B08_Fire_Alarm_Components.pdf

PDF 7 MB Posted

Attached to
Fire Alarm Maintenance Services - CA Federal contract opportunity
Solicitation number
140FC224R0019
Issued by
Department of the Interior Fish and Wildlife Service

About this file

This document is a submittal for fire alarm system components related to the Farallon Fire Alarm System federal contract opportunity, Solicitation Number 140FC224R0019, issued by the U.S. Fish and Wildlife Service.

The submittal lists the specific fire alarm system components being provided by the subcontractor/supplier Deep Blue Integration, including the fire alarm control panel, smoke detectors, heat detectors, monitor modules, carbon monoxide detectors, and various notification appliances. The components are all Notifier brand products with accompanying part numbers. The submittal is seeking approval of these specified components for the Farallon Island National Wildlife Refuge Quarters 50 & 51 in San Francisco, CA under the federal contract.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Alarm Maintenance Services - CA, newest first.
File Type Posted
Sol_140FC224R0019_Amd_0001.pdf PDF
B08_Past_Performance_Survey.doc DOC document
B08_Drawings_ASBUILTS_03-12-18.pdf PDF
B08_SOW.pdf PDF
Sol_140FC224R0019.pdf PDF
B08_Door_Components.pdf PDF
B08_Bid_Schedule.pdf PDF
B08_Wages.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SUBMITTAL # 02

RESUBMITTAL #

DATE: 09/05/2017

Mark J. Harris, P.E.

USFWS Region 1/8 Engineering 911 NE 11th Ave Portland, OR 97232

RE: F17PD01094 – Farallon Fire Alarm System

ATTACHED FOR YOUR APPROVAL:

SPECIFICATION SECTION: Fire Alarm – System Components SUBCONTRACTOR/SUPPLIER: Deep Blue Integration

ITEM: Alarm System Components

SUBMITTED BY: David Sansone

THIS SUBMITTAL IS RETURNED WITH ACTION DESIGNATED WITH THE FOLLOWING:

APPROVED REJECTED, SEE REMARKS

NO EXCEPTION TAKEN REMARKS ATTACHED

RESUMBITTAL NOT REQUIRED

REVISE & RESUBMIT MAKE CORRECTIONS NOTED,

RESUBMIT FOR RECORDS ONLY

AUTHORIZED SIGNATURE TITLE DATE

Deep Blue Integration, Inc. ● Phone 888.6000.DBI ● Fax 805.791.2037 ● www.deepblueintegration.com

3442 Empresa Drive Suite C, San Luis Obispo, CA 93401 ● C.10, C.16 943465 ● ACO 6864 ● CA Small Business # 1242460 ● DIR # 1000002283

FIRE ALARM MATERIAL SUBMITTAL

FARALLON ISLAND NATIONAL WILDLIFE REFUGE

QUARTERS 50 & 51

SAN FRANCISCO, CA

DESCRIPTION MANUFACTURER PART #

FIRE ALARM CONTROL PANEL NOTIFIER NFS-320

SMOKE DETECTOR NOTIFIER FSP-851

HEAT DETECTOR NOTIFIER FST-851

HEAT DETECTOR NOTIFIER FST-581H

MONITOR MODULE NOTIFIER FMM-101

CARBON MONOXIDE DETECTOR SYSTEM SENSOR CO1224T

WEATHERPROOF HORN SYSTEM SENSOR HRK

HORN/STROBE WALL MOUNT SYSTEM SENSOR P2RL

HORN/STOBE CEILING MOUNT SYSTEM SENSOR PC2RL

STROBE WALL MOUNT SYSTEM SENSOR SRL

STROBE CEILING MOUNT SYSTEM SENSOR SCRL

DETECTOR SOUNDER BASE SYSTEM SENSOR B200S-LF

DN-7112:J • 12/20/2013 — Page 1 of 8

NFS-320

Intelligent Addressable Fire Alarm System

Intelligent Fire Alarm Control Panels

DN-7112:J • A-14

NFS-320

ph o1

.jp g

General The NFS-320 intelligent Fire Alarm Control Panel is part of the ONYX® Series of Fire Alarm Controls from NOTIFIER.

In stand-alone or network configurations, ONYX Series prod-ucts meet virtually every application requirement.

The NFS-320’s modular design makes system planning eas-ier. The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application.

For installations using NFS-320C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order separately; see DN-60085).

NOTE: Unless called out with a version-specific “R”, “C” or “E” at the end of the part number, “NFS-320” refers to models NFS-320, NFS-320R, NFS-320C, and NFS-320E.

Features

• Certified for seismic applications when used with the appropriate seismic mounting kit.

• Approved for Marine applications when used with listed compatible equipment. See DN-60688.

• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7.

• Up to 159 detectors (any mix of ion, photo, thermal, or multi-sensor) and 159 modules (Addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay). 318 devices maximum.

• Standard 80-character display.

• Network options:

– High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-

EM, ONYXWorks, NFS-3030, NFS-640, and NCA).

– Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-

EM, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC-EM is used in network paging.

• 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization.

• Built-in Alarm, Trouble, Security, and Supervisory relays.

• VeriFire® Tools online or offline programming utility.

Upload/Download, save, store, check, compare, and simu-late panel databases. Upgrade panel firmware.

• Autoprogramming and Walk Test reports.

• Multiple central station communication options:

– Standard UDACT

– Internet

– Internet/GSM

• 80-character remote annunciators (up to 32).

• EIA-485 annunciators, including custom graphics.

• Printer interface (80-column and 40-column printers).

• History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file.

• Alarm Verification selection per point, with automatic counter.

• Presignal/Positive Alarm Sequence (PAS).

• Silence inhibit and Auto Silence timer options.

• NAC coding functions:

– March time.

– Temporal.

– California two-stage coding.

– Canadian two-stage.

– Strobe synchronization.

• Field-programmable on panel or on PC, with VeriFire® Tools program check, compare, simulate.

• Full QWERTY keypad.

• Battery charger supports 18 – 200 AH batteries.

• Non-alarm points for lower priority functions.

• Remote ACK/Signal Silence/System Reset/Drill via moni-tor modules.

• Automatic time control functions, with holiday exceptions.

• Extensive, built-in transient protection.

• Powerful Boolean logic equations.

FLASHSCAN® INTELLIGENT FEATURES

• Polls up to 318 devices in less than two seconds.

• Activates up to 159 outputs in less than five seconds.

• Multicolor LEDs blink device address during Walk Test.

• Fully digital, high-precision protocol (U.S. Patent 5,539,389).

• Manual sensitivity adjustment — up to nine levels.

• Pre-alarm ONYX intelligent sensing — up to nine levels.

• Day/Night automatic sensitivity adjustment.

• Sensitivity windows:

– Ion – 0.5 to 2.5%/foot obscuration.

msanchez Highlight

Page 2 of 8 — DN-7112:J • 12/20/2013

– Photo – 0.5 to 2.35%/foot obscuration.

– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.

– Acclimate® Plus™ – 0.5 to 4.0%/foot obscuration.

– IntelliQuad – 1.0 to 4.0%/foot obscuration.

– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration

• Drift compensation (U.S. Patent 5,764,142).

• Degraded mode — in the unlikely event that the NFS- 320’s primary microprocessor fails, FlashScan detectors revert to degraded operation and can activate the control panel’s NAC circuits and alarm relay. Each of the four built-in panel circuits includes a Disable/Enable switch for this feature.

• Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515).

• Automatic detector sensitivity testing (NFPA-72 compli-ant).

• Maintenance alert (two levels).

• Self-optimizing pre-alarm.

FSL-751 VIEW (VERY INTELLIGENT EARLY WARNING)

SMOKE DETECTION TECHNOLOGY

• Advanced ONYX intelligent sensing algorithms differenti-ate between smoke and non-smoke signals (U.S. Patent 5,831,524).

• Addressable operation pinpoints the fire location.

• Early warning performance comparable to the best aspira-tion systems at a fraction of the lifetime cost.

FAPT-851 ACCLIMATE® PLUS™

LOW-PROFILE INTELLIGENT MULTI-SENSOR

• Detector automatically adjusts sensitivity levels without operator intervention or programming. Sensitivity increases with heat.

• Microprocessor-based technology; combination photo and thermal technology.

• Low-temperature warning signal at 40°F ± 5°F (4.44°C ± 2.77°C).

FSC-851 INTELLIQUAD

ADVANCED MULTI-CRITERIA DETECTOR

• Detects all four major elements of a fire (smoke, heat, CO, and flame).

• Automatic drift compensation of smoke sensor and CO cell.

• High nuisance-alarm immunity.

FSA-8000 INTELLIGENT FAAST DETECTOR

• Connects directly to the SLC loop of compatible ONYX series panels

• Provides five event thresholds that can be individually pro-grammed with descriptive labels for control-by-event pro-gramming; uses five detector addresses.

• Uses patented particle separator and field-replaceable fil-ter to remove contaminants.

• Advanced algorithms reject common nuisance conditions

FCO-851 INTELLIQUAD™ PLUS

ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR

• Detects all four major elements of a fire.

• Separate signal for life-safety CO detection.

Sample System Options

7112blok-201311.wmf

SLC Intelligent Loop

DEVICES

FSC-851 IntelliQuad FAPT-851 Acclimate PLUS FSL-751 FlashScan VIEW

FSP-851 Photo FSI-851 Ion

FST-851 Thermal

FSA-8000

...etc.

NBG-12LX XP6/10 I/O Modules

FMM-1

IDCFDU-80

LCD2-80

Up to 32 remote displays

EIA-485

EIA-485

EIA-232

2048 annunciator/control points

Optional 318-point UDACT

Dual phone lines to Central Station

ACM/AEM-24AT

LED Annunciator

LDM-32

Custom Graphics

ACM-8R

Relay Control

FCM-1

NAC

FRM-1

Relay Contact

PRN Series Printer

NFS-320

DN-7112:J • 12/20/2013 — Page 3 of 8

• Optional addressable sounder base for Temp-3 (fire) or Temp-4(CO) tone.

• Automatic drift compensation of smoke sensor and CO cell.

• High nuisance-alarm immunity.

RELEASING FEATURES

• Ten independent hazards.

• Sophisticated cross-zone (three options).

• Delay timer and Discharge timers (adjustable).

• Abort (four options).

• Low-pressure CO2 listed.

VOICE FEATURES

• Integrates with FirstCommand Series. See DN-60772.

• Telephone applications require NFC-FFT.

HIGH-EFFICIENCY OFFLINE SWITCHING

3.0 A POWER SUPPLY (6.0 A IN ALARM)

• 120 VAC (NFS-320/NFS-320C); 240 VAC (NFS-320E).

• Displays battery current/voltage on panel (with display).

FlashScan, Exclusive World-Leading Detector Protocol At the heart of the NFS-320 is a set of detection devices and device protocol — FlashScan (U.S. Patent 5,539,389). Flash- Scan is an all-digital protocol that gives superior precision and high noise immunity.

In addition to providing quick identification of an active input device, this protocol can also activate many output devices in a fraction of the time required by competitive protocols. This high speed also allows the NFS-320 to have the largest device per loop capacity in the industry — 318 points — yet every input and output device is sampled in less than two seconds. The microprocessor-based FlashScan detectors have bicolor LEDs that can be coded to provide diagnostic information, such as device address during Walk Test.

ONYX Intelligent Sensing Intelligent sensing is a set of software algorithms that pro-vides the NFS-320 with industry-leading smoke detection capability. These complex algorithms require many calcula-tions on each reading of each detector, and are made possi-ble by the high-speed microcomputer used by the NFS-320.

Drift Compensation and Smoothing: Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces maintenance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72. Smoothing filters are also provided by software to remove transient noise signals, such as those caused by electrical interference.

Maintenance Warnings: When the drift compensation per-formed for a detector reaches a certain level, the perfor-mance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit.

Sensitivity Adjust: Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automatically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on prede-termined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to activate special control functions.

Self-Optimizing Pre-Alarm: Each detector may be set for “Self-Optimizing” pre-alarm. In this special mode, the detec-tor “learns” its normal environment, measuring the peak ana-log readings over a long period of time, and setting the pre-alarm level just above these normal peaks.

Cooperating Multi-Detector Sensing: A patented feature of ONYX intelligent sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensi-tivity to actual smoke by a factor of almost two to one.

Field Programming Options Autoprogram is a timesaving feature. The FACP “learns” what devices are physically connected and automatically loads them in the program with default values for all parame-ters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.

Keypad Program Edit (with KDM-R2) The NFS-320, like all NOTIFIER intelligent panels, has the exclusive feature of pro-gram creation and editing capability from the front panel key-pad, while continuing to provide fire protection. The architecture of the NFS-320 software is such that each point entry carries its own program, including control-by-event links to other points. This allows the program to be entered with independent per-point segments, while the NFS-320 simulta-neously monitors other (already installed) points for alarm conditions.

VeriFire® Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confidence in the site-specific software. It is Win-dows®-based and provides technologically advanced capa-bilities to aid the installer. The installer may create the entire program for the NFS-320 in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel.

Placement of Equipment in Chassis and Cabinet The following guidelines outline the NFS-320’s flexible sys-tem design.

Wiring: When designing the cabinet layout, consider separa-tion of power-limited and non-power-limited wiring as dis-cussed in the NFS-320 Installation Manual.

It is critical that all mounting holes of the NFS-320 are secured with a screw or standoff to ensure continuity of Earth Ground.

Networking: If networking two or more control panels, each unit requires a Network Communication Module or High- Speed Network Communication Module (HS-NCM can sup-port two nodes; see “Networking Options” on page 4). These modules can be installed in any option board position (see manual), and additional option boards can be mounted in front of them.

Page 4 of 8 — DN-7112:J • 12/20/2013

KDM-R2 Controls and Indicators Program Keypad: QWERTY type (keyboard layout).

12 LED Indicators: Power; Fire Alarm; Pre-Alarm; Security;

Supervisory; System Trouble; Signals Silenced; Points Dis-abled; Control Active; Abort; Pre-Discharge; Discharge.

Keypad Switch Controls: Acknowledge/Scroll Display; Sig-nal Silence; Drill; System Reset; Lamp Test.

LCD Display: 80 characters (2 x 40) with long-life LED back-light.

Product Line Information

• “Configuration Guidelines” on page 4

• “Networking Options” on page 4

• “Auxiliary Power Supplies and Batteries” on page 4

• “Audio Options” on page 4

• “Compatible Devices, EIA-232 Ports” on page 4

• “Compatible Devices, EIA-485 Ports” on page 4

• “Compatible Intelligent Devices” on page 5

• “Enclosures, Chassis, and Dress Plates” on page 5

• “Other Options” on page 6

CONFIGURATION GUIDELINES

The NFS-320 system ships assembled; description and some options follow. See “Enclosures, Chassis, and Dress Plates” on page 5 for information about mounting peripher-als.

NOTE: Stand-alone and network systems require a main display.

On stand-alone systems, the panel’s keypad provides the required display. On network systems (two or more networked fire panel nodes), at least one NCA-2, NCS, or ONYXWorks annunciation device is required. (For NCA-2, see DN-7047.)

NFS-320: The standard, factory-assembled NFS-320 system includes the following components: one control panel mounted on chassis (120 V operation — ships with ground-ing cable, battery interconnect cables, and document kit);

includes integral power supply mounted to the main circuit board; one primary display KDM-R2 keypad/display; and one cabinet for surface or semi-flush mounting. Purchase batter-ies separately. One or two option boards may be mounted inside the NFS-320 cabinet; additional option boards can be used in remote cabinets. (Non-English versions also avail-able. NFS-320-SP, NFS-320-PO.)

NFS-320R: Same as NFS-320, but in red enclosure.

NFS-320C: Based on NFS-320 above. NFS-320C supports installation of an optional ACM-series annunciator in the same cabinet. UL- and ULC-listed. (Non-English version also available: NFS-320C-FR.) For NFS-320C, see DN-60085.

NFS-320CR: Same as NFS-320C but in a red enclosure. For NFS-320C, see DN-60085.

NFS-320E: Same as NFS-320, but with 240 V operation.

(Non-English versions also available. NFS-320E-SP, NFS-

320E-PO.)

TR-320: Trim ring for the NFS-320 cabinet.

NETWORKING OPTIONS

NCM-W, NCM-F: Standard Network Communications Mod-ules. Wire and multi-mode fiber versions available. See DN- 6861.

HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network Communications Modules. Wire, single-mode fiber, multi-mode fiber, and media conversion models are available. See

DN-60454.

RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), multi-mode fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See

DN-6971.

ONYXWorks: UL-listed graphics PC workstation, software, and computer hardware. See DN-7048 for specific part num-bers.

NFN-GW-EM-3: NFN Gateway, embedded. See DN-60499.

NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928.

CAP-GW: Common Alerting Protocol Gateway. See DN- 60576.

VESDA-HLI-GW: VESDAnet high-level interface gateway.

See DN-60753.

LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and high-speed NOTI•FIRE•NET networks through the NFN Gateway. See DN-60679.

OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW.

See DN-60679.

AUXILIARY POWER SUPPLIES AND BATTERIES

ACPS-610: 6.0 A or 10.0 A addressable charging power sup-ply. See DN-60244.

APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and transfer relay, and overcurrent protection. Mounts on two of four positions on a CHS-4L or CHS-4 chassis. See

DN-5952.

FCPS-24S6/S8: Remote 6 A and 8 A power supplies with battery charger. See DN-6927.

BAT Series: Batteries. NFS-320 uses two 12 volt, 18 to 200 AH batteries. See DN-6933.

AUDIO OPTIONS

NFC-50/100: 25 watt, 25 VRMS, emergency Voice Evacua-tion Control Panel (VECP) with integral commercial micro-phone, digital message generator, and Class A or Class B speaker circuits. See DN-60772.

COMPATIBLE DEVICES, EIA-232 PORTS

PRN-6: 80-column printer. See DN-6956.

VS4095/5: Printer, 40-column, 24 V. Mounted in external backbox. See DN-3260.

DPI-232: Direct Panel Interface, specialized modem for extending serial data links to remotely located FACPs and/or peripherals; mount on NFS-320 chassis. See DN-6870.

COMPATIBLE DEVICES, EIA-485 PORTS

ACM-24AT: ONYX Series ACS annunciator – up to 96 points of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) by point to be red, green, or yellow; the Trouble LED is always yellow. See DN-6862.

AEM-24AT: Same LED and switch capabilities as ACM-24AT, expands the ACM-24AT to 48, 72, or 96 points. See DN- 6862.

ACM-48A: ONYX Series ACS annunciator – up to 96 points of annunciation with Alarm or Active LED per circuit. Active/ Alarm LEDs can be programmed (by powered-up switch

DN-7112:J • 12/20/2013 — Page 5 of 8 selection) in groups of 24 to be red, green, or yellow. Expand-able to 96 points with one AEM-48A. See DN-6862.

AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-48A to 96 points. See DN-6862.

ACM-8R: Remote Relay Module with eight Form-C contacts.

Can be located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN-3558.

FDU-80: Terminal mode. 80-character, backlit LCD display.

Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See DN-6820.

LCD2-80: Terminal and ACS mode. 80-character, backlit LCD display. Mounts up to 6,000 ft. (1828.8 m) from panel.

Up to 32 per FACP. See DN-60548.

LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM- R32; remote custom driver modules. See DN-0551.

SCS: Smoke control stations SCS-8, SCE-8, with lamp driv-ers SCS-8L, SCE-8L; eight (expandable to 16) circuits (HVAC only). See DN-4818.

TM-4: Transmitter Module. Includes three reverse-polarity cir-cuits and one municipal box circuit; mount on NFS-320 chas-sis or remotely. See DN-6860.

UDACT-2: Universal Digital Alarm Communicator Transmit-ter, 636 channel. See DN-60686.

UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Micropro-cessor-controlled, field-programmable from IBM®-compatible PCs (requires optional programming kit). Mounts in BB-UZC.

See DN-3404.

COMPATIBLE INTELLIGENT DEVICES

FSA-8000: Intelligent FAAST Fire Alarm Aspiration Sensing Technology®. Intelligent aspirating smoke detector. For Canadian applications, order FSA-8000A. See DN-60792.

FSB-200: Intelligent beam smoke detector. See DN-6985.

FSB-200S: Intelligent beam smoke detector with integral sensitivity test. See DN-6985

FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria Detector. See DN-60412.

FCO-851: FlashScan IntelliQuad PLUS Advanced Multi-Cri-teria Fire/CO Detector. See DN-60689.

FSI-851: Low-profile FlashScan ionization detector. See DN- 6934.

FSP-851: Low-profile FlashScan photoelectric detector. See

DN-6935.

FSP-851T: Low-profile FlashScan photoelectric detector with 135°F (57°C) thermal. See DN-6935.

FSP-851R: Remote-test capable photoelectric detector for use with DNR(W) duct detector housings. See DN-6935.

FST-851: FlashScan thermal detector 135°F (57°C). See

DN-6936.

FST-851R: FlashScan thermal detector 135°F (57°C) with rate-of-rise. See DN-6936.

FST-851H: FlashScan 190°F (88°C) high-temperature ther-mal detector. See DN-6936.

FAPT-851: FlashScan Acclimate Plus low-profile multi-sen-sor detector. See DN-6937.

FSL-751: FlashScan VIEW laser photo detector. See DN- 6886.

DNR: InnovairFlex low-flow non-relay duct-detector housing (order FSP-851R separately). Replaces FSD-751PL/FSD- 751RPL. See DN-60429.

DNRW: Same as above with NEMA-4 rating, watertight. See

DN-60429.

B224RB: Low-profile relay base. See DN-60054.

B224BI: Isolator base for low-profile detectors. See DN- 60054.

B210LP: Low-profile base. Standard U.S. style. Replaces B710LP. See DN-60054.

B501: European-style, 4" (10.16 cm) base. See DN-60054.

B200S: Intelligent programmable sounder base, capable of producing a variety of tone patterns including ANSI Temporal

3. Compatible with sychronization protocol. See DN-60054.

B200SR: Sounder base, Temporal 3 or Continuous tone. See

DN-60054.

FMM-1: FlashScan monitor module. See DN-6720.

FDM-1: FlashScan dual monitor module. See DN-6720.

FZM-1: FlashScan two-wire detector monitor module. See

DN-6720.

FMM-101: FlashScan miniature monitor module. See DN- 6720.

FCM-1: FlashScan control module. See DN-6724.

FCM-1-REL: FlashScan releasing control module. See DN- 60390.

FRM-1: FlashScan relay module. See DN-6724.

FDRM-1: FlashScan dual monitor/dual relay module. See

DN-60709.

NBG-12LX: Manual pull station, addressable. See DN-6726.

ISO-X: Isolator module. See DN-2243.

XP6-C: FlashScan six-circuit supervised control module. See

DN-6924.

XP6-MA: FlashScan six-zone interface module; connects intelligent alarm system to two-wire conventional detection zone. See DN-6925.

XP6-R: FlashScan six-relay (Form-C) control module. See

DN-6926.

XP10-M: FlashScan ten-input monitor module. See DN- 6923.

SLC-IM: SLC integration module, for VESDAnet detectors.

See DN-60755.

ENCLOSURES, CHASSIS, AND DRESS PLATES

CAB-BM Marine System: Protects equipment in shipboard and waterfront applications. Also order BB-MB for systems using 100 AH batteries. For a full list of required and optional equipment, see DN-60688.

BB-UZC: Backbox for housing the UZC-256. Required for NFS-320 applications. Black. For red, order BB-UZC-R.

NFS-LBB: Battery Box (required for batteries larger than 26

AH).

NFS-LBBR: Same as above, but red.

SEISKIT-320/B26: Seismic mounting kit. Required for seis-mic-certified applications with NFS-320 and BB-26. Includes battery bracket for two 26 AH batteries.

Page 6 of 8 — DN-7112:J • 12/20/2013

SEISKIT-BB25: Seismic mounting kit for the BB-25. Includes battery bracket for two 26 AH batteries.

SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery bracket for two 55 AH batteries.

OTHER OPTIONS

411: Slave Digital Alarm Communicator. See DN-6619.

411UDAC: Digital Alarm Communicator. See DN-6746.

IPDACT-2/2UD, IPDACT Internet Monitoring Module: Con-nects to primary and secondary DACT telephone output ports for internet communications over customer-provided Ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IP. See DN-60408.

IPSPLT: Y-adapter option allow connection of both panel dialer outputs to one IPDACT-2/2UD cable input.

IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket; Red. For Black order IPENC-B.

IPGSM-4G: Internet and Digital Cellular Fire Alarm Commu-nicator. Provides selectable configurable paths: cellular only, IP only, or IP primary with cellular backup. Connects to the primary and secondary ports of a DACT. See DH-60769.

NFS-320-RB: Replacement board with central processing unit (CPU). NOTE: Keypad must be removed before shipping old unit out for repair.

• NFS-320-RBE: Replacement CPU, Export.

• NFS-320-RB-PO: Replacement CPU, Portuguese.

• NFS-320-RB-POE: Replacement CPU, Export, Portu-guese.

• NFS-320-RBC-FR: Replacement CPU, Canadian French.

• NFS-320-RB-SP: Replacement CPU, Spanish.

• NFS-320-RB-SPE: Replacement CPU, Export, Spanish.

NOTE: For other options including compatibility with retrofit equip-ment, refer to the panel's installation manual, the SLC manual, and the Device Compatibility Document.

System Specifications

SYSTEM CAPACITY

• Intelligent Signaling Line Circuits

• Intelligent detectors

• Addressable monitor/control modules

• Programmable internal hardware and output circuits

• Programmable software zones

• Special programming zones

• LCD annunciators per NFS-320/-320E

• ACS annunciators per NFS-320/-320E ................... 32 addresses x 64 points

SPECIFICATIONS

• Primary input power

– NFS-320: 120 VAC, 50/60 Hz, 5.0 A.

– NFS-320E: 220/240 VAC, 50/60 Hz, 2.5 A.

• Current draw (standby/alarm):

– NFS-320(E) board: 0.250 A. Add 0.035 A for each NAC in use.

– KDM-R2 (Backlight on): 0.100 A.

• Total output 24 V power: 6.0 A in alarm.

NOTE: The power supply has a total of 6.0 A of available power.

This is shared by all internal circuits. See Installation Manual for a complete current draw calculation sheet.

• Standard notification circuits (4): 1.5 A each.

• Resettable regulated 24V power: 1.25 A.

• Two non-resettable regulated 24V power outputs:

– 1.25 A.

– 0.50 A.

• Non-resettable 5V power: 0.15 A.

• Battery charger range: 18 AH – 200 AH. Use separate cabinet for batteries over 26 AH.

• Float rate: 27.6 V.

CABINET SPECIFICATIONS

NFS-320 cabinet dimensions:

• Backbox: 18.12 in. (46.025 cm) width; 18.12 in. (46.025

cm) height; 5.81 in. (14.76 cm) depth.

• Door: 18.187 in. (46.195 cm) width; 18.40 in. (46.736 cm) height; 0.75 in. (1.905 cm) depth.

• Trim ring: Molding width is 0.905 in. (2.299 cm).

• Shipping weight (without batteries): 36.15 lb. (16.4 kg).

TEMPERATURE AND HUMIDITY RANGES

This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the elec-tronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recom-mended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/ 60 – 80°F.

AGENCY LISTINGS AND APPROVALS

The listings and approvals below apply to the basic NFS-320 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in pro-cess. Consult factory for latest listing status.

• UL Listed: S635.

• ULC Listed: S635 (NFS-320C only, excludes IPDACT).

• FM Approved.

• CSFM: 7165-0028:0243.

• MEA: 128-07-E.

• FDNY: COA#6085, #6121.

• City of Chicago.

NOTE: For additional information on UL- and ULC-listed model NFS-320C, see DN-60085. For information on NFS-320SYS, see

DN-60637.

Marine Applications: Marine approved systems must be configured using components itemized in this document.

(See Main System Components, in “Product Line Informa-tion.) Specific connections and requirements for those com-ponents are described in the installation document, DN-7112:J • 12/20/2013 — Page 7 of 8

PN 54756. When these requirements are followed, systems are approved by the following agencies:

• US Coast Guard 161.002/50/0, 161.002/55/0 (Standard 46 CFR and 161.002).

• Lloyd's Register 11/600013 (ENV 3 category).

• American Bureau of Shipping (ABS) Type Approval.

NOTE: For information on marine applications, see DN-60688.

STANDARDS

The NFS-320 complies with the following UL Standards and NFPA 72, International Building Code (IBC), and California Building Code (CBC) Fire Alarm Systems requirements:

• UL 864 (Fire).

• UL 1076 (Burglary).

• UL 2572 (Mass Notification Systems).

• LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory).

• AUXILIARY (Automatic, Manual and Waterflow) (requires

TM-4).

• REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires TM-4).

• PROPRIETARY (Automatic, Manual, Waterflow and Sprin-kler Supervisory). Not applicable for FM.

• CENTRAL STATION (Automatic, Manual, Waterflow and Sprinkler Supervisory) (requires DACT).

• EMERGENCY VOICE/ALARM.

• OT, PSDN (Other Technologies, Packet-switched Data Network).

• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000

(Seismic).

• CBC 2007 (Seismic).

Page 8 of 8 — DN-7112:J • 12/20/2013

NOTI•FIRE•NET™, IntelliQuad™, and ONYXWorks™ are trademarks; and Acclimate® Plus™, FirstCommand®, FlashScan®, NOTIFIER®, ONYX®, VeriFire®, and VIEW® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of Microsoft Corporation. IBM® is a registered trademark of IBM Corporation.

©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7165-0028:0243 Page 1 of 4

CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)

LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653

Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309

Email: vladimir.kireyev@honeywell.com

DESIGN: Models NFS2-640, NFS-320/C (R), and NFS-320SYS fire alarm control units. Local, auxiliary, remote station (PPU), proprietary (PPU), central station (PPU), manual, automatic, waterfowl and sprinkler supervisory services. Also suitable for releasing service, Process

Management and Emergency Voice/Alarm communication System *. Model numbers may be followed by an “R” suffix representing the enclosure color being red. Refer to listee's data sheet for additional detailed product description and operational considerations. System components:

ACM-8R, -16AT, -32A, -24AT, -48A; Annunciator Control Modules

ACPS-610, AMPS-24; Addressable power supply/charger

ADP-4B, -A4, -1, -2, DP-DISP2; Dress Panel

AEM-16AT, -32A, -24AT, -48A; Annunciator Expander Modules

AFM-16A, -16AT, -32A; Annunciator Fixed Modules

AKS-1B; Annunciator Key Switch

APS2-6R; Power supply

BB-100, -200, NFS-LBB/-LBBR; Battery Boxes

BGRA-SCS, BGRB-SCS; Smoke Control Station

BMP-1; Blank Module

BP-4, BP2-4; Battery Dress Plates

CAB-3/-4 Series; Enclosure

CAB-RP, CAB-RPR; Cabinets

CEF-SCS; Smoke Control Station

CHS-4, CHS-4N, CHS-4L; Chassis

CPU2-640, CPU-320SYS; CPU Board

CRT-2; Display Terminal

DP-1B; Blank Panel

DPA-1A4/1/2, DP-DISP2; Dress Panel

DPI-232; Panel Interface

DR-A4, DR-A4B, DR-A4BR, DR-A4R; Door Assembly

DR-AA4, DR-AA4B, DR-AA4BR, DR-AA4R; Door Assembly

DR-B3F; Door Assembly

DR-B4, DR-B4B, DR-B4BR, DR-B4R; Door Assembly

DR-C4, DR-C4B, DR-C4BR, DR-C4R; Door Assembly

DR-D4, DR-D4B, DR-D4BR, DR-D4R; Door Assembly

*Rev. 10-29-13 gt

July 01, 2017Date Issued: Listing Expires June 30, 2018

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

DAVID CASTILLO, Program Coordinator

Listing No.

7165-0028:0243

EQ Series; Cabinets

EQBB-B4, EQBB-C4, EQBB-D4; Backbox Assembly

EQDR-B4, EQDR-C4, EQDR-D4; Door Assembly

FCM-1, FCM-1-REL; Releasing Control Module

FCPS-24S6, -24S8; Field Charger/Power Supply

FDM-1; Dual Monitor Module

FDRM-1:Multiple Module with two Relay Outputs

FDU-80/-80G; Remote Annunciator

FIRSTVISION-LCD/ENC; Interactive Firefighters’ display/enclosure

FRM-1; Relay Module

FTM-1; Control Module

FZM-1, FMM-1, FMM-101; Monitor Modules

HS-NCM-W/-MF/-SF/-WMF/-WSF/-MSSF; High Speed Network Control Modules

IPDACT-2/-2UD; IP Fire Alarm Communicator

ISO-X; Isolator Module

KAPS-24, CPS-24; Power Supply

KDM-R2; Keyboard Display Module

LCD-80, -160; Annunciators

LCD-80TM; Annunciator Terminal Module LCD

LCD2-80; Remote Annunciator

LDM-32/-E32/-R32; Lamp Driver Module

LEM-320/ELEM-320; Loop Expander Module

NBG-12LRA; Agent Releasing Abort Station

NBG-12LX; Addressable Manual Pull Station

NCA, NCA-2; Network Communication Annunciator

NCM-W, -F; Network Control Module

NCS4-W-ONYX, NCS4-F-ONYX; Network Control Station

NCS5-W-ONYX, NCS5-F-ONYX; Network Control Station

NFS-LBB/NFS-LBBR; Battery Box/Red

NFS-320SYS; Chassis

NFV-25/50, NFV-25/50ZS/ZST; Voice Evacuation Control Panels

NFV-25/50DA, NFV-25/50DAZS; Distributed Audio Panels

ONYXWorks-EW/-NW-/NF/-HNW/-HNMF/-HNSF/-TS/-EW-TS/-NF-TS/-HW-TS/

-HNMFT/-HNSFT/-HNWT; PC workstation for NOTI●FIRE●NET, Wire/Fiber/ with Touch screen monitors

PRN-6; Printer

RKS-S; Remote Security Key Switch

RPT-W, -485W; Repeater Wire

RPT-F; Repeater Fiber

RPT -485FW; Repeater Fiber/Wire

RSA-SCS, RSB-SCS, RSC-SCS, RSD-SCS, RSE-SCS; Smoke Control Station

SBB-A3F; Backbox Assembly

SBB-A4, SBB-A4R, SBB-AA4, SBB-AA4R; Backbox Assembly

SBB-B4, SBB-B4R-L8, SBB-C4, SBB-C4R; Backbox Assembly

SBB-D4, SBB-D4R; Backbox Assembly

*Rev. 10-29-13 gt

July 01, 2017Date Issued: Listing Expires June 30, 2018

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

7165-0028:0243

SCE-8; Smoke Control Expander

SCS-8L; Smoke Control Lamp Driver Station

SCE-8L; Smoke Control Expander Lamp

SCS-8; Smoke Control Station

STS-1; Security Tamper Switch

TM-4; Transmitter Module

TR-A4/-B3N/-B4/-C4/-D3N/-D4; Trim Ring

UDACT, UDACT-2; Universal DACT

UZC-256; Universal Zone Coder

VP-2B; Dress Panel

XP5-C/-M; Transponder Modules

XP6-C; Supervised Control Modules

XP6-MA; Six Zone Interface Modules

XP6-R; Six Relay Control Modules

XP10-M(A); Ten Input Monitor Modules

XPM-8L; Transponder Monitor Modules

The following models are intended for use on NFS2-640 only:

AA-30, -100, -120; Amplifiers

ACT-1, -2, -4, -25, -70; Audio Coupling Transformer

ADDR-B4/-B4R/-C4/-C4R/-D4/-D4R; Door Assemblies

AMG-E; Audio Message Generator

AVL-1; Audio Voice Link

BDA-25V/-70V; Backup Digital Audio Amplifiers

CHS2-M2, CA-1, CA-2; Chassis

CMIC-1, CMIC-RP; Microphone Assembly

DAA-5025/-5070; Digital Audio Amplifiers

DAA-5025F/DAA-5025SF; Digital Audio Amplifiers

DAA-5070F/DAA-5070SF; Digital Audio Amplifiers, Fiber Mode

DAA-75 Series; Digital Audio Amplifiers

DAA-7525, DAA-7525F, DAA-7525SF; Digital Audio Amplifiers

DAA2-5025/-5070/-7525; Digital Audio Amplifiers

DAX-3525/-3570/-5025/-5070; Digital Audio Amplifiers

DS-AMP/E; Digital Series Audio Amplifier

DS-BDA; Digital Series Backup Amplifier

DS-DB; Digital Series Distribution Board

DS-FM, DS-RFM, DS-SFM; Digital Series Fiber Module

DVC; Digital Voice Command

DVC-EM/-EMF/-EMSF; Digital Voice Command Extended Memory Module

DVC-RPU; Remote Paging Unit

FFT-7, -7S; Fire Fighter’s Telephone

FHS; Fireman’s Handset

FPJ; Fireman’s Phone Jack

RM-1, RM-1SA; Remote Microphone

*Rev. 10-29-13 gt

July 01, 2017Date Issued: Listing Expires June 30, 2018

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

7165-0028:0243

TELH-1; Telephone Assembly

XPIQ; Transponder Quad Intelligent Audio

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical ratings, and UL Label

APPROVAL: Listed as fire alarm control units suitable for use in high-rise applications when used in conjunction with separately listed compatible initiating and indicating devices. *Control units may be used with Notifier's First Command NFC-50/100 emergency voice evacuation panals

(CSFM # 6911-0028:0265). This control unit can generate the temporal code pattern fire alarm signal as required per NFPA 72. Refer to manufacturer’s Installation Manual for details.

This control unit meets the requirements of UL Standard 864, 9th

Edition.

NOTE: 1. For Fire Alarm Verification feature (delay of fire alarm signal), the maximum

Retard/Reset/Restart period shall not exceed 30 Seconds.

2. Combined with 7170-028:244

*Rev. 10-29-13 gt

July 01, 2017Date Issued: Listing Expires June 30, 2018

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

DN-6935:D • 12/08/2011 — Page 1 of 2

FSP-851(A) Series Intelligent Plug-In Photoelectric Smoke Detectors with FlashScan®

Intelligent/Addressable Devices

DN-6935:D • H-202

General Notifier FSP-851(A) Series intelligent plug-in smoke detectors with integral communication provide features that surpass con-ventional detectors. Detector sensitivity can be programmed in the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detec-tor’s address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level.

The FSP-851(A) photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-temperature thermal sensing on the FSP- 851T(A). The FSP-851R(A) is a remote test capable detector for use with DNR(A)/DNRW duct detector housings. FSP-851(A) series detectors are compatible with Notifier Onyx and CLIP series Fire Alarm Control Panels (FACPs).

FlashScan® (U.S. Patent 5,539,389) is a communication proto-col developed by Notifier that greatly increases the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices in the group has new information, the panel’s CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of earlier designs.

Features

• Sleek, low-profile design.

• Addressable-analog communication.

• Stable communication technique with noise immunity.

• Low standby current.

• Two-wire SLC connection.

• Compatible with FlashScan® and CLIP protocol systems.

• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on

FlashScan systems).

• Optional remote, single-gang LED accessory.

• Dual LED design provides 360° viewing angle.

• Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan systems only).

• Remote test feature from the panel.

• Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only).

• Built-in functional test switch activated by external magnet.

• Built-in tamper-resistant feature.

• Sealed against back pressure.

• Constructed of off-white fire-resistant plastic, designed to commercial standards, and offers an attractive appearance.

• 94-5V plastic flammability rating.

• SEMS screws for wiring of the separate base.

• Optional relay, isolator, and sounder bases.

Specifications Sensitivity: 0.5% to 2.35% per foot obscuration

Size: 2.1" (5.3 cm) high; base determines diameter.

– B210LP(A): 6.1" (15.5 cm) diameter.

– B501(A): 4.1" (10.4 cm) diameter.

– B200S(A): 6.875" (17.46 cm) diameter.

– B200SR(A): 6.875" (17.46 cm) diameter.

– B224RB(A): 6.2" (15.748 cm) diameter.

– B224BI(A): 6.2" (15.748 cm) diameter.

Shipping Weight: 5.2oz. (147g).

Operating Temperature range: FSP-851(A), 0°C to 49°C (32°F to 120°F). FSP-851T(A), 0°C to 38°C (32°F to 100°F).

Low temperature signal for FSP-851T(A) at 45°F +/- 10°F (7.22°C +/- 5.54°C). FSP-851R(A) installed in a DNR(A)/DNRW, -20°C to 70°C (-4°F to 158°F).

UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/ min.), suitable for installation in ducts.

Relative Humidity: 10%-93% noncondensing.

Thermal Ratings: Fixed-temperature setpoint 135°F (57°C).

DETECTOR SPACING AND APPLICATIONS

FSP-851(A) in B210LP(A) Base B2

-2

1.

jp g

Notifier recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.144m) for ceiling heights 10 feet (3.148m) and higher. For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05-1003, is available at systemsensor.com

ELECTRICAL SPECIFICATIONS

Voltage Range: 15-32 volts DC peak.

Standby Current (max. avg.): 300μA @ 24VDC (one commu-nication every five seconds with LED enabled).

LED Current (max.): 6.5mA @ 24 VDC (“ON”).

Installation FSP-851(A) plug-in detectors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug in and remove detectors without using a ladder.

Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60054.

NOTE: 1) Because of inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring. 2) When using relay or sounder bases, consult the ISO-X(A) installation

Page 2 of 2 — DN-6935:D • 12/08/2011

-Notifier® and FlashScan® are registered trademarks of Honeywell International Inc.

©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

sheet I56-1380 for device limitations between isolator modules and isolator bases.

Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

• UL Listed: S1115.

• ULC Listed: S1115 (FSP-851A, FSP-851RA, FSP-851TA).

• MEA Listed: 225-02-E .

• FM Approved.

• CSFM: 7272-0028:0206 .

• Maryland State Fire Marshal: Permit # 2122 .

• BSMI: CI313066760036.

• CCCF: Certif. # 2004081801000017 (FSP-851T)

Certif. # 2004081801000016 (FSP-851).

• U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0

(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).

• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-

320C, excluding B210LP(A)).

Product Line Information NOTE: “A” suffix indicates ULC Listed model.

FSP-851: Low-profile intelligent photoelectric sensor. Must be mounted to one of the bases listed below.

FSP-851A: Same as FSP-851 but with ULC listing.

FSP-851T: Same as FSP-851 but includes a built-in 135°F (57°C) fixed-temperature thermal device.

FSP-851TA: Same as FSP-851T but with ULC listing.

FSP-851R: Low-profile intelligent photoelectric sensor, remote test capable. For use with DNRA/DNRW.

FSP-851RA: Same as FSP-851R but with ULC listing. For use with DNRA.

INTELLIGENT BASES

NOTE: “A” suffix indicates ULC Listed model.

NOTE: For details on intelligent bases, see DN-60054.

B210LP(A): Standard U.S. flanged low-profile mounting base.

B210LPBP: Bulk pack of B210LP; package contains 10.

B501(A): Standard European flangeless mounting base.

B501BP: Bulk pack of B501; package contains 10.

B200S(A): Intelligent, programmable sounder base capable of producing sound output in high or low volume with ANSI Tempo-ral 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone.

B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone.

Replaces B501BH series bases in retrofit applications.

B224RB(A): Plug-in System Sensor relay base. Screw termi-nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.

B224BI(A): Plug-in System Sensor isolator detector base.

Maximum 25 devices between isolator bases .

ACCESSORIES

F110: Retrofit flange to convert B210LP(A) to match the B710LP(A) profile, or to convert older high-profile bases to low-profile.

F110BP: Bulk pack of F110; package contains 15.

F210: Replacement flange for B210LP(A) base.

RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and B210LP(A) bases only.

SMB600: Surface mounting kit

M02-04-00:Test magnet.

M02-09-00: Test magnet with telescoping handle.

XR2B: Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applications.

XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections.

T55-127-010: Detector removal tool without pole.

BCK-200B: Black detector covers for use with FSP-851(A) only;

box of 10.

WCK-200B: White detector covers for use with FSP-851(A) only; box of 10.

LISTING No. 7272-0028:0206 Page 1 of 1

CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC

LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653

Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309

Email: vladimir.kireyev@honeywell.com

DESIGN: Models FSP-751, HPX-751, FSP-751T, FSH-751, FAPT-751, FAPT-851, FSP-851, FSP-851R* and FSP-851T photoelectric type smoke detectors. Models FSP-751T and

FSP-851T employ a 135°F supplement integral heat sensor which only assists in a fire situation. This thermal circuitry is NOT approved for use in lieu of a required heat detector.

Refer to listee's data sheet for additional detailed product description and operational considerations.

RATING: 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, product number, electrical rating and UL label.

APPROVAL: Listed as photoelectric type smoke detector for use with listee's separately listed compatible base and fire alarm control units. Models FSP-751, FSP-751T, FAPT-751, FAPT-851, FSP-851, FSP-851R*, FSP-851T are suitable for open areas and inside duct installation with air velocities between 0-4000 fpm. Model HPX-751 is suitable for open areas with air velocities between 0-300 fpm. Model FSH-751 is suitable for open areas with air velocity between 0-4000 fpm.

NOTE: Combined with 7272-0028:208

The photoelectric type detectors are generally more effective at detecting slow, smoldering fires that smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires that consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen.

*Rev. 01-07-2009 fm

July 01, 2017Date Issued: Listing Expires June 30, 2018

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

DN-6936:B • 12/07/2011 — Page 1 of 2

FST-851(A) Series Intelligent Thermal (Heat) Detectors with FlashScan®

Intelligent / Addressable Devices

DN-6936:B • H-211

General Notifier FST-851(A) Series intelligent…