B08_Solicitation_-_Att_2_-_Drawings_DistributionPanel_FOLS_258470.pdf
PDF 2 MB Posted
- Attached to
- FOLS, Replace Alarm System & Electrical Panel Federal contract opportunity
- Solicitation number
- 140P6026Q0042
About this file
This document is a Final Construction Documents package for the Electrical Distribution Panel replacement project at Fort Larned National Historic Site in Pawnee County, Kansas. The project involves replacing the existing electrical distribution infrastructure at the Visitor Center (HS-1) building.
The scope of work includes installation of a new 225-ampere, 208/120-volt, 3-phase electrical panel with a new 225-ampere enclosed breaker as service equipment in a NEMA 4X enclosure. The project requires relocation of the electrical panel from the cellar to the kitchen/break room on the first floor, installation of new underground electrical feeder conductors in existing conduit, and conversion of the existing panel into a junction box. The work encompasses new conduit installation, ground bar installation with dedicated grounding to a new 10-foot copperclad ground rod, new branch circuit wiring throughout the building (including 72-pole capacity with mixed amperage breakers), feeder connections to existing buildings HS-2, fire alarm panel installation, and intrusion alarm panel installation. All work must maintain electrical power outages to a maximum of 48 hours and coordinate with the Contracting Officer and Contracting Officer Representative. The project requires coordination with a National Park Service-designated archaeologist for any ground disturbance activities and restoration of disturbed areas including pathways, seeding, and utility repair at no additional government expense. Kenneth Hahn Architects, Inc. serves as the prime A/E firm with Alvine Engineering as subcontractor; the PMIS number is 258470 with drawing number AE# 20239961.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6026Q0042_Amd_0002.pdf | ||
| Sol_140P6026Q0042_Amd_0001.pdf | ||
| Sol_140P6026Q0042.pdf | ||
| B08_Solicitation_-_Att_1_-_Specifications_DistributionPanel_FOLS_258470.pdf | ||
| B08_Solicitation_-_Att_3_DOL_Wage_Determination_KS20260044.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAWNEE RIVER
PAWNEE RIVER
HIGHWAY 156
FORT LARNED NATIONAL HISTORIC SITE
STEPHEN R. SMITH, AIA
KENNETH HAHN ARCHITECTS, INC.
ARCHITECT
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Registered Architect under the laws of the State of Kansas.
Pages or Sheets covered by this seal: TS1, C1, C2, C3, C4, C5, C6, C7, A1, A2, A3, A4, A5, A6, A7, A8, A9, A10, A11.
2/6/2024
AREA MAP-
FT. LARNED NATIONAL HISTORIC SITE
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
BRANDON D. RICH
License Number 29677 My license renewal date is April 30, 2025
(date)
Pages or sheets covered by this seal:
02/06/2024
E0, ED1, ED2, ED3, ED4, ED5, ED6, ED7, ED8,
ED9, E1, E1A, E1B, E1C, E1D, E1E, E1F, E1G,
E2, E3, E4, E5, E6, E7, E8, E9, E10, E11, E12, E13, E14, E15, E16, E17, E18, E19, E20, E21.
Kansas.
20. E0 ELECTRICAL SYMBOLS AND ABBREVIATIONS
https://ksbtp.ks.gov/statutes-rules/seal-sig-faq
HS-1 - VISITOR CENTER
HS-2
MANHOLE
WATER METER
HS-3
WELL
MANHOLE
HS-9WELL
FENCE
HS-8
MANHOLE
LEECHFIELD
WELL
DRAIN TILE
DAYLIGHT
C7
C7
C7
C7
SITE PLAN GENERAL NOTES
1. A NATIONAL PARK SERVICE DESIGNATED
ARCHEOLOGIST MUST BE ON SITE DURING ANY
GROUND DISTURBANCE ACTIVITIES. SCHEDULE AND
COORDINATE WITH CO/COR. SEE DIVISION 1.
2. PREP ALL AREAS DISTURBED BY THIS PROJECT FOR
SEEDING BY NPS. PREP AREA BY FINE GRADING AND
RAKING AREA TO A FIRM EVEN SURFACE, FREE FROM
LUMPS, STONES OR CLUMPS 1-INCH OR MORE IN ANY
DIMENSION.
DISTURBED AREAS INCLUDE BUT ARE NOT LIMITED TO;
TRENCHING ACTIVITIES, BORING ACTIVITIES,
CONTRACTOR VEHICLE TRAFFIC WEAR.
3 REPAIR ALL EXISTING STABILIZED PATHWAYS
DISTURBED BY THIS PROJECT. DISTURBED AREAS
INCLUDE BUT AREA NOT LIMITED TO; TRENCHING
ACTIVITIES, BORING ACTIVITIES, CONTRACTOR
VEHICLE TRAFFIC WEAR.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING
AND PREVENTING DAMAGE TO KNOWN UTILITIES. IF
CONTRACTOR DAMAGE OCCURS, ALERT CO AND COR
AS SOON AS SAFELY POSSIBLE, AND REPAIR UTILITY
AT NO ADDITIONAL EXPENSE TO THE GOVERNMENT. IF
DAMAGE OCCURS TO AN UNKNOWN UTILITY, CONTACT
CO AND COR AS SOON AS SAFELY POSSIBLE. SEE
DIVISION 1.
5 LIMITS OF CONSTRUCTION SHALL BE WITHIN 10' OF
TRENCH CENTER LINE AND AS PER DIVISION 1.
6 CONTRACTOR TO PROVIDE GIS/GPS SHAPE FILES, PER
NPS REQUIREMENTS, FOR ALL EXISTING UTILITIES
PHYSICALLY ENCOUNTERED DURING THIS PROJECT.
7. SEE ELECTRICAL DRAWINGS FOR AS-BUILT
DOCUMENTATION REQUIREMENTS FOR ALL
UNDERGROUND WORK INSTALLED AS PART OF THIS
PROJECT.
EXISTING ELECTRICAL
EXISTING WATER
EXISTING PHONE
EXISTING SEWER
EXISTING GAS
EXISTING AC LINE
EXISTING AT & T
EXISTING UNKNOWN UTILITY
EXISTING SECURITY
EXISTING DRAIN TILE
LEGEND
EXISTING UTILITY PLAN GEN. NOTES
1. THIS EXISTING UTILITY PLAN IS FOR INFORMATION
ONLY, AND MAY NOT BE REPRESENTATIVE OF
CONDITIONS ENCOUNTERED.
2. ALL EXISTING UTILITIES SHOWN ARE APPROXIMATE
LOCATIONS BASED ON INFORMATION OBTAINED FROM
NPS. THIS EXISTING UTILITIES PLAN MAY NOT SHOW
ALL UTILITIES THAT MAY EXIST ON SITE. CONTRACTOR
SHALL USE CAUTION DURING GROUND DISTURBANCE
ACTIVITIES AS THEY MAY ENCOUNTER CONDITIONS
NOT SHOWN ON THESE DRAWINGS.
ENLARGED SITE PLAN AND
C2
0SCALE: 1" = 40'-0" 40' 20' 40'
ENLARGED SITE PLAN AND EXISTING UTILITIES PLAN
N
EXISTING UTILITIES PLAN
F e b a m
C
T o d d A
K
H A w o r k
F t
L a r n e d D
R A
W I N
G S
F
O L S
C d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
DRAWN BY:
TECH. REVIEW:
DATE:
2/6/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
258470
425 / 80087
LIBRARY
KITCHEN/
BREAK
MEN
OFFICE
MUSEUM
VEIWING
ROOM
UP
OFFICE
OFFICE
ENTRY
OPEN
OFFICE
OFFICE
OFFICE
ENTRY
OFFICE
CLOS.
MEN
WOMEN
MUSEUM
SHOP
WOMEN
117 CLOS.
HALL
CLOS.
HALL
PIPE CHASE
HALL
STAIR
EXISTING WINDOW
WELL
ATTIC
DN
WALKWAYWALKWAY
ATTIC
ATTIC
CHIMNEY
CHIMNEY
CHIMNEYCHIMNEY CHIMNEY
CELLAR
C01
CELLAR
C02
UP UPEXISTING
WINDOW WELL
HS-1
FLOOR PLANS
A3SCALE: 1/8" = 1'-0" 8' 4' 0 8'
HS-1 FLOOR PLAN
N
PLAN TRUE
N
GENERAL NOTES
G1. PATCH/REPAIR/PAINT CEILING/WALL
FINISHES AS REQUIRED TO MATCH
ADJACENT AREA WHERE NEW
DEVICES DON'T COMPLETELY
COVER OLD DEVICE LOCATIONS.
G2. WHERE PAINTING IS REQUIRED DUE
TO REMOVAL/ PATCHING; PAINT
ENTIRE CEILING/ WALL PLANE
CORNER TO CORNER, EDGE TO
EDGE. PAINT COLOR AND FINISH TO
MATCH ADJACENT CEILING/ WALL.
G3 PATCHING MATERIAL SHALL MATCH
EXISTING CONDITIONS (ie: DRYWALL
/DRYWALL MUD AT EXIST. DRYWALL,
PLASTER AT EXISTING PLASTER
WALLS, ETC.)
G4. INSTALL SURFACE MOUNTED
CONDUIT IN A NEAT AND ORDERLY
MANNER. DO NOT RUN CONDUIT
DIAGONALLY. SEE ELECTRICAL
DRAWINGS AND SPECIFICATIONS.
G5. PAINT EXPOSED CONDUIT AND
FITTINGS TO MATCH ADJACENT
SURFACE. PAINT FLAT BLACK AT
EXPOSED RAFTERS/WOOD DECK.
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
HS-1 ATTIC PLAN
N
PLAN TRUE
N
SCALE: 1/8" = 1'-0" 8' 4' 0 8'
HS-1 CRAWL SPACE PLAN
N
PLAN TRUE
N
F e b a m
C
T o d d A
K
H A w o r k
F t
L a r n e d D
R A
W I N
G S
F
O L S
A
H
S d w g
U
S E
R t o d d
SUB SHEET NO.
OF
DESIGNED:
KJH
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
DRAWN BY:
TECH. REVIEW:
DATE:
2/6/2024
DRAWING NO.
PMIS NO.
SHEET
TITLE OF SHEET
A/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
TWM
CLZ
FINAL CONSTRUCTION DOCUMENTS
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND
CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.
LAY OUT AND COORDINATE ALL WORK PRIOR TO
INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR
OPERATION, MAINTENANCE, AND CODES AND VERIFY
NON-INTERFERENCE WITH OTHER WORK. DO NOT
FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR
ALL TRADES. READ SPECIFICATIONS.
F eb
5,
- 2
:0 3p m J:
\2
3_ Pr oje cts
\2
1\ Dw gs \ 2
1E
0.
dw g
- U
SE
R jsa nc he z
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
02/06/2024
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
GAN
AE# 20239961
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
FINAL CONSTRUCTION DOCUMENTS
DRAWING NO.
PMIS NO.
258470
425 / 80087ELECTRICAL SYMBOLS AND
ABBREVIATIONS
E0
CARBON MONOXIDE DETECTOR
ELECTRICAL SYMBOLS
FIBER OPTIC CABLE
("#" INDICATES NUMBER OF STRANDS
"T" INDICATES TYPE AND
"X" INDICATES CABLE NAME)
COMBINATION DATA/AV FLOOR OUTLET
("#" INDICATES DEVICE TYPE IN SCHEDULE)
CABLE SLACK
("X" INDICATES SLACK LENGTH)
CABLE PROTECTOR
("XXX" INDICATES NUMBER OF PROTECTORS)
AV GEAR BOX, REFER TO
SCHEMATICS AND SPECS
UNSHIELDED TWISTED PAIR COPPER CABLE -
"C" INDICATES CATEGORY NUMBER
"#" INDICATES NUMBER OF PAIRS
"G" INDICATES AWG, "X" INDICATES CABLE NAME
CROSS-CONNECT FIELD
SPLICE
MECHANICAL TERMINATION OF CABLE
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
TELECOMMUNICATIONS
#-T X
XXX
X C-#-G X
COMMUNICATIONS OUTLET CEILING COMMUNICATIONS OUTLET FLOOR COMMUNICATIONS OUTLET
MUTOA - MULTI-USER TELECOMMUNICATIONS
OUTLET ASSEMBLYSPECIAL SERVICES COMMUNICATIONS OUTLET
WIRELESS ACCESS POINT
("#" INICATES QUANTITY OF ANTENAS)
AV
GROUND BAR
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
PATHWAYS
CONDUIT SLEEVE WITH BUSHINGS DISTRIBUTION RINGS
WALL MOUNT TELECOMMUNICATIONS EQUIPMENT J-HOOK STYLE CABLE HANGERS CABLE TRAY DROP OUT
CABLE TRAY
("#" INDICATES TRAY DIMENSIONS)
CABLE RUNWAY
("#" INDICATES TRAY DIMENSIONS)
CABLE TRAY - SOLID BOTTOM
("#" INDICATES TRAY DIMENSIONS)
CABLE TRAY - WALL MOUNTED
("#" INDICATES TRAY DIMENSIONS)
EQUIPMENT RACK
("#" INDICATES RACK NO. AND FRONT OF RACK)#
FIRE ALARM AUTOMATIC SMOKE DETECTOR
WIRELESS GATEWAY
FIRE ALARM LOW FREQUENCY SOUNDER
FIRE ALARM WIRELESS AUTOMATIC SMOKE DETECTOR
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM AUTOMATIC WALL SMOKE DETECTOR
CEILING FIRE ALARM HORN AND LIGHT COMBINATION
(# INDICATES CANDELA RATING)
FIRE ALARM CONTROL PANEL
FIRE ALARM AUTOMATIC CEILING HEAT DETECTOR
FIRE ALARM AUTOMATIC WALL HEAT DETECTOR
FIRE ALARM MANUAL STATION
FIRE ALARM CONTROL MODULE
CEILING FIRE ALARM LIGHT
(# INDICATES CANDELA RATING)
WALL FIRE ALARM LIGHT
(# INDICATES CANDELA RATING) SAMPLING TUBE TYPE SMOKE DETECTOR
ASPIRATING SMOKE DETECTION
SAMPLING PORT AND TUBING
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
FIRE DETECTION AND ALARM
F
F CM
F
F #
F
F #
FAA
FACP
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SUBSCRIPTS
SUBSCRIPT "E" ADDED TO ANY SYMBOL
INDICATES EXISTING
SUBSCRIPT "PD" ADDED TO ANY FLOOR OUTLET
INDICATES PEDESTAL MOUNTED
SUBSCRIPT "K" ADDED TO ANY SYMBOL
INDICATES KEY OPERATED
SUBSCRIPT "WG" ADDED TO ANY SYMBOL
INDICATES WIRE GUARD
SUBSCRIPT "P" ADDED TO ANY SYMBOL
INDICATES PILOT LIGHT
SUBSCRIPT "AC" ADDED TO ANY SYMBOL INDICATES ABOVE COUNTER. LOCATE CENTER OF DEVICE 4" ABOVE COUNTER SURFACE OR WHERE PRESENT, 4" ABOVE BACKSPLASH.
WHERE INDICATED ADJACENT TO LAVATORY WITHOUT COUNTER, LOCATE CENTER OF DEVICE 8" ABOVE RIM OF LAVATORY.
EP
E
PD
AC
K
WG
P
RT WP
SUBSCRIPT "RT" APPLIED TO ANY SYMBOL
INDICATES RAIN TIGHT NEMA 3R
OR EQUIVALENT
SUBSCRIPT "WP" APPLIED TO ANY SYMBOL
INDICATES WEATHERPROOF NEMA TYPE 4
OR EQUIVALENT
SUBSCRIPT "EP" APPLIED TO ANY SYMBOL
INDICATES EXPLOSION PROOF,
CLASS, GROUP AND DIVISION AS NOTED
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SECURITY
WALL MOUNT MOTION SENSOR
CEILING MOUNT MOTION SENSOR
SOUNDER
STROBE
POINT OF CONNECTION FOR 120VAC BY
ELECTRICAL CONTRACTOR
GLASS BREAK SENSOR
INTERCOM STATION
("S" SUBSTATION, "M" MASTER STATION)
JUNCTION BOX FOR SPECIALTY SECURITY SENSOR
DOME CAMERA
("#" INDICATES NUMBER IN SPECIFICATIONS)
SECURITY KEYPAD DEVICE
REMOTE ANNUNCIATOR DEVICE
DOOR LOCK POWER SUPPLY
PTZ DOME CAMERA
("#" INDICATES NUMBER IN SCHEDULE)
SECURITY EQUIPMENT CABINET(S), TYPE AND
QUANTITY MAY VARY FROM WALL MOUNTED,
FREE STANDING RACKS, OR EXTERIOR RATED,
REFER TO DETAILS
KEY SWITCH
REQUEST TO EXIT DEVICE
("M" MOTION SENSOR, "P" PUSH BUTTON)ACCESS CONTROL DEVICE LOCATION
"M" INDICATES MULLION MOUNT
ELECTRONICALLY CONTROLLED AND
MONITORED DOOR LOCATION
(REFER TO ACCESS CONTROL OPENING SCHEDULE)
WIRELESS DOOR POSITION SWITCH
AUTOMATIC OPERATOR CONNECTION POINT
('G' GATE, 'D' DOOR)
SECURITY PUSH BUTTON - ("P/D" INDICATES
PANIC ALARM OR DOOR RELEASE)
M
P/D
J S
IC S,M
GB
E
G,D
PS
RA
KP
KS
RQE M,P
SEC
DESCRIPTIONSYMBOLSYMBOL DESCRIPTION SYMBOL DESCRIPTION
LIGHTING AND POWER
BRANCH CIRCUIT EXPOSED
BRANCH CIRCUIT -
CONCEALED IN CEILING OR WALL
BRANCH CIRCUIT - CONCEALED IN FLOOR
(UNDERGROUND IF EXTERIOR)
SPECIAL PURPOSE HOMERUN AS INDICATED
HOMERUN TO PANEL (NUMBER OF ARROWS
INDICATES NUMBER OF CIRCUITS)
CIRCUIT DOWN
SIMPLEX RECEPTACLE
CORD AND PLUG
PULL BOX
CEILING MOUNTED DUPLEX RECEPTACLE
POLE LUMINAIRE(S)
(# INDICATES FIXTURE NUMBER IN SCHEDULE)
ABOVE GRADE FIXTURE
(# INDICATES FIXTURE NUMBER IN SCHEDULE)
LIGHTING PANEL - FLUSH MOUNTED
TRANSFORMER
ENCLOSED CIRCUIT BREAKER
SAFETY SWITCH
(FUSED UNLESS OTHERWISE NOTED)
WALL MOUNTED JUNCTION BOX
JUNCTION BOX
("F" INDICATES FLOOR, "C" INDICATES CEILING)
T
PB J
J XCIRCUIT BREAK
CIRCUIT UP
CONDUIT STUB OUT
STRIP LIGHT
(# INDICATES FIXTURE NUMBER IN SCHEDULE)
LIGHTING PANEL - SURFACE MOUNTED
SINGLE POLE SWITCH
G,T,U
DUPLEX RECEPTACLE
"G" SUBSCRIPT INDICATES GFCI, "T" SUBSCRIPT
INDICATES TAMPER RESISTANT TYPE, "U" SUBSCRIPT
INDICATES COMBINATION USB CHARGING STATION
SYMBOLS INDICATED HERE AND NOT USED IN THE
CONTRACT DOCUMENTS DO NOT APPLY TO THIS
PROJECT. ADDITIONAL SYMBOLS AND ABBREVIATIONS
MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
FIRE ALARM WIRELESS MANUAL STATION
FIRE ALARM HORN AND LIGHT COMBINATION
WATER DETECTOR
BLDG BUILDING
BTUH BRITISH THERMAL UNIT PER HOUR
C CONDUIT
CAB CABINET
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CLR CLEAR
CRAC COMPUTER ROOM AIR CONDITIONER
CV CONSTANT VOLUME
DD DOUBLE DUCT
DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EL ELEVATION
EHC ELECTRIC HEATING COIL
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FB FLOOR BOX
FL FLOOR
FLA FULL LOAD AMPS
FMG FACTORY MUTUAL GLOBAL
FT FEET
PWR POWER
PVC POLYVINYL CHLORIDE
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
PRV PRESSURE REGULATING VALVE
PP PATCH PANEL
PNL PANEL
PLBG PLUMBING
PIV POST INDICATOR VALVE
RM ROOM
RH RELATIVE HUMIDITY
REQD REQUIRED
RLFA RELIEF AIR
RA RETURN AIR
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UL UNDERWRITERS LABORATORY
UG UNDERGROUND
(TYP) TYPICAL
TV TELEVISION
TEMP TEMPERATURE
TEL TELEPHONE
TELECOM TELECOMMUNICATIONS
SWGR SWITCHGEAR
SWBD SWITCHBOARD
SW SWITCH
STD STANDARD
SS STAINLESS STEEL
SPECS SPECIFICATIONS
(SIM) SIMILAR
SCH SCHEDULE
SAN SANITARY
SA SUPPLY AIR, SOUND ATTENUATOR
KV KILOVOLT
NC NORMALLY CLOSED
MTG MOUNTING
MTD MOUNTED
MISC MISCELLANEOUS
(MIN) MINIMUM
MECH MECHANICAL
(MAX) MAXIMUM
MA MAKEUP AIR
LTG LIGHTING
LBS POUNDS
LAN LOCAL AREA NETWORK
KW KILOWATT
KVA KILOVOLT AMPERE
OC ON CENTER
OA OUTSIDE AIR
NTS NOT TO SCALE
NOM NOMINAL
NO NORMALLY OPEN
NIC NOT IN CONTRACT
NEC NATIONAL ELECTRICAL CODE
GA GAUGE
J-BOX JUNCTION BOX
HVAC HEATING, VENTILATING
HTG HEATING
HP HORSEPOWER, HEAT PUMP
HGT HEIGHT
GPM GALLONS PER MINUTE
GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GEN GENERATOR
GALV GALVANIZED
AND AIR CONDITIONING
ELEC ELECTRICAL
DIA
CPVC CHLORINATED POLYVINYL CHLORIDE
CT COOLING TOWER, CABLE TRAY
DX DIRECT EXPANSION
EPO EMERGENCY POWER OFF
F FIRE WATER
FCO FLOOR CLEAN OUT
FDC FIRE DEPARTMENT CONNECTION
FHC FIRE HOSE CABINET
FURN FURNISHED
FW FILTERED WATER
G GAS
GC GENERAL CONTRACTOR
HW HOT WATER
HWC HOT WATER CIRCULATING
MAU MAKEUP AIR UNIT
MBH 1000 BTU/HOUR
MXA MIXED AIR
NPW NON-POTABLE WATER
PS PLASTER SINK
PTAC PACKAGED TERMINAL AIR CONDITIONER
RO REVERSE OSMOSIS WATER
RPBFP REDUCED PRESSURE BACKFLOW
SCW SOFT COLD WATER
SM SPRINKLER MAIN, SINGLE MODE
SSS SURGEON SCRUB SINK
SSD SUB SOIL DRAIN
ST STORM
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS'
T TRANSFORMER
BICSI BUILDING INDUSTRY CONSULTING
BTU BRITISH THERMAL UNIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CM COMMUNICATIONS CABLE
CMP COMMUNICATIONS PLENUM CABLE
CMR COMMUNICATIONS RISER CABLE
COAX COAXIAL CABLE
EMD ESTIMATED MAXIMUM DEMAND
EMI ELECTROMAGNETIC INTERFERENCE
ER EQUIPMENT ROOM
FO FIBER OPTIC
FP FIBER PANEL
PB PULLBOX
PERP PERPENDICULAR
PBX PRIVATE BRANCH EXCHANGE
RGS RIGID GALVANIZED STEEL
TR TELECOMMUNICATIONS ROOM
TMGB TELECOMMUNICATIONS MAIN
TGB TELECOMMUNICATIONS
TBB TELECOMMUNICATIONS
T-1 TRUNK LEVEL 1
STP SHIELDED TWISTED PAIR
OUTLET ASSEMBLY
MM MULTIMODE
MLO MAIN LUGS ONLY
MDF MAIN DISTRIBUTION FRAME
MC MAIN CROSS CONNECT
MATV MASTER ANTENNA TELEVISION
OSP OUTSIDE PLANT
KCMIL THOUSAND CIRCULAR MILS
ISP INSIDE PLANT
HZ HERTZ
GEC GROUNDING ELECTRODE CONDUCTOR
SERVICE INTERNATIONAL
MUTOA MULTI USER TELECOMMUNICATIONS
GROUNDING BUSBAR
GROUNDING BUSBAR
TBBIBC TELECOMMUNICATIONS BONDING
CFH CUBIC FEET PER HOUR
SHW SOFT HOT WATER
TTB TELEPHONE TERMINAL BOARD
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MOA MINIMUM OUTDOOR AIR
EOA ECONOMIZER OUTDOOR AIR
IE INVERT ELEVATION
IDF INTERMEDIATE DISTRIBUTION FRAME
IC INTERCOM
BACKBONE INTERCONNECTING
PREVENTER
NATIONAL ASSOCIATION
BONDING BACKBONE
BONDING CONDUCTOR
A
AC
ACEG
AHJ
APPROX
ASHRAE
ATS
AUX
AV
AVI
AW
AWG
BFP
AMP
ALTERNATING CURRENT
AC EQUIPMENT GROUND
AUTHORITY HAVING JURISDICTION
APPROXIMATELY
AMERICAN SOCIETY OF HEATING,
REFRIGERATING AND
AIR-CONDITIONING ENGINEERS
AUTOMATIC TRANSFER SWITCH
AUXILIARY
ACID VENT, AUDIOVISUAL
AUTOMATIC VEHICLE IDENTIFICATION
ACID WASTE
AMERICAN WIRE GAUGE
BACKFLOW PREVENTER
UTILITY SINK
UNSHIELDED TWISTED PAIR
VOLT, VENT
VOLUME DAMPER
VERTICAL
VARIABLE FREQUENCY CONTROL
VENT THROUGH ROOF
WATER, WATT
WIDE AREA NETWORK
WIRELESS ACCESS POINT
WIRE MANAGEMENT PANEL
WEATHERPROOF
WIRE SIZING AMPS
WATER SOURCE HEAT PUMP
TRANSFORMER
US
UTP
V
VD
VERT
VFC
VTR
W
WAN
WAP
WMP
WP
WSA
WSHP
XFMR
AFF ABOVE FINISHED FLOOR
ALF ALUMINUM FRAME DOOR
AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
STANDARD SPECIFICATIONS OF
THE AMERICAN SOCIETY FOR
ASME
ASTM
TESTING MATERIALS
AVG AVERAGE
BAS BUILDING AUTOMATION SYSTEM
BTC BONDING CONDUCTOR FOR
TELECOMMUNICATION
CLEC COMPETITIVE LOCAL
EXCHANGE CARRIER
CUSTOMER OWNER-OUTSIDE PLANT
DAS DISTRIBUTION ANTENNA SYSTEM
DP DEMARCATION POINT
DPS DOOR POSITION SWITCH
DVR DIGITAL VIDEO RECORDER
EAC ELECTRONIC ACCESS CONTROL
EC ELECTRICAL CONTRACTOR
EMS ENERGY MANAGEMENT SYSTEM
FM FACTORY MUTUAL
ENGINEERING CORPORATION
FOV FIELD OF VIEW
HH HANDHOLE
HMF HOLLOW METAL FRAME DOOR
IDC INSULATION DISPLACEMENT
CONNECTOR
IDS INTRUSION DETECTION SYSTEM
IP INTERNET PROTOCOL
LEC LOCAL EXCHANGE CARRIER
LBM LATCH BOLT MONITOR
MCB MAIN CIRCUIT BREAKER
MPOE MAIN POINT OF ENTRANCE
NATIONAL FIRE PROTECTION
ASSOCIATION
MANUFACTURERS ASSOCIATION
NATIONAL ELECTRICALNEMA
NFPA
NVE NETWORK VIDEO ENCODER
NVR NETWORK VIDEO RECORDER
OR OPERATOR ROOM
OPE OWNER PROVIDED ELECTRONICS
PABX PRIVATE AUTOMATIC
BRANCH EXCHANGE
PBO PROVIDE BY OTHERS
PDU POWER DISTRIBUTION UNIT
PIC PLASTIC INSULATED CABLE
POE POWER OVER ETHERNET
POP POINT OF PRESENCE
PSTN PUBLIC SWITCH TELEPHONE NETWORK
PTZ PAN-TILT-ZOOM
RQE REQUEST TO EXIT
SCTP SCREENED TWISTED PAIR
SLAB SEALED LEAD ACID BATTERY
SSI SECURITY SYSTEMS INTEGRATOR
TC TELECOMMUNICATIONS CLOSET
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSION
VOICE OVER INTERNET PROTOCOLVOIP
WIRE TRANSFER HINGEWTH
CO-OSP
SPD SURGE PROTECTIVE DEVICE
WATER GUAGEWG
ABBREVIATIONS
R
H20
CO
FIRE ALARM WIRELESS AUTOMATIC CEILING
HEAT DETECTOR
FS
F
F
WALL MOUNT WIRELESS MOTION DETECTOR
CEILING MOUNT WIRELESS MOTION DETECTOR
YELLOW INTRUSION ALARM WARNING LIGHT CEILINGYELLOW INTRUSION ALARM WARNING LIGHT WALLY IA Y IA
SP
WIRELESS RECEIVER WIRELESS REPEATERP
E19
ENLARGED SITE PLAN
E1G
SCALE: 1" = 20'-0" 20' 10' 0 20'
ELECTRICAL ENGLARGED SITE PLAN
N
INSTALL GREEN INSULATED
GROUND WIRE WITH EACH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUIT.
PROVIDE A DEDICATED NEUTRAL
CONDUCTOR FOR EACH BRANCH
CIRCUIT REQUIRING A NEUTRAL,
UNLESS OTHERWISE NOTED.
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND
CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.
LAY OUT AND COORDINATE ALL WORK PRIOR TO
INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR
OPERATION, MAINTENANCE, AND CODES AND VERIFY
NON-INTERFERENCE WITH OTHER WORK. DO NOT
FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR
ALL TRADES. READ SPECIFICATIONS.
F eb
5,
- 2
:0 5p m J:
\2
3_ Pr oje cts
\2
1\ Dw gs \ 2
1E
1G .d wg
US
ER
js an ch ez
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
02/06/2024
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
GAN
AE# 20239961
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
FINAL CONSTRUCTION DOCUMENTS
DRAWING NO.
PMIS NO.
ONE LINE DIAGRAMS
E19
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND
CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.
LAY OUT AND COORDINATE ALL WORK PRIOR TO
INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR
OPERATION, MAINTENANCE, AND CODES AND VERIFY
NON-INTERFERENCE WITH OTHER WORK. DO NOT
FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR
ALL TRADES. READ SPECIFICATIONS.
F eb
5,
- 2
:0 8p m J:
\2
3_ Pr oje cts
\2
1\ Dw gs \ 2
1E
.d wg
US
ER
js an ch ez
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
02/06/2024
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
GAN
AE# 20239961
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
FINAL CONSTRUCTION DOCUMENTS
DRAWING NO.
PMIS NO.
258470
425 / 80087
FLAG NOTES - DETAIL 1/E19
EXISTING FEEDER TO EXISTING CHILLER.1
ONE LINE DIAGRAM - DEMOLITION
NO SCALE
E19
EXISTING
PANEL
HS-2
BARRACKS/HOSPITAL
EXISTING 208/120V 1 PHASE
150 AMP FEEDER
E19
EXISTING PANEL
HS-1 VISITOR CENTER
EXISTING 100 AMP 208/120V.
1 PHASE PANEL 'C'
G
G,WP
EXISTING 80 KW
PORTABLE GENERATOR
EXISTING OUTPUT
BREAKER
NN
EXISTING
CONCRETE PAD
EXISTING ABANDONED
METER SOCKETS
E
N
EXISTING MANUAL
TRANSFER SWITCH
EXISTING 225/3 ENCLOSED BREAKER
VISITOR CENTER SERVICE DISCONNECT
EXISTING 200 AMP CHILLER
SERVICE DISCONNECT
EXISTING SIX
CIRCUIT PANEL
EXISTING WIREWAY 4
2(TYP)
EXISTING UNDERGROUND SECONDARY
ELECTRICAL 4 #250 KCMIL IN EACH OF TWO 4"C
EXISTING
METERING
EXISTING UNDERGROUND
PRIMARY ELECTRICAL
EXISTING
CONCRETE PAD
EXISTING MID WEST ENERGY
300 KVA 208/120V PAD
MOUNTED TRANSFORMER
REMOVE EXISTING 4 #250 KCMIL CONDUCTORS FROM
EXISTING 4"C EXISTING CONDUIT TO REMAIN. REFER TO
DETAIL 2/E19 FLAG NOTE 10 FOR NEW CONDUCTORS
EXISTING IN GROUND UNISTRUT.2
3 EXISTING 120V. CIRCUITS TO EXISTING GENERATOR.
4 DISCONNECT EXISTING GROUNDED CONDUCTORS AND REMOVE EXISTING
GROUNDING LUG. PROVIDE A NEW GROUND BAR AND RECONNECT EXISTING
GROUNDED CONDUCTORS.
5 EXISTING PANEL TUB AND DOOR TO REMAIN AND BE CONVERTED INTO A JUNCTION
BOX.
6 REMOVE EXISTING 225 AMP INTERNAL PANEL WITH 1-100/3, 1-150/2, 1-20/3 BREAKERS
AND SUB FEED LUGS. DISCONNECT EXISTING FEEDERS AND BRANCH CIRCUIT
WIRING.
7 REMOVE 4 #250 KCMIL CONDUCTORS.
8 REMOVE EXISTING 225 AMP INTERNAL PANEL WITH 1-100/3, 1-50/2, 2-30/2, 1-20/2,
35-20/1, AND 1-20/1 GFCI BREAKERS. DISCONNECT EXISTING BRANCH CIRCUIT
WIRING.
9 REMOVE EXISTING SURGE PROTECTIVE DEVICE.
10 REMOVE EXISTING 100 AMP FEEDER CONDUCTORS. EXISTING CONDUIT TO REMAIN.
ONE LINE DIAGRAM - NEW WORK
NO SCALE
E19
EXISTING 208/120V
1 PHASE PANEL
HS-2
BARRACKS/HOSPITAL
EXISTING 150 AMP FEEDER
CONDUCTORS RECONNECTED TO NEW
125/2 BREAKER IN NEW PANEL 'VC'
HS-1 VISITOR CENTER 1ST FLOOR
(TYP)
(TYP)
(TYP)
2ND FLOOR
125F3
12-20F2
20,30,50F2
8 (TYP)
12-20F2
100F3
12-20F2
225F4
9 (TYP)
NEW PANEL 'VC'
EXISTING
PANEL TUB
100F3E
CELLAR
225F4
GROUND BAR
E21
SERVICE GROUNDING
E21
NEW 225/3, 18,000 A.I.C.
ENCLOSED BREAKER
NEMA 4X ENCLOSURE
FLAG NOTES - DETAIL 2/E19
1 PROVIDE A GROUND BAR ATTACHED TO EXISTING PANEL TUB. CONNECT THE TWO
GROUND BARS TOGETHER WITH #4 GREEN INSULATED GROUND WIRE. CONNECT
NEW AND EXISTING BRANCH CIRCUIT GROUND WIRES TO THE NEW GROUND BAR.
2 PROVIDE A #4 GREEN INSULATED GROUND TO GROUND BAR IN NEW PANEL 'VC',
ROUTE GROUND WIRE WITH NEW 225F4 FEEDER.
3 PROVIDE NEW 2 1/2" CONDUIT NIPPLE WITH A BUSHING ON EACH END.
4 PROVIDE BUSHING ON EACH END OF EXISTING 4" NIPPLE.
5 PROVIDE INSULATED BUSHING ON NEW AND EXISTING CONDUITS 1" AND LARGER
INSIDE EXISTING PANEL TUB.
6 SPLICE NEW BRANCH CIRCUIT CONDUCTORS TO EXISTING CONDUCTORS.
7 NEW CONDUCTORS INSIDE EXISTING PANEL TUB ARE NOT INSTALLED IN CONDUIT.
8 NEW CONDUITS ON 2ND FLOOR CAN BE FLEXIBLE GALVANIZED STEEL CONDUIT OR
LIQUID TIGHT FLEXIBLE CONDUIT IN ORDER TO ROUTE AROUND EXISTING DUCT
WORK. PROVIDE STRAPPING PER NEC REQUIREMENTS.
9 PROVIDE CORE DRILLING OF EXISTING CONCRETE FLOOR FOR NEW CONDUITS.
PROVIDE FIRE CAULKING AFTER CONDUITS ARE INSTALLED.
10 PROVIDE 4 #250 KCMIL 1 #2 INSULATED GREEN GROUND WIRE IN EXISTING 4"C TO
EXISTING OUTDOOR MANUAL TRANSFER SWITCH.
11 DO NOT BOND NEUTRAL AND GROUND TOGETHER.
11 PROVIDE A NEW 10'X3/4" COPPERCLAD DRIVEN GROUND ROD.
FOR NEW
REQUIRED WORK
PROVIDE #6 GROUND
IN 1/2"C
EXISTING FEEDER
12 PUNCH OUT HOLES ON TOP OF EXISTING PANEL TUB FOR NEW CONDUIT FITTINGS.
12(TYP)
EXISTING
PANEL 'C'
PROVIDE A DEDICATED NEUTRAL
CONDUCTOR FOR EACH BRANCH
CIRCUIT REQUIRING A NEUTRAL,
UNLESS OTHERWISE NOTED.
1. KEEP ELECTRICAL POWER OUTAGE TO 48 HOURS MAXIMUM.
GENERAL NOTES
2. COORDINATE POWER OUTAGES WITH CONTRACTING OFFICER OR CONTRACTING
OFFICER REPRESENTATIVE.
30F4
100F4
13 PROVIDE A SURGE PROTECTIVE DEVICE.
14 REMOVE AND REPLACE DRYWALL IN KITCHEN/BREAK ROOM 124 IN ORDER TO
INSTALL NEW CONDUIT. PRIME AND PAINT THE NORTH WALL TO MATCH EXISTING.
15 MOUNT PANEL ON NEW WALL MOUNTED UNISTRUT.
16 FILL IN VOID UNDER EXISTING PANEL WITH EXPANDING FOAM. TRIM EXCESS FOAM
FROM OUTER SURFACE.
17 SEAL ENDS OF CONDUITS.
UP
LIBRARY
KITCHEN/
BREAK
STAIR
DN
ATTIC
CHIMNEY
T
G
VC-59
UP
CELLAR
C01
CELLAR
C02
KEY NOTES
ENLARGED HS-1
E20
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
ENLARGED HS-1 ELECTRICAL CRAWL
SPACE PLAN - CELLAR C02
N
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
ENLARGED HS-1 ELECTRICAL PLAN -
KITCHEN/BREAK 124
N
SCALE: 1/4" = 1'-0" 4' 2' 0 4'
ENLARGED HS-1 ELECTRICAL ATTIC PLAN -
ATTIC 200
N
PLAN TRUE
N
PLAN TRUE
N
PLAN TRUE
N
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND
CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.
LAY OUT AND COORDINATE ALL WORK PRIOR TO
INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR
OPERATION, MAINTENANCE, AND CODES AND VERIFY
NON-INTERFERENCE WITH OTHER WORK. DO NOT
FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR
ALL TRADES. READ SPECIFICATIONS.
F eb
5,
- 2
:0 8p m J:
\2
3_ Pr oje cts
\2
1\ Dw gs \ 2
1E
.d wg
US
ER
js an ch ez
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
02/06/2024
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
GAN
AE# 20239961
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
FINAL CONSTRUCTION DOCUMENTS
DRAWING NO.
PMIS NO.
258470
425 / 80087
INSTALL GREEN INSULATED
GROUND WIRE WITH EACH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUIT.
PROVIDE A DEDICATED NEUTRAL
CONDUCTOR FOR EACH BRANCH
CIRCUIT REQUIRING A NEUTRAL,
UNLESS OTHERWISE NOTED.
PLANS
NOTE:
DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND
CLEARANCES FROM ARCHITECTURAL, STRUCTURAL,
SHOP AND OTHER APPROPRIATE DRAWING OR AT SITE.
LAY OUT AND COORDINATE ALL WORK PRIOR TO
INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR
OPERATION, MAINTENANCE, AND CODES AND VERIFY
NON-INTERFERENCE WITH OTHER WORK. DO NOT
FABRICATE PRIOR TO VERIFICATION OF CLEARANCE FOR
ALL TRADES. READ SPECIFICATIONS.
F eb
5,
- 2
:0 8p m J:
\2
3_ Pr oje cts
\2
1\ Dw gs \ 2
1E
.d wg
US
ER
js an ch ez
SUB SHEET NO.
OF
DESIGNED:
RCF
DRAWN BY:
TECH. REVIEW:
DATE:
02/06/2024
SHEET
TITLE OF SHEETA/E FIRM
PRIME:
KENNETH HAHN
ARCHITECTS, INC.
OMAHA, NE.
SUBCONTRACTOR:
ALVINE
ENGINEERING
OMAHA, NE.
JAS
GAN
AE# 20239961
ELECTRICAL DISTRIBUTION PANEL
FORT LARNED NATIONAL HISTORIC SITE
PAWNEE COUNTY, KANSAS
FINAL CONSTRUCTION DOCUMENTS
DRAWING NO.
PMIS NO.
258470
425 / 80087ELECTRICAL DETAILS AND
SCHEDULES
E21
PANEL VC
208/120V 3 PHASE 4 WIRE W/ GND BAR SURFACE MOUNTED COPPER BUS
225 AMP MLO COPPER LUGS
10,000 AIC COPPER GROUND BAR
72 POLES ONE SECTION
DESCRIPTION LOAD VA REMARKS O/C CKT # PH CKT # O/C REMARKS LOAD VA DESCRIPTION
EXISTING LOAD 20/1 1 A 2 20/1 EXISTING LOAD
EXISTING LOAD 20/1 3 B 4 20/1 EXISTING LOAD
EXISTING LOAD 20/1 5 C 6 20/1 EXISTING LOAD
EXISTING LOAD 20/1 7 A 8 20/1 EXISTING LOAD
EXISTING LOAD 20/1 9 B 10 20/1 EXISTING LOAD
EXISTING LOAD 20/1 11 C 12 20/1 EXISTING LOAD
EXISTING LOAD 20/1 13 A 14 20/1 EXISTING LOAD
EXISTING LOAD 20/1 15 B 16 20/1 EXISTING LOAD
EXISTING LOAD 20/1 17 C 18 20/1 EXISTING LOAD
EXISTING LOAD 20/1 19 A 20 20/1 EXISTING LOAD
EXISTING LOAD 20/1 21 B 22 20/1 EXISTING LOAD
EXISTING LOAD 20/1 23 C 24 20/1 EXISTING LOAD
EXISTING LOAD 20/1 25 A 26 20/1 EXISTING LOAD
EXISTING LOAD 20/1 27 B 28 20/1 EXISTING LOAD
EXISTING LOAD 20/1 29 C 30 20/1 EXISTING LOAD
EXISTING LOAD 20/1 31 A 32 20/1 EXISTING LOAD
EXISTING LOAD 20/1 33 B 34 20/1 GFCI EXISTING LOAD
FIRE ALARM 100 1 20/1 35 C 36 20/1 EXISTING LOAD
EXISTING LOAD 30/2 37 A 38 20/1 1 1200 FIRE ALARM PANEL
- - 39 B 40 20/1 1 1000 INTRUSION ALARM PANEL
EXISTING LOAD 30/2 41 C 42 20/2 EXISTING LOAD
- - 43 A 44 - -
EXISTING LOAD 50/2 45 B 46 100/2 EX. PANEL 'C'
- - 47 C 48 - -
SPARE 20/3 49 A 50 100/3 EXISTING LOAD
- - 51 B 52 - -
- - 53 C 54 - -
F.A. DUCT DETECTOR 75 20/1 55 A 56 20/1 GFCI SPARE
IT RACK PDU 1200 20/1 57 B 58 20/1 GFCI SPARE
ATTIC RECEPT 180 20/1 59 C 60 20/1 SPARE
SPARE 20/1 61 A 62 20/1 SPARE
SPARE 20/1 63 B 64 20/1 SPARE
SPARE 20/1 65 C 66 20/1 SPARE
SURGE PROTECTOR 20/3 67 A 68 20/1 SPARE
- - 69 B 70 125/2 EX BLDG HS-2
- - 71 C 72 - -
E21
COPPER GROUND BAR
2" HIGH INSULATORS (TYP FOR 2)
MOUNTING BOLT WITH
LOCK WASHER (TYP)
COPPER GROUND BAR
BOLT TO WALL
WALL MOUNTING BRACKET
ANCHOR BOLTS
MAIN
GROUND BAR
GROUND BAR
NO SCALE
SECTION
ISOMETRIC VIEW
GROUND BAR SCHEDULE
NOMINAL SIZE ERICO CAT #MARK
EGBA14420CCT1/4" x 4" x 20"
E21
E21
TO EXISTING I.T. PRIMARY BONDING
BUSBAR AT EXISTING I.T. RACK IN
KITCHEN/BREAK ROOM 124
MAIN GROUND BAR
#2, 3/4"C TO STREET SIDE
OF WATER METER
#6, 3/4"C TO GROUND ROD
225/3 ENCLOSED BREAKER
SERVICE EQUIPMENT
GROUNDED CONDUCTOR
(NEUTRAL)
BOND CONDUIT TO
GROUND BUS (TYP FOR
METAL CONDUIT)
SERVICE CONDUIT
BOND CONDUIT TO GROUND BAR OR TO
GROUNDING ELECTRODE CONDUCTOR;
MATCH SIZE OF GROUNDING
ELECTRODE CONDUCTOR (TYP FOR
METAL CONDUIT)
SERVICE GROUNDING
NO SCALE
BOND CONDUIT TO GROUNDING
ELECTRODE OR TO GROUNDING
ELECTRODE CONDUCTOR; MATCH SIZE OF
GROUNDING ELECTRODE CONDUCTOR
(TYP FOR METAL CONDUIT)
NEUTRAL BUS
GROUND BUS
#2, 3/4"C
#2, 3/4"C
FEEDER AND BRANCH CIRCUIT
SCHEDULE
MARK CONDUCTORS AND CONDUIT
2 WIRE PLUS GROUND
12-20F2 24 #8, 1 #8 GND. 2"C.
20,30,50F2 2 #10, 4 #8, 2 #6, 1 #6 GND. 1-1/4"C.
3 WIRE PLUS GROUND
100F3 3 #2, #8 GND. 1-1/4" C.
100F3E 3 #2, #8 GND. IN EXISITNG CONDUIT
125F3 3 #1, #6 GND. 1-1/2" C.
4 WIRE PLUS GROUND
30F4 4 #10, #10 GND. 3/4" C.
100F4 4 #2, #8 GND. 1-1/4" C.
225F4 4 #4/0, #4 GND. 2-1/2" C.
REMARKS
1. PROVIDE A BREAKER HANDLE LOCK.
PROVIDE LUGS
DO NOT BOND NEUTRAL
AND GROUND
| Sheets and Views |
| 02_FOLS_C1-C1 |
| 03_FOLS_C2-C2 |
| 04_FOLS_C3-C3 |
| 05_FOLS_C4-C4 |
| 06_FOLS_C5-C5 |
| 07_FOLS_C6-C6 |
| 08_FOLS_C7-C7 |
| 09_FOLS_A1 Photo Sheet-A1 |
| 10_FOLS_A2 Photo Sheet-A2 |
| 11_FOLS_A3 HS-1-A3 |
| 12_FOLS_A4 HS-2-A4 |
| 13_FOLS_A5 HS-3-4-A5 |
| 14_FOLS_A6 HS-5-A6 |
| 15_FOLS_A7 HS-6-A7 |
| 16_FOLS_A8 HS-7-A8 |
| 17_FOLS_A9 HS-8-A9 |
| 18_FOLS_A10 HS-9-A10 |
| 19_FOLS_A11 HS-10 - MAINT-A11 |
[1] COVER SHEET