B08_Solicitation_-_Att_2_-_Drawings_DistributionPanel_FOLS_258470.pdf

PDF 2 MB Posted

Attached to
FOLS, Replace Alarm System & Electrical Panel Federal contract opportunity
Solicitation number
140P6026Q0042
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document is a Final Construction Documents package for the Electrical Distribution Panel replacement project at Fort Larned National Historic Site in Pawnee County, Kansas. The project involves replacing the existing electrical distribution infrastructure at the Visitor Center (HS-1) building.

The scope of work includes installation of a new 225-ampere, 208/120-volt, 3-phase electrical panel with a new 225-ampere enclosed breaker as service equipment in a NEMA 4X enclosure. The project requires relocation of the electrical panel from the cellar to the kitchen/break room on the first floor, installation of new underground electrical feeder conductors in existing conduit, and conversion of the existing panel into a junction box. The work encompasses new conduit installation, ground bar installation with dedicated grounding to a new 10-foot copperclad ground rod, new branch circuit wiring throughout the building (including 72-pole capacity with mixed amperage breakers), feeder connections to existing buildings HS-2, fire alarm panel installation, and intrusion alarm panel installation. All work must maintain electrical power outages to a maximum of 48 hours and coordinate with the Contracting Officer and Contracting Officer Representative. The project requires coordination with a National Park Service-designated archaeologist for any ground disturbance activities and restoration of disturbed areas including pathways, seeding, and utility repair at no additional government expense. Kenneth Hahn Architects, Inc. serves as the prime A/E firm with Alvine Engineering as subcontractor; the PMIS number is 258470 with drawing number AE# 20239961.

View the file

Other files for this federal contract opportunity

Other files attached to FOLS, Replace Alarm System & Electrical Panel, newest first.
File Type Posted
Sol_140P6026Q0042_Amd_0002.pdf PDF
Sol_140P6026Q0042_Amd_0001.pdf PDF
Sol_140P6026Q0042.pdf PDF
B08_Solicitation_-_Att_1_-_Specifications_DistributionPanel_FOLS_258470.pdf PDF
B08_Solicitation_-_Att_3_DOL_Wage_Determination_KS20260044.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAWNEE RIVER

PAWNEE RIVER

HIGHWAY 156

FORT LARNED NATIONAL HISTORIC SITE

STEPHEN R. SMITH, AIA

KENNETH HAHN ARCHITECTS, INC.

ARCHITECT

I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Registered Architect under the laws of the State of Kansas.

Pages or Sheets covered by this seal: TS1, C1, C2, C3, C4, C5, C6, C7, A1, A2, A3, A4, A5, A6, A7, A8, A9, A10, A11.

2/6/2024

AREA MAP-

FT. LARNED NATIONAL HISTORIC SITE

I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.

BRANDON D. RICH

License Number 29677 My license renewal date is April 30, 2025

(date)

Pages or sheets covered by this seal:

02/06/2024

E0, ED1, ED2, ED3, ED4, ED5, ED6, ED7, ED8,

ED9, E1, E1A, E1B, E1C, E1D, E1E, E1F, E1G,

E2, E3, E4, E5, E6, E7, E8, E9, E10, E11, E12, E13, E14, E15, E16, E17, E18, E19, E20, E21.

Kansas.

20. E0 ELECTRICAL SYMBOLS AND ABBREVIATIONS

https://ksbtp.ks.gov/statutes-rules/seal-sig-faq

HS-1 - VISITOR CENTER

HS-2

MANHOLE

WATER METER

HS-3

WELL

MANHOLE

HS-9WELL

FENCE

HS-8

MANHOLE

LEECHFIELD

WELL

DRAIN TILE

DAYLIGHT

C7

C7

C7

C7

SITE PLAN GENERAL NOTES

1. A NATIONAL PARK SERVICE DESIGNATED

ARCHEOLOGIST MUST BE ON SITE DURING ANY

GROUND DISTURBANCE ACTIVITIES. SCHEDULE AND

COORDINATE WITH CO/COR. SEE DIVISION 1.

2. PREP ALL AREAS DISTURBED BY THIS PROJECT FOR

SEEDING BY NPS. PREP AREA BY FINE GRADING AND

RAKING AREA TO A FIRM EVEN SURFACE, FREE FROM

LUMPS, STONES OR CLUMPS 1-INCH OR MORE IN ANY

DIMENSION.

DISTURBED AREAS INCLUDE BUT ARE NOT LIMITED TO;

TRENCHING ACTIVITIES, BORING ACTIVITIES,

CONTRACTOR VEHICLE TRAFFIC WEAR.

3 REPAIR ALL EXISTING STABILIZED PATHWAYS

DISTURBED BY THIS PROJECT. DISTURBED AREAS

INCLUDE BUT AREA NOT LIMITED TO; TRENCHING

ACTIVITIES, BORING ACTIVITIES, CONTRACTOR

VEHICLE TRAFFIC WEAR.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING

AND PREVENTING DAMAGE TO KNOWN UTILITIES. IF

CONTRACTOR DAMAGE OCCURS, ALERT CO AND COR

AS SOON AS SAFELY POSSIBLE, AND REPAIR UTILITY

AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT. IF

DAMAGE OCCURS TO AN UNKNOWN UTILITY, CONTACT

CO AND COR AS SOON AS SAFELY POSSIBLE. SEE

DIVISION 1.

5 LIMITS OF CONSTRUCTION SHALL BE WITHIN 10' OF

TRENCH CENTER LINE AND AS PER DIVISION 1.

6 CONTRACTOR TO PROVIDE GIS/GPS SHAPE FILES, PER

NPS REQUIREMENTS, FOR ALL EXISTING UTILITIES

PHYSICALLY ENCOUNTERED DURING THIS PROJECT.

7. SEE ELECTRICAL DRAWINGS FOR AS-BUILT

DOCUMENTATION REQUIREMENTS FOR ALL

UNDERGROUND WORK INSTALLED AS PART OF THIS

PROJECT.

EXISTING ELECTRICAL

EXISTING WATER

EXISTING PHONE

EXISTING SEWER

EXISTING GAS

EXISTING AC LINE

EXISTING AT & T

EXISTING UNKNOWN UTILITY

EXISTING SECURITY

EXISTING DRAIN TILE

LEGEND

EXISTING UTILITY PLAN GEN. NOTES

1. THIS EXISTING UTILITY PLAN IS FOR INFORMATION

ONLY, AND MAY NOT BE REPRESENTATIVE OF

CONDITIONS ENCOUNTERED.

2. ALL EXISTING UTILITIES SHOWN ARE APPROXIMATE

LOCATIONS BASED ON INFORMATION OBTAINED FROM

NPS. THIS EXISTING UTILITIES PLAN MAY NOT SHOW

ALL UTILITIES THAT MAY EXIST ON SITE. CONTRACTOR

SHALL USE CAUTION DURING GROUND DISTURBANCE

ACTIVITIES AS THEY MAY ENCOUNTER CONDITIONS

NOT SHOWN ON THESE DRAWINGS.

ENLARGED SITE PLAN AND

C2

0SCALE: 1" = 40'-0" 40' 20' 40'

ENLARGED SITE PLAN AND EXISTING UTILITIES PLAN

N

EXISTING UTILITIES PLAN

F e b a m

C

T o d d A

K

H A w o r k

F t

L a r n e d D

R A

W I N

G S

F

O L S

C d w g

U

S E

R t o d d

SUB SHEET NO.

OF

DESIGNED:

KJH

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

DRAWN BY:

TECH. REVIEW:

DATE:

2/6/2024

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CLZ

FINAL CONSTRUCTION DOCUMENTS

258470

425 / 80087

LIBRARY

KITCHEN/

BREAK

MEN

OFFICE

MUSEUM

VEIWING

ROOM

UP

OFFICE

OFFICE

ENTRY

OPEN

OFFICE

OFFICE

OFFICE

ENTRY

OFFICE

CLOS.

MEN

WOMEN

MUSEUM

SHOP

WOMEN

117 CLOS.

HALL

CLOS.

HALL

PIPE CHASE

HALL

STAIR

EXISTING WINDOW

WELL

ATTIC

DN

WALKWAYWALKWAY

ATTIC

ATTIC

CHIMNEY

CHIMNEY

CHIMNEYCHIMNEY CHIMNEY

CELLAR

C01

CELLAR

C02

UP UPEXISTING

WINDOW WELL

HS-1

FLOOR PLANS

A3SCALE: 1/8" = 1'-0" 8' 4' 0 8'

HS-1 FLOOR PLAN

N

PLAN TRUE

N

GENERAL NOTES

G1. PATCH/REPAIR/PAINT CEILING/WALL

FINISHES AS REQUIRED TO MATCH

ADJACENT AREA WHERE NEW

DEVICES DON'T COMPLETELY

COVER OLD DEVICE LOCATIONS.

G2. WHERE PAINTING IS REQUIRED DUE

TO REMOVAL/ PATCHING; PAINT

ENTIRE CEILING/ WALL PLANE

CORNER TO CORNER, EDGE TO

EDGE. PAINT COLOR AND FINISH TO

MATCH ADJACENT CEILING/ WALL.

G3 PATCHING MATERIAL SHALL MATCH

EXISTING CONDITIONS (ie: DRYWALL

/DRYWALL MUD AT EXIST. DRYWALL,

PLASTER AT EXISTING PLASTER

WALLS, ETC.)

G4. INSTALL SURFACE MOUNTED

CONDUIT IN A NEAT AND ORDERLY

MANNER. DO NOT RUN CONDUIT

DIAGONALLY. SEE ELECTRICAL

DRAWINGS AND SPECIFICATIONS.

G5. PAINT EXPOSED CONDUIT AND

FITTINGS TO MATCH ADJACENT

SURFACE. PAINT FLAT BLACK AT

EXPOSED RAFTERS/WOOD DECK.

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

HS-1 ATTIC PLAN

N

PLAN TRUE

N

SCALE: 1/8" = 1'-0" 8' 4' 0 8'

HS-1 CRAWL SPACE PLAN

N

PLAN TRUE

N

F e b a m

C

T o d d A

K

H A w o r k

F t

L a r n e d D

R A

W I N

G S

F

O L S

A

H

S d w g

U

S E

R t o d d

SUB SHEET NO.

OF

DESIGNED:

KJH

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

DRAWN BY:

TECH. REVIEW:

DATE:

2/6/2024

DRAWING NO.

PMIS NO.

SHEET

TITLE OF SHEET

A/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

TWM

CLZ

FINAL CONSTRUCTION DOCUMENTS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND

CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,

SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.

LAY OUT AND COORDINATE ALL WORK PRIOR TO

INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR

OPERATION, MAINTENANCE, AND CODES AND VERIFY

NON-INTERFERENCE WITH OTHER WORK. DO NOT

FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR

ALL TRADES. READ SPECIFICATIONS.

F eb

5,

- 2

:0 3p m J:

\2

3_ Pr oje cts

\2

1\ Dw gs \ 2

1E

0.

dw g

- U

SE

R jsa nc he z

SUB SHEET NO.

OF

DESIGNED:

RCF

DRAWN BY:

TECH. REVIEW:

DATE:

02/06/2024

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

JAS

GAN

AE# 20239961

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

FINAL CONSTRUCTION DOCUMENTS

DRAWING NO.

PMIS NO.

258470

425 / 80087ELECTRICAL SYMBOLS AND

ABBREVIATIONS

E0

CARBON MONOXIDE DETECTOR

ELECTRICAL SYMBOLS

FIBER OPTIC CABLE

("#" INDICATES NUMBER OF STRANDS

"T" INDICATES TYPE AND

"X" INDICATES CABLE NAME)

COMBINATION DATA/AV FLOOR OUTLET

("#" INDICATES DEVICE TYPE IN SCHEDULE)

CABLE SLACK

("X" INDICATES SLACK LENGTH)

CABLE PROTECTOR

("XXX" INDICATES NUMBER OF PROTECTORS)

AV GEAR BOX, REFER TO

SCHEMATICS AND SPECS

UNSHIELDED TWISTED PAIR COPPER CABLE -

"C" INDICATES CATEGORY NUMBER

"#" INDICATES NUMBER OF PAIRS

"G" INDICATES AWG, "X" INDICATES CABLE NAME

CROSS-CONNECT FIELD

SPLICE

MECHANICAL TERMINATION OF CABLE

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

TELECOMMUNICATIONS

#-T X

XXX

X C-#-G X

COMMUNICATIONS OUTLET CEILING COMMUNICATIONS OUTLET FLOOR COMMUNICATIONS OUTLET

MUTOA - MULTI-USER TELECOMMUNICATIONS

OUTLET ASSEMBLYSPECIAL SERVICES COMMUNICATIONS OUTLET

WIRELESS ACCESS POINT

("#" INICATES QUANTITY OF ANTENAS)

AV

GROUND BAR

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

PATHWAYS

CONDUIT SLEEVE WITH BUSHINGS DISTRIBUTION RINGS

WALL MOUNT TELECOMMUNICATIONS EQUIPMENT J-HOOK STYLE CABLE HANGERS CABLE TRAY DROP OUT

CABLE TRAY

("#" INDICATES TRAY DIMENSIONS)

CABLE RUNWAY

("#" INDICATES TRAY DIMENSIONS)

CABLE TRAY - SOLID BOTTOM

("#" INDICATES TRAY DIMENSIONS)

CABLE TRAY - WALL MOUNTED

("#" INDICATES TRAY DIMENSIONS)

EQUIPMENT RACK

("#" INDICATES RACK NO. AND FRONT OF RACK)#

FIRE ALARM AUTOMATIC SMOKE DETECTOR

WIRELESS GATEWAY

FIRE ALARM LOW FREQUENCY SOUNDER

FIRE ALARM WIRELESS AUTOMATIC SMOKE DETECTOR

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM AUTOMATIC WALL SMOKE DETECTOR

CEILING FIRE ALARM HORN AND LIGHT COMBINATION

(# INDICATES CANDELA RATING)

FIRE ALARM CONTROL PANEL

FIRE ALARM AUTOMATIC CEILING HEAT DETECTOR

FIRE ALARM AUTOMATIC WALL HEAT DETECTOR

FIRE ALARM MANUAL STATION

FIRE ALARM CONTROL MODULE

CEILING FIRE ALARM LIGHT

(# INDICATES CANDELA RATING)

WALL FIRE ALARM LIGHT

(# INDICATES CANDELA RATING) SAMPLING TUBE TYPE SMOKE DETECTOR

ASPIRATING SMOKE DETECTION

SAMPLING PORT AND TUBING

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

FIRE DETECTION AND ALARM

F

F CM

F

F #

F

F #

FAA

FACP

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

SUBSCRIPTS

SUBSCRIPT "E" ADDED TO ANY SYMBOL

INDICATES EXISTING

SUBSCRIPT "PD" ADDED TO ANY FLOOR OUTLET

INDICATES PEDESTAL MOUNTED

SUBSCRIPT "K" ADDED TO ANY SYMBOL

INDICATES KEY OPERATED

SUBSCRIPT "WG" ADDED TO ANY SYMBOL

INDICATES WIRE GUARD

SUBSCRIPT "P" ADDED TO ANY SYMBOL

INDICATES PILOT LIGHT

SUBSCRIPT "AC" ADDED TO ANY SYMBOL INDICATES ABOVE COUNTER. LOCATE CENTER OF DEVICE 4" ABOVE COUNTER SURFACE OR WHERE PRESENT, 4" ABOVE BACKSPLASH.

WHERE INDICATED ADJACENT TO LAVATORY WITHOUT COUNTER, LOCATE CENTER OF DEVICE 8" ABOVE RIM OF LAVATORY.

EP

E

PD

AC

K

WG

P

RT WP

SUBSCRIPT "RT" APPLIED TO ANY SYMBOL

INDICATES RAIN TIGHT NEMA 3R

OR EQUIVALENT

SUBSCRIPT "WP" APPLIED TO ANY SYMBOL

INDICATES WEATHERPROOF NEMA TYPE 4

OR EQUIVALENT

SUBSCRIPT "EP" APPLIED TO ANY SYMBOL

INDICATES EXPLOSION PROOF,

CLASS, GROUP AND DIVISION AS NOTED

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

SECURITY

WALL MOUNT MOTION SENSOR

CEILING MOUNT MOTION SENSOR

SOUNDER

STROBE

POINT OF CONNECTION FOR 120VAC BY

ELECTRICAL CONTRACTOR

GLASS BREAK SENSOR

INTERCOM STATION

("S" SUBSTATION, "M" MASTER STATION)

JUNCTION BOX FOR SPECIALTY SECURITY SENSOR

DOME CAMERA

("#" INDICATES NUMBER IN SPECIFICATIONS)

SECURITY KEYPAD DEVICE

REMOTE ANNUNCIATOR DEVICE

DOOR LOCK POWER SUPPLY

PTZ DOME CAMERA

("#" INDICATES NUMBER IN SCHEDULE)

SECURITY EQUIPMENT CABINET(S), TYPE AND

QUANTITY MAY VARY FROM WALL MOUNTED,

FREE STANDING RACKS, OR EXTERIOR RATED,

REFER TO DETAILS

KEY SWITCH

REQUEST TO EXIT DEVICE

("M" MOTION SENSOR, "P" PUSH BUTTON)ACCESS CONTROL DEVICE LOCATION

"M" INDICATES MULLION MOUNT

ELECTRONICALLY CONTROLLED AND

MONITORED DOOR LOCATION

(REFER TO ACCESS CONTROL OPENING SCHEDULE)

WIRELESS DOOR POSITION SWITCH

AUTOMATIC OPERATOR CONNECTION POINT

('G' GATE, 'D' DOOR)

SECURITY PUSH BUTTON - ("P/D" INDICATES

PANIC ALARM OR DOOR RELEASE)

M

P/D

J S

IC S,M

GB

E

G,D

PS

RA

KP

KS

RQE M,P

SEC

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION

LIGHTING AND POWER

BRANCH CIRCUIT EXPOSED

BRANCH CIRCUIT -

CONCEALED IN CEILING OR WALL

BRANCH CIRCUIT - CONCEALED IN FLOOR

(UNDERGROUND IF EXTERIOR)

SPECIAL PURPOSE HOMERUN AS INDICATED

HOMERUN TO PANEL (NUMBER OF ARROWS

INDICATES NUMBER OF CIRCUITS)

CIRCUIT DOWN

SIMPLEX RECEPTACLE

CORD AND PLUG

PULL BOX

CEILING MOUNTED DUPLEX RECEPTACLE

POLE LUMINAIRE(S)

(# INDICATES FIXTURE NUMBER IN SCHEDULE)

ABOVE GRADE FIXTURE

(# INDICATES FIXTURE NUMBER IN SCHEDULE)

LIGHTING PANEL - FLUSH MOUNTED

TRANSFORMER

ENCLOSED CIRCUIT BREAKER

SAFETY SWITCH

(FUSED UNLESS OTHERWISE NOTED)

WALL MOUNTED JUNCTION BOX

JUNCTION BOX

("F" INDICATES FLOOR, "C" INDICATES CEILING)

T

PB J

J XCIRCUIT BREAK

CIRCUIT UP

CONDUIT STUB OUT

STRIP LIGHT

(# INDICATES FIXTURE NUMBER IN SCHEDULE)

LIGHTING PANEL - SURFACE MOUNTED

SINGLE POLE SWITCH

G,T,U

DUPLEX RECEPTACLE

"G" SUBSCRIPT INDICATES GFCI, "T" SUBSCRIPT

INDICATES TAMPER RESISTANT TYPE, "U" SUBSCRIPT

INDICATES COMBINATION USB CHARGING STATION

SYMBOLS INDICATED HERE AND NOT USED IN THE

CONTRACT DOCUMENTS DO NOT APPLY TO THIS

PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS

MAY BE INDICATED IN THE CONTRACT DOCUMENTS.

FIRE ALARM WIRELESS MANUAL STATION

FIRE ALARM HORN AND LIGHT COMBINATION

WATER DETECTOR

BLDG BUILDING

BTUH BRITISH THERMAL UNIT PER HOUR

C CONDUIT

CAB CABINET

CATV CABLE TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

CFM CUBIC FEET PER MINUTE

CL CENTER LINE

CLG CEILING

CLR CLEAR

CRAC COMPUTER ROOM AIR CONDITIONER

CV CONSTANT VOLUME

DD DOUBLE DUCT

DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DWG DRAWING

EA EXHAUST AIR

EL ELEVATION

EHC ELECTRIC HEATING COIL

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EXH EXHAUST

EXIST EXISTING

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FB FLOOR BOX

FL FLOOR

FLA FULL LOAD AMPS

FMG FACTORY MUTUAL GLOBAL

FT FEET

PWR POWER

PVC POLYVINYL CHLORIDE

PSI POUNDS PER SQUARE INCH

PSF POUNDS PER SQUARE FOOT

PRV PRESSURE REGULATING VALVE

PP PATCH PANEL

PNL PANEL

PLBG PLUMBING

PIV POST INDICATOR VALVE

RM ROOM

RH RELATIVE HUMIDITY

REQD REQUIRED

RLFA RELIEF AIR

RA RETURN AIR

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UL UNDERWRITERS LABORATORY

UG UNDERGROUND

(TYP) TYPICAL

TV TELEVISION

TEMP TEMPERATURE

TEL TELEPHONE

TELECOM TELECOMMUNICATIONS

SWGR SWITCHGEAR

SWBD SWITCHBOARD

SW SWITCH

STD STANDARD

SS STAINLESS STEEL

SPECS SPECIFICATIONS

(SIM) SIMILAR

SCH SCHEDULE

SAN SANITARY

SA SUPPLY AIR, SOUND ATTENUATOR

KV KILOVOLT

NC NORMALLY CLOSED

MTG MOUNTING

MTD MOUNTED

MISC MISCELLANEOUS

(MIN) MINIMUM

MECH MECHANICAL

(MAX) MAXIMUM

MA MAKEUP AIR

LTG LIGHTING

LBS POUNDS

LAN LOCAL AREA NETWORK

KW KILOWATT

KVA KILOVOLT AMPERE

OC ON CENTER

OA OUTSIDE AIR

NTS NOT TO SCALE

NOM NOMINAL

NO NORMALLY OPEN

NIC NOT IN CONTRACT

NEC NATIONAL ELECTRICAL CODE

GA GAUGE

J-BOX JUNCTION BOX

HVAC HEATING, VENTILATING

HTG HEATING

HP HORSEPOWER, HEAT PUMP

HGT HEIGHT

GPM GALLONS PER MINUTE

GND GROUND

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GEN GENERATOR

GALV GALVANIZED

AND AIR CONDITIONING

ELEC ELECTRICAL

DIA

CPVC CHLORINATED POLYVINYL CHLORIDE

CT COOLING TOWER, CABLE TRAY

DX DIRECT EXPANSION

EPO EMERGENCY POWER OFF

F FIRE WATER

FCO FLOOR CLEAN OUT

FDC FIRE DEPARTMENT CONNECTION

FHC FIRE HOSE CABINET

FURN FURNISHED

FW FILTERED WATER

G GAS

GC GENERAL CONTRACTOR

HW HOT WATER

HWC HOT WATER CIRCULATING

MAU MAKEUP AIR UNIT

MBH 1000 BTU/HOUR

MXA MIXED AIR

NPW NON-POTABLE WATER

PS PLASTER SINK

PTAC PACKAGED TERMINAL AIR CONDITIONER

RO REVERSE OSMOSIS WATER

RPBFP REDUCED PRESSURE BACKFLOW

SCW SOFT COLD WATER

SM SPRINKLER MAIN, SINGLE MODE

SSS SURGEON SCRUB SINK

SSD SUB SOIL DRAIN

ST STORM

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS'

T TRANSFORMER

BICSI BUILDING INDUSTRY CONSULTING

BTU BRITISH THERMAL UNIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CM COMMUNICATIONS CABLE

CMP COMMUNICATIONS PLENUM CABLE

CMR COMMUNICATIONS RISER CABLE

COAX COAXIAL CABLE

EMD ESTIMATED MAXIMUM DEMAND

EMI ELECTROMAGNETIC INTERFERENCE

ER EQUIPMENT ROOM

FO FIBER OPTIC

FP FIBER PANEL

PB PULLBOX

PERP PERPENDICULAR

PBX PRIVATE BRANCH EXCHANGE

RGS RIGID GALVANIZED STEEL

TR TELECOMMUNICATIONS ROOM

TMGB TELECOMMUNICATIONS MAIN

TGB TELECOMMUNICATIONS

TBB TELECOMMUNICATIONS

T-1 TRUNK LEVEL 1

STP SHIELDED TWISTED PAIR

OUTLET ASSEMBLY

MM MULTIMODE

MLO MAIN LUGS ONLY

MDF MAIN DISTRIBUTION FRAME

MC MAIN CROSS CONNECT

MATV MASTER ANTENNA TELEVISION

OSP OUTSIDE PLANT

KCMIL THOUSAND CIRCULAR MILS

ISP INSIDE PLANT

HZ HERTZ

GEC GROUNDING ELECTRODE CONDUCTOR

SERVICE INTERNATIONAL

MUTOA MULTI USER TELECOMMUNICATIONS

GROUNDING BUSBAR

GROUNDING BUSBAR

TBBIBC TELECOMMUNICATIONS BONDING

CFH CUBIC FEET PER HOUR

SHW SOFT HOT WATER

TTB TELEPHONE TERMINAL BOARD

MERV MINIMUM EFFICIENCY REPORTING

VALUE

MOA MINIMUM OUTDOOR AIR

EOA ECONOMIZER OUTDOOR AIR

IE INVERT ELEVATION

IDF INTERMEDIATE DISTRIBUTION FRAME

IC INTERCOM

BACKBONE INTERCONNECTING

PREVENTER

NATIONAL ASSOCIATION

BONDING BACKBONE

BONDING CONDUCTOR

A

AC

ACEG

AHJ

APPROX

ASHRAE

ATS

AUX

AV

AVI

AW

AWG

BFP

AMP

ALTERNATING CURRENT

AC EQUIPMENT GROUND

AUTHORITY HAVING JURISDICTION

APPROXIMATELY

AMERICAN SOCIETY OF HEATING,

REFRIGERATING AND

AIR-CONDITIONING ENGINEERS

AUTOMATIC TRANSFER SWITCH

AUXILIARY

ACID VENT, AUDIOVISUAL

AUTOMATIC VEHICLE IDENTIFICATION

ACID WASTE

AMERICAN WIRE GAUGE

BACKFLOW PREVENTER

UTILITY SINK

UNSHIELDED TWISTED PAIR

VOLT, VENT

VOLUME DAMPER

VERTICAL

VARIABLE FREQUENCY CONTROL

VENT THROUGH ROOF

WATER, WATT

WIDE AREA NETWORK

WIRELESS ACCESS POINT

WIRE MANAGEMENT PANEL

WEATHERPROOF

WIRE SIZING AMPS

WATER SOURCE HEAT PUMP

TRANSFORMER

US

UTP

V

VD

VERT

VFC

VTR

W

WAN

WAP

WMP

WP

WSA

WSHP

XFMR

AFF ABOVE FINISHED FLOOR

ALF ALUMINUM FRAME DOOR

AMERICAN SOCIETY OF

MECHANICAL ENGINEERS

STANDARD SPECIFICATIONS OF

THE AMERICAN SOCIETY FOR

ASME

ASTM

TESTING MATERIALS

AVG AVERAGE

BAS BUILDING AUTOMATION SYSTEM

BTC BONDING CONDUCTOR FOR

TELECOMMUNICATION

CLEC COMPETITIVE LOCAL

EXCHANGE CARRIER

CUSTOMER OWNER-OUTSIDE PLANT

DAS DISTRIBUTION ANTENNA SYSTEM

DP DEMARCATION POINT

DPS DOOR POSITION SWITCH

DVR DIGITAL VIDEO RECORDER

EAC ELECTRONIC ACCESS CONTROL

EC ELECTRICAL CONTRACTOR

EMS ENERGY MANAGEMENT SYSTEM

FM FACTORY MUTUAL

ENGINEERING CORPORATION

FOV FIELD OF VIEW

HH HANDHOLE

HMF HOLLOW METAL FRAME DOOR

IDC INSULATION DISPLACEMENT

CONNECTOR

IDS INTRUSION DETECTION SYSTEM

IP INTERNET PROTOCOL

LEC LOCAL EXCHANGE CARRIER

LBM LATCH BOLT MONITOR

MCB MAIN CIRCUIT BREAKER

MPOE MAIN POINT OF ENTRANCE

NATIONAL FIRE PROTECTION

ASSOCIATION

MANUFACTURERS ASSOCIATION

NATIONAL ELECTRICALNEMA

NFPA

NVE NETWORK VIDEO ENCODER

NVR NETWORK VIDEO RECORDER

OR OPERATOR ROOM

OPE OWNER PROVIDED ELECTRONICS

PABX PRIVATE AUTOMATIC

BRANCH EXCHANGE

PBO PROVIDE BY OTHERS

PDU POWER DISTRIBUTION UNIT

PIC PLASTIC INSULATED CABLE

POE POWER OVER ETHERNET

POP POINT OF PRESENCE

PSTN PUBLIC SWITCH TELEPHONE NETWORK

PTZ PAN-TILT-ZOOM

RQE REQUEST TO EXIT

SCTP SCREENED TWISTED PAIR

SLAB SEALED LEAD ACID BATTERY

SSI SECURITY SYSTEMS INTEGRATOR

TC TELECOMMUNICATIONS CLOSET

TVSS TRANSIENT VOLTAGE SURGE

SUPPRESSION

VOICE OVER INTERNET PROTOCOLVOIP

WIRE TRANSFER HINGEWTH

CO-OSP

SPD SURGE PROTECTIVE DEVICE

WATER GUAGEWG

ABBREVIATIONS

R

H20

CO

FIRE ALARM WIRELESS AUTOMATIC CEILING

HEAT DETECTOR

FS

F

F

WALL MOUNT WIRELESS MOTION DETECTOR

CEILING MOUNT WIRELESS MOTION DETECTOR

YELLOW INTRUSION ALARM WARNING LIGHT CEILINGYELLOW INTRUSION ALARM WARNING LIGHT WALLY IA Y IA

SP

WIRELESS RECEIVER WIRELESS REPEATERP

E19

ENLARGED SITE PLAN

E1G

SCALE: 1" = 20'-0" 20' 10' 0 20'

ELECTRICAL ENGLARGED SITE PLAN

N

INSTALL GREEN INSULATED

GROUND WIRE WITH EACH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUIT.

PROVIDE A DEDICATED NEUTRAL

CONDUCTOR FOR EACH BRANCH

CIRCUIT REQUIRING A NEUTRAL,

UNLESS OTHERWISE NOTED.

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND

CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,

SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.

LAY OUT AND COORDINATE ALL WORK PRIOR TO

INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR

OPERATION, MAINTENANCE, AND CODES AND VERIFY

NON-INTERFERENCE WITH OTHER WORK. DO NOT

FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR

ALL TRADES. READ SPECIFICATIONS.

F eb

5,

- 2

:0 5p m J:

\2

3_ Pr oje cts

\2

1\ Dw gs \ 2

1E

1G .d wg

US

ER

js an ch ez

SUB SHEET NO.

OF

DESIGNED:

RCF

DRAWN BY:

TECH. REVIEW:

DATE:

02/06/2024

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

JAS

GAN

AE# 20239961

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

FINAL CONSTRUCTION DOCUMENTS

DRAWING NO.

PMIS NO.

ONE LINE DIAGRAMS

E19

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND

CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,

SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.

LAY OUT AND COORDINATE ALL WORK PRIOR TO

INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR

OPERATION, MAINTENANCE, AND CODES AND VERIFY

NON-INTERFERENCE WITH OTHER WORK. DO NOT

FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR

ALL TRADES. READ SPECIFICATIONS.

F eb

5,

- 2

:0 8p m J:

\2

3_ Pr oje cts

\2

1\ Dw gs \ 2

1E

.d wg

US

ER

js an ch ez

SUB SHEET NO.

OF

DESIGNED:

RCF

DRAWN BY:

TECH. REVIEW:

DATE:

02/06/2024

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

JAS

GAN

AE# 20239961

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

FINAL CONSTRUCTION DOCUMENTS

DRAWING NO.

PMIS NO.

258470

425 / 80087

FLAG NOTES - DETAIL 1/E19

EXISTING FEEDER TO EXISTING CHILLER.1

ONE LINE DIAGRAM - DEMOLITION

NO SCALE

E19

EXISTING

PANEL

HS-2

BARRACKS/HOSPITAL

EXISTING 208/120V 1 PHASE

150 AMP FEEDER

E19

EXISTING PANEL

HS-1 VISITOR CENTER

EXISTING 100 AMP 208/120V.

1 PHASE PANEL 'C'

G

G,WP

EXISTING 80 KW

PORTABLE GENERATOR

EXISTING OUTPUT

BREAKER

NN

EXISTING

CONCRETE PAD

EXISTING ABANDONED

METER SOCKETS

E

N

EXISTING MANUAL

TRANSFER SWITCH

EXISTING 225/3 ENCLOSED BREAKER

VISITOR CENTER SERVICE DISCONNECT

EXISTING 200 AMP CHILLER

SERVICE DISCONNECT

EXISTING SIX

CIRCUIT PANEL

EXISTING WIREWAY 4

2(TYP)

EXISTING UNDERGROUND SECONDARY

ELECTRICAL 4 #250 KCMIL IN EACH OF TWO 4"C

EXISTING

METERING

EXISTING UNDERGROUND

PRIMARY ELECTRICAL

EXISTING

CONCRETE PAD

EXISTING MID WEST ENERGY

300 KVA 208/120V PAD

MOUNTED TRANSFORMER

REMOVE EXISTING 4 #250 KCMIL CONDUCTORS FROM

EXISTING 4"C EXISTING CONDUIT TO REMAIN. REFER TO

DETAIL 2/E19 FLAG NOTE 10 FOR NEW CONDUCTORS

EXISTING IN GROUND UNISTRUT.2

3 EXISTING 120V. CIRCUITS TO EXISTING GENERATOR.

4 DISCONNECT EXISTING GROUNDED CONDUCTORS AND REMOVE EXISTING

GROUNDING LUG. PROVIDE A NEW GROUND BAR AND RECONNECT EXISTING

GROUNDED CONDUCTORS.

5 EXISTING PANEL TUB AND DOOR TO REMAIN AND BE CONVERTED INTO A JUNCTION

BOX.

6 REMOVE EXISTING 225 AMP INTERNAL PANEL WITH 1-100/3, 1-150/2, 1-20/3 BREAKERS

AND SUB FEED LUGS. DISCONNECT EXISTING FEEDERS AND BRANCH CIRCUIT

WIRING.

7 REMOVE 4 #250 KCMIL CONDUCTORS.

8 REMOVE EXISTING 225 AMP INTERNAL PANEL WITH 1-100/3, 1-50/2, 2-30/2, 1-20/2,

35-20/1, AND 1-20/1 GFCI BREAKERS. DISCONNECT EXISTING BRANCH CIRCUIT

WIRING.

9 REMOVE EXISTING SURGE PROTECTIVE DEVICE.

10 REMOVE EXISTING 100 AMP FEEDER CONDUCTORS. EXISTING CONDUIT TO REMAIN.

ONE LINE DIAGRAM - NEW WORK

NO SCALE

E19

EXISTING 208/120V

1 PHASE PANEL

HS-2

BARRACKS/HOSPITAL

EXISTING 150 AMP FEEDER

CONDUCTORS RECONNECTED TO NEW

125/2 BREAKER IN NEW PANEL 'VC'

HS-1 VISITOR CENTER 1ST FLOOR

(TYP)

(TYP)

(TYP)

2ND FLOOR

125F3

12-20F2

20,30,50F2

8 (TYP)

12-20F2

100F3

12-20F2

225F4

9 (TYP)

NEW PANEL 'VC'

EXISTING

PANEL TUB

100F3E

CELLAR

225F4

GROUND BAR

E21

SERVICE GROUNDING

E21

NEW 225/3, 18,000 A.I.C.

ENCLOSED BREAKER

NEMA 4X ENCLOSURE

FLAG NOTES - DETAIL 2/E19

1 PROVIDE A GROUND BAR ATTACHED TO EXISTING PANEL TUB. CONNECT THE TWO

GROUND BARS TOGETHER WITH #4 GREEN INSULATED GROUND WIRE. CONNECT

NEW AND EXISTING BRANCH CIRCUIT GROUND WIRES TO THE NEW GROUND BAR.

2 PROVIDE A #4 GREEN INSULATED GROUND TO GROUND BAR IN NEW PANEL 'VC',

ROUTE GROUND WIRE WITH NEW 225F4 FEEDER.

3 PROVIDE NEW 2 1/2" CONDUIT NIPPLE WITH A BUSHING ON EACH END.

4 PROVIDE BUSHING ON EACH END OF EXISTING 4" NIPPLE.

5 PROVIDE INSULATED BUSHING ON NEW AND EXISTING CONDUITS 1" AND LARGER

INSIDE EXISTING PANEL TUB.

6 SPLICE NEW BRANCH CIRCUIT CONDUCTORS TO EXISTING CONDUCTORS.

7 NEW CONDUCTORS INSIDE EXISTING PANEL TUB ARE NOT INSTALLED IN CONDUIT.

8 NEW CONDUITS ON 2ND FLOOR CAN BE FLEXIBLE GALVANIZED STEEL CONDUIT OR

LIQUID TIGHT FLEXIBLE CONDUIT IN ORDER TO ROUTE AROUND EXISTING DUCT

WORK. PROVIDE STRAPPING PER NEC REQUIREMENTS.

9 PROVIDE CORE DRILLING OF EXISTING CONCRETE FLOOR FOR NEW CONDUITS.

PROVIDE FIRE CAULKING AFTER CONDUITS ARE INSTALLED.

10 PROVIDE 4 #250 KCMIL 1 #2 INSULATED GREEN GROUND WIRE IN EXISTING 4"C TO

EXISTING OUTDOOR MANUAL TRANSFER SWITCH.

11 DO NOT BOND NEUTRAL AND GROUND TOGETHER.

11 PROVIDE A NEW 10'X3/4" COPPERCLAD DRIVEN GROUND ROD.

FOR NEW

REQUIRED WORK

PROVIDE #6 GROUND

IN 1/2"C

EXISTING FEEDER

12 PUNCH OUT HOLES ON TOP OF EXISTING PANEL TUB FOR NEW CONDUIT FITTINGS.

12(TYP)

EXISTING

PANEL 'C'

PROVIDE A DEDICATED NEUTRAL

CONDUCTOR FOR EACH BRANCH

CIRCUIT REQUIRING A NEUTRAL,

UNLESS OTHERWISE NOTED.

1. KEEP ELECTRICAL POWER OUTAGE TO 48 HOURS MAXIMUM.

GENERAL NOTES

2. COORDINATE POWER OUTAGES WITH CONTRACTING OFFICER OR CONTRACTING

OFFICER REPRESENTATIVE.

30F4

100F4

13 PROVIDE A SURGE PROTECTIVE DEVICE.

14 REMOVE AND REPLACE DRYWALL IN KITCHEN/BREAK ROOM 124 IN ORDER TO

INSTALL NEW CONDUIT. PRIME AND PAINT THE NORTH WALL TO MATCH EXISTING.

15 MOUNT PANEL ON NEW WALL MOUNTED UNISTRUT.

16 FILL IN VOID UNDER EXISTING PANEL WITH EXPANDING FOAM. TRIM EXCESS FOAM

FROM OUTER SURFACE.

17 SEAL ENDS OF CONDUITS.

UP

LIBRARY

KITCHEN/

BREAK

STAIR

DN

ATTIC

CHIMNEY

T

G

VC-59

UP

CELLAR

C01

CELLAR

C02

KEY NOTES

ENLARGED HS-1

E20

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

ENLARGED HS-1 ELECTRICAL CRAWL

SPACE PLAN - CELLAR C02

N

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

ENLARGED HS-1 ELECTRICAL PLAN -

KITCHEN/BREAK 124

N

SCALE: 1/4" = 1'-0" 4' 2' 0 4'

ENLARGED HS-1 ELECTRICAL ATTIC PLAN -

ATTIC 200

N

PLAN TRUE

N

PLAN TRUE

N

PLAN TRUE

N

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND

CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,

SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.

LAY OUT AND COORDINATE ALL WORK PRIOR TO

INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR

OPERATION, MAINTENANCE, AND CODES AND VERIFY

NON-INTERFERENCE WITH OTHER WORK. DO NOT

FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR

ALL TRADES. READ SPECIFICATIONS.

F eb

5,

- 2

:0 8p m J:

\2

3_ Pr oje cts

\2

1\ Dw gs \ 2

1E

.d wg

US

ER

js an ch ez

SUB SHEET NO.

OF

DESIGNED:

RCF

DRAWN BY:

TECH. REVIEW:

DATE:

02/06/2024

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

JAS

GAN

AE# 20239961

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

FINAL CONSTRUCTION DOCUMENTS

DRAWING NO.

PMIS NO.

258470

425 / 80087

INSTALL GREEN INSULATED

GROUND WIRE WITH EACH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUIT.

PROVIDE A DEDICATED NEUTRAL

CONDUCTOR FOR EACH BRANCH

CIRCUIT REQUIRING A NEUTRAL,

UNLESS OTHERWISE NOTED.

PLANS

NOTE:

DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND

CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,

SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.

LAY OUT AND COORDINATE ALL WORK PRIOR TO

INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR

OPERATION, MAINTENANCE, AND CODES AND VERIFY

NON-INTERFERENCE WITH OTHER WORK. DO NOT

FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR

ALL TRADES. READ SPECIFICATIONS.

F eb

5,

- 2

:0 8p m J:

\2

3_ Pr oje cts

\2

1\ Dw gs \ 2

1E

.d wg

US

ER

js an ch ez

SUB SHEET NO.

OF

DESIGNED:

RCF

DRAWN BY:

TECH. REVIEW:

DATE:

02/06/2024

SHEET

TITLE OF SHEETA/E FIRM

PRIME:

KENNETH HAHN

ARCHITECTS, INC.

OMAHA, NE.

SUBCONTRACTOR:

ALVINE

ENGINEERING

OMAHA, NE.

JAS

GAN

AE# 20239961

ELECTRICAL DISTRIBUTION PANEL

FORT LARNED NATIONAL HISTORIC SITE

PAWNEE COUNTY, KANSAS

FINAL CONSTRUCTION DOCUMENTS

DRAWING NO.

PMIS NO.

258470

425 / 80087ELECTRICAL DETAILS AND

SCHEDULES

E21

PANEL VC

208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED COPPER BUS

225 AMP MLO COPPER LUGS

10,000 AIC COPPER GROUND BAR

72 POLES ONE SECTION

DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION

EXISTING LOAD 20/1 1 A 2 20/1 EXISTING LOAD

EXISTING LOAD 20/1 3 B 4 20/1 EXISTING LOAD

EXISTING LOAD 20/1 5 C 6 20/1 EXISTING LOAD

EXISTING LOAD 20/1 7 A 8 20/1 EXISTING LOAD

EXISTING LOAD 20/1 9 B 10 20/1 EXISTING LOAD

EXISTING LOAD 20/1 11 C 12 20/1 EXISTING LOAD

EXISTING LOAD 20/1 13 A 14 20/1 EXISTING LOAD

EXISTING LOAD 20/1 15 B 16 20/1 EXISTING LOAD

EXISTING LOAD 20/1 17 C 18 20/1 EXISTING LOAD

EXISTING LOAD 20/1 19 A 20 20/1 EXISTING LOAD

EXISTING LOAD 20/1 21 B 22 20/1 EXISTING LOAD

EXISTING LOAD 20/1 23 C 24 20/1 EXISTING LOAD

EXISTING LOAD 20/1 25 A 26 20/1 EXISTING LOAD

EXISTING LOAD 20/1 27 B 28 20/1 EXISTING LOAD

EXISTING LOAD 20/1 29 C 30 20/1 EXISTING LOAD

EXISTING LOAD 20/1 31 A 32 20/1 EXISTING LOAD

EXISTING LOAD 20/1 33 B 34 20/1 GFCI EXISTING LOAD

FIRE ALARM 100 1 20/1 35 C 36 20/1 EXISTING LOAD

EXISTING LOAD 30/2 37 A 38 20/1 1 1200 FIRE ALARM PANEL

- - 39 B 40 20/1 1 1000 INTRUSION ALARM PANEL

EXISTING LOAD 30/2 41 C 42 20/2 EXISTING LOAD

- - 43 A 44 - -

EXISTING LOAD 50/2 45 B 46 100/2 EX. PANEL 'C'

- - 47 C 48 - -

SPARE 20/3 49 A 50 100/3 EXISTING LOAD

- - 51 B 52 - -

- - 53 C 54 - -

F.A. DUCT DETECTOR 75 20/1 55 A 56 20/1 GFCI SPARE

IT RACK PDU 1200 20/1 57 B 58 20/1 GFCI SPARE

ATTIC RECEPT 180 20/1 59 C 60 20/1 SPARE

SPARE 20/1 61 A 62 20/1 SPARE

SPARE 20/1 63 B 64 20/1 SPARE

SPARE 20/1 65 C 66 20/1 SPARE

SURGE PROTECTOR 20/3 67 A 68 20/1 SPARE

- - 69 B 70 125/2 EX BLDG HS-2

- - 71 C 72 - -

E21

COPPER GROUND BAR

2" HIGH INSULATORS (TYP FOR 2)

MOUNTING BOLT WITH

LOCK WASHER (TYP)

COPPER GROUND BAR

BOLT TO WALL

WALL MOUNTING BRACKET

ANCHOR BOLTS

MAIN

GROUND BAR

GROUND BAR

NO SCALE

SECTION

ISOMETRIC VIEW

GROUND BAR SCHEDULE

NOMINAL SIZE ERICO CAT #MARK

EGBA14420CCT1/4" x 4" x 20"

E21

E21

TO EXISTING I.T. PRIMARY BONDING

BUSBAR AT EXISTING I.T. RACK IN

KITCHEN/BREAK ROOM 124

MAIN GROUND BAR

#2, 3/4"C TO STREET SIDE

OF WATER METER

#6, 3/4"C TO GROUND ROD

225/3 ENCLOSED BREAKER

SERVICE EQUIPMENT

GROUNDED CONDUCTOR

(NEUTRAL)

BOND CONDUIT TO

GROUND BUS (TYP FOR

METAL CONDUIT)

SERVICE CONDUIT

BOND CONDUIT TO GROUND BAR OR TO

GROUNDING ELECTRODE CONDUCTOR;

MATCH SIZE OF GROUNDING

ELECTRODE CONDUCTOR (TYP FOR

METAL CONDUIT)

SERVICE GROUNDING

NO SCALE

BOND CONDUIT TO GROUNDING

ELECTRODE OR TO GROUNDING

ELECTRODE CONDUCTOR; MATCH SIZE OF

GROUNDING ELECTRODE CONDUCTOR

(TYP FOR METAL CONDUIT)

NEUTRAL BUS

GROUND BUS

#2, 3/4"C

#2, 3/4"C

FEEDER AND BRANCH CIRCUIT

SCHEDULE

MARK CONDUCTORS AND CONDUIT

2 WIRE PLUS GROUND

12-20F2 24 #8, 1 #8 GND. 2"C.

20,30,50F2 2 #10, 4 #8, 2 #6, 1 #6 GND. 1-1/4"C.

3 WIRE PLUS GROUND

100F3 3 #2, #8 GND. 1-1/4" C.

100F3E 3 #2, #8 GND. IN EXISITNG CONDUIT

125F3 3 #1, #6 GND. 1-1/2" C.

4 WIRE PLUS GROUND

30F4 4 #10, #10 GND. 3/4" C.

100F4 4 #2, #8 GND. 1-1/4" C.

225F4 4 #4/0, #4 GND. 2-1/2" C.

REMARKS

1. PROVIDE A BREAKER HANDLE LOCK.

PROVIDE LUGS

DO NOT BOND NEUTRAL

AND GROUND

Sheets and Views
02_FOLS_C1-C1
03_FOLS_C2-C2
04_FOLS_C3-C3
05_FOLS_C4-C4
06_FOLS_C5-C5
07_FOLS_C6-C6
08_FOLS_C7-C7
09_FOLS_A1 Photo Sheet-A1
10_FOLS_A2 Photo Sheet-A2
11_FOLS_A3 HS-1-A3
12_FOLS_A4 HS-2-A4
13_FOLS_A5 HS-3-4-A5
14_FOLS_A6 HS-5-A6
15_FOLS_A7 HS-6-A7
16_FOLS_A8 HS-7-A8
17_FOLS_A9 HS-8-A9
18_FOLS_A10 HS-9-A10
19_FOLS_A11 HS-10 - MAINT-A11

[1] COVER SHEET

File details come from the government source that posted it. Updated .