B08 - Attachment 002 - Technical Data Sheet (Purchase Description Attachment A).pdf

PDF 4 MB Posted

Attached to
60 Ton Daikin Air Cooled Chiller Unit - Pine Bluff Arsenal
Solicitation number
W519TC25Q2019
Issued by

About this file

This is a technical data sheet for a Daikin AGZ006F air-cooled scroll compressor chiller unit with a 56.07-ton capacity. The unit features a 208V/60Hz/3Ph electrical configuration, microchannel condenser coils, brazed plate evaporator, and meets ASHRAE 90.1 standards for '07, '10, '13, '16 & '19 with LEED Enhanced Refrigerant Management Credit compliance.

The specifications detail a high-efficiency packaged unit using R32 refrigerant (60 lb per unit), with door-mounted display, AC fan motors & DC first fans, and ETL/cETL/AHRI & ASHRAE 90.1 approvals. The unit includes comprehensive safety features like phase voltage protection, RapidRestore capability for quick restart after power loss, and BACnet/Modbus communication protocols. It has a 1-year standard warranty on parts and labor, with an extended 4-year warranty on compressor parts. The unit's physical dimensions are 128" length x 99" height x 88" width, with an operating weight of 4,865 lbs and requires specific clearances for service access and proper operation as detailed in the close spacing performance charts.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Daikin Applied reserves the right to alter, amend, modify, or change any product manufacture including, but not limited to, its designs, images or specifications at any time without notice, recourse, or remedy from the Owner, Contractor, or Buyer.

CSD-02019-00 (Apr-18)

©2019 Daikin Applied | (800) 432-1342 | www.DaikinApplied.com

Phase Voltage Monitor

Part Number:

Description

The MotorSaver® 460 is a 3-phase voltage monitor that protects

190 480VAC or 475 600V, 50/60Hz motors regardless of size.

The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically senses line voltage.

This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions such as low, high, and unbalanced voltage, loss of any phase, and phase reversal.

When a harmful condition is detected, the 460 output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (restart delay). The trip and restart delays prevent nuisance tripping due to rapidly fluctuating power line conditions.

All 460 models feature adjustable 1 30 second trip delay, 1 500 second restart delay, 2 8% voltage unbalance trip point, and one form C contact except where noted.

Features

Auto-sensing wide voltage range

Automatically senses system voltage between 190 480VAC or 475 600VAC

Adjustable trip & restart delay settings

Prevent nuisance tripping due to rapidly fluctuating power line conditions

Microcontroller based circuitry

Improved accuracy and higher reliability

Advanced LED diagnostics Quick visual indicator for cause of trip and relay status

Adjustable voltage unbalance trip setting

Provides reliable protection when regenerative voltage is present

Wiring Diagram

Code Item

Code Value Description

46 A ASHRAE APPROVAL; With ASHRAE Label 47 N CRN-EVAPORATOR; No CRN Required 48 B SHIPPING/PACKAGING; Bagged - Type A or B 49 W WATER PUMP HP; Without Pumps 50 N PUMP POWER SUPPLY; None 51 N PUMP SPEED; None 52 N PUMP NUMBER; None

53 0134 PUMP FLOW; 0134

54 NNN PUMP HEAD; None 55 N PUMP PACKAGE STARTER; No Pump Package 56 N PUMP GAUGES; No Pressure Gauges 57 NNNN PUMP IMPELLER SIZE; No Pumps

NNNNNNN

NNNNNNN

NN

PUMP PART NUMBER; No Pumps

59 DSU UNIT START; Domestic Startup 60 DPL 1ST YEAR WARRANTY ; Unit Parts & Unit Labor Warranty 61 CPE4 EXT. COMPRESSOR WARRANTY; Comp. Only - Ext. 4yr Parts Only (5 Years Total) 62 NNNN EXT. UNIT WARRANTY; None 63 R31 REFRIGERANT WARRANTY; 1 Year Refrigerant 64 D00 DELAYED WARRANTY START; Additional Months: 0 [12-18] STD 65 S UNIT MISC; Standard Unit 66 F0 TESTING; Functional Test

67 038 CIRC 1 REFRIGERANT QTY; 038

68 022 CIRC 2 REFRIGERANT QTY; 022

69 NHT PUMP HEAT TRACE; No Pump Heat Trace 70 ERNS TUBING OPTIONS; EEXV, Repl FD, Liq/Disch Shutoff 71 WSV SUCTION VALVE; With Shutoff Valve 72 NHG HOT GAS BYPASS OPTION; No Hot Gas 73 S SHIP; Standard Ship 74 00 UNIT REVISION; Major Unit Change Revision 75 B PUMP CONN AT EVAP; 2.5 inch 76 N PUMP SUCTION VALVE; No Pump Package Suction Valve Shutoff 77 N PUMP DISCHARGE VALVE; No Pump Package Discharge Valve Shutoff

78 056 UNIT TONS; 056

79 1144 UNIT EER; 1144

80 1800 UNIT IPLV; 1800

81 2 REFRIGERANT TYPE; R32

82 00197 LRA AMPS 1; 00197

83 00147 LRA AMPS 2; 00147

84 00197 LRA AMPS 3; 00197

85 00147 LRA AMPS 4; 00147

86 00000 LRA AMPS 5; Amps 87 00000 LRA AMPS 6; Amps 88 00000 LRA AMPS 7; Amps 89 00000 LRA AMPS 8; Amps 90 0000 INPUT RLA 7; Nameplate RLA 91 0000 INPUT RLA 8; Nameplate RLA

92 0254 MCA 1; 0254

93 0000 MCA 2; MCA

94 0000 MCA 3; MCA

95 0300 MOCP 1; 0300

96 0000 MOCP 2; MOCP

PART 1: GENERAL

1.01 SUMMARY

A. A. Section includes design, performance criteria, refrigerants, controls, and installation requirements for air-cooled scroll compressor chillers.

1.02 REFERENCES

A. Comply with applicable Standards/Codes of AHRI 550/590, ANSI/ASHRAE 15, ETL, cETL, NEC, and OSHA as adopted by the State.

B. Units shall meet the efficiency standards of the current version of ASHRAE Standard 90.1, and FEMP standard 2012.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with the specifications.

B. Submittals shall include the following:

1. Dimensioned plan and elevation view drawings, required clearances, and location of all field connections

2. Summary of all auxiliary utility requirements such as electricity, water, etc. Summary shall indicate quality and quantity of each required utility.

3. Single line schematic drawing of the field power hookup requirements, indicating all items that are furnished.

4. Schematic diagram of control system indicating points for field interface/connection.

5. Diagram shall fully delineate field and factory wiring.

6. Installation and operating manuals.

1.04 QUALITY ASSURANCE

A. Qualifications: Equipment manufacturer must specialize in the manufacture of the products specified and have five years experience with the type of equipment and refrigerant offered.

B. Regulatory Requirements: Comply with the codes and standards specified.

C. Chiller manufacturer plant must be ISO Registered.

1.05 DELIVERY AND HANDLING

A. Chiller shall be delivered to the job site completely assembled and charged with refrigerant and oil by the manufacturer.

B. Comply with the manufacturer's instructions for rigging and handling equipment.

1.06 WARRANTY

A. 1st Year Labor Warranty: Parts & Compressor B. Extended Compressor Warranty: Four (4) years extended compressor warranty, parts only.

C. Extended Unit Warranty: None.

D. Refrigerant Warranty: One (1) year R32 refrigerant.

E. Delay Warranty Start: None.

1.07 MAINTENANCE

A. Maintenance of the chillers shall be the responsibility of the owner and performed in accordance with the

PART 2: PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. Daikin Applied B. (Approved Equal)

2.02 UNIT DESCRIPTION

A. Provide and install as shown on the plans factory-assembled, factory-charged air-cooled scroll compressor packaged chillers in the quantity specified. Each chiller shall consist of hermetic tandem scroll compressor sets, brazed plate evaporator, air-cooled condenser section, microprocessor-based control system and all components necessary for controlled unit operation.

B. Chiller shall be functionally tested at the factory to ensure trouble free field operation

2.03 DESIGN REQUIREMENTS

A. Flow Range: The chiller shall have the ability to support variable flow range down to 40% of nominal design (based on AHRI conditions).

B. Operating Range: The chiller shall have the ability to control leaving chilled fluid temperature from 15F to 65F.

C. General: Provide a complete scroll compressor packaged chiller as specified herein and as shown on the drawings. The unit shall be in accordance with the standards referenced in section 1.02 and any local codes in effect.

D. Refer to the schedule of performance on the drawings. The chiller shall be capable of stable operation to a minimum percentage of full load (without hot gas bypass) of 25%. Performance shall be in accordance with AHRI Standard 550/590.

E. Acoustics: Sound pressure levels for the unit shall not exceed the following specified levels. All manufacturers shall provide the necessary sound treatment ( parts and labor) to meet these levels if required.

Sound data shall be provided with the quotation. Test shall be in accordance with AHRI Standard 370.

2.04 CHILLER COMPONENTS

A. Compressor

1. The compressors shall be sealed hermetic, scroll type with crankcase oil heater and suction strainer. The compressor motor shall be refrigerant gas cooled, high torque, hermetic induction type, two-pole, with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads. The compressors shall be equipped with an internal module providing compressor protection and communication capability.

B. Evaporator

1. The evaporator shall be a compact, high efficiency, dual circuit, brazed plate-to-plate type heat exchanger consisting of parallel stainless steel plates. Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor.

2. The evaporator shall be protected with an external, electric resistance heater plate. The evaporator and flexible elastomeric foam insulation material with 100% adhesive coverage. The insulation shall have an additional outer protective layer of 3mm thick PE embossed film to provide superior damage resistance.

Insulation without the protective outer film shall not be acceptable. UV resistance level shall meet or

3. The water-side maximum design pressure shall be rated at a minimum of 469 psig (3235 kPa).

Evaporators shall be designed and constructed according to, and listed by, Underwriters Laboratories (UL).

C. Condenser

1. Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors. The fans shall be equipped with a heavy-gauge vinyl-coated fan guard. Fan motors shall be TEAO type with permanently lubricated ball bearings, inherent overload protection, three-phase, direct-drive, 1140 rpm. Each fan section shall be partitioned to avoid cross circulation.

2. Coil shall be microchannel design and shall have a series of flat tubes containing multiple, parallel flow microchannels layered between the refrigerant manifolds. Tubes shall be 9153 aluminum alloy. Tubes made of 3102 alloy or other alloys of lower corrosion resistance shall not be accepted. Coils shall consist of a two-pass arrangement. Each condenser coil shall be factory leak tested with high-pressure air under water.

D. Refrigerant Circuit

1. Each of the two refrigerant circuits shall include a replaceable-core refrigerant filter-drier, sight glass with moisture indicator, liquid line solenoid valve (no exceptions), expansion valve, and insulated suction line.

E. Construction

1. Unit formed sheet metal components shall be painted using a corrosion resistant paint system, for aesthetics and long-term durability. Paint system will include a base primer with a high-quality polyester resin topcoat. Painted galvanized parts shall be G60 or greater and finished, unabraded panel surfaces shall be capable to be exposed to an ASTM B117 salt spray environment and exhibit no visible red rust at a minimum of 3,000 hours exposure. Finished, abraded surfaces shall be tested per ASTM D1654, having a environment.

2. Upper condenser coil and base section of unit shall have protective, 12 GA, PVC-coated, wire grille guards and have painted steel wraps enclosing the coil end sections and piping.

F. Control System

1. A centrally located weatherproof control panel shall contain the field power connection points, control interlock terminals, and control system. Box shall be designed in accordance with NEMA 3R rating. Power and starting components shall include factory circuit breaker for fan motors and control circuit, individual contactors for each fan motor, solid-state compressor three-phase motor overload protection, inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote, contractor supplied disconnect switches. Hinged access doors shall be lockable. Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system.

2. Shall include high short circuit current rating of 65,000 amps with single-point disconnect switch

G. Unit Controller

1. An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions. The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure. The controller shall contain the following features as a minimum:

2. The unit shall be protected in two ways: (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition. Shut down alarms shall activate an alarm signal.

3. Shutdown Alarms

a. No evaporator water flow (auto-restart)

b. Sensor failures

c. Low evaporator pressure

d. Evaporator freeze protection

e. High condenser pressure

f. Outside ambient temperature (auto-restart)

g. Motor protection system

h. Phase voltage protection (Optional)

4. Limit Alarms

a. Condenser pressure stage down, unloads unit at high discharge pressures.

b. Low ambient lockout, shuts off unit at low ambient temperatures.

c. Low evaporator pressure hold, holds stage #1 until pressure rises.

d. Low evaporator pressure unload, shuts off one compressor.

5. Unit Enable Section

a. Enables unit operation from either local keypad, digital input, or BAS

6. Unit Mode Selection

a. Selects standard cooling, ice, glycol, or test operation mode

7. Analog Inputs:

a. Reset of leaving water temperature, 4-20 mA\

b. Current Limit

8. Digital Inputs

a. Unit off switch

b. Remote start/stop

c. Flow switch

d. Ice mode switch, converts operation and setpoints for ice production

e. Motor protection

9. Digital Outputs

a. Shutdown alarm; field wired, activates on an alarm condition, off when alarm is cleared

b. Evaporator pump; field wired, starts pump when unit is set to start

10. Condenser fan control - The unit controller shall provide control of condenser fans based on compressor discharge pressure.

11. Building Automation System (BAS) Interface a.

network via one of the data link / physical layers listed below as specified by the successful Building Automation System (BAS) supplier.

b. BACnet MS/TP master (Clause 9)

c. BACnet IP, (Annex J)

d. BACnet ISO 8802-3, (Ethernet) e.

f. The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring, control and alarm notification as specified in the unit sequence of operation and the unit points list.

g. For chillers communicating over a LONMARK network, the corresponding LONMARK eXternal Interface File (XIF) shall be provided with the chiller submittal data.

h. All communication from the chiller unit controller as specified in the points list shall be via standard BACnet objects. Proprietary BACnet objects shall not be allowed. BACnet communications shall conform to the BACnet protocol (ANSI/ASHRAE135-2001). A BACnet Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal.

2.05 OPTIONS AND ACCESSORIES

A. The following options are to be included:

1.

quickly than standard in case of a power interruption. The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds. The time to restart the chiller shall be a maximum of 125 seconds, and full load shall be achieved in 220 seconds from power restoration. Fast Loading Stand-By Chiller: The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled. The chiller shall be capable of rapidly achieving full capacity. The time to full load shall be achieved in 115 seconds.

2.

3. Phase loss with under/over voltage protection and with LED indication of the fault type to guard against compressor motor burnout.

4. BAS interface module to provide interface with a combination of BACnet IP, BACnet MSTP, and Modbus protocols.

5. The following accessories, if selected, are to be included:

a. Spring vibration isolators for field installation

b. Rubber-in-shear vibration isolators for field installation

c. Factory-mounted thermal dispersion type flow switch

d. Field-mounted, paddle type, chilled water flow switch field wired to the control panel

e. Wye strainer, to be installed at the evaporator inlet and sized for the design flow rate , with perforation diameter of 0.063" with blowdown valve and Victaulic couplings (factory mounted or field installed)

f. 115V GFI convenience outlet B. Optional Factory-Installed Pump Package: None

PART 3: EXECUTION

3.01 INSTALLATION

A.

B. Adjust and level chiller in alignment on supports.

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Install a field-supplied or optional manufacturer-supplied strainer in the chilled water return line at the evaporator inlet that meets manufacturer perforation size specifications.

3.02 START-UP

A. Provide testing and starting of machine, and instruct the Owner in its proper operation and maintenance.

File details come from the government source that posted it. Updated .