2-11 FIRE PROTECTION ENGINEERING ANALYSIS 2-11 ANALYSISANALYSIS — BUILDING 33-670

Ordinary Hazard Category (Mechanical or Sprinkler Riser Room) - 0.2 gpm per SF over 2,500 SF

Light Hazard (Office and Similar) - 0.1 gpm per SF over 1,500 SF

Ordnance Facility Special Hazard - At a minimum, an automatic sprinkler shall be installed for all ordnance facilities in accordance with UFC 3-600-010 Ch. 4 and NFPA 13. Consult a qualified fire protection engineer before making any changes to the process, materials used, or sprinkler design.