About this file
This is a construction specifications document for a telecommunications infrastructure project at Pu'ukohola Heiau National Historic Site in Hawaii. The National Park Service Pacific West Region project (PMIS No. 340780) involves replacing telecommunications lines from headquarters to the visitor center and includes detailed product specifications and installation requirements for fiber optic infrastructure components.
The project specifies several key components: a FHD-FWME2 wall mount fiber enclosure (2 ports, maximum 48 fibers, SPCC black coating, dimensions 10.2"x13.0"x2.3") for interconnecting and splicing applications; CommScope fiber optic cable (48-fiber, gel-filled stranded loose tube with singlemode and OM3 multimode fiber, 10.2mm diameter) meeting ANSI/ICEA S-87-640 and EN 187105 standards with operating temperatures of -40°C to +70°C; MaxCell fabric innerduct products in various configurations (2" through 4" sizes with 1- to 3-cell options) for cable protection and management; concrete polymer handholes (HPC 2436-36 Tier-22 rated) for access points; and associated termination cassettes, adapter panels, and splice trays for fiber management. The specifications include comprehensive technical data on mechanical performance (bend radius, tensile loads, compression resistance), environmental testing standards, and installation guidelines. All materials must comply with TIA/EIA standards, RoHS requirements, and ISO 9001 certification where applicable. The document was prepared in February 2026 and provides detailed product datasheets, dimensional drawings, and bill of materials for procurement and installation purposes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PU’UKOHOLA HEIAU NATIONAL
HISTORIC SITE (PUHE), HAWAI’I
REPLACE TELECOMMUNICATIONS LINES FROM
HEADQUARTERS TO THE VISITOR CENTER
PMIS No. 340780
CONSTRUCTION SPECIFICATIONS
NATIONAL PARK SERVICE
PACIFIC WEST REGION
PRODUCT INFORMATION
FEBRUARY 2026
Fiber Termination Cabinet
1www.fs.com
Designed to provide a convenient convergence point for interconnecting and splicing in wall mount applications.
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
Description
FHD Fiber Optic Wall Mount Enclosures can be used as an interconnect or cross-connect in any telecommunications room and can use
FHD series fiber adapter panels and cassettes (exclude 36F). Enclosures are designed to manage and organize fiber distribution in areas where space is limited.
Features
• Dual Doors with Slam Latch for Ease of Access.
• Optional Key/Lock Kit Secures Service-side Door or Customer-side Doors.
• Accepts FHD Series Adapter Panels, MTP Cassettes (Exclude 36F), and Splice Trays for Multiple Solution Capabilities.
• Removable Cable Entry/Exit Grommets Allow for Pre-terminated Fiber Trunk Installation, Cable Protection, and Minimizes Dust
Build-up.
• Ensure Signal Integrity, Proper Cable Routing, Bend Radius Control and Cable Protection.
FHD-FWME2 Wall Mount Fiber Enclosure
2www.fs.com
Product Specifications
2 Ports
Max. 48 Fibers
Wall-mountable
SPCC (Black Coating)
10.2''x13.0''x2.3'' (259.6x330.6x59.1mm)
FHD Series FAPs and Cassettes (Exclude 36F)
-25℃ to 50℃
-40℃ to 65 ℃
0℃ to 50℃
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
• TIA/EIA-568-C.3
• RoHS Compliant
• ISO9001 Certificate
Standards Compliance
Capacity
Fiber Count
Enclosure Type
Material
Dimensions (HxWxD)
Installation
Environmental Characteristics
Operating Temperature
Storage Temperature
Installation Temperature https://www.fs.com/
Grommet x4Slack Spool x2 Strain Relief Bracket x4
M4*8 Screw x6 and M4 Nut x10Cable Tie x2 Location Label x1
3www.fs.com
Accessories List
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
Key x2 Screwdriver x1
Assembly Structure Illustration
Grommet
Slack Spool
Key / Lock
Fiber Adapter Panel (2pcs sold separately)
Strain Relief Bracket
Layout and Dimensions
4www.fs.com
Dimensions are in inches. (Dimensions in parentheses are in millimeters).
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
[2
.6
[330.6]
[5 9.
1]
[209.4] 8.24
13.01
.2
2.
Front View
Bottom View
[63.1]
[59.1]
2.48
2.33
Side View
5www.fs.com
Product Application
I. Patch Cord Connections
II. Fiber Optic Splicing
① ② ③
Item No. #ID Description
1 #40234 1m (3ft) SC UPC to SC UPC Duplex Single Mode Fiber Patch Cable
2 #35484 6x SC Duplex, 12 Fibers OS2 Single Mode FHD Fiber Adapter Panel
3 #50550 FHD Fiber Optic Wall Mount Enclosure, 2-Door 2-Adapter Panel
① ③ ④ ⑤ ⑥
Item No.
Description
1m (3ft) 12 Fibers LC/UPC 9/125 Single Mode Color-Coded Fiber Optic Pigtail
24 Fibers Fusion Splice Tray, Plastic, 6.26"x4.13"x0.72"
Splice Tray Holder for FHD Wall Mount Enclosure
FHD Fiber Optic Wall Mount Enclosure, 2-Door 2-Adapter Panel
12x LC Duplex, 24 Fibers OS2 Single Mode FHD Fiber Adapter Panel
1m (3ft) Grade B LC UPC to LC UPC Duplex OS2 Fiber Patch Cable
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
#ID
②
#42459
#28774
#73717
#50550
#50550
#68294 https://www.fs.com/ https://www.fs.com/products/40234.html https://www.fs.com/products/35484.html https://www.fs.com/products/50550.html https://www.fs.com/products/42459.html https://www.fs.com/products/28774.html https://www.fs.com/products/73717.html https://www.fs.com/products/50550.html https://www.fs.com/products/35488.html https://www.fs.com/products/68294.html
III. MTP Cabling Management
6www.fs.com
① ② ③
Item No. #ID
1 #68294
2 #57341
3 #68102
4 #68540
5 #50550
Description
1m (3ft) Grade B LC UPC to LC UPC Duplex OS2 Fiber Patch Cable
2x MTP-12 to 12x LC Duplex, Type A, 24 Fibers OS2 FHD MTP/MPO Cassette
5m (16ft) MTP Female 12 Fibers OS2 9/125 Single Mode Trunk Cable, Type A
2x MTP-12 to 12x LC Duplex, Type AF, 24 Fibers OS2 FHD MTP/MPO Cassette
FHD Fiber Optic Wall Mount Enclosure, 2-Door 2-Adapter Panel
④ ⑤
Note:
The basic application and matching products for wall mount enclosures are shown for reference.
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
https://www.fs.com/ https://www.fs.com/products/68294.html https://www.fs.com/products/57341.html https://www.fs.com/products/68102.html https://www.fs.com/products/68540.html https://www.fs.com/products/50550.html
7www.fs.com
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
Fiber Enclosure Loading
I. Fiber Adapter Panel
#ID (OS2) #ID (OM4)
#35488 #51284
#35484 #41998
#35510 #35510
/ #52022
#183380 #183382
#183381 #183383
#336339 /
#147015 /
#143239 #143239
Description
24F, 12x LC Duplex Fiber Adapter Panel
12F, 16x SC Duplex Fiber Adapter Panel
12x MTP® Key Up to Key Down Fiber Adapter Panel
8x MTP® Key Up to Key Up Fiber Adapter Panel
6F, 6x ST Simplex Fiber Adapter Panel
8F, 8x ST Simplex Fiber Adapter Panel
12F, 12x LSH Simplex Fiber Adapter Panel
48F, 12x MDC 2-Port Duplex Fiber Adapter Panel
6-Port Multimedia Modular Panel with 6 Plastic Clips
II. MTP®/MPO Cassette
#ID (OS2) #ID (OM4)
#68401 #68402
/ #230555
#143164 #68399
#181822 #181823
#57016 #57017
#57037 #57038
#182641 #182642
#57341 #57342
Description
#68540 #68541
#ID (OM5)
#174246
#174247
#174248
#174249
#182643 #182644 /
8F, MTP®-8 to 4x LC Duplex Cassette, Universal
16F, 2x MTP®-8 to 8x LC Duplex Cassette, Universal
24F, 3x MTP®-8 to 12x LC Duplex Cassette, Universal
24F, 3x MTP®-8 to 2x LC Shuttered Duplex Cassette, Universal
12F, MTP®-12 to 6x LC Duplex Cassette, Type A
12F, MTP®-12 to 6x LC Duplex Cassette, Type AF
12F, MTP®-12 to 6x LC Duplex Cassette, Universal
24F, 2x MTP®-12 to 12x LC Duplex Cassette, Type A
24F, 2x MTP®-12 to 12x LC Duplex Cassette, Type AF
24F, 2x MTP®-12 to 12x LC Duplex Cassette, Universal https://www.fs.com/products/35488.html https://www.fs.com/products/51284.html https://www.fs.com/products/35484.html https://www.fs.com/products/41998.html https://www.fs.com/products/35510.html https://www.fs.com/products/52022.html https://www.fs.com/products/183380.html https://www.fs.com/products/183382.html https://www.fs.com/products/183381.html https://www.fs.com/products/183383.html https://www.fs.com/products/336339.html https://www.fs.com/products/147015.html https://www.fs.com/products/143239.html https://www.fs.com/products/68401.html https://www.fs.com/products/68402.html https://www.fs.com/products/230555.html https://www.fs.com/products/143164.html https://www.fs.com/products/68399.html https://www.fs.com/products/181822.html https://www.fs.com/products/181823.html https://www.fs.com/products/57016.html https://www.fs.com/products/57017.html https://www.fs.com/products/174246.html https://www.fs.com/products/57037.html https://www.fs.com/products/57038.html https://www.fs.com/products/174247.html https://www.fs.com/products/182641.html https://www.fs.com/products/182642.html https://www.fs.com/products/57341.html https://www.fs.com/products/57342.html https://www.fs.com/products/174248.html https://www.fs.com/products/68540.html https://www.fs.com/products/68541.html https://www.fs.com/products/174249.html https://www.fs.com/products/182643.html https://www.fs.com/products/182644.html https://www.fs.com/products/105333.html https://www.fs.com/products/105335.html https://www.fs.com/products/105334.html https://www.fs.com/products/105336.html
8www.fs.com
FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET
#57023 #57024
#68549 #68550
* MTP® is a registered trademark of US Conec Ltd.
* The US Conec MTP® connectors are fully compliant with the MPO standards.
Warranty Information
For FS product warranties, visit https://www.fs.com/policies/warranty.html
II. MTP®/MPO Cassette
#ID (OS2) #ID (OM4) #ID (OM5)Description
24F, MTP®-24 to 12x LC Duplex Cassette, Type A
24F, MTP®-24 to 12x LC Duplex Cassette, Type AF
III. Splice Tray
Fiber Count #ID
24F #28774
12F #28773
Description
24F, Fusion Splice Tray, Plastic, 6.26"x4.13"x0.72"
12F, Fusion Splice Tray, Plastic, 6.42"x3.96"x0.69"
Splice Tray Holder for FHD Wall Mount Enclosure N/A #73717 https://www.fs.com/products/57023.html https://www.fs.com/products/57024.html https://www.fs.com/products/68549.html https://www.fs.com/products/68550.html https://www.fs.com/policies/warranty.html
Fiber Optic Cable
760185942 | O-048-LN-CM-F12NS/25T/8W024
/5L024
©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025
Page of 1 4
Fiber OSP cable, LightScope® ZWP Single Jacket All-Dielectric, 48 fiber, Gel-Filled, Stranded Loose Tube, Singlemode + Multimode OM3, Feet jacket marking, Black jacket color
Product Classification Regional Availability Asia | Australia/New Zealand | EMEA | Latin America | North
America
Portfolio CommScope®
Product Type Fiber OSP cable
Product Series O-LN
General Specifications Cable Type Stranded loose tube
Construction Type Non-armored
Subunit Type Gel-filled
Filler, quantity 1
Jacket Color Black
Jacket Marking Feet
Subunit, quantity 4
Fibers per Subunit, quantity 12
Composite Fiber Count 24 + 24
Total Fiber Count 48
Dimensions Buffer Tube/Subunit Diameter 2.5 mm | 0.098 in
Diameter Over Jacket 10.2 mm | 0.402 in
Representative Image
©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025
Page of 2 4
Material Specifications Jacket Material PE
Mechanical Specifications Minimum Bend Radius, loaded 153 mm | 6.024 in
Minimum Bend Radius, unloaded 102 mm | 4.016 in
Tensile Load, long term, maximum 800 N | 179.847 lbf
Tensile Load, short term, maximum 2700 N | 606.984 lbf
Compression 22 N/mm | 125.623 lb/in
Compression Test Method FOTP-41 | IEC 60794-1 E3
Flex 25 cycles
Flex Test Method FOTP-104 | IEC 60794-1 E6
Impact 4.41 N-m | 39.032 in lb
Impact Test Method FOTP-25 | IEC 60794-1 E4
Strain See long and short term tensile loads
Strain Test Method FOTP-33 | IEC 60794-1 E1
Twist 10 cycles
Twist Test Method FOTP-85 | IEC 60794-1 E7
Vertical Rise, maximum 1199 m | 3,933.727 ft
Optical Specifications Fiber Type Composite MM/SM | G.652.D and G.657.A1 | OM3, LazrSPEED®
300 | OS2
©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025
Page of 3 4
Environmental Specifications Installation temperature -30 °C to +70 °C (-22 °F to +158 °F)
Operating Temperature -40 °C to +70 °C (-40 °F to +158 °F)
Storage Temperature -40 °C to +75 °C (-40 °F to +167 °F)
Cable Qualification Standards ANSI/ICEA S-87-640 | EN 187105
Environmental Space Aerial, lashed | Buried
Jacket UV Resistance UV stabilized
Water Penetration 24 h
Water Penetration Test Method FOTP-82 | IEC 60794-1 F5
Environmental Test Specifications Cable Freeze -2 °C | 28.4 °F
Cable Freeze Test Method FOTP-98 | IEC 60794-1 F15
Drip 70 °C | 158 °F
Drip Test Method FOTP-81 | IEC 60794-1 E14
Heat Age -40 °C to +85 °C (-40 °F to +185 °F)
Heat Age Test Method IEC 60794-1 F9
Low High Bend -30 °C to +60 °C (-22 °F to +140 °F)
Low High Bend Test Method FOTP-37 | IEC 60794-1 E11
Temperature Cycle -40 °C to +70 °C (-40 °F to +158 °F)
Temperature Cycle Test Method FOTP-3 | IEC 60794-1 F1
Packaging and Weights Cable weight 68 kg/km | 45.694 lb/kft
Regulatory Compliance/Certifications Agency Classification
ISO 9001:2015 Designed, manufactured and/or distributed under this quality management system
Included Products CS-5L-LT – LazrSPEED® 300 OM3 Bend-Insensitive Multimode
Fiber
CS-8W-LT – TeraSPEED® G652D/G657A1 Singlemode Fiber
* Footnotes
©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025
Page of 4 4
Operating Temperature Specification applicable to non-terminated bulk fiber cable
Handhole
SECTION A-A SECTION B-B
BILL OF MATERIALS
DESCRIPTIONPART NUMBERQTYUNIT QTYITEM
CONCRETE COMPOSITE BOX MIX BRUCE1000350381.996 ft^31.996 ft^31
HPC PLUGS 5/8X1-3/8-14-2 PE-LD67 BLK100022548212
SQUARE NUT 1/2-13 304SS100021840213
INSERT THREADED METAL 3/8-16 UNC 1IN100002783414
A A
B
B i d w
SHEET:
REV:
B-1
3/11/2019 10/31/2022
MODIFIED:CREATED:
PART #: DRAWN BY:
DESCRIPTION:
HPC 2436-36 Polymer Box, Tier-22, 1/2-13 SS Nut
DESIGN/TEST LOAD:
244.06 lbs
200022186 T.Larson
©2022 Jensen Precast- All rights reserved.
Unless expressly authorized by Jensen Precast any use or duplication is strictly prohibited under penalty of civil action or codes.
APPROX. WEIGHT:
22.5/33.75 kip
DESIGN SPEC:
ANSI/SCTE-77
AGENCY:
AGENCY SPEC: LOADING SPEC:
Tier-22
33 7/8"
35 7/8"
36"
29"
22 1/4"
24 1/4"
REVISION HISTORY
REV DESCRIPTION DATE BY
A INITIAL RELEASE
35"
3" 3"
23 3/8"
17 3/8"
35 7/8"
24 1/4"
3 7/8"
12 3/4"
3"
3" 3"
2 3
Fabric Innerduct
888.387.3828 | WWW.MAXCELL.US |
PRODUCT LINES & TYPES
MAXCELL IS OFFERED IN MULTIPLE PRODUCT LINES & TYPES
Standard, Detectable, Plenum & Riser. MaxCell product types refer to the different conduit application sizes and number of cells/pathways per product type. Most product lines are offered in all of the product type variations.
STANDARD MAXCELL
A versatile solution for the complex problems faced by today’s engineers, contractors and network providers. Manufactured from internally designed and produced materials, this model yields superior performance over existing rigid innerduct.
Standard MaxCell is the primary product line used in common outside plant applications, including long lines, under-bridge; road, river and rail borings;
under streets and all the way to building entrance points. In dense multiple cables and multiple MaxCell pack installations where the conduit path is not clear to surface markers, Standard MaxCell is often partnered with Detectable MaxCell so that path or service interruption points can be easily located.
Standard MaxCell is available for conduit sizes ranging from 1" to 4", and in 1-, 2- and 3-cell configurations — giving you the flexibility to choose the right product for your system and applications.
FEATURES & ADVANTAGES:
• �Melt point of 419°F — almost 2X of HDPE
• Resistant to ground chemicals and petroleum products
• Pre-lubed for lower friction during MaxCell and cable installation
• Pull tape included
| 888.387.3828 | WWW.MAXCELL.US
*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).
MaxCell 4" 3-Cell (Equivalent to three 1.5" I.D. innerducts) This product was designed for use in 4" or larger ducts. Multiple combinations of large and medium cable sizes are applicable. Since larger cable applications are anticipated, the number of cables and packs that can be placed is reduced; therefore, a smaller number of cables is available.
MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 4" MaxCell 4" 3-Cell 2 6 1.5" 1,250' 2,000'
5" MaxCell 4" 3-Cell 3 9 1.5" 1,250' 2,000'
6" MaxCell 4" 3-Cell 4 12 1.5" 1,250' 2,000'
4" 3-CELL PART NUMBERS
PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)
4" 3-Cell Product Standard color is Green
(GR)
250 MXC4003XX250 MXD4003XX250 MXP4003XX250 MXR4003XX250
500-999 MXC4003XX500 MXD4003XX500 MXP4003XX500 MXR4003XX500
1,000-2,649 MXC4003XX1000 MXD4003XX1000 MXP4003XX1000 MXR4003XX1000
2,650-5,299 MXC4003XX2650 MXD4003XX2650 MXP4003XX2650 MXR4003XX2650
5,300-9,999 MXC4003XX5300 MXD4003XX5300 MXP4003XX5300 MXR4003XX5300
10,000 MXC4003XX10000 MXD4003XX10000 MXP4003XX10000 MXR4003XX10000
4 INCH – 3-CELL
4" 3-CELL
For use in 4" or larger conduits, the 4" 3-Cell product is designed to hold larger backbone cables up to 1.5" in diameter in each cell.
Up to two packs can be placed in a 4" conduit.
• Standard color is green
• Color-coded pull tapes are preinstalled
• Factory lubricated
4" 3-Cell packs with 6 1" OD cables in 4" conduit
4" 3-Cell packs overriding existing cable plant
Add 8.5 lbs per 1,000ft for Detectable product weight estimates.
4" 3-CELL REEL SIZES AND WEIGHTS
DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.
PRODUCT LENGTH MAX PRODUCT ON REEL
4" 3-Cell Standard/Riser/Plenum
MXC4003
Product Wt:
107.5 lbs/1,000ft
500' 33"H x 15"W Composite 60 lbs 114 lbs 1,133'
1,000' 33"H x 15"W Composite 60 lbs 168 lbs 1,133'
2,650' 48"H x 22"W Steel 78 lbs 340 lbs 4,267'
5,300' 72"H x 22"W Steel 88 lbs 658 lbs 8,099'
10,000' 72"H x 30"W Steel 106 lbs 1,181 lbs 10,000'
4" 3-CELL APPLICATION GUIDE General Guidelines When Using MaxCell in Various Applications
3 INCH – 3-CELL
3" 3-CELL
For use in 3" or larger conduits, the 3" 3-Cell product is designed to hold cables up to 1.05" in diameter in each cell. Up to 3 packs can be placed in a 4" conduit.
• Standard colors are black, blue or red
• Color-coded pull tapes are preinstalled
• Factory lubricated
3" 3-Cell pack overriding existing cable plant in 4" conduit
MaxCell 3" 3-Cell (Equivalent to three 1.25" I.D. innerducts) This product was designed for use in 3" or larger ducts.
Multiple combinations of large, medium and smaller cable sizes are applicable and anticipated.
*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).
MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 3" MaxCell 3" 3-Cell 2 6 1.05" 1,250' 2,000'
4" MaxCell 3" 3-Cell 3 9 1.05" 1,250' 2,000'
5" MaxCell 3" 3-Cell 4 12 1.05" 1,250' 2,000'
6" MaxCell 3" 3-Cell 5 15 1.05" 1,250' 2,000'
3" 3-CELL PART NUMBERS
PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)
3" 3-Cell Product Standard colors are either Black (BK) or Blue (BL) or Red (RD)
250 MXC3456XX250 MXD3456XX250 MXP3456XX250 MXR3456XX250
500–999 MXC3456XX500 MXD3456XX500 MXP3456XX500 MXR3456XX500
1,000–2,649 MXC3456XX1000 MXD3456XX1000 MXP3456XX1000 MXR3456XX1000
2,650–5,299 MXC3456XX2650 MXD3456XX2650 MXP3456XX2650 MXR3456XX2650
5,300–9,999 MXC3456XX5300 MXD3456XX5300 MXP3456XX5300 MXR3456XX5300
10,000 MXC3456XX10000 MXD3456XX10000 MXP3456XX10000 MXR3456XX10000
3" 3-CELL REEL SIZES AND WEIGHTS
DESCRIPTION STD. PRODUCT
LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT
OF REEL
REEL WT. W/ STD.
PRODUCT LENGTH MAX PRODUCT ON REEL
3" 3-Cell Standard/Riser/Plenum
MXC3456
Product Wt:
88.5 lbs/1,000ft
500' 33"H x 15"W Composite 60 lbs 104 lbs 1,407'
1,000' 33"H x 15"W Composite 60 lbs 149 lbs 1,407'
2,650' 33"H x 22"W Composite 85 lbs 320 lbs 2,667'
5,300' 48"H x 22"W Steel 78 lbs 525 lbs 5,300'
10,000' 72"H x 30"W Steel 106 lbs 991 lbs 10,000'
3" 4-CELL STANDARD MXC3004 | Product Wt: 96 lbs/1,000ft Call for information
3" 3-CELL APPLICATION GUIDE General Guidelines When Using MaxCell in Various Applications
3" 3-Cell packs, 9 cables in 4" conduit
Add 8.5 lbs per 1,000ft for Detectable product weight estimates.
2" 3-Cell pack in 2" conduit2" 3-Cell packs, 6 cables in 3" conduit
MaxCell 2" 3-Cell (Equivalent to three 1.0" I.D. innerducts) This product was designed for use in 2" ducts where three cables are being placed.
2" 3-CELL APPLICATION GUIDE
2 INCH – 3-CELL
2" 3-CELL
For use in 2" conduits, the 2" 3-Cell product is designed to hold three cables up to 0.85" in diameter in each cell.
• Standard color is yellow
• Color-coded pull tapes are preinstalled
• Factory lubricated
MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 2" MaxCell 2" 3-Cell 1 3 .85" 800' 1,500'
2" 3-CELL PART NUMBERS
PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)
2" 3-Cell Product Standard color is
Yellow (YL)
250 MXC2003XX250 MXD2003XX250 MXP2003XX250 MXR2003XX250
500-999 MXC2003XX500 MXD2003XX500 MXP2003XX500 MXR2003XX500
1,000-2,649 MXC2003XX1000 MXD2003XX1000 MXP2003XX1000 MXR2003XX1000
2,650-5,299 MXC2003XX2650 MXD2003XX2650 MXP2003XX2650 MXR2003XX2650
5,300-9,999 MXC2003XX5300 MXD2003XX5300 MXP2003XX5300 MXR2003XX5300
10,000 MXC2003XX10000 MXD2003XX10000 MXP2003XX10000 MXR2003XX10000
2" 3-CELL REEL SIZES AND WEIGHTS
DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.
PRODUCT LENGTH MAX PRODUCT ON REEL
2" 3-Cell Standard/Riser/Plenum
MXC2003
Prod. Wt: 76 lbs/1,000ft
500' 33"H x 15"W Composite 60 lbs 98 lbs 1,592'
1,000' 33"H x 15"W Composite 60 lbs 136 lbs 1,592'
2,650' 33"H x 22"W Composite 85 lbs 287 lbs 3,018'
5,300' 48"H x 22"W Steel 78 lbs 458 lbs 5,997'
10,000' 72"H x 22"W Steel 88 lbs 848 lbs 10,000'
General Guidelines When Using MaxCell in Various Applications
Add 8.5 lbs per 1000ft for Detectable product weight estimates
*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).
2 INCH – 2-CELL
MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 2" MaxCell 2" 3-Cell 1 2 .85" 800' 1,500'
2" 2-CELL
For use in 2" conduits, the 2" 2-Cell product is designed to hold two cables up to 0.85" in diameter in each cell. It's ideal for overlay when one cable exists in a 2" conduit.
• Standard color is black
• Color-coded pull tapes are pre-installed
• Factory lubricated
MaxCell 2" 2-Cell (Equivalent to two 1.0" I.D. innerducts) This product was designed for use in 2" ducts where two cables are being placed.
*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).
2" 2-CELL APPLICATION GUIDE
2" 2-Cell pack in 2" conduit 2" 2-Cell pack overriding incumbent cable in 2" conduit
2" 2-CELL PART NUMBERS
PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)
2" 2-Cell Product Standard color is
Black (BK)
250 MXC2002XX250 MXD2002XX250 MXP2002XX250 MXR2002XX250
500-999 MXC2002XX500 MXD2002XX500 MXP2002XX500 MXR2002XX500
1,000-2,649 MXC2002XX1000 MXD2002XX1000 MXP2002XX1000 MXR2002XX1000
2,650-5,299 MXC2002XX2650 MXD2002XX2650 MXP2002XX2650 MXR2002XX2650
5,300-9,999 MXC2002XX5300 MXD2002XX5300 MXP2002XX5300 MXR2002XX5300
10,000 MXC2002XX10000 MXD2002XX10000 MXP2002XX10000 MXR2002XX10000
2" 2-CELL REEL SIZES AND WEIGHTS
DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.
PRODUCT LENGTH MAX PRODUCT ON REEL
2" 2-Cell Standard/Riser/Plenum
MXC2002
Prod. Wt: 51.5 lbs/1,000ft
500' 33"H x 15"W Composite 60 lbs 86 lbs 2,336'
1,000' 33"H x 15"W Composite 60 lbs 112 lbs 2,336'
2,650' 33"H x 22"W Composite 85 lbs 222 lbs 4,429'
5,300' 48"H x 22"W Steel 78 lbs 328 lbs 8,802'
10,000' 72"H x 22"W Steel 88 lbs 603 lbs 10,000'
General Guidelines When Using MaxCell in Various Applications
2" 1-CELL
For use in 1.5" and 2" conduits, the 2" 1-Cell product is designed to hold cables up to 0.85" in diameter in each cell.
• Standard color is white
• Color-coded pull tapes are preinstalled
• Factory lubricated
2 INCH – 1-CELL
2" 1-CELL PART NUMBERS
PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)
2" 1-Cell Product Standard color is
White (WH)
250 MXC2001XX250 MXD2001XX250 MXP2001XX250 MXR2001XX250
500-999 MXC2001XX500 MXD2001XX500 MXP2001XX500 MXR2001XX500
1,000-2,649 MXC2001XX1000 MXD2001XX1000 MXP2001XX1000 MXR2001XX1000
2,650-5,299 MXC2001XX2650 MXD2001XX2650 MXP2001XX2650 MXR2001XX2650
5,300-9,999 MXC2001XX5300 MXD2001XX5300 MXP2001XX5300 MXR2001XX5300
10,000 MXC2001XX10000 MXD2001XX10000 MXP2001XX10000 MXR2001XX10000
2" 1-CELL REEL SIZES AND WEIGHTS
DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.
PRODUCT LENGTH MAX PRODUCT ON REEL
2" 1-Cell Standard/Riser/Plenum
MXC2001
Prod. Wt: 28 lbs/1,000ft
500' 33"H x 15"W Composite 60 lbs 74 lbs 4,390'
1,000' 33"H x 15"W Composite 60 lbs 88 lbs 4,390'
2,650' 33"H x 15"W Composite 60 lbs 135 lbs 4,390'
5,300' 33"H x 22"W Composite 85 lbs 234 lbs 8,322'
10,000' 48"H x 22"W Steel 78 lbs 335 lbs 10,000'
2" 1-Cell MaxCell overriding incumbent cable in 2" conduit
MaxCell 2" 1-Cell (Equivalent to one 1.0" I.D. innerducts) This product was designed for use in 1.5" and 2" ducts.
It is designed to deploy an additional cable in a confined small conduit or innerduct.
2" 1-CELL APPLICATION GUIDE
*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).
MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 1.5" + MaxCell 2" 1-Cell 1 1 .85" 800' 1,500'
General Guidelines When Using MaxCell in Various Applications
File details come from the government source that posted it. Updated .