B25-0392_City_of_Santa_Cruz_Delaveaga_Golf_Course_Roof_Repair_Plans.pdf
PDF 28 MB Posted
- Solicitation number
- IFB No. PR-0286
- Issued by
- Santa Cruz County, San Francisco City, California
About this file
This is a construction document set for the City of Santa Cruz's DeLaveaga Golf Course Driving Range Roof and Building Improvements Project (Project No. c302214), prepared by licensed architect Alan Glen Kroeker and civil/structural engineer MME. The project scope encompasses comprehensive roof repairs and structural improvements to the existing driving range building at 401 Upper Park Road, Santa Cruz, California 95060, including replacement of structural framing with 8"x15" Glu-Lam beams, installation of new STRUC-I rated plywood sheathing, a 2-inch thick cast-in-place fiber-reinforced concrete topping slab, Con Dek waterproofing system, thermoplastic (TPO) roofing, and sheet metal flashing and trim. Site improvements include creation of a van-accessible parking space with ADA-compliant striping and signage, new accessible concrete pedestrian pathways with proper slope and joint detailing per California Building Code specifications, asphalt paving work, and handrail repairs. A mandatory pre-bid conference is scheduled for May 4, 2026, at 10:00 AM at the project site, with sealed bids due May 20, 2026, at 2:00 PM Pacific Standard Time. The successful bidder must be a Class "A" General Engineering Contractor licensed under California law and must complete all work within fifty (50) working days from receipt of the Notice to Proceed, with construction scheduled to commence approximately September 14, 2026.
The construction documents indicate that bid security of not less than ten percent (10%) of the bid amount is required, with the City awarding the contract to the lowest responsible and responsive bidder. Performance and payment bonds equal to one hundred percent (100%) of the contract price must be submitted within ten (10) calendar days of award notification. All work is subject to prevailing wage requirements as determined by the California Department of Industrial Relations, with all contractors and subcontractors required to register with DIR. The project is subject to local hiring requirements under Santa Cruz Municipal Code Chapter 3.10, mandating good faith efforts to hire county residents and apprentices from approved apprenticeship programs. The City will retain five percent (5%) of progress payments until thirty-five (35) calendar days after recording the Notice of Completion, and liquidated damages of three thousand six hundred dollars ($3,600) per calendar day will be assessed for delays beyond the fifty (50) working day completion deadline. All work must comply with California Air Resources Board (CARB) regulations regarding in-use off-road diesel-fueled fleets, with valid Certificates of Reported Compliance required before equipment can operate on site. Bidding documents are available without charge at the City's e-procurement portal at https://www.cityofsantacruz.com/business/bidding-information.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A101
SIM
A101
SIM
A-101
1A
1A
1 CMNT #
DATUM -
CONTROL POINT
DIMENSION
LINE AND TICK
01.23.A
DETAIL VIEW
A101
TYP.
1A
1A
DRAFTING ITEMS
VIEW REFERENCES
PROJECT
NORTH
_____99
A1-100
Name Elevation
BREAK LINE
KEYNOTE
PROJECT LEVEL
MARKER
COLUMN GRID
MARKER
A101
SIM
VIEW REFERENCE
SHEET REFERENCE
SECTION
VIEW
ENLARGED
VIEW
INTERIOR
ELEVATION
EXTERIOR
ELEVATION
VIEW REFERENCE
SHEET REFERENCE
REVISION CLOUD
REVISION TAG
PROJECT
NORTH
ARROW
MATCHLINE - SEE: 1 / A101
SYMBOLS
DELAVEAGA GOLF COURSE
36.996608, -122.000249
PROJECT LOCATION
VICINITY MAP
ABBREVIATIONS
AT
CENTER LINE
PENNY
POUND
PERPENDICULAR
ANGLE
ANCHOR BOLT
ASPHALTIC CONCRETE
ACOUSTICAL CEILING TILE
ABOVE FINISH FLOOR
ALTERNATE
ALUMINUM
ANODIZED
APPROXIMATE
ARCHITECT OR
ARCHITECTURAL
BOARD
BUILDING
BLOCK(ING)
BOTTOM OF BEAM
BEAM
CATCH BASIN
CAST IRON
CONSTRUCTION JOINT
CEILING
CLEAR
CONCRETE MASONRY UNIT
CLEAN OUT
COLUMN
CONCRETE
CONTINUOUS
COUNTERSINK
COLD WATER
CHANNEL
DOUBLE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DOWN
DOWNSPOUT
DRAWING
EAST
EXISTING
EXPANSION BOLT
EXPANSION JOINT
ELEVATION
ELECTRIC(AL)
EDGE OF PAVING
EQUAL
EQUIPMENT
FLOOR DRAIN
FIRE EXTINGUISHER (&
CABINET)
FINISHED FLOOR
FINISHED GRADE
FLAT HEAD OR FIRE
HYDRANT
FINISH
FLOW LINE
FLASHING
FLOOR
FACE OF CONCRETE
FACE OF FINISH
FACE OF MASONRY
FACE OF STUD
FIBERGLASS REINFORCED
PANEL
FOOT OR FEET
FOOTING
GAUGE
GALVANIZED
GRAB BAR, GRADE BREAK
GLASS
GLUE LAMINATED BEAM
GYPSUM
GYPSUM WALL BOARD
HOSE BIBB
HEADER
HEIGHT
HORIZONTAL
HEATER
HEATING/VENTILATING/AIR
CONDITIONING
INSIDE DIAMETER
INSULATION OR INSULATED
INVERT
LAVATORY
MATERIAL
MAXIMUM
MACHINE BOLT
MECHANICAL
MANUFACTURE OR
MANUFACTURER
MAN HOLE
MINIMUM
MISCELLANEOUS
MASONRY OPENING
NORTH
NEW
NOT IN CONTRACT
NUMBER
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OPENING
d 0#
AB
AC
ACT
AFF
ALT
ALUM
ANOD
APPROX
ARCH
BD
BLDG
BLK(G)
BOB
BM
CB
CI
CJ
CLG
CLR
CMU
CO
COL
CONC
CONT
CSK
CW
DBL
DEPT
DET
DF
DIA
DIAG
DN
DS
DWG
E (E)
EB
EJ
ELEV
ELEC
EP
EQ
EQUIP
FD
FE(C)
FF
FG
FH
FIN
FL
FLG
FLR
FOC
FOF
FOM
FOS
FRP
FT
FTG
GA
GALV
GB
GL
GLB
GYP
GWB
HB
HDR
HGT
HORIZ
HTR
HVAC
ID
INSUL
INV
LAV
MATL
MAX
MB
MECH
MFR
MH
MIN
MISC
MO
N (N)
NIC
NO OR #
NTS
OC
OD
OPNG
CL
PLATE OR PROPERTY LINE
PLASTIC LAMINATE
PLASTER (NUMBER - SEE SPECS)
PLYWOOD
PAINT (NUMBER - SEE SPECS)
PRESSURE TREATED DOUGLAS
FUR
QUARRY TILE
ROOF DRAIN
REFRIGERATOR
REINFORCE OR REINFORCING
ROUND HEAD
ROOM
ROUGH OPENING
REDWOOD
SOUTH
SCHEDULE
STORM DRAIN
SHOWER
SHEET
SHEATHING
SIMILAR
THE ARCH SHEET METAL MANUAL
SPECIFICATION
SQUARE
STAINLESS STEEL
STANDARD
STEEL
SUSPENDED
SYMMETRICAL
TOP OF BEAM
TOP OF CURB OR TOP OF
CONCRETE
TOP OF CATCH BASIN
TELEPHONE
TEMPERATURE OR TEMPERED
TONGUE & GROOVE
TOP OF PAVING
STRUCTURAL TUBING
TELEVISION
TOP OF WALL
TYPICAL (ITEMS TYPICAL UNLESS
SHOWN OR NOTED OTHERWISE)
UNLESS OTHERWISE NOTED
VINYL COMPOSITION TILE
VERTICAL
VERTICAL GRAIN DOUGLAS FIR
VENT THRU ROOF
WEST
WATER CLOSET
WHEELCHAIR ACCESSIBLE
WOOD
WIDE FLANGE
WATER HEATER
WATERPROOF
WOOD SCREW
WAINSCOT
WELDED WIRE FABRIC
WITH
WITHOUT
PL
PLAM
PLAS
PLYWD
PNT
PTDF
QT
RD
REF
REINF
RH
RM
RO
RWD
S
SCH
SD
SHR
SHT
SHTHG
SIM
SMACNA
SPEC
SQ
SSTL
STD
STL
SUSP
SYM
TOB
TOC
TCB
TEL
TEMP
T&G
TP
TS
TV
TOW
TYP
UON
VCT
VERT
VGDF
VTR
W
WC
W.C.
WD
WF
WH
WP
WS
WSCT
WWF
W/ W/O
DEFERRED SUBMITTALS
NONE
PROJECT DESCRIPTION
THE PROPOSED PROJECT CONSISTS OF IMPROVEMENTS TO THE EXISTING
DRIVING RANGE BUILDING AT DELAVEAGA GOLF COURSE. THE SCOPE INCLUDES
ROOF REPAIRS, INCLUDING STRUCTURAL FRAMING (GLU-LAM BEAMS).
ADDITIONAL SITE IMPROVEMENTS INCLUDE A VAN-ACCESSIBLE PARKING SPACE
AND AN ACCESSIBLE PEDESTRIAN ROUTE TO THE EXISTING STAIR AND RAMPS, IN
COMPLIANCE WITH THE CURRENT CALIFORNIA BUILDING CODE.
7. ALL REQUIRED EXITS SHALL BE OPERABLE FROM THE INSIDE AT ANY TIME BY
TURNING OF THE LEVER OR DEPRESSING BAR OF PANIC EXIT DEVICE,
WITHOUT THE USE OF A KEY OR ANY SPECIAL EFFORT OR KNOWLEDGE.
8. ILLUMINATED EXIT SIGNS SHALL BE INSTALLED WHERE INDICATED AND OTHER
REQUIRED EXIT DOORWAYS IN ACCORDANCE WITH CALIFORNIA BUILDING CODE
WHERE NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS WHEN
TWO OR MORE EXITS ARE REQUIRED AND AT ROOMS SERVING AN OCCUPANT
LOAD OF MORE THAN 49.
9. DOOR OPENING SIZES INDICATED ON DOOR SCHEDULE ARE OPENING
DIMENSIONS. ALLOWANCES FOR THRESHOLDS, FLOOR FINISHES, ETC. SHALL
BE TAKEN OFF DOOR.
10. THE PRECISE DIMENSIONS AND LOCATIONS OF ALL DOORS, LOUVERS AND
WINDOW OPENINGS SHALL BE DETERMINED BY ARCHITECTURAL PLANS AND
DETAILS. OTHER WALL AND FLOOR OPENINGS AS REQUIRED BY MECHANICAL OR
ELECTRICAL SHALL BE VERIFIED FROM SHOP DRAWINGS, EQUIPMENT DATA,
ETC. AS REQUIRED, AND IF NOT CLEAR AN RFI SHALL BE ISSUED TO THE
ARCHITECT FOR CLARIFICATION.
11. DOOR OPENINGS NOT LOCATED BY DIMENSIONS SHALL BE LOCATED 6 INCHES
FROM FINISH WALL TO FINISH JAMB UNLESS OTHERWISE NOTED. IF DOOR
CLEARANCE REQUIREMENTS AT PULL SIDE AND PUSH SIDE OF STRIKE ARE NOT
ACHIEVABLE, THEN CONTRACTOR SHALL ISSUE A FIR FOR CLARIFICATION
PRIOR TO PROCEEDING.
12. THERE SHALL BE A LEVEL FLOOR OR LEVEL LANDING ON EACH SIDE OF THE
DOOR REGARDLESS OF THE OCCUPANT LOAD.
13. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR DIMENSIONS
LOCATING LIGHT FIXTURES, DIFFUSERS AND WALL MOUNTED FIXTURES.
REFER TO ELECTRICAL DRAWINGS FOR ALL LIGHTING FIXTURE TYPES,
WIRING, ETC.
14. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNTING HEIGHTS.
WALL FIXTURES OR ITEMS THAT PROTRUDE BEYOND 4 INCHES OF WALL
SURFACE SHALL BE LOCATED WITH BOTTOM OF FIXTURE/ITEMS 80 INCHES
CLEAR OF FINISH FLOOR.
15. CEILING SUSPENSION SYSTEM SHALL PROVIDE FOR CEILING SYSTEM ONLY.
ADDITIONAL INDEPENDENT FRAMING FOR LIGHTING FIXTURES, EXIT SIGNS,
GRILLES AND AIR CONDITIONING DIFFUSERS SHALL BE REQUIRED.
16. PROVIDE ADEQUATE ANCHORAGE, BLOCKING, BACKING AND FRAMING FOR FIRE
SPRINKLERS, PIPING, LIGHTING FIXTURES, ELECTRICAL UNITS, HVAC
EQUIPMENT AND CEILING TRACKS AS REQUIRED FOR A COMPLETE
INSTALLATION.
17. GYPSUM BOARD ON METAL STUDS SHALL BE 5/8" THICK, TYPE 'X' UNLESS NOTED
OTHERWISE AND IN COMPLIANCE WITH PLAN DOCUMENTS "WALL TYPES"
REQUIREMENTS AND SPECIFICATIONS.
FIRE PROTECTION NOTES
1. THE BUILDING SHALL BE PROVIDED WITH AN AUTOMATIC FIRE EXTINGUISHING
SYSTEM THROUGHOUT, SYSTEM TYPES SHALL BE WET PIPE AND DRY PIPE FIRE
SPRINKLER SYSTEMS. SYSTEMS SHALL CONFORM TO THE CALIFORNIA BUILDING
CODE (CBC), CALIFORNIA FIRE CODE (CFC), NFPA, UL AND CALIFORNIA STATE
FIRE MARSHALL (CSFM).
2. ALL AUTOMATIC FIRE SPRINKLER SYSTEM WORK AND THE FIRE ALARM SYSTEM
WORK ARE TO BE ENGINEERED, FURNISHED AND INSTALLED BY A LICENSE FIRE
SPRINKLER CONTRACTOR.
3. FIRE SPRINKLER CONTRACTOR AND FIRE ALARM CONTRACTOR SHALL SUBMIT
FIRE SPRINKLER AND FIRE ALARM DRAWINGS AND CALCULATIONS TO THE CSFM
FOR APPROVAL AND PERMIT PRIOR TO COMMENCING THE WORK.
4. PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED IN OCCUPANCIES AND
LOCATIONS AS INDICATED ON DRAWINGS, AS HEREIN INDICATED AND SET FORTH
IN THE CODE AND AS REQUIRED BY THE FIRE DEPARTMENT. THE MAXIMUM
TRAVEL DISTANCE TO THE FIRE EXTINGUISHER SHALL NOT EXCEED 75 FEET
ALONG AN UNOBSTRUCTED PATH OF TRAVEL, CFC TABLE 906.3(1). ALL PORTABLE
FIRE EXTINGUISHERS SHALL HAVE A SERVICE TAG AFFIXED TO THEM SHOWING
THAT THE EXTINGUISHER HAS BEEN SERVICED BY A CALIFORNIA STATE
LICENSED FIRE EXTINGUISHER CONCERN. ALL FIRE EXTINGUISHERS SHALL BE
ATTACHED TO A BRACKET OR WITHIN AN APPROVED CABINET, REFER TO
DRAWINGS AND SPECIFICATIONS. MAXIMUM DISTANCE FROM THE FLOOR SHALL
NOT EXCEED THE REQUIREMENTS OF CFC SECTION 906.9 AND ADA.
A. REFER TO DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION,
LOCATION, TYPES, ETC.
GENERAL NOTES - COMMERCIAL
BUILDING SECURITY STANDARDS
1. ALL WORK SHALL COMPLY WITH THE FOLLOWING BUILDING SECURITY STANDARDS:
A. GENERAL NOTES
a. SECURITY AND LOCKING DEVICES SHALL NOTE CREATE HAZARDS TO LIFE BY
OBSTRUCTING:
• EXITWAYS OR MEANS OF EGRESS
• EXIT DOORS EQUIPPED WITH PANIC HARDWARE.
2. ASSEMBLIES AND SECURITY HARDWARE INSTALLED SHALL BE LABELED AND
CERTIFIED AS MEETING UL (UNDERWRITERS LABORATORY) STANDARDS, OR OTHER
APPROVED PERFORMANCE TESTING CRITERIA AS APPROVED BY AGENCY HAVING
JURISDICTION.
3. REQUIRED AREA LIGHTING AND ADDRESS IDENTIFICATION SHALL BE INSTALLED
BEFORE FINAL INSPECTION IS CALLED FOR.
4. ILLUMINATION PER CODE REQUIREMENTS SHALL BE PROVIDED ADJACENT TO ALL
EXTERIOR DOORS DURING ALL HOURS OF DARKNESS TO PROVIDE MINIMUM
REQUIRED FOOT CANDLE LEVEL AT PAVING.
5. WINDOW PROVISIONS:
A. GLAZING IN EXTERIOR DOORS OR WITHIN A 23 INCH ARC OF EITHER VERTICAL
EDGE OF DOOR IN THE CLOSED POSITION SHALL BE TEMPERED SAFETY
GLAZING.
B. GLAZING AND GLAZED ASSEMBLIES FOR ACCESSIBLE OPENING SHALL BE
CERTIFIED AS MEETING TEST PROVISIONS OF UL (UNDERWRITERS
LABORATORY).
C. ALL GLAZING INSTALLED IN A HAZARDOUS LOCATION SHALL BE TEMPERED
SAFETY GLASS.
D. GLAZING AND INSTALLATION SHALL BE IN COMPLIANCE WITH THE CALIFORNIA
BUILDING CODE INCLUDING CHAPTER 24.
E. GLAZING SHALL BE TEMPERED SAFETY GLAZING WHERE INDICATED.
CONTRACTOR RESPONSIBILITIES
1. THE CONTRACTOR SHALL EXAMINE EXISTING CONDITIONS, THE DRAWINGS AND
SPECIFICATIONS AND SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIES
FOUND PRIOR TO PROCEEDING WITH THE WORK IN UNCERTAINTY.
2. THE CONTRACTOR SHALL VERIFY CONDITIONS AT THE SITE AND REPORT ANY
DISCREPANCIES TO THE ARCHITECT BEFORE PROCEEDING WITH THE WORK IN
UNCERTAINTY.
3. THE CONTRACTOR SHALL NOTIFY UNDERGROUND SERVICE ALERT PRIOR TO ANY
EXCAVATING.
4. THE CONTRACTOR SHALL COORDINATE THE REMOVAL, ABANDONMENT AND/OR
LOCATIONS OF EXISTING UTILITIES ABOVE OR BELOW GRADE WITH THE RESPECTIVE
UTILITY COMPANIES.
5. THE CONTRACTOR SHALL PERFORM ALL WORK WITHIN STREET RIGHT-OF-WAYS
ACCORDING TO APPROVED STANDARD PLANS AND SPECIFICATIONS OF THE
AGENCY HAVING JURISDICTION.
6. THE CONTRACTOR PROVIDE TEMPORARY BRACES, SHORES, AND GUYS REQUIRED
TO SUPPORT ALL LOADS TO WHICH THE BUILDING STRUCTURES AND COMPONENTS,
ADJACENT STRUCTURES, UTILITIES AND RIGHT-OF-WAYS MAY BE SUBJECT DURING
CONSTRUCTIONS.
7. FLOOR AND WALL OPENINGS, SLEEVES, VARIATIONS IN THE STRUCTURAL SLAB
ELEVATIONS, DEPRESSED AREAS AND ALL OTHER ARCHITECTURAL , STRUCTURAL,
MECHANICAL, ELECTRICAL, AND/OR CIVIL REQUIREMENTS MUST BE COORDINATED
BEFORE THE CONTRACTOR PROCEEDS WITH THE WORK.
8. THE CONTRACTOR SHALL INSPECT AND APPROVE ALL EXISTING WORK AS
COMPLETE AND READY TO PROCEED WITH WORK UNDER THIS CONTRACT AND IN
COMPLIANCE WITH DRAWINGS, SPECIFICATIONS AND DIVISION 1 REQUIREMENTS
PRIOR TO COMMENCING.
TYPICAL NOTES
1. SIMILAR - MEANS COMPARABLE CHARACTERISTICS FOR THE CONDITIONS NOTES.
VERIFY DIMENSIONS AND/OR ORIENTATIONS ON PLANS AND/OR ELEVATIONS.
2. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT APPROVAL OF ARCHITECT IN
WRITING.
3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY THE ARCHITECT
OF ANY CONFLICTS HEREIN, EITHER UNAPPARENT OR OBLIVIOUS, PRIOR TO START
OF WORK ON THAT ITEM OR BEAR THE RESPONSIBILITY OF CORRECTING SUCH
WORK AS DIRECTED BY THE ARCHITECT AND AT NO ADDITIONAL COST AND NO TIME
EXTENSION OF THE PROJECT.
4. UNDERCUT ALL DOORS TO CLEAR TOP OF FLOOR FINISH AND/OR THRESHOLD .25
INCHES MAXIMUM. COORDINATE WITH AUTOMATIC DOOR BOTTOMS.
5. PREPARE DOORS FOR HARDWARE SPECIFIED. TEST AND ADJUST DOORS FOR
SMOOTH, QUIET OPERATION BEFORE FINAL OBSERVATIONS TO CONFIRM MAXIMUM
PRESSURE TO OPEN DOOR IS NOT EXCEEDED.
6. USE WATER RESISTANT / GLASS FIBER FACED GYPSUM WALLBOARD ON ALL WALL
FACES WHICH ARE EXPOSED TO WATER OR MOISTURE AS WELL AS THOSE USED
FOR JANITOR AND TOILET WALLS, COORDINATE AND COMPLY WITH
SPECIFICATIONS, SECTION 09250.
7. ALL EXTERIOR WALLS SHALL BE INSULATED AND IN COMPLIANCE WITH
SPECIFICATIONS AND PLAN DOCUMENTS AND SHALL NOT FALL BELOW MINIMUM
TITLE 24 REQUIREMENTS WHERE NOT INDICATED, COORDINATE WITH WALL
SCHEDULE.
8. PROVIDE ADEQUATE BLOCKING AND ANCHORAGE FOR CEILING AND WALL
MOUNTED EQUIPMENT - I.E. FIRE EXTINGUISHER CABINETS, HANDRAILS AND
GUARDRAILS, ETC.
9. ALL CEILING CONSTRUCTIONS SHALL COMPLY WITH CBC CHAPTER 25 (MAXIMUM 12"
JOIST SPACING AT CEILINGS) AND AS INDICATED IN DRAWINGS.
10. ALL CEILING CONSTRUCTION SHALL COMPLY WITH CBC CHAPTER 25 (MAXIMUM 12"
JOIST SPACING AT CEILINGS) AND AS INDICATED IN DRAWINGS.
MECHANICAL AND PLUMBING
1. MECHANICAL AND PLUMBING SHALL COMPLY WITH THE CURRENT ADOPTED EDITION
ON THE CALIFORNIA MECHANICAL AND PLUMBING CODES AT TIME OF PERMIT
ISSUANCE.
2. TOILET ROOMS SHALL BE QUIPPED WITH A VENTILATION SYSTEM, REFER TO
MECHANICAL DRAWINGS.
3. ACCESS PANELS SHALL BE PROVIDED WHERE REQUIRED FOR ACCESS TO ALL
DUCTWORK, FIRE DAMPERS, ETC.; REFER ALSO TO SPECIFICATIONS. COORDINATE
LOCATIONS WITH ARCHITECT PRIOR TO INSTALLATION.
4. LOCATION OF ALL MECHANICAL ROOF OPENINGS SHALL BE DETERMINED AND
VERIFIED BY THE MECHANICAL AND GENERAL CONTRACTOR.
5. ELECTROLYSIS PROTECTION SHALL BE PROVIDED BETWEEN ALL DISSIMILAR
METALS WHEREVER THE TWO ARE IN CONTACT.
COMPLIANCE WITH PLAN DOCUMENTS
1. DIMENSIONS:
A. DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.
B. ALL DIMENSIONS TO OPENINGS ARE TO THE ROUGH OPENING UNLESS NOTED
OTHERWISE.
C. ALL DIMENSIONS TO STUD PARTITIONS ARE TO THE FACE OF FRAMING UNLESS
NOTED OTHERWISE.
D. CEILING HEIGHT DIMENSIONS ARE FROM FINISH FLOOR TO FINISH FACE OF
CEILING.
E. ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD BEFORE PROCEEDING WITH
THE WORK.
F. ACCESSIBILITY DIMENSIONS SHALL BE MEASURED TO FACE OF WALL FINISH.
CLEAR OPENING AND AS INDICATED ON ENLARGED PLAN, MOUNTING HEIGHTS
SHEET, TOILET ROOM ELEVATIONS AND STANDARD DETAIL DRAWING SHEETS.
G. DIMENSIONING PROTOCOLS / HIERARCHY:
a. "ENLARGED PLAN" INCLUDES ALL DIMENSIONING ASSOCIATED WITH THE
GRAPHICS SHOWN.
b. OVERALL PLANS SHOW DIMENSIONS NOT INDICATED ON THE "PARTIAL
DIMENSIONING PLANS."
2. WHERE NO SPECIFIC DETAIL IS SHOWN, THE FRAMING OR CONSTRUCTION SHALL BE
IDENTICAL OR SIMILAR TO THAT INDICATED FOR LIKE CASES OR
CONSTRUCTIONS ON THE PROJECT AND IF NOT CLEAR A REQUEST FOR
INFORMATION (RFI) SHALL BE ISSUED TO THE ARCHITECT FOR CLARIFICATION.
3. CONCRETE CONSTRUCTION SHALL COMPLY WITH THE CALIFORNIA BUILDING CODE
INCLUDING BUT NOT LIMITED TO CHAPTERS 16, 17, 18 AND 19 AND
SPECIFICATIONS.
4. STEEL CONSTRUCTION SHALL COMPLY WITH THE CALIFORNIA BUILDING CODE
INCLUDING BUT NOT LIMITED TO CHAPTERS 16, 17 AND 22 AND SPECIFICATIONS.
5. ALL INTERIOR FINISH MATERIALS SHALL HAVE A FLAME SPREAD CLASSIFICATION
RATING PER CALIFORNIA BUILDING CODE INCLUDING BUT NOT LIMITED TO
CHAPTER 8.
6. ROOF COVERING AND ROOFING MATERIALS SHALL BE FIRE RETARDANT AND SHALL
COMPLY WITH THE UNDERWRITERS LABORATORIES, INC. AND CLASSIFIED AS
CLASS B U.L. FIRE HAZARD, MINIMUM UNLESS NOTED OTHERWISE ON DRAWINGS OR
IN SPECIFICATIONS AND SHALL COMPLY WITH THE CALIFORNIA BUILDING CODE
INCLUDING CHAPTER 15.
SHEET # SHEET NAME REV # DATE
1. OVERALL GENERAL INFORMATION
G-001 TITLE SHEET 1 03/10/2026
G-101 CODE SITE PLAN
GENERAL SHEETS TOTAL: 2
2. CIVIL ENGINEERING
C1 PLAN
C2 DETAILS
C3 CIVIL SPECIFICATIONS
CIVIL SHEETS TOTAL: 3
4. ARCHITECTURAL DRAWINGS
A-102 ENLARGED SITE PLAN
A-111 SITE DETAILS
A-221 ROOF PLANS 1 03/10/2026
A-711 ROOF DETAILS
ARCHITECTURAL SHEETS TOTAL: 4
5. STRUCTURAL ENGINEERING
S1 STRUCTURAL NOTES AND SPECIFICATIONS
S2 ROOF FRAMING PLAN STAIR REPAIR PLAN
S3 STRUCTURAL DETAILS
STRUCTURAL SHEETS TOTAL: 3
OVERALL SHEET TOTAL: 12
SHEET # SHEET NAME REV # DATE
SHEET INDEX
L
IC
E
NSED ARCH
TI E
C
T
ET
A T
S
O F CALIF
OR
N
IA
A L A
N
GLEN KROE
K E
R
SHEET ISSUE DATE:
JOB NUMBER:
SHEET TITLE
DRAWN BY:
THE ARCHITECT DOES NOT REPRESENT THAT THESE
PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY
SITE OTHER THAN THE ONE FOR WHICH THEY WERE
SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS
RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS
IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER
SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL
HAVE PRECEDENCE OVER SCALED DIMENSIONS.
ARCHITECT STAMP
REVISIONS
PROJECT OWNER & TITLE
SHEET NO.
D A
T E
P L O
T T
E D
F
IL
E
L O
C A
T
IO
N
REN. 10-31-25
C-22474
CONSULTANT STAMP
303 POTRERO STREET, SUITE 5
SANTA CRUZ, CA 95060
TEL (831) 440-7300
AGENCY APPROVAL:
5 4 3 2 1
A
B
C
D
E
A
B
C
D
E
6 5 4 3 2 1
ORIGINAL ISSUE DATE:
CONSULTANTS
/1
/2
:1 :4
A
M A u to d e s k D o c s /2
.0
C it y o f S
C D e la v e a g a
G o lf C o u rs e R o o f R e p a ir /2
.0
C it y o f S a n ta
C ru z D e la v e a g a
G o lf C o u rs e
R o o f R e p a ir A k n a ru p .r v t
G-001
TITLE SHEET
11/14/2025
25034.01KAN
C O
N S T R
U C
T
IO
N D
O C
U M
E N
T S
DELAVEAGA GOLF COURSE - ROOF
REPAIR
401 Upper Park Road
Santa Cruz, CA. 95060
CITY OF SANTA CRUZ
B25-0392BLDG#
September 9,2025
CITY OF SANTA CRUZ
DELAVEAGA GOLF COURSE - ROOF REPAIR
B25-0392
C I V I L / S T R U C T U R A L E N G I N E E R
MME
224 Walnut Ave, Suite B, Santa Cruz, cA. 95060
TEL (831) 426-3186
email@email.com
APPLICABLE CODES AND STANDARDS
PARTIAL LIST OF APPLICABLE CODES:
ALL PARTS OF THE TITLE 24 CODE SHOWN BELOW HAVE AN EFFECTIVE
DATE OF
EXCEPT:
• CALIFORNIA ADMINISTRATIVE CODE - EFFECTIVE
CALIFORNIA CODE OF REGULATIONS, TITLE 24
CALIFORNIA ADMINISTRATIVE CODE [CAC] (CCR, TITLE 24, PART 1)
CALIFORNIA BUILDING CODE [CBC] (CCR, TITLE 24, PART 2)
(INTERNATIONAL BUILDING CODE, VOL. 1 & 2, WITH AMENDMENTS)
CALIFORNIA ELECTRICAL CODE [CEC] (CCR, TITLE 24, PART 3)
(NATIONAL ELECTRICAL CODE WITH AMENDMENTS)
CALIFORNIA MECHANICAL CODE [CMC] (CCR, TITLE 24, PART 4)
(IAPMO UNIFORM MECHANICAL CODE WITH AMENDMENTS)
CALIFORNIA PLUMBING CODE [CPC] (CCR, TITLE 24, PART 5)
(IAPMO UNIFORM MECHANICAL CODE WITH AMENDMENTS)
CALIFORNIA ENERGY CODE [CEC] (CCR, TITLE 24, PART 6)
CALIFORNIA FIRE CODE [CFC] (CCR, TITLE 24, PART 9)
(INTERNATIONAL FIRE CODE WITH AMENDMENTS)
CALIFORNIA GREEN BUILDING STANDARDS CODE
[CALGREEN] (CCR, TITLE 24, PART 11)
CALIFORNIA REFERENCED STANDARDS CODE (CCR, TITLE 24, PART 12)
JAN. 1, 2023
MAR. 5, 2022
APPLICABLE NFPA STANDARDS, AS AMMENDED BY CHAPTER 35 OF THE CBC.
1. NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
2. NFPA 14 - STANDPIPE AND HOSE SYSTEMS
3. NFPA 24 - STANDARD FOR THE INSTALLATION OF PRIVATE SERVICE MAINS AND THEIR
APPURTENANCES (AS AMMENDED)
4. NFPA 25 - INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE PROTECTIONS
SYSTEMS
5. NFPA 30 - FLAMMABLE AND COMBUSTIBLE LIQUID CODE
6. NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE
7. NFPA 110 - EMERGENCY AND STANDBY POWER SYSTEMS
8. NFPA 10-21 - STANDARD FOR PORTABLE FIRE EXTINGUISHERS
9. NFPA 12-15 - STANDARD ON CARBON DIOXIDE EXTINGUISHING SYSTEMS
10. NFPA 12A-18 - STANDARD ON HALON 1301 FIRE EXTINGUISHING SYSTEMS
11. NFPA 17-21 - STANDARD FOR DRY CHEMICAL EXTINGUISHING SYSTEMS
12. NFPA 17A-21 - STANDARD FOR WET CHEMICAL EXTINGUISHING SYSTEMS
13. NFPA 20-19 - STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE
PROTECTION
14. NFPA 80-19 - STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES
APPLICABLE UL / ICC STANDARDS
1. UL 300-2005(R2010) - STANDARD FOR FIRE TESTING OF FIRE EXTINGUISHING SYSTEMS FOR
PROTECTION OF COMMERCIAL COOKING EQUIPMENT
2. UL 464-03 - AUDIBLE SIGNALING DEVICES FOR FIRE ALARM AND SIGNALING SYSTEMS,
INCLUDING ACCESSORIES
3. UL 521-99 - STANDARD FOR HEAT DETECTORS FOR FIRE PROTECTIVE SIGNALING SYSTEMS
4. UL 1971-2002(R2010) - STANDARD FOR SIGNALING DEVICES FOR THE HEARING IMPAIRED
5. ICC 300-17 - STANDARD FOR BLEACHERS, FOLDING AND TELESCOPIC SEATING, AND
GRANDSTANDS
ADDITIONAL APPLICABLE STANDARDS
1. 2010 AMERICANS WITH DISABILITIES ACT - STANDARDS FOR ACCESSIBLE DESIGN
2. ASME A17.1/CSA B44-13 SAFETY CODE FOR ELEVATORS AND ESCALATORS PER 2022 CBC
PART 2 CH 35) - CAL/OSHA ELEVATOR UNIT ENFORCES CCR TITLE 8 AND USES THE 2004
ASME A17.1 BY ADOPTION
3. OFFICE OF THE STATE FIRE MARSHAL REGULATIONS - CALIFORNIA CODE OF REGULATIONS, TITLE 19
4. CALIFORNIA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION - CAL-OSHA
5. OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION - OSHA
NO. DATE DESCRIPTION
1 03/10/2026 ADDENDUM 01
(N) CONCRETE PAVING
(N) ASPHALT CONCRETE PAVING
(E) BUILDING
ASSUMED PROPERTY LINE
PROJECT BUILDING
LIMITS OF WORK
PATH OF TRAVEL (P.O.T.)
AS INDICATED, IS A COMMON BARRIER FREE
ACCESS ROUTE
IS AT LEAST 48" WIDE.
NO ABRUPT VERTICAL CHANGES EXCEEDING 1/2"
BEVELED AT 1:2 MAXIMUM SLOPE, EXCEPT THAT
LEVEL CHANGES DO NOT EXCEED 1/4" VERTICAL.
THE PATH SURFACE IS SLIP RESISTANT, STABLE,
FIRM, AND SMOOTH.
PASSING SPACES (11B-403.2) AT LEAST 60"x60" ARE
LOCATED NOT MORE THAN 200' APART.
PARTS OF P.O.T. WITH CONTINUOUS GRADIENTS
HAVE 60" LEVEL AREAS (11B-403.7) NOT MORE
THAN 400' APART.
THE CROSS-SLOPE DOES NOT EXCEED 2% AND
SLOPE IN THE DIRECTION OF TRAVEL IS LESS THAN
5% UNLESS OTHERWISE INDICATED.
(POT) SHALL BE MAINTAINED FREE OF
OVERHANGING OBSTRUCTIONS TO 80" MINIMUM
(11B-307.4) AND PROTRUDING OBJECTS GREATER
THAN 4" PROJECTION FROM WALL AND ABOVE 27"
AND LESS THAN 80" (11B-307).
ARCHITECT SHALL VERIFY PATH OF TRAVEL
CONFORMS WITH THE ABOVE.
EXPANSION JOINT PER
CONTROL JOINT PER
A-111
A-221
A-111
LEGEND - SITE PLAN
A-221
C2
EXISTING GENDER NEUTRAL RESTROOMGN
EXISTING DRINKING FOUNTAINDF
CODE SITE GENERAL NOTES
1.
2.
3.
4.
5.
ALL NEW CONCRETE AND AC PAVING IN P.O.T. SHALL HAVE 2% MAX. SLOPE IN
ALL DIRECTIONS U.N.O. AND SHALL HAVE FLUSH TRANSITIONS TO ALL
ADJACENT NEW AND EXISTING WALK SURFACES IN P.O.T .
ALL LANDSCAPE EDGES ALONG ALL NEW OR EXISTING WALK SURFACES IN
P.O.T. SHALL BE PER CIVIL DRAWINGS.
FOR GRATINGS OR STRAINERS LOCATED IN THE SURFACE OF ANY
PEDESTRIAN WAY OR IN P.O.T., THE MAXIMUM GRATE OR STRAINER OPENINGS
SHALL NOT EXCEED 1/2" IN THE DIRECTION OF TRAFFIC FLOW.
THE P.O.T. IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS IS COMPLIANT
WITH THE CURRENT APPLICABLE CALIFORNIA BUILDING CODE ACCESSIBILITY
PROVISIONS FOR THE PATH OF TRAVEL REQUIREMENTS FOR ALTERATIONS,
ADDITIONS, AND STRUCTURAL REPAIRS. AS PART OF THE DESIGN OF THIS
PROJECT, THE P.O.T. WAS EXAMINED AND ANY ELEMENTS, COMPONENTS OR
PORTIONS OF THE P.O.T. THAT WERE DETERMINED TO BE NON-COMPLIANT 1)
HAVE BEEN IDENTIFIED AND 2) THE CORRECTIVE WORK NECESSARY TO BRING
THEM INTO COMPLIANCE HAS BEEN INCLUDED WITHIN THE SCOPE OF THIS
PROJECT'S WORK THROUGH DETAILS, DRAWINGS AND SPECIFICATIONS
INCORPORATED INTO THESE CONSTRUCTION DOCUMENTS. ANY NON-
COMPLIANT ELEMENTS, COMPONENTS, OR PORTIONS OF THE P.O.T. THAT WILL
NOT BE CORRECTED BY THIS PROJECT BASED ON VALUATION THRESHOLD
LIMITATIONS OR A FINDING OF UNREASONABLE HARDSHIP ARE SO INDICATED
IN THESE CONSTRUCTION DOCUMENTS. DURING CONSTRUCTION, IF POT
ITEMS WITHIN THE SCOPE OF THE PROJECT REPRESENTED AS CODE
COMPLIANT ARE FOUND TO BE NON-CONFORMING BEYOND REASONABLE
CONSTRUCTION TOLERANCES, THEY SHALL BE BROUGHT INTO COMPLIANCE
WITH THE CBC AS PART OF THIS PROJECT BY MEANS OF A CONSTRUCTION
CHANGE DOCUMENT.
THIS PROJECT DOES NOT PROPOSE THE REMOVAL OF A HERITAGE-SIZED
TREE OR GROUND DISTURBANCE WITHIN 10'-0" OF A HERITAGE-SIZED TREE.
EXISTING CLUBHOUSE
EXISTING DRIVING RANGE &
GOLF CART PARKING & MAINTENANCE
BUILDING
GN
01.41.A
(E) AC
PAVING
(E) AC
PAVING
(E) AC
PAVING
(E) LANDSCAPE
(E)
CONC.
(E) STAFF & VISITOR
PARKING
A-021
A-102
01.41.D
UPPER PARK ROAD
DF
10.19.A
A-111
03.00.A
KEYNOTES
01.41.A (E) ACCESSIBLE GENDER NEUTRAL RESTROOM. SEE CITY OF SANTA CRUZ
PERMIT # B16-0520 DETAILS 3&6/A2.1
01.41.D NEW SITE ARRIVAL POINT PER CBC 11B-206.2.1
03.00.A (E) CONCRETE PLATFORM AT BASE OF STAIRS TO REMAIN.
10.19.A UNAUTHORIZED VEHICLES PARKED IN DESIGNATED ACCESSIBLE SPACES NOT
DISPLAYING DISTINGUISHING LICENSE PLATES OR PLACARDS ISSUED FOR
PERSONS WITH DISABILITIES MAY BE TOWED AWAY AT THE OWNER ’S EXPENSE.
40'20'10'0
1" = 20'
PROJECT
NORTH
LI
CENSED ARCH TI ECT
ETATS
O F CALIFORNIA
AL
AN
GLEN KROEKER
SHEET ISSUE DATE:
JOB NUMBER:
SHEET TITLE
DRAWN BY:
THE ARCHITECT DOES NOT REPRESENT THAT THESE
PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY
SITE OTHER THAN THE ONE FOR WHICH THEY WERE
SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS
RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS
IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER
SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL
HAVE PRECEDENCE OVER SCALED DIMENSIONS.
ARCHITECT STAMP
REVISIONS
PROJECT OWNER & TITLE
SHEET NO.
D
AT
E
PL
O
TT
ED
FI
LE
L O
C
AT
IO
N
REN. 10-31-27
C-22474
CONSULTANT STAMP
303 POTRERO STREET, SUITE 5
SANTA CRUZ, CA 95060
TEL (831) 440-7300
AGENCY APPROVAL:
5 4 3 2 1
A
B
C
D
E
A
B
C
D
E
6 5 4 3 2 1
ORIGINAL ISSUE DATE:
CONSULTANTS
/1
4/
:2 3:
P
M Au to de sk D oc s:
//2
.0
C ity o f S C
D el av ea ga G ol f C ou rs e R oo f R ep ai r/2
.0
1_ C ity o f S an ta C ru z_
D el av ea ga G ol f C ou rs e_ R oo f R ep ai r_ A2
4_ kn ar up
.rv t
G-101
CODE SITE PLAN
11/14/25
25034.01KAN
CO
N
ST
RU
CT
IO
N D
O
CU
M
EN
TS
DELAVEAGA GOLF COURSE - ROOF
REPAIR
401 Upper Park Road Santa Cruz, CA. 95060
CITY OF SANTA CRUZ
B25-0392BLDG#
September 9,2025
C I V I L / S T R U C T U R A L E N G I N E E R
MME
224 Walnut Ave, Suite B, Santa Cruz, cA. 95060
TEL (831) 426-3186
email@email.com
QA/QC - 04 - CODE ANALYSIS - SITE PLAN
TASK REVIEWED CHECKED BY REVIEWED (PM) CHECKED BY
01 SCHEMATIC DESIGN
PROJECT LIMITS OF WORK / EXTENTS AND PROPERTY LINES ARE SHOWN CLEARLY AND ACCURATELY, WITH RELEVANT EASEMENTS AND SET BACKS
IDENTIFIED
No XX No XX
FIRE LANES AND EMERGENCY ACCESS ROUTES ARE CLEARLY IDENTIFIED AND GRAPHICALLY SHOWN. No JM No XX PATH OF TRAVEL (P.O.T.) IS CLEARLY DRAWN AND IDENTIFIED (SEE SITE PLAN LEGEND) No JM No XX PROJECT BUILDING IS SHOWN GRAPHICALLY, AND CORRECTLY IDENTIFIES: BLDG NUM., NAMES, BUILDING AREA IN SF, AND OCCUPANCY No JM No XX INDICATE ACCESSIBLE PATH OF TRAVEL TO ENTRY AND RESTROOMS FROM ADA PARKING No JM No XX VERIFY THE CORRECT NUMBER OF ACCESSIBLE STALLS REQUIRED ARE INCLUDED. No XX No XX THE SCALE OF LEGEND GRAPHIC MATCHES THE PLAN SCALE No JM No XX DRAWING VIEW TITLE, NORTH ARROW, AND GRAPHIC SCALE ARE SHOWN ON PLAN No JM No XX
DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE STATEMENT PER SECTION 2 OF
DSA PR 15-01 IS LISTED AND UP TO DATE.
No XX No XX
FIRE FLOW REPORT FOR ALL FIRE HYDRANTS NEEDED FOR CODE COMPLIANCE IS COORDINATED W/ CONSULTANT TEAM(S) AND CSFM / LOCAL
FIRENS
No XX No XX
FIRE FLOW REPORT IS LESS THAN 1-YEAR OLD No XX No XX
02 DESIGN DEVELOPMENT
THE ACCESSIBLE PARKING TABULATION TABLE IS SHOWN AND UPDATED TO REFLECT PROJECT CONDITIONS / REQ. No XX No XX VERIFY THE CORRECT NUMBER OF ACCESSIBLE STALLS REQUIRED ARE INCLUDED. No XX No XX EXISTING FIRE FLOW REPORT IS DOCUMENTED, AND REQUIRED FIRE FLOW FOR PROJECT IS DOCUMENTED / LISTED No XX No XX REQUIRED NUMBER OF FIRE HYDRANTS HAS BEEN DOCUMENTED / UPDATED PER PROJECT REQ. No JM No XX FIRE FLOW REPORT FOR ALL FIRE HYDRANTS NEEDED FOR CODE COMPLIANCE IS COORDINATED W/ CONSULTANT TEAM(S) AND CSFM / LOCAL
FIRENS
No XX No XX
EACH REQUIRED FIRE HYDRANT(S) FOR THE PROJECT HAS MAX. COVERAGE DISTANCE RADIUS SHOWN (LINE IS A LIGHTWEIGHT DASHED LINE) No JM No XX PROJECT BUILDING IS SHOWN GRAPHICALLY, AND CORRECTLY IDENTIFIES: BLDG NUM., NAMES, BUILDING AREA IN SF, AND OCCUPANCY No JM No XX ALL GENERAL NOTES ARE APPROPRIATE FOR THE PROJECT No JM No XX SAFE DISPERSAL AREA CALCULATIONS ARE SHOWN AND ARE CORRECT. No XX No XX SAFE DISPERSAL AREA IS SHOWN WITH A DASHED BOX WITH LIGHT GREY BACKGROUND No XX No XX THE SAFE DISPERSAL AREA BOX IS DRAWN TO THE EXACT SQUARE FOOTAGE OF THE SAFE DISPERSAL CALCULATIONS No XX No XX THE SAFE DISPERSAL AREA IS A MINIMUM OF 50'-0" FROM ALL BUIDINGS No XX No XX THE DDCV / DDCA OR PIV IS SHOWN AND LABELED. No XX No XX ALL EASEMENTS, PROPERTY LINES, BOUNDARIES, AND RIGHT OF WAYS ARE SHOWN AND DIMENSIONED CLEARLY AND MATCH CIVIL PLANS No XX No XX ALL HYDRANTS ARE SHOWN AND LABELED No JM No XX PROVIDE A#'S FOR EXISTING SIGNAGE No XX No XX KEYNOTE LOCATION OF FIRE LANE SIGNAGE No XX No XX VERIFY ALL CORRECTIONS REQUIRED BY LOCAL FIRE AUTHORITY HAVE BEEN MADE, IF ANY. No XX No XX VERIFY LEGEND ITEMS HATCH/POCHE PATTERN AND SCALE MATCH THE HATCH/POCHE PATTERN AND SCALE OF THE FIRE SAFETY PLAN No JM No XX DRAWING VIEW TITLE, NORTH ARROW, AND GRAPHIC SCALE ARE SHOWN ON PLAN No JM No XX EXISTING CROSSWALKS, CURB RAMPS, AND ACCESSIBLE PARKING SPACES TO REMAIN HAVE THEIR ASSOCIATED A# ’S SHOWN. No XX No XX
03 CONSTRUCTION DOCUMENTS
LOCATION OF FIRE LANE SIGNAGE IS KEYNOTED No XX No XX A#'S IS PROVIDED FOR EXISTING SIGNAGE No XX No XX NEW/ EXISTING KNOX BOX ARE SHOWN, KEYNOTED AND COORDINATED WITH THE LOCAL FIRE AUTHORITY No XX No XX FIRE VEHICLE TURN-AROUND MEET THE CONDITIONS OUTLINED IN THE CALIFORNIA FIRE CODE. No XX No XX ALL CAMPUS FIRE HYDRANTS ARE SHOWN AND LABELED No XX No XX FIRE HYDRANT RADIUS DIMENSION IS CORRECTLY SHOWN (NO OVERRIDEN DIMENSIONS). No XX No XX ALL GENERAL NOTES ARE APPROPRIATE FOR THE PROJECT No XX No XX ALL EASEMENTS, PROPERTY LINES, BOUNDARIES, AND RIGHT OF WAYS ARE SHOWN AND DIMENSIONED CLEARLY AND MATCH CIVIL PLANS No XX No XX
NEW/ EXISTING KNOX BOX IS SHOWN, KEYNOTED AND COORDINATED WITH THE LOCAL FIRE
AUTHORITY
No XX No XX
THE FIRE VEHICLE TURN-AROUND MEETS THE CONDITIONS OUTLINED IN THE CALIFORNIA
FIRE CODE.
No XX No XX
KEYNOTE LOCATION OF FIRE LANE SIGNAGE No XX No XX
EACH REQUIRED FIRE HYDRANT(S) FOR THE PROJECT HAS MAX. COVERAGE DISTANCE RADIUS
SHOWN (LINE IS A LIGHTWEIGHT DASHED LINE)
No XX No XX
THE RADIUS DIMENSION IS CORRECTLY SHOWN (NO OVERRIDEN DIMENSIONS). No XX No XX SAFE DISPERSAL AREA CALCULATIONS ARE SHOWN AND ARE CORRECT. No XX No XX SAFE DISPERSAL AREA IS SHOWN WITH A DASHED BOX WITH LIGHT GREY BACKGROUND No XX No XX THE SAFE DISPERSAL AREA IS A MINIMUM OF 50'-0" FROM ALL BUIDINGS No XX No XX DRAWING VIEW TITLE, NORTH ARROW, AND GRAPHIC SCALE ARE SHOWN ON PLAN No XX No XX
1" = 20'-0" 1CODE OVERALL SITE PLAN
NO. DATE DESCRIPTION
PARKING LOT - MAIN ANALYSIS
Parking Lot Parking Stall Total
NUMBER OF ACC.
STALLS REQUIRED
NUMBER OF ACC.
STALLS PROVIDED
NUMBER OF VAN ACC.
STALLS REQUIRED
NUMBER OF VAN ACC.
STALLS PROVIDED
A 144 5 5 1 3 A: 144 Grand total: 144
BUILDING INFORMATION
DESCRIPTION
BUILDING
HEIGHT STORIES
BLDG. AREA
ACTUAL UNIT
AREA OCCUPANCY CONSTRUCTION TYPE SPRINKLER
CLUB HOUSE 29'-0" 2 9,164 SF A-2, M, B VB
DRIVING RANGE 24'-3" 2 9,959 SF S-2, B VB
100.00
CP
102.43
CP
101.26
CP
101.38101.25101.17 101.17101.07
100.66
100.66 100.65100.65 100.67
100.69 100.79 100.88 100.93
100.79100.71
100.62 100.54
100.60
100.32 100.27 100.30 100.37 100.45
100.45
100.31 100.0899.97
99.79
99.56
99.51
99.23
99.57
99.56
99.78
100.22100.15100.04100.00
99.94
99.90
99.95
99.98
100.02
100.06
100.06
100.12
100.11
99.22
99.50
99.88
100.26
100.49
100.72
101.27
101.25
100.72
100.69
100.96
100.46
100.34
99.82
100.18
100.44
100.49
100.66
100.77
100.77 100.85
100.87
100.80
100.72
100.65
100.44
100.22
100.16
100.06
100.34
100.62
100.78
100.95
100.82 100.68
100.70
101.02
100.90
100.87
100.77
100.72
100.82
100.70
100.88
100.92
101.22
101.38
101.25
101.10
100.96
100.91
100.87 100.98
101.03
100.90
100.71
100.44
100.35
100.29 100.30
100.34
100.40
100.50
100.59
100.70 100.83
101.14
101.30
100.86
101.07
101.38
101.47
101.53
101.52
101.40
101.43
101.29
101.39
101.53
101.87
101.91
101.90
101.82
101.61
101.37
101.26
101.28 101.55
101.54
101.41
101.56 101.64 101.80 101.85 102.35102.26102.06
102.00
101.87
102.28
102.42
102.41 102.08
102.02
102.08
101.82
101.61
101.55
101.55 101.63 101.77 101.84
101.40101.23101.18101.15
101.01100.92
100.64 100.65
100.71 100.65
100.97100.98100.94
100.56
100.58 100.62
100.61
100.94100.92
100.59 100.60
100.58 100.58
100.49
100.44
100.27 100.28
100.44
100.56
101.13101.02
101.80
102.38
102.28
102.08101.69
101.51 101.66
101.93 101.97
102.03
102.00
102.19
101.92
101.72
101.83101.60
101.51
101.40 101.42
101.41
101.47 102.08
101.98 102.08
101.57
101.41
101.35
101.35
101.39
101.46
101.48 101.48
101.48
101.50
101.48
101.44
101.36
101.27
101.13
101.05
101.09
100.98
100.74
100.76
100.81
100.97
101.15
101.28
101.37
101.47
101.48 101.48
101.43101.36101.21 100.88
100.86
101.09
101.52 101.34
101.37
101.32
101.38
101.30
101.32
101.41
101.54 101.54
101.54
101.46
101.41
101.24 101.09
101.06
100.89 101.11
101.27
101.14
101.26
101.41
101.48
101.38
101.26
101.09
100.90
100.77
100.72 100.70
100.68
100.82
100.92
101.06
100.83
100.80
100.75 100.69
100.65 100.61
100.59 100.59
100.63
100.63
100.66
100.75
100.85
101.03
101.12
101.22 101.31
101.31
101.22
101.12
101.00
100.84
100.66
101.95
101.45
101.35 101.52
102.85 102.84
102.85 102.85
102.78
102.65
102.35
102.13
101.99101.83
101.82
101.83
101.82
101.78
101.78 101.79
101.73
101.68102.11
102.11
102.09
102.11
102.08
108.63
105.02104.84
102.29
102.29 102.32
102.28
102.53
102.72
102.98
103.22
103.28
103.31
103.28
103.21
103.36 103.36
103.37
103.10
102.60
102.52 102.51
102.36 103.34
103.35 103.35
102.13
102.60
102.61
103.07
103.00
103.34
103.12
103.06
102.83
102.29
102.02
101.91
102.26
102.73
102.53
102.02
101.79101.72
101.81
102.30
102.07
101.84
101.55
101.87
101.64
101.36
101.33
101.52
101.51
101.46
101.25
100.76
N00° 00' 00.00"E
105.72
SD
SD
SD
SD
-1 .7
-1 .3
-1 .1
-1
.3
-5 .1
-0.6%
-0.9%
-1.0%
-0.9%
-0.9%
-1.3%
-0.5%
-0.3%
-4.6%
-1.3%
-0.5%
-0.5%
-1.
1%
-1.6%
-1 .0
-0.8%
-1.1%
-1.2%
-1 .3
-4.5%
-3.1%
-1.2%
-1 .2
-1 .2
-1 .5
-0 .3
-0.0%
-1 .6
-1 .8
102.04
101.51
101.63
101.08
101.10
101.37
101.28
TC 101.22
TC 101.28
TC 101.24
TC 101.16
TC 101.09
TC 101.15
100.74100.74
101.52
101.58
-1.0%
-1.4%
101.37
101.33
101.28
101.34
101.09
-0.5%
-7.8%
-5 .9
-2.2%
-0.1% -0.1%
-1 .3
%101.00
100.97
-1 .3
-1 .6
-1
.6
101.73
101.77
SD SD SD SD SD SD SD
101.14
101.16
TC 101.41
TC 101.19
101.50
-1.7%
TC 100.97
-3.5%
-4.9%
TC 101.20
100.33 99.90
100.35
-1 .4
-1.6%
-1.6%
-1 .4
-1 .3
-0.2%
101.05
BC 100.98
BC 100.99
BC 101.01
BC 101.01
BC 100.92
BC 100.80
BC 100.71
BC 100.96
BC 100.96
TC 101.98
TC 101.51
TC 101.86
BC 100.77
TC 102.24
TC 102.11
100.96
TC 102.08
TC 101.17
SCALE:
PLAN
1" = 5' 05' 2.5' 5' 10'
1" = 5'
SHEET NOTES
ADA VAN PARKING AND STRIPING PER DETAIL 3 / SHT C2
NEW CONCRETE WALK PER DET 1 / SHT C2, AND DETAILS 2-7 SHT
A-111
SAW CUT AND CONFORM TO EXISTING AC PER DETAIL 2 / SHT C2,
AND DETAIL 2 SHT A-111
RELOCATE EXISTING DUAL 3" CURB DRAIN, REPLACE WITH
CURB-O-LET DRAIN AT EACH END PER DETAIL TCD35-NS SHT C2,
MAINTAIN EXISTING FLOWLINES WITH NEW AC CONFORM
TERMINATE EXISTING AC DIKE AT WALKWAY
VEHICULAR CONCRETE PAD PER DETAIL 4 SHT C2
FLUSH WITH EXISTING CC
ADA PATH OF TRAVEL
CONCRETE EXPANSION JOINT PER DETAIL 1 SHT A-111
CONCRETE JOINT AT EX CONCRETE PER DETAIL 6 SHT A-111
CURB AT CONCRETE PAVEMENT PER DETAIL 7 SHT A-111
CONCRETE EDGE AT FINISHED GRADE PER DETAIL 3 SHT A-111
ADA PARKING SIGNAGE PER DETAIL 13 SHT A-111
TOOL JOINT PER DETAIL 5 SHT A-111, TYP
CURB AT AC PER DETAIL 5 SHT C2
REPLACE CURB TO MATCH EXISTING WITH NEW ELEVATIONS
SIMILAR TO DETAIL 5 SHT C2
PROVIDE INLET PROTECTION PER CONSTRUCTION BMP NOTES
EX RAISED PLATFORM AT BASE OF STAIR SEE ARCHITECT
DRAWINGS FOR DEMARCATION
REMOVE TREE
AC CONFORM 10'
AC CONFORM 9.4'
AC CONFORM 14'
AC
C
O N
FO
R
M 12.4'
SHEET ISSUE DATE:
JOB NUMBER:
SHEET TITLE
DRAWN BY:
THE ARCHITECT DOES NOT REPRESENT THAT THESE
PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY
SITE OTHER THAN THE ONE FOR WHICH THEY WERE
SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS
RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS
IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER
SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL
HAVE PRECEDENCE OVER SCALED DIMENSIONS.
ARCHITECT STAMP
REVISIONS
PROJECT OWNER & TITLE
SHEET NO.
D
AT
E
PL
O
TT
ED
FI
LE
L O
C
AT
IO
N
CONSULTANT STAMP
303 POTRERO STREET, SUITE 5
SANTA CRUZ, CA 95060
TEL (831) 440-7300
AGENCY APPROVAL:
5 4 3 2 1
A
B
C
D
E
A
B
C
D
6 5 4 3 2 1
ORIGINAL ISSUE DATE:
CONSULTANTS
4/ 2/
:0
2:
P M
C :\0
0_ re vi t l oc al m od el s\
R ev it
\2
.0 1_
C ity o f S an ta
C ru z_ D el av ea ga
G ol f C ou rs e_
R oo f R ep ai r_
A2 4_ ke nN
4Y 9G
.rv t
04/02/25
25034.01
PR
O
GR
ES
S
SE
T
DELAVEAGA GOLF COURSE - ROOF
REPAIR
401 Upper Park Road Santa Cruz, CA. 95060
CITY OF SANTA CRUZ
XX-XXXXXXXXXBLDG#
MARCH 18, 2025
C I V I L / S T R U C T U R A L E N G I N E E R
E L E C T R I C A L E N G I N E E R
MME
224 Walnut Ave, Suite B, Santa Cruz, cA. 95060
TEL (831) 426-3186
email@email.com
AURUM CONSULTING ENGINEERS
1798 Technology Drive, Suite 242, San Jose, CA. 95110 TEL (408) 564-7925 ext. 201
NO. DATE DESCRIPTION
CIVIL+STRUCTURAL ENGINEERING
224 Walnut Ave, Suite B Santa Cruz, CA 95060
Phone (831) 426-3186
0 08/25/2025 PERMIT SUBMITTAL
C1
JP
SITE & GRADING PLAN
FROMTO
AC CONFORM ± 2'
50 LF
2 LF
AC CONFORM ± 2'
16 ±9 LF
Construction Best Management Practices (BMP's):
· Project construction and demolition activities shall comply with the City’s Storm Water Best Management Practices for Construction. See the City website at:
http://www.cityofsantacruz.com/home/showdocument?id=6031
· Erosion & sediment control BMP's, such as inlet protection, fiber rolls, or wattles, shall be inspected regularly during construction and after each significant rain event. Make needed repairs immediately.
· Check the sidewalk and street daily during demolition and construction for soil drag-out, and sweep if needed. Routinely maintain the construction entrance/exit to ensure it remains effective at preventing drag-out.
· Store open bags of particulate, granular or powder materials (such as plaster or concrete) indoors if possible. If stored outside, they must be kept covered or closed, and during the rainy season kept within secondary containment.
· Dumpster lids must be kept closed and secured when not in use.
· Soil & Material Stockpiles: soil shall be hauled off site at end of each day.
· Construction Entrance/Exit: Use existing paved driveway/parking lot. ensure any drag out near the site is swept clean at the end of each day.
· During the rainy season, ensure that sediment control measures are in place and effective at preventing sediment from leaving the site.
· Storm Drain Inlet/Catch Basin Protection: Please use filter fabric or inserts for any adjacent street catch basins and BMP's for any onsite inlets. (Sand bags, gravel bags and straw wattles around storm drain inlets exposed to street traffic are not recommended). If using filter fabric, may use Filtrex 8” Soxx with Mirafi 140N fabric (or similar) underneath the grate.
Ensure fabric extends a minimum of 6-inches beyond catch basin after placement of grate and secure properly.
Contractor shall remove filter fabric upon project completion.
· Concrete and Masonry Washout: Refer to Concrete and Masonry BMP 's sheet C2
3.
3'
2'
±4
FT
T
O
IN
LE
T
±7
FT
T
O
IN
LE
T
15 35 LF
4INV = 100.86
INV = 101.26
I:\ six
D eL a
Ra ng e\ dw g\ C1
Ci vi l P la n.
dw g, 1/
5/
:3 1:
P
M , D
W G
To P
D F.
pc
SCALE: 1/4" = 1'-0"
3ACCESSIBLE PARKING
9' VARIES (NOTE 1)
4'-5"
3' -9
ACCESSIBLE PARKING
SIGN PER NOTE 2 AND
DET 13 SHT A-111
NOTES:
1. 5' FOR ACCESSIBLE
SPACE OR 8' FOR VAN
ACCESSIBLE SPACE PER
CBC §1129B.3, ¶2
2. SIGNAGE PER CBC
§1129B.4
3. GRADING TO BE NO
MORE THAN 2% IN ANY
DIRECTION PER CBC
§1129B.3, ¶4
4. LETTERING TO BE 12"
HIGH PER CBC §1129B.3, ¶1WHITE WHEELCHAIR ON
BLUE BACKGROUND
2% M
AX
(N
O
TE
LETTERS PAINTED IN
WHITE
3'
STRIPES IN BLUE OR
WHITE
ACCESS AISLE BORDER
PAINTED IN BLUE
STALL OUTLINE BORDER
PAINTED IN BLUE
2' -3
6"
BLUE WHEELSTOP
3'
ISI MARKING PER CALTRANS
STD PLAN A24C
SHEET ISSUE DATE:
JOB NUMBER:
SHEET TITLE
DRAWN BY:
THE ARCHITECT DOES NOT REPRESENT THAT THESE
PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY
SITE OTHER THAN THE ONE FOR WHICH THEY WERE
SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS
RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS
IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER
SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL
HAVE PRECEDENCE OVER SCALED DIMENSIONS.
ARCHITECT STAMP
REVISIONS
PROJECT OWNER & TITLE
SHEET NO.
D
AT
E
PL
O
TT
ED
FI
LE
L O
C
AT
IO
N
CONSULTANT STAMP
303 POTRERO STREET, SUITE 5
SANTA CRUZ, CA 95060
TEL (831) 440-7300
AGENCY APPROVAL:
5 4 3 2 1
A
B
C
D
E
A
B
C
D
6 5 4 3 2 1
ORIGINAL ISSUE DATE:
CONSULTANTS
4/ 2/
:0
2:
P M
C :\0
0_ re vi t l oc al m od el s\
R ev it
\2
.0 1_
C ity o f S an ta
C ru z_ D el av ea ga
G ol f C ou rs e_
R oo f R ep ai r_
A2 4_ ke nN
4Y 9G
.rv t
04/02/25
25034.01
PR
O
GR
ES
S
SE
T
DELAVEAGA GOLF COURSE - ROOF
REPAIR
401 Upper Park Road Santa Cruz, CA. 95060
CITY OF SANTA CRUZ
XX-XXXXXXXXXBLDG#
MARCH 18, 2025
C I V I L / S T R U C T U R A L E N G I N E E R
E L E C T R I C A L E N G I N E E R
MME
224 Walnut Ave, Suite B, Santa Cruz, cA. 95060
TEL (831) 426-3186
email@email.com
AURUM CONSULTING ENGINEERS
1798 Technology Drive, Suite 242, San Jose, CA. 95110 TEL (408) 564-7925 ext. 201
NO. DATE DESCRIPTION
CIVIL+STRUCTURAL ENGINEERING
224 Walnut Ave, Suite B Santa Cruz, CA 95060
Phone (831) 426-3186
0 08/25/2025 PERMIT SUBMITTAL
6" 8"
4"
SCALE:
PEDESTRIAN CONCRETE PVMT
1 1/2" = 1'-0"
EX NATIVE MATERIAL
CLASS II AGGREGATE BASE (AB)
COMPACT TO 95% RC
SCARIFY & RECOMPACT
SUBGRADE TO 95% RC
#4 AT 18" OC
EACH WAY
CONCRETE
3" 6"
SCALE:
VEHICULAR AC PAVEMENT
1 1/2" = 1'-0"
ASPHALT CONCRETE (AC)
CLASS II AGGREGATE BASE (AB)
COMPACT TO 95% RC IN TWO LIFTS
EXISTING BASE MATERIAL
SCARIFY 8" AND RECOMPACT
TO 95% RC
C2
JP
CIVIL DETAILS
SCALE: 1 1/2" = 1'
4VEHICULAR CONCRETE PVMT
6" 6"
#5 AT 16" OC, EW
AT MIDDEPTH, TYP
CONCRETE
SCARIFY AND RECOMPACT EXISTING
BASE TO 95% RC
CLASS II AGGREGATE BASE ROCK
COMPACT TO 95% RC
8"
SCALE:
REINFORCED CONCRETE CURB
1 1/2" = 1'-0"
CLASS II AGGREGATE BASE (AB)
COMPACT TO 95% RC
#4 AT 18" OC
EACH WAY
CONCRETE WALKWAY
PER DETAIL
#5 AT 2" MIN CLR
BATTER AND HEIGHT TO MATCH
EXISTING CURBS WHERE APPROPRIATE
±6
6- 8"
EXISTING AC OR LANDSCAPE MEDIA
6" 1"
6"
I:\ six
D eL a
Ra ng e\ dw g\ C2
D
ET
AI
LS
.d w g, 1/
5/
:3 1:
P
M , D
W G
To P
D F.
ASPHALT CONCRETE PAVEMENT
1. Aggregate Base, Class 2, shall be in accordance with Sections 26-1.02B, 26-1.03, 26-1.04 and 26-1.05 of the Caltrans Standard Specifications.
2. Hot Mix Asphalt (HMA) shall be "Type A", binder grade shall be "PG 64-10" and shall conform to the provisions in Section 39, "Asphalt Concrete," of the Standard Specifications and these special provisions.
3. HMA shall be produced from commercial quality asphalt and aggregates. The spreading and compacting requirements of the Standard Specifications shall apply. HMA shall be produced at a central mixing plant.
4. Aggregate shall conform to the grading specified in Section 39-2.02 of the Caltrans Standard Specifications.
5. Aggregate gradation for Type A HMA placed in a single lift shall comply with requirements shown in the following table:
HMA THICKNESS Maximum Aggregate 0.10' (1.2") 3/8" >0.10' to <0.20' (>1.2" to <2.4") 1/2" 0.20' to <0.25' (2.4" to <3.0") 3/4" >0.25' (>3.0") 3/4" or 1"
6. Where pavement is 0.30' (3.6”) or greater, you may use multiple lifts not less than 0.15' (1.8”) each. The thickness of any HMA layer must not exceed 0.33 feet (4 inches) for lower courses and
0.25 feet (3 inches) for surface courses. The Engineer may allow thicker lifts if the contractor demonstrates the ability to achieve specified density throughout the lift. A tack coat shall be applied before placing subsequent lifts. Aggregate gradation for Type A HMA placed in a multiple lifts shall comply with requirements shown in the following table:
HMA LIFT THICKNESS Maximum Aggregate 0.15' to <0.20' (1.8" to <2.4") 1/2" 0.20' to <0.25' (2.4" to <3.0") 3/4"
>0.25' (>3.0") 3/4" OR 1"
7. The amount of asphalt binder to be mixed with the aggregate shall be between 4 percent and 7 percent, by weight, of the dry aggregate.
8. Spreading and compacting shall be performed by methods that will produce an HMA surfacing of uniform smoothness, texture and density.
9. A prime coat of liquid asphalt, SC-70, and a tack coat and fog seal coat of asphaltic emulsion shall be applied in accordance with the appropriate section of the Caltrans Standard Specifications.
10. Existing pavement shall be coated with asphaltic emulsion at all locations where new pavement joins existing pavement. Existing AC or PCC pavement to be removed shall be saw cut and removed to clean straight lines.
11. An approved soil sterilizer shall be used on all natural-ground subgrades when placing AC pavement directly on subgrade.
12. Paving contractor shall reset manhole rings 1/8" below grade after placement of AC pavement.
13. All areas which are to receive AC overlay shall be edge-ground for a smooth conform prior to the placement of the overlay. Existing cracks over 1/8" wide shall be sealed with an approved rubberized asphaltic material crack sealant.
14. All temporary patches shall be of the "hot mix" variety. "Cold mix" shall not be allowed under any circumstances.
15. Pavement Reinforcement Mat shall be "Tencate Mirafi TruPave" or approved equal. Pavement reinforcement mat shall be placed in accordance with:
- Caltrans Standard Specifications Section 39-4.03
- "Installation Guidelines for Truepave Engineered Paving Mat Under Hot Mix Asphalt Concrete (HMAC)", Owens Corning, 2005
- "General Conditions and Special Provisions, Non-woven Fibergalss/polyester Interlayer Paving Mat", Owens Corning, 2005
SECTION 024119 - SELECTIVE SITE DEMOLITION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Demolition or disconnecting and capping designated utilities.
2. Protecting items designated to remain.
3. Removal of demolished materials.
1.3 DEFINITIONS
A. Remove: Detach items from existing construction and legally dispose of them off-site unless indicated to be removed and salvaged or removed and reinstalled.
B. Remove and Salvage: Carefully detach from existing construction, in a manner to prevent damage, and deliver to
Owner ready for reuse.
C. Remove and Reinstall: Detach items from existing construction, prepare for reuse, and reinstall where indicated.
D. Existing to Remain: Existing items of construction that are not to be permanently removed and that are not otherwise indicated to be removed, removed and salvaged, or removed and reinstalled.
1.4 MATERIALS OWNERSHIP
A. Unless otherwise indicated, demolition waste becomes property of Contractor.
B. Historic items, relics, antiques, and similar objects including, but not limited to, cornerstones and their contents, commemorative plaques and tablets, and other items of interest or value to Owner that may be uncovered during demolition remain the property of Owner.
1. Carefully salvage in a manner to prevent damage and promptly return to Owner.
1.5 PREINSTALLATION MEETINGS
A. Predemolition Conference: Conduct conference at San Lorenzo Valley Elementary School.
1. Inspect and discuss condition of construction to be selectively demolished.
2. Review and finalize selective demolition schedule and verify availability of materials, demolition personnel, equipment, and facilities needed to make progress and avoid delays.
3. Review areas where existing construction is to remain and requires protection.
1.6 INFORMATIONAL SUBMITTALS
A. Schedule of Selective Demolition Activities: Indicate the following:
1. Detailed sequence of selective demolition and removal work, with starting and ending dates for each activity.
Ensure Owner's manager's and tenants on-site operations are uninterrupted.
2. Interruption of utility services. Indicate how long utility services will be interrupted.
3. Coordination for shutoff, capping, and continuation of utility services.
1.7 CLOSEOUT SUBMITTALS
A. Project Record Documents: Record actual locations of capped utilities.
1.8 FIELD CONDITIONS
A. Owner will occupy portions of building immediately adjacent to selective demolition area. Conduct selective demolition so Owner's operations will not be disrupted.
B. Notify Architect of discrepancies between existing conditions and Drawings before proceeding with selective demolition.
C. Storage or sale of removed items or materials on-site is not permitted.
D. Utility Service: Maintain existing utilities indicated to remain in service and protect them against damage during selective demolition operations.
1. Maintain fire-protection facilities in service during selective demolition operations.
PART 2 - EXECUTION
2.1 EXAMINATION
A. Verify that utilities have been disconnected and capped before starting selective demolition operations.
B. Review record documents of existing construction provided by Owner. Owner does not guarantee that existing conditions are same as those indicated in record documents.
C. Survey existing conditions and correlate with requirements indicated to determine extent of selective demolition required.
2.2 UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS
A. Existing Services/Systems to Remain: Maintain services/systems indicated to remain and protect them against damage.
1. Comply with requirements for existing services/systems interruptions specified in Division 01 Section
"Summary."
B. Existing Services/Systems to Be Removed, Relocated, or Abandoned: Locate, identify, disconnect, and seal or cap off indicated utility services and mechanical/electrical systems serving areas to be selectively demolished.
1. Owner will arrange to shut off indicated services/systems when requested by Contractor.
2. Existing utilities shall be abandoned in accordance with the geotechnical investigation.
3. If services/systems are required to be removed, relocated, or abandoned, provide temporary services/systems that bypass area of selective demolition and that maintain continuity of services/systems to other parts of site.
2.3 PREPARATION
A. Temporary Facilities: Provide temporary barricades and other protection required to prevent injury to people and damage to adjacent buildings and facilities to remain.
1. Provide protection to ensure safe passage of people around selective demolition area and to and from occupied portions of building.
2. Provide temporary weather protection, during interval between selective demolition of existing construction on exterior surfaces and new construction, to prevent water leakage and damage to structure and interior areas.
2.4 SELECTIVE DEMOLITION, GENERAL
A. General: Demolish and remove existing construction only to the extent required by new construction and as indicated.
2.5 SELECTIVE DEMOLITION PROCEDURES FOR SPECIFIC MATERIALS
A. Concrete: Demolish in sections. Cut concrete full depth at junctures with construction to remain and at regular intervals using power-driven saw, then remove concrete between saw cuts.
2.6 DISPOSAL OF DEMOLISHED MATERIALS
A. General: Except for items or materials indicated to be recycled, reused, salvaged, reinstalled, or otherwise indicated to remain Owner's property, remove demolished materials from Project site and legally dispose of them in an EPA-approved landfill.
1. Do not allow demolished materials to accumulate on-site.
2. Remove and transport debris in a manner that will prevent spillage on adjacent surfaces and areas.
3. Comply with requirements specified in Division 01 Section "Construction Waste Management and Disposal."
B. Burning: Do not burn demolished materials.
C. Disposal: Transport demolished materials off Owner's property and legally dispose of them.
2.7 CLEANING
A. Clean adjacent structures and improvements of dust, dirt, and debris caused by selective demolition operations.
Return adjacent areas to condition existing before selective demolition operations began.
2.8 SELECTIVE DEMOLITION SCHEDULE.
A. Reuse items designated as such on the plans, coordinate with San Lorenzo Valley School District.
END OF SECTION 024119
SECTION 321313 - CONCRETE PAVING
PART 1 GENERAL
1.1 SUMMARY
A. Related Documents:
1. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Division 01 Specification Sections, apply to this Section.
B. Section Includes:
1. Concrete flatwork, walkways and accessible ramps.
1.2 SUBMITTALS
A. Product Data: Submit data on mix design including water cement ration and mix history verifying compressive strength, joint filler (including color), admixtures and curing compounds.
1.3 QUALITY ASSURANCE
A. Perform Work in accordance with ACI 301 and the requirements of Section 033000.
B. Perform Work in accordance with Caltrans Standard Plans and Specifications.
C. Perform Work in accordance with California Building Code 2010.
D. Obtain cementitious materials from same source throughout.
1.4 ENVIRONMENTAL REQUIREMENTS
B. Do not place concrete when base surface temperature is less than 40 degrees F, or surface is wet or frozen.
PART 2…