B08_Attachment_2_Site_Drawings_and_Unit_Details.pdf
PDF 546 KB Posted
- Attached to
- FY25 SEED WAREHOUSE Federal contract opportunity
- Solicitation number
- 140PS125Q0019
About this file
The file contains detailed site drawings and specifications for a seed storage unit concrete pad at Wind Cave National Park in Hot Springs, South Dakota. The technical drawings from Polar King International depict a refrigeration unit with specific dimensions of 62'-7" x 13'-11" x 8'-5 1/4", featuring a crowned roof, LED lighting, and multiple refrigeration and heating components. The plan and elevation views outline a storage unit with 4" walls, a 60" door, vinyl strip curtain, and electrical specifications including 47.5 MCA conductors and a 120V outlet. The accompanying location map shows the unit's proximity to other regional landmarks like Mount Rushmore and Jewel Cave, with a note that the actual placement will be determined after contract award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140PS125Q0019_Amd_0002.pdf | ||
| E_Panel_Pictures_0002.zip | ZIP file | |
| Sol_140PS125Q0019_Amd_0001.pdf | ||
| Sol_140PS125Q0019.pdf | ||
| B08_Attachment_5_Solicitation_-_Notice_to_Contractors.pdf | ||
| B08_Attachment_3_Bid_Schedule_-_Seed_Storage_Concrete_Pad_Final.xlsx | XLSX spreadsheet | |
| B08_Attachment_7_Solicitation_-_Construction_Contract_Administration.pdf | ||
| B08_Attachment_1_SOW_WICA_Seed_Storage_Concrete_Pad_and_Electrical.pdf | ||
| B08_Attachment_9_WH347.pdf | ||
| B08_Attachment_4_B03_Davis-Bacon_Act_WD___SD20250022_1-3-2025_Rev_0.pdf | ||
| B08_Attachment_8_Transmittal-Submittal_Form.pdf | ||
| B08_Attachment_6_Solicitation_-_Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| B08_Attachment_10_SF_25A_-_Payment_Bond_Form.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Wind Cave (WICA) National Park Seed Storage Unit Concrete Pad
CONTRACT BID NOTES
1. Drawings are for information purposes only. Actual placement TBD after contract award.
ELEVATION VIEW
PLAN VIEW
DRAWING APPROVAL
National Park Service
Hot Springs, SD
AutoCAD SHX Text THE REFRIGERATION SYSTEM SHOWN IS DESIGNED TO MAINTAIN INDICATED TEMPERATURE IF PRODUCT ENTERS WITHIN 10°F. REFRIGERATION DESIGN IS SUBJECT TO CHANGE FOR IMPROVEMENTS. ALL DIMENSIONS ARE NOMINAL. FINAL DIMENSIONS WILL BE ±1 INCH OF DRAWING. CONTACT YOUR SALES REP IF INCOMING PRODUCT WILL BE ENTERING AT HIGHER TEMPERATURES, IN LARGE QUANTITIES, OR IF TIGHTER TOLERANCES ARE REQUIRED.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
BY:
AutoCAD SHX Text PLEASE INDICATE YOUR APPROVAL OF THIS DESIGN BY SIGNING BELOW. (DIMENSIONS, DOOR LOCATION/SWING, ELECTRICAL REQS., ETC.)
AutoCAD SHX Text 4" WALLS 6" CROWNED ROOF CART DUTY FLOOR 8'-0" INTERIOR HEIGHT 3" FRAME 4' LED LIGHTING VINYL STRIP CURTAIN - 60" DOOR SPRING HINGES - 36" DOOR (2) INTERIOR RAMP INTERIOR RAMP DESICCANT DEHUMIDIFIER SHELF MOUNT REFRIGERATION FREEZE PROTECTION (1) 120V OUTLET BY DOOR
AutoCAD SHX Text
HORSEPOWER:
AutoCAD SHX Text
REFRIGERANT:
AutoCAD SHX Text
VOLTAGE:
AutoCAD SHX Text
AMPERAGE:
AutoCAD SHX Text
CONDUCTORS:
AutoCAD SHX Text
PHASE:
AutoCAD SHX Text
ROOM TEMP.:
AutoCAD SHX Text
INTERIOR AREA:
AutoCAD SHX Text 45%%dF
AutoCAD SHX Text 785 sq. ft.
AutoCAD SHX Text
2.5 hp.
AutoCAD SHX Text R-404A
AutoCAD SHX Text 208-230
AutoCAD SHX Text Single
AutoCAD SHX Text
AutoCAD SHX Text
47.5 MCA
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
MODEL:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWING NAME:
AutoCAD SHX Text
FORT WAYNE, INDIANA
AutoCAD SHX Text 1-800-752-7178
AutoCAD SHX Text National Park Service H1460 Hot Springs SD
AutoCAD SHX Text
BJS
AutoCAD SHX Text H1460
AutoCAD SHX Text 1/8" = 1'
AutoCAD SHX Text 5/5/25
AutoCAD SHX Text
XFAM-025Z-CFV-081
AutoCAD SHX Text
SHIPPING DIMENSIONS: 62'-7" X 13'-11" X 9'-5 1/4"9'-5 1/4"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 8 "18"
AutoCAD SHX Text 9'-5 "14"
AutoCAD SHX Text 59'-3"
AutoCAD SHX Text 13'-3"
AutoCAD SHX Text 59'-11"
AutoCAD SHX Text 13'-11"
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text 57"
AutoCAD SHX Text 60" x 79" x 79"
AutoCAD SHX Text 6'-11"
AutoCAD SHX Text 62'-2 "12"
AutoCAD SHX Text
ROOF CROWN
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
LED LIGHT
AutoCAD SHX Text
RM6A-276
AutoCAD SHX Text 35%%dF
AutoCAD SHX Text 5'-0 "18"
AutoCAD SHX Text REFRIGERATION SETPOINTS: ON AT 47°F, OFF AT 43°F HEATING SETPOINTS: ON AT 40°F, OFF AT 43°F
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text 33"
AutoCAD SHX Text 36" x 79" x 79"
AutoCAD SHX Text 29'-11 "12"
File details come from the government source that posted it. Updated .