B08_Solicitation_-_Att_1_Drawings_Specifications__FOSC_HVAC_341293.pdf
PDF 12 MB Posted
- Attached to
- FOSC, HVAC Repair & Restroom Remodel
- Solicitation number
- 140P6026Q0041
About this file
This is a set of Final Construction Documents for PMIS 341293 - Remove and Replace Furnaces and Condensing Units in Infantry Barracks (Package A - HS6) at Fort Scott National Historic Site in Fort Scott, Kansas. The documents are dated April 9, 2026, and were prepared by Schemmer Associates.
The project scope encompasses the removal and replacement of HVAC equipment including furnaces and condensing units serving the Infantry Barracks building. The construction documents include architectural sheets with reflected ceiling plans and window details; mechanical sheets detailing floor plans, demolition plans, equipment schedules, and specifications for new air handling units, heat pump condensing units, electric dehumidifiers, and various HVAC accessories including ductwork, diffusers, grilles, registers, and louvers; and electrical sheets covering power distribution, demolition plans, floor plans, riser diagrams, and equipment schedules. Key mechanical equipment includes four heat pump condensing units (HP-1 through HP-4), two air handling units (AHU-1 and AHU-2), one electric dehumidifier (DH-1), one exhaust fan (EF-1), and one supply fan (SF-1). Electrical work involves providing new power circuits and disconnects for all mechanical equipment, with service from existing panels HS-6 and HS-6A. The documents establish specifications for materials, installation requirements, demolition procedures, and coordination between trades, along with detailed schedules of all equipment to be installed with manufacturer information and electrical data.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH
PROJECT
LOCATION
CONTRACTOR
PARKING &
STAGING AREA
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs
\r s c a rb o ro u g h \D o c u m e n ts
\0
-A
R C
H
R rS c a rb o ro u g h
D Q
X C
S .r v t
RAS
RAS
JB
4/09/2026
09258015
G1.2
COVER SHEET
009258015-0-G1.2 COVER SHEET
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
FORT SCOTT NATIONAL HISTORIC SITE
MECHANICAL.2
M 00.2 MECHANICAL INFO SHEET
M 01.2 SHEET SPECIFICATIONS - MECHANICAL
M 02.2 SHEET SPECIFICATIONS - MECHANICAL
MD01.2 DEMOLITION FLOOR PLAN - MECHANICAL
M101.2 FLOOR PLAN - MECHANICAL
M102.2 FLOOR PLAN - MECHANICAL
M401.2 DETAILS - MECHANICAL
M501.2 SCHEDULE - MECHANICAL
GENERAL.2
G1.2 COVER SHEET
ELECTRICAL.2
E 00.2 ELECTRICAL INFO SHEET
E 01.2 ELECTRICAL INFO SHEET
E 02.2 ELECTRICAL SPECIFICATIONS
E 03.2 ELECTRICAL SPECIFICATIONS
E 04.2 ELECTRICAL SPECIFICATIONS
ED01.2 FLOOR PLAN - DEMOLITION
E201.2 FLOOR PLAN - POWER
E202.2 FLOOR PLAN - POWER
E501.2 POWER RISER DIAGRAMS
E601.2 ELECTRICAL SCHEDULES
PMIS 341293 - REMOVE AND REPLACE FURNACES AND CONDENSING UNITS IN INFANTRY BARRACKS
PACKAGE A - HS6
ARCHITECTURAL.2
A201.2 REFLECTED CEILING PLAN
DATE INITIAL
FINAL CONSTRUCTION DOCUMENTS
4/09/2026
DRAWING INDEX
4/9/26
S
OS
OS
LIGHT FIXTURES
(SEE ELECTRICAL)
CONTROL JOINT (CJ)
GRILLES AND DIFFUSERS
(SEE MECHANICAL)
GYPSUM BOARD CEILING
LEGEND:
FOR CEILING HEIGHTS, SEE ROOM FINISH SCHEDULE
NEW 2x2 LAY-IN CEILING GRID
AND PADS
FIRE ALARM STROBE, SEE ELEC
FIRE ALARM SPEAKER, SEE ELEC
FIRE ALARM SPEAKER STROBE,
SEE ELEC
OCCUPANCY SENSOR, SEE ELEC
EXIT SIGN, SEE ELEC
FIRE ALARM HORN, SEE ELEC
FIRE ALARM HORN STROBE,
SEE ELEC
SMOKE DETECTOR, SEE ELEC
SPEAKER, SEE ELEC
F
F S
F S
OS
F
F
S
S
26 26 26 26
AFF 8' - 0"
AFF 9' - 6"
320 SF OF ACT CEILING
WOMENS RR
MENS RR
STORAGE
DRESSING
DRESSING
UTILITY
CORRIDOR
FIRE
MECH
EXIST. WALL
NEW REPLICA WOOD WINDOW
WITHOUT GLAZING AT BOTTOM
SASH.
MEETING RAIL
HEAD DETAIL
PREFIN ALUM. BRAKE
MTL SECURED OVER 2X
BLOCKING. ALUM SHALL
COVER ALL EXPOSED
SURFACES OF
BLOCKING
WOOD SASH BOTTOM RAIL
WOOD SILL
SILL DETAIL
EXIST WALL
NO GLAZING AT BOTTOM SASH
NEW LOUVER, LV-1 REF:
MECH. SET LOUVER IN
SEALANT AND SECURE
TO SOLID BLOCKING AS
REC BY MFG.
ALUM. BRAKE MTL ON
BLOCKING AS NOTED.
BOTTOM SASH W/O GLAZING TO ALLOW
AIRFLOW TO LV-1 LOUVER BEHIND
WINDOW, REF: MECH
EXTERIOR ELEVATION
MEETING RAIL
SILL
V
.I .F
3'-6" V.I.F.
NEW REPLICA DOUBLE
HUNG WINDOW TO MATCH
EXISTING WINDOWS.
ASSEMBLY
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs
\r s c a rb o ro u g h \D o c u m e n ts
\0
-A
R C
H
R rS c a rb o ro u g h
D Q
X C
S .r v t
RAS
RAS
JB
4/09/2026
09258015
A201.2
REFLECTED CEILING PLAN
009258015-2-A201.2 REFLECTED CEILING PLAN
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
SCALE: 1/8" = 1'-0"
FIRST FLOOR - REFLECTED CEILING
NORTH DATE INITIAL
22 NO ARCHITECTURAL WORK THIS AREA.
26 CONTRACTOR TO REMOVE TILES AS NECESSARY TO CONDUCT MECHANICAL SCOPE.
REPLACE TILES AFTER WORK IS COMPLETED. CONTRACTOR TO REPLACE ANY DAMAGED
GRID OR TILES .
27 REMOVE EXISTING WINDOW AND SALVAGE FOR OWNER STORAGE. INSTALL NEW REPLICA
WINDOW WITHOUT GLAZING AT BOTTOM SASH. MECHANICAL LOUVER LV-1 TO BE
INSTALLED BEHIND WINDOW. REF: MECHANICAL FOR PRODUCT DETAILS. REF:
ARCHITECTURAL DETAILS 2 & 4 A201.2
28 SOFFIT VENT S-2 / E-1, REF: MECH TYP.
REF. NOTES ( ):X
SCALE: 3/4" = 1'-0"
EXISTING WINDOW ELEVATION
SCALE: 1 1/2" = 1'-0"
EXISTING WINDOW DETAIL
SCALE: 1/8" = 1'-0"
SECOND FLOOR - REFLECTED CEILING
NORTH
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND
LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER
OF ANY DISCREPANCIES OR VARIATIONS FROM THOSE SHOWN ON THE
DRAWINGS. THE CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT
NO ADDITIONAL EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF
DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL
NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF
DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE
RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD
CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE WORK
AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN.
FULL-TONE LINES INDICATED NEW OR RELOCATED CONSTRUCTION.
E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH
STRUCTURE, CEILING, LIGHTING, AND PIPING.
F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL EQUIPMENT TO
ALLOW FOR MAINTENANCE ACCESS.
G. ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT ANGLES AND
PARALLEL TO BUILDING WALLS UNLESS OTHERWISE INDICATED.
H. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS. MAINTAIN
ALL CODE REQUIRED CLEARANCES.
I. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL
REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER
HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE
CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND
REPORT THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE WORK
IN THE AFFECTED AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY
WRITTEN AGREEMENT OF THE OWNER AND CONTRACTOR.
J. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INLET SIZE UNLESS OTHERWISE
NOTED.
K. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING CONSTRUCTION
SHALL BE COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL
DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.
DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED TO BE
REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS FULL-TONE LINES. ALL
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN AS HALF-
TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED BELOW
OR HERE-IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION
AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL
EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED BELOW.
C. THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING EQUIPMENT FROM
FINISHED AREAS AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED
WITH ARCHITECTURAL PLANS AND DETAILS AS WELL AS NOTES ON THE
MECHANICAL DRAWING TO ENSURE PROPER PATCHING AND REPAIR IS MADE TO
THE BUILDING.
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL
OF ALL EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES
TO BUILD, ERECT, INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH
THE OWNER HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.
E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE
CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND STORED OR
REINSTALLED ON THE SITE AS DIRECTED. REMOVED OR SALVAGED ITEMS SHALL
REMAIN THE PROPERTY OF THE OWNER.
F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND CONTROLS
WITH ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL REMOVALS.
G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL
REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER
HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE
CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND
REPORT THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE WORK
IN THE AFFECTED AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY
WRITTEN AGREEMENT OF THE OWNER AND ARCHITECT.
H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION SHALL
BE COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.
I. CONTRACTOR RESPONSIBLE FOR ANY DAMAGE CAUSED DURING DEMOLITION.
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M 00.2
MECHANICAL INFO SHEET
009258015-6-M 00.2 MECHANICAL INFO SHEET
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
SYMBOL LEGEND
VOLUME DAMPER
DEMO TO EXISTING CONNECTION
SPRINKLER DRAIN
FIRE SUPPRESSION PIPING
ISOLATION VALVE
TAMPER SWITCH
MANUAL BALANCING VALVE
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
CONTROL VALVE (3 WAY)
CONTROL VALVE (2 WAY)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
HVAC DUCTWORK AND SPECIALTIES
(CONT.)
MISCELLANEOUS SYMBOLS
RETURN DUCT DOWN
AIR TERMINAL (VERTICAL MOUNTING)
ROUND DUCT UP / DOUBLE LINE PIPE
ROUND DUCT DOWN / DOUBLE
LINE PIPE
RETURN DUCT UP
TURNING VANES
SUPPLY AND FRESH AIR DUCT DOWN
SUPPLY AND FRESH AIR DUCT UP
SIZE/TYPE
SIZE/TYPE
FLOW
FLOW
SIZE/TYPE
FLOW
SMOKE DAMPER
FIRE DAMPER-HORIZ FIRE SEPARATION
MOTORIZED DAMPER-OPPOSED BLADE
MOTORIZED DAMPER-PARALLEL BLADE
ROUND AIR TERMINAL
(HORIZONTAL MOUNTING)
GRAVITY DAMPER
(OR) SAFETY VALVE-STEAM
TEMP & PRESS RELIEF
FLOOR SINK
FLOOR DRAIN
GRADE CLEANOUT
PLUMBING VENT THRU ROOF
CLEANOUT / WALL CLEANOUT
THERMOSTATIC MIXING VALVE
M
M
MANHOLE
TRENCH DRAIN
OVERFLOW ROOF DRAIN
OXYGEN OUTLET
PIPE CAP
ELBOW UP
AIR OUTLET
TEE
ELBOW DOWN
VACUUM OUTLET
ROOF DRAIN
SIZE/TYPE
FLOW
HUMIDISTAT
THERMOSTAT
FLEXIBLE DUCT
H
T
UNION
TEE DOWN
STRAINER
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
AIR VENT
TEE UP
FIRE/SMOKE DAMPER
RECTANGULAR RETURN AIR TERMINAL
(HORIZONTAL MOUNTING)
RECTANGULAR SUPPLY AIR TERMINAL
(HORIZONTAL MOUNTING)
SOLENOID VALVE
F
D
TS
VALVES
FS
M
M
S
LPR
HPS
MPR
MPS
LPS
HVAC PIPING
GHWR
GHWS
HWR
HWS
PC
HPR
ES
BBD BOILER BLOW DOWN
EXHAUST STEAM
PUMPED CONDENSATE
HIGH PRESSURE RETURN
HIGH PRESSURE STEAM
MEDIUM PRESSURE RETURN
MEDIUM PRESSURE STEAM
LOW PRESSURE RETURN
LOW PRESSURE STEAM
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
FS-_
FD-_
CO
VTR
GCO
ORD-_
MH
X
A
V
RD-_
PIPING SPECIALTIES AND FITTINGS
WCO
FIRE PROTECTION
SIZE/TYPE
FLOW
RECTANGULAR EXHAUST AIR TERMINAL
(HORIZONTAL MOUNTING)
CWS
GCWS
CWR
CR
CS
RL
RDL
RS
GCWR GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
REFRIGERANT LIQUID LINE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION LINE
HCWS
HCWR
HOT/CHILLED WATER SUPPLY
HOT/CHILLED WATER RETURN
DOMESTIC HOT WATER
RECIRCULATING (DHWR)
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
ST/OST
PLUMBING PIPING
ACID VENT
TW
AV
AW
W
DS
DSCW
TWR
DSHW
SANITARY VENT
BURIED EXTERIOR WATER
TEPID WATER RECIRCULATING
TEPID WATER
DISTILLED WATER
SOFTENED HOT WATER
SOFTENED COLD WATER
ACID WASTE
STORM DRAIN
SANITARY DRAIN (BELOW FLOOR)
SANITARY DRAIN (ABOVE FLOOR)
OXYGEN
VACUUM
OX
VAC
RO
A
REVERSE OSMOSIS WATER
COMPRESSED AIR
DEIONIZED WATERDI
AIR FLOW STATIONAFS
HPWR
HPWS
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
F
S
FS
NEW TO EXISTING CONNECTION
G NATURAL GAS
FOF
FOG
LPG
FOV
FOR
FOS
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL GAGE
FUEL OIL FILL
FUEL OIL VENT
LIQUEFIED PETROLEUM GAS
CD CONDENSATE DRAIN
EXHAUST DUCT DOWN
EXHAUST DUCT UP
DOUBLE - GRADE CLEANOUTDGCO
ST/OST STORM DRAIN (BELOW FLOOR)
WASTE AND ANESTHETIC
GAS DISPOSAL
NITROGEN
WAGD
N
MEDICAL AIRMA
PIPE GUIDE
HOSE BIBB
THERMOMETER
PIPE ANCHOR
HB
STEAM TRAP
RHY
WH
ROOF HYDRANT
WALL HYDRANT
PRESSURE GAUGE
EXISTINGDEMO
EXISTINGNEW
18 Ø
18x10
18/10
ROUND DUCT
FLAT OVAL DUCT-1ST FIG IS SIDE
SHOWN
RECT DUCT-1ST FIG IS SIDE SHOWN
ACOUSTICAL DUCT LINER
HVAC DUCTWORK AND SPECIALTIES
HIGH EFFICIENCY TAKEOFF
HIGH EFFICIENCY TAKOFF
WITH VOLUME DAMPER
NITROGEN OUTLET
MEDICAL AIR OUTLET
WASTE AND ANESTHETIC GAS
DISPOSAL OUTLET
N
MA
V
FLEXIBLE DUCTWORK CONNECTION
ABBREVIATIONS
NORTH
ARROW
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XXXX
SIM/OPP
X
XXXX
XX-1
X
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
ROOM / SPACE
NUMBER
LETTER/NUMBER
INDICATES NEW
COLUMN LINE
LETTER/NUMBER
INDICATES EXISTING
COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DRAWING/DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
XXX-1
PLUMBING
FIXTURES PLUMBING FIXTURE
DESIGNATION
X"PIPE
SIZE
PIPE SIZE (DIAMETER)
X"xX"
DUCT
SIZE
WIDTH x HEIGHT
X"/X" WIDTH / HEIGHT
X" DIAMETER
REF. DEMO NOTES ( ) XX REF. NOTES ( )
SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.
GENERAL DEMOLITION NOTES GENERAL NOTES
MECHANICAL SHEET LIST
NORTH PLAN
NORTH
TRUE
NORTH
S TEMPERATURE SENSOR
CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR
NO2 NITROGEN DIOXIDE SENSOR
SENSOR WITH GUARD'X'
SW SWITCH
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPS
MD MOTORIZED DAMPER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
MPR MEDIUM PRESSURE
RETURN
MPS MEDIUM PRESSURE STEAM
MS MOP SINK
N NITROGEN
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPCW NONPOTABLE COLD WATER
NPHW NONPOTABLE HOT WATER
NPHWR NONPOTABLE HOT WATER
RECIRCULATING
OA OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
OX OXYGEN
P PUMP
PHC PREHEAT COIL
PIV POST INDICATING VALVE
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH,
GAUGE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
RA RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF AREA DRAINS
RL REFRIGERANT DISCHARGE LINE
RF RETURN FAN
RH RELIEF HOOD
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RELIEF AIR
RLF RELIEF FAN
RO REVERSE OSMOSIS WATER
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION LINE
RTU ROOF TOP UNIT
RV RELIEF VALVE
S SINK
SA SUPPLY AIR
SAN SANITARY SEWER
SD SMOKE DAMPER
SF SUPPLY FAN
SFU SANITARY FIXTURE UNIT
SH SHOWER
SP STATIC PRESSURE
SSS SURGICAL SCRUB SINK
ST STORM WATER
TD TRENCH DRAIN
TMV THERMOSTATIC MIXING VALVE
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T THERMOSTAT
UH UNIT HEATER
UR URINAL
V VENT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSETS
WCO WALL CLEANOUT
WF WASH FOUNTAINS
WFU WATER FIXTURE UNITS
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WS WATER SOFTENER
WSHP WATER SOURCE HEAT PUMP
WWHP WATER TO WATER HEAT PUMP
YH YARD HYDRANT
A COMPRESSED AIR
AC AIR COMPRESSOR
AD AIR DOOR
AFCV AUTO FLOW CONTROL VALVE
AHU AIR HANDLING UNIT
AMP AMPERE
APD AIR PRESSURE DROP
AS AIR SEPARATOR
AV ACID VENT
AW ACID WASTE
B BOILER
BC BLOWER COIL
BD BIDET
BFP BACKFLOW PREVENTER
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLKG BLOCKING
BLV BALANCING VALVE
BT BATHTUB
BV BALL VALVE
BW BEDPAN WASHER
CH CHILLER
CC COOLING COIL
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CUH CABINET HEATER
CI CAST IRON
CMU COMBINATION UNITS
CR CONDENSER WATER RETURN
CRAC COMPUTER ROOM AIR
CONDITIONER
CS CONDENSER WATER SUPPLY
CSS CLINICAL SERVICE SINKS
CT COOLING TOWER
CU CONDENSING UNIT - SPLIT SYSTEM
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DB DRY-BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DEG DEGREE
DF DRINKING FOUNTAIN
DGCO DOUBLE GRADE CLEANOUT
DH EMERGENCY DRENCH HOSES
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER
RECIRCULATING
DI DEIONIZED WATER
DOAS DEDICATED OUTDOOR AIR SYSTEM
DS DISTILLED WATER
DSA DUCT SOUND ATTENUATORS
DSCW DOMESTIC SOFT COLD WATER
DSHW DOMESTIC SOFT HOT WATER
DSHWR DOMESTIC SOFT HOT WATER
RECIRCULATING
DST DOMESTIC STORAGE TANK
DTW DOMESTIC TEPID WATER
DTWR DOMESTIC TEPID WATER
RECIRCULATING
EA. EACH
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE
WASH/SHOWER
EF EXHAUST FAN
EFF EFFICIENCY
EFW EMERGENCY FACE WASH
EH EXHAUST HOOD
ERV ENERGY RECOVERY
VENTILATOR
ES EMERGENCY SHOWER
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER
TEMPERATURE
ET EXPANSION TANK
F FIRE SUPPRESSION PIPING
F-_ FURNACE
FCO FLOOR CLEANOUT
FC FLUID COOLER
FCU FAN COIL UNIT
FD FIRE DAMPER
FLA FULL LOAD AMPS
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD FIRE/SMOKE DAMPER
FT FINNED TUBE
G GAS
GCWR GLYCOL CHILLED
WATER RETURN
GCWS GLYCOL CHILLED
WATER SUPPLY
GD GARBAGE DISPOSAL
GDH GAS DUCT HEATER
GHCR GLYCOL HOT/CHILLED
WATER RETURN
GHCS GLYCOL HOT/CHILLED
WATER SUPPLY
GHWR GLYCOL HOT WATER RETURN
GHWS GLYCOL HOT WATER SUPPLY
GI GREASE INTERCEPTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GAS VENT
GWH GAS WATER HEATER
HB HOSE BIBB
HC HEATING COIL
HCR HOT/CHILLED WATER RETURN
HCS HOT/CHILLED WATER SUPPLY
ACC AIR COOLED CONDENSER
ACCU AIR COOLED CONDENSING UNIT
ASHP AIR SOURCE HEAT PUMP
ARU AIR ROTATION UNIT
OI OIL INTERCEPTOR
SOI SAND OIL INTERCEPTOR
DSS DUCTLESS SPLIT SYSTEM
SP SUMP PUMP
OST OVERFLOW STORM WATER
WMB WASHING MACHINE BOX
OB OUTLET BOX
RH ROOF HYDRANT
H HUMIDIFIER
DHWP DOMESTIC HOT WATER
RECIRCULATING PUMP
DWET DOMESTIC WATER EXPANSION
TANK
HP HORSEPOWER
HPR HIGH PRESSURE RETURN
HPS HIGH PRESURE STEAM
HRC HEAT RECOVERY COIL
HWR HOT WATER RETURN (HEATING)
HWS HOT WATER SUPPLY (HEATING)
HX HEAT EXCHANGER
HY HYDRANTS
HP-_ HEAT PUMP
HVLS HIGH VOLUME LOW SPEED
IH INTAKE HOOD
IRH INFRARED RADIANT HEATER
KH KITCHEN HOOD
KW KILOWATT
KWH KILOWATT HOURS
L LAVATORY
LAT LEAVING AIR TEMPERATURE
LPR LOW PRESSURE RETURN
LPG LIQUIFIED PETROLEUM GAS
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPS
LS LAUNDRY SINK
LV LOUVER
LWT LEAVING WATER TEMPERATURE
PROJECT MECHANICAL REFERENCED DEMOLITION NOTES PROJECT MECHANICAL REFERENCED NOTES
HF WHOLE HOUSE FAN
M 00.2 MECHANICAL INFO SHEET
M 01.2 SHEET SPECIFICATIONS - MECHANICAL
M 02.2 SHEET SPECIFICATIONS - MECHANICAL
MD01.2 DEMOLITION FLOOR PLAN - MECHANICAL
M101.2 FLOOR PLAN - MECHANICAL
M102.2 FLOOR PLAN - MECHANICAL
M401.2 DETAILS - MECHANICAL
M501.2 SCHEDULE - MECHANICAL
DATE INITIAL
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M 01.2
SHEET SPECIFICATIONS -
MECHANICAL
009258015-6-M 01.2 SHEET SPECIFICATIONS - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M 02.2
SHEET SPECIFICATIONS -
MECHANICAL
009258015-6-M 02.2 SHEET SPECIFICATIONS - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
UP UP
RA
SA
SA
RA
SA
SA
RA
RA
S A
S A
S A
R A S A
R A
S A
RA
2 2 2 2
33 3
R S
/R L
R S
/R L
R S
/R L
R S
/R L
44444
4 4 4
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
MD01.2
DEMOLITION FLOOR PLAN -
MECHANICAL
009258015-6-MD01.2 DEMOLITION FLOOR PLAN - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
REF. DEMO NOTES ( ):X
1 REMOVE EXISTING EXHAUST FAN.
2 REMOVE EXISTING CONDENSING UNIT AND LINE SETS. PREPARE FOR NEW
CONSTRUCTION.
3 REMOVE EXISTING FURNACE.
4 AIR TERMINAL TO REMAIN. ABANDON IN PLACE.
5 REMOVE TOP WINDOW PANES AND PREPARE FOR NEW CONSTRUCTION. SEE
ARCHITECTURAL FOR DETAILS. COORDINATE REMOVAL WITH NEW OUTSIDE AIR
CONSTRUCTION SCHEDULE TO LIMIT EXTERIOR EXPOSURE TO INTERIOR.
6 REMOVE TOP WINDOW AND PREPARE FOR NEW OUTSIDE AIR CONSTRUCTION. SEE
ARCHITECTURAL FOR DETAILS. COORDINATE REMOVAL WITH NEW CONSTRUCTION
SCHEDULE TO LIMIT EXTERIOR EXPOSURE TO INTERIOR.
7 REMOVE EXISTING RETURN AIR DUCT UP TO CEILING. PREPARE FOR NEW OUTSIDE AIR
CONNECTION.
8 CAP AND ABANDON RETURN AIR DUCT.
9 ABANDON SUPPLY AIR DUCT SERVING GRAND HALL ABOVE.
SCALE: 1/8" = 1'-0"
FIRST FLOOR DEMOLITION PLAN - MECHANICAL
SCALE: 1/8" = 1'-0"
SECOND FLOOR DEMOLITION PLAN - MECHANICAL
NORTH
DATE INITIAL
0 6 12 18 '''' 0 6 12 18 ''''
T
H S
T
RA
S A
EF-1
EF-1
AHU-1
HP-1 HP-4 HP-3 HP-2
AHU-2
DH-1
R S
/R L
RS/RL
8 Ø S-(E)
8 Ø S-(E)
8 Ø S-(E)
8 Ø S-(E)
8 Ø S-(E) 150
8 Ø S-(E)
12 Ø
8 Ø
8 Ø x1
8 Ø S-(E)
8 Ø S-(E)
14x12
14x12 RA 14x12 SA
14x12 RA
1 1/2" CD
10x8 S-3
8 Ø S-(E)
8 Ø S-(E)
16x16 R-1
12x12 R-(E)
12x12 R-(E)
8x8
EXISTING TO REMAIN
(TYP.)
12x12 R-(E)
12 Ø
14x12 SA
16x12 RA
14x12
RS/RL UP
CD UP
3/4" CD
R S
/R L
6 Ø EA
8 Ø8 Ø
8x20 OA
12 Ø S-1
16x16 R-1
AHU-2
16x8 RA
16x8 RA
16x8 RA
16x16 R-1
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M101.2
FLOOR PLAN - MECHANICAL
009258015-6-M101.2 FLOOR PLAN - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
REF. NOTES ( ):X
1 IF VOLUME 1 (PMIS 307909) IS SELECTED, OMIT EXHAUST FAN AND DUCTING.
2 EXTEND CONDENSATE TO EXISTING FLOOR DRAIN. TERMINATE WITH AHJ APPROVED AIR
GAP.
3 EXTEND 6" DIAMETER OUTSIDE AIR DUCT FROM OUTSIDE AIR PLENUM BOX. PROVIDE
MOTORIZED DAMPER IN DUCT AND INTERLOCK AHU-2. PROVIDE BALANCING DAMPER AND
BALANCE TO 100 CFM.
4 REPLACE TOP OF EXISTING WINDOW PANE WITH APPROXIMATELY 42" X28" LV-1. FIELD
VERIFY DIMENSIONS. PROVIDE 10" DEEP INSULATED PLENUM BEHIND LOUVER. BOTTOM
WINDOW PANE TO REMAIN. COORDINATE WITH ARCHITECTURAL.
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - MECHANICAL NORTH
DATE INITIAL
0 3 6 9 ''''
T
T H
H
S
S
SWSW
M
M
10 Ø S-1
14x14 R-1
14x14 R-1
(TYP.10)
30x24 R-(E)
30x24 R-(E)
3x48 S-2
HUMIDITY REMOTE
SENSOR
5'-0" A.F.F.
HUMIDITY REMOTE
SENSOR
5'-0" A.F.F.
AHU-4
AHU-3
CD UP/DN
RS/RL UP/DN
(TYP. 2)
12x6 RLA
212x12 R-1
12x12 R-1
12"X12" UP12"X12" UP
12x6 RLA
3x48 S-2
(TYP. 2)
INTERLOCK
SWITCHES WITH SF-1.
5'-0" A.F.F.HUMIDIFIER INTAKE
HUMIDIFIER INTAKE
3x48 E-1 3x48 E-1 3x48 E-1
S A
S A
RS/RL
RS/RL
1 1/2" CD
AHU-3
AHU-4
VD IN DROP (TYP.)
VD IN DROP (TYP.)
FILTER BOX
F
IL
T E
R B
O X
DH-1
RA
8" Ø DN
(TYP.)
12x12 10x10 8 Ø
12 Ø
14x14
14x14 RA
12 Ø
14x14
1 1/4" CD
14x14
14x14 RA14x14
12 Ø 12 Ø
14x12 12x12 8 Ø
8 Ø
8 Ø
12x12 RLA
12X12 OA DN, ROUTE IN
PORCH ATTIC SPACE TO
INTAKE GRILLS.
CD DN
RS/RL DN
RA DN
RA DN
1" CD
1" CD 1" CD
1 1/4" CD
8x
O A
20"X8"
OUTSIDE AIR
FROM BELOW
DH-1
12 Ø SA
SF-1
SF-1
12x12 RLA
12X12 OA OPEN ON
TOP. PROVIDE
INSECT SCREEN.
12X12 OA DN, ROUTE IN
PORCH ATTIC SPACE TO
INTAKE GRILLS.
12X12 OA OPEN ON
TOP. PROVIDE
INSECT SCREEN.
2X6 JOIST - 18" O.C.
NOTE: COORDINATE WITH
TRUSSES WITH ALL DUCTING
AND EQUIPMENT BEING
INSTALL.
SECOND FLOORBALCONY
FIRST FLOOR
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M102.2
FLOOR PLAN - MECHANICAL
009258015-6-M102.2 FLOOR PLAN - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
REF. NOTES ( ):X
1 PROVIDE 12" DEEP DUCT PLENUM BEHIND TO PREVENT INSULATION AND DEBRIS FROM
BLOCKING THE BACKSIDE OF THE VENT.
2 EXTEND EXISTING RETURN DUCT UP INTO ATTIC FOR OUTSIDE AIR CONNECTION.
3 8" DIAMETER OUTSIDE AIR DUCT WITH MOTORIZED DAMPER INTERLOCKED WITH AHU
FAN. PROVIDE BALANCING DAMPER, BALANCE TO 185 CFM.
SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN - MECHANICAL
SCALE: 1/4" = 1'-0"
ATTIC PLAN - MECHANICAL
NORTH
DATE INITIAL
0 3 6 9 ''''0 6 12 18 ''''
NOT TO SCALE
BUILDING CROSS SECTION - MECHANICAL
DIRT LEG
TO EQUIPMENT
SHUT-OFF VALVE
REMOVABLE
CAP
UNION
SUPPLY PIPING
PRESSURE REGULATOR (IF REQUIRED)
ECCENTRIC TRANSITION
B (MAX.)=30°
(EXCEPT 45° IS PERMITTED AT
ROUND TO FLAT OVAL)
(ANGLED)
Offset Type 1
C (MAX.)=45° DIVERGING, 60° CONVERGING
CONCENTRIC TRANSITION
W
W
L
A (MAX.)=15°
A
W
L
W
W
B
W
W
L
C
SHEET METAL 90° ELBOW
DIFFUSER NECK
TRANSITION
(AS REQUIRED)
CEILING
SUPPLY DUCT-SEE
PLANS FOR SIZES
SUPPLY DIFFUSER
DUCT INSULATION
FLEX DUCT
INSULATED BACKPAN
ELEVATION PLAN
ELEVATION PLAN
DUCT
DUCT SEAM
FLOOR CONSTRUCTION
ANGLE IRON RIVETED
TO DUCT, SEE SIZING
CHART
DUCT
FLOOR CONSTRUCTION
DUCT
DUCT AND
SEAM
LOCATE A FASTENER WITHIN 2" OF
THE DUCT EDGES. LOCATE OTHERS
AT EVENLY SPACED INTERVALS PER
SMACNA.
DUCT SIZE ANGLE
36" x 18" 1-1/2" x 1-1/2" x 1/8" 48" x 24" 1-1/2" x 1-1/2" x 1/8" 60" x 30" 1-1/2" x 1-1/2" x 3/16" 60" x 30" 1-1/2" x 1-1/2" x 1/4" or 2" x 2" x 1/8"
DUCT DIA. BAND SIZE BOLT DIA.
UP TO 12" 1" x 16 GAUGE 1/4" 13" TO 24" 1-1/2" x 16 GAUGE 1/4" 25" TO 36" 2" x 16 GAUGE 3/8" 37" TO 60" 2" x 10 GAUGE 3/8"
SPLIT BAND
SUPPORT
FASTENER, MIN. OF 2 IN EACH
HALF OF BAND OR SPACE THEM
AT 8"
DUCT JOINT
CONNECTION
C-CHANEL
SPLIT BAND
SUPPORT
C-CHANEL
NOTE: FIRE CAULK AS REQUIRED.
SL
AB
A T
BO
TH
E
ND
S (T
YP
AN
G
LE
S
TO
H
AV
E
3" B
EA
R
IN
G
O N
SL
AB
A T
BO
TH
E
ND
S.
(T
YP
AN
G
LE
TO
H
AV
E 3"
B
EA
R
IN
G O
N
DAMPER
STANDOFF
DAMPER
QUADRANT LOCK
NOTE:
ALL TAPS TO AIR TERMINALS REQUIRING BALANCING AT DUCT SHALL
BE MADE USING A HIGH EFFICIENCY TAKEOFF.
TYPE RE 1
RADIUS ELBOW
CENTERLINE R = (3W)/2 UNLESS OTHERWISE
SPECIFIED Θ IS NOT RESTRICTED TO 90°.
W
H
R
Θ
TYPE RE 2
SQUARE THROAT ELBOW
WITH VANES
TYPE RE 3
RADIUS ELBOW WITH VANES
NOT PERMITTED
DO NOT USE
FLOORS
E
E N
O T
E S
B E
L O
W
T Y
P
IC
A L
L Y
A
.F .F
TYPICAL HVAC CONTROL DEVICE INSTALLATION
THERMOSTAT
OR OTHER HVAC
CONTROL DEVICE
LIGHT
SWITCH
NOTES:
1. WHEN THERMOSTAT IS LOCATED ADJACENT TO LIGHT SWITCH OR OTHER
WALL MOUNTED ELECTRICAL OR CONTROL DEVICE, DEVICES TO BE
INSTALLED AT THE SAME ELEVATION.
2. ALL USER INPUT BUTTONS OR SWITCHES ON CONTORL DEVICE TO BE
LOCATED BELOW 48" A.F.F. TO MEET ADA REQUIREMENTS.
3. WHEN INSTALLED NEAR DOOR, LIGHT SWITCH SHALL BE DEVICE CLOSEST TO
DOOR FRAME.
4. IF DEVICE IS LOCATED ABOVE COUNTER, INSTALL AT 40" A.F.F.
CL
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M401.2
DETAILS - MECHANICAL
009258015-6-M401.2 DETAILS - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
SCALE: NOT TO SCALE
TYPICAL GAS PIPING DETAIL
SCALE: NOT TO SCALE
OFFSETS AND TRANSITIONS DETAIL
SCALE: NOT TO SCALE
SUPPLY DIFFUSER/ DUCT CONNECTION DETAIL
SCALE: NOT TO SCALE
VERTICAL DUCT SUPPORT DETAILS
SCALE: NOT TO SCALE
HIGH EFFICIENCY TAKEOFF DETAIL
SCALE: NOT TO SCALE
DUCT ELBOW DETAIL
SCALE: 12" = 1'-0"
THERMOSTAT DETAIL
TOTAL
HEIGHT
OF TRAP
TO FLOOR DRAIN
TOTAL HEIGHT OF TRAP:
X + H + (1 1/2 x PIPE DIAMETER)
H = AT LEAST 1 INCH PLUS
CASING STATIC PRESSURE
X = 1/2 "H"
COIL CONDENSATE
DRAIN PAN
SLOPE DOWN
X
H
CLEAN OUT
HOUSEKEEPING PAD,
HEIGHT IS BASED ON TRAP
HEIGHT
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \m b e c k m a n n
\D o c u m e n ts
\0
-M e c h
H S
R m b e c k m a n n s c h e m m e r.
c o m .r v t
MPH
MLB
MPH
4/9/2026
09258015
M501.2
SCHEDULE - MECHANICAL
009258015-6-M501.2 SCHEDULE - MECHANICAL
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
SCALE: NOT TO SCALE
CONDENSATE DRAIN TRAP NEGATIVE STATIC PRESSURE
2. PROVIDE WITH NEMA 3R RATED SCCR DISCONNECT SWITCH.
NOTES: 1. UNIT TO BE PROVIDED WITH HAIL GUARD AND LOW AMBIENT OPERATION .
HP-4 OUTDOOR AHU-4 R-32 123.5 11 95 12 2 ROTARY 2 125 27x56x13 211.6 62 208 1 36.2 40 SAMSUNG AC048DXSCCG/AA (CXG48SCD) 1,2
HP-3 OUTDOOR AHU-3 R-32 123.5 11 95 12 2 ROTARY 2 125 27x56x13 211.6 62 208 1 36.2 40 SAMSUNG AC048DXSCCG/AA (CXG48SCD) 1,2
HP-2 OUTDOOR AHU-2 R-32 123.5 10 95 13 2 ROTARY 2 125 37x56x13 211.6 60 208 1 35 40 SAMSUNG AC030DXSCCG/AA (CXG30SCD) 1,2
HP-1 OUTDOOR AHU-1 R-32 123.5 10 95 13 2 ROTARY 2 125 37x56x13 211.6 60 208 1 35 40 SAMSUNG AC030DXSCCG/AA (CXG30SCD) 1,2
QTY TYPE QTY WATTS
DIMENSIONS
(HxWxL)
WEIGHT
(LBS)
SOUND
(dBA) VOLTAGE PHASE MCA MOCPMARK LOCATION SERVES
REFRIGERANT
TYPE
REFRIGERANT
CHARGE (OZ)
MIN CAP
MBH
AMBIENT
TEMP (°F)
EFFICIENCY
(EER)
COMPRESSOR DATA CONDENSER FAN DATA PHYSICAL DATA ELECTRICAL DATA
BASIS OF DESIGN REMARKS
AIR COOLED CONDENSING UNIT SCHEDULE
2. PROVIDE WITH DEH3000 CONTROLLER AND REMOTE SENSOR. PROVIDE WITH MINIBLUE CONDENSATE PUMP. INTERLOCK WITH ASSOCIATED HEAT PUMP TO LOCK OUT HUMIDIFIER WHEN HEAT PUMP COMPRESSOR IS RUNNING.
NOTES: 1. AHU'S FAN IS TO RUN WHILE UNIT IS ON.
DH-1 AHU 115 500 R454B 18 18 75 50 26.8 23.6 20.9 130 3/4 0.75 6.9 120 1 60 15 15 QWEST 115 1,2
WIDTH HT TEMP (°F) % RH LENGTH (IN) WIDTH (IN) HEIGHT (IN) WEIGHT (LBS)
DRAIN
CONNECTION (IN) KW AMP VOLTS PH HZ MCA MOPMARK SERVES
HUMIDIFICATION
CAPACITY
(PINT/DAY) CFM REF TYPE
DUCT CONDITIONS PHYSICAL DATA ELECTRICAL DATA
BASIS OF DESIGN REMARKS
ELECTRIC DEHUMIDIFIER SCHEDULE
NOTES: 1. PROVIDE WITH BIRD SCREEN, BACKDRAFT DAMPER AND SPEED CONTROLLER.
SF-1 ATTIC INLINE 470 0.2 DIRECT 1550 5.4 SONES 1/10 --- 115 1 60 60 WALL SWITCH GREENHECK SQ-90-VG1X-QD 1
TYPE CFM
EXT SP
(IN WG) DRIVE RPM SOUND LEVEL HP WATTS VOLTS PH HZMARK LOCATION
FAN DATA ELECTRICAL DATA UNIT
WEIGHT
(LBS) FAN CONTROL BASIS OF DESIGN REMARKS
FAN SCHEDULE
NOTES: 1. PROVIDE UNIT WITH REFRIGERANT DETECTION SYSTEM.
AHU-4 GRAND HALL 1450 185 0.58 98.4 75.4 48 54 34 15 208 1 590 208 1 60 18 SAMSUNG AC048DNZDCG/AA (CNG48ZDD) 1
AHU-3 GRAND HALL 1450 185 0.58 98.4 75.4 48 54 34 15 208 1 590 208 1 60 18 SAMSUNG AC048DNZDCG/AA (CNG48ZDD) 1
AHU-2 DRESSING ROOMS 1000 100 0.58 98.4 75.4 30 34 31 10 208 1 410 208 1 60 19 SAMSUNG AC030DNZDCG/AA (CNG30ZDD) 1
AHU-1 RESTROOM GROUP 1000 0 0.58 98.4 75.4 30 34 31 10 208 1 410 208 1 60 19 SAMSUNG AC030DNZDCG/AA (CNG30ZDD) 1
EDBT (°F)
EWBT
(°F)
TOTAL CAP
(MBH)
TOTAL CAPACITY
(MBH)
TEMP RISE
(°F) KW VOLT PH W VOLTS PH HZ SEER2MARK SERVES
TOTAL
CFM OUTSIDE AIR CFM
ESP (IN
WG)
COOLING DATA HEATING DATA SUPPLEMENTAL ELEC. HEAT DATA ELECTRICAL DATA
BASIS OF DESIGN REMARKS
HEAT PUMP BLOWER COIL UNIT SCHEDULE
2. PROVIDE WITH STANDARD WHITE GRILL AND CEILING RADIATION DAMPER.
NOTES: 1 . PROVIDE WITH GREENHECK WC-6, BIRD SCREEN, BACKDRAFT DAMPER AND SPEED CONTROLLER.
EF-1 RESTROOMS CEILING 225 0.38 DIRECT 900 4.5 SONES 57 110 1 60 24 OCC. SENSOR GREENHECK SP-A250 1,2
TYPE CFM
EXT SP
(IN WG) DRIVE RPM
SOUND
LEVEL HP VOLTS PH HZMARK LOCATION
FAN DATA ELECTRICAL DATA UNIT
WEIGHT
(LBS) FAN CONTROL
MANUFACTURER AND
MODEL NUMBER REMARKS
CEILING EXHAUST FAN SCHEDULE
DATE INITIAL
2. SIZE TO APPROXIMATLY MATCH TOP WINDOW PANE. FIELD VERIFY FOR EXACT MEASUREMENTS. PROVIDE INSECT SCREEN. PROVIDE CUSTOM COLOR TO MATCH
BUILDING EXTERIOR. COLOR TO BE SELECTED BY ARCHITECT.
NOTES: 1. PROVIDE WITH BIRD SCREEN AND COLOR TO BE SELECTED BY ARCHITECT.
LV-1 OUTSIDE AIR ALUMINUM 460 --- 500 42 28 6 SEE ARCH RUSKIN ELF375DX 1
W H DMARK SERVES MATERIAL CFM
MAX SP
(IN WG)
FREE AREA FACE
VELOCITY
(FPM)
SIZE (INCHES)
FINISH BASIS OF DESIGN REMARKS
LOUVER SCHEDULE
NOTES: 1. PROVIDE WITH STRAIGHTENING GRID IN NECK.
R-1 SURFACE 24 X 24 SEE PLANS --- --- STEEL / WHITE 0.1 25 KRUGER EGC10 1
E-1 SURFACE 4x48 SEE PLANS --- --- STEEL / WHITE 0.1 25 BRAND X METAL SV75-V-400/50 ---
S-2 SURFACE 4x48 SEE PLANS --- --- STEEL / WHITE 0.1 25 BRAND X METAL SV75-V-400/50 ---
S-1 LAY-IN 24 X 24 SEE PLANS --- DAMPER IN DUCT STEEL / WHITE 0.1 25 KRUEGER PLQ 1
MARK
MOUNTING
TYPE FACE SIZE (IN.) NECK SIZE (IN.)
BLADE
ANGLE VOLUME CONTROL MATERIAL / FINISH
MAX PD (IN
WG)
MAX NC AT
PD SHOWN BASIS OF DESIGN REMARKS
DIFFUSER, REGISTER AND GRILLE SCHEDULE
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E 00.2
ELECTRICAL INFO SHEET
009258015-7-E 00.2 ELECTRICAL INFO SHEET
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
E 00.2 ELECTRICAL INFO SHEET
E 01.2 ELECTRICAL INFO SHEET
E 02.2 ELECTRICAL SPECIFICATIONS
E 03.2 ELECTRICAL SPECIFICATIONS
E 04.2 ELECTRICAL SPECIFICATIONS
ED01.2 FLOOR PLAN - DEMOLITION
E201.2 FLOOR PLAN - POWER
E202.2 FLOOR PLAN - POWER
E501.2 POWER RISER DIAGRAMS
E601.2 ELECTRICAL SCHEDULES
S
NORTH
ARROW
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE NOTE
REFERENCE
DEMOLITION NOTE
ROOM
NUMBER
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES EXISTING
COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF
VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
ABBREVIATIONS
ROOM NAME
150 SF
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
ROOM AREA DESIGNATION
SYMBOL LEGEND
P C
J
J
O S
MS
IC
S
S
M
N
T V
VC
N E
N S
N
N D
N 2
G
K1
V
A
R
M
M
T
WALL MOUNTED STRIP LUMINAIRE
SYMBOL NOTES:
PHOTOCELL
VOICE AND DATA
JUNCTION BOX - CEILING MOUNT
JUNCTION BOX - WALL MOUNT
VOICE OUTLET
DATA OUTLET
OCCUPANCY SENSOR
MOTION SENSOR
CEILING FAN
POLE MOUNTED SITE LUMINAIRE
FLOOD LIGHT
NURSE CALL
SPEAKER
BEDSIDE STATION
INTERCOM SPEAKER STATION
VOLUME CONTROL STATION
MICROPHONE JACK
TELEVISION OUTLET
CCTV CAMERA
SOUND, TELEVISION, AND SECURITY
FUSE
EMERGENCY PULL STATION
DISCONNECT SWITCH
STAFF STATION
DUTY STATION
DOME LIGHT
MASTER STATION
EMERGENCY GENERATOR
POWER DISTRIBUTION ONE LINE
CONDUIT UP
CONDUIT DOWN
INDICATES BUSHED CONDUIT
VOICE/DATA OUTLET
DOUBLE BED BEDSIDE STATION
DRAW OUT VACUUM CIRCUIT BREAKER
LIGHTNING SURGE ARRESTOR
THERMAL OVERLOAD RELAY
PLUG-IN OR DRAWOUT CONNECTOR
CIRCUIT BREAKER
FUSED DISCONNECT SWITCH
VOLTMETER
AMMETER
X:Y CURRENT TRANSFORMER - (RATIO)
KIRK KEY INTERLOCK
"C" INDICATES CEILING MOUNTED
"F" INDICATES FLOOR MOUNTED
"S" INDICATES SURFACE MOUNTED
"G" INDICATES GROUND FAULT INTERRUPTING
"IG" INDICATES ISOLATED GROUND
"AC" INDICATES MOUNTING 6" ABOVE
COUNTERTOP OR BACKSPLASH
"WP" INDICATES WEATHERPROOF
"XP" INDICATES EXPLOSION PROOF
"U" INDICATES USB CHARGER
"R" INDICATES EXISTING DEVICE REMOVED
AND RELOCATED
LOWER CASE LETTER BY SWITCHES AND
FIXTURES
INDICATE ASSOCIATED UNIT FOR SWITCHING
LIGHTING
LUMINAIRE
WALL MOUNTED LUMINAIRE
RECESSED LUMINAIRE
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE
TRACK LIGHTING
DIMMER SWITCH
TIMER SWITCH
WIRING DEVICES - SWITCHES
SINGLE POLE SWITCH
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT
THERMAL ELEMENT SWITCH
FOUR-WAY SWITCH
TWO POLE SWITCH
THREE-WAY SWITCH
STRIP / INDUSTRIAL LUMINAIRE
LUMINAIRE - NIGHT LIGHTING
LUMINAIRE - EMERGENCY SYSTEM
EMERGENCY BATTERY PACK LUMINAIRE
REMOTE EMERGENCY HEAD
WALL WASH LUMINAIRE
PENDANT MOUNTED LUMINAIRE
POWER POLE
METER SOCKET
POWER EQUIPMENT
WIRING DEVICES - RECEPTACLES
COMBINATION STARTER SAFETY
SWITCH
RELAY - CONTROL AS NOTED
PUSHBUTTON STATION
MOTOR CONNECTION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
EMERGENCY RECEPTACLE
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION NOTED
PLUG-IN STRIP - LENGTH AND
QUANTITY OF OUTLETS AS SHOWN
SAFETY SWITCH
DROP CORD RECEPTACLE ASSEMBLY
FUSIBLE SWITCH (FUSETRON)
PANELS AND CABINETS
DISTRIBUTION PANEL
SWITCHBOARD, SWITCHGEAR, MCC
EQUIPMENT OR TERMINAL CABINET
DRY TYPE TRANSFORMER
BRANCH CIRCUIT PANEL
CONDUIT AND BOXES
HORN (PA, PUBLIC
ADDRESS)
TRANSFORMER
EXIT LIGHT - WALL MOUNT WITH
DIRECTIONAL ARROWS AS
INDICATED, FILLED-IN QUARTERS
INDICATE ILLUMINATION SIDES
EXIT LIGHT - CEILING OR PENDANT
MOUNT WITH DIRECTIONAL ARROWS
AS INDICATED, FILLED-IN QUARTERS
INDICATE ILLUMINATION SIDES
EMERGENCY EXIT LIGHT COMBO
LOW VOLTAGE MOMENTARY
CONTACT SWITCH
N P PILLOW SPEAKER
FB FLOOR BOX
FP FLOOR POKE-THROUGH DEVICE
N M
WIRELESS ACCESS POINT
S
S2
S3
S4
SD
SK
SP
STE
ST
SFT
X
CONTROLLED RECEPTACLE
WB WALL AV BOX
F
F
F
F
F S
D
P S
T S
DH
STROBE
HORN
MANUAL PULL STATION
HORN STROBE
HEAT DETECTOR
SMOKE DETECTOR
REMOTE INDICATOR LIGHT
SPRINKLER TAMPER SWITCH
DUCT SMOKE DETECTOR
FLOW SWITCH
POST INDICATING VALVE SWITCH
MAGNETIC DOOR HOLDER
FIRE ALARM SYSTEM
H
S
S
F SPEAKER STROBES
F SPEAKERS
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
AFF ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
AUTO AUTOMATIC
AVG AVERAGE
L ANGLE
BKR BREAKER
C OR CL CENTER LINE
C OR CND CONDUIT (ELECTRICAL
SHEETS)
CKT CIRCUIT
CLG CEILING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CPT CONTROL POWER
TRANSFORMER
DC DIRECT CURRENT
DEG DEGREE
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
E EAST
EA EACH
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR
ELECTRICAL
ELEV ELEVATOR
EMD ESTIMATED MAXIMUM
DEMAND
ENCL ENCLOSURE
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER
COOLER
EXIST, EXTG EXISTING
EXP EXPOSED
EXT EXTERIOR
FA FIRE ALARM
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
AWG GAUGE
HP HORSE POWER
HR HOUR
HTG HEATING
HTR HEATER
HZ HERTZ
ID INSIDE DIAMETER
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
KCMIL KCM KILO CIRCULAR MIL
KV KILOVOLTS
KVA KILOVOLT AMPERES
KW KILOWATT
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FACP FIRE ALARM CONTROL PANEL
FAEP FIRE ALARM EXTENDER PANEL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CUH CABINET UNIT HEATER
EMI ELECTROMAGNETIC
INTERFERENCE
MCCB MOLDED CASE CIRCUIT
BREAKER
GFI GROUND FAULT CIRCUIT
INTERRUPTER
QTY QUANTITY
REC RECEPTACLE
REFR REFRIGERATOR
REINF REINFORCEMENT
REQD REQUIRED
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PSI POUNDS PER SQUARE IN.
OCPD OVERCURRENT PROTECTIVE
DEVICE
RFI RADIO FREQUENCY
INTERFERENCE
TEL TELEPHONE
TEMP TEMPERATURE
TVSS TRANSIENT VOLTAGE
SURGE SUPPRESSOR
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UPS UNINTERRUPTIBLE
POWER SYSTEM
VFD VARIABLE FREQUENCY
DRIVE
W WEST
W/ WITH
W/O WITHOUT
WHM WATTHOUR METER
WT WEIGHT
XFMR TRANSFORMER
SOUTH
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SPEC SPECIFICATIONS
SPKR SPEAKER
SQ SQUARE
STD STANDARD
STL STEEL
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
S
SCCR SHORT CIRCUIT CURRENT
RATING
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE
THROW
VFC VARIABLE FREQUENCY
CONTROLLER
NON-SCHEDULED
EQUIPMENT
XXXX
SCHEDULED
EQUIPMENT EQUIPMENT NUMBER
XX-XX PANEL & CIRCUIT NUMBER
XX
EQUIPMENT SIZE
(WHERE APPLICABLE)
EQUIPMENT
XX-XX PANEL & CIRCUIT NUMBER
EQUIPMENT NAME/NUMBER
NORTH PLAN
NORTH
TRUE
NORTH
ELECTRICAL SHEET LIST
04/09/2026
A. SEE ARCHITECTURAL SHEETS FOR EXACT AREAS AND WALLS
AFFECTED BY THE DEMOLITION AND REMODEL.
B. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR
SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS.
ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE
SHOWN AS HALF-TONE.
C. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE
PROJECT. COORDINATE DEMOLITION WITH THE WORK OF OTHER
TRADES. PROVIDE TEMPORARY POWER AND LIGHTS AS
REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO
PROCEED OR AS REQUIRED TO ALLOW THE OWNER TO OCCUPY
THE SPACE.
D. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING
ARE EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES
WERE OBTAINED FROM EXISTING DRAWING AND FIELD
INVESTIGATION. THE LOCATIONS OF THE EXISTING EQUIPMENT
AND DEVICES ARE SHOWN FOR THE CONVENIENCE OF THE
CONTRACTOR. ACCURACY OF THE INFORMATION SHOWN IS NOT
GUARANTEED. THE CONTRACTOR IS ENCOURAGED TO VERIFY ALL
EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. SITE VISITS
PRIOR TO SUBMISSION OF BIDS NEED TO BE FULLY COORDINATED
WITH THE OWNER.
E. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE
VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE
INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES
IS NOT GUARANTEED.
F. LUMINAIRES AND DEVICES INDICATED TO BE REMOVED, WHICH
ARE LOCATED ON CEILINGS OR WALLS, SHALL HAVE LUMINAIRES,
DEVICE AND ALL ASSOCIATED CIRCUIT WIRING AND CONDUIT
REMOVED BACK TO NEAREST JUNCTION BOX, OR DEVICE NOT
INDICATED TO BE REMOVED. ACTUAL CIRCUITING MUST BE
DETERMINED IN THE FIELD. THE CONTRACTOR SHALL PROVIDE
ALL NECESSARY WIRE, CONDUIT, DEVICES AND CONNECTIONS
NECESSARY TO ENSURE CIRCUIT CONTINUITY OF THE REMAINING
DEVICES.
G. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE
MATERIAL. ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT
SHALL BE REMOVED FROM THE SITE AND PROPERLY DISPOSED
OF BY THE CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR
THE REMOVAL OF ANY PCB BALLAST OR HAZARDOUS LAMPS.
H. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE
LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT
BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE
CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE
CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND
PANEL LOADING WILL ALLOW.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE
PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING
PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE
TO THE DEMOLITION WORK DONE BY THE ELECTRICAL
CONTRACTOR, UNDER THE TERMS OF THIS SPECIFICATION.
CLOSE AND SEAL ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS
REQUIRED.
J. FIRE ALARM DEVICES SHALL BE REMOVED, REPLACED AND
RECONNECTED TO FIRE ALARM SYSTEM AS SPECIFIED. DUCT
SMOKE DETECTORS AND FIRE SMOKE DAMPERS SHALL BE
REMOVED ONLY WHEN THE ASSOCIATED MECHANICAL
EQUIPMENT IS BEING REMOVED.
K. EXISTING FIRE ALARM DEVICES, EMERGENCY LIGHTS AND EXIT
SIGNS SHALL BE COMPLETE AND OPERABLE AT ALL TIMES.
PROVIDE TEMPORARY DEVICES IN AREAS BEING WORKED ON TO
ALLOW FOR A WORKABLE SYSTEM DURING CONSTRUCTION.
L. PROVIDE MINIMUM [2] DAYS ADVANCE NOTICE OF OUTAGES.
COORDINATE WITH OWNER FOR ALL ANTICIPATED OUTAGES.
OWNER HAS FINAL APPROVAL ON TIME AND EXTENT OF POWER
OUTAGE.
M. PROTECT EXISTING FURNITURE, CARPET AND OTHER
APPURTENANCES FROM DAMAGE DURING THE COURSE OF
CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO
THE OWNER.
A. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS
INDICATED OTHERWISE.
B. ALL AUXILIARY CABLE ABOVE CEILING SHALL BE PLENUM RATED
WHERE REQUIRED.
C. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE
WHERE INSTALLED IN ACOUSTICAL TILE CEILING.
D. PROVIDE 120 VOLT POWER CIRCUIT(S) FOR AUXILIARY SYSTEMS
AS REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS.
A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR
CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS
NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT
FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC,
SHALL ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR
SIZES AS NEEDED TO LIMIT VOLTAGE DROP TO LEVELS
RECOMMENDED BY NEC. THE CONTRACTOR SHALL ALSO
COORDINATE INSPECTIONS WITH THE AHJ.
B. SEE ARCHITECTURAL SHEETS FOR REFLECTED CEILING PLANS.
C. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN
SHARE AN INSULATED GREEN GROUND WIRE IN MINIMUM 3/4" EMT
CONDUIT.
D. NO BOXES SHALL BE MOUNTED BACK TO BACK.
E. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR
FIRE/SMOKE RATED WALLS AND FLOORS.
F. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN
ACCORDANCE WITH NEC PARAGRAPHS 230.8, 300.5(G) AND
300.7(A). ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC
AND NFPA.
G. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT
ACCESS.
H. ALL CABLING ABOVE CEILING SHALL BE PROPERLY SUPPORTED
(NOT FROM CEILING SYSTEM).
I. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES
WITH OWNER.
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E 01.2
ELECTRICAL INFO SHEET
009258015-7-E 01.2 ELECTRICAL INFO SHEET
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
GENERAL LIGHTING NOTES
GEN. POWER & AUX SYS. NOTES
XREF. NOTES ( )
PROJECT ELECTRICAL REFERENCED NOTES
GENERAL NOTES REF. DEMO NOTES ( )
PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES
DXGENERAL DEMO NOTES
SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E 02.2
ELECTRICAL SPECIFICATIONS
009258015-7-E 02.2 ELECTRICAL SPECIFICATIONS
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E 03.2
ELECTRICAL SPECIFICATIONS
009258015-7-E 03.2 ELECTRICAL SPECIFICATIONS
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E 04.2
ELECTRICAL SPECIFICATIONS
009258015-7-E 04.2 ELECTRICAL SPECIFICATIONS
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
S
D4
D4
D5
EXTG PANEL 'HS-6'
D6 (TYP.)
D6(TYP.)
D3
D10
D10
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
ED01.2
FLOOR PLAN - DEMOLITION
009258015-7-ED01.2 FLOOR PLAN - DEMOLITION
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL DEMOLITION - PACKAGE B
DATE INITIAL
REF. DEMO NOTES ( ):DX
D3 DISCONNECT EXISTING EXHAUST FAN FOR REMOVAL BY MECHANICAL.
D4 DISCONNECT EXISTING FURNACE FOR REMOVAL BY MECHANICAL.
D5 DISCONNECT EXISTING CONDENSING UNIT FOR REMOVAL BY
MECHANICAL.
D6 SUPPORT AND REINSTALL LIGHTING/CEILING DEVICES AS NECESSARY
FOR CEILING REMOVAL AND RE-INSTALLATION.
D10 NO ELECTRICAL DEMOLITION IN THIS SPACE.
ALL POWERED RECEPTACLES, DEVICES, AND EQUIPMENT SHOWN SHALL BE
CIRCUITED AS OUTLINED IN THIS NOTE, UNLESS INDICATED OTHERWISE.
PANELBOARD CIRCUITING, INCLUDING IDENTIFYING SEPARATE
PANELBOARDS' BRANCH CIRCUIT AREAS, IS DELINEATED WITH A DASH-DOT
LINE BOUNDARY, WITH PANEL NAMES IDENTIFIED AT BOUNDARY LINE.
CIRCUIT NUMBERS ARE IDENTIFIED ADJACENT TO RECEPTACLE, DEVICE, OR
EQUIPMENT. REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION.
PANELBOARD CIRCUITING
EF-1
EF-1
HS-6 - 23,25
HP-1
HS-6 - 27,29
HP-2
HS-6 - 31,33
HP-3
HS-6 - 35,37
HP-4
HS-6 - 38,40
AHU-2
HS-6 - 39,41
AHU-1
PANEL 'HS-6'
HS-6 - 42
DH-1
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E201.2
FLOOR PLAN - POWER
009258015-7-E201.2 FLOOR PLAN - POWER
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
REF. NOTES ( ):X
6 CONNECT TO UNSWITCHED LIGHTING CIRCUIT SERVING SPACE. PROVIDE
POWER PACK/RELAY COMPATIBLE WITH ROOM LIGHTING CONTROL TO
CONTROL FAN WITH ROOM LIGHTING.
7 AHU UNIT GENERAL POWER SERVED FROM ASSOCIATED HP UNIT WITH
SEPARATE CIRCUIT FOR AUXILIARY HEAT.
12 COORDINATE WORK IN THIS SPACE WITH PROJECT 1.
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - POWER PACKAGE B
ALL POWERED RECEPTACLES, DEVICES, AND EQUIPMENT SHOWN SHALL BE
CIRCUITED AS OUTLINED IN THIS NOTE, UNLESS INDICATED OTHERWISE.
PANELBOARD CIRCUITING, INCLUDING IDENTIFYING SEPARATE
PANELBOARDS' BRANCH CIRCUIT AREAS, IS DELINEATED WITH A DASH-DOT
LINE BOUNDARY, WITH PANEL NAMES IDENTIFIED AT BOUNDARY LINE.
CIRCUIT NUMBERS ARE IDENTIFIED ADJACENT TO RECEPTACLE, DEVICE, OR
EQUIPMENT. REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION.
PANELBOARD CIRCUITING
HS-6A - 2
SF-1
HS-6 - 44,46
AHU-4
HS-6 - 43,45
AHU-3
HS-6A - 2
SF-1
HS-6A - 6
DH-1
HS-6A - 1
DH-1
G
G
HS-6A - 5
HS-6A - 5
EXTG PANEL 'HS-6A'
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E202.2
FLOOR PLAN - POWER
009258015-7-E202.2 FLOOR PLAN - POWER
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
REF. NOTES ( ):X
7 AHU UNIT GENERAL POWER SERVED FROM ASSOCIATED HP UNIT WITH
SEPARATE CIRCUIT FOR AUXILIARY HEAT.
SCALE: 1/4" = 1'-0"
ATTIC FLOOR PLAN - POWER PACKAGE B
SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN - POWER PACKAGE B
PANEL
'XXX'
FIRST FLOOR
SECOND FLOOR
PANEL
'HS-6'
FIRST FLOOR
SECOND FLOOR
EXTG
PANEL
'HS-6A'
F600A3
10FIRST FLOOR
SECOND FLOOR
EXTG
PANEL
'HS-6'
FIRST FLOOR
SECOND FLOOR
EXTG
PANEL
'HS-6A'
D7
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb in g e .r v t
JCB
JCB
KJS
04/09/2026
09258015
E501.2
POWER RISER DIAGRAMS
009258015-7-E501.2 POWER RISER DIAGRAMS
FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD
FORT SCOTT, KS 66701
80073
FINAL CONSTRUCTION DOCUMENTS
341293
REMOVE AND REPLACE HS-6 HVAC
FEEDER SCHEDULE ( ):FXXXXXXX
F600A3 2 SETS OF 3#350 - 2-1/2"C
REF. NOTES ( ):X
8 PROVIDE NEW CONDUIT AND WIRING FROM SERVING UTILITY
TRANSFORMER.
9 RECONNECT EXISTING CIRCUITS TO REMAIN.
10 GROUND PER NEC.
SCALE: NOT TO SCALE
POWER RISER DIAGRAM
SCALE: NOT TO SCALE
POWER RISER DIAGRAM DEMOLITION
GENERAL EQUIPMENT SCHEDULE NOTES:
A. THIS SCHEDULE DISPLAYS SIZING INFORMATION THAT IS GENERIC IN
NATURE. SCHEDULE DOES NOT ITEMIZE ALL INSTANCES OF
EQUIPMENT. CONTRACTOR SHALL REFER TO THE PLANS FOR FINAL
QUANTITIES AND LOCATIONS.
B. MOUNT ALL DISCONNECTS AND STARTERS ON ASSOCIATED
EQUIPMENT UNLESS SHOWN OTHERWISE. MAINTAIN WORKING
CLEARANCES PER NEC; COORDINATE WITH MECHANICAL
CONTRACTOR.
C. BCU = BOX COVER UNIT (COOPER #SSY / #STY OR EQUAL) WITH FUSE.
D. NFD OR FD = NON-FUSED OR FUSED DISCONNECT SWITCH.
E. CS/NFD, FD = COMBINATION STARTER/ NON OR FUSED DISCONNECT
SWITCH.
F. INT = INTEGRAL DISCONNECT FURNISHED WITH EQUIPMENT.
G. ALL SWITCHES, DISCONNECTS, ETC SHALL BE LOCKABLE.
H. ALL SWITCHES, DISCONNECTS, ETC SHALL BE NEMA 3R WHERE
REQUIRED.
I. PROVIDE FUSES AS SHOWN; REVISE SIZES PER ACTUAL NAMEPLATE
DATA.
EQUIPMENT SCHEDULE NOTES:
1. AHU POWERED FROM ASSOCIATED HP, PROVIDE SEPARATE CIRCUIT
FOR AUX HEAT.
2. PROVIDE CONDUIT AND WIRING FROM HP TO ASSOCIATED AHU FOR
GENERAL AHU POWER.
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts
\0
-E le c
H S
R jb…
This is the start of the file's text. The full file is on GovTribe.