B08_Attachment_2_-_Drawings.pdf
PDF 7 MB Posted
- Attached to
- BOST - REPLACE CONNECTOR ROOF Federal contract opportunity
- Solicitation number
- 140P4324R0030
About this file
This document appears to be a set of construction drawings and technical specifications for the replacement of the USS Constitution Museum Connector Roof at the Boston National Historic Park in Charlestown, Massachusetts. The key details include:
The project involves the demolition of the existing 4-ply built-up roof system with ballast and tapered insulation, and the installation of a new fully adhered EPDM roof membrane system with tapered insulation over the existing 3/4" plywood deck. Work also includes the replacement of roof-mounted equipment, flashing, and accessories. The solicitation number is 140P4324R0030, and the project is being procured by the Department of the Interior National Park Service Northeast Region. The drawings provide construction details for the roof system, flashing, and roof accessories.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Question_Responses__0002.pdf | ||
| Sol_140P4324R0030_Amd_0002.pdf | ||
| Sol_140P4324R0030_Amd_0001.pdf | ||
| Attachment_4_-_Temporary_Parking_Request_0001.pdf | ||
| Sol_140P4324R0030.pdf | ||
| Provisions_Clauses.pdf | ||
| B08_Attachment_3_-_WD_MA20240001_docx.pdf | ||
| B08_Attachment_1_-_Scope_of_Work.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SheetMark REVISION Date Initial QUALITY DESIGN CERTIFICATION Prepared in Accordance with Design Development (Title I)
OR
Variance from Design Development (Title I) Approved by Superintendent on
OR
Construction Drawing Not Preceded By Design Development (Title I)
Date
Date
Project Manager Date
BOSTON NATIONAL HISTORIC PARK
SUFFOLK MASSACHUSETTSNORTH ATLANTIC
CHARLESTOWN NAVY YARD
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
STATEREGION COUNTY
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF PROJECT DRAWING NO.
PMIS/PKG NO.
SHEET
UNITED STATES
DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
OF
BOST 256859
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111
MASSACHUSETTS
BOSTON NATIONAL HISTORICAL PARK
179756
6/ 9/
:4
0:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
BID SET
06/10/2022
SHEET INDEX
SHEET SUB SHEET TITLE OF SHEET
1 G-001 COVER SHEET
2 G-002 GENERAL NOTES, SYMBOLS & ABBREVIATIONS
3 AD-101 ROOF DEMOLITION PLAN AND NOTES
4 A-101 ROOF PLAN
5 A-501 ROOF DETALS
6 A-502 EPDM ROOFING DETAILS
7 A-503 EPDM ROOFING DETAILS
PROJECT
LOCATION
1 7
X
X-XXX
TYP
DETAIL NUMBER
EXTERIOR ELEVATION
xx 1/8" = 1'-0" View Name
1/8" = 1'-0" View Namexx
X-XXXX
NORTH ARROW
SHEET NUMBER
VIEW NAME
VIEW SCALE
INDICATES PLAN NORTH
VIEW NUMBER
VIEW NAME
INDICATES TRUE NORTH
VIEW SCALE
VIEW NUMBER
A101
SIM
VIEW NUMBER
SHEET NUMBER
TYPICAL VIEW TITLE
DETAIL VIEW TITLE
DETAIL SECTION
A101
SIM
VIEW NUMBER
SHEET NUMBER
BUILDING SECTION
REFERENCE LABEL
(WHERE INDICATED)
INDICATES ELEVATION
TYPICAL CONDITION
INDICATES THE CONDITION IS
SIMILAR TO THE REFERRING
DETAIL
NAME
ELEVATION
SHEET NUMBER
LEVEL MARKER
SPOT ELEVATION
KEYED NOTE TAG
STRUCTURAL GRID
LEVEL ELEVATION
LEVEL NAME
XX'-X"
KEYED NOTE VALUE
GENERAL CONSTRUCTION NOTES:
'ALIGN' MEANS TO ACCURATELY LOCATE FINISHED FACES IN SAME PLANE.
DIMENSIONS ARE TO FACE OF CMU OR G.W.B. FINISH UNLESS NOTED
OTHERWISE.
CONTRACTOR SHALL INVESTIGATE JOB SITE TO COMPARE CONTRACT
DOCUMENTS AND EXISTING CONDITIONS. INCLUDE COST FOR ALL
WORK DESCRIBED IN CONTRACT DOCUMENTS AND REQUIRED OR
IMPLIED BY EXISTING CONDITIONS. NOTIFY
CONTRACTING OFFICER OF ANY CONFLICTS BETWEEN EXISTING
CONDITIONS AND NEW WORK, OMISSIONS OR CONFLICTS IN THE
DRAWINGS AND ANY RESTRICTIONS RELATED TO THE EXECUTION OF
THE WORK.
CONTRACTOR SHALL FULLY ACQUAINT THEMSELF WITH THE
CONDITIONS OF THE CONTRACT, LOCAL CONDITIONS RELATING TO
LOCATION, ACCESSIBILITY AND GENERAL CHARACTER OF THE
CONSTRUCTION SITE AND LOCAL LABOR CONDITIONS SO THAT THEY
UNDERSTAND THE NATURE, EXTENT, DIFFICULTIES, AND RESTRICTIONS
RELATED TO THE EXECUTION OF WORK. NOTIFY CONTRACTING OFFICER
OF ALL DISCREPANCIES PRIOR TO COMMENCING WORK.
CONTRACTOR SHALL PROVIDE, AND PAY FOR ALL MATERIALS,
LABOR, EQUIPMENT, TOOLS, CONSTRUCTION EQUIPMENT,
WAREHOUSING, TRANSPORTATION AND DELIVER COSTS, HOISTING,
REMOVAL OF TRASH AND DEBRIS, AND OTHER FACILITIES AND
SERVICES NECESSARY FOR THE EXECUTION AND COMPLETION OF
THE WORK.
ALL WORK SHALL BE PERFORMED BY THE GENERAL CONTRACTOR
UNLESS OTHERWISE NOTED. ALL REFERENCES TO THE
"CONTRACTOR" INCLUDE THE GENERAL CONTRACTOR AND THE
SUBCONTRACTORS.
1.
2.
4.
5.
6.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR, AND HAVE
CONTROL OVER, ALL CONSTRUCTION MEANS, TECHNIQUES,
SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL
PORTIONS OF THE WORK REQUIRED BY THE CONTRACT
DOCUMENTS.
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ACTS
AND OMISSIONS OF THE CONTRACTOR'S EMPLOYEES,
SUBCONTRACTORS AND THEIR AGENTS AND EMPLOYEES, AND
ANY OTHER PERSONS PERFORMING ANY OF THE WORK UNDER A
CONTRACT WITH A CONTRACTOR.
OTHER CONTRACTORS AND THEIR SUBCONTRACTORS MAY BE
WORKING ON THE PREMISES SIMULTANEOUS WITH THE DURATION
OF THIS CONTRACT. NO ACTION SHALL BE TAKEN ON THE PART OF
THIS CONTRACTOR OR ANY SUBCONTRACTOR TO IMPEDE THE
ACCESS OR OPERATION OF ANY OTHER CONTRACTOR ON THE
PREMISES.
CONTRACTOR SHALL ISSUE COMPLETE SETS OF THE CONTRACT
DOCUMENTS TO EACH OF THE SUBCONTRACTORS FOR COORDINATION OF
THEIR WORK AND DESCRIPTION OF SCOPE. COORDINATE ALL DEMOLITION
AND CONSTRUCTION WITH OTHER TRADES.
CONTRACTOR SHALL COMPLY AND COORDINATE ALL WORK WITH THE
GOVERNMENT REPRESENTATIVE REGARDING HEAT, WATER, ELECTRICITY,
DELIVERIES, ACCESS, EXTERIOR STORAGE AVAILABILITY, NOISE CONTROL,
TRASH AND DEBRIS REMOVAL, HOISTING, AND ANY OTHER UTILITIES OR
OWNER'S RULES AND REGULATIONS CONCERNING THE PROJECT SITE.
7.
8.
9.
10.
11.
12.
CONTRACTOR SHALL PROCURE MATERIALS SO AS NOT TO DELAY
SUBSTANTIAL COMPLETION. NOTIFY CONTRACTING OFFICER WITHIN 5
DAYS OF EXECUTION OF CONTRACT OF ANY MATERIAL DELIVERY WHICH
COULD DELAY COMPLETION OF CONTRACT.
CONTRACTOR SHALL COORDINATE SCHEDULING, PROVISIONS FOR
INSTALLATION, LOCATIONS AND THE ACTUAL INSTALLATION OF
ITEMS FURNISHED BY GOVERNMENT OR BY OTHERS.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD.
CONTRACT DRAWINGS ARE NOT INTENDED TO REPRESENT EXACT
DIMENSIONS. FIELD DIMENSIONS ARE THE RESPONSIBILITY OF THIS
CONTRACTOR FOR ALL PHASES INCLUDING
BIDDING, FABRICATION, COORDINATION AND CONSTRUCTION.
DO NOT SCALE DRAWINGS: WRITTEN DIMENSIONS GOVERN.
16.
15.
14.
13.
17.
CHANGES IN DRAWINGS OR ACTUAL WORK SHALL BE ISSUED BY THE
CONTRACTING OFFICER.
CONTRACTOR SHALL EXAMINE ALL SURFACES TO DETERMINE THAT THEY
ARE SOUND, DRY, CLEAN AND READY TO RECEIVE FINISHES PRIOR TO
INSTALLATION. START OF INSTALLATION SHALL IMPLY ACCEPTANCE OF
SUBSTRATE AND SHALL NOT BE GROUNDS FOR CLAIMS AGAINST
IMPROPER PERFORMANCE OF INSTALLED MATERIALS.
18.
PERFORM ALL WORK AND INSTALL MATERIALS IN STRICT
ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND
INSTRUCTIONS AND IN A MANNER CONSISTENT WITH INDUSTRY
STANDARD OF WORKMANSHIP.
WORK DAMAGED DURING CONSTRUCTION OR NOT CONFORMING
TO SPECIFIED STANDARDS, TOLERANCES OR MANUFACTURER'S
INSTRUCTIONS FOR INSTALLATION SHALL BE REPLACED, BY THE
CONTRACTOR, AT NO ADDITIONAL CHARGE TO THE OWNER.
23.
24.
25.
26.
27.
29.
30.
CONTRACTOR TO REMOVE ANY STRAY PAINT, DIRT, OR STAINS
INCURRED DURING THE CONSTRUCTION PROCESS. CONTRACTOR SHALL
BE RESPONSIBLE FOR REMOVING ALL TEMPORARY EQUIPMENT
COVERINGS USED DURING CONSTRUCTION AND HE SHALL ALSO BE
RESPONSIBLE FOR REMOVING HIS TRASH OFF OF THE JOB SITE DAILY.
28.
THE CONTRACTOR SHALL PERFORM ALL CUTTING & WELDING IN
COMPLIANCE WITH THE PUBLISHED STANDARDS OF N.F.P.A. THE
CONTRACTOR SHALL PROVIDE FIRE WATCHES FOR ALL CUTTING,
GRINDING, AND WELDING OPERATIONS. THE TRAINING OF THESE FIRE
WATCHES AND THE USE OF THE CONTRACTOR'S SUPPLIED FIRE
EXTINGUISHERS IS THE RESPONSIBILITY OF THE CONTRACTOR.
ANY STRUCTURAL MATERIAL NOT SHOWN ON THE DRAWINGS IS TO BE
FURNISHED BY THE GENERAL CONTRACTOR.
ANY AREA OUTSIDE THE LIMITS OF CONSTRUCTION DISTURBED BY
OPERATIONS OF THE CONTRACTOR SHALL BE RESTORED AT THE
CONTRACTORS EXPENSE.
WHEREVER A FOAM BACKER ROD AND SEALANT ARE USED, THE
SEALANT AND BACKER ROD MUST BE COMPATIBLE WITH EACH OTHER.
USE A SIZE BACKER ROD THAT COMPRESSES 25% WHEN INSERTED
INTO THE JOINT. (TYPICAL ALL JOINTS)
19.
20.
SUBSTANTIAL COMPLETION SHALL BE THE DATE ON WHICH THE ROOF
IS TURNED OVER FROM THE CONTRACTOR TO THE NATIONAL PARK
SERVICE. ADDITIONAL TOUCH-UP OR MINOR INSTALLATION WORK MAY
BE INCOMPLETE.
CONTRACTOR SHALL PROVIDE A WARRANTY TO THE OWNER THAT ALL
MATERIALS, AND EQUIP. FURNISHED AND INSTALLED UNDER THIS
CONTRACT SHALL BE NEW, UNLESS OTHERWISE SPECIFIED, AND THAT ALL
WORK SHALL BE OF GOOD QUALITY, FREE FROM FAULTS AND DEFECTS
AND SHALL CONFORM TO THE CONTRACT DOCUMENTS.
22.
21.
FOR A PERIOD OF ONE YEAR BEGINNING AT THE DATE OF SUBSTANTIAL
COMPLETION, CONTRACTOR SHALL PROMPTLY CORRECT WORK FOUND
NOT TO BE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
CONTRACTOR SHALL BEAR ALL COST OF CORRECTIONS.
31.
AUTHORITY OF ARCHITECT/ ENGINEER WILL BE DELEGATED FROM NPS
CONTRACTING OFFICER (CO).
ALL FIELD COMMUNICATIONS FROM CONTRACTOR MUST BE SUBMITTED
TO THE CO.
ALL FIELD APPROVALS MUST BE ISSUED TO THE CONTRACTOR
THROUGH THE CO OR CONTRACTING OFFICER'S REP (COR).
3.
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111 OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO. DRAWING NO.
SHEET
TITLE OF SHEET
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
BOSTON NATIONAL HISTORIC PARK
DRAWN:
179756
6/ 7/
:1
1:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
GENERAL NOTES,
SYMBOLS &
ABBREVIATIONS
G-002
EJB
EJB
JPD
06/10/2022
SYMBOLS LEGEND
ABA ARCHITECTURAL BARRIERS ACT
ABO ADDITIVE BID OPTION
ACC ACCESSORY
AD AREA DRAIN
ADD ADDENDUM
ADJ ADJACENT
AFF ABOVE FLOOR FINISH
AGGR AGGREGATE
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
APPRO
X
APPROXIMATE
ARCH ARCHITECTURAL
BD BOARD
BG BUMPER GUARD
BL BUILDING LINE
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BSMT BASEMENT
BU ROD BACK UP ROD
BUR BUILT-UP ROOF
C TO C CENTER TO CENTER
CBB CONCRETE BACKER BOARD
CEM CEMENT
CER CERAMIC
CF CUBIC FOOT
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CG CORNER GUARD
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CONRTACTING OFFICER
COL COLUMN
COMM COMMUNICATIONS
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATE
COR CONRACTING OFFICER'S
REPRESENTATIVE
CT CERAMIC TILE
CTR CENTER
CW CURTAIN WALL
D DEPTH
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DS DOWN SPOUT
DTL DETAIL
DWG DRAWING
DWGS DRAWINGS
DWLS DOWELS
EA EACH
EIFS EXTERIOR INSULATION FINISH
SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
EQUIP EQUIPMENT
ESC ESCALATOR
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXP
BOLT
EXPANSION BOLT
EXT EXTERIOR
FA FIRE ALARM
FAU FORCED AIR UNIT
FD FLOOR DRAIN
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FHC FIRE HOSE CABINET
FIN FINISH
FIXT FIXTURE
FLASH FLASHING
FLOUR FLOURESCENT
FLR FLOOR
FO FACE OF
FR FIRE RESISTIVE
FT FEET
FTG FOOTING
FVC FIRE VALVE CABINET
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GFRC GLASS FIBER REINFORCED
CONCRETE
GI GALVANIZED IRON
GL GLASS
GND GROUND
GR GRADE
GRG GLASS REINFORCED GYPSUM
GYP GYPSUM
GYP BD GYPSUM BOARD
H HIGH
HB HOSE BIB
HC HOLLOW CORE
HD HEAD
HDW HARDWARE
HM HOLLOW METAL
HOR HORIZONTAL
HP HIGH POINT
HR HOUR
HT HEIGHT
HTR HEATER
ID INSIDE DIAMETER
IN INCH
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
K KIPS (1,000 LB)
KO KNOCK OUT
KP KICK PLATE
KS KNEE SPACE
KSF KIPS PER SQUARE FOOT
L ANGLE
LAM LAMINATE
LAV LAVITORY
LB POUND (WIEGHT)
LF LINEAL FOOT
LG LONG
LIN LINEAR, LINEAL
LL LIVE LOAD
LOC LOCATION
LP LOW POINT
LT LIGHT
LWC LIGHT WEIGHT CONCRETE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFIED
MOD
BIT
MODIFIED BITUMEN
MSL MEAN SEA LEVEL
MTD MOUNTED
MTL METAL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
O TO O OUTSIDE TO OUTSIDE
OA OVERALL
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED, OWNER
INSTALLED
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OTS OPEN TO STRUCTURE
OVHD OVERHEAD
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PD PLANTER DRAIN
PERF PERFORATED
PLAM PLASTIC LAMINATE
PLUMB PLUMBING
PLYWD PLYWOOD
PNL PANEL
PNT PAINT
POL POLISHED
POLYIS
O
POLYISOCYANURATE
PORT
CEM
PORTLAND CEMENT
PR PAIR
PREFA
B
PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PTD PAINTED
R RISER, REFRIGERATOR
RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REBAR REINFORCING BAR
RECP RECEPTABLE
REF REFER OR REFERENCE
REINF REINFORCING
RELOC RELOCATED
REQD REQUIRED
RFVC RECESSED FIRE VALVE CABINET
RM ROOM
RO ROUGH OPENING
RWL RAIN WATER LEADER
SAB SOUND ATTENUATION BLANKET
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SED STANDARD EMBASSY DESIGN
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SP STAND PIPE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STA STATION
STC SOUND TRANSMISSION CLASS
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
T&B TOP AND BOTTOM
TC TOP OF CURB
TEL TELEPHONE
TEMP TEMPERATURE
THK THICK
THOLD THRESHOLD
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOP TOP OF PARAPET
TOS TOP OF SLAB
TOSHP TOP OF STEEL HIGH POINT
TOSLP TOP OF STEEL LOW POINT
TOSMP TOP OF STEEL MIDPOINT
TOSTL TOP OF STEEL
TS TUBE STEEL
TW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VENDING
VAR VARIES
VCT VINYL COMPOSITE TILE
VET VERTICAL
VWC VINYL WALL COVERING
W WIDTH
W/ WITH
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WH WATER HEATER
WL WIND LOAD
WP WATERPROOFING
WR WATER RESISTANT
WT WEIGHT
WWF WELDED WIRE FABRIC
ABBREVIATIONS
2 7
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ADHERE TO THE
FOLLOWING:
1. ERECT AND MAINTAIN TEMPORARY STAGING, LIGHTS, BARRICADES, WARNING
SIGNS, AND GUARDS NECESSARY TO PROTECT BUILDING OCCUPANTS, AND
ADJOINING TENANTS FROM INJURY, AND/OR DAMAGE, ALL IN ACCORDANCE WITH
APPLICABLE CODES AND REGULATIONS.
2. DO NOT CLOSE OR OBSTRUCT THE PATH OF EGRESS, CORRIDORS, OR OTHER
OCCUPIED OR USED SPACES. UTILITY INTERRUPTIONS REQUIRE COORDINATION
WITH THE OWNER AND A MINIMUM 15 CALENDAR DAY ADVANCE NOTICE TO THE
OWNER. IF NECESSARY PROVIDE TEMPORARY UTILITIES.
3. PRIOR TO OBSTRUCTION OF EGRESS PATHS OR IMPAIRMENT OF FIRE/LIFE
SAFETY COMPONENTS, THE NFPA 241 AND IMPAIRMENTS PLANS MUST BE
SUBMITTED FOR APPROVAL BY DESIGN TEAM FIRE PROTECTION ENGINEER WHO
IS LICENSED PROFESSIONAL ENGINEER (IN FIRE PROTECTION ENGINEERING)
(DTFPEPE).
4. CEASE OPERATION IF PUBLIC SAFETY OR REMAINING STRUCTURES ARE
ENDANGERED. PERFORM TEMPORARY CORRECTIVE MEASURES UNTIL
OPERATIONS CAN BE CONTINUED PROPERLY.
5. IN COMPANY OF THE CONTRACTING OFFICER, THE CONTRACTOR WILL VISIT THE
SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE DEMOLITION
REQUIRED PRIOR TO STARTING THE WORK. CAREFULLY IDENTIFY THE LIMITS OF
SELECTIVE DEMOLITION. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE
THE WORKMEN TO ALSO IDENTIFY THE ITEMS TO BE REMOVED AND STORED, AS
WELL AS THE ITEMS TO BE LEFT IN PLACE INTACT.
6. USE MEANS NECESSARY TO PREVENT DUST FROM BECOMING A NUISANCE TO
OTHER TENANTS OF THE BUILDING, THE PUBLIC, NEIGHBORING BUILDINGS, AND
TO ANY OTHER WORK BEING PERFORMED.
7. EXECUTE DEMOLITION WORK TO ENSURE THE SAFETY OF PERSONS AND
ADJACENT PROPERTY AGAINST DAMAGE BY DEBRIS. CONTRACTOR WILL TAKE
PROTECTIVE MEASURES TO PREVENT DUST FROM GETTING INTO DUCTS.
8. IN THE EVENT OF DEMOLITION OF ITEMS NOT SO SCHEDULED TO BE
DEMOLISHED, PROMPTLY REPLACE SUCH ITEMS TO THE APPROVAL OF THE
CONTRACTING OFFICER AT NO ADDITIONAL COST TO THE OWNER. IT SHALL BE
THE CONTRACTORS RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO
EXISTING FEATURES AS A RESULT OF THIS WORK. DAMAGED ITEMS SHALL BE
REPLACED IN KIND AND AT NO ADDITIONAL COST TO THE OWNER.
9. COORDINATE THE DISCONNECT, REMOVAL AND RE-INSTALLATION OF ALL
EXISTING ELECTRICAL AND MECHANICAL EQUIPMENT
10. IF FOUND, THE CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF ANY
HAZARDOUS MATERIALS AND IN DOING SO SHALL COMPLY WITH ALL APPLICABLE
OSHA REGULATIONS AND ALL OTHER FEDERAL, STATE AND LOCAL GUIDELINES
REGARDING LEAD-CONTAINING MATERIAL REMOVAL AND DISPOSAL.
11. THE GOVERNMENT AND DESIGN PROFESSIONALS SHALL NOT BE HELD
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES,
SEQUENCES OR PROCEDURES FOR SAFETY PRECAUTIONS OR FOR THE
CONTRACTORS FAILURE TO CARRY OUT THE WORK IN STRICT ACCORDANCE
WITH THE CONSTRUCTION DOCUMENTS. OWNER SHALL NOT BE RESPONSIBLE
FOR ERRORS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR
THEIR AGENTS OR EMPLOYEES OR ANY OTHER PERSONS PERFORMING ANY OF
THE WORK.
12. SUBMIT DEMOLITION SCHEDULE FOR APPROVAL INCLUDING SCHEDULE AND
METHODS OF CAPPING AND CONTINUING UTILITY SERVICE.
DEMOLITION NOTES
BLDG 28
BLDG 22
SUBSTATION
5 5 5 5 5
5 5 5 5 5 5 5 5
7 7
AD-101 3
AD-101 2
AD-1014
AD-1017
AD-101
AD-101
LEGEND
EXTENT OF DEMOLITION
BUILDING 22
SUBSTATION
MUSEUM CONNECTOR
BU
IL
D
IN
G
KEY PLAN
EXISTING MONITOR ROOF NOT IN CONTRACT
REMOVE 4-PLY BUILT-UP ROOF SYSTEM WITH BALLAST AND TAPERED ROOF
INSULATION. 3/4" PLYWOOD DECK TO REMAIN. PREPARE SURFACE FOR NEW
MEMBRANE ROOF SYSTEM. DISCONNECT, REMOVE AND SAFELY STORE ALL HEAT
TRACE CABLE TO BE REINSTALLED.
REMOVE COPPER FLASHING AND ALL UPTURNED ASPHALT FLASHING MATERIAL,
COORDINATE WITH MASONRY REPAIRS, PMIS No. BOST325372
REMOVE COPPER FLASHING AND ALL UPTURNED ASPHALT FLASHING MATERIAL
REMOVE BREATHER VENT, PREPARE OPENING FOR NEW VENT
REMOVE DOME COVER OF ROOF DRAIN. MAINTAIN OUTLET BOWL, CLAMP RING AND
FIXING BOLTS. PROTECT EXISTING 3" DRAIN PIPE FROM DEMOLITION DEBRIS
REMOVE COPPER PARAPET CAP FLASHING AND ALL UPTURNED ASPHALT FLASHING
MATERIAL
REMOVE COPPER OVERFLOW SCUPPER
REMOVE BUILT-UP ROOF MATERIAL FROM UNDER MONITOR WINDOW WALLS.
PRESERVE EXISTING COPPER FLASHING AT BASE OF WINDOW WALL. PREPARE
SURFACE FOR NEW ROOFING SYSTEM.
MAKE SAFE, DISCONNECT AND REMOVE ROOF MOUNTED CONDENSING UNIT. SAFELY
STORE IN LOCATION TO BE DETERMINED BY THE NPS.
DEMOLITION KEY NOTES
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111 OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO. DRAWING NO.
SHEET
TITLE OF SHEET
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
BOSTON NATIONAL HISTORIC PARK
DRAWN:
179756
6/ 7/
:3
2:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
ROOF DEMOLITION PLAN
AND NOTESAD-101
EJB
EJB
JPD
06/10/2022
3/16" = 1'-0"1 DEMOLITION ROOF PLAN
NTS3 BUILDING 28 FLASHING
NTS2 ROOF LOOKING EAST
NTS4 ROOF LOOKING WEST NTS5 NORTH WEST CORNER
NTS6 NORTH SCUPPER
NTS7 CONDENSING UNITS
3 7
PLAN NORTH
BLDG 28
BLDG 22
SUBSTATION
BUILDING 22
SUBSTATION
MUSEUM CONNECTOR
BU
IL
D
IN
G
KEY PLAN
A-501
A-501
A-501
A-501
10 10 10101010
10 10 10 10 10 10 10 10
A-501
TYP
A-501
TYP
A-501
A-501
A-501
A-501
1/4"/12", MIN.
TYPICAL
TYP
ROOF PLAN KEY NOTES
FULLY ADHERED EPDM ROOF WITH TAPERED INSULATION
MONITOR ROOF, NOT IN CONTRACT
GRANITE WALL
GRANITE WALL WITH CURB
BRICK WALL
BRICK WALL WITH CURB
PARAPET WITH COPPER COPING
COPPER OVERFLOW SCUPPER
COPPER OVERFLOW SCUPPER, CONNECT TO DOWNSPOUT
ROOF DRAIN
ROOF BREATHER VENT
REINSTALLED EXISTING CONDENSING UNITS
WALK PADS, COORDINATE LOCATIONS WITH USER
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111 OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO. DRAWING NO.
SHEET
TITLE OF SHEET
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
BOSTON NATIONAL HISTORIC PARK
DRAWN:
179756
6/ 7/
:1
0:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
ROOF PLAN
A-101
EJB
EJB
JPD
06/10/2022
1/4" = 1'-0"1 ROOF PLAN
SCALE IN FEET - 1/4" = 1'-0"
4' 2' 0' 4' 12'8'
PLAN NORTH
4 7
TERMINATION PER ROOFING
MANUFACTURER INSTRUCTION
EXISTING STRUCTURE
TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE
COPPER FLASHING AND REGLET
COPPER FLASHING SLOPED TO ROOF
CONTINUOUS SEALANT OVER
BACKER ROD
S.S. DRIVE PINS
WITH NYLON
SLEEVES, 6" O.C.
A-501
TERMINATION PER ROOFING
MANUFACTURER INSTRUCTION
EXISTING STRUCTURE
TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE
COPPER FLASHING AND REGLET
CONTINUOUS BACKER ROD
AND SEALANT
S.S. DRIVE PINS
WITH NYLON
SLEEVES, 6" O.C.
A-501
TERMINATION PER ROOFING
MANUFACTURER INSTRUCTION
EXISTING STRUCTURE
TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE
COPPER FLASHING AND REGLET
CONTINUOUS BACKER ROD AND SEALANT
S.S. DRIVE PINS
WITH NYLON
SLEEVES, 6" O.C. A-501
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
REPLACEMENT DRAIN,
ZURN RD2150 OR EQUAL
EXISTING PLYWOOD DECK
EXISTING ROOF DRAIN BODY
EXISTING 3" LEADER PIPE, FIELD
VERIFY DIAMETER
EPDM ROOF MEMBRANE
EXISTING STRUCTURE
TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EXISTING CURB, TYP.
EPDM ROOF MEMBRANE,
EXTEND OVER TOP OF CURB
EXISTING STRUCTURE
TO REMAIN
NEW COPPER BREATHER VENT
WITH INSECT SCREEN
V.I.F.
1' - 0"
8"
EXISTING PARAPET AND ROOF
STRUCTURE TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE, EXTEND
OVER TOP OF PARAPET WALL
CLEATED COPPER COPING.
PROVIDE IN TEN FOOT LENGTHS,
SOLDER ALL LAP JOINTS
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE
PARAPET BEYOND
EXISTING ROOF
STRUCTURE TO REMAIN
4"
EPDM ROOF MEMBRANE FLASHING
COPPER SCUPPER FLASHING
EXISTING STRUCTURE
TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE
COPPER FLASHING AND REGLET,
REFER TO DETAIL 4 ON THIS SHEET
COPPER SCUPPER FLASHING
MASONRY WALL BEYOND
EPDM ROOF MEMBRANE FLASHING
CURB BEYOND
TERMINATION PER ROOFING
MANUFACTURER INSTRUCTION
EXISTING STRUCTURE
TO REMAIN
TAPERED INSULATION, MIN. 1/4"
PER FOOT SLOPE TO DRAIN
EXISTING PLYWOOD DECK
EPDM ROOF MEMBRANE
EXISTING COPPER FLASHING.
COORDINATE WITH DEMOLITION,
RESOLDER JOINTS AND CORNER LAPS
EXISTING WINDOW
COPPER REGLET FLASHING
SLOPED TO EXTERIOR
CONTINUOUS BACKER ROD
AND SEALANT. DUST
SURFACE OF SEALANT WITH
SAND MATCHING MORTAR
S.S. DRIVE PINS
WITH NYLON
SLEEVES, 6" O.C.
3/8"
5/ 8"
1"
MASONRY WALL
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111 OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO. DRAWING NO.
SHEET
TITLE OF SHEET
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
BOSTON NATIONAL HISTORIC PARK
DRAWN:
179756
6/ 7/
:1
0:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
ROOF DETALS
A-501
EJB
EJB
JPD
06/10/2022
1 1/2" = 1'-0"1 ROOF FLASHING AT WALL WITH CURB
1 1/2" = 1'-0"2 ROOF FLASHING AT BRICK WALL
1 1/2" = 1'-0"3 ROOF FLASHING AT GRANITE WALL
1 1/2" = 1'-0"5 ROOF DRAIN SECTION
1 1/2" = 1'-0"6 ROOF BREATHER VENT SECTION
1 1/2" = 1'-0"10 TYPICAL PARAPET SECTION
1 1/2" = 1'-0"8 TYPICAL SCUPPER SECTION
1 1/2" = 1'-0"9 TYPICAL SCUPPER AT WALL
1 1/2" = 1'-0"7 TYPICAL SECTION AT MONITOR WINDOW WALL
5 7
3" = 1'-0"4 TYPICAL REGLET FLASHING SECTION
EPDM MEMBRANE
8" (2 m
m) M
IN
. A
BO
VE
F
IN
IS
HE
D
RO
OF
RE
QU
IR
ED
NOTES:
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION.
2. REGULAR MAINTENANCE OF COUNTER-FLASHING AND
SEALANT REQUIRED. NOT INCLUDED AS PART OF THE
MANUFACTURER'S WARRANTY
3. METAL COUNTER-FLASHING SHALL BE 24 GAUGE PRE-FINISHED
STEEL OR COPPER, OR .032" MIN. ALUMINUM FORMED WITH HEMMED
LOWER EDGE.
4. INSTALL METAL WORK IN ACCORDANCE WITH CURRENT SMACNA
RECOMMENDATIONS
5. APPLY WATER BLOCK IN A 3/8" (10mm) TO 1/2" (13 mm) BEAD AT
APPROXIMATELY 10 L.F. PER TUBE
(MASONRY/
CONCRETE
SUBSTRATE
ONLY)
USE
APPROPRIATE
BASE TIE-IN
APPROPRIATE MANUFACTURER'S
FASTENER
12" (305 mm) O.C. MAX.
CONTINUOUS BEAD OF
MANUFACTURER'S
AP SEALANT
METAL COUNTERFLASHING BY
OTHERS
3" (76 mm) MIN. FACE (SEE NOTE #3)
USE APPROPRIATE
MANUFACTURER'S
BONDING ADHESIVE
CONTINUOUS BEAD OF
MANUFACTURER'S
AP SEALANT
INSULATION
SUBSTRATE
WALL /PARAPET/ CURB
3" QUICKSEAM SPLICE TAPE
ACCEPTABLE MANUFACTURER'S PRIMER
USE APPROPRIATE
TERMINATION
2" (5
1m m)
M
IN
BATTEN STRIP POSITIONED 1/2" (13mm)
BEYOND WALL/CURB
NOTES:
2. MAXIMUM 10" (254 mm) LONG FASTENERS. (NOTE: WOOD
BLOCKING MAY BE SUBSTITUTED FOR INSULATION TO REDUCE
FASTENER LENGTH REQUIREMENTS).
3. MEMBRANE ADHESIVE REQUIRED BETWEEN MEMBRANE
AND INSULATION FOR FULLY ADHERED SYSTEMS
4. METAL BATTEN REQUIRED FOR 20 YEAR
WARRANTIES.
MANUFACTURER'S BATTEN FASTENED 12" (305mm) O.C.
MAX WITH MANUFACTURER'S FASTENERS AND AP
SEALANT OVER FASTENER HEADS (SEE NOTE #2 & #4)
EPDM MEMBRANE OR QUICKSEAM CURB FLASHING
USE APPROPRIATE MANUFACTURER'S
MEMBRAME ADHESIVE. (SEE NOTE #3)
USE APPROPRIATE MANUFACTURER'S
MEMBRAME ADHESIVE. (SEE NOTE #3)
EPDM MEMBRANE
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION
MANUFACTURER'S INSULATION
SUBSTRATE
CANT STRIP
WOOD NAILER (SEE NOTE)
2" (5
1 m m)
M
IN
BATTEN STRIP POSITIONED
1/4" (6mm) MIN. BEYOND TOE OF CANT
6" (152 mm) MAX.
2. WOOD NAILER MUST BE INSTALLED TO MEET
APPLICABLE BUILDING CODES OR 200 LB. PER
LINEAR FOOT MINIMUM IN ANY DIRECTION.
4. 2" (50.8 mm) METAL PLATES MAY BE USED IN LIEU OF
BATTEN STRIP. EDGE OF PLATE MUST BE POSITIONED
SIMILAR TO BATTEN
5. BONDING ADHESIVE REQUIRED BETWEEN MEMBRANE
AND INSULATION FOR ADHERED SYSTEMS
MANUFACTURER'S BATTEN FASTENED
@ 12" (305mm) O.C.MAX. WITH MANUFACTURER'S
FASTENERS AND AP SEALANT OVER FASTENER
HEADS (SEE NOTE #4)
EPDM MEMBRANE
USE APPROPRIATE
TERMINATIONS ACCEPTABLE MANUFACTURER'S PRIMER
CONTINUOUS BEAD OF
SEALANT
EPDM MEMBRANE EXTEND MIN. 3" (76 mm)
PAST SEAM PLATE
NOTES:
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION
WALL/PARAPET
1/2" (13 mm) MIN.
USE APPROPRIATE BASE TIE-IN
1/2" (13 mm) MIN.
EPDM MEMBRANE
ANCHOR CLIP FASTENERS
WOOD NAILER
(SEE NOTE #3)
COPING
USE APPROPRIATE
MANUFACTURER'S
MEMBRANE ADHESIVE
1-1/4" HOT DIPPED GALVANIZED ROOF
NAILS @ 4" (102 mm) O. C. MAX
NOTES:
2. NON-MANUFACTURER'S METAL COPING IS ACCEPTABLE
FOR THE USE IN THIS DETAIL PROVIDED
FABRICATION AND INSTALLATION IS IN
ACCORDANCE WITH CURRENT SMACNA
RECOMMENDATIONS. HOWEVER, WATERTIGHT
INTEGRITY OF WALL AND NON-MANUFACTURER'S METAL
COPING SHALL BE ENSURED BY OTHERS AND
EXCLUDED FROM WARRANTY COVERAGE.
3. WOOD NAILER MUST BE INSTALLED TO MEET
APPLICABLE BUILDING CODES
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION
INSULATION (SEE NOTES)
INSULATION
SUBSTRATE
COMPRESSION RINGSTRAINER BASKET
SUBSTRATE
1/2" (13 mm) MIN.
(SEE NOTE #2)
12" (305 mm)
NOTES:
2. HOLE IN MEMBRANE SHOULD EXTEND A MINIMUM OF 1/2" (13 mm)
BEYOND CLAMPING RING AND BE LARGER THAN THE DIAMETER OF
THE LEADER PIPE
3. INSULATION ADJACENT TO DRAIN TO BE APPROPRIATE
INSULATION WITH APPROPRIATE BONDING SURFACE
4. WATERBLOCK MINIMUM 1/2 OF 10 OZ (295 ml) TUBE PER 4" (102
mm) DRAIN. USE ADDITIONAL WATERBLOCK FOR LARGER DRAINS
5. IN RE-ROOF APPLICATIONS:
-REMOVE EXISTING FLASHING DOWN TO METAL BOWL.
-REPAIR OR REPLACE BROKEN DRAIN COMPONENTS.
-DRILL AND TAP BROKEN DRAIN BOLTS AND REPLACE IF NECESSARY
MEMBRANE SLOPE LIMITS:
A. MAXIMUM SLOPE FOR REINFORCED MEMBRANE
SHALL BE 2" (51 mm) - 12" (305 mm).
B. MAXIMUM SLOPE FOR STANDARD MEMBRANE
SHALL BE 6" (152 mm)/12"(305 mm).
SUMP AREA FIELD SEAM REQUIREMENTS:
A. IF SEAM EDGE IS WITHIN 9" (229 mm) OF DRAIN
COMPRESSION RING, EPDM TARGET PATCH
REQUIRED.
B. IF SEAM EDGE IS WITHIN 9" (229 mm) TO 18" (457 mm)
OF DRAIN COMPRESSION RING, INSTALL A LAYER OF 5"
(127 mm) QUICKSEAM FLASHING CENTERED OVER SEAM EDGE. EXTEND 5" (127 mm) QUICKSEAM FLASHING 3" (76
mm) MIN. BEYOND EDGE OF SUMP.
CONTINUOUS BEAD OF
WATERBLOCK
(SEE NOTE #4)
EPDM MEMBRANE
APPROPRIATE
MEMBRANE ADHESIVE
(ADHERED SYSTEM ONLY)
SEE SLOPE
LIMITS
1. REFER TO MANUFACTURER'S WEBSITE FOR THE MOST
CURRENT INFORMATION
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111 OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO. DRAWING NO.
SHEET
TITLE OF SHEET
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
BOSTON NATIONAL HISTORIC PARK
DRAWN:
179756
6/ 7/
:1
0:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
EPDM ROOFING DETAILS
A-502
EJB
EJB
JPD
06/10/2022
NTS1 EPDM DETAIL - WALL TERMINATION
NTS2 EPDM DETAIL - BASE TIE-IN
NTS3 EPDM DETAIL - BASE TIE-IN WITH EXISTING CANT
NTS4 EPDM DETAIL - PARAPET TERMINATION
NTS5 EPDM DETAIL - ROOF DRAIN
6 7
WALL
WALL
QUICKSEAM JOINT COVER AS
CORNER FLASHING (SEE NOTES)
ACCEPTABLE MANUFACTURER'S PRIMER
NON-WELDED METAL SCUPPER SLEEVE
(SEE NOTES)
EPDM MEMBRANE
ACCEPTABLE MANUFACTURER'S PRIMER
MEMBRANE ADHESIVE
9" QUICKSEAM FLASHING CENTERED
OVER 5" QUICKSEAM FLASHING AT BASE
OF SCUPPER ONLY.
5" QUICKSEAM FLASHING
CENTERED OVER
EDGE OF SCUPPER FLANGE
NOTE:
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION.
2. ROUND ALL SHEET METAL FLANGE CORNERS.
CONTINUOUS BEAD OF
MANUFACTURER'S AP
SEALANT
OR HIGH-GRADE
URETHANE SEALANT
CONTINUOUS BEAD OF
MANUFACTURER'S WATERBLOCK
5" QUICKSEAM FLASHING CENTERED
OVER EDGE OF SCUPPER FLANGE.
CONTINUOUS BEAD OF LAP SEALANT
(SEE NOTE #3)
APPROPRIATE FASTENER
4" (102 mm) O.C. MAX.
3. APPLY LAP SEALANT AROUND ENTIRE PERIMETER OF FLASHING.
SUBSTRATE
WALL
1-1/4" HOT DIPPED GALVANIZED ROOF NAILS 4" (102 mm) O.C. MAX
WOOD NAILER (SEE NOTE #4)
EPDM MEMBRANE
NOTES:
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION
2. ROUND ALL SHEET METAL FLANGE CORNERS.
3. APPLY LAP SEALANT AROUND ENTIRE PERIMETER OF FLASHING.
4. WOOD NAILER MUST BE INSTALLED TO MEET
APPLICABLE BUILDING CODES.
5. FLANGE OF METAL MUST BE FULLY SUPPORTED
BY WOOD AND TERMINATED AT LEAST
1/2" (13mm) FROM EDGE OF WOOD.
5" QUICKSEAM FLASHING CENTERED
OVER EDGE OF SCUPPER FLANGE
9" QUICKSEAM FORMFLASH CENTERED OVER 5"
QUICKSEAM FLASHING AT BASE OF SCUPPER ONLY
QUICKSEAM JOINT COVER
AS CORNER FLASHING
APPROPRIATE MANUFACTURER'S
MEMBRANE ADHESIVE (ADHERED
SYSTEMS ONLY)
RO
OF
S
LO
PE
APPROPRIATE MANUFACTURER'S
WALKWAY PAD
2 m m)
30" (762 mm)
ENLARGED TO SHOW SURFACE TEXTURE
3" Q
UI
CK
SE
AM
S
PL
IC
E
TA
PE
(F
AC
TO
RY
LA
MI
NA
TE
D
TO
U
ND
ER
SI
DE
3" Q
UI
CK
SE
AM
S
PL
IC
E
TA
PE
(F
AC
TO
RY
LA
MI
NA
TE
D)
3" Q
UI
CK
SE
AM
S
PL
IC
E
TA
PE
(F
AC
TO
RY
LA
MI
NA
TE
D)
NOTES:
1. REFER TO MANUFACTURER'S WEBSITE FOR MOST
CURRENT INFORMATION.
2. DO NOT INSTALL ON FIELD OR FLASHING SEAMS.
3. LEAVE 2" (51 mm) BETWEEN WALKWAY PADS.
4. QUICKSEAM TAPE IS FACTORY LAMINATED
TO UNDERSIDE OF WALKWAY PADS: 3 ROWS OF
3" (76 mm) WIDE TAPE, OR TWO ROWS OF 7" (178 mm) WIDE TAPE.
A/E FIRM
BBIX,LLC.
102 SOUTH STREET, UNIT 3
BOSTON, MA 02111 OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO. DRAWING NO.
SHEET
TITLE OF SHEET
REPLACE USS CONSTITUTION MUSEUM CONNECTOR ROOF
BOSTON NATIONAL HISTORIC PARK
DRAWN:
179756
6/ 7/
:1
0:
P M
G :\B
BI
X\
.0
C
H
AR
LE
ST
O W
N N
AV
Y
YA
R
D \D
R
AW
IN
G
S\
0% S
U
BM
IS
SI
O N
\R
EV
IT
\U
SS
C
O N
ST
IT
U
TI
O N
M U
SE
U
M C
O N
N
EC
TO
R
R O
O F.
rv t
EPDM ROOFING DETAILS
A-503
EJB
EJB
JPD
06/10/2022
NTS1 EPDM DETAIL - SCUPPER PLAN DETAIL
NTS2 EPDM DETAIL - SCUPPER SECTION
NTS3 EPDM DETAIL - WALKWAY PAD
7 7