B08_Attach3_Spec_016500_Lighting.doc
DOC document 40 KB Posted
- Solicitation number
- 140L4325R0030
About this file
This document is a technical specification (Section 016500) for electrical lighting replacement at the Roseburg District Warehouse Building. The project involves a complete lighting system replacement with energy-efficient LED fixtures, specifically 4' linear LED shop lights with specifications including 110V AC input, daylight white color temperature (5000K), 4200 lumens output, and a 50,000-hour lifespan. The lighting installation requires mounting fixtures at specified heights, ensuring proper electrical connections, and supporting fixtures securely while avoiding space conflicts.
The contract is solicited by the Department of the Interior Bureau of Land Management Oregon-Washington (Solicitation Number: 140L4325R0030), with payment structured on a lump sum basis. The specification details installation requirements, including using UL-listed fixtures for wet locations, properly routing electrical connections, and conducting post-installation testing. The lighting replacement is part of broader warehouse environmental improvements, with the contractor responsible for providing all necessary components, supports, wiring, and completing the work according to contract provisions.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DIVISON 16
SECTION 016500
ELECTRICAL
LIGHTING
1 PART 1
GENERAL
1 .01 SUMMARY
A. The work of this section consists of furnishing and installing a complete replacement of the lighting system for the Roseburg District Warehouse Building with energy efficient LED lighting.
1 .02 RELATED SECTIONS:
A. Section 001000 - Summary & General Requirements B. Section 002222 – Minor Demolition C. Section 016010 – Electrical Requirements
1 .03 QUALITY ASSURANCE
A. Refer to Section 016010.
1 .04 SUBMITTALS
A. Provide light fixture and light bulb replacement schedule.
B. Provide time of when, how long and where power disruptions are expected during lighting replacement.
1 .05 CLOSEOUT SUBMITTALS
A. Operation and maintenance data for review and approval.
1. Manufacturer's operation and maintenance data for light fixtures.
2. Lighting fixture schedule for each type of lighting fixture listing designation, manufacturer, product name, catalog or model number, type of lamps installed, and number of lamps installed.
2 PART 2
PRODUCTS
PART 2
PRODUCTS
2 .01 INTERIOR LIGHTING FIXTURES
Interior lighting fixtures designated in accordance with the drawings shall be like kind style color, size, wattage, and lumens.
Product Example:
Description: 4’ Linear LED Shop Lights
Manufacture: Lepre
Size: 4’ Long
Input Voltage: 110V AC
Material: PC, SPCC
Fixture Color: White
Light Color: Daylight White
Dimmable: non-dimmable
Brightness: 4200 lumens
Power Consumption:
Color Temperature: 5000
Lifespan: 50,000 hours
Safety Rating/Certifications: FCC, ETL
Warranty: 5 years
OR approved Equal.
3 PART 3
EXECUTION
PART 3
EXECUTION
3 .01 GENERAL ‑ LIGHTING FIXTURES
A. Provide all accessories required for a complete and operable system. For recessed fixtures, provide plaster frames and flanges suitable for ceiling. Provide plates, barriers, or rings to cover any exposed ceiling material between fixture canopy or pan and outlet box. Fixtures installed in damp and wet locations shall be UL listed and marked "Suitable for Wet Locations.”
B. All Light fixtures shall be energy efficient LED compatibility with LED bulbs provided.
3 .02 INTERIOR LIGHTING FIXTURES
A. Mount at heights shown, adjusting fixture locations to avoid space conflicts. Securely support fixtures, attaching to outlet box if box is adequately supported. Support suspended fixtures by metal stems that hang level in same horizontal plane. Do not use fixtures as a raceway for circuit conductors except for single branch circuit supplying the fixtures. Branch circuit wiring shall not pass through an outlet box that is an integral part of an incandescent fixture unless fixture is identified for the purpose. Flush and recessed fixtures without integral outlet box shall have tap connection conductor, with insulation rated for 90 degrees C, run from fixture terminal connection to an outlet box at least 1 foot from fixture. Tap shall be between 4 and 6 feet long in metallic raceway. Wiring within fixtures shall be neatly arranged and protected from damage. Protect conductor insulation from abrasion where it passes through metal using chase nipples or equivalent.
3 .03 EXTERIOR LIGHTING FIXTURES
A. WAREHOUSE DOCK
3 .04 TESTS
A. After fixture installation, test lighting circuits. Replace noisy or defective fixtures.
4 PART 4
MEASUREMENT AND PAYMENT
PART 4: PAYMENT
4 .01 METHOD OF MEASUREMENT:
A. The work described in this section will be measured and paid for on a per lump sum basis. The quantity shall include all of the lighting specified above and within the drawings and shall be completed and accepted to include all components, appurtenances, supports, housing, raceways, wiring, testing, and all other materials, parts, components, appurtenances, labor, equipment, overhead, profit, and all other items associated with completing this work according to the contract provisions.
4 .02 BASIS OF PAYMENT:
A. Payment will be full compensation for the work described in the section. Payment will be made under:
Pay Item
Pay Unit
016500(01) Lighting
Lump Sum
END OF SECTION
JANUARY 2024
ROSEBURG DISTRICT OFFICE
LIGHTING
WAREHOUSE ENVIRONMENTAL IMPROVEMENTS
016500-1
File details come from the government source that posted it. Updated .