B08_Solicitation_-_Att_1_Drawings_Specifications__FOSC_HVAC_341293.pdf

PDF 12 MB Posted

Attached to
FOSC, HVAC Repair & Restroom Remodel
Solicitation number
140P6026Q0041
Issued by

About this file

This is a set of Final Construction Documents for PMIS 341293 - Remove and Replace Furnaces and Condensing Units in Infantry Barracks (Package A - HS6) at Fort Scott National Historic Site in Fort Scott, Kansas. The documents are dated April 9, 2026, and were prepared by Schemmer Associates.

The project scope encompasses the removal and replacement of HVAC equipment including furnaces and condensing units serving the Infantry Barracks building. The construction documents include architectural sheets with reflected ceiling plans and window details; mechanical sheets detailing floor plans, demolition plans, equipment schedules, and specifications for new air handling units, heat pump condensing units, electric dehumidifiers, and various HVAC accessories including ductwork, diffusers, grilles, registers, and louvers; and electrical sheets covering power distribution, demolition plans, floor plans, riser diagrams, and equipment schedules. Key mechanical equipment includes four heat pump condensing units (HP-1 through HP-4), two air handling units (AHU-1 and AHU-2), one electric dehumidifier (DH-1), one exhaust fan (EF-1), and one supply fan (SF-1). Electrical work involves providing new power circuits and disconnects for all mechanical equipment, with service from existing panels HS-6 and HS-6A. The documents establish specifications for materials, installation requirements, demolition procedures, and coordination between trades, along with detailed schedules of all equipment to be installed with manufacturer information and electrical data.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NORTH

PROJECT

LOCATION

CONTRACTOR

PARKING &

STAGING AREA

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs

\r s c a rb o ro u g h \D o c u m e n ts

\0

-A

R C

H

R rS c a rb o ro u g h

D Q

X C

S .r v t

RAS

RAS

JB

4/09/2026

09258015

G1.2

COVER SHEET

009258015-0-G1.2 COVER SHEET

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

FORT SCOTT NATIONAL HISTORIC SITE

MECHANICAL.2

M 00.2 MECHANICAL INFO SHEET

M 01.2 SHEET SPECIFICATIONS - MECHANICAL

M 02.2 SHEET SPECIFICATIONS - MECHANICAL

MD01.2 DEMOLITION FLOOR PLAN - MECHANICAL

M101.2 FLOOR PLAN - MECHANICAL

M102.2 FLOOR PLAN - MECHANICAL

M401.2 DETAILS - MECHANICAL

M501.2 SCHEDULE - MECHANICAL

GENERAL.2

G1.2 COVER SHEET

ELECTRICAL.2

E 00.2 ELECTRICAL INFO SHEET

E 01.2 ELECTRICAL INFO SHEET

E 02.2 ELECTRICAL SPECIFICATIONS

E 03.2 ELECTRICAL SPECIFICATIONS

E 04.2 ELECTRICAL SPECIFICATIONS

ED01.2 FLOOR PLAN - DEMOLITION

E201.2 FLOOR PLAN - POWER

E202.2 FLOOR PLAN - POWER

E501.2 POWER RISER DIAGRAMS

E601.2 ELECTRICAL SCHEDULES

PMIS 341293 - REMOVE AND REPLACE FURNACES AND CONDENSING UNITS IN INFANTRY BARRACKS

PACKAGE A - HS6

ARCHITECTURAL.2

A201.2 REFLECTED CEILING PLAN

DATE INITIAL

FINAL CONSTRUCTION DOCUMENTS

4/09/2026

DRAWING INDEX

4/9/26

S

OS

OS

LIGHT FIXTURES

(SEE ELECTRICAL)

CONTROL JOINT (CJ)

GRILLES AND DIFFUSERS

(SEE MECHANICAL)

GYPSUM BOARD CEILING

LEGEND:

FOR CEILING HEIGHTS, SEE ROOM FINISH SCHEDULE

NEW 2x2 LAY-IN CEILING GRID

AND PADS

FIRE ALARM STROBE, SEE ELEC

FIRE ALARM SPEAKER, SEE ELEC

FIRE ALARM SPEAKER STROBE,

SEE ELEC

OCCUPANCY SENSOR, SEE ELEC

EXIT SIGN, SEE ELEC

FIRE ALARM HORN, SEE ELEC

FIRE ALARM HORN STROBE,

SEE ELEC

SMOKE DETECTOR, SEE ELEC

SPEAKER, SEE ELEC

F

F S

F S

OS

F

F

S

S

26 26 26 26

AFF 8' - 0"

AFF 9' - 6"

320 SF OF ACT CEILING

WOMENS RR

MENS RR

STORAGE

DRESSING

DRESSING

UTILITY

CORRIDOR

FIRE

MECH

EXIST. WALL

NEW REPLICA WOOD WINDOW

WITHOUT GLAZING AT BOTTOM

SASH.

MEETING RAIL

HEAD DETAIL

PREFIN ALUM. BRAKE

MTL SECURED OVER 2X

BLOCKING. ALUM SHALL

COVER ALL EXPOSED

SURFACES OF

BLOCKING

WOOD SASH BOTTOM RAIL

WOOD SILL

SILL DETAIL

EXIST WALL

NO GLAZING AT BOTTOM SASH

NEW LOUVER, LV-1 REF:

MECH. SET LOUVER IN

SEALANT AND SECURE

TO SOLID BLOCKING AS

REC BY MFG.

ALUM. BRAKE MTL ON

BLOCKING AS NOTED.

BOTTOM SASH W/O GLAZING TO ALLOW

AIRFLOW TO LV-1 LOUVER BEHIND

WINDOW, REF: MECH

EXTERIOR ELEVATION

MEETING RAIL

SILL

V

.I .F

3'-6" V.I.F.

NEW REPLICA DOUBLE

HUNG WINDOW TO MATCH

EXISTING WINDOWS.

ASSEMBLY

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs

\r s c a rb o ro u g h \D o c u m e n ts

\0

-A

R C

H

R rS c a rb o ro u g h

D Q

X C

S .r v t

RAS

RAS

JB

4/09/2026

09258015

A201.2

REFLECTED CEILING PLAN

009258015-2-A201.2 REFLECTED CEILING PLAN

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

SCALE: 1/8" = 1'-0"

FIRST FLOOR - REFLECTED CEILING

NORTH DATE INITIAL

22 NO ARCHITECTURAL WORK THIS AREA.

26 CONTRACTOR TO REMOVE TILES AS NECESSARY TO CONDUCT MECHANICAL SCOPE.

REPLACE TILES AFTER WORK IS COMPLETED. CONTRACTOR TO REPLACE ANY DAMAGED

GRID OR TILES .

27 REMOVE EXISTING WINDOW AND SALVAGE FOR OWNER STORAGE. INSTALL NEW REPLICA

WINDOW WITHOUT GLAZING AT BOTTOM SASH. MECHANICAL LOUVER LV-1 TO BE

INSTALLED BEHIND WINDOW. REF: MECHANICAL FOR PRODUCT DETAILS. REF:

ARCHITECTURAL DETAILS 2 & 4 A201.2

28 SOFFIT VENT S-2 / E-1, REF: MECH TYP.

REF. NOTES ( ):X

SCALE: 3/4" = 1'-0"

EXISTING WINDOW ELEVATION

SCALE: 1 1/2" = 1'-0"

EXISTING WINDOW DETAIL

SCALE: 1/8" = 1'-0"

SECOND FLOOR - REFLECTED CEILING

NORTH

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND

LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER

OF ANY DISCREPANCIES OR VARIATIONS FROM THOSE SHOWN ON THE

DRAWINGS. THE CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT

NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL

NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF

DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE WORK

AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN.

FULL-TONE LINES INDICATED NEW OR RELOCATED CONSTRUCTION.

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH

STRUCTURE, CEILING, LIGHTING, AND PIPING.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL EQUIPMENT TO

ALLOW FOR MAINTENANCE ACCESS.

G. ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT ANGLES AND

PARALLEL TO BUILDING WALLS UNLESS OTHERWISE INDICATED.

H. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS. MAINTAIN

ALL CODE REQUIRED CLEARANCES.

I. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER

HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE

CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND

REPORT THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE WORK

IN THE AFFECTED AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY

WRITTEN AGREEMENT OF THE OWNER AND CONTRACTOR.

J. ALL RUNOUTS TO AIR TERMINALS SHALL MATCH INLET SIZE UNLESS OTHERWISE

NOTED.

K. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING CONSTRUCTION

SHALL BE COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.

A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL

DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.

DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED TO BE

REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS FULL-TONE LINES. ALL

OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN AS HALF-

TONE.

B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED BELOW

OR HERE-IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION

AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL

EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED BELOW.

C. THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING EQUIPMENT FROM

FINISHED AREAS AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED

WITH ARCHITECTURAL PLANS AND DETAILS AS WELL AS NOTES ON THE

MECHANICAL DRAWING TO ENSURE PROPER PATCHING AND REPAIR IS MADE TO

THE BUILDING.

D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL

OF ALL EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES

TO BUILD, ERECT, INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH

THE OWNER HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.

E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE

CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND STORED OR

REINSTALLED ON THE SITE AS DIRECTED. REMOVED OR SALVAGED ITEMS SHALL

REMAIN THE PROPERTY OF THE OWNER.

F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND CONTROLS

WITH ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL REMOVALS.

G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER

HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE

CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND

REPORT THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE WORK

IN THE AFFECTED AREA SHALL NOT THEREAFTER BE RESUMED EXCEPT BY

WRITTEN AGREEMENT OF THE OWNER AND ARCHITECT.

H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION SHALL

BE COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.

I. CONTRACTOR RESPONSIBLE FOR ANY DAMAGE CAUSED DURING DEMOLITION.

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M 00.2

MECHANICAL INFO SHEET

009258015-6-M 00.2 MECHANICAL INFO SHEET

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

SYMBOL LEGEND

VOLUME DAMPER

DEMO TO EXISTING CONNECTION

SPRINKLER DRAIN

FIRE SUPPRESSION PIPING

ISOLATION VALVE

TAMPER SWITCH

MANUAL BALANCING VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

CONTROL VALVE (3 WAY)

CONTROL VALVE (2 WAY)

HOSE END DRAIN VALVE

PRESSURE REDUCING VALVE

AUTO FLOW CONTROL VALVE

CHECK VALVE

HVAC DUCTWORK AND SPECIALTIES

(CONT.)

MISCELLANEOUS SYMBOLS

RETURN DUCT DOWN

AIR TERMINAL (VERTICAL MOUNTING)

ROUND DUCT UP / DOUBLE LINE PIPE

ROUND DUCT DOWN / DOUBLE

LINE PIPE

RETURN DUCT UP

TURNING VANES

SUPPLY AND FRESH AIR DUCT DOWN

SUPPLY AND FRESH AIR DUCT UP

SIZE/TYPE

SIZE/TYPE

FLOW

FLOW

SIZE/TYPE

FLOW

SMOKE DAMPER

FIRE DAMPER-HORIZ FIRE SEPARATION

MOTORIZED DAMPER-OPPOSED BLADE

MOTORIZED DAMPER-PARALLEL BLADE

ROUND AIR TERMINAL

(HORIZONTAL MOUNTING)

GRAVITY DAMPER

(OR) SAFETY VALVE-STEAM

TEMP & PRESS RELIEF

FLOOR SINK

FLOOR DRAIN

GRADE CLEANOUT

PLUMBING VENT THRU ROOF

CLEANOUT / WALL CLEANOUT

THERMOSTATIC MIXING VALVE

M

M

MANHOLE

TRENCH DRAIN

OVERFLOW ROOF DRAIN

OXYGEN OUTLET

PIPE CAP

ELBOW UP

AIR OUTLET

TEE

ELBOW DOWN

VACUUM OUTLET

ROOF DRAIN

SIZE/TYPE

FLOW

HUMIDISTAT

THERMOSTAT

FLEXIBLE DUCT

H

T

UNION

TEE DOWN

STRAINER

EXPANSION JOINT

FLEXIBLE PIPE CONNECTION

AIR VENT

TEE UP

FIRE/SMOKE DAMPER

RECTANGULAR RETURN AIR TERMINAL

(HORIZONTAL MOUNTING)

RECTANGULAR SUPPLY AIR TERMINAL

(HORIZONTAL MOUNTING)

SOLENOID VALVE

F

D

TS

VALVES

FS

M

M

S

LPR

HPS

MPR

MPS

LPS

HVAC PIPING

GHWR

GHWS

HWR

HWS

PC

HPR

ES

BBD BOILER BLOW DOWN

EXHAUST STEAM

PUMPED CONDENSATE

HIGH PRESSURE RETURN

HIGH PRESSURE STEAM

MEDIUM PRESSURE RETURN

MEDIUM PRESSURE STEAM

LOW PRESSURE RETURN

LOW PRESSURE STEAM

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

FS-_

FD-_

CO

VTR

GCO

ORD-_

MH

X

A

V

RD-_

PIPING SPECIALTIES AND FITTINGS

WCO

FIRE PROTECTION

SIZE/TYPE

FLOW

RECTANGULAR EXHAUST AIR TERMINAL

(HORIZONTAL MOUNTING)

CWS

GCWS

CWR

CR

CS

RL

RDL

RS

GCWR GLYCOL CHILLED WATER RETURN

GLYCOL CHILLED WATER SUPPLY

REFRIGERANT LIQUID LINE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION LINE

HCWS

HCWR

HOT/CHILLED WATER SUPPLY

HOT/CHILLED WATER RETURN

DOMESTIC HOT WATER

RECIRCULATING (DHWR)

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

ST/OST

PLUMBING PIPING

ACID VENT

TW

AV

AW

W

DS

DSCW

TWR

DSHW

SANITARY VENT

BURIED EXTERIOR WATER

TEPID WATER RECIRCULATING

TEPID WATER

DISTILLED WATER

SOFTENED HOT WATER

SOFTENED COLD WATER

ACID WASTE

STORM DRAIN

SANITARY DRAIN (BELOW FLOOR)

SANITARY DRAIN (ABOVE FLOOR)

OXYGEN

VACUUM

OX

VAC

RO

A

REVERSE OSMOSIS WATER

COMPRESSED AIR

DEIONIZED WATERDI

AIR FLOW STATIONAFS

HPWR

HPWS

HEAT PUMP WATER RETURN

HEAT PUMP WATER SUPPLY

F

S

FS

NEW TO EXISTING CONNECTION

G NATURAL GAS

FOF

FOG

LPG

FOV

FOR

FOS

FUEL OIL RETURN

FUEL OIL SUPPLY

FUEL OIL GAGE

FUEL OIL FILL

FUEL OIL VENT

LIQUEFIED PETROLEUM GAS

CD CONDENSATE DRAIN

EXHAUST DUCT DOWN

EXHAUST DUCT UP

DOUBLE - GRADE CLEANOUTDGCO

ST/OST STORM DRAIN (BELOW FLOOR)

WASTE AND ANESTHETIC

GAS DISPOSAL

NITROGEN

WAGD

N

MEDICAL AIRMA

PIPE GUIDE

HOSE BIBB

THERMOMETER

PIPE ANCHOR

HB

STEAM TRAP

RHY

WH

ROOF HYDRANT

WALL HYDRANT

PRESSURE GAUGE

EXISTINGDEMO

EXISTINGNEW

18 Ø

18x10

18/10

ROUND DUCT

FLAT OVAL DUCT-1ST FIG IS SIDE

SHOWN

RECT DUCT-1ST FIG IS SIDE SHOWN

ACOUSTICAL DUCT LINER

HVAC DUCTWORK AND SPECIALTIES

HIGH EFFICIENCY TAKEOFF

HIGH EFFICIENCY TAKOFF

WITH VOLUME DAMPER

NITROGEN OUTLET

MEDICAL AIR OUTLET

WASTE AND ANESTHETIC GAS

DISPOSAL OUTLET

N

MA

V

FLEXIBLE DUCTWORK CONNECTION

ABBREVIATIONS

NORTH

ARROW

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW

COLUMN

X

X

X

XXXX

SIM/OPP

X

XXXX

XX-1

X

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

ROOM / SPACE

NUMBER

LETTER/NUMBER

INDICATES NEW

COLUMN LINE

LETTER/NUMBER

INDICATES EXISTING

COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DRAWING/DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE DRAWING

XXX-1

PLUMBING

FIXTURES PLUMBING FIXTURE

DESIGNATION

X"PIPE

SIZE

PIPE SIZE (DIAMETER)

X"xX"

DUCT

SIZE

WIDTH x HEIGHT

X"/X" WIDTH / HEIGHT

X" DIAMETER

REF. DEMO NOTES ( ) XX REF. NOTES ( )

SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.

GENERAL DEMOLITION NOTES GENERAL NOTES

MECHANICAL SHEET LIST

NORTH PLAN

NORTH

TRUE

NORTH

S TEMPERATURE SENSOR

CO CARBON MONOXIDE SENSOR

CO2 CARBON DIOXIDE SENSOR

NO2 NITROGEN DIOXIDE SENSOR

SENSOR WITH GUARD'X'

SW SWITCH

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MBH 1000 BTUH

MCA MINIMUM CIRCUIT AMPS

MD MOTORIZED DAMPER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT

PROTECTION

MPR MEDIUM PRESSURE

RETURN

MPS MEDIUM PRESSURE STEAM

MS MOP SINK

N NITROGEN

NC NORMALLY CLOSED

NO NORMALLY OPEN

NPCW NONPOTABLE COLD WATER

NPHW NONPOTABLE HOT WATER

NPHWR NONPOTABLE HOT WATER

RECIRCULATING

OA OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

OX OXYGEN

P PUMP

PHC PREHEAT COIL

PIV POST INDICATING VALVE

PRV PRESSURE REGULATING VALVE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH,

GAUGE

PTAC PACKAGED TERMINAL AIR

CONDITIONER

RA RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF AREA DRAINS

RL REFRIGERANT DISCHARGE LINE

RF RETURN FAN

RH RELIEF HOOD

RHC REHEAT COIL

RL REFRIGERANT LIQUID LINE

RLA RELIEF AIR

RLF RELIEF FAN

RO REVERSE OSMOSIS WATER

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION LINE

RTU ROOF TOP UNIT

RV RELIEF VALVE

S SINK

SA SUPPLY AIR

SAN SANITARY SEWER

SD SMOKE DAMPER

SF SUPPLY FAN

SFU SANITARY FIXTURE UNIT

SH SHOWER

SP STATIC PRESSURE

SSS SURGICAL SCRUB SINK

ST STORM WATER

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVE

TONS TONS OF REFRIGERATION

TSP TOTAL STATIC PRESSURE

T THERMOSTAT

UH UNIT HEATER

UR URINAL

V VENT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

WB WET BULB

WC WATER CLOSETS

WCO WALL CLEANOUT

WF WASH FOUNTAINS

WFU WATER FIXTURE UNITS

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WS WATER SOFTENER

WSHP WATER SOURCE HEAT PUMP

WWHP WATER TO WATER HEAT PUMP

YH YARD HYDRANT

A COMPRESSED AIR

AC AIR COMPRESSOR

AD AIR DOOR

AFCV AUTO FLOW CONTROL VALVE

AHU AIR HANDLING UNIT

AMP AMPERE

APD AIR PRESSURE DROP

AS AIR SEPARATOR

AV ACID VENT

AW ACID WASTE

B BOILER

BC BLOWER COIL

BD BIDET

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BHP BRAKE HORSEPOWER

BLKG BLOCKING

BLV BALANCING VALVE

BT BATHTUB

BV BALL VALVE

BW BEDPAN WASHER

CH CHILLER

CC COOLING COIL

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CUH CABINET HEATER

CI CAST IRON

CMU COMBINATION UNITS

CR CONDENSER WATER RETURN

CRAC COMPUTER ROOM AIR

CONDITIONER

CS CONDENSER WATER SUPPLY

CSS CLINICAL SERVICE SINKS

CT COOLING TOWER

CU CONDENSING UNIT - SPLIT SYSTEM

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

DB DRY-BULB TEMPERATURE

DCW DOMESTIC COLD WATER

DEG DEGREE

DF DRINKING FOUNTAIN

DGCO DOUBLE GRADE CLEANOUT

DH EMERGENCY DRENCH HOSES

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER

RECIRCULATING

DI DEIONIZED WATER

DOAS DEDICATED OUTDOOR AIR SYSTEM

DS DISTILLED WATER

DSA DUCT SOUND ATTENUATORS

DSCW DOMESTIC SOFT COLD WATER

DSHW DOMESTIC SOFT HOT WATER

DSHWR DOMESTIC SOFT HOT WATER

RECIRCULATING

DST DOMESTIC STORAGE TANK

DTW DOMESTIC TEPID WATER

DTWR DOMESTIC TEPID WATER

RECIRCULATING

EA. EACH

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDH ELECTRIC DUCT HEATER

EEW EMERGENCY EYE WASH

EEWS EMERGENCY EYE

WASH/SHOWER

EF EXHAUST FAN

EFF EFFICIENCY

EFW EMERGENCY FACE WASH

EH EXHAUST HOOD

ERV ENERGY RECOVERY

VENTILATOR

ES EMERGENCY SHOWER

ESP EXTERNAL STATIC PRESSURE

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER

TEMPERATURE

ET EXPANSION TANK

F FIRE SUPPRESSION PIPING

F-_ FURNACE

FCO FLOOR CLEANOUT

FC FLUID COOLER

FCU FAN COIL UNIT

FD FIRE DAMPER

FLA FULL LOAD AMPS

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOOR SINK

FSD FIRE/SMOKE DAMPER

FT FINNED TUBE

G GAS

GCWR GLYCOL CHILLED

WATER RETURN

GCWS GLYCOL CHILLED

WATER SUPPLY

GD GARBAGE DISPOSAL

GDH GAS DUCT HEATER

GHCR GLYCOL HOT/CHILLED

WATER RETURN

GHCS GLYCOL HOT/CHILLED

WATER SUPPLY

GHWR GLYCOL HOT WATER RETURN

GHWS GLYCOL HOT WATER SUPPLY

GI GREASE INTERCEPTOR

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GV GAS VENT

GWH GAS WATER HEATER

HB HOSE BIBB

HC HEATING COIL

HCR HOT/CHILLED WATER RETURN

HCS HOT/CHILLED WATER SUPPLY

ACC AIR COOLED CONDENSER

ACCU AIR COOLED CONDENSING UNIT

ASHP AIR SOURCE HEAT PUMP

ARU AIR ROTATION UNIT

OI OIL INTERCEPTOR

SOI SAND OIL INTERCEPTOR

DSS DUCTLESS SPLIT SYSTEM

SP SUMP PUMP

OST OVERFLOW STORM WATER

WMB WASHING MACHINE BOX

OB OUTLET BOX

RH ROOF HYDRANT

H HUMIDIFIER

DHWP DOMESTIC HOT WATER

RECIRCULATING PUMP

DWET DOMESTIC WATER EXPANSION

TANK

HP HORSEPOWER

HPR HIGH PRESSURE RETURN

HPS HIGH PRESURE STEAM

HRC HEAT RECOVERY COIL

HWR HOT WATER RETURN (HEATING)

HWS HOT WATER SUPPLY (HEATING)

HX HEAT EXCHANGER

HY HYDRANTS

HP-_ HEAT PUMP

HVLS HIGH VOLUME LOW SPEED

IH INTAKE HOOD

IRH INFRARED RADIANT HEATER

KH KITCHEN HOOD

KW KILOWATT

KWH KILOWATT HOURS

L LAVATORY

LAT LEAVING AIR TEMPERATURE

LPR LOW PRESSURE RETURN

LPG LIQUIFIED PETROLEUM GAS

LPS LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LS LAUNDRY SINK

LV LOUVER

LWT LEAVING WATER TEMPERATURE

PROJECT MECHANICAL REFERENCED DEMOLITION NOTES PROJECT MECHANICAL REFERENCED NOTES

HF WHOLE HOUSE FAN

M 00.2 MECHANICAL INFO SHEET

M 01.2 SHEET SPECIFICATIONS - MECHANICAL

M 02.2 SHEET SPECIFICATIONS - MECHANICAL

MD01.2 DEMOLITION FLOOR PLAN - MECHANICAL

M101.2 FLOOR PLAN - MECHANICAL

M102.2 FLOOR PLAN - MECHANICAL

M401.2 DETAILS - MECHANICAL

M501.2 SCHEDULE - MECHANICAL

DATE INITIAL

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M 01.2

SHEET SPECIFICATIONS -

MECHANICAL

009258015-6-M 01.2 SHEET SPECIFICATIONS - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M 02.2

SHEET SPECIFICATIONS -

MECHANICAL

009258015-6-M 02.2 SHEET SPECIFICATIONS - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

UP UP

RA

SA

SA

RA

SA

SA

RA

RA

S A

S A

S A

R A S A

R A

S A

RA

2 2 2 2

33 3

R S

/R L

R S

/R L

R S

/R L

R S

/R L

44444

4 4 4

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

MD01.2

DEMOLITION FLOOR PLAN -

MECHANICAL

009258015-6-MD01.2 DEMOLITION FLOOR PLAN - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

REF. DEMO NOTES ( ):X

1 REMOVE EXISTING EXHAUST FAN.

2 REMOVE EXISTING CONDENSING UNIT AND LINE SETS. PREPARE FOR NEW

CONSTRUCTION.

3 REMOVE EXISTING FURNACE.

4 AIR TERMINAL TO REMAIN. ABANDON IN PLACE.

5 REMOVE TOP WINDOW PANES AND PREPARE FOR NEW CONSTRUCTION. SEE

ARCHITECTURAL FOR DETAILS. COORDINATE REMOVAL WITH NEW OUTSIDE AIR

CONSTRUCTION SCHEDULE TO LIMIT EXTERIOR EXPOSURE TO INTERIOR.

6 REMOVE TOP WINDOW AND PREPARE FOR NEW OUTSIDE AIR CONSTRUCTION. SEE

ARCHITECTURAL FOR DETAILS. COORDINATE REMOVAL WITH NEW CONSTRUCTION

SCHEDULE TO LIMIT EXTERIOR EXPOSURE TO INTERIOR.

7 REMOVE EXISTING RETURN AIR DUCT UP TO CEILING. PREPARE FOR NEW OUTSIDE AIR

CONNECTION.

8 CAP AND ABANDON RETURN AIR DUCT.

9 ABANDON SUPPLY AIR DUCT SERVING GRAND HALL ABOVE.

SCALE: 1/8" = 1'-0"

FIRST FLOOR DEMOLITION PLAN - MECHANICAL

SCALE: 1/8" = 1'-0"

SECOND FLOOR DEMOLITION PLAN - MECHANICAL

NORTH

DATE INITIAL

0 6 12 18 '''' 0 6 12 18 ''''

T

H S

T

RA

S A

EF-1

EF-1

AHU-1

HP-1 HP-4 HP-3 HP-2

AHU-2

DH-1

R S

/R L

RS/RL

8 Ø S-(E)

8 Ø S-(E)

8 Ø S-(E)

8 Ø S-(E)

8 Ø S-(E) 150

8 Ø S-(E)

12 Ø

8 Ø

8 Ø x1

8 Ø S-(E)

8 Ø S-(E)

14x12

14x12 RA 14x12 SA

14x12 RA

1 1/2" CD

10x8 S-3

8 Ø S-(E)

8 Ø S-(E)

16x16 R-1

12x12 R-(E)

12x12 R-(E)

8x8

EXISTING TO REMAIN

(TYP.)

12x12 R-(E)

12 Ø

14x12 SA

16x12 RA

14x12

RS/RL UP

CD UP

3/4" CD

R S

/R L

6 Ø EA

8 Ø8 Ø

8x20 OA

12 Ø S-1

16x16 R-1

AHU-2

16x8 RA

16x8 RA

16x8 RA

16x16 R-1

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M101.2

FLOOR PLAN - MECHANICAL

009258015-6-M101.2 FLOOR PLAN - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

REF. NOTES ( ):X

1 IF VOLUME 1 (PMIS 307909) IS SELECTED, OMIT EXHAUST FAN AND DUCTING.

2 EXTEND CONDENSATE TO EXISTING FLOOR DRAIN. TERMINATE WITH AHJ APPROVED AIR

GAP.

3 EXTEND 6" DIAMETER OUTSIDE AIR DUCT FROM OUTSIDE AIR PLENUM BOX. PROVIDE

MOTORIZED DAMPER IN DUCT AND INTERLOCK AHU-2. PROVIDE BALANCING DAMPER AND

BALANCE TO 100 CFM.

4 REPLACE TOP OF EXISTING WINDOW PANE WITH APPROXIMATELY 42" X28" LV-1. FIELD

VERIFY DIMENSIONS. PROVIDE 10" DEEP INSULATED PLENUM BEHIND LOUVER. BOTTOM

WINDOW PANE TO REMAIN. COORDINATE WITH ARCHITECTURAL.

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - MECHANICAL NORTH

DATE INITIAL

0 3 6 9 ''''

T

T H

H

S

S

SWSW

M

M

10 Ø S-1

14x14 R-1

14x14 R-1

(TYP.10)

30x24 R-(E)

30x24 R-(E)

3x48 S-2

HUMIDITY REMOTE

SENSOR

5'-0" A.F.F.

HUMIDITY REMOTE

SENSOR

5'-0" A.F.F.

AHU-4

AHU-3

CD UP/DN

RS/RL UP/DN

(TYP. 2)

12x6 RLA

212x12 R-1

12x12 R-1

12"X12" UP12"X12" UP

12x6 RLA

3x48 S-2

(TYP. 2)

INTERLOCK

SWITCHES WITH SF-1.

5'-0" A.F.F.HUMIDIFIER INTAKE

HUMIDIFIER INTAKE

3x48 E-1 3x48 E-1 3x48 E-1

S A

S A

RS/RL

RS/RL

1 1/2" CD

AHU-3

AHU-4

VD IN DROP (TYP.)

VD IN DROP (TYP.)

FILTER BOX

F

IL

T E

R B

O X

DH-1

RA

8" Ø DN

(TYP.)

12x12 10x10 8 Ø

12 Ø

14x14

14x14 RA

12 Ø

14x14

1 1/4" CD

14x14

14x14 RA14x14

12 Ø 12 Ø

14x12 12x12 8 Ø

8 Ø

8 Ø

12x12 RLA

12X12 OA DN, ROUTE IN

PORCH ATTIC SPACE TO

INTAKE GRILLS.

CD DN

RS/RL DN

RA DN

RA DN

1" CD

1" CD 1" CD

1 1/4" CD

8x

O A

20"X8"

OUTSIDE AIR

FROM BELOW

DH-1

12 Ø SA

SF-1

SF-1

12x12 RLA

12X12 OA OPEN ON

TOP. PROVIDE

INSECT SCREEN.

12X12 OA DN, ROUTE IN

PORCH ATTIC SPACE TO

INTAKE GRILLS.

12X12 OA OPEN ON

TOP. PROVIDE

INSECT SCREEN.

2X6 JOIST - 18" O.C.

NOTE: COORDINATE WITH

TRUSSES WITH ALL DUCTING

AND EQUIPMENT BEING

INSTALL.

SECOND FLOORBALCONY

FIRST FLOOR

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M102.2

FLOOR PLAN - MECHANICAL

009258015-6-M102.2 FLOOR PLAN - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

REF. NOTES ( ):X

1 PROVIDE 12" DEEP DUCT PLENUM BEHIND TO PREVENT INSULATION AND DEBRIS FROM

BLOCKING THE BACKSIDE OF THE VENT.

2 EXTEND EXISTING RETURN DUCT UP INTO ATTIC FOR OUTSIDE AIR CONNECTION.

3 8" DIAMETER OUTSIDE AIR DUCT WITH MOTORIZED DAMPER INTERLOCKED WITH AHU

FAN. PROVIDE BALANCING DAMPER, BALANCE TO 185 CFM.

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - MECHANICAL

SCALE: 1/4" = 1'-0"

ATTIC PLAN - MECHANICAL

NORTH

DATE INITIAL

0 3 6 9 ''''0 6 12 18 ''''

NOT TO SCALE

BUILDING CROSS SECTION - MECHANICAL

DIRT LEG

TO EQUIPMENT

SHUT-OFF VALVE

REMOVABLE

CAP

UNION

SUPPLY PIPING

PRESSURE REGULATOR (IF REQUIRED)

ECCENTRIC TRANSITION

B (MAX.)=30°

(EXCEPT 45° IS PERMITTED AT

ROUND TO FLAT OVAL)

(ANGLED)

Offset Type 1

C (MAX.)=45° DIVERGING, 60° CONVERGING

CONCENTRIC TRANSITION

W

W

L

A (MAX.)=15°

A

W

L

W

W

B

W

W

L

C

SHEET METAL 90° ELBOW

DIFFUSER NECK

TRANSITION

(AS REQUIRED)

CEILING

SUPPLY DUCT-SEE

PLANS FOR SIZES

SUPPLY DIFFUSER

DUCT INSULATION

FLEX DUCT

INSULATED BACKPAN

ELEVATION PLAN

ELEVATION PLAN

DUCT

DUCT SEAM

FLOOR CONSTRUCTION

ANGLE IRON RIVETED

TO DUCT, SEE SIZING

CHART

DUCT

FLOOR CONSTRUCTION

DUCT

DUCT AND

SEAM

LOCATE A FASTENER WITHIN 2" OF

THE DUCT EDGES. LOCATE OTHERS

AT EVENLY SPACED INTERVALS PER

SMACNA.

DUCT SIZE ANGLE

36" x 18" 1-1/2" x 1-1/2" x 1/8" 48" x 24" 1-1/2" x 1-1/2" x 1/8" 60" x 30" 1-1/2" x 1-1/2" x 3/16" 60" x 30" 1-1/2" x 1-1/2" x 1/4" or 2" x 2" x 1/8"

DUCT DIA. BAND SIZE BOLT DIA.

UP TO 12" 1" x 16 GAUGE 1/4" 13" TO 24" 1-1/2" x 16 GAUGE 1/4" 25" TO 36" 2" x 16 GAUGE 3/8" 37" TO 60" 2" x 10 GAUGE 3/8"

SPLIT BAND

SUPPORT

FASTENER, MIN. OF 2 IN EACH

HALF OF BAND OR SPACE THEM

AT 8"

DUCT JOINT

CONNECTION

C-CHANEL

SPLIT BAND

SUPPORT

C-CHANEL

NOTE: FIRE CAULK AS REQUIRED.

SL

AB

A T

BO

TH

E

ND

S (T

YP

AN

G

LE

S

TO

H

AV

E

3" B

EA

R

IN

G

O N

SL

AB

A T

BO

TH

E

ND

S.

(T

YP

AN

G

LE

TO

H

AV

E 3"

B

EA

R

IN

G O

N

DAMPER

STANDOFF

DAMPER

QUADRANT LOCK

NOTE:

ALL TAPS TO AIR TERMINALS REQUIRING BALANCING AT DUCT SHALL

BE MADE USING A HIGH EFFICIENCY TAKEOFF.

TYPE RE 1

RADIUS ELBOW

CENTERLINE R = (3W)/2 UNLESS OTHERWISE

SPECIFIED Θ IS NOT RESTRICTED TO 90°.

W

H

R

Θ

TYPE RE 2

SQUARE THROAT ELBOW

WITH VANES

TYPE RE 3

RADIUS ELBOW WITH VANES

NOT PERMITTED

DO NOT USE

FLOORS

E

E N

O T

E S

B E

L O

W

T Y

P

IC

A L

L Y

A

.F .F

TYPICAL HVAC CONTROL DEVICE INSTALLATION

THERMOSTAT

OR OTHER HVAC

CONTROL DEVICE

LIGHT

SWITCH

NOTES:

1. WHEN THERMOSTAT IS LOCATED ADJACENT TO LIGHT SWITCH OR OTHER

WALL MOUNTED ELECTRICAL OR CONTROL DEVICE, DEVICES TO BE

INSTALLED AT THE SAME ELEVATION.

2. ALL USER INPUT BUTTONS OR SWITCHES ON CONTORL DEVICE TO BE

LOCATED BELOW 48" A.F.F. TO MEET ADA REQUIREMENTS.

3. WHEN INSTALLED NEAR DOOR, LIGHT SWITCH SHALL BE DEVICE CLOSEST TO

DOOR FRAME.

4. IF DEVICE IS LOCATED ABOVE COUNTER, INSTALL AT 40" A.F.F.

CL

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M401.2

DETAILS - MECHANICAL

009258015-6-M401.2 DETAILS - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

SCALE: NOT TO SCALE

TYPICAL GAS PIPING DETAIL

SCALE: NOT TO SCALE

OFFSETS AND TRANSITIONS DETAIL

SCALE: NOT TO SCALE

SUPPLY DIFFUSER/ DUCT CONNECTION DETAIL

SCALE: NOT TO SCALE

VERTICAL DUCT SUPPORT DETAILS

SCALE: NOT TO SCALE

HIGH EFFICIENCY TAKEOFF DETAIL

SCALE: NOT TO SCALE

DUCT ELBOW DETAIL

SCALE: 12" = 1'-0"

THERMOSTAT DETAIL

TOTAL

HEIGHT

OF TRAP

TO FLOOR DRAIN

TOTAL HEIGHT OF TRAP:

X + H + (1 1/2 x PIPE DIAMETER)

H = AT LEAST 1 INCH PLUS

CASING STATIC PRESSURE

X = 1/2 "H"

COIL CONDENSATE

DRAIN PAN

SLOPE DOWN

X

H

CLEAN OUT

HOUSEKEEPING PAD,

HEIGHT IS BASED ON TRAP

HEIGHT

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \m b e c k m a n n

\D o c u m e n ts

\0

-M e c h

H S

R m b e c k m a n n s c h e m m e r.

c o m .r v t

MPH

MLB

MPH

4/9/2026

09258015

M501.2

SCHEDULE - MECHANICAL

009258015-6-M501.2 SCHEDULE - MECHANICAL

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

SCALE: NOT TO SCALE

CONDENSATE DRAIN TRAP NEGATIVE STATIC PRESSURE

2. PROVIDE WITH NEMA 3R RATED SCCR DISCONNECT SWITCH.

NOTES: 1. UNIT TO BE PROVIDED WITH HAIL GUARD AND LOW AMBIENT OPERATION .

HP-4 OUTDOOR AHU-4 R-32 123.5 11 95 12 2 ROTARY 2 125 27x56x13 211.6 62 208 1 36.2 40 SAMSUNG AC048DXSCCG/AA (CXG48SCD) 1,2

HP-3 OUTDOOR AHU-3 R-32 123.5 11 95 12 2 ROTARY 2 125 27x56x13 211.6 62 208 1 36.2 40 SAMSUNG AC048DXSCCG/AA (CXG48SCD) 1,2

HP-2 OUTDOOR AHU-2 R-32 123.5 10 95 13 2 ROTARY 2 125 37x56x13 211.6 60 208 1 35 40 SAMSUNG AC030DXSCCG/AA (CXG30SCD) 1,2

HP-1 OUTDOOR AHU-1 R-32 123.5 10 95 13 2 ROTARY 2 125 37x56x13 211.6 60 208 1 35 40 SAMSUNG AC030DXSCCG/AA (CXG30SCD) 1,2

QTY TYPE QTY WATTS

DIMENSIONS

(HxWxL)

WEIGHT

(LBS)

SOUND

(dBA) VOLTAGE PHASE MCA MOCPMARK LOCATION SERVES

REFRIGERANT

TYPE

REFRIGERANT

CHARGE (OZ)

MIN CAP

MBH

AMBIENT

TEMP (°F)

EFFICIENCY

(EER)

COMPRESSOR DATA CONDENSER FAN DATA PHYSICAL DATA ELECTRICAL DATA

BASIS OF DESIGN REMARKS

AIR COOLED CONDENSING UNIT SCHEDULE

2. PROVIDE WITH DEH3000 CONTROLLER AND REMOTE SENSOR. PROVIDE WITH MINIBLUE CONDENSATE PUMP. INTERLOCK WITH ASSOCIATED HEAT PUMP TO LOCK OUT HUMIDIFIER WHEN HEAT PUMP COMPRESSOR IS RUNNING.

NOTES: 1. AHU'S FAN IS TO RUN WHILE UNIT IS ON.

DH-1 AHU 115 500 R454B 18 18 75 50 26.8 23.6 20.9 130 3/4 0.75 6.9 120 1 60 15 15 QWEST 115 1,2

WIDTH HT TEMP (°F) % RH LENGTH (IN) WIDTH (IN) HEIGHT (IN) WEIGHT (LBS)

DRAIN

CONNECTION (IN) KW AMP VOLTS PH HZ MCA MOPMARK SERVES

HUMIDIFICATION

CAPACITY

(PINT/DAY) CFM REF TYPE

DUCT CONDITIONS PHYSICAL DATA ELECTRICAL DATA

BASIS OF DESIGN REMARKS

ELECTRIC DEHUMIDIFIER SCHEDULE

NOTES: 1. PROVIDE WITH BIRD SCREEN, BACKDRAFT DAMPER AND SPEED CONTROLLER.

SF-1 ATTIC INLINE 470 0.2 DIRECT 1550 5.4 SONES 1/10 --- 115 1 60 60 WALL SWITCH GREENHECK SQ-90-VG1X-QD 1

TYPE CFM

EXT SP

(IN WG) DRIVE RPM SOUND LEVEL HP WATTS VOLTS PH HZMARK LOCATION

FAN DATA ELECTRICAL DATA UNIT

WEIGHT

(LBS) FAN CONTROL BASIS OF DESIGN REMARKS

FAN SCHEDULE

NOTES: 1. PROVIDE UNIT WITH REFRIGERANT DETECTION SYSTEM.

AHU-4 GRAND HALL 1450 185 0.58 98.4 75.4 48 54 34 15 208 1 590 208 1 60 18 SAMSUNG AC048DNZDCG/AA (CNG48ZDD) 1

AHU-3 GRAND HALL 1450 185 0.58 98.4 75.4 48 54 34 15 208 1 590 208 1 60 18 SAMSUNG AC048DNZDCG/AA (CNG48ZDD) 1

AHU-2 DRESSING ROOMS 1000 100 0.58 98.4 75.4 30 34 31 10 208 1 410 208 1 60 19 SAMSUNG AC030DNZDCG/AA (CNG30ZDD) 1

AHU-1 RESTROOM GROUP 1000 0 0.58 98.4 75.4 30 34 31 10 208 1 410 208 1 60 19 SAMSUNG AC030DNZDCG/AA (CNG30ZDD) 1

EDBT (°F)

EWBT

(°F)

TOTAL CAP

(MBH)

TOTAL CAPACITY

(MBH)

TEMP RISE

(°F) KW VOLT PH W VOLTS PH HZ SEER2MARK SERVES

TOTAL

CFM OUTSIDE AIR CFM

ESP (IN

WG)

COOLING DATA HEATING DATA SUPPLEMENTAL ELEC. HEAT DATA ELECTRICAL DATA

BASIS OF DESIGN REMARKS

HEAT PUMP BLOWER COIL UNIT SCHEDULE

2. PROVIDE WITH STANDARD WHITE GRILL AND CEILING RADIATION DAMPER.

NOTES: 1 . PROVIDE WITH GREENHECK WC-6, BIRD SCREEN, BACKDRAFT DAMPER AND SPEED CONTROLLER.

EF-1 RESTROOMS CEILING 225 0.38 DIRECT 900 4.5 SONES 57 110 1 60 24 OCC. SENSOR GREENHECK SP-A250 1,2

TYPE CFM

EXT SP

(IN WG) DRIVE RPM

SOUND

LEVEL HP VOLTS PH HZMARK LOCATION

FAN DATA ELECTRICAL DATA UNIT

WEIGHT

(LBS) FAN CONTROL

MANUFACTURER AND

MODEL NUMBER REMARKS

CEILING EXHAUST FAN SCHEDULE

DATE INITIAL

2. SIZE TO APPROXIMATLY MATCH TOP WINDOW PANE. FIELD VERIFY FOR EXACT MEASUREMENTS. PROVIDE INSECT SCREEN. PROVIDE CUSTOM COLOR TO MATCH

BUILDING EXTERIOR. COLOR TO BE SELECTED BY ARCHITECT.

NOTES: 1. PROVIDE WITH BIRD SCREEN AND COLOR TO BE SELECTED BY ARCHITECT.

LV-1 OUTSIDE AIR ALUMINUM 460 --- 500 42 28 6 SEE ARCH RUSKIN ELF375DX 1

W H DMARK SERVES MATERIAL CFM

MAX SP

(IN WG)

FREE AREA FACE

VELOCITY

(FPM)

SIZE (INCHES)

FINISH BASIS OF DESIGN REMARKS

LOUVER SCHEDULE

NOTES: 1. PROVIDE WITH STRAIGHTENING GRID IN NECK.

R-1 SURFACE 24 X 24 SEE PLANS --- --- STEEL / WHITE 0.1 25 KRUGER EGC10 1

E-1 SURFACE 4x48 SEE PLANS --- --- STEEL / WHITE 0.1 25 BRAND X METAL SV75-V-400/50 ---

S-2 SURFACE 4x48 SEE PLANS --- --- STEEL / WHITE 0.1 25 BRAND X METAL SV75-V-400/50 ---

S-1 LAY-IN 24 X 24 SEE PLANS --- DAMPER IN DUCT STEEL / WHITE 0.1 25 KRUEGER PLQ 1

MARK

MOUNTING

TYPE FACE SIZE (IN.) NECK SIZE (IN.)

BLADE

ANGLE VOLUME CONTROL MATERIAL / FINISH

MAX PD (IN

WG)

MAX NC AT

PD SHOWN BASIS OF DESIGN REMARKS

DIFFUSER, REGISTER AND GRILLE SCHEDULE

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E 00.2

ELECTRICAL INFO SHEET

009258015-7-E 00.2 ELECTRICAL INFO SHEET

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

E 00.2 ELECTRICAL INFO SHEET

E 01.2 ELECTRICAL INFO SHEET

E 02.2 ELECTRICAL SPECIFICATIONS

E 03.2 ELECTRICAL SPECIFICATIONS

E 04.2 ELECTRICAL SPECIFICATIONS

ED01.2 FLOOR PLAN - DEMOLITION

E201.2 FLOOR PLAN - POWER

E202.2 FLOOR PLAN - POWER

E501.2 POWER RISER DIAGRAMS

E601.2 ELECTRICAL SCHEDULES

S

NORTH

ARROW

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW COLUMN

X

X

X

XX-XX

SIM

X

XX-XX

DX

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE NOTE

REFERENCE

DEMOLITION NOTE

ROOM

NUMBER

LETTER INDICATES

NEW COLUMN LINE

LETTER INDICATES EXISTING

COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF

VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE DRAWING

ABBREVIATIONS

ROOM NAME

150 SF

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

ROOM AREA DESIGNATION

SYMBOL LEGEND

P C

J

J

O S

MS

IC

S

S

M

N

T V

VC

N E

N S

N

N D

N 2

G

K1

V

A

R

M

M

T

WALL MOUNTED STRIP LUMINAIRE

SYMBOL NOTES:

PHOTOCELL

VOICE AND DATA

JUNCTION BOX - CEILING MOUNT

JUNCTION BOX - WALL MOUNT

VOICE OUTLET

DATA OUTLET

OCCUPANCY SENSOR

MOTION SENSOR

CEILING FAN

POLE MOUNTED SITE LUMINAIRE

FLOOD LIGHT

NURSE CALL

SPEAKER

BEDSIDE STATION

INTERCOM SPEAKER STATION

VOLUME CONTROL STATION

MICROPHONE JACK

TELEVISION OUTLET

CCTV CAMERA

SOUND, TELEVISION, AND SECURITY

FUSE

EMERGENCY PULL STATION

DISCONNECT SWITCH

STAFF STATION

DUTY STATION

DOME LIGHT

MASTER STATION

EMERGENCY GENERATOR

POWER DISTRIBUTION ONE LINE

CONDUIT UP

CONDUIT DOWN

INDICATES BUSHED CONDUIT

VOICE/DATA OUTLET

DOUBLE BED BEDSIDE STATION

DRAW OUT VACUUM CIRCUIT BREAKER

LIGHTNING SURGE ARRESTOR

THERMAL OVERLOAD RELAY

PLUG-IN OR DRAWOUT CONNECTOR

CIRCUIT BREAKER

FUSED DISCONNECT SWITCH

VOLTMETER

AMMETER

X:Y CURRENT TRANSFORMER - (RATIO)

KIRK KEY INTERLOCK

"C" INDICATES CEILING MOUNTED

"F" INDICATES FLOOR MOUNTED

"S" INDICATES SURFACE MOUNTED

"G" INDICATES GROUND FAULT INTERRUPTING

"IG" INDICATES ISOLATED GROUND

"AC" INDICATES MOUNTING 6" ABOVE

COUNTERTOP OR BACKSPLASH

"WP" INDICATES WEATHERPROOF

"XP" INDICATES EXPLOSION PROOF

"U" INDICATES USB CHARGER

"R" INDICATES EXISTING DEVICE REMOVED

AND RELOCATED

LOWER CASE LETTER BY SWITCHES AND

FIXTURES

INDICATE ASSOCIATED UNIT FOR SWITCHING

LIGHTING

LUMINAIRE

WALL MOUNTED LUMINAIRE

RECESSED LUMINAIRE

WALL MOUNTED LUMINAIRE

SURFACE MOUNTED LUMINAIRE

TRACK LIGHTING

DIMMER SWITCH

TIMER SWITCH

WIRING DEVICES - SWITCHES

SINGLE POLE SWITCH

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT

THERMAL ELEMENT SWITCH

FOUR-WAY SWITCH

TWO POLE SWITCH

THREE-WAY SWITCH

STRIP / INDUSTRIAL LUMINAIRE

LUMINAIRE - NIGHT LIGHTING

LUMINAIRE - EMERGENCY SYSTEM

EMERGENCY BATTERY PACK LUMINAIRE

REMOTE EMERGENCY HEAD

WALL WASH LUMINAIRE

PENDANT MOUNTED LUMINAIRE

POWER POLE

METER SOCKET

POWER EQUIPMENT

WIRING DEVICES - RECEPTACLES

COMBINATION STARTER SAFETY

SWITCH

RELAY - CONTROL AS NOTED

PUSHBUTTON STATION

MOTOR CONNECTION

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

EMERGENCY RECEPTACLE

SPECIAL PURPOSE RECEPTACLE, NEMA

CONFIGURATION NOTED

PLUG-IN STRIP - LENGTH AND

QUANTITY OF OUTLETS AS SHOWN

SAFETY SWITCH

DROP CORD RECEPTACLE ASSEMBLY

FUSIBLE SWITCH (FUSETRON)

PANELS AND CABINETS

DISTRIBUTION PANEL

SWITCHBOARD, SWITCHGEAR, MCC

EQUIPMENT OR TERMINAL CABINET

DRY TYPE TRANSFORMER

BRANCH CIRCUIT PANEL

CONDUIT AND BOXES

HORN (PA, PUBLIC

ADDRESS)

TRANSFORMER

EXIT LIGHT - WALL MOUNT WITH

DIRECTIONAL ARROWS AS

INDICATED, FILLED-IN QUARTERS

INDICATE ILLUMINATION SIDES

EXIT LIGHT - CEILING OR PENDANT

MOUNT WITH DIRECTIONAL ARROWS

AS INDICATED, FILLED-IN QUARTERS

INDICATE ILLUMINATION SIDES

EMERGENCY EXIT LIGHT COMBO

LOW VOLTAGE MOMENTARY

CONTACT SWITCH

N P PILLOW SPEAKER

FB FLOOR BOX

FP FLOOR POKE-THROUGH DEVICE

N M

WIRELESS ACCESS POINT

S

S2

S3

S4

SD

SK

SP

STE

ST

SFT

X

CONTROLLED RECEPTACLE

WB WALL AV BOX

F

F

F

F

F S

D

P S

T S

DH

STROBE

HORN

MANUAL PULL STATION

HORN STROBE

HEAT DETECTOR

SMOKE DETECTOR

REMOTE INDICATOR LIGHT

SPRINKLER TAMPER SWITCH

DUCT SMOKE DETECTOR

FLOW SWITCH

POST INDICATING VALVE SWITCH

MAGNETIC DOOR HOLDER

FIRE ALARM SYSTEM

H

S

S

F SPEAKER STROBES

F SPEAKERS

ACSR ALUMINUM CONDUCTOR

STEEL REINFORCED

AFF ABOVE FINISH FLOOR

AIC AMPS INTERRUPTING

CAPACITY (SYM RMS)

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

APPROX APPROXIMATE

AUTO AUTOMATIC

AVG AVERAGE

L ANGLE

BKR BREAKER

C OR CL CENTER LINE

C OR CND CONDUIT (ELECTRICAL

SHEETS)

CKT CIRCUIT

CLG CEILING

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CPT CONTROL POWER

TRANSFORMER

DC DIRECT CURRENT

DEG DEGREE

DEMO DEMOLITION

DIA DIAMETER

DIM DIMENSION

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DWG DRAWING

E EAST

EA EACH

EL OR

ELEV

ELEVATION - GRADE OR

BUILDING

ELEC ELECTRIC OR

ELECTRICAL

ELEV ELEVATOR

EMD ESTIMATED MAXIMUM

DEMAND

ENCL ENCLOSURE

EQUIP EQUIPMENT

EST ESTIMATE

EWC ELECTRIC WATER

COOLER

EXIST, EXTG EXISTING

EXP EXPOSED

EXT EXTERIOR

FA FIRE ALARM

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLUOR FLUORESCENT

AWG GAUGE

HP HORSE POWER

HR HOUR

HTG HEATING

HTR HEATER

HZ HERTZ

ID INSIDE DIAMETER

IES ILLUMINATING

ENGINEERING SOCIETY

IN INCH

INSUL INSULATION

INT INTERIOR

KCMIL KCM KILO CIRCULAR MIL

KV KILOVOLTS

KVA KILOVOLT AMPERES

KW KILOWATT

LRA LOCKED ROTOR AMPS

LTG LIGHTING

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

FAAP FIRE ALARM ANNUNCIATOR

PANEL

FACP FIRE ALARM CONTROL PANEL

FAEP FIRE ALARM EXTENDER PANEL

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

CUH CABINET UNIT HEATER

EMI ELECTROMAGNETIC

INTERFERENCE

MCCB MOLDED CASE CIRCUIT

BREAKER

GFI GROUND FAULT CIRCUIT

INTERRUPTER

QTY QUANTITY

REC RECEPTACLE

REFR REFRIGERATOR

REINF REINFORCEMENT

REQD REQUIRED

N NORTH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO NUMBER

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OH OVERHEAD

OPNG OPENING

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PSI POUNDS PER SQUARE IN.

OCPD OVERCURRENT PROTECTIVE

DEVICE

RFI RADIO FREQUENCY

INTERFERENCE

TEL TELEPHONE

TEMP TEMPERATURE

TVSS TRANSIENT VOLTAGE

SURGE SUPPRESSOR

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UPS UNINTERRUPTIBLE

POWER SYSTEM

VFD VARIABLE FREQUENCY

DRIVE

W WEST

W/ WITH

W/O WITHOUT

WHM WATTHOUR METER

WT WEIGHT

XFMR TRANSFORMER

SOUTH

SCHED SCHEDULE

SF SQUARE FOOT (FEET)

SPEC SPECIFICATIONS

SPKR SPEAKER

SQ SQUARE

STD STANDARD

STL STEEL

SW SWITCH

SWBD SWITCH BOARD

SYM SYMMETRICAL

S

SCCR SHORT CIRCUIT CURRENT

RATING

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE, DOUBLE

THROW

VFC VARIABLE FREQUENCY

CONTROLLER

NON-SCHEDULED

EQUIPMENT

XXXX

SCHEDULED

EQUIPMENT EQUIPMENT NUMBER

XX-XX PANEL & CIRCUIT NUMBER

XX

EQUIPMENT SIZE

(WHERE APPLICABLE)

EQUIPMENT

XX-XX PANEL & CIRCUIT NUMBER

EQUIPMENT NAME/NUMBER

NORTH PLAN

NORTH

TRUE

NORTH

ELECTRICAL SHEET LIST

04/09/2026

A. SEE ARCHITECTURAL SHEETS FOR EXACT AREAS AND WALLS

AFFECTED BY THE DEMOLITION AND REMODEL.

B. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR

SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS.

ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE

SHOWN AS HALF-TONE.

C. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE

PROJECT. COORDINATE DEMOLITION WITH THE WORK OF OTHER

TRADES. PROVIDE TEMPORARY POWER AND LIGHTS AS

REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO

PROCEED OR AS REQUIRED TO ALLOW THE OWNER TO OCCUPY

THE SPACE.

D. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING

ARE EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES

WERE OBTAINED FROM EXISTING DRAWING AND FIELD

INVESTIGATION. THE LOCATIONS OF THE EXISTING EQUIPMENT

AND DEVICES ARE SHOWN FOR THE CONVENIENCE OF THE

CONTRACTOR. ACCURACY OF THE INFORMATION SHOWN IS NOT

GUARANTEED. THE CONTRACTOR IS ENCOURAGED TO VERIFY ALL

EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. SITE VISITS

PRIOR TO SUBMISSION OF BIDS NEED TO BE FULLY COORDINATED

WITH THE OWNER.

E. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE

VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE

INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES

IS NOT GUARANTEED.

F. LUMINAIRES AND DEVICES INDICATED TO BE REMOVED, WHICH

ARE LOCATED ON CEILINGS OR WALLS, SHALL HAVE LUMINAIRES,

DEVICE AND ALL ASSOCIATED CIRCUIT WIRING AND CONDUIT

REMOVED BACK TO NEAREST JUNCTION BOX, OR DEVICE NOT

INDICATED TO BE REMOVED. ACTUAL CIRCUITING MUST BE

DETERMINED IN THE FIELD. THE CONTRACTOR SHALL PROVIDE

ALL NECESSARY WIRE, CONDUIT, DEVICES AND CONNECTIONS

NECESSARY TO ENSURE CIRCUIT CONTINUITY OF THE REMAINING

DEVICES.

G. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE

MATERIAL. ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT

SHALL BE REMOVED FROM THE SITE AND PROPERLY DISPOSED

OF BY THE CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR

THE REMOVAL OF ANY PCB BALLAST OR HAZARDOUS LAMPS.

H. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE

LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT

BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE

CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE

CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND

PANEL LOADING WILL ALLOW.

I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE

PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING

PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE

TO THE DEMOLITION WORK DONE BY THE ELECTRICAL

CONTRACTOR, UNDER THE TERMS OF THIS SPECIFICATION.

CLOSE AND SEAL ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS

REQUIRED.

J. FIRE ALARM DEVICES SHALL BE REMOVED, REPLACED AND

RECONNECTED TO FIRE ALARM SYSTEM AS SPECIFIED. DUCT

SMOKE DETECTORS AND FIRE SMOKE DAMPERS SHALL BE

REMOVED ONLY WHEN THE ASSOCIATED MECHANICAL

EQUIPMENT IS BEING REMOVED.

K. EXISTING FIRE ALARM DEVICES, EMERGENCY LIGHTS AND EXIT

SIGNS SHALL BE COMPLETE AND OPERABLE AT ALL TIMES.

PROVIDE TEMPORARY DEVICES IN AREAS BEING WORKED ON TO

ALLOW FOR A WORKABLE SYSTEM DURING CONSTRUCTION.

L. PROVIDE MINIMUM [2] DAYS ADVANCE NOTICE OF OUTAGES.

COORDINATE WITH OWNER FOR ALL ANTICIPATED OUTAGES.

OWNER HAS FINAL APPROVAL ON TIME AND EXTENT OF POWER

OUTAGE.

M. PROTECT EXISTING FURNITURE, CARPET AND OTHER

APPURTENANCES FROM DAMAGE DURING THE COURSE OF

CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO

THE OWNER.

A. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS

INDICATED OTHERWISE.

B. ALL AUXILIARY CABLE ABOVE CEILING SHALL BE PLENUM RATED

WHERE REQUIRED.

C. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE

WHERE INSTALLED IN ACOUSTICAL TILE CEILING.

D. PROVIDE 120 VOLT POWER CIRCUIT(S) FOR AUXILIARY SYSTEMS

AS REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS.

A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR

CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS

NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT

FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC,

SHALL ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR

SIZES AS NEEDED TO LIMIT VOLTAGE DROP TO LEVELS

RECOMMENDED BY NEC. THE CONTRACTOR SHALL ALSO

COORDINATE INSPECTIONS WITH THE AHJ.

B. SEE ARCHITECTURAL SHEETS FOR REFLECTED CEILING PLANS.

C. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN

SHARE AN INSULATED GREEN GROUND WIRE IN MINIMUM 3/4" EMT

CONDUIT.

D. NO BOXES SHALL BE MOUNTED BACK TO BACK.

E. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR

FIRE/SMOKE RATED WALLS AND FLOORS.

F. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN

ACCORDANCE WITH NEC PARAGRAPHS 230.8, 300.5(G) AND

300.7(A). ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC

AND NFPA.

G. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT

ACCESS.

H. ALL CABLING ABOVE CEILING SHALL BE PROPERLY SUPPORTED

(NOT FROM CEILING SYSTEM).

I. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES

WITH OWNER.

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E 01.2

ELECTRICAL INFO SHEET

009258015-7-E 01.2 ELECTRICAL INFO SHEET

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

GENERAL LIGHTING NOTES

GEN. POWER & AUX SYS. NOTES

XREF. NOTES ( )

PROJECT ELECTRICAL REFERENCED NOTES

GENERAL NOTES REF. DEMO NOTES ( )

PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES

DXGENERAL DEMO NOTES

SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E 02.2

ELECTRICAL SPECIFICATIONS

009258015-7-E 02.2 ELECTRICAL SPECIFICATIONS

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E 03.2

ELECTRICAL SPECIFICATIONS

009258015-7-E 03.2 ELECTRICAL SPECIFICATIONS

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E 04.2

ELECTRICAL SPECIFICATIONS

009258015-7-E 04.2 ELECTRICAL SPECIFICATIONS

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

S

D4

D4

D5

EXTG PANEL 'HS-6'

D6 (TYP.)

D6(TYP.)

D3

D10

D10

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

ED01.2

FLOOR PLAN - DEMOLITION

009258015-7-ED01.2 FLOOR PLAN - DEMOLITION

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - ELECTRICAL DEMOLITION - PACKAGE B

DATE INITIAL

REF. DEMO NOTES ( ):DX

D3 DISCONNECT EXISTING EXHAUST FAN FOR REMOVAL BY MECHANICAL.

D4 DISCONNECT EXISTING FURNACE FOR REMOVAL BY MECHANICAL.

D5 DISCONNECT EXISTING CONDENSING UNIT FOR REMOVAL BY

MECHANICAL.

D6 SUPPORT AND REINSTALL LIGHTING/CEILING DEVICES AS NECESSARY

FOR CEILING REMOVAL AND RE-INSTALLATION.

D10 NO ELECTRICAL DEMOLITION IN THIS SPACE.

ALL POWERED RECEPTACLES, DEVICES, AND EQUIPMENT SHOWN SHALL BE

CIRCUITED AS OUTLINED IN THIS NOTE, UNLESS INDICATED OTHERWISE.

PANELBOARD CIRCUITING, INCLUDING IDENTIFYING SEPARATE

PANELBOARDS' BRANCH CIRCUIT AREAS, IS DELINEATED WITH A DASH-DOT

LINE BOUNDARY, WITH PANEL NAMES IDENTIFIED AT BOUNDARY LINE.

CIRCUIT NUMBERS ARE IDENTIFIED ADJACENT TO RECEPTACLE, DEVICE, OR

EQUIPMENT. REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION.

PANELBOARD CIRCUITING

EF-1

EF-1

HS-6 - 23,25

HP-1

HS-6 - 27,29

HP-2

HS-6 - 31,33

HP-3

HS-6 - 35,37

HP-4

HS-6 - 38,40

AHU-2

HS-6 - 39,41

AHU-1

PANEL 'HS-6'

HS-6 - 42

DH-1

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E201.2

FLOOR PLAN - POWER

009258015-7-E201.2 FLOOR PLAN - POWER

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

REF. NOTES ( ):X

6 CONNECT TO UNSWITCHED LIGHTING CIRCUIT SERVING SPACE. PROVIDE

POWER PACK/RELAY COMPATIBLE WITH ROOM LIGHTING CONTROL TO

CONTROL FAN WITH ROOM LIGHTING.

7 AHU UNIT GENERAL POWER SERVED FROM ASSOCIATED HP UNIT WITH

SEPARATE CIRCUIT FOR AUXILIARY HEAT.

12 COORDINATE WORK IN THIS SPACE WITH PROJECT 1.

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - POWER PACKAGE B

ALL POWERED RECEPTACLES, DEVICES, AND EQUIPMENT SHOWN SHALL BE

CIRCUITED AS OUTLINED IN THIS NOTE, UNLESS INDICATED OTHERWISE.

PANELBOARD CIRCUITING, INCLUDING IDENTIFYING SEPARATE

PANELBOARDS' BRANCH CIRCUIT AREAS, IS DELINEATED WITH A DASH-DOT

LINE BOUNDARY, WITH PANEL NAMES IDENTIFIED AT BOUNDARY LINE.

CIRCUIT NUMBERS ARE IDENTIFIED ADJACENT TO RECEPTACLE, DEVICE, OR

EQUIPMENT. REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION.

PANELBOARD CIRCUITING

HS-6A - 2

SF-1

HS-6 - 44,46

AHU-4

HS-6 - 43,45

AHU-3

HS-6A - 2

SF-1

HS-6A - 6

DH-1

HS-6A - 1

DH-1

G

G

HS-6A - 5

HS-6A - 5

EXTG PANEL 'HS-6A'

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E202.2

FLOOR PLAN - POWER

009258015-7-E202.2 FLOOR PLAN - POWER

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

REF. NOTES ( ):X

7 AHU UNIT GENERAL POWER SERVED FROM ASSOCIATED HP UNIT WITH

SEPARATE CIRCUIT FOR AUXILIARY HEAT.

SCALE: 1/4" = 1'-0"

ATTIC FLOOR PLAN - POWER PACKAGE B

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - POWER PACKAGE B

PANEL

'XXX'

FIRST FLOOR

SECOND FLOOR

PANEL

'HS-6'

FIRST FLOOR

SECOND FLOOR

EXTG

PANEL

'HS-6A'

F600A3

10FIRST FLOOR

SECOND FLOOR

EXTG

PANEL

'HS-6'

FIRST FLOOR

SECOND FLOOR

EXTG

PANEL

'HS-6A'

D7

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATEwww.schemmer.comC U s e rs \j b in g e \D o c u m e n ts

\0

-E le c

H S

R jb in g e .r v t

JCB

JCB

KJS

04/09/2026

09258015

E501.2

POWER RISER DIAGRAMS

009258015-7-E501.2 POWER RISER DIAGRAMS

FORT SCOTT HISTORIC SITE, 199 OLD FORT BLVD

FORT SCOTT, KS 66701

80073

FINAL CONSTRUCTION DOCUMENTS

341293

REMOVE AND REPLACE HS-6 HVAC

FEEDER SCHEDULE ( ):FXXXXXXX

F600A3 2 SETS OF 3#350 - 2-1/2"C

REF. NOTES ( ):X

8 PROVIDE NEW CONDUIT AND WIRING FROM SERVING UTILITY

TRANSFORMER.

9 RECONNECT EXISTING CIRCUITS TO REMAIN.

10 GROUND PER NEC.

SCALE: NOT TO SCALE

POWER RISER DIAGRAM

SCALE: NOT TO SCALE

POWER RISER DIAGRAM DEMOLITION

GENERAL EQUIPMENT SCHEDULE NOTES:

A. THIS SCHEDULE DISPLAYS SIZING INFORMATION THAT IS GENERIC IN

NATURE. SCHEDULE DOES NOT ITEMIZE ALL INSTANCES OF

EQUIPMENT. CONTRACTOR SHALL REFER TO THE PLANS FOR FINAL

QUANTITIES AND LOCATIONS.

B. MOUNT ALL DISCONNECTS AND STARTERS ON ASSOCIATED

EQUIPMENT UNLESS SHOWN OTHERWISE. MAINTAIN WORKING

CLEARANCES PER NEC; COORDINATE WITH MECHANICAL

CONTRACTOR.

C. BCU = BOX COVER UNIT (COOPER #SSY / #STY OR EQUAL) WITH FUSE.

D. NFD OR FD = NON-FUSED OR FUSED DISCONNECT SWITCH.

E. CS/NFD, FD = COMBINATION STARTER/ NON OR FUSED DISCONNECT

SWITCH.

F. INT = INTEGRAL DISCONNECT FURNISHED WITH EQUIPMENT.

G. ALL SWITCHES, DISCONNECTS, ETC SHALL BE LOCKABLE.

H. ALL SWITCHES, DISCONNECTS, ETC SHALL BE NEMA 3R WHERE

REQUIRED.

I. PROVIDE FUSES AS SHOWN; REVISE SIZES PER ACTUAL NAMEPLATE

DATA.

EQUIPMENT SCHEDULE NOTES:

1. AHU POWERED FROM ASSOCIATED HP, PROVIDE SEPARATE CIRCUIT

FOR AUX HEAT.

2. PROVIDE CONDUIT AND WIRING FROM HP TO ASSOCIATED AHU FOR

GENERAL AHU POWER.

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED