional Employee Safety and Health Office. Copies are kept with the Program Area and Regional Employee Safety and Health Office (see attached under the Reference Section)

Entry Supervisor verifies requirements of the written entry permit and ensures means of rescue are readily available; cancels or terminates entry as required and removes unauthorized personnel; periodically monitors operation for conformance. When appropriate, can reclassify a PRCS to non-permit-required confined space in accordance with the OSHA Permit-Required Confined Space Standard.

Attendant(s) maintains accurate account of authorized entrants and remains at entry site until relieved by another attendant or until work is complete; monitors conditions around space with air monitoring equipment and maintains communication with entrant(s); performs non-entry rescue or summons rescue and medical services, as needed.

Entrant(s) enters the PRCS to conduct work tasks. Shall properly use required PPE, confined space equipment, maintain communication with attendant, and evacuate if emergency occurs.

Air Monitoring PRCSs shall be monitored for oxygen and flammable gases before and during entry. When organic material is present, hydrogen sulfide levels will be tested (afour-gas meter for oxygen, flammable gases, hydrogen sulfide and carbon monoxide is utilized). Testing shall be conducted from top down as space allows at various levels. Testing equipment shall be calibrated in accordance with manufacturer and must be in proper working condition. Test results shall be recorded on the entry permit. When oxygen levels are less than 19.5% or greater than 23.5%; or when combustible gases are greater than 10% of lower explosion limit; or toxic gases greater than permissible exposure limits, entry shall not be made, or the space shall be vacated.

Mechanical ventilation (portable blower with flexible duct work) is strongly recommended to purge the PRCS and provide continuous ventilation.

Equipment hard hats, safety vests, safety boots, are mandatory when working in PRCS. Hearing protection, boots for wetness or other appropriate safety footwear, flashlights, gloves, protective garments, low voltage and explosion-proof lighting and ladders should be available. Atmospheric monitoring device(s) are mandatory working in PRCSs. Communication equipment is mandatory when normal voice contact is not possible. Respiratory protection is generally not required to enter PRCSs. However, in certain instances, such as dust and odor control, respiratory protection may be appropriate.

Mechanical Retrieval Equipment is required for entry into vertical PRCS greater than 6 feet deep. Full-body harness attached to a mechanical lifting device shall be provided. Rescue by non-entry mechanical retrieval is preferred. If a PRCS has obstructions or turns such that mechanical retrieval equipment is not practical or creates more of a hazard, on-site rescue shall be immediately available prior to entry. On-site rescue shall be made by rescue personnel, properly trained and equipped, who have practiced rescue in PRCSs.

Safety Bulletin Date: 6/27/2025 Page 4

Rescue and Medical Services shall be provided by a local emergency responder. Means to summons rescue and medical services shall be immediately available and detailed on the written entry permit.

TRAINING

The NYSDOT Confined Space University offers two levels of Confined Space Training which are: Initial Training for New Employees and Annual Refresher Training.

This training shall be conducted before work assignments are to occur and entry into the permit confined spaces; when there is a change in operations; or when deviation in policy occurs. All training is posted on the NYSDOT Learning Management (LMS) system.

Training shall be documented and address:

• Types of confined space hazards

• Components of the NYSDOT written plan and written permit

• Entry Supervisor, Attendant, Entrant responsibilities

• Atmospheric monitoring equipment: use, calibration, and maintenance

• Acceptable entry conditions: oxygen, combustibles, carbon monoxide, and hydrogen sulfide

• Methods to control or eliminate hazards

• Health symptoms: narcosis, hypoxia, and other health effects

• Personal protective and other confined space equipment: full body harness, lifeline, tripod, respiratory protection, protective clothing, eye/face/hearing protection, communication equipment, and any other appropriate equipment

• Use of Non-Entry Rescue and Rescue/Medical Services when necessary

RECORDKEEPING

NYSDOT Written Confined Space Plan will be evaluated annually of the procedures that are implemented and continue to be in compliance with the OSHA PRCS Standard. Entry permits shall be retained yearly and evaluated to determine confined space hazards and address any corrective actions. PRCS inventory list shall be maintained and updated when necessary. Any relevant documents such as this Safety Bulletin, job hazard assessments and any other relevant documentation shall also be maintained and updated with the Written Plan.

REFERENCES

1910.146 - Permit-required confined spaces | Occupational Safety and Health Administration (osha.gov)

NYSDOT Confined Space Program: Confined Space Entry https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.146 https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.146 https://nysemail.sharepoint.com/sites/NYSDOTIntraDOT/AdminServices/safetyandhealth/Safety%20Written%20Plans/Forms/AllItems.aspx?id=%2Fsites%2FNYSDOTIntraDOT%2FAdminServices%2Fsafetyandhealth%2FSafety%20Written%20Plans%2FConfined%20Space%20Entry&viewid=c765221f%2Def6f%2D468b%2D9031%2Dfb817fd20746

NYSDOT PERMIT-REQUIRED CONFINED SPACE ENTRY PERMIT

Permit No.

Employee Safety and Health Approving Member

Name:

Signature:

Location and Hazard

Location:

Purpose of Entry:

Entry Permit Valid for: From date: To date:

Name and Model of Meter:

(Meter must be calibrated and calibration records available)

Atmospheric Testing: Check meter readings, record readings on separate worksheet

Prior to entry

During entry

Oxygen

Entry not permitted oxygen less than 19.5% or greater than 23.5%.

Explosive (Gas/Vapor)

Entry not permitted if LEL greater than 10%.

Carbon Monoxide

Entry not permitted if carbon monoxide greater than 35 ppm.

Hydrogen Sulfide

Entry not permitted if hydrogen sulfide greater than 10 parts ppm.

Dust (Some dusts such as wood, coal, grain, sugar is explosive)

Entry not permitted if visibility less than 5 feet.

Other Hazards Check Yes / No /

Electrical Hazards

Mechanical Hazards

Entry not permitted in confined spaces with serious hazards.

Identify controls for electrical and mechanical hazards, (if applicable).

Isolation

Inserting

First Aid

Equipment

Personal Protective Equipment Check /

Hard Hat

Gloves

Hearing protection (if needed)

Coveralls (if needed)

Respiratory protection (if needed)

Foot protection

Other equipment

Lighting (intrinsically safe electrical lighting or equipment)

Ladders

Meter (oxygen, combustible gas, carbon monoxide and hydrogen sulfide)

Entry not permitted without meter.

Communication equipment (if needed)

Entry not permitted without communication

Rescue

Entry not permitted without rescue provisions

Type of rescue provided Check /

Non entry retrieval by attendant (preferred)

Rescue by on-site rescue personnel. Indicate rescue provider.

Mechanical retrieval equipment harness, lifeline, tripod and winch.

Mechanical retrieval required for vertical entries over 5 feet.

For non-entry retrieval indicate first aid provider and means for summoning. CALL 911 for emergencies

For on-site rescue verify rescue personnel are currently certified and equipped.

Provider:

Summoned by:

On-site rescue will provide first aid.

CPR/FA Certified Employee:

DOT is not equipped and trained andwill not provide rescue other than non-entry attendant retrieval.

Employees

Attendant:

Entrants:

NYSDOT Supervisor Name/Signature: Date:

OWS Cleaning Completion Worksheet (one worksheet per OWS)

Location: ____________________________________________________________Start Work Date: _____________________________

Contractor: __________________________________________________________End Work Date: ______________________________

Manufacturer/ Model (if known): ____________________________Material: ___________ OWS Gallons: ___________

Grit Chamber: Material: ___________ Grit Chamber Gallons: ___________

Prior to Cleaning, Residency notes that the OWS is working properly: YES NO

Sample taken for testing: YES NO

VISUAL OBSERVATIONS at time of cleaning: LEAKS CRACKS

OTHER STRUCTURAL DEFECTS: ____________________________________________________________________________________

Oil Level: ________________________________________________(Note the approx. oil layer depth)

Sediment Level: _________________________________________(Note the approx. sediment depth)

INLET FLOWING: YES NO OULET FLOWING: YES NO

ALARM STATUS: WORKING NOT WORKING

MAINTENANCE PERFORMED: FLOOR DRAINS JETTED CHAMBERS PUMPED OUT

WALLS HOSED PLATES HOSED NEW FILTERS INSTALLED

COALESCING PLATES: NUMBER _____________SIZE____________

RECOMMENDATIONS for repairs /replacement: ____________________________________________________________________

DISCONTINUE USE OF OWS BASED ON FINDINGS: __________________________________________________________________

OWS CLEANING COMPLETE OWS CLEANING INCOMPLETE __________________________

Signatures:

Contractor Foreman: __________________________________________________________________Date: ______________________

NYSDOT Resident Engineer: ____________________________________________________________Date: ______________________

SIGN/SCAN/ATTACH this worksheet to with PHOTOS and email to Maintenance Environmental Coordinator.

EXHIBIT 3

Exhibit 1 OWS Locations and Specs
Exhibit 2 Permit-Required Confined Space
PROCEDURE
TRAINING
RECORDKEEPING
REFERENCES
NYSDOT PERMIT-REQUIRED CONFINED SPACE ENTRY PERMIT

Exhibit 3 OWS Cleaning Completion Worksheet

Location:
Start Work Date:
Contractor:
End Work Date:
Manufacturer Model if known:
Material:
OWS Gallons:
Grit Chamber Material:
Grit Chamber Gallons:
Prior to Cleaning Residency notes that the OWS is working properly: Off
Sample taken for testing: Off
LEAKS: Off
CRACKS: Off
OTHER STRUCTURAL DEFECTS:
Oil Level:
Sediment Level:
INLET FLOWING: Off
WORKING: Off
NOT WORKING: Off
FLOOR DRAINS JETTED: Off
CHAMBERS PUMPED OUT: Off
WALLS HOSED: Off
PLATES HOSED: Off
NEW FILTERS INSTALLED: Off
COALESCING PLATES NUMBER:
SIZE:
RECOMMENDATIONS for repairs replacement 1:
RECOMMENDATIONS for repairs replacement 2:
DISCONTINUE USE OF OWS BASED ON FINDINGS:
OWS CLEANING COMPLETE: Off
undefined: Off
OWS CLEANING INCOMPLETE:
Contractor Foreman:
Date:
NYSDOT Resident Engineer:
Date_2: