This document provides details for a federal solicitation to rehabilitate Quarters 3. The solicitation number is 140P6023B0007 issued by the Department of the Interior National Park Service Midwest Region. It seeks to rehabilitate a residential property located within a National Park by replacing all windows, doors, siding, and roofing along with electrical, plumbing and HVAC system upgrades. Bids are due by April 15th, 2023 with award notice expected on or around May 1st. The attached file contains 29 pages of detailed construction drawings specifying the scope of work.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

�SPRINKLER PROTECTION

NOT REQUIRED IN GARAGED

ATTACHED TO DWELLING

UNIT PER NFPA 13D.

GARAGE

U!19J

SEE SITE PLAN SHEET

FP100 FOR CONTINUATION

l

I

�I

CONTRACTOR SHALL BEGIN AT

DISCHARGE OF EXISTING REDUCED

PRESSURE BACKFLOW PREVENTER.

PROVIDE NEW WATERFLOW SWITCH,

TEST AND DRAIN ASSEMBLY, PRESSURE

RELIEVE, AND EXPANSION TANK FOR

ANTIFREEZE SYSTEM.

jJ I

UTILITY ROOM

_J_Q_8

I,¾'

' D-, n1¼

ITT

lli

DINING

I till

[GE

1¼'

1'' 1-6½

9'-0"

KITCHEN

[_j_Q!U

I¼" 5 6 7 5 4 g 10 10½

1'' 5-4

4'-1"

11,r--------,f b

I \

I" 5-4

LIVING ROOM

0 I

SPRINKLER PROTECTION NOT

REQUIRED IN CLOSET SMALLER

THAN 55 SQ FT IN DWELLING

UNIT PER NFPA 130.

FIRE SPRINKLER PLAN

SCALE: 1/8" = 1'-0"

l 1-2023

FIN. FLOOR ELEV. = 100'-0"

ENGINEER OF RECORD:

WILLIAM B. SMITH, PE

LICENSE NO. E-1491�

CODE CONSULTANTS

PROFESSIONAL ENGINEERS, PC

2043 WOODLAND PKWY, SUITE 300

ST. LOUIS, MU 63146-4235

COIIPORATE CfRTIF!CATE OF AUTHORITY

NO. 10188652

�o ™ I

2043 WOODLAND PKWY, SUITE 300

ST. LOUIS, MISSOURI 63146-4235

314-991-2633 www.codeconsullants.com

LAYOUT IS CONCEPTUAL ONLY.

CONTRACTOR SHALL VERIFY ACTUAL

LAYOUT UPON INSPECTION AND REMOVAL

OF EXISTING SYSTEM. COORDINATE WITH

EXISTING SPRINKLER PLACEMENT WHERE

POSSIBLE WHEN INSTALLING NEW

SPRINKLERS AND PIPE ROUTING. VERIFY

FINAL LAYOUT WITH HYDRAULIC

CALCULATIONS.

I

SPRINKLER PROTECTION NOT

REQUIRED IN BATHROOM

SMALLER THAN 55 SQ FT IN

DWELLING UNIT PER NFPA 130.

C]

BEDROOM

10�7

BATHROOY

1-05

6'-0" 0 ._ _ _ _ ____ ·J,roo:, ========r

- I " I¼"

' '7

1"1

BEDROOM

1___1_Q_J_I

8'-5"

HC BATHROOM

U2lJ

1" GLOBE VALVE WITH 3/4"

HOSE END ADAPTER

(MANUAL AIR VENT AND

ANTIFREEZE TEST PORT) 6'-1"

NATIONAL

PARK

SERVICE

O<?artmcnt ot •�• lnlcrior

I� SPRINKLER PROTECTION NOT

I REQUIRED IN CLOSET SMALLER

THAN 55 SQ FT IN DWELLING

UNIT PER NFPA 130.

SCH::MM::R

Dtiign with Pu,_,,. Build ...th C,,,,fidem,,_

1044 North 115th Street I Suite 300 Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED

DATE I INITIAL

PREPARED

JLK

DESIGNED

JLK

DRAWN

JLK

CHECKED

04/11/2023

DATE

SYMBOL KEY

� - - ----( EXISTING UNDERGROUND WATER MAIN

,_, ___ ,, _' NEW PIPING

ff

RECOMMENDED CENTER LINE ELEVATION OF PIPE AF.F. AND/OR CENTER

LINE ELEVATION OF PIPE FROM TOP OF JOIST

--I, CJ

NOTE

GLOBE VALVE

RISER

FIRE DEPARTMENT CONNECTION

RISE FROM LEFT TO RIGHT ANO DROP FROM RIGHT TO LEFT

CAPPED PIPE

PLUGGED OUTLET

HYDRAULIC REFERENCE POINT

CENTER LINE OF SPRINKLER: ALIGN WITH LIGHTS AND/OR OTHER

SPRINKLERS; COORDINATE WITH OTHER TRADES.

PIPE HANGER

TRAPEZE HANGER

ZONE BOUNDARY LINE

AREA OF DEMOLITION. REMOVE ALL PIPING AND SPRINKLER

COMPONENTS NOT INTENDED FOR REUSE

STRUCTURAL SHOWN FOR REFERENCE ONLY, VERIFY ACTUAL STRUCTURAL LOCATIONS.

SPRINKLER LEGEND

SYMBOL SPRINKLER TYPE TEMP. K FINISH RESP. QTY.

• WHITE EXTENDED COVERAGE RESIDENTIAL ORO PENDENT WITH RECESSED ESCUTCHEON 4.9 WHITE QR 45

)8( EXISTING SPRINKLER TO BE DEMOLISHED

TITLE OF SHEET

FLOOR PLAN

FIRE PROTECTION

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

ARCH/ENG PROJ #

07310.035

SUB SHEET NO.

DRAWING NO.

80054

PMIS / PKG. NO.

256385

SHEET

7 OF29

SUB SHEET NO.

FP102

SPECIFICATIONS 211313 FIRE SPRINKLER SYSTEMS

PART 1 GENERAL

1.1 RELATED DOCUMENTS

A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL

AND SUPPLEMENTARY CONDITIONS ANO DIVISION 01 SPECIFICATION SECTIONS,

APPLY TO THIS SECTION.

B. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND RELATED ITEMS

REQUIRED FOR THE COMPLETE DESIGN AND INSTALLATION OF AUTOMATIC

SPRINKLER SYSTEM.

C. ALL AREAS OF THE BUILDING SHALL BE PROTECTED BY WET AUTOMATIC FIRE

SPRINKLERS. THE SYSTEM SHALL BE HYDRAULICALLY CALCULATED. DENSITY

SHALL SE IN ACCORDANCE WITH NFPA 13D UNLESS SPECIAL CIRCUMSTANCES

SUCH AS STACKING HEIGHTS OR MATERIALS TO BE STORED CAUSE OTHER

CHAPTERS OF THE NFPA TO BE REQUIRED. FOLLOW THOSE CHAPTERS FOR THE

APPROPRIATE SPRINKLER REQUIREMENTS.

1.2 SUMMARY

A. SECTION INCLUDES:

1. PIPES, FITTINGS, AND SPECIALTIES.

2. HANGERS AND SLEEVES.

3. FIRE PROTECTION VALVES:

a. ELECTRONICALLY SUPERVISED INDICATING CONTROL VALVES.

b. CHECK VALVES.

c. GLOBE VALVES.

d. BALL VALVES.

e. ANGLE VALVES.

4. TEST CONNECTIONS, MAIN DRAINS AND AUXILIARY DRAINS.

5. SPRINKLERS,

6. ALARM DEVICES.

7. PRESSURE GAGES.

8. SIGNS.

9. CORROSION MANAGEMENT PRODUCTS.

1.3 DESCRIPTION OF WORK

A. PROVIDE ALL REQUIRED LABOR, MATERIALS, EQUIPMENT, TESTING AND

SERVICES NECESSARY FOR A COMPLETE AND OPERATIONAL WET PIPE FIRE

PROTECTION SYSTEM FOR THE BUILDING AS HEREINAFTER DESCRIBED AND AS

SHOWN ON THE ENGINEERING DRAWINGS.

B. WORK SHALL BEGIN AT THE FLANGE LOCATED AT THE BACKFLOW PREVENTER

INSIDE THE BUILDING AND SHALL INCLUDE THE FOLLOWING:

1. ANTI-FREEZE (WET PIPE) FIRE SPRINKLER SYSTEM FOR THE ENTIRE

BUILDING.

2. COORDINATION OF WORK AND SCHEDULES WITH OTHER TRADES.

C. IT IS INTENDED THAT THE ENGINEERING DRAWINGS AND SPECIFICATION SHALL

DESCRIBE AND PROVIDE FOR A WORKING INSTALLATION COMPLETE IN EVERY

DETAIL AND ALL ITEMS NECESSARY FOR SUCH COMPLETE INSTALLATION SHALL

BE PROVIDED WHETHER OR NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN

ON THE ENGINEERING DRAWINGS,

1.4 DEFINITIONS

A. STANDARD PRESSURE SPRINKLER PIPING: LISTED FOR 175 PSI MINIMUM

WORKING PRESSURE.

1.5 SYSTEM DESCRIPTION

A. FIRE SPRINKLER SYSTEM DESIGN CRITERIA SHALL BE STRICTLY PER THIS

SPECIFICATION.

B, FIRE SPRINKLER SYSTEM TO PROVIDE FIRE PROTECTION FOR THE ENTIRE

BUILDING.

C. INTERFACE FIRE SPRINKLER SYSTEM WITH BUILDING FIRE ALARM SYSTEMS.

D. RESIDENCE (NFPA 13D - RESIDENTIAL DWELLING UNIT - ANTIFREEZE (WET PIPE)

FIRE SPRINKLER SYSTEM):

DENSITY - 0.05 GPM/SQ FT

OPERATING AREA - ALL SPRINKLERS WITHIN A COMPARTMENT. UP TO A

MAXIMUM OF TWO. (FLAT SMOOTH CEILINGS LESS THAN 24 FT IN HEIGHT).

TEMPERATURE CLASSIFICATION / NOMINAL K-FACTOR I RESPONSE TYPE -

ORD 1 4.9 / QR

DURATION: 10 MINUTES

COMMON SUPPLY ALLOWANCE: 5 GPM SHALL BE ADDED TO COMPENSATE

FOR DOMESTIC DEMAND

E. SPRINKLER SPACING SHALL BE AS SHOWN ON THE ENGINEERING DRAWINGS.

1. HARD CEILINGS - LOCATE SPRINKLERS IN ACCORDANCE WITH THE

ENGINEERING DRAWINGS. SPRINKLERS SHALL BE IN LINE WITH LIGHT

FIXTURES AND OTHER SPRINKLERS WHERE INDICATED ON THE DRAWINGS.

COORDINATE CLOSELY WITH THE ELECTRICAL CONTRACTOR.

2. UNFINISHED AREAS - LOCATE SPRINKLERS AS SHOWN ON THE ENGINEERING

DRAWINGS.

F. PROVIDE ALL NECESSARY OFFSETS, RAISES OR DROPS IN MAIN OR BRANCH LINE

PIPING AND AUXILIARY DRAINS REQUIRED BY BUILDING CONDITIONS WHETHER

OR NOT SHOWN ON THE ENGINEERING DRAWINGS.

G. EXAMINE THE JOB CONDITIONS AND VERIFY ALL MEASUREMENTS, DISTANCES,

ELEVATIONS, CLEARANCES, PIPE SIZES, ETC.

H. IT IS UNDERSTOOD, UNLESS SPECIFICALLY INDICATED OTHERWISE, THAT THE

PIPE SIZES AS SHOWN ON THE ENGINEERING DRAWINGS WILL BE USED,

1.6 PERFORMANCE REQUIREMENTS

A. STANDARD PRESSURE PIPING SYSTEM COMPONENT: LISTED FOR 175 PSI

MINIMUM WORKING PRESSURE.

B. WATER SUPPLY:

THE AVAILABLE WATER SUPPLY WAS NOT AVAILABLE AT THE TIME OF

CONSTRUCTION DOCUMENT ISSUE. UPON AWARD, THE SUCCESSFUL FIRE

SPRINKLER CONTRACTOR SHALL PERFORM A NFPA 291 COMPLIANT WATERFLOW

TEST ANO FORWARD A REPORT OF THE TEST RESULTS TO CODE CONSULTANTS,

INC, THE OWNER'S REPRESENTATIVE, AND ARCHITECT. A MINIMUM SAFETY

FACTOR OF 10% OF THE STATIC PRESSURE SHALL BE APPLIED TO BOTH THE

STATIC AND RESIDUAL PRESSURES FOR THE PURPOSE OF HYDRAULIC

CALCULATIONS. PROVIDE LOCATION AND ELEVATION DIFFERENCES BETVVEEN

THE FLOW TEST AND THE FINISHED FLOOR OF PROJECT SPACE.

THE FIRE PROTECTION WATER SUPPLY WILL BE PROVIDED BY COMBINATION

DOMESTIC/FIRE WATER SERVICE FEED FROM THE PUBLIC UTILITY. THE WATER

SERVICE IS 1-112" UNDERGROUND WITH A 1-1/4' REDUCED PRESSURE BACKFLOW

PREVENTER (AMES 40006).

FIRE PROTECTION WATER SUPPLY HAS BEEN ASSUMED BASED ON EXISTING MAIN

DRAIN TEST OBTAINED FROM AN ANNUAL TEST REPORT. THE STATIC PRESSURE

AVAILABLE IS 60 PSI PERFORMED ON 07/2212021 BY CONTINENTAL FIRE SPRINKLER

COMPANY. THE WATER SUPPLY SHALL BE CONSIDERED EFFECTIVE AT THE

DISCHARGE OF THE BACKFLOW PREVENTER. THE APPROXIMATE WATER SUPPLY

ELEVATION IS 3 FT ABOVE THE FINISH FLOOR.

ACTUAL STATIC:

ESTIMATED RESIDUAL:

ESTIMATED FLOW:

60 PSI

30 PSI

50 GPM

THE ABOVE WATER SUPPLY COORDINATES DO NOT INCLUDE THE REQUIRED 10%

OF THE STATIC PRESSURE SAFETY FACTOR THAT SHALL BE ENFORCED. THE

FOLLOWING WATER SUPPLY COORDINATES HAVE BEEN ADJUSTED -6 PSI FOR THE

REQUIRED SAFETY FACTOR.

DESIGN STATIC:

DESIGN RESIDUAL:

DESIGN FLOW:

1.7 SUBMITTAL$

54 PSI

24 PSI

50 GPM

A. THE ENGINEERING DRAWINGS HAVE BEEN PREPARED USING AUTOCAD. THE

HYDRAULIC CALCULATIONS HAVE BEEN PREPARED USING HYORACALC. THESE

DOCUMENTS WILL BE MADE AVAILABLE TO THE SUCCESSFUL FIRE SPRINKLER

CONTRACTOR IN EITHER ELECTRONIC FORM OR HARD COPY. UTILIZATION OF

THESE DOCUMENTS FOR THE DEVELOPMENT OF SHOP DRAWINGS AND

SUBMITTAL$ DOES NOT RELIEVE THE FIRE SPRINKLER CONTRACTOR FROM ANY

OF HIS RESPONSIBILITIES REQUIRED HEREIN.

B. SUBMITTAL$ SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF THE GENERAL

CONDITIONS OF THE CONTRACT.

C. PRODUCT LITERATURE: FOR ALL WET PIPE SPRINKLER SYSTEM EQUIPMENT.

1. LITERATURE SHALL CLEARLY IDENTIFY EXACTLY WHAT COMPONENTS ARE

BEING PROVIDED AND SHALL INCLUDE: FINISH, SIZE, TYPE, ETC. LITERATURE

WHICH IS NOT CLEARLY IDENTIFIED WILL BE REJECTED.

D. SHOP DRAWINGS:

1. DRAWINGS MUST BE COMPREHENSIVE OF ENTIRE PROJECT,

DEMONSTRATING COORDINATION WITH OTHER DISCIPLINES, COMPLETE IN

ALL DETAIL AND THE SAME SCALE AS THE ENGINEERING DRAWINGS.

2. HYDRAULIC CALCULATIONS (CALCULATIONS SHALL INCLUDE PEAKING

INFORMATION),

3. NPS REGIONAL FIRE MARSHAL (AHJ) WILL REVIEW THIS SUBMITTAL FOR

CONSISTENCY WITH CONTRACT DOCUMENTS AND FOR APPROVAL.

E. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR RESPONDING.

IN WRITING, TO ANY COMMENTS FROM THE AHJ WITHIN TEN (10) WORKING DAYS

AFTER THE RECEIPT OF THEIR COMMENTS. COPIES OF THE RESPONSE SHALL BE

SENT TO THE GENERAL CONTRACTOR.

E. PROVIDE AS-BUILT DOCUMENTS IN ACCORDANCE WITH REQUIREMENTS OF THE

GENERAL CONDITIONS OF THE CONTRACT.

E. FIELD TEST REPORTS AND CERTIFICATES: INDICATE TEST RESULTS FOR

COMPLIANCE WITH PERFORMANCE REQUIREMENTS AND AS DESCRIBED IN NFPA

13. INCLUDE "CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR

ABOVEGROUND PIPING."

F. PROVIDE OPERATING ANO MAINTENANCE INSTRUCTIONS TO THE OWNER IN

ACCORDANCE WITH REQUIREMENTS OF THE GENERAL CONDITIONS OF THE

CONTRACT AND NFPA 130.

1.8 QUALITY ASSURANCE

A INSTALLER QUALIFICATIONS:

1. INSTALLER'S RESPONSIBILITIES INCLUDE PREPARING SHOP DRAWING

SUBMITTAL, FABRICATING, AND INSTALLING SPRINKLER SYSTEMS. BASE

CALCULATIONS ON WATER SUPPLY COORDINATES PROVIDED HEREIN.

a. INSTALLER SHALL BE STATE AND LOCALLY LICENSED.

b. INSTALLER SHALL BE MINIMALLY NICET LEVEL Ill OR A PROFESSIONAL

ENGINEER

B. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED

AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR

INTENDED LOCATION AND APPLICATION.

C. REFERENCES: FIRE SPRINKLER SYSTEM EQUIPMENT, SPECIAL TIES,

ACCESSORIES, INSTALLATION, AND TESTING SHALL COMPLY WITH ALL

APPLICABLE CODES AND REFERENCED DESIGN STANDARDS:

1. 2021 INTERNATIONAL BUILDING CODE

2. 2021 INTERNATIONAL FIRE CODE

3. NFPA 130, SPRINKLER SYSTEMS- 2022 EDITION.

D. EQUIPMENT AND COMPONENTS SHALL BE UL LISTED FOR FIRE PROTECTION

SYSTEMS INSTALLATION.

E. ALL FIRE SPRINKLER SYSTEM COMPONENTS SHALL BE INSTALLED FREE OF ANY

RUST, CORROSION OR VISIBLE DAMAGE. ALL ITEMS NOT COMPLYING WITH THIS

REQUIREMENT SHALL BE REPLACED WITHOUT COST TO THE OWNER.

1.9 COORDINATION

A. COORDINATE LAYOUT AND INSTALLATION OF SPRINKLERS WITH OTHER

CONSTRUCTION THAT PENETRATES CEILINGS, INCLUDING LIGHT FIXTURES, HVAC

EQUIPMENT, ANO PARTITION ASSEMBLIES.

B. COORDINATE INSTALLATION OF SYSTEM WITH ALL OTHER DISCIPLINES,

1.10 EXTRA MATERIALS

A. FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED AND THAT ARE

PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED WITH

LABELS DESCRIBING CONTENTS.

B. PROVIDE AT THE RISER ONE (1) TWELVE (12) HEAD SPARE SPRINKLER CABINETS

STOCKED WITH SPRINKLERS ANO ESCUTCHEON ASSEMBLIES PROPORTIONATE

TO THOSE PROVIDED IN THE BUILDING AND ALL NECESSARY SPRINKLER

WRENCHES AS REQUIRED BY NFPA 13D,

1.11 REGULATORY REQUIREMENTS

A. THE FIRE SPRINKLER CONTRACTOR SHALL NOT PURSUE ANY APPROVALS OR

INTERPRETATIONS OF THE CONTRACT DOCUMENTS EXCEPT THROUGH NPS

REGIONAL FIRE MARSHAL.

B. SPRINKLER PIPING SHALL NOT BE CONCEALED WHERE IT IS INACCESSIBLE

UNLESS IT IS FIRST INSPECTED AND ACCEPTED BY A REPRESENTATIVE OF THE

AUTHORITY HAVING JURISDICTION.

C. ANY WORK PERFORMED PRIOR TO THE SATISFACTORY REVIEW BY AND

APPROVAL BY THE AUTHORITY HAVING JURISDICTION, WILL BE SOLELY AT THE

FIRE SPRINKLER CONTRACTOR'S RISK.

0. THE SYSTEM WILL NOT BE ACCEPTABLE UNTIL FINAL TESTING AND RECEIPT OF

THE CONTRACTOR'S MATERIAL AND TEST CERTIFICATE HAS BEEN OBTAINED.

1.12 WARRANTY

A. REPAIR ALL DEFECTIVE WORKMANSHIP OR REPLACE ALL DEFECTIVE MATERIALS

FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER.

WORKMANSHIP OR EQUIPMENT FOUND TO BE DEFECTIVE DURING THAT PERIOD

SHALL BE REPLACED WITHOUT COST TO THE OWNER

PART 2- PRODUCTS

2.1 PIPE AND FITTINGS

A. PER LOCAL REQUIREMENTS AND NFPA 130. ALL PIPE SHALL HAVE A CORROSION

RESISTANCE RATIO (CRR) EQUAL TO OR GREATER THAN 1.00. REFER TO THE

CURRENT UL FIRE PROTECTION EQUIPMENT DIRECTORY - STEEL SPRINKLER PIPE

FOR ACCEPTABLE MANUFACTURERS, SIZES, AND JOINING METHODS.

B. THE ENGINEER'S HYDRAULIC CALCULATIONS ANTICIPATES THAT ALL GROOVED

WET PIPE SYSTEM RISERS, FEED AND CROSS MAINS, AND BRANCH LINES SHALL

HAVE HYDRAULIC CHARACTERISTICS EQUAL TO OR GREATER THAN SCHEDULE 10

PIPE.

C. ALL THREADED PIPING SHALL BE SCHEDULE 40 PIPE.

0. ALL 1 IN. SHALL BE SCHEDULE 40 PIPE.

E. ALL PIPING IN DRY SYSTEMS SHALL BE SCHEDULE 40 PIPE.

F. FITTINGS SHALL BE SCREWED OR FLANGED BLACK CAST IRON OR APPROVED

EQUAL SUCH AS MECHANICAL, GROOVED OR WELDED CONNECTIONS,

G. PRESSURE RATING: 175 PSI MINIMUM.

2.2 JOINING OF PIPE AND FITTINGS

A. ALL PIPE SHALL BE JOINED IN ACCORDANCE WITH NFPA 13D AND

MANUFACTURERS RECOMMENDATIONS.

B. WHERE GROOVED FITTINGS AND COUPLINGS ARE USED TOGETHER THEY SHALL

BE OF THE SAME MANUFACTURER.

C. BUSHINGS SHALL NOT BE USED.

D. FLEXIBLE COUPLINGS SHALL BE IDENTIFIED ON THE SHOP DRAWINGS.

2.3 HANGERS

A. ALL HANGERS TO BE OF APPROVED MATERIALS AND SPACED IN ACCORDANCE

WITH NFPA 130 AND THE PIPING MANUFACTURER'S SPECIFICATIONS.

B. THE SECTION MODULUS REQUIRED BY NFPA 130 SHALL BE PROVIDED FOR ALL

TRAPEZE MEMBERS SUPPORTING PIPING.

2.4 LISTED FIRE PROTECTION VALVES

A. GENERAL REQUIREMENTS:

1. PRESSURE RATING: 175 PSI MINIMUM.

B, INDICATING BUTTERFLY VALVES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. GRUVLOCK.

b. NIBCO.

c. TYCO.

d. VICTAULIC.

e. VIKING.

2. BODY MATERIAL: CAST IRON.

3. SUPERVISORY SWITCH.

C. CHECK VALVES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. MILWAUKEE VALVE.

b. MUELLER CO.

c. NIBCO.

d. STOCKHAM.

e. TYCO.

f. UNITED BRASS WORKS.

g. VICTAULIC,

2. TYPE: SWING CHECK OR WAFER.

3. BODY MATERIAL: CAST IRON.

D. OS&Y GATE VALVES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. MILWAUKEE VALVE.

b. MUELLER CO.

c. NIBCO.

d. STOCKHAM.

e. VIKING.

2. BODY MATERIAL: CAST IRON.

3. SUPERVISORY SWITCH.

2.5 TRIM AND DRAIN VALVES

A GENERAL REQUIREMENTS:

1. PRESSURE RATING: 175 PSI MINIMUM.

B. ANGLE VALVES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. MILWAUKEE VALVE.

b. NIBCO.

c. UNITED BRASS WORKS.

C. BALL VALVES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. MILWAUKEE VALVE.

b. NIBCO.

c. UNITED BRASS WORKS.

d. VICTAULIC.

D. GLOBE VALVES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. CRANE.

b. MILWAUKEE VALVE.

c. NIBCO.

2.6 SPECIALTY VALVES

A. GENERAL REQUIREMENTS:

1. PRESSURE RATING 175 PSI MINIMUM.

2. BODY MATERIAL: CAST IRON.

B. AUTOMATIC {BALL DRIP) DRAIN VALVES

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. NIBCO.

b. RELIABLE.

c. TYCO.

2. TYPE: AUTOMATIC DRAINING, BALL CHECK.

3. SIZE: NPS 3/4,

2.7 SPRINKLER SPECIAL TY PIPE FITTINGS

A. GENERAL REQUIREMENTS:

1. PRESSURE RATING: 175 PSI MINIMUM.

B. FLOW DETECTION AND ALARM TEST DRAIN ASSEMBLIES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. AGF MANUFACTURING INC. - MODEL 1011 WITH PRESSURE RELIEF (OR

EQUAL).

2. SIZE: 2 IN.

3. INLET AND OUTLET: THREADED.

C. SPRINKLER TEST FITTINGS:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. AGF MANUFACTURING INC.

b. TYCO.

c. VICTAULIC.

d. VIKING.

2. BODY MATERIAL: CAST OR DUCTILE IRON HOUSING WITH SIGHT GLASS.

3. SIZE: SAME AS CONNECTED PIPING.

4. INLET AND OUTLET: THREADED.

2.8 SPRINKLERS

A MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE

MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE

WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

1. GLOBE.

2. RELIABLE.

3. TYCO.

4. VICTAULIC.

5. VIKING.

B. GENERAL REQUIREMENTS:

1. PRESSURE RATING: 175 PSI MINIMUM.

2. ONLY SPRINKLERS MANUFACTURED AFTER JANUARY 1. 2021 WILL BE

ACCEPTED FOR USE.

3. ONLY SPRINKLERS MANUFACTURED UTILIZING BELLEVILLE SPRING SEALS

WILL BE ACCEPTABLE FOR USE.

C. SPRINKLER TYPES:

1. WHITE RECESSED - GLASS BULB QUICK RESPONSE RESIDENTIAL RECESSED

SPRINKLER WITH MATCHING RECESSED ESCUTCHEON.

D. SPRINKLER ESCUTCHEONS: MATERIALS, TYPES, AND FINISHES SHALL MATCH

SPRINKLERS.

1. ESCUTCHEONS SHALL BE LISTED FOR USE WITH THE SPRINKLER IT IS

INSTALLED WITH.

E, SPRINKLER GUARDS:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. GLOBE.

b. RELIABLE.

c. TYCO.

d. VICTAULIC.

e. VIKING.

2. TYPE: WIRE CAGE WITH FASTENING DEVICE FOR ATTACHING TO SPRINKLER.

2.9 ALARM DEVICES

A. ALARM DEVICE TYPES SHALL MATCH PIPING AND EQUIPMENT CONNECTIONS.

B. WATERFLOW SWITCHES - VANE TYPE:

1. MANUFACTURERS· SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. GUARDIAN.

b. POTTER ELECTRIC.

c. SYSTEM SENSOR.

2. WATERFLOW DETECTOR: ELECTRICALLY SUPERVISED.

3. COMPONENTS: TWO SINGLE-POLE, DOUBLE-THROW CIRCUIT SWITCHES FOR

ISOLATED ALARM AND AUXILIARY CONTACTS. 24-VOLT O.C. OR 110·VOLT A.C,;

COMPLETE WITH FACTORY SET. FIELD-ADJUSTABLE RETARD ELEMENT TO

PREVENT FALSE SIGNALS AND TAMPERPROOF COVER; CORROSION

RESISTANT COMPONENTS IN WATERWAY; DUST TIGHT CONSTRUCTION,

4. TYPE: PADDLE OPERATED.

5. PRESSURE RATING: 175 PSI MINIMUM.

6. DESIGN INSTALLATION: HORIZONTAL OR VERTICAL.

7. SIGNALS WATERFLOW THAT EQUALS OR EXCEEDS 10 GPM.

8. 0 TO 60 SECONDS ADJUSTABLE RANGE.

9. DETECTOR SHALL BE FURNISHED AND INSTALLED BY THE FIRE SPRINKLER

CONTRACTOR AND WIRED COMPLETE BY THE FIRE ALARM CONTRACTOR.

C. VALVE SUPERVISORY SWITCHES:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,

AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE

INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE

FOLLOWING:

a. GUARDIAN.

b. POTTER ELECTRIC.

c. SYSTEM SENSOR.

2. TYPE: ELECTRICALLY SUPERVISED.

3. COMPONENTS: SINGLE-POLE, DOUBLE-THROW SWITCH WITH NORMALLY

CLOSED CONTACTS: 24-VOLT D.C. OR 110-VOLT A.G.; TAMPER PROOF COVER;

DUST TIGHT CONSTRUCTION.

4. DESIGN: SIGNALS THAT CONTROLLED VALVE IS IN OTHER THAN FULLY OPEN

POSITION.

5. THE SUPERVISORY SWITCH SHALL BE FURNISHED AND INSTALLED BY THE

FIRE SPRINKLER CONTRACTOR AND WIRED COMPLETE BY THE FIRE ALARM

CONTRACTOR.

2.10 PRESSURE GAGES

A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE

MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE

WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

1. AMETEK: U.S. GAUGE DIVISION.

2. BRECCO CORPORATION.

3. WIKA INSTRUMENT CORPORATION.

B. DIAL SIZE: 31/i TO 4%-INCH DIAMETER

C. PRESSURE GAGE RANGE: 0 TO 250 PSI MINIMUM.

D. WATER SYSTEM PIPING GAGE: INCLUDE "WATER' OR "AIR/WATER" LABEL ON DIAL

FACE.

2.11 SIGNS

A. APPROVED ENAMELED METAL SIGNS SHALL BE SECURELY ATTACHED AT ALL

MAIN DRAINS, AUXILIARY DRAINS, ALARM TEST CONNECTIONS AND CONTROL

VALVES.

B. PROVIDE A PERMANENTLY ATTACHED PLACARD INDICATING HYDRAULIC DESIGN

INFORMATION IN ACCORDANCE WITH NFPA 130 AND PLACED ON THE RISER. A

MOCK-UP OF PLACARD SHALL BE INCLUDED WITH EQUIPMENT LITERATURE.

C. PROVIDE A PERMANENTLY ATTACHED PLACARD INDICATING GENERAL

INFORMATION IN ACCORDANCE WITH NFPA 13D AND PLACED ON THE RISER. A

MOCK-UP OF PLACARD SHALL BE INCLUDED WITH EQUIPMENT LITERATURE.

2.12 CORROSION MANAGEMENT

A. MANUAL AIR VENTS

1. PROVIDE MANUAL AIR VENTS: 175 PSI RATED WORKING PRESSURE WHERE

INDICATED ON DRAWINGS MOUNTED IN ACCORDANCE WITH THE

MANUFACTURER'S INSTRUCTIONS.

PART 3 - EXECUTION

3.1 COORDINATION WITH OTHER TRADES

REVISED

A. COORDINATE CLOSELY WITH ALL OTHER TRADES TO EXPEDITE CONSTRUCTION

AND AVOID INTERFERENCE.

3.2 SERVICE ENTRANCE PIPING

A CONNECT SPRINKLER PIPING TO FIRE WATER SERVICE PIPING TO BUILDING.

3.3 SYSTEM INSTALLATION

A. DEVIATIONS FROM ENGINEERING DOCUMENTS REQUIRE PRIOR WRITTEN

APPROVAL FROM THE ENGINEER OF RECORD.

B. PIPING STANDARD: COMPLY WITH REQUIREMENTS IN NFPA 13D FOR

INSTALLATION OF SPRINKLER PIPING.

C. INSTALL TEST CONNECTIONS IN SPRINKLER SYSTEM PIPING AS REQUIRED.

0. AUXILIARY DRAINS CONSISTING OF PLUGS, OR GLOBE VALVES ANO PLUGS

WHERE CAPACITY OF TRAPPED PIPE SECTION EXCEEDS 5 GALLONS, SHALL BE

PROVIDED TO DRAIN ALL POINTS IN THE SYSTEM THAT CANNOT BE DRAINED

BACK TO MAIN RISER.

E. INSTALL AUTOMATIC (BALL DRIP) DRAIN VALVE AT EACH CHECK VALVE FOR FIRE

DEPARTMENT CONNECTION, OR ON PIPING BETWEEN FIRE DEPARTMENT

CONNECTION AND CHECK VALVE. INSTALL DRAIN PIPING TO EXTERIOR.

F. INSTALL ALARM DEVICES IN PIPING SYSTEMS.

G. INSTALL HANGERS ANO SUPPORTS FOR SPRINKLER SYSTEM PIPING ACCORDING

TO NFPA 130.

H. INSTALL PRESSURE GAGES WHERE REQUIRED BY NFPA 13D. INCLUDE PRESSURE

GAGES WITH CONNECTION NOT LESS THAN NPS ¼ AND WITH SOFT METAL

SEATED GLOBE VALVE, ARRANGED FOR DRAINING PIPE BETWEEN GAGE AND

VALVE. INSTALL GAGES TO PERMIT REMOVAL, AND INSTALL WHERE THEY WILL

NOT BE SUBJECT TO FREEZING.

I. SLEEVES SHALL BE PROVIDED FOR PIPING PASSING THROUGH CONCRETE SLABS,

CONCRETE OR MASONRY WALLS AND PARTITIONS, THROUGH FLOORS, CEILINGS,

WALLS, OR PARTITIONS OF OTHER BUILDING MATERIALS. WATERTIGHT SLEEVES

CAULKED WITH MASTIC OR LEAD SHALL BE PROVIDED FOR FLOOR SLABS AND

WALLS ON OR BELOW GRADE. STANDARD PIPE OR GALVANIZED SHEET METAL

SLEEVES SHALL BE INSTALLED IN ABOVE GRADE CONSTRUCTION AS MAY BE

REQUIRED. THE SLEEVES SHALL BE OF SUFFICIENT DIAMETER TO PASS PIPE

LINES WITH COUPLINGS OR WITH INSULATION OR ANNULAR AREA FOR CAULKING

WHERE REQUIRED.

J. ESCUTCHEONS SHALL BE APPROVED FLOOR AND CEILING PLATES MADE OF

STEEL OR BRASS, PLAIN OR CHROMIUM PLATE FINISH AND SHALL BE INSTALLED

AROUND ALL EXPOSED PIPING PASSING THROUGH A FINISHED FLOOR, WALL OR

CEILING. THE PLATES SHALL BE OF SUFFICIENT OUTSIDE DIAMETER TO COVER

THE SLEEVE OPENING AND SHALL BE PROVIDED WITH SPRINGS OR SET SCREWS

TO INSURE THEM FITTING SNUGLY AROUND THE PIPE.

3.4 IDENTIFICATION

A INSTALL LABELING AND PIPE MARKERS ON EQUIPMENT AND PIPING ACCORDING

TO REQUIREMENTS IN NFPA 130 AND THE LOCAL AHJS.

3.5 FIELD QUALITY CONTROL

A. PERFORM TESTS AND INSPECTIONS.

B, TESTS AND INSPECTIONS:

1. LEAK TEST: AFTER INSTALLATION, HYDROSTATICALLY TEST ENTIRE SYSTEM

AND TEST FOR LEAKS BY CHARGING SYSTEM TO 10 PSI ABOVE MAXIMUM

OPERATING PRESSURE OR 150 PSI. WHICHEVER IS LESS IN ACCORDANCE

WITH NFPA 13D. REPAIR LEAKS AND RETEST UNTIL NO LEAKS EXIST.

2. TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE DAMAGED AND

MALFUNCTIONING CONTROLS AND EQUIPMENT.

3. FLUSH, TEST, AND INSPECT SPRINKLER SYSTEMS ACCORDING TO NFPA 130,

"SYSTEMS ACCEPTANCE" CHAPTER.

4. COORDINATE WITH FIRE ALARM TESTS. OPERATE AS REQUIRED.

5. VERIFY THAT EQUIPMENT HOSE THREADS ARE SAME AS LOCAL FIRE

DEPARTMENT EQUIPMENT.

C. TESTS SHALL BE WITNESSED BY THE AUTHORITY HAVING JURISDICTION, AND

OWNER'S AUTHORIZED AGENT.

0. PRELIMINARY TESTING PROCEDURES SHALL BE CONDUCTED AS MENTIONED

ABOVE TO ASSURE PROPER OPERATION WHEN THE FINAL TESTING IS

PERFORMED.

E. THE CONTRACTOR'S MATERIAL AND TEST CERTIFICATES AS SHOWN IN NFPA 13

MUST BE COMPLETED AND SUBMITTED TO THE ENGINEER BEFORE FINAL

ACCEPTANCE MAY BE GIVEN.

3.6 CLEANING

A REMOVE AND REPLACE SPRINKLERS WITH PAINT, OTHER THAN FACTORY FINISH,

INCLUDING OVERSPRAY.

3.7 DEMONSTRATION

A. TRAIN OWNER'S MAINTENANCE PERSONNEL TO ADJUST, OPERATE, AND MAINTAIN

FIRE SPRINKLER SYSTEM COMPONENTS.

B. AFTER COMPLETION OF ALL INSTALLATION, TESTS, ETC. AND PRIOR TO THE

OPENING DATE. THE SPRINKLER CONTRACTOR SHALL INSTRUCT THE OWNER IN

THE OPERATION OF THE SPRINKLER SYSTEM. PROVIDE WRITTEN OPERATING

INSTRUCTIONS AND MOUNT ON WALL IN A FRAME WITH GLASS FRONT. INCLUDE

THE FOLLOWING SO THAT THE OWNER

1. WILL IMMEDIATELY RECOGNIZE THE MAIN VALVES ARE IN OPEN OR CLOSED

POSITION,

2. WILL KNOW HOW TO DRAIN THE SYSTEM.

3. WILL KNOW HOW TO RESET THE ALARM SYSTEM.

4. Will KNOW NOW TO MAKE COMPLETE WEEKLY INSPECTION.

5. WILL KNOW HOW TO MAINTAIN THE SYSTEM IN ACCORDANCE WITH NFPA 130

AND 25,

END OF SECTION 211313

TITLE OF SHEET ARCH/ENG PROJ #

07310.035

ENGINEER OF RECORD:

WILLIAM B. SMITH, PE

LICENSE NO. E-1491�

�o

SCH::MM::R

DATE INITIAL

PREPARED

JLK

DESIGNED

JLK

SPECIFICATIONS

FIRE PROTECTION

SUB SHEET NO.

CODE CONSULTANTS

PROFESSIONAL ENGINEERS, PC

2043 WOODLAND PKWY. SUITE 300

ST. LOUIS, MO 63146-4235

CORPORATE CfRTIF!CATE OF AUTHORITY

NO. 10188652

I

2043 WOODLAND PKWY, SUITE 300

ST. LOUIS, MISSOURI 63146-4235

314-991-2633 www.codeconsullants.com

Dtiign with Pu,_,,. Build .-..th C,,,,fideft«,_

1044 North 115th Street I Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

DRAWN

JLK

CHECKED

04/11/2023

DATE

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

FP103

DRAWING NO.

80054

PMIS / PKG. NO.

256385

SHEET

8 OF29

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL

FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND

NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR

VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE

CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO

ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET

OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK.

CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO

FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL

FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER.

COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER

TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO

REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED

CONSTRUCTION.

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK

WITH STRUCTURE, CEILING, LIGHTING, AND PIPING.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

G. ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT

ANGLES AND PARALLEL TO BUILDING WALLS UNLESS OTHERWISE

INDICATED.

H. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

I. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,

MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED

PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN

RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP

WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE

OWNER AND ARCHITECT IN WRITING. THE WORK IN THE AFFECTED

AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY WRITTEN

AGREEMENT OF THE OWNER AND CONTRACTOR.

J. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INLET SIZE UNLESS

OTHERWISE NOTED.

K. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND

GENERAL CONTRACTOR.

A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE

ORIGINAL DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD

VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,

RELOCATED, OR SALVAGED ARE SHOWN AS SOLID, FULL-TONE

LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND

ARE SHOWN AS HALF-TONE.

B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS

LISTED BELOW OR HERE-IN. THE CONTRACTOR SHALL

COORDINATE ALL REQUIRED RENOVATION AND NEW

CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE

TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED

BELOW.

C. THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING

EQUIPMENT FROM FINISHED AREAS AND THROUGH WEATHER

BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL PLANS

AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING

TO ENSURE PROPER PATCHING AND REPAIR IS MADE TO THE

BUILDING.

D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION

AND REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS,

EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT, INSTALL, OR

ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER

HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.

E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED

SHALL BE CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT

DAMAGE AND STORED OR REINSTALLED ON THE SITE AS DIRECTED.

REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF

THE OWNER.

F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND

CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO

MECHANICAL REMOVALS.

G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,

MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED

PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT

BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL

IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT

THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE

WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE

RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND

ARCHITECT.

H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING

DEMOLITION SHALL BE COORDINATED WITH THE OWNER AND

GENERAL CONTRACTOR.

SYMBOL LEGEND

VOLUME DAMPER

DEMO TO EXISTING CONNECTION

SPRINKLER DRAIN

FIRE SUPPRESSION PIPING

ISOLATION VALVE

TAMPER SWITCH

MANUAL BALANCING VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

CONTROL VALVE (3 WAY)

CONTROL VALVE (2 WAY)

HOSE END DRAIN VALVE

PRESSURE REDUCING VALVE

AUTO FLOW CONTROL VALVE

CHECK VALVE

HVAC DUCTWORK AND SPECIALTIES

(CONT.)

MISCELLANEOUS SYMBOLS

RETURN DUCT DOWN

AIR TERMINAL (VERTICAL MOUNTING)

ROUND DUCT UP / DOUBLE LINE PIPE

ROUND DUCT DOWN / DOUBLE

LINE PIPE

RETURN DUCT UP

TURNING VANES

SUPPLY AND FRESH AIR DUCT DOWN

SUPPLY AND FRESH AIR DUCT UP

SIZE/TYPE

SIZE/TYPE

FLOW

FLOW

SIZE/TYPE

FLOW

SMOKE DAMPER

FIRE DAMPER-HORIZ FIRE SEPARATION

MOTORIZED DAMPER-OPPOSED BLADE

MOTORIZED DAMPER-PARALLEL BLADE

ROUND AIR TERMINAL

(HORIZONTAL MOUNTING)

GRAVITY DAMPER

(OR) SAFETY VALVE-STEAM

TEMP & PRESS RELIEF

FLOOR SINK

FLOOR DRAIN

GRADE CLEANOUT

PLUMBING VENT THRU ROOF

CLEANOUT / WALL CLEANOUT

THERMOSTATIC MIXING VALVE

M

M

MANHOLE

TRENCH DRAIN

OVERFLOW ROOF DRAIN

OXYGEN OUTLET

PIPE CAP

ELBOW UP

AIR OUTLET

TEE

ELBOW DOWN

VACUUM OUTLET

ROOF DRAIN

SIZE/TYPE

FLOW

HUMIDISTAT

THERMOSTAT

FLEXIBLE DUCT

S

H

T

TEMPERATURE SENSORUNION

TEE DOWN

STRAINER

EXPANSION JOINT

FLEXIBLE PIPE CONNECTION

AIR VENT

TEE UP

FIRE/SMOKE DAMPER

RECTANGULAR RETURN AIR TERMINAL

(HORIZONTAL MOUNTING)

RECTANGULAR SUPPLY AIR TERMINAL

(HORIZONTAL MOUNTING)

SOLENOID VALVE

F

D

TS

VALVES

FS

M

M

S

LPR

HPS

MPR

MPS

LPS

HVAC PIPING

GHWR

GHWS

HWR

HWS

PC

HPR

ES

BBD BOILER BLOW DOWN

EXHAUST STEAM

PUMPED CONDENSATE

HIGH PRESSURE RETURN

HIGH PRESSURE STEAM

MEDIUM PRESSURE RETURN

MEDIUM PRESSURE STEAM

LOW PRESSURE RETURN

LOW PRESSURE STEAM

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

FS-_

FD-_

CO

VTR

GCO

ORD-_

MH

X

A

V

RD-_

PIPING SPECIALTIES AND FITTINGS

WCO

FIRE PROTECTION

SIZE/TYPE

FLOW

RECTANGULAR EXHAUST AIR TERMINAL

(HORIZONTAL MOUNTING)

CWS

GCWS

CWR

CR

CS

RL

RDL

RS

GCWR GLYCOL CHILLED WATER RETURN

GLYCOL CHILLED WATER SUPPLY

REFRIGERANT LIQUID LINE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION LINE

HCWS

HCWR

HOT/CHILLED WATER SUPPLY

HOT/CHILLED WATER RETURN

DOMESTIC HOT WATER

RECIRCULATING (DHWR)

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

ST/OST

PLUMBING PIPING

ACID VENT

TW

AV

AW

W

DS

DSCW

TWR

DSHW

SANITARY VENT

BURIED EXTERIOR WATER

TEPID WATER RECIRCULATING

TEPID WATER

DISTILLED WATER

SOFTENED HOT WATER

SOFTENED COLD WATER

ACID WASTE

STORM DRAIN

SANITARY DRAIN (BELOW FLOOR)

SANITARY DRAIN (ABOVE FLOOR)

OXYGEN

VACUUM

OX

VAC

RO

A

REVERSE OSMOSIS WATER

COMPRESSED AIR

DEIONIZED WATERDI

AIR FLOW STATIONAFS

HPWR

HPWS

HEAT PUMP WATER RETURN

HEAT PUMP WATER SUPPLY

F

S

FS

NEW TO EXISTING CONNECTION

G NATURAL GAS

FOF

FOG

LPG

FOV

FOR

FOS

FUEL OIL RETURN

FUEL OIL SUPPLY

FUEL OIL GAGE

FUEL OIL FILL

FUEL OIL VENT

LIQUEFIED PETROLEUM GAS

CD CONDENSATE DRAIN

EXHAUST DUCT DOWN

EXHAUST DUCT UP

CO CARBON MONOXIDE SENSOR

CO2 CARBON DIOXIDE SENSOR

NO2 NITROGEN DIOXIDE SENSOR

SENSOR WITH GUARD'X'

DOUBLE - GRADE CLEANOUTDGCO

ST/OST STORM DRAIN (BELOW FLOOR)

WASTE AND ANESTHETIC

GAS DISPOSAL

NITROGEN

WAGD

N

MEDICAL AIRMA

PIPE GUIDE

HOSE BIBB

THERMOMETER

PIPE ANCHOR

HB

STEAM TRAP

RHY

WH

ROOF HYDRANT

WALL HYDRANT

PRESSURE GAUGE

EXISTINGDEMO

EXISTINGNEW

18 Ø

18x10

18/10

ROUND DUCT

FLAT OVAL DUCT-1ST FIG IS SIDE

SHOWN

RECT DUCT-1ST FIG IS SIDE SHOWN

ACOUSTICAL DUCT LINER

HVAC DUCTWORK AND SPECIALTIES

HIGH EFFICIENCY TAKEOFF

HIGH EFFICIENCY TAKOFF

WITH VOLUME DAMPER

NITROGEN OUTLET

MEDICAL AIR OUTLET

WASTE AND ANESTHETIC GAS

DISPOSAL OUTLET

N

MA

V

FLEXIBLE DUCTWORK CONNECTION

ABBREVIATIONS

NORTH

ARROW

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW

COLUMN

X

X

X

XXXX

SIM/OPP

X

XXXX

XX-1

X

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

ROOM / SPACE

NUMBER

LETTER/NUMBER

INDICATES NEW

COLUMN LINE

LETTER/NUMBER

INDICATES EXISTING

COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DRAWING/DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE DRAWING

XXX-1

PLUMBING

FIXTURES PLUMBING FIXTURE

DESIGNATION

X"PIPE

SIZE

PIPE SIZE (DIAMETER)

X"xX"

DUCT

SIZE

WIDTH x HEIGHT

X"/X" WIDTH / HEIGHT

X" DIAMETER

REF. DEMO NOTES ( ) XX REF. NOTES ( )

SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.

GENERAL DEMOLITION NOTES GENERAL NOTES

MECHANICAL SHEET LIST

NORTH PLAN

NORTH

TRUE

NORTH

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MBH 1000 BTUH

MCA MINIMUM CIRCUIT AMPS

MD MOTORIZED DAMPER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT

PROTECTION

MPR MEDIUM PRESSURE

RETURN

MPS MEDIUM PRESSURE STEAM

MS MOP SINK

N NITROGEN

NC NORMALLY CLOSED

NO NORMALLY OPEN

NPCW NONPOTABLE COLD WATER

NPHW NONPOTABLE HOT WATER

NPHWR NONPOTABLE HOT WATER

RECIRCULATING

OA OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

OX OXYGEN

P PUMP

PHC PREHEAT COIL

PIV POST INDICATING VALVE

PRV PRESSURE REGULATING VALVE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH,

GAUGE

PTAC PACKAGED TERMINAL AIR

CONDITIONER

RA RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF AREA DRAINS

RL REFRIGERANT DISCHARGE LINE

RF RETURN FAN

RH RELIEF HOOD

RHC REHEAT COIL

RL REFRIGERANT LIQUID LINE

RLA RELIEF AIR

RLF RELIEF FAN

RO REVERSE OSMOSIS WATER

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION LINE

RTU ROOF TOP UNIT

RV RELIEF VALVE

S SINK

SA SUPPLY AIR

SAN SANITARY SEWER

SD SMOKE DAMPER

SF SUPPLY FAN

SFU SANITARY FIXTURE UNIT

SH SHOWER

SP STATIC PRESSURE

SSS SURGICAL SCRUB SINK

ST STORM WATER

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVE

TONS TONS OF REFRIGERATION

TSP TOTAL STATIC PRESSURE

T THERMOSTAT

UH UNIT HEATER

UR URINAL

V VENT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

WB WET BULB

WC WATER CLOSETS

WCO WALL CLEANOUT

WF WASH FOUNTAINS

WFU WATER FIXTURE UNITS

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WS WATER SOFTENER

WSHP WATER SOURCE HEAT PUMP

WWHP WATER TO WATER HEAT PUMP

YH YARD HYDRANT

A COMPRESSED AIR

AC AIR COMPRESSOR

AD AIR DOOR

AFCV AUTO FLOW CONTROL VALVE

AHU AIR HANDLING UNIT

AMP AMPERE

APD AIR PRESSURE DROP

AS AIR SEPARATOR

AV ACID VENT

AW ACID WASTE

B BOILER

BC BLOWER COIL

BD BIDET

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BHP BRAKE HORSEPOWER

BLKG BLOCKING

BLV BALANCING VALVE

BT BATHTUB

BV BALL VALVE

BW BEDPAN WASHER

CH CHILLER

CC COOLING COIL

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CUH CABINET HEATER

CI CAST IRON

CMU COMBINATION UNITS

CR CONDENSER WATER RETURN

CRAC COMPUTER ROOM AIR

CONDITIONER

CS CONDENSER WATER SUPPLY

CSS CLINICAL SERVICE SINKS

CT COOLING TOWER

CU CONDENSING UNIT - SPLIT SYSTEM

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

DB DRY-BULB TEMPERATURE

DCW DOMESTIC COLD WATER

DEG DEGREE

DF DRINKING FOUNTAIN

DGCO DOUBLE GRADE CLEANOUT

DH EMERGENCY DRENCH HOSES

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER

RECIRCULATING

DI DEIONIZED WATER

DOAS DEDICATED OUTDOOR AIR SYSTEM

DS DISTILLED WATER

DSA DUCT SOUND ATTENUATORS

DSCW DOMESTIC SOFT COLD WATER

DSHW DOMESTIC SOFT HOT WATER

DSHWR DOMESTIC SOFT HOT WATER

RECIRCULATING

DST DOMESTIC STORAGE TANK

DTW DOMESTIC TEPID WATER

DTWR DOMESTIC TEPID WATER

RECIRCULATING

EA. EACH

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDH ELECTRIC DUCT HEATER

EEW EMERGENCY EYE WASH

EEWS EMERGENCY EYE

WASH/SHOWER

EF EXHAUST FAN

EFF EFFICIENCY

EFW EMERGENCY FACE WASH

EH EXHAUST HOOD

ERV ENERGY RECOVERY

VENTILATOR

ES EMERGENCY SHOWER

ESP EXTERNAL STATIC PRESSURE

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER

TEMPERATURE

ET EXPANSION TANK

F FIRE SUPPRESSION PIPING

F-_ FURNACE

FCO FLOOR CLEANOUT

FC FLUID COOLER

FCU FAN COIL UNIT

FD FIRE DAMPER

FLA FULL LOAD AMPS

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOOR SINK

FSD FIRE/SMOKE DAMPER

FT FINNED TUBE

G GAS

GCWR GLYCOL CHILLED

WATER RETURN

GCWS GLYCOL CHILLED

WATER SUPPLY

GD GARBAGE DISPOSAL

GDH GAS DUCT HEATER

GHCR GLYCOL HOT/CHILLED

WATER RETURN

GHCS GLYCOL HOT/CHILLED

WATER SUPPLY

GHWR GLYCOL HOT WATER RETURN

GHWS GLYCOL HOT WATER SUPPLY

GI GREASE INTERCEPTOR

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GV GAS VENT

GWH GAS WATER HEATER

HB HOSE BIBB

HC HEATING COIL

HCR HOT/CHILLED WATER RETURN

HCS HOT/CHILLED WATER SUPPLY

ACC AIR COOLED CONDENSER

ACCU AIR COOLED CONDENSING UNIT

ASHP AIR SOURCE HEAT PUMP

ARU AIR ROTATION UNIT

OI OIL INTERCEPTOR

SOI SAND OIL INTERCEPTOR

DSS DUCTLESS SPLIT SYSTEM

SP SUMP PUMP

OST OVERFLOW STORM WATER

WMB WASHING MACHINE BOX

OB OUTLET BOX

RH ROOF HYDRANT

H HUMIDIFIER

DHWP DOMESTIC HOT WATER

RECIRCULATING PUMP

DWET DOMESTIC WATER EXPANSION

TANK

HP HORSEPOWER

HPR HIGH PRESSURE RETURN

HPS HIGH PRESURE STEAM

HRC HEAT RECOVERY COIL

HWR HOT WATER RETURN (HEATING)

HWS HOT WATER SUPPLY (HEATING)

HX HEAT EXCHANGER

HY HYDRANTS

HP-_ HEAT PUMP

HVLS HIGH VOLUME LOW SPEED

IH INTAKE HOOD

IRH INFRARED RADIANT HEATER

KH KITCHEN HOOD

KW KILOWATT

KWH KILOWATT HOURS

L LAVATORY

LAT LEAVING AIR TEMPERATURE

LPR LOW PRESSURE RETURN

LPG LIQUIFIED PETROLEUM GAS

LPS LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LS LAUNDRY SINK

LV LOUVER

LWT LEAVING WATER TEMPERATURE

PROJECT MECHANICAL REFERENCED DEMOLITION NOTES PROJECT MECHANICAL REFERENCED NOTES

M 00 MECHANICAL INFO SHEET

M 01 SHEET SPECIFICATIONS - MECHANICAL

M 02 SHEET SPECIFICATIONS - MECHANICAL

M101 DEMOLITION FLOOR PLAN - MECHANICAL

M102 FLOOR PLAN - MECHANICAL

M501 SCHEDULE - MECHANICAL

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

256385

80054

C U s e rs \t ja m e s o n

\D o c u m e n ts

\0

H O

M E

M

E C

H R tj a m e s o n

V L

C Q

K .r v t

TMJ

TMJ

JEK

04/11/2023

07310.035

M 00

MECHANICAL INFO SHEET

07310035- 5- M 00 MECHANICAL INFO SHEET

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

DATE INITIAL

4/11/23

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

256385

80054

C U s e rs \t ja m e s o n

\D o c u m e n ts

\0

H O

M E

M

E C

H R tj a m e s o n

V L

C Q

K .r v t

TMJ

TMJ

JEK

04/11/2023

07310.035

M 01

SHEET SPECIFICATIONS -

MECHANICAL

07310035- 5- M 01 SHEET SPECIFICATIONS - MECHANICAL

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

256385

80054

C U s e rs \t ja m e s o n

\D o c u m e n ts

\0

H O

M E

M

E C

H R tj a m e s o n

V L

C Q

K .r v t

TMJ

TMJ

JEK

04/11/2023

07310.035

M 02

SHEET SPECIFICATIONS -

MECHANICAL

07310035- 5- M 02 SHEET SPECIFICATIONS - MECHANICAL

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

T

LIVING ROOM

BED ROOM

BED ROOM

BED ROOM

BATHROOM

DINING

GARAGE

UTILITY ROOM

KITCHEN

HALL

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

256385

80054

C U s e rs \t ja m e s o n

\D o c u m e n ts

\0

H O

M E

M

E C

H R tj a m e s o n

V L

C Q

K .r v t

TMJ

TMJ

JEK

04/11/2023

07310.035

M101

DEMOLITION FLOOR PLAN -

MECHANICAL

07310035- 5- M101 DEMOLITION FLOOR PLAN - MECHANICAL

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

REF. DEMO NOTES ( ):X

1 REMOVE EXISTING CONDENSING UNIT AND ASSOCIATED REFRIGERANT

LINE SET. PREPARE FOR INSTALLATION OF NEW CONDENSING UNIT AND

REFRIGERANT LINES.

2 REMOVE EXISTING ELECTRIC FURNACE AND SUPPLY DUCT INTO CEILING

AS SHOWN. PREPARE FOR INSTALLATION OF NEW FURNACE.

3 REMOVAL OF EXISTING WATER HEATER. PREPARE FOR INSTALLATION OF

NEW WATER HEATER.

4 REMOVE BRANCH OF DUCTWORK ASSOCIATED WITH EXISTING GRILLE.

PREPARE DUCT MAIN FOR NEW DUCT CONNECTION.

5 REMOVE EXISTING ENERGY RECOVERY VENTILATOR AND ASSOCIATED

AIR TRANSFER DUCTWORK. PATCH ALL RESULTING HOLES AS

NECESSARY.

6 REMOVE EXISTING REGISTER AND ASSOCIATED DUCTWORK. PATCH HOLE

IN WALL.

7 REMOVE DRYER VENT AND SEAL WALL PENETRATION AS REQUIRED.

SCALE: 1/4" = 1'-0"

FIRST FLOOR DEMOLITION PLAN - MECHANICAL

NORTH

TF-1

CU-1

12x10 SA

22x20 SA

6x10 S-1

(TYP. 3)

10x6 SA

10x6 SA

10x6 SA

10x6 SA

10x6 R-1

(TYP. 2)

10x8 RA

10x6 RA

10x6 RA

RL

RS

EF-1

6 Ø EA

4 Ø EA

LIVING ROOM

100 BED ROOM

BED ROOM

DINING

GARAGE

109 KITCHEN

106UTILITY ROOM

BATHROOM

HC BATHROOM

HALL

6x8 S-1

6x10 S-1

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

256385

80054

C U s e rs \t ja m e s o n

\D o c u m e n ts

\0

H O

M E

M

E C

H R tj a m e s o n

V L

C Q

K .r v t

TMJ

TMJ

JEK

04/11/2023

07310.035

M102

FLOOR PLAN - MECHANICAL

07310035- 5- M102 FLOOR PLAN - MECHANICAL

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

REF. NOTES ( ):X

1 VERIFY LOCATION OF EXISTING SUPPLY DUCT. CONNECT NEW SUPPLY

DUCT AS SHOWN.

2 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S

REQUIREMENTS AND THE SPECIFICATIONS. ALL PIPE PENETRATIONS

SHALL BE DONE VIA A CORE DRILL TO BE NEAT AND CLEAN.

3 CONNECT NEW AIR HANDLER UNIT EXISTING RETURN DUCT AS NEEDED.

INSTALL NEW SECTION OF MAIN SUPPLY DUCT AND CONNECT NEW

SUPPLY BRANCH TO MAIN DUCT AS SHOWN.

4 ROUTE HEAT PUMP CONDENSATE TO EXISTING CONDENSATE DRAIN.

5 ROUTE BATHROOM EXHAUST THROUGH ROOF AS SHOWN. CAP WITH

GOOSENECK FITTING AND SEAL ROOF PENETRATION AS REQUIRED.

6 ROUTE ALUMINUM DRYER DUCT UP THROUGH ROOF AS SHOWN. CAP

WITH GOOSENECK VENT FITTING AND SEAL ROOF PENETRATION AS

REQUIRED.

7 EXISTING RETURN AND ASSOCIATED RETURN GRILLE TO REMAIN.

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - MECHANICAL

NORTH

LONG FLAT SPANS ON OVAL DUCT HAVE A TENDENCY TO SAG. OVAL

DUCT

WITH A MAJOR AXIS OF 42 INCHES OR MORE SHALL BE REINFORCED PER

SMACNA HVAC DUCT CONSTRUCTION STANDARDS TYPE 2.

CHANNEL OR ANGLE

HANGER CLAMP

OR BAND

BOLT

STRAP

OR

ANGLE

ROD (TYP)

DUCT (TYP)

ANGLE (TYP)

NUT (TYP)

NOTES:

1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.

2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO DUCTWORK.

3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCT AS ROUND DUCT TENDS TO DEFORM ON TRAPEZE HANGERS.

4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINTAIN THE INTEGRITY OF THE VAPOR BARRIER.

5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALLY WRAPPED.

SHEET METAL 90° ELBOW

DIFFUSER NECK

TRANSITION

(AS REQUIRED)

CEILING

SUPPLY DUCT-

SEE PLANS FOR

SIZES

SUPPLY DIFFUSER

DUCT INSULATION

FLEX DUCT

INSULATE BACKPANPLASTER FRAME

DAMPER

STANDOFF

DAMPER

QUADRANT LOCK

NOTE:

ALL TAPS TO AIR TERMINALS REQUIRING BALANCING AT DUCT SHALL

BE MADE USING A HIGH EFFICIENCY TAKEOFF.

NOTES:

1/2"x1/2" CHAMFER STRIP

REMOVE AND CAULK.

6x6 - 10/10 WWF

#4 BENT RE-BAR

AT EACH CORNER

DRILL 3/4"Ø HOLE IN FLOOR SLAB

AND GROUT IN REBAR.

1. INSTALL NEW HOUSEKEEPING PADS AS INDICATED ON PLANS. VERIFY DIMENSIONS

WITH EQUIPMENT SIZES.

2. VERIFY SIZE AND LOCATION OF EQUIPMENT ANCHOR BOLTS.

3. PROVIDE DOWEL RODS 18" ON CENTER AROUND FULL PERIMETER OF PAD IF

LONG DIMENSION IS GREATER THAN 72".

4"

/256"

3-1/2"

FLOOR

#4 BARS @12" O.C. EACH WAY

CONCRETE BASE

1" CHAMFER

.6

LENGTH AND WIDTH

TO SUIT UNIT FURNISHED

GRADE

METAL SCREEN FRAME

ANGLE IRON

REINFORCING

WHERE REQUIRED

SCREEN

BOLT

STANDARD DUCT CONSTRUCTION

(WATERTIGHT SEAMS)

ROOF DECK

ROOFING

DUCT SIZE

SPECIFIED

S N

O W

D E

P T

H

M

IN

O R

A B

O V

E L

O C

A L

D U C

T SIZE

+ 25%

ANGLE RIVETED OR

SPOT WELDED AS

REQUIRED

1/2" SCREEN - DO NOT INCLUDE

SCREEN FOR DRYER

APPLICATIONS

.0

S T

E P

C A

N T

ROOF

INSULATION

COUNTER FLASHING

WOOD NAILER

RIGID INSULATION

HEAVY GA.

GALV. STEEL

ROOFING

135° MIN.

M

IN

M

IN

R

R=W/2

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

256385

80054

C U s e rs \t ja m e s o n

\D o c u m e n ts

\0

H O

M E

M

E C

H R tj a m e s o n

V L

C Q

K .r v t

TMJ

TMJ

JEK

04/11/2023

07310.035

M501

SCHEDULE - MECHANICAL

07310035- 5- M501 SCHEDULE - MECHANICAL

REHAB INTERIOR & EXTERIOR ON QUARTERS #3

HOMESTEAD NATIONAL MONUMENT OF AMERICA

8523 NE-4

BEATRICE, NE 68310

R-1 GRILLE SEE PLANS SEE PLANS WHITE 0.1 30 PRICE 500 ---

S-1 GRILLE SEE PLANS SEE PLANS WHITE 0.1 30 PRICE 540 ---

MARK TYPE FACE SIZE (IN.)

NECK SIZE

(IN.) FINISH

MAX PD (IN

WG)

MAX NC AT

PD SHOWN

BASIS OF

DESIGN REMARKS

DIFFUSER, REGISTER AND GRILLE SCHEDULE

NOTES: 1. PROVIDE WITH REFRIGERANT LINESET, SIZED PER MANUFACTURER REQUIREMENTS. PROVIDE LONG LINE LENGTH ACCESSORIES WHEN MANUFACTURER STANDARD LENGTHS ARE EXCEEDED.

F-1 UTILITY ROOM 1500 80 67 42400 33700 ELECTRIC 240 1 14.4 0.5 120 1 60 TRANE GAM5A0C42M31SA CU-1 95.0 R-410A 24.0 40.0 230 1 60 14.6 TRANE 4TWR4042 1

DB WB

EAT (°F)

TOTAL MBH SENS. MBH

AIRSIDE DATA MIN CAP

FUEL TYPE VOLTS PH

OUTPUT

(KW) HP VOLTS PH HZ

MINIMUM

CIRCUIT

AMPS

MAXIMUM

FUSE AMPS VOLTS PH HZ

COOLING COIL DATA HEATING DATA MOTOR DATA

FURNACE BASIS OF DESIGN MARK

AMB TEMP

(°F)

REFER

TYPE

ELECTRICAL DATA

SEER

CONDENSING UNIT

BASIS OF DESIGNMARK LOCATION CFM

FURNACE DATA CONDENSING UNIT DATA

REMARKS

ELECTRIC FURNACE & CONDENSING UNIT, SPLIT SYSTEM SCHEDULE

SCALE: NOT TO SCALE

DUCT HANGER DETAIL

SCALE: NOT TO SCALE

SUPPLY DIFFUSER/ DUCT CONNECTION DETAIL

SCALE: NOT TO SCALE

HIGH EFFICIENCY TAKEOFF DETAIL

SCALE: NOT TO SCALE

HOUSEKEEPING PAD DETAIL

SCALE: NOT TO SCALE

EXTERIOR EQUIPMENT PAD DETAIL

EF-1 RESTROOM CENTRIFUGAL 50 0.5 DIRECT 586 30 950 30W 115 1 60 GREENHECK SP-B110ES ---

TYPE CFM

EXT SP

(IN WG) DRIVE RPM

MAX

SONES RPM POWER VOLTS PH HZMARK SERVES

FAN DATA ELECTRICAL DATA

MANUFACTURER AND MODEL

NUMBER REMARKS

FAN SCHEDULE

SCALE: 6" = 1'-0"

GOOSENECK AND COUNTER FLASHING DETAIL

A. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET

OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK.

CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO

FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.

B. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL

FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER.

COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER

TRADES AFFECTED.

C. ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT

ANGLES AND PARALLEL TO BUILDING WALLS UNLESS OTHERWISE

INDICATED.

D. ALL PLUMBING INSTALLATION SHALL BE IN ACCORDANCE WITH THE

REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.

A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE

ORIGINAL DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD

VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE

APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,

RELOCATED, OR SALVAGED ARE SHOWN AS SOLID, FULL-TONE

LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND

ARE SHOWN AS HALF-TONE.

B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS

LISTED BELOW OR HERE-IN. THE CONTRACTOR SHALL

COORDINATE ALL REQUIRED RENOVATION AND NEW

CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE

TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED

BELOW.

C. THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING

EQUIPMENT FROM FINISHED AREAS AND THROUGH WEATHER

BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL PLANS

AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING

TO ENSURE PROPER PATCHING AND REPAIR IS MADE TO THE

BUILDING.

D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION

AND REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS,

EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT, INSTALL, OR

ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER

HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.

E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED

SHALL BE CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT

DAMAGE AND STORED OR REINSTALLED ON THE SITE AS DIRECTED.

REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF

THE OWNER.

F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND

CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO

MECHANICAL REMOVALS.

G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,

MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED

PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT

BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL

IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT

THE CONDITION TO THE OWNER AND ARCHITECT IN…