B429 - Point_Schedule_BACnet.xlsx

XLSX spreadsheet 54 KB Posted

Attached to
Solicitation Bldg. 120 and 429 Server Room & HVAC Controls Repairs
Solicitation number
W91QF42025IFB04
Issued by

About this file

The document is a detailed Points Schedule Excel file for Building 429's HVAC Control System, specifying comprehensive technical specifications for various system components including Air Handling Units (AHUs), Energy Recovery Ventilators (ERVs), Chilled Water Systems, Hot Water Systems, and Building Spaces (Fan Powered VAV). The schedule meticulously outlines point-by-point technical requirements for system monitoring, including status indicators, temperature measurements, valve commands, fan controls, and alarm conditions across multiple system elements.

The related federal contract opportunity (Solicitation W91QF42025IFB04) involves HVAC control system repairs at Buildings 120 and 429 for the Department of the Army. Specifically, the project requires replacing interior computer room units and condensing units at Building 120, and upgrading the existing HVAC control system at Building 429 to the current Automated Logic control system. The solicitation seeks a general contractor capable of managing multiple task orders, involving construction scheduling, cost estimation, quality control, and subcontractor coordination across various construction trades.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Read Me Not all columns of the Points Schedule will be used. Which are used depends on the protocol selection. Rows 4-7 of the Points Schedule in this file indicate which columns apply to which protocols. Once unused columns are deleted or hidden, rows 4-7 may also be deleted or hidden

Similarly, some notes will not apply depending on protocol selection. The column next to the notes indicate when a note is or not applicable. Remove non-applicable notes and replace the colored cells indicating applicability with blank cells.

Points Schedule-Blank

BUILDING 429 HVAC CONTROL SYSTEM
ATTACHMENT A - POINTS SCHEDULE
ALARMINGPRIMARY POINT INFORMATIONNETWORK DATA EXCHANGEOVERRIDESTREND OBJECT LOCATION (L OR R), TYPE AND INSTANCE NUMBER
(PROVIDE DDC ID FOR REMOTE IN NOTES)ALARM INFORMATIONCONFIGURATION INFORMATION
FUNCTIONPOINT NAMEDESCRIPTIONDDC

HARDWARE

IDSETTING
(WITH UNITS)RANGE
(WITH UNITS)IO
TYPEHOA REQ'DCONFIG. TYPEM&C VIEW AND OVRDLDP VIEW AND OVRDTREND REQ'DALARM CONDITION
(SEE NOTES)ALARM
PRIORITYM&C
ROUTINGOBJECT TYPE AND INSTANCE NUMBER
(AND PROPERTY ID)DATA FROMDATA TOOBJECT TYPE & INSTANCE NUMBER

OR

COMMANDABLEALARM TYPE
(PROVIDE DDC ID FOR REMOTE IN NOTES)NOTIFICATION CLASS OBJECT INSTANCE NUMBEREVENT ENROLLMENT OBJECT INSTANCE NUMBER
AIR HANDLING UNITs (AHU)SF-SSUPPLY FAN STATUS<___>ON/OFFBI[~]V[V]YPROOF FAILED[INFO] [CRIT][___]
SF-CSUPPLY FAN START/STOP<___>ENABLE/DISABLEBOYVOVY
FN-SPSUPPLY FAN COMMAND<___>0-100%AO[~]VOVY
RA-TRETURN AIR TEMPERATURE<___>[____ DEG F]AIVVV
RA-CO2RETURN AIR CO2<___>AIVVV
MA-TMIXED AIR TEMPERATURE<___>[____ DEG F]<___>AIVVYIF MA-T < 35 DEG F[INFO] [CRIT][___]
FLT-PFILTER PRESSURE<___>[___ IWC]<___>AIVVNPRESSURE IS OVER 1 IN. W.G. DROP[INFO][___]
CLG-V-SCHILLED WATER COIL STATUS<___>0-100%AIVVY
CLG-V-CCHILLED VALVE COMMAND<___>0-100%AOVOVY
CLG-DA-TCOOLING COIL DISCHARGE AIR TEMP<___>[____ DEG F]<___>AIVVYIF CLG-DA-T > 10 + CLG-DA-T-SP
IF CLG-DA-T < 10 - CLG-DA-T-SP[INFO] [CRIT][___]
CLG-DA-T-SPCOILING COIL DISCHARGE AIR TEMP SETPOINT<___>[____ DEG F]<___>AOVOVY
HTG-V-SHEATING HOT WATER COIL STATUS<___>0-100%AIVVY
HTG-V-CHEATING VALVE COMMAND<___>0-100%AOVOVY
DA-TSUPPLY AIR DB TEMP<___>[____ DEG F]<___>AIVVYIF DA-T > 10 + DA-SP
IF DA-T < 10 - DA-SP[INFO] [CRIT][___]
DA-SPSUPPLY AIR TEMPERATURE SETPOINT<___>[____ DEG F]<___>AOVOVY
STPSTATIC PRESSURE<___>[___ IWC]<___>AI[~]VVYSA-P MORE THAN 20% ABOVE OR BELOW STP-SP[INFO] [CRIT][___]
STP-SPSTATIC PRESSURE SETPOINT<___>[___ IWC]<___>AOVOVY
ENERGY RECOVERY VENTILATOR (ERV)OA-TOUTSIDE AIR TEMPERATURE<___>[____ DEG F]<___>AIVVY
EA-TEXHAUST AIR TEMPERATURE<___>[____ DEG F]<___>AIVVY
DA-TSUPPLY AIR TEMPERATURE<___>[____ DEG F]<___>AIVVY
DA-SPSUPPLY AIR TEMPERATURE SETPOINT<___>[____ DEG F]<___>AOVOVY
RA-TRETURN AIR TEMPERATURE<___>[____ DEG F]<___>AIVVY
Heat Recvy-SHEAT WHEEL STATUS<___>ON/OFFBIVVYPROOF FAILED[INFO] [CRIT][___]
Heat Recvy-CHEAT WHEEL COMMAND<___>ENABLE/DISABLEBOVOVY
SF-SSUPPLY FAN STATUS<___>ON/OFFBIVVYPROOF FAILED[INFO] [CRIT][___]
SF-CSUPPLY FAN START/STOP<___>ENABLE/DISABLEBOYVOVY
EF-SEXHAUST FAN STATUS<___>ON/OFFBIVVYPROOF FAILED[INFO] [CRIT][___]
EF-CEXHAUST FAN START/STOP<___>ENABLE/DISABLEBOVOVY
CHILLED WATER SYSTEMChWS-T-SPCHILLED WATER SUPPLY TEMPERATURE SETPOINT<___>[____ DEG F]<___>AOVOVY
ChWS-TCHILLED WATER SUPPLY TEMPERATURE<___>[____ DEG F]<___>AIVVYIF ChWS-T > 55 DEG F
IF ChWS-T < 40 DEG F[INFO] [CRIT][___]
ChWR-TCHILLED WATER RETURN TEMPERATURE<___>[____ DEG F]<___>AIVVY
CWSYS-ECHILLER COMMAND<___>ENABLE/DISABLEBOYVOVY
CWP-SALL PUMP SPEED<___>0-100%AIVVY
CWP-EALL PUMP START-STOP COMMAND<___>ENABLE/DISABLEBOYVOVY
CW-DPCHILLED WATER LOOP DIFFERENTIAL PRESSURE<___>[___ PSI]<___>AIVVYCW-DP MORE THAN 20% ABOVE OR BELOW CW-DP-SP[INFO] [CRIT][___]
CW-DP-SPCHILLED WATER LOOP DIFFERENTIAL PRESSURE SETPOINT<___>[___ PSI]<___>AOVOVY
HOT WATER SYSTEMHWS-THOT WATER SUPPLY TEMPERATURE<___>[____ DEG F]<___>AIVVYIF HWS-T > 180DEG F
IF HWS-T < 100 DEG F[INFO] [CRIT][___]
HWS-T-SPHOT WATER SUPPLY TEMPERATURE SETPOINT<___>[____ DEG F]<___>AOVOVY
HWR-THOT WATER RETURN TEMPERATURE<___>[____ DEG F]<___>AIVVY
HW-DPHOW WATER DIFFERENTIAL PRESSURE<___>[___ PSI]<___>AIVVYHW-DP MORE THAN 20% ABOVE OR BELOW HW-DP-SP[INFO] [CRIT][___]
HW-DP-SPHOW WATER DIFFERENTIAL PRESSURE SETPOINT<___>[___ PSI]<___>AOVOVY
HWP-EALL PUMP START-STOP COMMAND<___>ENABLE/DISABLEBOYVOVY
HWP-SALL PUMP SPEED<___>0-100%AIVVY
HWSYS-EHOT WATER SYSTEM ENABLE<___>ENABLE/DISABLEBOYVOVY
BUILDING SPACES (Fan Powered VAV)ZN-TZONE TEMPERATURE<___>[____ DEG F]<___>AIVVYIF ZN-T > 78 DEG F
IF ZN-T < 68 DEG F[INFO] [CRIT][___]
ZN-T-SPZONE TEMPERATURE SETPOINT<___>[____ DEG F]<___>AOVOVY
DAMPER%DAMPER POSITION<___>ENABLE/DISABLEBIVVY
ZN-FTERMINAL AIRFLOW<___>[___ CFM]<___>AIVVY
HTG-SHEATING STATUS<___>ON/OFFBIVVY
HTG-CHEATING COMMAND<___>ENABLE/DISABLEBOVOVY
ZN-OCCZONE OCCUPANCY INPUT<___><___>BIVVY
DA-TDISCHARGE AIR TEMP<___>[____ DEG F]<___>AIVVYIF DA-T > 10 + DA-SP
IF DA-T < 10 - DA-SP[INFO] [CRIT][___]
Fan-CFAN STATUS<___>ON/OFFBOVVYPROOF FAILED[INFO] [CRIT][___]
Notes:
1)THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.
2)UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
3)UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.
4)DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____>
5)DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>

Points Schedule-Sample Entries

VAV [WITH][WITHOUT] RETURN FAN
EXAMPLE ONLY. This example Points Schedule is intended to demonstrate the overall format for a Points Schedule and illustrate the type and scope of entries. Points Schedules for actual systems/sequences are being updated and created under a separate effort to update HVAC Sequences of Operation. The points shown is this Points Schedule are not represetnative of a properly designed system.
COLUMN IS USED FOR BACNET (NO NIAGARA)YYYYYYYYY
COLUMN IS USED FOR BACNET (WITH NIAGARA)YYYYNYYNY
COLUMN IS USED FOR LNS LONWORKS (NO NIAGARA)NNNNNNNNY
COLUMN IS USED FOR LONWORKS (WITH NIAGARA)NNNNNNNNY
ALARMINGPRIMARY POINT INFORMATIONNETWORK DATA EXCHANGEOVERRIDESTREND OBJECT LOCATION (L OR R), TYPE AND INSTANCE NUMBER
(PROVIDE DDC ID FOR REMOTE IN NOTES)ALARM INFORMATIONCONFIGURATION INFORMATION
FUNCTIONPOINT NAMEDESCRIPTIONDDC

HARDWARE

IDSETTING
(WITH UNITS)RANGE
(WITH UNITS)IO
TYPEHOA REQ'DCONFIG. TYPEM&C VIEW AND OVRDLDP VIEW AND OVRDTREND REQ'DALARM CONDITION
(SEE NOTES)ALARM
PRIORITYM&C
ROUTINGOBJECT TYPE AND INSTANCE NUMBER
(AND PROPERTY ID)DATA FROMDATA TOOBJECT TYPE & INSTANCE NUMBER

OR

COMMANDABLEALARM TYPE
(PROVIDE DDC ID FOR REMOTE IN NOTES)NOTIFICATION CLASS OBJECT INSTANCE NUMBEREVENT ENROLLMENT OBJECT INSTANCE NUMBER

PROOFS

SAFETIESSF-SSUPPLY FAN STATUSON/OFFBIV[ V ][ ~ ]SUPPLY FAN PROOF FAILED[info] [crit][___]<INTRINSIC><REMOTE ALGORITHMIC><LOCAL ALGORITHMIC><NIAGARA FRAMEWORK>
RF-SRETURN FAN STATUSON/OFFBIV[ V ][ ~ ]RETURN FAN PROOF FAILED[info] [crit][___]
SA-SMKSUPPLY AIR SMOKEALM/NORMALBIALM[info] [crit][___]
RA-SMKRETURN AIR SMOKEALM/NORMALBIALM[info] [crit][___]
CLG-DA-T-LLCOOLING COIL DISCHARGE AIR TEMP LOW LIMIT39 DEG FALM/NORMALBIHV[~]ALM[info] [crit][___]
SA-P-HLSUPPLY AIR PRESSURE HIGH LIMIT[___ IWC]ALM/NORMALBIHALM[info] [crit][___]
RST-BUTSYSTEM RESET BUTTON (FOR SAFETIES)[NET-IN][BI]

SCHEDULING SYS-OCC-SCHED SYSTEM OCCUPANCY SCHEDULE SEE OCCUPANCY SCHEDULE DRAWING <NET-OUT> OC V [~] SCHEDULE OBJECT <___> <___>

START/STOPUNIT STATUSUNIT STATUS (HTG AND/OR CLG REQUEST) (SEE NOTES)NET-OUT[V][ ~ ][ ~ ]~~~
SYS-OCC-COCCUPANCY COMMANDOCCUPIED(1)/WUCD(2)/UNOCCUPIED(3)<NET-IN>VO[~][ ~ ]MSV <___>
SYS-OCCSYSTEM OCCUPANCY (ACTUAL)OCCUPIED(1)/WUCD(2)/UNOCCUPIED(3)<~><NET-OUT>V[V]XMSV <___>
SF-SSSUPPLY FAN START/STOPON/OFFBO[~]VO[ V ][ ~ ]
RF-SSRETURN FAN START/STOPON/OFFBO[~]VO[ V ][ ~ ]
BLDG-TBUILDING TEMPERATURE (NIGHT STAT)<___><AI><NET-IN>V[ ~ ][ ~ ]BLDG-T LESS THAN BLDG-T-LL[info] [crit][___]
BLDG-T-LLBUILDING TEMPERATURE LOW LIMIT[55 DEG F]CVO[ ~ ]<___>
SUPPLY FAN CAPACITY CONTROLSF-CSUPPLY FAN COMMAND0-100%AO[~]VO[ ~ ][ ~ ]
SA-PSUPPLY AIR PRESSURE<___>AI, NET-OUTV[ V ]XSYSTEM HAS BEEN IN OCCUPIED MODE FOR MORE THAN 5 MINUTES AND SA-P IS MORE THAN 20% ABOVE OR BELOW SA-P-SP[info] [crit]<___>DDC #17,

DDC #18,

DDC #19

SA-P-SPSUPPLY AIR PRESSURE SETPOINT<___>CVO[ ~ ]
SUPPLY FAN CONTROL LOOP

CONFIGURATION

SETTINGSPROPORTIONAL CONSTANT
INTEGRAL CONSTANT
BIAS
MAXIMUM OUTPUT
MINIMUM OUTPUT
<____>
RETURN FAN CAPACITY CONTROLSA-FSUPPLY AIR FLOW[0 - ___ CFM]NET-INV[ V ][ ~ ][ ~ ]~[___]DDC#12
RA-FRETURN AIR FLOW[0 - ___ CFM]AIV[ V ][ ~ ][ ~ ]~[___]
RF-CRETURN FAN COMMAND0-100%AO[~]VO[ ~ ][ ~ ]
F-DIFF-SPFLOW DIFFERENCE SETPOINT[___ CFM]OCVO[ ~ ]<___>
RETURN FAN CONTROL LOOP

CONFIGURATION

SETTINGSPROPORTIONAL CONSTANTC<___>
INTEGRAL CONSTANTC<___>
BIASC<___>
MAXIMUM OUTPUTC<___>
MINIMUM OUTPUTC<___>
<____>C<___>
MINIMUM
OUTSIDE AIRMINOA-FMINIMUM OUTSIDE AIR FLOW[0 - ___ CFM]AIV[ V ]XMINOA-F LESS THAN 80% OF MINOA-F-SP[info] [crit][___]
MINOA-D-CMINIMUM OUTSIDE AIR DAMPER COMMAND<0-100% OPEN>AO[~]VO[ V ][ ~ ]
MINOA RESET SCHEDULE FOR DCVCO2 MAXIMUM VALUE[___ PPM]C
CO2 MINIMUM VALUE[___ PPM]C
MINOA FLOW MINIMIM VALUE (AT CO2 MINIMUM VALUE)[___ CFM]C
MINOA FLOW MAXIMUM VALUE (AT CO2 MAXIMUM VALUE)[___ CFM]C
MINOA-F-SPMINIMUM OUTSIDE AIR FLOW SETPOINT (SETTING)[___ CFM]CVO[~]<___>
MINIMIM OUTSIDE AIR DAMPER CONTROL LOOP

CONFIGURATION

SETTINGSPROPORTIONAL CONSTANT<___>C<___>
INTEGRAL CONSTANT<___>C<___>
BIAS<___>C<___>
MAXIMUM OUTPUT<___>C<___>
MINIMUM OUTPUT<___>C<___>
<____><___>C<___>
MIXED AIR TEMPERATURE CONTROL WITH ECONOMIZEROA-TOUTSIDE AIR TEMPERATURE<___>AIV[ V ]X[ ~ ]~[ ~ ]
MA-TMIXED AIR TEMPERATURE<___>AIV[ V ]X[ ~ ]~[ ~ ]
MA-D-CMIXED AIR DAMPER COMMAND0-100% OPENAO[~]VO[ V ][ ~ ]
ECO-HL-SPECONOMIZER HIGH LIMIT SETPOINT[___]C[~][ V ]<___>
ECO-LL-SPECONOMIZER LOW LIMIT SETPOINT[___]CVO[ V ]<___>
MA-T-SPMIXED AIR TEMPERATURE SETPOINT[___]CVO[~]<___>
MIXED AIR DAMPER CONTROL LOOP

CONFIGURATION

SETTINGS<THROTTLING RANGE><PROPORTIONAL GAIN><___>C<___>
INTEGRAL CONSTANT<___>C<___>
BIAS<___>C<___>
MAXIMUM OUTPUT<___>C<___>
MINIMUM OUTPUT<___>C<___>
<ALL OTHER CONFIG SETTINGS - ADD ROWS AS NEEDED><___>C<___>
SUPPLY AIR TEMPERATURESA-TSUPPLY AIR TEMPERATURE<___>AIV[ V ]XSYSTEM HAS BEEN IN OCCUPIED MODE FOR MORE THAN 5 MINUTES AND SA-T MORE THAN 10 DEG F ABOVE OR BELOW SETPOINT[info] [crit][___]
CLG-V-CCOOLING VALVE COMMAND<0-100% OPEN>AO[~]VO[ V ][ ~ ]
SA-T-SPSUPPLY AIR TEMPERATURE SETPOINT[55 DEG F]OCVO[ V ]<___>
COOLING VALVE CONTROL LOOP CONFIGURATION SETTINGS<THROTTLING RANGE><PROPORTIONAL GAIN><___>C<___>
INTEGRAL CONSTANT<___>C<___>
BIAS<___>C<___>
MAXIMUM OUTPUT<___>C<___>
MINIMUM OUTPUT<___>C<___>
<____><___>C<___>
OTHER POINTSRA-TRETURN AIR TEMPERATURE<___>AIV[ ~ ][ ~ ][ ~ ]~[___]
MA-FLT-P-HLMIXED AIR FILTER PRESSURE HIGH LIMIT SWITCH<___>ALM/NORMALBIH~[ ~ ]ALM[info] [crit][___]
OA-FLT-POUTSIDE AIR FILTER PRESSURE<___>AIV[ ~ ]OA-FLT-P LESS THAN OA-FLT-P-LL[info] [crit][___]
OA-FLT-P-LLOUTSIDE AIR FILTER PRESSURE LOW LIMIT<___>C~[ ~ ]
Notes:
1)THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.
2)UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
3)UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.
THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA)4)DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____>
THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA)5)DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>
THIS NOTE IS USED ONLY FOR LNS LONWORKS (NO NIAGARA)6)DDC HW IF FOR DEVICE CONTAINING SIMPLE SCHEDULER OBJECT (OR SYSTEM SCHEDULER SEQUENCE OF OPERATIONS) FOR THIS SYSTEM: <_____>