This is a construction specifications document for a telecommunications infrastructure project at Pu'ukohola Heiau National Historic Site in Hawaii. The National Park Service Pacific West Region project (PMIS No. 340780) involves replacing telecommunications lines from headquarters to the visitor center and includes detailed product specifications and installation requirements for fiber optic infrastructure components.

The project specifies several key components: a FHD-FWME2 wall mount fiber enclosure (2 ports, maximum 48 fibers, SPCC black coating, dimensions 10.2"x13.0"x2.3") for interconnecting and splicing applications; CommScope fiber optic cable (48-fiber, gel-filled stranded loose tube with singlemode and OM3 multimode fiber, 10.2mm diameter) meeting ANSI/ICEA S-87-640 and EN 187105 standards with operating temperatures of -40°C to +70°C; MaxCell fabric innerduct products in various configurations (2" through 4" sizes with 1- to 3-cell options) for cable protection and management; concrete polymer handholes (HPC 2436-36 Tier-22 rated) for access points; and associated termination cassettes, adapter panels, and splice trays for fiber management. The specifications include comprehensive technical data on mechanical performance (bend radius, tensile loads, compression resistance), environmental testing standards, and installation guidelines. All materials must comply with TIA/EIA standards, RoHS requirements, and ISO 9001 certification where applicable. The document was prepared in February 2026 and provides detailed product datasheets, dimensional drawings, and bill of materials for procurement and installation purposes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PU’UKOHOLA HEIAU NATIONAL

HISTORIC SITE (PUHE), HAWAI’I

REPLACE TELECOMMUNICATIONS LINES FROM

HEADQUARTERS TO THE VISITOR CENTER

PMIS No. 340780

CONSTRUCTION SPECIFICATIONS

NATIONAL PARK SERVICE

PACIFIC WEST REGION

PRODUCT INFORMATION

FEBRUARY 2026

Fiber Termination Cabinet

1www.fs.com

Designed to provide a convenient convergence point for interconnecting and splicing in wall mount applications.

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

Description

FHD Fiber Optic Wall Mount Enclosures can be used as an interconnect or cross-connect in any telecommunications room and can use

FHD series fiber adapter panels and cassettes (exclude 36F). Enclosures are designed to manage and organize fiber distribution in areas where space is limited.

Features

• Dual Doors with Slam Latch for Ease of Access.

• Optional Key/Lock Kit Secures Service-side Door or Customer-side Doors.

• Accepts FHD Series Adapter Panels, MTP Cassettes (Exclude 36F), and Splice Trays for Multiple Solution Capabilities.

• Removable Cable Entry/Exit Grommets Allow for Pre-terminated Fiber Trunk Installation, Cable Protection, and Minimizes Dust

Build-up.

• Ensure Signal Integrity, Proper Cable Routing, Bend Radius Control and Cable Protection.

FHD-FWME2 Wall Mount Fiber Enclosure

2www.fs.com

Product Specifications

2 Ports

Max. 48 Fibers

Wall-mountable

SPCC (Black Coating)

10.2''x13.0''x2.3'' (259.6x330.6x59.1mm)

FHD Series FAPs and Cassettes (Exclude 36F)

-25℃ to 50℃

-40℃ to 65 ℃

0℃ to 50℃

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

• TIA/EIA-568-C.3

• RoHS Compliant

• ISO9001 Certificate

Standards Compliance

Capacity

Fiber Count

Enclosure Type

Material

Dimensions (HxWxD)

Installation

Environmental Characteristics

Operating Temperature

Storage Temperature

Installation Temperature https://www.fs.com/

Grommet x4Slack Spool x2 Strain Relief Bracket x4

M4*8 Screw x6 and M4 Nut x10Cable Tie x2 Location Label x1

3www.fs.com

Accessories List

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

Key x2 Screwdriver x1

Assembly Structure Illustration

Grommet

Slack Spool

Key / Lock

Fiber Adapter Panel (2pcs sold separately)

Strain Relief Bracket

Layout and Dimensions

4www.fs.com

Dimensions are in inches. (Dimensions in parentheses are in millimeters).

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

[2

.6

[330.6]

[5 9.

1]

[209.4] 8.24

13.01

.2

2.

Front View

Bottom View

[63.1]

[59.1]

2.48

2.33

Side View

5www.fs.com

Product Application

I. Patch Cord Connections

II. Fiber Optic Splicing

① ② ③

Item No. #ID Description

1 #40234 1m (3ft) SC UPC to SC UPC Duplex Single Mode Fiber Patch Cable

2 #35484 6x SC Duplex, 12 Fibers OS2 Single Mode FHD Fiber Adapter Panel

3 #50550 FHD Fiber Optic Wall Mount Enclosure, 2-Door 2-Adapter Panel

① ③ ④ ⑤ ⑥

Item No.

Description

1m (3ft) 12 Fibers LC/UPC 9/125 Single Mode Color-Coded Fiber Optic Pigtail

24 Fibers Fusion Splice Tray, Plastic, 6.26"x4.13"x0.72"

Splice Tray Holder for FHD Wall Mount Enclosure

FHD Fiber Optic Wall Mount Enclosure, 2-Door 2-Adapter Panel

12x LC Duplex, 24 Fibers OS2 Single Mode FHD Fiber Adapter Panel

1m (3ft) Grade B LC UPC to LC UPC Duplex OS2 Fiber Patch Cable

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

#ID

②

#42459

#28774

#73717

#50550

#50550

#68294 https://www.fs.com/ https://www.fs.com/products/40234.html https://www.fs.com/products/35484.html https://www.fs.com/products/50550.html https://www.fs.com/products/42459.html https://www.fs.com/products/28774.html https://www.fs.com/products/73717.html https://www.fs.com/products/50550.html https://www.fs.com/products/35488.html https://www.fs.com/products/68294.html

III. MTP Cabling Management

6www.fs.com

① ② ③

Item No. #ID

1 #68294

2 #57341

3 #68102

4 #68540

5 #50550

Description

1m (3ft) Grade B LC UPC to LC UPC Duplex OS2 Fiber Patch Cable

2x MTP-12 to 12x LC Duplex, Type A, 24 Fibers OS2 FHD MTP/MPO Cassette

5m (16ft) MTP Female 12 Fibers OS2 9/125 Single Mode Trunk Cable, Type A

2x MTP-12 to 12x LC Duplex, Type AF, 24 Fibers OS2 FHD MTP/MPO Cassette

FHD Fiber Optic Wall Mount Enclosure, 2-Door 2-Adapter Panel

④ ⑤

Note:

The basic application and matching products for wall mount enclosures are shown for reference.

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

https://www.fs.com/ https://www.fs.com/products/68294.html https://www.fs.com/products/57341.html https://www.fs.com/products/68102.html https://www.fs.com/products/68540.html https://www.fs.com/products/50550.html

7www.fs.com

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

Fiber Enclosure Loading

I. Fiber Adapter Panel

#ID (OS2) #ID (OM4)

#35488 #51284

#35484 #41998

#35510 #35510

/ #52022

#183380 #183382

#183381 #183383

#336339 /

#147015 /

#143239 #143239

Description

24F, 12x LC Duplex Fiber Adapter Panel

12F, 16x SC Duplex Fiber Adapter Panel

12x MTP® Key Up to Key Down Fiber Adapter Panel

8x MTP® Key Up to Key Up Fiber Adapter Panel

6F, 6x ST Simplex Fiber Adapter Panel

8F, 8x ST Simplex Fiber Adapter Panel

12F, 12x LSH Simplex Fiber Adapter Panel

48F, 12x MDC 2-Port Duplex Fiber Adapter Panel

6-Port Multimedia Modular Panel with 6 Plastic Clips

II. MTP®/MPO Cassette

#ID (OS2) #ID (OM4)

#68401 #68402

/ #230555

#143164 #68399

#181822 #181823

#57016 #57017

#57037 #57038

#182641 #182642

#57341 #57342

Description

#68540 #68541

#ID (OM5)

#174246

#174247

#174248

#174249

#182643 #182644 /

8F, MTP®-8 to 4x LC Duplex Cassette, Universal

16F, 2x MTP®-8 to 8x LC Duplex Cassette, Universal

24F, 3x MTP®-8 to 12x LC Duplex Cassette, Universal

24F, 3x MTP®-8 to 2x LC Shuttered Duplex Cassette, Universal

12F, MTP®-12 to 6x LC Duplex Cassette, Type A

12F, MTP®-12 to 6x LC Duplex Cassette, Type AF

12F, MTP®-12 to 6x LC Duplex Cassette, Universal

24F, 2x MTP®-12 to 12x LC Duplex Cassette, Type A

24F, 2x MTP®-12 to 12x LC Duplex Cassette, Type AF

24F, 2x MTP®-12 to 12x LC Duplex Cassette, Universal https://www.fs.com/products/35488.html https://www.fs.com/products/51284.html https://www.fs.com/products/35484.html https://www.fs.com/products/41998.html https://www.fs.com/products/35510.html https://www.fs.com/products/52022.html https://www.fs.com/products/183380.html https://www.fs.com/products/183382.html https://www.fs.com/products/183381.html https://www.fs.com/products/183383.html https://www.fs.com/products/336339.html https://www.fs.com/products/147015.html https://www.fs.com/products/143239.html https://www.fs.com/products/68401.html https://www.fs.com/products/68402.html https://www.fs.com/products/230555.html https://www.fs.com/products/143164.html https://www.fs.com/products/68399.html https://www.fs.com/products/181822.html https://www.fs.com/products/181823.html https://www.fs.com/products/57016.html https://www.fs.com/products/57017.html https://www.fs.com/products/174246.html https://www.fs.com/products/57037.html https://www.fs.com/products/57038.html https://www.fs.com/products/174247.html https://www.fs.com/products/182641.html https://www.fs.com/products/182642.html https://www.fs.com/products/57341.html https://www.fs.com/products/57342.html https://www.fs.com/products/174248.html https://www.fs.com/products/68540.html https://www.fs.com/products/68541.html https://www.fs.com/products/174249.html https://www.fs.com/products/182643.html https://www.fs.com/products/182644.html https://www.fs.com/products/105333.html https://www.fs.com/products/105335.html https://www.fs.com/products/105334.html https://www.fs.com/products/105336.html

8www.fs.com

FHD-FWME2 WALL MOUNT FIBER ENCLOSURE DATASHEET

#57023 #57024

#68549 #68550

* MTP® is a registered trademark of US Conec Ltd.

* The US Conec MTP® connectors are fully compliant with the MPO standards.

Warranty Information

For FS product warranties, visit https://www.fs.com/policies/warranty.html

II. MTP®/MPO Cassette

#ID (OS2) #ID (OM4) #ID (OM5)Description

24F, MTP®-24 to 12x LC Duplex Cassette, Type A

24F, MTP®-24 to 12x LC Duplex Cassette, Type AF

III. Splice Tray

Fiber Count #ID

24F #28774

12F #28773

Description

24F, Fusion Splice Tray, Plastic, 6.26"x4.13"x0.72"

12F, Fusion Splice Tray, Plastic, 6.42"x3.96"x0.69"

Splice Tray Holder for FHD Wall Mount Enclosure N/A #73717 https://www.fs.com/products/57023.html https://www.fs.com/products/57024.html https://www.fs.com/products/68549.html https://www.fs.com/products/68550.html https://www.fs.com/policies/warranty.html

Fiber Optic Cable

760185942 | O-048-LN-CM-F12NS/25T/8W024

/5L024

©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025

Page of 1 4

Fiber OSP cable, LightScope® ZWP Single Jacket All-Dielectric, 48 fiber, Gel-Filled, Stranded Loose Tube, Singlemode + Multimode OM3, Feet jacket marking, Black jacket color

Product Classification Regional Availability Asia | Australia/New Zealand | EMEA | Latin America | North

America

Portfolio CommScope®

Product Type Fiber OSP cable

Product Series O-LN

General Specifications Cable Type Stranded loose tube

Construction Type Non-armored

Subunit Type Gel-filled

Filler, quantity 1

Jacket Color Black

Jacket Marking Feet

Subunit, quantity 4

Fibers per Subunit, quantity 12

Composite Fiber Count 24 + 24

Total Fiber Count 48

Dimensions Buffer Tube/Subunit Diameter 2.5 mm | 0.098 in

Diameter Over Jacket 10.2 mm | 0.402 in

Representative Image

©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025

Page of 2 4

Material Specifications Jacket Material PE

Mechanical Specifications Minimum Bend Radius, loaded 153 mm | 6.024 in

Minimum Bend Radius, unloaded 102 mm | 4.016 in

Tensile Load, long term, maximum 800 N | 179.847 lbf

Tensile Load, short term, maximum 2700 N | 606.984 lbf

Compression 22 N/mm | 125.623 lb/in

Compression Test Method FOTP-41 | IEC 60794-1 E3

Flex 25 cycles

Flex Test Method FOTP-104 | IEC 60794-1 E6

Impact 4.41 N-m | 39.032 in lb

Impact Test Method FOTP-25 | IEC 60794-1 E4

Strain See long and short term tensile loads

Strain Test Method FOTP-33 | IEC 60794-1 E1

Twist 10 cycles

Twist Test Method FOTP-85 | IEC 60794-1 E7

Vertical Rise, maximum 1199 m | 3,933.727 ft

Optical Specifications Fiber Type Composite MM/SM | G.652.D and G.657.A1 | OM3, LazrSPEED®

300 | OS2

©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025

Page of 3 4

Environmental Specifications Installation temperature -30 °C to +70 °C (-22 °F to +158 °F)

Operating Temperature -40 °C to +70 °C (-40 °F to +158 °F)

Storage Temperature -40 °C to +75 °C (-40 °F to +167 °F)

Cable Qualification Standards ANSI/ICEA S-87-640 | EN 187105

Environmental Space Aerial, lashed | Buried

Jacket UV Resistance UV stabilized

Water Penetration 24 h

Water Penetration Test Method FOTP-82 | IEC 60794-1 F5

Environmental Test Specifications Cable Freeze -2 °C | 28.4 °F

Cable Freeze Test Method FOTP-98 | IEC 60794-1 F15

Drip 70 °C | 158 °F

Drip Test Method FOTP-81 | IEC 60794-1 E14

Heat Age -40 °C to +85 °C (-40 °F to +185 °F)

Heat Age Test Method IEC 60794-1 F9

Low High Bend -30 °C to +60 °C (-22 °F to +140 °F)

Low High Bend Test Method FOTP-37 | IEC 60794-1 E11

Temperature Cycle -40 °C to +70 °C (-40 °F to +158 °F)

Temperature Cycle Test Method FOTP-3 | IEC 60794-1 F1

Packaging and Weights Cable weight 68 kg/km | 45.694 lb/kft

Regulatory Compliance/Certifications Agency Classification

ISO 9001:2015 Designed, manufactured and/or distributed under this quality management system

Included Products CS-5L-LT – LazrSPEED® 300 OM3 Bend-Insensitive Multimode

Fiber

CS-8W-LT – TeraSPEED® G652D/G657A1 Singlemode Fiber

* Footnotes

©2025 CommScope, Inc. All rights reserved. CommScope and the CommScope logo are registered trademarks of CommScope and/or its affiliates in the U.S. and other countries. For additional trademark information see https://www.commscope.com/trademarks. All product names, trademarks and registered trademarks are property of their respective owners. Revised: July 30, 2025

Page of 4 4

Operating Temperature Specification applicable to non-terminated bulk fiber cable

Handhole

SECTION A-A SECTION B-B

BILL OF MATERIALS

DESCRIPTIONPART NUMBERQTYUNIT QTYITEM

CONCRETE COMPOSITE BOX MIX BRUCE1000350381.996 ft^31.996 ft^31

HPC PLUGS 5/8X1-3/8-14-2 PE-LD67 BLK100022548212

SQUARE NUT 1/2-13 304SS100021840213

INSERT THREADED METAL 3/8-16 UNC 1IN100002783414

A A

B

B i d w

SHEET:

REV:

B-1

3/11/2019 10/31/2022

MODIFIED:CREATED:

PART #: DRAWN BY:

DESCRIPTION:

HPC 2436-36 Polymer Box, Tier-22, 1/2-13 SS Nut

DESIGN/TEST LOAD:

244.06 lbs

200022186 T.Larson

©2022 Jensen Precast- All rights reserved.

Unless expressly authorized by Jensen Precast any use or duplication is strictly prohibited under penalty of civil action or codes.

APPROX. WEIGHT:

22.5/33.75 kip

DESIGN SPEC:

ANSI/SCTE-77

AGENCY:

AGENCY SPEC: LOADING SPEC:

Tier-22

33 7/8"

35 7/8"

36"

29"

22 1/4"

24 1/4"

REVISION HISTORY

REV DESCRIPTION DATE BY

A INITIAL RELEASE

35"

3" 3"

23 3/8"

17 3/8"

35 7/8"

24 1/4"

3 7/8"

12 3/4"

3"

3" 3"

2 3

Fabric Innerduct

888.387.3828 | WWW.MAXCELL.US |

PRODUCT LINES & TYPES

MAXCELL IS OFFERED IN MULTIPLE PRODUCT LINES & TYPES

Standard, Detectable, Plenum & Riser. MaxCell product types refer to the different conduit application sizes and number of cells/pathways per product type. Most product lines are offered in all of the product type variations.

STANDARD MAXCELL

A versatile solution for the complex problems faced by today’s engineers, contractors and network providers. Manufactured from internally designed and produced materials, this model yields superior performance over existing rigid innerduct.

Standard MaxCell is the primary product line used in common outside plant applications, including long lines, under-bridge; road, river and rail borings;

under streets and all the way to building entrance points. In dense multiple cables and multiple MaxCell pack installations where the conduit path is not clear to surface markers, Standard MaxCell is often partnered with Detectable MaxCell so that path or service interruption points can be easily located.

Standard MaxCell is available for conduit sizes ranging from 1" to 4", and in 1-, 2- and 3-cell configurations — giving you the flexibility to choose the right product for your system and applications.

FEATURES & ADVANTAGES:

• �Melt point of 419°F — almost 2X of HDPE

• Resistant to ground chemicals and petroleum products

• Pre-lubed for lower friction during MaxCell and cable installation

• Pull tape included

| 888.387.3828 | WWW.MAXCELL.US

*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).

MaxCell 4" 3-Cell (Equivalent to three 1.5" I.D. innerducts) This product was designed for use in 4" or larger ducts. Multiple combinations of large and medium cable sizes are applicable. Since larger cable applications are anticipated, the number of cables and packs that can be placed is reduced; therefore, a smaller number of cables is available.

MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 4" MaxCell 4" 3-Cell 2 6 1.5" 1,250' 2,000'

5" MaxCell 4" 3-Cell 3 9 1.5" 1,250' 2,000'

6" MaxCell 4" 3-Cell 4 12 1.5" 1,250' 2,000'

4" 3-CELL PART NUMBERS

PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)

4" 3-Cell Product Standard color is Green

(GR)

250 MXC4003XX250 MXD4003XX250 MXP4003XX250 MXR4003XX250

500-999 MXC4003XX500 MXD4003XX500 MXP4003XX500 MXR4003XX500

1,000-2,649 MXC4003XX1000 MXD4003XX1000 MXP4003XX1000 MXR4003XX1000

2,650-5,299 MXC4003XX2650 MXD4003XX2650 MXP4003XX2650 MXR4003XX2650

5,300-9,999 MXC4003XX5300 MXD4003XX5300 MXP4003XX5300 MXR4003XX5300

10,000 MXC4003XX10000 MXD4003XX10000 MXP4003XX10000 MXR4003XX10000

4 INCH – 3-CELL

4" 3-CELL

For use in 4" or larger conduits, the 4" 3-Cell product is designed to hold larger backbone cables up to 1.5" in diameter in each cell.

Up to two packs can be placed in a 4" conduit.

• Standard color is green

• Color-coded pull tapes are preinstalled

• Factory lubricated

4" 3-Cell packs with 6 1" OD cables in 4" conduit

4" 3-Cell packs overriding existing cable plant

Add 8.5 lbs per 1,000ft for Detectable product weight estimates.

4" 3-CELL REEL SIZES AND WEIGHTS

DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.

PRODUCT LENGTH MAX PRODUCT ON REEL

4" 3-Cell Standard/Riser/Plenum

MXC4003

Product Wt:

107.5 lbs/1,000ft

500' 33"H x 15"W Composite 60 lbs 114 lbs 1,133'

1,000' 33"H x 15"W Composite 60 lbs 168 lbs 1,133'

2,650' 48"H x 22"W Steel 78 lbs 340 lbs 4,267'

5,300' 72"H x 22"W Steel 88 lbs 658 lbs 8,099'

10,000' 72"H x 30"W Steel 106 lbs 1,181 lbs 10,000'

4" 3-CELL APPLICATION GUIDE General Guidelines When Using MaxCell in Various Applications

3 INCH – 3-CELL

3" 3-CELL

For use in 3" or larger conduits, the 3" 3-Cell product is designed to hold cables up to 1.05" in diameter in each cell. Up to 3 packs can be placed in a 4" conduit.

• Standard colors are black, blue or red

• Color-coded pull tapes are preinstalled

• Factory lubricated

3" 3-Cell pack overriding existing cable plant in 4" conduit

MaxCell 3" 3-Cell (Equivalent to three 1.25" I.D. innerducts) This product was designed for use in 3" or larger ducts.

Multiple combinations of large, medium and smaller cable sizes are applicable and anticipated.

*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).

MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 3" MaxCell 3" 3-Cell 2 6 1.05" 1,250' 2,000'

4" MaxCell 3" 3-Cell 3 9 1.05" 1,250' 2,000'

5" MaxCell 3" 3-Cell 4 12 1.05" 1,250' 2,000'

6" MaxCell 3" 3-Cell 5 15 1.05" 1,250' 2,000'

3" 3-CELL PART NUMBERS

PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)

3" 3-Cell Product Standard colors are either Black (BK) or Blue (BL) or Red (RD)

250 MXC3456XX250 MXD3456XX250 MXP3456XX250 MXR3456XX250

500–999 MXC3456XX500 MXD3456XX500 MXP3456XX500 MXR3456XX500

1,000–2,649 MXC3456XX1000 MXD3456XX1000 MXP3456XX1000 MXR3456XX1000

2,650–5,299 MXC3456XX2650 MXD3456XX2650 MXP3456XX2650 MXR3456XX2650

5,300–9,999 MXC3456XX5300 MXD3456XX5300 MXP3456XX5300 MXR3456XX5300

10,000 MXC3456XX10000 MXD3456XX10000 MXP3456XX10000 MXR3456XX10000

3" 3-CELL REEL SIZES AND WEIGHTS

DESCRIPTION STD. PRODUCT

LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT

OF REEL

REEL WT. W/ STD.

PRODUCT LENGTH MAX PRODUCT ON REEL

3" 3-Cell Standard/Riser/Plenum

MXC3456

Product Wt:

88.5 lbs/1,000ft

500' 33"H x 15"W Composite 60 lbs 104 lbs 1,407'

1,000' 33"H x 15"W Composite 60 lbs 149 lbs 1,407'

2,650' 33"H x 22"W Composite 85 lbs 320 lbs 2,667'

5,300' 48"H x 22"W Steel 78 lbs 525 lbs 5,300'

10,000' 72"H x 30"W Steel 106 lbs 991 lbs 10,000'

3" 4-CELL STANDARD MXC3004 | Product Wt: 96 lbs/1,000ft Call for information

3" 3-CELL APPLICATION GUIDE General Guidelines When Using MaxCell in Various Applications

3" 3-Cell packs, 9 cables in 4" conduit

Add 8.5 lbs per 1,000ft for Detectable product weight estimates.

2" 3-Cell pack in 2" conduit2" 3-Cell packs, 6 cables in 3" conduit

MaxCell 2" 3-Cell (Equivalent to three 1.0" I.D. innerducts) This product was designed for use in 2" ducts where three cables are being placed.

2" 3-CELL APPLICATION GUIDE

2 INCH – 3-CELL

2" 3-CELL

For use in 2" conduits, the 2" 3-Cell product is designed to hold three cables up to 0.85" in diameter in each cell.

• Standard color is yellow

• Color-coded pull tapes are preinstalled

• Factory lubricated

MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 2" MaxCell 2" 3-Cell 1 3 .85" 800' 1,500'

2" 3-CELL PART NUMBERS

PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)

2" 3-Cell Product Standard color is

Yellow (YL)

250 MXC2003XX250 MXD2003XX250 MXP2003XX250 MXR2003XX250

500-999 MXC2003XX500 MXD2003XX500 MXP2003XX500 MXR2003XX500

1,000-2,649 MXC2003XX1000 MXD2003XX1000 MXP2003XX1000 MXR2003XX1000

2,650-5,299 MXC2003XX2650 MXD2003XX2650 MXP2003XX2650 MXR2003XX2650

5,300-9,999 MXC2003XX5300 MXD2003XX5300 MXP2003XX5300 MXR2003XX5300

10,000 MXC2003XX10000 MXD2003XX10000 MXP2003XX10000 MXR2003XX10000

2" 3-CELL REEL SIZES AND WEIGHTS

DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.

PRODUCT LENGTH MAX PRODUCT ON REEL

2" 3-Cell Standard/Riser/Plenum

MXC2003

Prod. Wt: 76 lbs/1,000ft

500' 33"H x 15"W Composite 60 lbs 98 lbs 1,592'

1,000' 33"H x 15"W Composite 60 lbs 136 lbs 1,592'

2,650' 33"H x 22"W Composite 85 lbs 287 lbs 3,018'

5,300' 48"H x 22"W Steel 78 lbs 458 lbs 5,997'

10,000' 72"H x 22"W Steel 88 lbs 848 lbs 10,000'

General Guidelines When Using MaxCell in Various Applications

Add 8.5 lbs per 1000ft for Detectable product weight estimates

*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).

2 INCH – 2-CELL

MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 2" MaxCell 2" 3-Cell 1 2 .85" 800' 1,500'

2" 2-CELL

For use in 2" conduits, the 2" 2-Cell product is designed to hold two cables up to 0.85" in diameter in each cell. It's ideal for overlay when one cable exists in a 2" conduit.

• Standard color is black

• Color-coded pull tapes are pre-installed

• Factory lubricated

MaxCell 2" 2-Cell (Equivalent to two 1.0" I.D. innerducts) This product was designed for use in 2" ducts where two cables are being placed.

*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).

2" 2-CELL APPLICATION GUIDE

2" 2-Cell pack in 2" conduit 2" 2-Cell pack overriding incumbent cable in 2" conduit

2" 2-CELL PART NUMBERS

PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)

2" 2-Cell Product Standard color is

Black (BK)

250 MXC2002XX250 MXD2002XX250 MXP2002XX250 MXR2002XX250

500-999 MXC2002XX500 MXD2002XX500 MXP2002XX500 MXR2002XX500

1,000-2,649 MXC2002XX1000 MXD2002XX1000 MXP2002XX1000 MXR2002XX1000

2,650-5,299 MXC2002XX2650 MXD2002XX2650 MXP2002XX2650 MXR2002XX2650

5,300-9,999 MXC2002XX5300 MXD2002XX5300 MXP2002XX5300 MXR2002XX5300

10,000 MXC2002XX10000 MXD2002XX10000 MXP2002XX10000 MXR2002XX10000

2" 2-CELL REEL SIZES AND WEIGHTS

DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.

PRODUCT LENGTH MAX PRODUCT ON REEL

2" 2-Cell Standard/Riser/Plenum

MXC2002

Prod. Wt: 51.5 lbs/1,000ft

500' 33"H x 15"W Composite 60 lbs 86 lbs 2,336'

1,000' 33"H x 15"W Composite 60 lbs 112 lbs 2,336'

2,650' 33"H x 22"W Composite 85 lbs 222 lbs 4,429'

5,300' 48"H x 22"W Steel 78 lbs 328 lbs 8,802'

10,000' 72"H x 22"W Steel 88 lbs 603 lbs 10,000'

General Guidelines When Using MaxCell in Various Applications

2" 1-CELL

For use in 1.5" and 2" conduits, the 2" 1-Cell product is designed to hold cables up to 0.85" in diameter in each cell.

• Standard color is white

• Color-coded pull tapes are preinstalled

• Factory lubricated

2 INCH – 1-CELL

2" 1-CELL PART NUMBERS

PRODUCT (STD. COLOR) FOOTAGE (FEET) STANDARD PRODUCT (MXC) DETECTABLE PRODUCT (MXD) PLENUM PRODUCT (MXP) RISER PRODUCT (MXR)

2" 1-Cell Product Standard color is

White (WH)

250 MXC2001XX250 MXD2001XX250 MXP2001XX250 MXR2001XX250

500-999 MXC2001XX500 MXD2001XX500 MXP2001XX500 MXR2001XX500

1,000-2,649 MXC2001XX1000 MXD2001XX1000 MXP2001XX1000 MXR2001XX1000

2,650-5,299 MXC2001XX2650 MXD2001XX2650 MXP2001XX2650 MXR2001XX2650

5,300-9,999 MXC2001XX5300 MXD2001XX5300 MXP2001XX5300 MXR2001XX5300

10,000 MXC2001XX10000 MXD2001XX10000 MXP2001XX10000 MXR2001XX10000

2" 1-CELL REEL SIZES AND WEIGHTS

DESCRIPTION STD. PRODUCT LENGTH REEL SIZE TYPE OF REEL TARE WEIGHT OF REEL REEL WT. W/ STD.

PRODUCT LENGTH MAX PRODUCT ON REEL

2" 1-Cell Standard/Riser/Plenum

MXC2001

Prod. Wt: 28 lbs/1,000ft

500' 33"H x 15"W Composite 60 lbs 74 lbs 4,390'

1,000' 33"H x 15"W Composite 60 lbs 88 lbs 4,390'

2,650' 33"H x 15"W Composite 60 lbs 135 lbs 4,390'

5,300' 33"H x 22"W Composite 85 lbs 234 lbs 8,322'

10,000' 48"H x 22"W Steel 78 lbs 335 lbs 10,000'

2" 1-Cell MaxCell overriding incumbent cable in 2" conduit

MaxCell 2" 1-Cell (Equivalent to one 1.0" I.D. innerducts) This product was designed for use in 1.5" and 2" ducts.

It is designed to deploy an additional cable in a confined small conduit or innerduct.

2" 1-CELL APPLICATION GUIDE

*�Use of OFNR cable may result in reduced pulling lengths. Designers should make every effort to conform to industry standards with regard to distances between any two pull points (generally 600 to 1,000 feet), number of bends (maximum of two 90 degree bends or a total of 180 degrees) between any two pull points, and proofing of conduit pathway using appropriately sized mandrels (normally ¼ to ½ inch less than the inside diameter of the conduit).

MIN CONDUIT ID SUGGESTED PRODUCT MAX # OF PACKS MAX # OF CABLES MAXIMUM CABLE DIAMETER PER CELL REC. PULL LENGTH* MAX PULL LENGTH* 1.5" + MaxCell 2" 1-Cell 1 1 .85" 800' 1,500'

General Guidelines When Using MaxCell in Various Applications

File details come from the government source that posted it. Updated .