This document provides details for a federal solicitation to rehabilitate Quarters 3. The solicitation number is 140P6023B0007 issued by the Department of the Interior National Park Service Midwest Region. It seeks to rehabilitate a residential property located within a National Park by replacing all windows, doors, siding, and roofing along with electrical, plumbing and HVAC system upgrades. Bids are due by April 15th, 2023 with award notice expected on or around May 1st. The attached file contains 29 pages of detailed construction drawings specifying the scope of work.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
�SPRINKLER PROTECTION
NOT REQUIRED IN GARAGED
ATTACHED TO DWELLING
UNIT PER NFPA 13D.
GARAGE
U!19J
SEE SITE PLAN SHEET
FP100 FOR CONTINUATION
l
I
�I
CONTRACTOR SHALL BEGIN AT
DISCHARGE OF EXISTING REDUCED
PRESSURE BACKFLOW PREVENTER.
PROVIDE NEW WATERFLOW SWITCH,
TEST AND DRAIN ASSEMBLY, PRESSURE
RELIEVE, AND EXPANSION TANK FOR
ANTIFREEZE SYSTEM.
jJ I
UTILITY ROOM
_J_Q_8
I,¾'
' D-, n1¼
ITT
lli
DINING
I till
[GE
1¼'
1'' 1-6½
9'-0"
KITCHEN
[_j_Q!U
I¼" 5 6 7 5 4 g 10 10½
1'' 5-4
4'-1"
11,r--------,f b
I \
I" 5-4
LIVING ROOM
0 I
SPRINKLER PROTECTION NOT
REQUIRED IN CLOSET SMALLER
THAN 55 SQ FT IN DWELLING
UNIT PER NFPA 130.
FIRE SPRINKLER PLAN
SCALE: 1/8" = 1'-0"
l 1-2023
FIN. FLOOR ELEV. = 100'-0"
ENGINEER OF RECORD:
WILLIAM B. SMITH, PE
LICENSE NO. E-1491�
CODE CONSULTANTS
PROFESSIONAL ENGINEERS, PC
2043 WOODLAND PKWY, SUITE 300
ST. LOUIS, MU 63146-4235
COIIPORATE CfRTIF!CATE OF AUTHORITY
NO. 10188652
�o ™ I
2043 WOODLAND PKWY, SUITE 300
ST. LOUIS, MISSOURI 63146-4235
314-991-2633 www.codeconsullants.com
LAYOUT IS CONCEPTUAL ONLY.
CONTRACTOR SHALL VERIFY ACTUAL
LAYOUT UPON INSPECTION AND REMOVAL
OF EXISTING SYSTEM. COORDINATE WITH
EXISTING SPRINKLER PLACEMENT WHERE
POSSIBLE WHEN INSTALLING NEW
SPRINKLERS AND PIPE ROUTING. VERIFY
FINAL LAYOUT WITH HYDRAULIC
CALCULATIONS.
I
SPRINKLER PROTECTION NOT
REQUIRED IN BATHROOM
SMALLER THAN 55 SQ FT IN
DWELLING UNIT PER NFPA 130.
C]
BEDROOM
10�7
BATHROOY
1-05
6'-0" 0 ._ _ _ _ ____ ·J,roo:, ========r
- I " I¼"
' '7
1"1
BEDROOM
1___1_Q_J_I
8'-5"
HC BATHROOM
U2lJ
1" GLOBE VALVE WITH 3/4"
HOSE END ADAPTER
(MANUAL AIR VENT AND
ANTIFREEZE TEST PORT) 6'-1"
NATIONAL
PARK
SERVICE
O<?artmcnt ot •�• lnlcrior
I� SPRINKLER PROTECTION NOT
I REQUIRED IN CLOSET SMALLER
THAN 55 SQ FT IN DWELLING
UNIT PER NFPA 130.
SCH::MM::R
Dtiign with Pu,_,,. Build ...th C,,,,fidem,,_
1044 North 115th Street I Suite 300 Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED
DATE I INITIAL
PREPARED
JLK
DESIGNED
JLK
DRAWN
JLK
CHECKED
04/11/2023
DATE
SYMBOL KEY
� - - ----( EXISTING UNDERGROUND WATER MAIN
,_, ___ ,, _' NEW PIPING
ff
RECOMMENDED CENTER LINE ELEVATION OF PIPE AF.F. AND/OR CENTER
LINE ELEVATION OF PIPE FROM TOP OF JOIST
--I, CJ
NOTE
GLOBE VALVE
RISER
FIRE DEPARTMENT CONNECTION
RISE FROM LEFT TO RIGHT ANO DROP FROM RIGHT TO LEFT
CAPPED PIPE
PLUGGED OUTLET
HYDRAULIC REFERENCE POINT
CENTER LINE OF SPRINKLER: ALIGN WITH LIGHTS AND/OR OTHER
SPRINKLERS; COORDINATE WITH OTHER TRADES.
PIPE HANGER
TRAPEZE HANGER
ZONE BOUNDARY LINE
AREA OF DEMOLITION. REMOVE ALL PIPING AND SPRINKLER
COMPONENTS NOT INTENDED FOR REUSE
STRUCTURAL SHOWN FOR REFERENCE ONLY, VERIFY ACTUAL STRUCTURAL LOCATIONS.
SPRINKLER LEGEND
SYMBOL SPRINKLER TYPE TEMP. K FINISH RESP. QTY.
• WHITE EXTENDED COVERAGE RESIDENTIAL ORO PENDENT WITH RECESSED ESCUTCHEON 4.9 WHITE QR 45
)8( EXISTING SPRINKLER TO BE DEMOLISHED
TITLE OF SHEET
FLOOR PLAN
FIRE PROTECTION
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
ARCH/ENG PROJ #
07310.035
SUB SHEET NO.
DRAWING NO.
80054
PMIS / PKG. NO.
256385
SHEET
7 OF29
SUB SHEET NO.
FP102
SPECIFICATIONS 211313 FIRE SPRINKLER SYSTEMS
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL
AND SUPPLEMENTARY CONDITIONS ANO DIVISION 01 SPECIFICATION SECTIONS,
APPLY TO THIS SECTION.
B. FURNISH ALL LABOR, MATERIALS, TOOLS, EQUIPMENT AND RELATED ITEMS
REQUIRED FOR THE COMPLETE DESIGN AND INSTALLATION OF AUTOMATIC
SPRINKLER SYSTEM.
C. ALL AREAS OF THE BUILDING SHALL BE PROTECTED BY WET AUTOMATIC FIRE
SPRINKLERS. THE SYSTEM SHALL BE HYDRAULICALLY CALCULATED. DENSITY
SHALL SE IN ACCORDANCE WITH NFPA 13D UNLESS SPECIAL CIRCUMSTANCES
SUCH AS STACKING HEIGHTS OR MATERIALS TO BE STORED CAUSE OTHER
CHAPTERS OF THE NFPA TO BE REQUIRED. FOLLOW THOSE CHAPTERS FOR THE
APPROPRIATE SPRINKLER REQUIREMENTS.
1.2 SUMMARY
A. SECTION INCLUDES:
1. PIPES, FITTINGS, AND SPECIALTIES.
2. HANGERS AND SLEEVES.
3. FIRE PROTECTION VALVES:
a. ELECTRONICALLY SUPERVISED INDICATING CONTROL VALVES.
b. CHECK VALVES.
c. GLOBE VALVES.
d. BALL VALVES.
e. ANGLE VALVES.
4. TEST CONNECTIONS, MAIN DRAINS AND AUXILIARY DRAINS.
5. SPRINKLERS,
6. ALARM DEVICES.
7. PRESSURE GAGES.
8. SIGNS.
9. CORROSION MANAGEMENT PRODUCTS.
1.3 DESCRIPTION OF WORK
A. PROVIDE ALL REQUIRED LABOR, MATERIALS, EQUIPMENT, TESTING AND
SERVICES NECESSARY FOR A COMPLETE AND OPERATIONAL WET PIPE FIRE
PROTECTION SYSTEM FOR THE BUILDING AS HEREINAFTER DESCRIBED AND AS
SHOWN ON THE ENGINEERING DRAWINGS.
B. WORK SHALL BEGIN AT THE FLANGE LOCATED AT THE BACKFLOW PREVENTER
INSIDE THE BUILDING AND SHALL INCLUDE THE FOLLOWING:
1. ANTI-FREEZE (WET PIPE) FIRE SPRINKLER SYSTEM FOR THE ENTIRE
BUILDING.
2. COORDINATION OF WORK AND SCHEDULES WITH OTHER TRADES.
C. IT IS INTENDED THAT THE ENGINEERING DRAWINGS AND SPECIFICATION SHALL
DESCRIBE AND PROVIDE FOR A WORKING INSTALLATION COMPLETE IN EVERY
DETAIL AND ALL ITEMS NECESSARY FOR SUCH COMPLETE INSTALLATION SHALL
BE PROVIDED WHETHER OR NOT SPECIFICALLY MENTIONED HEREIN OR SHOWN
ON THE ENGINEERING DRAWINGS,
1.4 DEFINITIONS
A. STANDARD PRESSURE SPRINKLER PIPING: LISTED FOR 175 PSI MINIMUM
WORKING PRESSURE.
1.5 SYSTEM DESCRIPTION
A. FIRE SPRINKLER SYSTEM DESIGN CRITERIA SHALL BE STRICTLY PER THIS
SPECIFICATION.
B, FIRE SPRINKLER SYSTEM TO PROVIDE FIRE PROTECTION FOR THE ENTIRE
BUILDING.
C. INTERFACE FIRE SPRINKLER SYSTEM WITH BUILDING FIRE ALARM SYSTEMS.
D. RESIDENCE (NFPA 13D - RESIDENTIAL DWELLING UNIT - ANTIFREEZE (WET PIPE)
FIRE SPRINKLER SYSTEM):
DENSITY - 0.05 GPM/SQ FT
OPERATING AREA - ALL SPRINKLERS WITHIN A COMPARTMENT. UP TO A
MAXIMUM OF TWO. (FLAT SMOOTH CEILINGS LESS THAN 24 FT IN HEIGHT).
TEMPERATURE CLASSIFICATION / NOMINAL K-FACTOR I RESPONSE TYPE -
ORD 1 4.9 / QR
DURATION: 10 MINUTES
COMMON SUPPLY ALLOWANCE: 5 GPM SHALL BE ADDED TO COMPENSATE
FOR DOMESTIC DEMAND
E. SPRINKLER SPACING SHALL BE AS SHOWN ON THE ENGINEERING DRAWINGS.
1. HARD CEILINGS - LOCATE SPRINKLERS IN ACCORDANCE WITH THE
ENGINEERING DRAWINGS. SPRINKLERS SHALL BE IN LINE WITH LIGHT
FIXTURES AND OTHER SPRINKLERS WHERE INDICATED ON THE DRAWINGS.
COORDINATE CLOSELY WITH THE ELECTRICAL CONTRACTOR.
2. UNFINISHED AREAS - LOCATE SPRINKLERS AS SHOWN ON THE ENGINEERING
DRAWINGS.
F. PROVIDE ALL NECESSARY OFFSETS, RAISES OR DROPS IN MAIN OR BRANCH LINE
PIPING AND AUXILIARY DRAINS REQUIRED BY BUILDING CONDITIONS WHETHER
OR NOT SHOWN ON THE ENGINEERING DRAWINGS.
G. EXAMINE THE JOB CONDITIONS AND VERIFY ALL MEASUREMENTS, DISTANCES,
ELEVATIONS, CLEARANCES, PIPE SIZES, ETC.
H. IT IS UNDERSTOOD, UNLESS SPECIFICALLY INDICATED OTHERWISE, THAT THE
PIPE SIZES AS SHOWN ON THE ENGINEERING DRAWINGS WILL BE USED,
1.6 PERFORMANCE REQUIREMENTS
A. STANDARD PRESSURE PIPING SYSTEM COMPONENT: LISTED FOR 175 PSI
MINIMUM WORKING PRESSURE.
B. WATER SUPPLY:
THE AVAILABLE WATER SUPPLY WAS NOT AVAILABLE AT THE TIME OF
CONSTRUCTION DOCUMENT ISSUE. UPON AWARD, THE SUCCESSFUL FIRE
SPRINKLER CONTRACTOR SHALL PERFORM A NFPA 291 COMPLIANT WATERFLOW
TEST ANO FORWARD A REPORT OF THE TEST RESULTS TO CODE CONSULTANTS,
INC, THE OWNER'S REPRESENTATIVE, AND ARCHITECT. A MINIMUM SAFETY
FACTOR OF 10% OF THE STATIC PRESSURE SHALL BE APPLIED TO BOTH THE
STATIC AND RESIDUAL PRESSURES FOR THE PURPOSE OF HYDRAULIC
CALCULATIONS. PROVIDE LOCATION AND ELEVATION DIFFERENCES BETVVEEN
THE FLOW TEST AND THE FINISHED FLOOR OF PROJECT SPACE.
THE FIRE PROTECTION WATER SUPPLY WILL BE PROVIDED BY COMBINATION
DOMESTIC/FIRE WATER SERVICE FEED FROM THE PUBLIC UTILITY. THE WATER
SERVICE IS 1-112" UNDERGROUND WITH A 1-1/4' REDUCED PRESSURE BACKFLOW
PREVENTER (AMES 40006).
FIRE PROTECTION WATER SUPPLY HAS BEEN ASSUMED BASED ON EXISTING MAIN
DRAIN TEST OBTAINED FROM AN ANNUAL TEST REPORT. THE STATIC PRESSURE
AVAILABLE IS 60 PSI PERFORMED ON 07/2212021 BY CONTINENTAL FIRE SPRINKLER
COMPANY. THE WATER SUPPLY SHALL BE CONSIDERED EFFECTIVE AT THE
DISCHARGE OF THE BACKFLOW PREVENTER. THE APPROXIMATE WATER SUPPLY
ELEVATION IS 3 FT ABOVE THE FINISH FLOOR.
ACTUAL STATIC:
ESTIMATED RESIDUAL:
ESTIMATED FLOW:
60 PSI
30 PSI
50 GPM
THE ABOVE WATER SUPPLY COORDINATES DO NOT INCLUDE THE REQUIRED 10%
OF THE STATIC PRESSURE SAFETY FACTOR THAT SHALL BE ENFORCED. THE
FOLLOWING WATER SUPPLY COORDINATES HAVE BEEN ADJUSTED -6 PSI FOR THE
REQUIRED SAFETY FACTOR.
DESIGN STATIC:
DESIGN RESIDUAL:
DESIGN FLOW:
1.7 SUBMITTAL$
54 PSI
24 PSI
50 GPM
A. THE ENGINEERING DRAWINGS HAVE BEEN PREPARED USING AUTOCAD. THE
HYDRAULIC CALCULATIONS HAVE BEEN PREPARED USING HYORACALC. THESE
DOCUMENTS WILL BE MADE AVAILABLE TO THE SUCCESSFUL FIRE SPRINKLER
CONTRACTOR IN EITHER ELECTRONIC FORM OR HARD COPY. UTILIZATION OF
THESE DOCUMENTS FOR THE DEVELOPMENT OF SHOP DRAWINGS AND
SUBMITTAL$ DOES NOT RELIEVE THE FIRE SPRINKLER CONTRACTOR FROM ANY
OF HIS RESPONSIBILITIES REQUIRED HEREIN.
B. SUBMITTAL$ SHALL BE IN ACCORDANCE WITH REQUIREMENTS OF THE GENERAL
CONDITIONS OF THE CONTRACT.
C. PRODUCT LITERATURE: FOR ALL WET PIPE SPRINKLER SYSTEM EQUIPMENT.
1. LITERATURE SHALL CLEARLY IDENTIFY EXACTLY WHAT COMPONENTS ARE
BEING PROVIDED AND SHALL INCLUDE: FINISH, SIZE, TYPE, ETC. LITERATURE
WHICH IS NOT CLEARLY IDENTIFIED WILL BE REJECTED.
D. SHOP DRAWINGS:
1. DRAWINGS MUST BE COMPREHENSIVE OF ENTIRE PROJECT,
DEMONSTRATING COORDINATION WITH OTHER DISCIPLINES, COMPLETE IN
ALL DETAIL AND THE SAME SCALE AS THE ENGINEERING DRAWINGS.
2. HYDRAULIC CALCULATIONS (CALCULATIONS SHALL INCLUDE PEAKING
INFORMATION),
3. NPS REGIONAL FIRE MARSHAL (AHJ) WILL REVIEW THIS SUBMITTAL FOR
CONSISTENCY WITH CONTRACT DOCUMENTS AND FOR APPROVAL.
E. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR RESPONDING.
IN WRITING, TO ANY COMMENTS FROM THE AHJ WITHIN TEN (10) WORKING DAYS
AFTER THE RECEIPT OF THEIR COMMENTS. COPIES OF THE RESPONSE SHALL BE
SENT TO THE GENERAL CONTRACTOR.
E. PROVIDE AS-BUILT DOCUMENTS IN ACCORDANCE WITH REQUIREMENTS OF THE
GENERAL CONDITIONS OF THE CONTRACT.
E. FIELD TEST REPORTS AND CERTIFICATES: INDICATE TEST RESULTS FOR
COMPLIANCE WITH PERFORMANCE REQUIREMENTS AND AS DESCRIBED IN NFPA
13. INCLUDE "CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR
ABOVEGROUND PIPING."
F. PROVIDE OPERATING ANO MAINTENANCE INSTRUCTIONS TO THE OWNER IN
ACCORDANCE WITH REQUIREMENTS OF THE GENERAL CONDITIONS OF THE
CONTRACT AND NFPA 130.
1.8 QUALITY ASSURANCE
A INSTALLER QUALIFICATIONS:
1. INSTALLER'S RESPONSIBILITIES INCLUDE PREPARING SHOP DRAWING
SUBMITTAL, FABRICATING, AND INSTALLING SPRINKLER SYSTEMS. BASE
CALCULATIONS ON WATER SUPPLY COORDINATES PROVIDED HEREIN.
a. INSTALLER SHALL BE STATE AND LOCALLY LICENSED.
b. INSTALLER SHALL BE MINIMALLY NICET LEVEL Ill OR A PROFESSIONAL
ENGINEER
B. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED
AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR
INTENDED LOCATION AND APPLICATION.
C. REFERENCES: FIRE SPRINKLER SYSTEM EQUIPMENT, SPECIAL TIES,
ACCESSORIES, INSTALLATION, AND TESTING SHALL COMPLY WITH ALL
APPLICABLE CODES AND REFERENCED DESIGN STANDARDS:
1. 2021 INTERNATIONAL BUILDING CODE
2. 2021 INTERNATIONAL FIRE CODE
3. NFPA 130, SPRINKLER SYSTEMS- 2022 EDITION.
D. EQUIPMENT AND COMPONENTS SHALL BE UL LISTED FOR FIRE PROTECTION
SYSTEMS INSTALLATION.
E. ALL FIRE SPRINKLER SYSTEM COMPONENTS SHALL BE INSTALLED FREE OF ANY
RUST, CORROSION OR VISIBLE DAMAGE. ALL ITEMS NOT COMPLYING WITH THIS
REQUIREMENT SHALL BE REPLACED WITHOUT COST TO THE OWNER.
1.9 COORDINATION
A. COORDINATE LAYOUT AND INSTALLATION OF SPRINKLERS WITH OTHER
CONSTRUCTION THAT PENETRATES CEILINGS, INCLUDING LIGHT FIXTURES, HVAC
EQUIPMENT, ANO PARTITION ASSEMBLIES.
B. COORDINATE INSTALLATION OF SYSTEM WITH ALL OTHER DISCIPLINES,
1.10 EXTRA MATERIALS
A. FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED AND THAT ARE
PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED WITH
LABELS DESCRIBING CONTENTS.
B. PROVIDE AT THE RISER ONE (1) TWELVE (12) HEAD SPARE SPRINKLER CABINETS
STOCKED WITH SPRINKLERS ANO ESCUTCHEON ASSEMBLIES PROPORTIONATE
TO THOSE PROVIDED IN THE BUILDING AND ALL NECESSARY SPRINKLER
WRENCHES AS REQUIRED BY NFPA 13D,
1.11 REGULATORY REQUIREMENTS
A. THE FIRE SPRINKLER CONTRACTOR SHALL NOT PURSUE ANY APPROVALS OR
INTERPRETATIONS OF THE CONTRACT DOCUMENTS EXCEPT THROUGH NPS
REGIONAL FIRE MARSHAL.
B. SPRINKLER PIPING SHALL NOT BE CONCEALED WHERE IT IS INACCESSIBLE
UNLESS IT IS FIRST INSPECTED AND ACCEPTED BY A REPRESENTATIVE OF THE
AUTHORITY HAVING JURISDICTION.
C. ANY WORK PERFORMED PRIOR TO THE SATISFACTORY REVIEW BY AND
APPROVAL BY THE AUTHORITY HAVING JURISDICTION, WILL BE SOLELY AT THE
FIRE SPRINKLER CONTRACTOR'S RISK.
0. THE SYSTEM WILL NOT BE ACCEPTABLE UNTIL FINAL TESTING AND RECEIPT OF
THE CONTRACTOR'S MATERIAL AND TEST CERTIFICATE HAS BEEN OBTAINED.
1.12 WARRANTY
A. REPAIR ALL DEFECTIVE WORKMANSHIP OR REPLACE ALL DEFECTIVE MATERIALS
FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER.
WORKMANSHIP OR EQUIPMENT FOUND TO BE DEFECTIVE DURING THAT PERIOD
SHALL BE REPLACED WITHOUT COST TO THE OWNER
PART 2- PRODUCTS
2.1 PIPE AND FITTINGS
A. PER LOCAL REQUIREMENTS AND NFPA 130. ALL PIPE SHALL HAVE A CORROSION
RESISTANCE RATIO (CRR) EQUAL TO OR GREATER THAN 1.00. REFER TO THE
CURRENT UL FIRE PROTECTION EQUIPMENT DIRECTORY - STEEL SPRINKLER PIPE
FOR ACCEPTABLE MANUFACTURERS, SIZES, AND JOINING METHODS.
B. THE ENGINEER'S HYDRAULIC CALCULATIONS ANTICIPATES THAT ALL GROOVED
WET PIPE SYSTEM RISERS, FEED AND CROSS MAINS, AND BRANCH LINES SHALL
HAVE HYDRAULIC CHARACTERISTICS EQUAL TO OR GREATER THAN SCHEDULE 10
PIPE.
C. ALL THREADED PIPING SHALL BE SCHEDULE 40 PIPE.
0. ALL 1 IN. SHALL BE SCHEDULE 40 PIPE.
E. ALL PIPING IN DRY SYSTEMS SHALL BE SCHEDULE 40 PIPE.
F. FITTINGS SHALL BE SCREWED OR FLANGED BLACK CAST IRON OR APPROVED
EQUAL SUCH AS MECHANICAL, GROOVED OR WELDED CONNECTIONS,
G. PRESSURE RATING: 175 PSI MINIMUM.
2.2 JOINING OF PIPE AND FITTINGS
A. ALL PIPE SHALL BE JOINED IN ACCORDANCE WITH NFPA 13D AND
MANUFACTURERS RECOMMENDATIONS.
B. WHERE GROOVED FITTINGS AND COUPLINGS ARE USED TOGETHER THEY SHALL
BE OF THE SAME MANUFACTURER.
C. BUSHINGS SHALL NOT BE USED.
D. FLEXIBLE COUPLINGS SHALL BE IDENTIFIED ON THE SHOP DRAWINGS.
2.3 HANGERS
A. ALL HANGERS TO BE OF APPROVED MATERIALS AND SPACED IN ACCORDANCE
WITH NFPA 130 AND THE PIPING MANUFACTURER'S SPECIFICATIONS.
B. THE SECTION MODULUS REQUIRED BY NFPA 130 SHALL BE PROVIDED FOR ALL
TRAPEZE MEMBERS SUPPORTING PIPING.
2.4 LISTED FIRE PROTECTION VALVES
A. GENERAL REQUIREMENTS:
1. PRESSURE RATING: 175 PSI MINIMUM.
B, INDICATING BUTTERFLY VALVES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. GRUVLOCK.
b. NIBCO.
c. TYCO.
d. VICTAULIC.
e. VIKING.
2. BODY MATERIAL: CAST IRON.
3. SUPERVISORY SWITCH.
C. CHECK VALVES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. MILWAUKEE VALVE.
b. MUELLER CO.
c. NIBCO.
d. STOCKHAM.
e. TYCO.
f. UNITED BRASS WORKS.
g. VICTAULIC,
2. TYPE: SWING CHECK OR WAFER.
3. BODY MATERIAL: CAST IRON.
D. OS&Y GATE VALVES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. MILWAUKEE VALVE.
b. MUELLER CO.
c. NIBCO.
d. STOCKHAM.
e. VIKING.
2. BODY MATERIAL: CAST IRON.
3. SUPERVISORY SWITCH.
2.5 TRIM AND DRAIN VALVES
A GENERAL REQUIREMENTS:
1. PRESSURE RATING: 175 PSI MINIMUM.
B. ANGLE VALVES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. MILWAUKEE VALVE.
b. NIBCO.
c. UNITED BRASS WORKS.
C. BALL VALVES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. MILWAUKEE VALVE.
b. NIBCO.
c. UNITED BRASS WORKS.
d. VICTAULIC.
D. GLOBE VALVES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. CRANE.
b. MILWAUKEE VALVE.
c. NIBCO.
2.6 SPECIALTY VALVES
A. GENERAL REQUIREMENTS:
1. PRESSURE RATING 175 PSI MINIMUM.
2. BODY MATERIAL: CAST IRON.
B. AUTOMATIC {BALL DRIP) DRAIN VALVES
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. NIBCO.
b. RELIABLE.
c. TYCO.
2. TYPE: AUTOMATIC DRAINING, BALL CHECK.
3. SIZE: NPS 3/4,
2.7 SPRINKLER SPECIAL TY PIPE FITTINGS
A. GENERAL REQUIREMENTS:
1. PRESSURE RATING: 175 PSI MINIMUM.
B. FLOW DETECTION AND ALARM TEST DRAIN ASSEMBLIES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. AGF MANUFACTURING INC. - MODEL 1011 WITH PRESSURE RELIEF (OR
EQUAL).
2. SIZE: 2 IN.
3. INLET AND OUTLET: THREADED.
C. SPRINKLER TEST FITTINGS:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. AGF MANUFACTURING INC.
b. TYCO.
c. VICTAULIC.
d. VIKING.
2. BODY MATERIAL: CAST OR DUCTILE IRON HOUSING WITH SIGHT GLASS.
3. SIZE: SAME AS CONNECTED PIPING.
4. INLET AND OUTLET: THREADED.
2.8 SPRINKLERS
A MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE
MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE
WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:
1. GLOBE.
2. RELIABLE.
3. TYCO.
4. VICTAULIC.
5. VIKING.
B. GENERAL REQUIREMENTS:
1. PRESSURE RATING: 175 PSI MINIMUM.
2. ONLY SPRINKLERS MANUFACTURED AFTER JANUARY 1. 2021 WILL BE
ACCEPTED FOR USE.
3. ONLY SPRINKLERS MANUFACTURED UTILIZING BELLEVILLE SPRING SEALS
WILL BE ACCEPTABLE FOR USE.
C. SPRINKLER TYPES:
1. WHITE RECESSED - GLASS BULB QUICK RESPONSE RESIDENTIAL RECESSED
SPRINKLER WITH MATCHING RECESSED ESCUTCHEON.
D. SPRINKLER ESCUTCHEONS: MATERIALS, TYPES, AND FINISHES SHALL MATCH
SPRINKLERS.
1. ESCUTCHEONS SHALL BE LISTED FOR USE WITH THE SPRINKLER IT IS
INSTALLED WITH.
E, SPRINKLER GUARDS:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. GLOBE.
b. RELIABLE.
c. TYCO.
d. VICTAULIC.
e. VIKING.
2. TYPE: WIRE CAGE WITH FASTENING DEVICE FOR ATTACHING TO SPRINKLER.
2.9 ALARM DEVICES
A. ALARM DEVICE TYPES SHALL MATCH PIPING AND EQUIPMENT CONNECTIONS.
B. WATERFLOW SWITCHES - VANE TYPE:
1. MANUFACTURERS· SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. GUARDIAN.
b. POTTER ELECTRIC.
c. SYSTEM SENSOR.
2. WATERFLOW DETECTOR: ELECTRICALLY SUPERVISED.
3. COMPONENTS: TWO SINGLE-POLE, DOUBLE-THROW CIRCUIT SWITCHES FOR
ISOLATED ALARM AND AUXILIARY CONTACTS. 24-VOLT O.C. OR 110·VOLT A.C,;
COMPLETE WITH FACTORY SET. FIELD-ADJUSTABLE RETARD ELEMENT TO
PREVENT FALSE SIGNALS AND TAMPERPROOF COVER; CORROSION
RESISTANT COMPONENTS IN WATERWAY; DUST TIGHT CONSTRUCTION,
4. TYPE: PADDLE OPERATED.
5. PRESSURE RATING: 175 PSI MINIMUM.
6. DESIGN INSTALLATION: HORIZONTAL OR VERTICAL.
7. SIGNALS WATERFLOW THAT EQUALS OR EXCEEDS 10 GPM.
8. 0 TO 60 SECONDS ADJUSTABLE RANGE.
9. DETECTOR SHALL BE FURNISHED AND INSTALLED BY THE FIRE SPRINKLER
CONTRACTOR AND WIRED COMPLETE BY THE FIRE ALARM CONTRACTOR.
C. VALVE SUPERVISORY SWITCHES:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
AVAILABLE MANUFACTURERS OFFERING PRODUCTS THAT MAY BE
INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a. GUARDIAN.
b. POTTER ELECTRIC.
c. SYSTEM SENSOR.
2. TYPE: ELECTRICALLY SUPERVISED.
3. COMPONENTS: SINGLE-POLE, DOUBLE-THROW SWITCH WITH NORMALLY
CLOSED CONTACTS: 24-VOLT D.C. OR 110-VOLT A.G.; TAMPER PROOF COVER;
DUST TIGHT CONSTRUCTION.
4. DESIGN: SIGNALS THAT CONTROLLED VALVE IS IN OTHER THAN FULLY OPEN
POSITION.
5. THE SUPERVISORY SWITCH SHALL BE FURNISHED AND INSTALLED BY THE
FIRE SPRINKLER CONTRACTOR AND WIRED COMPLETE BY THE FIRE ALARM
CONTRACTOR.
2.10 PRESSURE GAGES
A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE
MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE
WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:
1. AMETEK: U.S. GAUGE DIVISION.
2. BRECCO CORPORATION.
3. WIKA INSTRUMENT CORPORATION.
B. DIAL SIZE: 31/i TO 4%-INCH DIAMETER
C. PRESSURE GAGE RANGE: 0 TO 250 PSI MINIMUM.
D. WATER SYSTEM PIPING GAGE: INCLUDE "WATER' OR "AIR/WATER" LABEL ON DIAL
FACE.
2.11 SIGNS
A. APPROVED ENAMELED METAL SIGNS SHALL BE SECURELY ATTACHED AT ALL
MAIN DRAINS, AUXILIARY DRAINS, ALARM TEST CONNECTIONS AND CONTROL
VALVES.
B. PROVIDE A PERMANENTLY ATTACHED PLACARD INDICATING HYDRAULIC DESIGN
INFORMATION IN ACCORDANCE WITH NFPA 130 AND PLACED ON THE RISER. A
MOCK-UP OF PLACARD SHALL BE INCLUDED WITH EQUIPMENT LITERATURE.
C. PROVIDE A PERMANENTLY ATTACHED PLACARD INDICATING GENERAL
INFORMATION IN ACCORDANCE WITH NFPA 13D AND PLACED ON THE RISER. A
MOCK-UP OF PLACARD SHALL BE INCLUDED WITH EQUIPMENT LITERATURE.
2.12 CORROSION MANAGEMENT
A. MANUAL AIR VENTS
1. PROVIDE MANUAL AIR VENTS: 175 PSI RATED WORKING PRESSURE WHERE
INDICATED ON DRAWINGS MOUNTED IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
PART 3 - EXECUTION
3.1 COORDINATION WITH OTHER TRADES
REVISED
A. COORDINATE CLOSELY WITH ALL OTHER TRADES TO EXPEDITE CONSTRUCTION
AND AVOID INTERFERENCE.
3.2 SERVICE ENTRANCE PIPING
A CONNECT SPRINKLER PIPING TO FIRE WATER SERVICE PIPING TO BUILDING.
3.3 SYSTEM INSTALLATION
A. DEVIATIONS FROM ENGINEERING DOCUMENTS REQUIRE PRIOR WRITTEN
APPROVAL FROM THE ENGINEER OF RECORD.
B. PIPING STANDARD: COMPLY WITH REQUIREMENTS IN NFPA 13D FOR
INSTALLATION OF SPRINKLER PIPING.
C. INSTALL TEST CONNECTIONS IN SPRINKLER SYSTEM PIPING AS REQUIRED.
0. AUXILIARY DRAINS CONSISTING OF PLUGS, OR GLOBE VALVES ANO PLUGS
WHERE CAPACITY OF TRAPPED PIPE SECTION EXCEEDS 5 GALLONS, SHALL BE
PROVIDED TO DRAIN ALL POINTS IN THE SYSTEM THAT CANNOT BE DRAINED
BACK TO MAIN RISER.
E. INSTALL AUTOMATIC (BALL DRIP) DRAIN VALVE AT EACH CHECK VALVE FOR FIRE
DEPARTMENT CONNECTION, OR ON PIPING BETWEEN FIRE DEPARTMENT
CONNECTION AND CHECK VALVE. INSTALL DRAIN PIPING TO EXTERIOR.
F. INSTALL ALARM DEVICES IN PIPING SYSTEMS.
G. INSTALL HANGERS ANO SUPPORTS FOR SPRINKLER SYSTEM PIPING ACCORDING
TO NFPA 130.
H. INSTALL PRESSURE GAGES WHERE REQUIRED BY NFPA 13D. INCLUDE PRESSURE
GAGES WITH CONNECTION NOT LESS THAN NPS ¼ AND WITH SOFT METAL
SEATED GLOBE VALVE, ARRANGED FOR DRAINING PIPE BETWEEN GAGE AND
VALVE. INSTALL GAGES TO PERMIT REMOVAL, AND INSTALL WHERE THEY WILL
NOT BE SUBJECT TO FREEZING.
I. SLEEVES SHALL BE PROVIDED FOR PIPING PASSING THROUGH CONCRETE SLABS,
CONCRETE OR MASONRY WALLS AND PARTITIONS, THROUGH FLOORS, CEILINGS,
WALLS, OR PARTITIONS OF OTHER BUILDING MATERIALS. WATERTIGHT SLEEVES
CAULKED WITH MASTIC OR LEAD SHALL BE PROVIDED FOR FLOOR SLABS AND
WALLS ON OR BELOW GRADE. STANDARD PIPE OR GALVANIZED SHEET METAL
SLEEVES SHALL BE INSTALLED IN ABOVE GRADE CONSTRUCTION AS MAY BE
REQUIRED. THE SLEEVES SHALL BE OF SUFFICIENT DIAMETER TO PASS PIPE
LINES WITH COUPLINGS OR WITH INSULATION OR ANNULAR AREA FOR CAULKING
WHERE REQUIRED.
J. ESCUTCHEONS SHALL BE APPROVED FLOOR AND CEILING PLATES MADE OF
STEEL OR BRASS, PLAIN OR CHROMIUM PLATE FINISH AND SHALL BE INSTALLED
AROUND ALL EXPOSED PIPING PASSING THROUGH A FINISHED FLOOR, WALL OR
CEILING. THE PLATES SHALL BE OF SUFFICIENT OUTSIDE DIAMETER TO COVER
THE SLEEVE OPENING AND SHALL BE PROVIDED WITH SPRINGS OR SET SCREWS
TO INSURE THEM FITTING SNUGLY AROUND THE PIPE.
3.4 IDENTIFICATION
A INSTALL LABELING AND PIPE MARKERS ON EQUIPMENT AND PIPING ACCORDING
TO REQUIREMENTS IN NFPA 130 AND THE LOCAL AHJS.
3.5 FIELD QUALITY CONTROL
A. PERFORM TESTS AND INSPECTIONS.
B, TESTS AND INSPECTIONS:
1. LEAK TEST: AFTER INSTALLATION, HYDROSTATICALLY TEST ENTIRE SYSTEM
AND TEST FOR LEAKS BY CHARGING SYSTEM TO 10 PSI ABOVE MAXIMUM
OPERATING PRESSURE OR 150 PSI. WHICHEVER IS LESS IN ACCORDANCE
WITH NFPA 13D. REPAIR LEAKS AND RETEST UNTIL NO LEAKS EXIST.
2. TEST AND ADJUST CONTROLS AND SAFETIES. REPLACE DAMAGED AND
MALFUNCTIONING CONTROLS AND EQUIPMENT.
3. FLUSH, TEST, AND INSPECT SPRINKLER SYSTEMS ACCORDING TO NFPA 130,
"SYSTEMS ACCEPTANCE" CHAPTER.
4. COORDINATE WITH FIRE ALARM TESTS. OPERATE AS REQUIRED.
5. VERIFY THAT EQUIPMENT HOSE THREADS ARE SAME AS LOCAL FIRE
DEPARTMENT EQUIPMENT.
C. TESTS SHALL BE WITNESSED BY THE AUTHORITY HAVING JURISDICTION, AND
OWNER'S AUTHORIZED AGENT.
0. PRELIMINARY TESTING PROCEDURES SHALL BE CONDUCTED AS MENTIONED
ABOVE TO ASSURE PROPER OPERATION WHEN THE FINAL TESTING IS
PERFORMED.
E. THE CONTRACTOR'S MATERIAL AND TEST CERTIFICATES AS SHOWN IN NFPA 13
MUST BE COMPLETED AND SUBMITTED TO THE ENGINEER BEFORE FINAL
ACCEPTANCE MAY BE GIVEN.
3.6 CLEANING
A REMOVE AND REPLACE SPRINKLERS WITH PAINT, OTHER THAN FACTORY FINISH,
INCLUDING OVERSPRAY.
3.7 DEMONSTRATION
A. TRAIN OWNER'S MAINTENANCE PERSONNEL TO ADJUST, OPERATE, AND MAINTAIN
FIRE SPRINKLER SYSTEM COMPONENTS.
B. AFTER COMPLETION OF ALL INSTALLATION, TESTS, ETC. AND PRIOR TO THE
OPENING DATE. THE SPRINKLER CONTRACTOR SHALL INSTRUCT THE OWNER IN
THE OPERATION OF THE SPRINKLER SYSTEM. PROVIDE WRITTEN OPERATING
INSTRUCTIONS AND MOUNT ON WALL IN A FRAME WITH GLASS FRONT. INCLUDE
THE FOLLOWING SO THAT THE OWNER
1. WILL IMMEDIATELY RECOGNIZE THE MAIN VALVES ARE IN OPEN OR CLOSED
POSITION,
2. WILL KNOW HOW TO DRAIN THE SYSTEM.
3. WILL KNOW HOW TO RESET THE ALARM SYSTEM.
4. Will KNOW NOW TO MAKE COMPLETE WEEKLY INSPECTION.
5. WILL KNOW HOW TO MAINTAIN THE SYSTEM IN ACCORDANCE WITH NFPA 130
AND 25,
END OF SECTION 211313
TITLE OF SHEET ARCH/ENG PROJ #
07310.035
ENGINEER OF RECORD:
WILLIAM B. SMITH, PE
LICENSE NO. E-1491�
�o
SCH::MM::R
DATE INITIAL
PREPARED
JLK
DESIGNED
JLK
SPECIFICATIONS
FIRE PROTECTION
SUB SHEET NO.
CODE CONSULTANTS
PROFESSIONAL ENGINEERS, PC
2043 WOODLAND PKWY. SUITE 300
ST. LOUIS, MO 63146-4235
CORPORATE CfRTIF!CATE OF AUTHORITY
NO. 10188652
I
2043 WOODLAND PKWY, SUITE 300
ST. LOUIS, MISSOURI 63146-4235
314-991-2633 www.codeconsullants.com
Dtiign with Pu,_,,. Build .-..th C,,,,fideft«,_
1044 North 115th Street I Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
DRAWN
JLK
CHECKED
04/11/2023
DATE
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
FP103
DRAWING NO.
80054
PMIS / PKG. NO.
256385
SHEET
8 OF29
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE
OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL
FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND
NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR
VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE
CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO
ADDITIONAL EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET
OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK.
CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO
FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE
RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL
FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER.
COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER
TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO
REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED
CONSTRUCTION.
E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK
WITH STRUCTURE, CEILING, LIGHTING, AND PIPING.
F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL
EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.
G. ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT
ANGLES AND PARALLEL TO BUILDING WALLS UNLESS OTHERWISE
INDICATED.
H. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.
MAINTAIN ALL CODE REQUIRED CLEARANCES.
I. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,
MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED
PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN
RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP
WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE
OWNER AND ARCHITECT IN WRITING. THE WORK IN THE AFFECTED
AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY WRITTEN
AGREEMENT OF THE OWNER AND CONTRACTOR.
J. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INLET SIZE UNLESS
OTHERWISE NOTED.
K. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING
CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND
GENERAL CONTRACTOR.
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE
ORIGINAL DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD
VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,
RELOCATED, OR SALVAGED ARE SHOWN AS SOLID, FULL-TONE
LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND
ARE SHOWN AS HALF-TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS
LISTED BELOW OR HERE-IN. THE CONTRACTOR SHALL
COORDINATE ALL REQUIRED RENOVATION AND NEW
CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE
TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED
BELOW.
C. THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING
EQUIPMENT FROM FINISHED AREAS AND THROUGH WEATHER
BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL PLANS
AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING
TO ENSURE PROPER PATCHING AND REPAIR IS MADE TO THE
BUILDING.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION
AND REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS,
EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT, INSTALL, OR
ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER
HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.
E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED
SHALL BE CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT
DAMAGE AND STORED OR REINSTALLED ON THE SITE AS DIRECTED.
REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF
THE OWNER.
F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND
CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO
MECHANICAL REMOVALS.
G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,
MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED
PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT
BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL
IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT
THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE
WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND
ARCHITECT.
H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING
DEMOLITION SHALL BE COORDINATED WITH THE OWNER AND
GENERAL CONTRACTOR.
SYMBOL LEGEND
VOLUME DAMPER
DEMO TO EXISTING CONNECTION
SPRINKLER DRAIN
FIRE SUPPRESSION PIPING
ISOLATION VALVE
TAMPER SWITCH
MANUAL BALANCING VALVE
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
CONTROL VALVE (3 WAY)
CONTROL VALVE (2 WAY)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
HVAC DUCTWORK AND SPECIALTIES
(CONT.)
MISCELLANEOUS SYMBOLS
RETURN DUCT DOWN
AIR TERMINAL (VERTICAL MOUNTING)
ROUND DUCT UP / DOUBLE LINE PIPE
ROUND DUCT DOWN / DOUBLE
LINE PIPE
RETURN DUCT UP
TURNING VANES
SUPPLY AND FRESH AIR DUCT DOWN
SUPPLY AND FRESH AIR DUCT UP
SIZE/TYPE
SIZE/TYPE
FLOW
FLOW
SIZE/TYPE
FLOW
SMOKE DAMPER
FIRE DAMPER-HORIZ FIRE SEPARATION
MOTORIZED DAMPER-OPPOSED BLADE
MOTORIZED DAMPER-PARALLEL BLADE
ROUND AIR TERMINAL
(HORIZONTAL MOUNTING)
GRAVITY DAMPER
(OR) SAFETY VALVE-STEAM
TEMP & PRESS RELIEF
FLOOR SINK
FLOOR DRAIN
GRADE CLEANOUT
PLUMBING VENT THRU ROOF
CLEANOUT / WALL CLEANOUT
THERMOSTATIC MIXING VALVE
M
M
MANHOLE
TRENCH DRAIN
OVERFLOW ROOF DRAIN
OXYGEN OUTLET
PIPE CAP
ELBOW UP
AIR OUTLET
TEE
ELBOW DOWN
VACUUM OUTLET
ROOF DRAIN
SIZE/TYPE
FLOW
HUMIDISTAT
THERMOSTAT
FLEXIBLE DUCT
S
H
T
TEMPERATURE SENSORUNION
TEE DOWN
STRAINER
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
AIR VENT
TEE UP
FIRE/SMOKE DAMPER
RECTANGULAR RETURN AIR TERMINAL
(HORIZONTAL MOUNTING)
RECTANGULAR SUPPLY AIR TERMINAL
(HORIZONTAL MOUNTING)
SOLENOID VALVE
F
D
TS
VALVES
FS
M
M
S
LPR
HPS
MPR
MPS
LPS
HVAC PIPING
GHWR
GHWS
HWR
HWS
PC
HPR
ES
BBD BOILER BLOW DOWN
EXHAUST STEAM
PUMPED CONDENSATE
HIGH PRESSURE RETURN
HIGH PRESSURE STEAM
MEDIUM PRESSURE RETURN
MEDIUM PRESSURE STEAM
LOW PRESSURE RETURN
LOW PRESSURE STEAM
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
FS-_
FD-_
CO
VTR
GCO
ORD-_
MH
X
A
V
RD-_
PIPING SPECIALTIES AND FITTINGS
WCO
FIRE PROTECTION
SIZE/TYPE
FLOW
RECTANGULAR EXHAUST AIR TERMINAL
(HORIZONTAL MOUNTING)
CWS
GCWS
CWR
CR
CS
RL
RDL
RS
GCWR GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
REFRIGERANT LIQUID LINE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION LINE
HCWS
HCWR
HOT/CHILLED WATER SUPPLY
HOT/CHILLED WATER RETURN
DOMESTIC HOT WATER
RECIRCULATING (DHWR)
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
ST/OST
PLUMBING PIPING
ACID VENT
TW
AV
AW
W
DS
DSCW
TWR
DSHW
SANITARY VENT
BURIED EXTERIOR WATER
TEPID WATER RECIRCULATING
TEPID WATER
DISTILLED WATER
SOFTENED HOT WATER
SOFTENED COLD WATER
ACID WASTE
STORM DRAIN
SANITARY DRAIN (BELOW FLOOR)
SANITARY DRAIN (ABOVE FLOOR)
OXYGEN
VACUUM
OX
VAC
RO
A
REVERSE OSMOSIS WATER
COMPRESSED AIR
DEIONIZED WATERDI
AIR FLOW STATIONAFS
HPWR
HPWS
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
F
S
FS
NEW TO EXISTING CONNECTION
G NATURAL GAS
FOF
FOG
LPG
FOV
FOR
FOS
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL GAGE
FUEL OIL FILL
FUEL OIL VENT
LIQUEFIED PETROLEUM GAS
CD CONDENSATE DRAIN
EXHAUST DUCT DOWN
EXHAUST DUCT UP
CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR
NO2 NITROGEN DIOXIDE SENSOR
SENSOR WITH GUARD'X'
DOUBLE - GRADE CLEANOUTDGCO
ST/OST STORM DRAIN (BELOW FLOOR)
WASTE AND ANESTHETIC
GAS DISPOSAL
NITROGEN
WAGD
N
MEDICAL AIRMA
PIPE GUIDE
HOSE BIBB
THERMOMETER
PIPE ANCHOR
HB
STEAM TRAP
RHY
WH
ROOF HYDRANT
WALL HYDRANT
PRESSURE GAUGE
EXISTINGDEMO
EXISTINGNEW
18 Ø
18x10
18/10
ROUND DUCT
FLAT OVAL DUCT-1ST FIG IS SIDE
SHOWN
RECT DUCT-1ST FIG IS SIDE SHOWN
ACOUSTICAL DUCT LINER
HVAC DUCTWORK AND SPECIALTIES
HIGH EFFICIENCY TAKEOFF
HIGH EFFICIENCY TAKOFF
WITH VOLUME DAMPER
NITROGEN OUTLET
MEDICAL AIR OUTLET
WASTE AND ANESTHETIC GAS
DISPOSAL OUTLET
N
MA
V
FLEXIBLE DUCTWORK CONNECTION
ABBREVIATIONS
NORTH
ARROW
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XXXX
SIM/OPP
X
XXXX
XX-1
X
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
ROOM / SPACE
NUMBER
LETTER/NUMBER
INDICATES NEW
COLUMN LINE
LETTER/NUMBER
INDICATES EXISTING
COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DRAWING/DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
XXX-1
PLUMBING
FIXTURES PLUMBING FIXTURE
DESIGNATION
X"PIPE
SIZE
PIPE SIZE (DIAMETER)
X"xX"
DUCT
SIZE
WIDTH x HEIGHT
X"/X" WIDTH / HEIGHT
X" DIAMETER
REF. DEMO NOTES ( ) XX REF. NOTES ( )
SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.
GENERAL DEMOLITION NOTES GENERAL NOTES
MECHANICAL SHEET LIST
NORTH PLAN
NORTH
TRUE
NORTH
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPS
MD MOTORIZED DAMPER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
MPR MEDIUM PRESSURE
RETURN
MPS MEDIUM PRESSURE STEAM
MS MOP SINK
N NITROGEN
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPCW NONPOTABLE COLD WATER
NPHW NONPOTABLE HOT WATER
NPHWR NONPOTABLE HOT WATER
RECIRCULATING
OA OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
OX OXYGEN
P PUMP
PHC PREHEAT COIL
PIV POST INDICATING VALVE
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH,
GAUGE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
RA RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF AREA DRAINS
RL REFRIGERANT DISCHARGE LINE
RF RETURN FAN
RH RELIEF HOOD
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RELIEF AIR
RLF RELIEF FAN
RO REVERSE OSMOSIS WATER
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION LINE
RTU ROOF TOP UNIT
RV RELIEF VALVE
S SINK
SA SUPPLY AIR
SAN SANITARY SEWER
SD SMOKE DAMPER
SF SUPPLY FAN
SFU SANITARY FIXTURE UNIT
SH SHOWER
SP STATIC PRESSURE
SSS SURGICAL SCRUB SINK
ST STORM WATER
TD TRENCH DRAIN
TMV THERMOSTATIC MIXING VALVE
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T THERMOSTAT
UH UNIT HEATER
UR URINAL
V VENT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSETS
WCO WALL CLEANOUT
WF WASH FOUNTAINS
WFU WATER FIXTURE UNITS
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WS WATER SOFTENER
WSHP WATER SOURCE HEAT PUMP
WWHP WATER TO WATER HEAT PUMP
YH YARD HYDRANT
A COMPRESSED AIR
AC AIR COMPRESSOR
AD AIR DOOR
AFCV AUTO FLOW CONTROL VALVE
AHU AIR HANDLING UNIT
AMP AMPERE
APD AIR PRESSURE DROP
AS AIR SEPARATOR
AV ACID VENT
AW ACID WASTE
B BOILER
BC BLOWER COIL
BD BIDET
BFP BACKFLOW PREVENTER
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLKG BLOCKING
BLV BALANCING VALVE
BT BATHTUB
BV BALL VALVE
BW BEDPAN WASHER
CH CHILLER
CC COOLING COIL
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CUH CABINET HEATER
CI CAST IRON
CMU COMBINATION UNITS
CR CONDENSER WATER RETURN
CRAC COMPUTER ROOM AIR
CONDITIONER
CS CONDENSER WATER SUPPLY
CSS CLINICAL SERVICE SINKS
CT COOLING TOWER
CU CONDENSING UNIT - SPLIT SYSTEM
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DB DRY-BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DEG DEGREE
DF DRINKING FOUNTAIN
DGCO DOUBLE GRADE CLEANOUT
DH EMERGENCY DRENCH HOSES
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER
RECIRCULATING
DI DEIONIZED WATER
DOAS DEDICATED OUTDOOR AIR SYSTEM
DS DISTILLED WATER
DSA DUCT SOUND ATTENUATORS
DSCW DOMESTIC SOFT COLD WATER
DSHW DOMESTIC SOFT HOT WATER
DSHWR DOMESTIC SOFT HOT WATER
RECIRCULATING
DST DOMESTIC STORAGE TANK
DTW DOMESTIC TEPID WATER
DTWR DOMESTIC TEPID WATER
RECIRCULATING
EA. EACH
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE
WASH/SHOWER
EF EXHAUST FAN
EFF EFFICIENCY
EFW EMERGENCY FACE WASH
EH EXHAUST HOOD
ERV ENERGY RECOVERY
VENTILATOR
ES EMERGENCY SHOWER
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER
TEMPERATURE
ET EXPANSION TANK
F FIRE SUPPRESSION PIPING
F-_ FURNACE
FCO FLOOR CLEANOUT
FC FLUID COOLER
FCU FAN COIL UNIT
FD FIRE DAMPER
FLA FULL LOAD AMPS
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD FIRE/SMOKE DAMPER
FT FINNED TUBE
G GAS
GCWR GLYCOL CHILLED
WATER RETURN
GCWS GLYCOL CHILLED
WATER SUPPLY
GD GARBAGE DISPOSAL
GDH GAS DUCT HEATER
GHCR GLYCOL HOT/CHILLED
WATER RETURN
GHCS GLYCOL HOT/CHILLED
WATER SUPPLY
GHWR GLYCOL HOT WATER RETURN
GHWS GLYCOL HOT WATER SUPPLY
GI GREASE INTERCEPTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GAS VENT
GWH GAS WATER HEATER
HB HOSE BIBB
HC HEATING COIL
HCR HOT/CHILLED WATER RETURN
HCS HOT/CHILLED WATER SUPPLY
ACC AIR COOLED CONDENSER
ACCU AIR COOLED CONDENSING UNIT
ASHP AIR SOURCE HEAT PUMP
ARU AIR ROTATION UNIT
OI OIL INTERCEPTOR
SOI SAND OIL INTERCEPTOR
DSS DUCTLESS SPLIT SYSTEM
SP SUMP PUMP
OST OVERFLOW STORM WATER
WMB WASHING MACHINE BOX
OB OUTLET BOX
RH ROOF HYDRANT
H HUMIDIFIER
DHWP DOMESTIC HOT WATER
RECIRCULATING PUMP
DWET DOMESTIC WATER EXPANSION
TANK
HP HORSEPOWER
HPR HIGH PRESSURE RETURN
HPS HIGH PRESURE STEAM
HRC HEAT RECOVERY COIL
HWR HOT WATER RETURN (HEATING)
HWS HOT WATER SUPPLY (HEATING)
HX HEAT EXCHANGER
HY HYDRANTS
HP-_ HEAT PUMP
HVLS HIGH VOLUME LOW SPEED
IH INTAKE HOOD
IRH INFRARED RADIANT HEATER
KH KITCHEN HOOD
KW KILOWATT
KWH KILOWATT HOURS
L LAVATORY
LAT LEAVING AIR TEMPERATURE
LPR LOW PRESSURE RETURN
LPG LIQUIFIED PETROLEUM GAS
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPS
LS LAUNDRY SINK
LV LOUVER
LWT LEAVING WATER TEMPERATURE
PROJECT MECHANICAL REFERENCED DEMOLITION NOTES PROJECT MECHANICAL REFERENCED NOTES
M 00 MECHANICAL INFO SHEET
M 01 SHEET SPECIFICATIONS - MECHANICAL
M 02 SHEET SPECIFICATIONS - MECHANICAL
M101 DEMOLITION FLOOR PLAN - MECHANICAL
M102 FLOOR PLAN - MECHANICAL
M501 SCHEDULE - MECHANICAL
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
256385
80054
C U s e rs \t ja m e s o n
\D o c u m e n ts
\0
H O
M E
M
E C
H R tj a m e s o n
V L
C Q
K .r v t
TMJ
TMJ
JEK
04/11/2023
07310.035
M 00
MECHANICAL INFO SHEET
07310035- 5- M 00 MECHANICAL INFO SHEET
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
DATE INITIAL
4/11/23
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
256385
80054
C U s e rs \t ja m e s o n
\D o c u m e n ts
\0
H O
M E
M
E C
H R tj a m e s o n
V L
C Q
K .r v t
TMJ
TMJ
JEK
04/11/2023
07310.035
M 01
SHEET SPECIFICATIONS -
MECHANICAL
07310035- 5- M 01 SHEET SPECIFICATIONS - MECHANICAL
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
256385
80054
C U s e rs \t ja m e s o n
\D o c u m e n ts
\0
H O
M E
M
E C
H R tj a m e s o n
V L
C Q
K .r v t
TMJ
TMJ
JEK
04/11/2023
07310.035
M 02
SHEET SPECIFICATIONS -
MECHANICAL
07310035- 5- M 02 SHEET SPECIFICATIONS - MECHANICAL
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
T
LIVING ROOM
BED ROOM
BED ROOM
BED ROOM
BATHROOM
DINING
GARAGE
UTILITY ROOM
KITCHEN
HALL
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
256385
80054
C U s e rs \t ja m e s o n
\D o c u m e n ts
\0
H O
M E
M
E C
H R tj a m e s o n
V L
C Q
K .r v t
TMJ
TMJ
JEK
04/11/2023
07310.035
M101
DEMOLITION FLOOR PLAN -
MECHANICAL
07310035- 5- M101 DEMOLITION FLOOR PLAN - MECHANICAL
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
REF. DEMO NOTES ( ):X
1 REMOVE EXISTING CONDENSING UNIT AND ASSOCIATED REFRIGERANT
LINE SET. PREPARE FOR INSTALLATION OF NEW CONDENSING UNIT AND
REFRIGERANT LINES.
2 REMOVE EXISTING ELECTRIC FURNACE AND SUPPLY DUCT INTO CEILING
AS SHOWN. PREPARE FOR INSTALLATION OF NEW FURNACE.
3 REMOVAL OF EXISTING WATER HEATER. PREPARE FOR INSTALLATION OF
NEW WATER HEATER.
4 REMOVE BRANCH OF DUCTWORK ASSOCIATED WITH EXISTING GRILLE.
PREPARE DUCT MAIN FOR NEW DUCT CONNECTION.
5 REMOVE EXISTING ENERGY RECOVERY VENTILATOR AND ASSOCIATED
AIR TRANSFER DUCTWORK. PATCH ALL RESULTING HOLES AS
NECESSARY.
6 REMOVE EXISTING REGISTER AND ASSOCIATED DUCTWORK. PATCH HOLE
IN WALL.
7 REMOVE DRYER VENT AND SEAL WALL PENETRATION AS REQUIRED.
SCALE: 1/4" = 1'-0"
FIRST FLOOR DEMOLITION PLAN - MECHANICAL
NORTH
TF-1
CU-1
12x10 SA
22x20 SA
6x10 S-1
(TYP. 3)
10x6 SA
10x6 SA
10x6 SA
10x6 SA
10x6 R-1
(TYP. 2)
10x8 RA
10x6 RA
10x6 RA
RL
RS
EF-1
6 Ø EA
4 Ø EA
LIVING ROOM
100 BED ROOM
BED ROOM
DINING
GARAGE
109 KITCHEN
106UTILITY ROOM
BATHROOM
HC BATHROOM
HALL
6x8 S-1
6x10 S-1
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
256385
80054
C U s e rs \t ja m e s o n
\D o c u m e n ts
\0
H O
M E
M
E C
H R tj a m e s o n
V L
C Q
K .r v t
TMJ
TMJ
JEK
04/11/2023
07310.035
M102
FLOOR PLAN - MECHANICAL
07310035- 5- M102 FLOOR PLAN - MECHANICAL
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
REF. NOTES ( ):X
1 VERIFY LOCATION OF EXISTING SUPPLY DUCT. CONNECT NEW SUPPLY
DUCT AS SHOWN.
2 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
REQUIREMENTS AND THE SPECIFICATIONS. ALL PIPE PENETRATIONS
SHALL BE DONE VIA A CORE DRILL TO BE NEAT AND CLEAN.
3 CONNECT NEW AIR HANDLER UNIT EXISTING RETURN DUCT AS NEEDED.
INSTALL NEW SECTION OF MAIN SUPPLY DUCT AND CONNECT NEW
SUPPLY BRANCH TO MAIN DUCT AS SHOWN.
4 ROUTE HEAT PUMP CONDENSATE TO EXISTING CONDENSATE DRAIN.
5 ROUTE BATHROOM EXHAUST THROUGH ROOF AS SHOWN. CAP WITH
GOOSENECK FITTING AND SEAL ROOF PENETRATION AS REQUIRED.
6 ROUTE ALUMINUM DRYER DUCT UP THROUGH ROOF AS SHOWN. CAP
WITH GOOSENECK VENT FITTING AND SEAL ROOF PENETRATION AS
REQUIRED.
7 EXISTING RETURN AND ASSOCIATED RETURN GRILLE TO REMAIN.
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL
NORTH
LONG FLAT SPANS ON OVAL DUCT HAVE A TENDENCY TO SAG. OVAL
DUCT
WITH A MAJOR AXIS OF 42 INCHES OR MORE SHALL BE REINFORCED PER
SMACNA HVAC DUCT CONSTRUCTION STANDARDS TYPE 2.
CHANNEL OR ANGLE
HANGER CLAMP
OR BAND
BOLT
STRAP
OR
ANGLE
ROD (TYP)
DUCT (TYP)
ANGLE (TYP)
NUT (TYP)
NOTES:
1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.
2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO DUCTWORK.
3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCT AS ROUND DUCT TENDS TO DEFORM ON TRAPEZE HANGERS.
4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINTAIN THE INTEGRITY OF THE VAPOR BARRIER.
5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALLY WRAPPED.
SHEET METAL 90° ELBOW
DIFFUSER NECK
TRANSITION
(AS REQUIRED)
CEILING
SUPPLY DUCT-
SEE PLANS FOR
SIZES
SUPPLY DIFFUSER
DUCT INSULATION
FLEX DUCT
INSULATE BACKPANPLASTER FRAME
DAMPER
STANDOFF
DAMPER
QUADRANT LOCK
NOTE:
ALL TAPS TO AIR TERMINALS REQUIRING BALANCING AT DUCT SHALL
BE MADE USING A HIGH EFFICIENCY TAKEOFF.
NOTES:
1/2"x1/2" CHAMFER STRIP
REMOVE AND CAULK.
6x6 - 10/10 WWF
#4 BENT RE-BAR
AT EACH CORNER
DRILL 3/4"Ø HOLE IN FLOOR SLAB
AND GROUT IN REBAR.
1. INSTALL NEW HOUSEKEEPING PADS AS INDICATED ON PLANS. VERIFY DIMENSIONS
WITH EQUIPMENT SIZES.
2. VERIFY SIZE AND LOCATION OF EQUIPMENT ANCHOR BOLTS.
3. PROVIDE DOWEL RODS 18" ON CENTER AROUND FULL PERIMETER OF PAD IF
LONG DIMENSION IS GREATER THAN 72".
4"
/256"
3-1/2"
FLOOR
#4 BARS @12" O.C. EACH WAY
CONCRETE BASE
1" CHAMFER
.6
LENGTH AND WIDTH
TO SUIT UNIT FURNISHED
GRADE
METAL SCREEN FRAME
ANGLE IRON
REINFORCING
WHERE REQUIRED
SCREEN
BOLT
STANDARD DUCT CONSTRUCTION
(WATERTIGHT SEAMS)
ROOF DECK
ROOFING
DUCT SIZE
SPECIFIED
S N
O W
D E
P T
H
M
IN
O R
A B
O V
E L
O C
A L
D U C
T SIZE
+ 25%
ANGLE RIVETED OR
SPOT WELDED AS
REQUIRED
1/2" SCREEN - DO NOT INCLUDE
SCREEN FOR DRYER
APPLICATIONS
.0
S T
E P
C A
N T
ROOF
INSULATION
COUNTER FLASHING
WOOD NAILER
RIGID INSULATION
HEAVY GA.
GALV. STEEL
ROOFING
135° MIN.
M
IN
M
IN
R
R=W/2
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
256385
80054
C U s e rs \t ja m e s o n
\D o c u m e n ts
\0
H O
M E
M
E C
H R tj a m e s o n
V L
C Q
K .r v t
TMJ
TMJ
JEK
04/11/2023
07310.035
M501
SCHEDULE - MECHANICAL
07310035- 5- M501 SCHEDULE - MECHANICAL
REHAB INTERIOR & EXTERIOR ON QUARTERS #3
HOMESTEAD NATIONAL MONUMENT OF AMERICA
8523 NE-4
BEATRICE, NE 68310
R-1 GRILLE SEE PLANS SEE PLANS WHITE 0.1 30 PRICE 500 ---
S-1 GRILLE SEE PLANS SEE PLANS WHITE 0.1 30 PRICE 540 ---
MARK TYPE FACE SIZE (IN.)
NECK SIZE
(IN.) FINISH
MAX PD (IN
WG)
MAX NC AT
PD SHOWN
BASIS OF
DESIGN REMARKS
DIFFUSER, REGISTER AND GRILLE SCHEDULE
NOTES: 1. PROVIDE WITH REFRIGERANT LINESET, SIZED PER MANUFACTURER REQUIREMENTS. PROVIDE LONG LINE LENGTH ACCESSORIES WHEN MANUFACTURER STANDARD LENGTHS ARE EXCEEDED.
F-1 UTILITY ROOM 1500 80 67 42400 33700 ELECTRIC 240 1 14.4 0.5 120 1 60 TRANE GAM5A0C42M31SA CU-1 95.0 R-410A 24.0 40.0 230 1 60 14.6 TRANE 4TWR4042 1
DB WB
EAT (°F)
TOTAL MBH SENS. MBH
AIRSIDE DATA MIN CAP
FUEL TYPE VOLTS PH
OUTPUT
(KW) HP VOLTS PH HZ
MINIMUM
CIRCUIT
AMPS
MAXIMUM
FUSE AMPS VOLTS PH HZ
COOLING COIL DATA HEATING DATA MOTOR DATA
FURNACE BASIS OF DESIGN MARK
AMB TEMP
(°F)
REFER
TYPE
ELECTRICAL DATA
SEER
CONDENSING UNIT
BASIS OF DESIGNMARK LOCATION CFM
FURNACE DATA CONDENSING UNIT DATA
REMARKS
ELECTRIC FURNACE & CONDENSING UNIT, SPLIT SYSTEM SCHEDULE
SCALE: NOT TO SCALE
DUCT HANGER DETAIL
SCALE: NOT TO SCALE
SUPPLY DIFFUSER/ DUCT CONNECTION DETAIL
SCALE: NOT TO SCALE
HIGH EFFICIENCY TAKEOFF DETAIL
SCALE: NOT TO SCALE
HOUSEKEEPING PAD DETAIL
SCALE: NOT TO SCALE
EXTERIOR EQUIPMENT PAD DETAIL
EF-1 RESTROOM CENTRIFUGAL 50 0.5 DIRECT 586 30 950 30W 115 1 60 GREENHECK SP-B110ES ---
TYPE CFM
EXT SP
(IN WG) DRIVE RPM
MAX
SONES RPM POWER VOLTS PH HZMARK SERVES
FAN DATA ELECTRICAL DATA
MANUFACTURER AND MODEL
NUMBER REMARKS
FAN SCHEDULE
SCALE: 6" = 1'-0"
GOOSENECK AND COUNTER FLASHING DETAIL
A. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET
OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK.
CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO
FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
B. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE
RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL
FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER.
COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER
TRADES AFFECTED.
C. ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT
ANGLES AND PARALLEL TO BUILDING WALLS UNLESS OTHERWISE
INDICATED.
D. ALL PLUMBING INSTALLATION SHALL BE IN ACCORDANCE WITH THE
REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE
ORIGINAL DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD
VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED,
RELOCATED, OR SALVAGED ARE SHOWN AS SOLID, FULL-TONE
LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND
ARE SHOWN AS HALF-TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS
LISTED BELOW OR HERE-IN. THE CONTRACTOR SHALL
COORDINATE ALL REQUIRED RENOVATION AND NEW
CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE
TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED
BELOW.
C. THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING
EQUIPMENT FROM FINISHED AREAS AND THROUGH WEATHER
BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL PLANS
AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING
TO ENSURE PROPER PATCHING AND REPAIR IS MADE TO THE
BUILDING.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION
AND REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS,
EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT, INSTALL, OR
ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER
HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.
E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED
SHALL BE CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT
DAMAGE AND STORED OR REINSTALLED ON THE SITE AS DIRECTED.
REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF
THE OWNER.
F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND
CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO
MECHANICAL REMOVALS.
G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE,
MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED
PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT
BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL
IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT
THE CONDITION TO THE OWNER AND ARCHITECT IN…