This is a Statement of Work (SOW) for fire protection system repairs and NFPA 25 inspections at Devils Tower National Monument in Wyoming, issued by the National Park Service, Department of the Interior.
The work encompasses corrective repairs and mandatory inspections for fire sprinkler and fire alarm systems at the Ranger Station and Visitor Center. At the Ranger Station, tasks include installing missing sprinkler head escutcheons, supplying head wrenches, replacing two fire alarm panel batteries, replacing water and air gauges on the dry sprinkler system, and replacing/repairing specific Rasco and Tyco components. The Ranger Station also requires a 5-year NFPA 25 internal obstruction inspection covering system valves, risers, cross mains, branch lines, dry pipe and wet alarm valves, check valves, and strainers, along with pressure gauge replacement and main drain flow testing. A past-due 3-year dry system full trip test must be performed with a 2-hour air test and auxiliary drain inspection. At the Visitor Center, work includes replacing a leaking 2.5" Victaulic control valve and 1" main drain, and repairing and retesting a 1.5" Wilkins 950XL domestic backflow preventer and 2.5" Ames 2000SS fire backflow preventer.
The contractor must furnish all valves, components, tools, equipment, PPE, and testing materials, while the government provides facility access, escorts, and utility availability. Work must be completed within 30 days of Notice to Proceed. Performance requirements include NFPA 25 (2020) compliance, UL/FM listed components, and certified technicians. Deliverables include completed NFPA 25 and backflow test reports, repair documentation, before/after photos, and final system operational verification. Special conditions prohibit electrical work, ceiling removal, patching, and painting unless negotiated with the NPS Contracting Officer's Representative. The work location is Highway 110, Building 170, Devils Tower, Wyoming 82714.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B08_Solicitation_140P1426Q0035_Attachment_2-DOL_Wage_Determination.pdf | ||
| Sol_140P1426Q0035.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of the Interior
NATIONAL PARK SERVICE
DEVILS TOWER NATIONAL MONUMENT
P.O. Box 10 Devils Tower, WY 82714
STATEMENT OF WORK (SOW)
Fire Protection System Repairs & NFPA 25 Inspections Devils Tower National Monument (DETO)
1.0 PROJECT OVERVIEW
Devils Tower National Monument requires corrective repairs and mandatory NFPA 25 inspections on the fire sprinkler and fire alarm systems located at the Ranger Station and Visitor Center. This work includes remedying identified system deficiencies, conducting overdue 3-year and 5-year inspections, replacing failed system components, and ensuring the facilities meet the fire protection requirements outlined in NFPA 25 (2020 edition).
2.0 BACKGROUND
Recent fire protection inspections at the Ranger Station and Visitor Center identified multiple system deficiencies, including leaking control valves, missing sprinkler system components, failed backflow preventers, and failed fire alarm panel batteries. Additionally, NFPA 25-required periodic inspections— specifically the 3-year dry system full trip test and the 5-year internal pipe obstruction investigation— are overdue.
3.0 SCOPE OF WORK AND TASKS
3.1 Ranger Station – Deficiency Corrections
• Install missing sprinkler head escutcheon.
• Supply and install head wrenches.
• Replace (2) fire alarm panel batteries.
• Replace 1 water and 1 air gauge on the dry sprinkler system.
• Replace/repair Rasco R5714 dry head escutcheon, Tyco Ty3131 brass upright (200° QR), and Tyco
Ty3131 brass sidewall (155° QR).
3.2 Ranger Station – 5-Year NFPA 25 Internal Obstruction Inspection
• Internal inspection of system valve, riser, cross main, branch lines.
• Internal inspection of dry pipe and wet alarm valves.
• Internal inspection of check valves and strainers.
• Replace expired pressure gauge(s).
• Main drain flow test.
• Provide NFPA inspection report.
3.3 Ranger Station – 3-Year Dry System Full Trip Test (Past Due)
• Perform 3-year full trip test.
• Conduct 2-hour air test.
• Inspect auxiliary drains.
• Submit NFPA inspection report.
3.4 Visitor Center – Sprinkler System Repairs
• Replace leaking 2.5" Victaulic control valve.
• Replace leaking 1" main drain.
3.5 Visitor Center – Backflow Preventer Repairs
• Repair and retest 1.5" Wilkins 950XL domestic backflow.
• Repair and retest 2.5" Ames 2000SS fire backflow.
4.0 GOVERNMENT FURNISHED MATERIALS
• Facility access, escorts, utility availability.
5.0 CONTRACTOR FURNISHED MATERIALS
• All valves, components, tools, equipment, PPE, testing materials.
6.0 PERIOD OF PERFORMANCE
• Complete within 30 days of Notice to Proceed (NTP).
7.0 PERFORMANCE REQUIREMENTS
• Compliance with NFPA 25 (2020).
• UL/FM listed components.
• Certified technicians.
• System restored to full operational status.
8.0 SPECIAL CONDITIONS
• No electrical work, ceiling removal, patching, painting. Unless otherwise negotiated with NPS COR or representative.
• Auxiliary drain maintenance is an owner responsibility.
• Normal business hours only.
• Fire watch by NPS (if required).
9.0 DELIVERABLES
• Completed NFPA 25 reports.
• Backflow test reports.
• Repair documentation.
• Before/after photos.
• Final system operational verification.
10.0 Service Address:
NPS. Devils Tower NM Hwy 110, Bldg 170 Devils Tower WY 82714
Address Fire Suppression System Deficiencies Parkwide
Item RSMeans Code
Ra nger Sta tion 21 13 13.20 0300 Escutcheon replacement
Repairs and 5yr 21 13 13.20 0500 Sprinkler head wrenches 21 13 13.20 0200 Tyco brass upright 200°F QR 21 13 13.20 0250 Tyco sidewall 155°F QR 21 13 13.20 0300 Dry head escutcheon 26 55 00.10 3000 FACP ba tteries (2) 26 05 19.20 0700 Ba ttery la bor 21 13 13.40 1100 Internal inspection - valves/mains/branches 21 13 13.40 1000 Interna l inspection - dry/wet va lves 21 13 13.40 1500 Internal inspection - check valves 21 13 13.20 1000 Repla ce pressure gauges 21 13 13.40 0500 Ma in dra in flow test 01 31 23.20 1000 Reporting
Ra nger Sta tion 21 13 13.40 2000 Dry system trip test
3 yr 21 13 13.40 2500 2-hour air test 21 13 13.40 0500 Auxilia ry dra in check 01 31 23.20 1000 Reporting 21 05 00.20 0200 La bor (6 hrs, 2 techs)
Visitor Center 21 13 13.20 2100 2.5” Victa ulic control va lve
Repa irs / Ba ckflows 21 13 13.40 0600 Va lve la bor 22 05 23.10 1600 1” ma in dra in ba ll va lve 22 05 23.10 2000 Ma in drain labor 22 11 19.40 1000 1.5” Wilkins 950XL repa ir 22 11 19.40 2000 950XLtest 22 11 19.40 1200 2.5” Ames 2000SS repair 22 11 19.40 2200 2000SS fire backflow test 21 05 00.20 0200 Labor (8 hrs, 2 techs)
| STATEMENT OF WORK (SOW) |
| 1.0 PROJECT OVERVIEW |
| 2.0 BACKGROUND |
| 3.0 SCOPE OF WORK AND TASKS |
| 3.2 Ranger Station – 5-Year NFPA 25 Internal Obstruction Inspection |
| 3.3 Ranger Station – 3-Year Dry System Full Trip Test (Past Due) |
| 3.4 Visitor Center – Sprinkler System Repairs |
| 3.5 Visitor Center – Backflow Preventer Repairs |
| 4.0 GOVERNMENT FURNISHED MATERIALS |
| 5.0 CONTRACTOR FURNISHED MATERIALS |
| 6.0 PERIOD OF PERFORMANCE |
| 7.0 PERFORMANCE REQUIREMENTS |
| 8.0 SPECIAL CONDITIONS |
| 9.0 DELIVERABLES |