B33805 Ice Machine Drawing Markup.pdf
PDF 6 MB Posted
- Attached to
- Ice Machine Install
- Solicitation number
- W9124925RA035
About this file
These documents are detailed technical specifications and as-built drawings for an Ice House America ice machine kiosk installation, focusing on plumbing, electrical, and site layout. The plans include comprehensive details for a 16' ice machine unit with optional water filtration systems, including reverse osmosis (RO), water softener, and water dispensing capabilities. Key infrastructure components include a dedicated electrical room (RM 159), scrub room (RM 166), and specific provisions for water and sewer connections, with precise routing and equipment placement diagrams.
The electrical specifications outline a complex power distribution system with multiple panel boards (DP1, MPB-1, MPB-2, PP1MA, PP1MB) supporting the ice machine and associated systems. The electrical design includes 60A 3-pole breakers for the icemaker and a 125A 2-pole breaker for the machine kiosk, with a total connected load of approximately 22.5 kW and 108 amps. The plumbing design features detailed water treatment and drainage systems, including filtration, UV sterilization, and specific drain line configurations, with provisions for connecting to existing site infrastructure and meeting local building and plumbing code requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation - W9124925RA035.pdf | ||
| Connect Ice Machine SOW 7 Aug 2025.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ice Machine
Electrical Room
Scrub Room (nearest sanitary and domestic)
2" FLOOR DRAIN TO
BOTTOM OF FRAME
WATER DISPENSER
DRAIN FROM BOTTOM OF
FRAME (1" AIR GAP)
UV LIGHT
4" BALL VALVE TO ICE MAKER
From RO Water Tank/ Softner
DRAIN LINE
WATER DISPENSER
(OPTIONAL)
COOLING UNIT
(ON ROOF)
ICE M
AKER
FLOOR DRAIN TROUGH
PRESSURE REGULATOR
FLOW SENSOR
SOLENOID VALVE
SEDIMENT FILTER
DECLORINATOR FILTER
WATER SOFTNER
(OPTIONAL)
RO SYSTEM (OPTIONAL)
W WWWW
W
WW
W
W
BRINE TANK
WATER TANK
GRUNDFOS PUMP
4" BALL VALVE
Y STRAINER
4" BALL VALVE FOR R.O.
SOFTNER BYPASS
2" SHUTOFF
D DD
D
D
D D
2" PEX PIPE (this side or other side)
D
WATER ENTRANCE
FROM BOTTOM OF FRAME
PRESSURE GUAGE
AIR GAP BEFORE TROUGH DRAIN
FOR ICE MAKER, COOLING UNIT,
WATER SOFTENER & RO
CARBON FILTER
(NOT SHOWN -
OPTIONAL)
W/ TRAP PRIMER OR
TRAP SEAL PROTECTION
Notes:
1. ALL AIR GAPS WILL BE A MINIMUM OF TWO PIPE DIAMETERS IN ACCORDANCE WITH IPC 802.3.1.
2. ALL INDIRECT WASTE IS IN THE INTERIOR OF THE BUILDING AND NOT LOCATED IN A WAY TO RECEIVE RAINWATER.
3. POTABLE WATER SUPPLY TO COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS, ALONG WITH
CARBONATED BEVERAGE DISPENSERS, SHALL BE PROTECTED BY AN APPROVED VENTED BACKFLOW PREVENTION DEVICE (TWO INDEPENDENT CHECK VALVES WITH A VENT TO THE ATMOSPHERE) CONFORMING TO ASSE 1022 OR BY
AN AIR GAP
ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550
COA: -
These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.
Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.
ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.
TITLE:
MODEL:
APPROVED BY: JOB NO:
DRAWN BY: DRAWING NO:
REVISIONS: SCALE:
DATE:
3/14/24 LML 16' IVK
[PROJECT NUMBER]NTS
P-1
PLUMBING LAYOUT
Jacksonville, FL 32224 Ice House America-
4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com
TBPE FIRM NO. F-19923
Water line connection located beneath ice machine
WATER TANK BRINE
TANK
WATER SOFTNER
Y-STRAINER
REVERSE
OSMOSIS
HOSE BIB LOCATED
FRONT OF MACHINE
PRESSURE GUAGE
WATER IN
ICE MAKER
20" 5
SEDIMENT FILTER
20" 0.5
CARBON FILTER
#2 34" PEX BALL VALVE
FOR RO BYPASS
(NC WHEN R.O. ON)
#7 12" PEX BALL VALVE
(LOCATED REAR END OF MACHINE)
#1 34" PEX BALL VALVE
UV BULB
FLOW METER
WATER
DISPENSOR
(OPTIONAL)
DISPENSING NOZZLE
(NOZZLE IS PROTECTED
FROM CONTAMINATION
VIA. EXTERNAL SHIELD)
RINSE CYLCE
METER BYPASS
SOLENOID VALVE
SOLENOID IS DRIVEN BY
PLC OUTPUT Y17 AND
WILL TURN OFF WITH UV
LIGHT UNDER ABNORMAL
CONDITIONS DEMA 38"
SOLENOID VALVE
#3 34" PEX
BALL VALVE
REVERSE OSMOSIS SYSTEM (OPTIONAL)
2" SHUTOFF VALVE
(LOCATED FRONT OF MACHINE)
PRESSURE GUAGE
8" Poly Tubing
2" Funny
Pipe 3 8" Poly Tubing
2" Pex Pipe
4" Pex Pipe
3 4" P ex P ip e
2" JG Tube
1 12" SCH40 Pipe
3 4" P ex P ip e
3 4" P ex P ip e
3 4" P ex P ip e
8" Poly Tubing
#4 34" PEX
BALL VALVE
ICE MAKER DRAIN
TO TROUGH
#5 34" PEX
BALL VALVE
RO water for Ice Maker & Water Dispenser Turn Off Valve # 2 & 5
Soften water for Ice Maker & RO Water for Water Dispenser Turn Off Valve # 2 & 4
Soften water for Ice Maker & Water Dispenser Turn Off Valve # 3
DELIVERY
PUMP
RO DRAIN TO TROUGH
WATER SOFTNER DRAIN
TO TROUGH
#6 12" PEX BALL VALVE
ROOF TOP
STERILIGHT UV LIGHT
HAS POWERED OUTPUT
(120V) INTO PLC INPUT
X17 WHICH WILL TURN
OFF UNDER ABNORMAL
CONDITIONS
WATER DISPENSER DRAIN
TO PIPE
GUAGE AND
PRESSURE REGULATORCOOLING UNIT
ON ROOF
COOLING UNIT DRAIN
TO TROUGH
HOSE BIB LOCATED
REAR OF MACHINE
ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550
COA: -
These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.
Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.
ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.
TITLE:
MODEL:
APPROVED BY: JOB NO:
DRAWN BY: DRAWING NO:
REVISIONS: SCALE:
DATE:
3/14/24 LML 16' IVK
[PROJECT NUMBER]NTS
P-2
PLUMBING SCHEMATIC
Jacksonville, FL 32224 Ice House America-
4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com
TBPE FIRM NO. F-19923
Water line connection located beneath ice machine
Scrub room with nearest available domestic water and sanitary sewer piping
Approximate location of ice machine kiosk
Nearest available domestic water piping
PLAN VIEW
SCALE 1 / 15
ELEVATION VIEW
SCALE 1 / 15
ICE BIN
ICE BAGGER
ICE MAKER COOLING UNIT
FILTRATION
SYSTEM
TYPICAL WATER DRAIN/ 'P' TRAP DIAGRAM
NO SCALE (REFER SITE SPECIFIC DWG/LOCAL CODE)
TO PUBLIC SEWER SYSTEM
OR PRIVATE DISPOSAL UNLESS
APPROVED BY LOCAL
AUTHORITIES OTHERWISE
TROUGH DRAIN FOR
ICE MAKER
COOLING UNIT
WATER SOFTNER
RO (OPTIONAL)
3" PVC MIN @ 18 FT
AAV VENT
2" PVC
1 12" PIPE DRAIN FOR
WATER DISPENSER
FROM FRONT OF UNIT
CLEAN OUT AT
EXTERIOR GRADE
SLOPE TO DRAIN
INSULATED FLOOR PANELS
4X4 STEEL BEAM UNDERNEATH
WATER SERVICE DETAIL
PRESSURE REDUCING VALVE
DOUBLE DETECTOR CHECK VALVE/ BACKFLOW PREVENTER
SHUT OFF VALVE, TYP
SHUT-OFF VALVE, TYP
3/4"
NO SCALE
DI
RE
CT
IO
N
OF
F
LO
W
3/4" DOMESTIC WATER SERVICE LINE FROM METER
SEE WATER DRAIN/ "P" TRAP DIAGRAM
BA
CK
O F
TH
E
UN
IT
ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550
COA: -
These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.
Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.
ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.
TITLE:
MODEL:
APPROVED BY: JOB NO:
DRAWN BY: DRAWING NO:
REVISIONS: SCALE:
DATE:
3/14/24 LML 16' IVK
[PROJECT NUMBER]
ARH
NTS
EQ-1A
EQUIPMENT INFORMATION W/ SEWER DRAINAGE
Jacksonville, FL 32224 Ice House America-
4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com
TBPE FIRM NO. F-19923
Drain line to be installed by contractor
Connect to existing drain line
Nearest available sanitary sewer piping
Notes:
1. ALL ELECTRICAL EQUIPMENT SHALL MEET WORKING CLEARANCE REQUIREMENT.
2. ALL FIXTURES SHALL BE SECURED TO STRUCTURE.
3. ALL FLEX SHALL CONTAIN FULL SIZE GREEN GROUND. NO ALUMINUM BONDS OR CONDUCTORS.
4. GROUND PER NEC CODES.
5. LOAD & BREAKER TABLE IS FOR GENERAL REFERENCE ONLY.
CALCULATE LOAD SIZE BASED ON ACTUAL MACHINE SPECIFICATION.
ICE MAKER
3P- DISC. SWITCH
NEMA 3R
COOLING
UNIT
240 / 120 V 3 Phase 4W
OR
208 / 120 V 3 PHASE 4 W
SERVICE BY UTILITY
FIELD CONNECTION
INSIDE
ELECTRICAL
PANEL
3 #6 THHN (CU),
#10 GD (CU), 1" C
STD KIOSK W/O OPTION:
3 #3 THHN (CU),
#8 GD (CU), 1.5" C
OR
REFER TABLE FOR DIFFERENT SPEC
60 Amp 3P
BREAKER FOR
ICE MAKER
OUTSIDE
ELECTRICAL
PANEL
FACTORY INSTALLED
2 #12 THHN (CU),
#12 GD (CU), 1/2" C
KIOSK WITH 5200 ARCTIC TEMP IM
1 PHASE POWER SUPPLY
#2(CU) SERVICE GD
TO GROUND ROD
METER
SEE TABLE TO
CALCULATE
BREAKER SIZE
C#20/22/24
C#1/3
NAME DETAIL WATTS VOLTAGE AMPERAGE WIRE GROUND CONDUIT
COOLING UNIT Cooling Unit 1886 230 8.2000 12 12 1
2" CONTROL PLC & All Prox Sensors 600 110 5 14 14 -
LIGHTS
7 LED RTFT Top hat Light 98 115 0.9500 14 14 1 2"
Inside Front Flood Lights 26 115 0.2500 14 14 1 2"
VF & Top Hat LED Module 158 115 1.5300 14 14 1 2"
Inside Rear Lights (Optional) 20 115 0.1900 14 14 1 2"
RECEPT
Air Compressor 1150 115 10 14 14 1 2"
MDB Pro 230 115 2 14 14 NA Router, Modem & (Optional) Camera 92 115 0.8000 14 14 NA
Audio Speaker (Optional) 3 24 0.1250 - - -
HEATERS
50W Heater (Ice MB) 50 115 0.5000 14 14 NA 50W Heater (Ele Cab) 50 115 0.5000 14 14 NA
Heater Inside Kiosk (Optional) 1500 115 12.5000 14 14 -
MOTORS
Bin Motor 621 230 2.7000 14 14 1
2" Rack Motor 1242 230 5.4000 14 14 1
2" Incline Auger Motor 1242 230 5.4000 14 14 1
2" ROOF TOP RECEPT Roof Heat tape (2x 18'L - Optional) 360 115 3.1300 14 14 -
WATER DISP.
Water Dispenser Controller
115 0.2000 14 14 -
50W Heater 115 0.5000 14 - NA UV Light 115 0.2000 14 14 -
WATER
SOFTENER/DELIVERY
PUMP
Water Softener 60 115 0.5000 14 14 1 2"
Scala Delivery Pump (Optional) 990 115 8.6200 12 14 1 2"
RO R4X40-1 RO System (Optional) 920 115 8 12 14 1 2"
BLOWER Bag Blower 1610 115 14 14 - 1 2"
(Optional)
13008 240 A SERVICE RATING
5200 Arctic Temp IM 9400 208-230 45.2000 6 10 1"
22408
22408 240 A SERVICE RATING
SERVICE FROM OUTSIDE ELECTRICAL PANEL
DOUBLE GANG RECEPTACLE FOR CWP (OPT.)
SINGLE GANG RECEPTACLE (STANDARD) FOR
AIR COMPRESSOR
INCLINED AUGER MOTOR SWITCH
BLOWER MOTOR SWITCH
C#11
C#6
C#4
C#5
TO SENSORS
BIN FLOOR MOTOR SWITCH
RAKE MOTOR SWITCH
INSIDE LIGHT
C#6 C#6
C#3
REAR JUNCTION BOX FOR RO
REAR JUNCTION BOX
SINGLE GANG RECEPTACLE
(STANDARD) FOR WATER
SOFTENER/RO DELIVERY PUMP
DOUBLE GANG RECEPTACLE FOR CWP (OPT.)
C#5
C#9
C#10
TO ROOF TOP
ELECTRICAL
CONTROL
CABINET
TO WATER
DISPENSOR
C#8
ROOF LINEROOF LINE
ROOF TOP JUNCTION BOX-2ROOF TOP JUNCTION BOX-1
ROOF TOP RECEPTACLE
C#7
TO ICE MAKER
TO COOLING UNIT
C#1
TO TOP HAT LIGHT
C#3
125 AMP DISCONNECT SWITCH
CONTROL PANEL SCHEDULE (INSIDE KIOSK)
VOLTAGE: 240 /120, 1PH., 4 WIRE
PHASE LOAD TOTALS
C# LOAD TRIP POLE A B POLE TRIP LOAD C#
1 COOLING UNIT 20 2
<-- 943 <-- 943
1 20 CONTROL 2600 -->
3 LIGHTS (TOP HAT, VF, INSIDE) 20 1
<-- 300
1 20 RECEPTACLE (AIR COMP) 41475 -->
5 HEATERS (ELE CAB & MB CAB HEATER & COLD
WEATHER 20 1
<-- 1660
2 20 MOTORS (BIN, RAKE & AUGER) 6
1553 --> 1553 -->
7 ROOF TOP RECEPT 1 (ROOF HEAT TAPE) 20 1
360 -->
1 20 WATER DISPENSER 8
<-- 100
9 WATER SOFTNER & DELIVERY PUMP (OPTIONAL) 20 1 1 20 RO (OPTIONAL) 101050 -->
<-- 920
11 BLOWER 20 1
<-- 1610
13 14
PHASE LOAD TOTALS
A B
11486 10981
TOTAL CONNECTED LOAD = 22.5 KW TOTAL CONNECTED AMPS= 108 A
ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550
COA: -
These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.
Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.
ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.
TITLE:
MODEL:
APPROVED BY: JOB NO:
DRAWN BY: DRAWING NO:
REVISIONS: SCALE:
DATE:
3/14/24 LML 16' IVK
[PROJECT NUMBER]NTS
E-2B
ELECTRICAL RISER 5200 ARTIC TEMP IM 3 PHASE
Jacksonville, FL 32224 Ice House America-
4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com
TBPE FIRM NO. F-19923
Electrical Room
RM 159
Scrub Room
RM 166
Electrical Panel
DP1
Install 60A 3-pole breaker on CKTs 14,16,18 for the ice maker
Install 125A 2-pole breaker on CKTs 22,24 for the ice machine kiosk
Install surface conduit from RM 159 to the ice machine, following the building exterior.
204.78 197.79 714.05
598.43 427.79
739.27 195.86 707.08 719.80 514.55
54.45 54.20
50.82
Install 60A 3-pole breaker on CKTs 14,16,18 for the ice maker
Install 125A 2-pole breaker on CKTs 22,24 for the ice machine kiosk
3.15 3.15
3.15
6.50 6.50
54.20 451.69
54.45
240.59 442.65 453.77423.49
159.47
50.82
86.68