Appendix B
June 14, 2022
Jennifer Claster, RLA Project Manager National Park Service Denver Service Center, Design and Construction 12795 West Alameda Parkway Lakewood, CO 80228-2838
Subject: Discussion of Existing Hazardous Materials Findings for 44 multiple non-historic structures for CACO 304727 Demolish Excess Structures to Improve Safety, Operations, and Promote Financial Sustainability Project
Dear Ms. Claster, WSP USA Inc. (WSP) is pleased to submit this updated summary to the National Park Service (NPS) detailing a review and evaluation of existing hazardous material reports and memoranda provided to us by NPS as well as our visual investigation of all properties.
BACKGROUND
The 44 structures for which a review of existing reports was conducted include: twenty five (25) structures at the Highlands Center, three (3) Mitre sites, sixteen (16) individual residential properties (including 2 foundations). These structures are over 60 years old, of low-quality construction, and present an immediate health and/or safety hazard. Many of the buildings are structurally compromised. The scope of this project is to remove/demolish these structures, their utilities, and impervious surfaces and to grade to natural conditions to allow restoration.
WSP reviewed all information related to Asbestos Containing Materials (ACM), Lead-based Paints (LBP), PCBs and Universal Waste which was provided by the NPS, in order to determine what additional testing and further documentation is required for the structures in this project’s scope of work.
On May 23rd through May 26th, 2022 WSP conducted a visual investigation of all properties for suspect hazardous materials to verify and supplement the findings from existing reports and memoranda.
REVIEW METHODOLOGY
All inspection and sampling data, laboratory analysis reports, assumptions, sample location plans (if any), licensing and certification information was reviewed. If not enough information or sampling of specific suspect hazardous materials was conducted that information was noted in the summary tables.
If the sampling and analysis of suspect materials recorded in existing reports did not conform to current federal and state sampling requirements and regulations, that information was noted as well. In such cases, these materials must be assumed to be hazardous until additional sampling is performed or the material is treated as hazardous.
The updated summaries of information related to ACM, LBP, PCBs and Universal Waste inspections found in existing reports is provided in table format in Appendix 1.
VISUAL INVESTIGATION METHODOLOGY
A thorough visual investigation of all suspect hazardous materials at all structures in the project scope of work was completed to determine the validity of results from the existing reports and to determine if they missed other suspect materials. In the absence of sampling of suspect materials for laboratory analysis, the suspect materials were assumed (presumed) to be hazardous. The suspect/assumed ACM, LBP, PCBs and Universal Waste were documented for locations, quantities and condition, as applicable.
CONCLUSION
A. Summary of Existing Information
In summary, there were some existing reports which listed confirmed ACM and confirmed Non-ACM materials, but did not have any supporting documents such as field data logs and chains of custody, lab analysis reports, sample location drawings, etc. Other Letters/memoranda noted that there were no ACM but again, with no supporting documentation.
There were several existing reports which listed inspection/testing results for suspect Lead-based Paints.
There were also Letters/memoranda which noted that there was no LBP but with no supporting documentation.
B. Summary of Field Visual Investigation
During the visual investigation of all suspect hazardous materials by the WSP team, many more suspect hazardous materials (specifically asbestos and lead paints) were found in all properties than were previously documented.
The updated ACM, LBP, PCBs-Universal Waste Inventories have sub-total quantities, where appropriate, based on the visual investigation and sub-total quantities based on previously provided information.
1. Summary of ACM
The total quantities of ACM at the Highlands Center based on visual investigation are approx.
471,000 SF (square feet) and 28,000 LF (linear feet), which is almost 3 times the quantities calculated based on reports provided by NPS.
The total quantities of ACM at the Mitre Sites based on visual investigation are approx. 54,000 SF and 1,500 LF. No quantities were given in reports provided by NPS.
The total quantities of ACM in Private Homes based on visual investigation are approx. 130,000 SF, 4000 LF and 90 CF (cubic feet). No quantities were given in reports provided by NPS.
2. Summary of LBP
The total quantity of LBP at the Highlands Center based on visual investigation is approx. 22,000 SF, which is 1.4 times higher than the quantity calculated based on reports provided by NPS.
The total quantities of LBP at the Mitre Sites based on visual investigation is approx. 4,000 SF. No quantities were given in reports provided by NPS.
The total quantities of LBP at the Private Homes based on visual investigation is approx. 12,000 SF. No quantities were given in reports provided by NPS.
3. Summary of PCBs and Universal Waste
In general, more universal waste items such as light fixtures, ballasts, water fountains, refrigerators and thermostats were found during visual investigation than was reported in information provided by NPS. However, the comparative difference is not significant.
In summary, the difference between previously reported ACM and LBP and assumed suspect ACM and LBP found during visual investigation is sufficiently great to warrant a full inspection including sampling of and laboratory analysis of all suspect materials.
If you have any questions, or require additional information, please do not hesitate to contact us.
Sincerely yours, Michael Gelfand Timothy Higginson Manager, Industrial Hygiene & Hazmat Services, Project Manager Earth & Environment
Encl.: Appendix 1 - Inventories of Hazardous Materials
USTH682761
Snapshot
APPENDIX 1
ACM, LBP AND UNIVERSAL WASTE INVENTORIES BASED ON VISUAL
INVESTIGATION
CACO ACM Inspection Inventory Page 1 of 16
Summary of Visual Inspection Results and Previously-completed Reports for Asbestos Containing Materials (ACM)
Line # Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
1 Throughout 1st and 2nd Floor 12”x12” Floor Tiles and 9”x9” Floor Tiles and assoc. Mastics, Carpet Glue Damaged Non-friable
2 Throughout 1st and 2nd Floor Vapor Barrier under Wood Flooring (between layers of wood floor) Damaged
4,400 SF
Non-friable
3 Throughout 1st and 2nd Floor Bathrooms
Tar Paper under Ceramic Floor Tiles Damaged 220 SF Non-friable
4 Throughout 1st and 2nd Floors, Attic, Exterior Braided Wiring Insulation Damaged 500 LF Non-Friable
5 Throughout 1st and 2nd Floor Bathrooms
Ceramic Wall Tile and Floor Tile Grout/Mortar/Backing Damaged 750 SF Friable
6 Throughout 1st and 2nd Floor Bathrooms
Tar Paper under Ceramic Floor Tiles Damaged 220 SF Non-friable
7 Throughout 1st and 2nd Floor (Hallways, Stairwells, Offices) Glue behind Wall Paneling Damaged 3,200 SF Non-friable
8 Throughout 1st and 2nd Floor Sheetrock Walls and Ceilings & Assoc. Joint Compound Damaged 12,000 SF Friable
9 1st and 2nd Floor Bathrooms Wall and Ceiling Plaster (2 coats) Damaged 2,000 SF Friable
10 1st and 2nd Floor Bathrooms Aircell Pipe & Fittings
Insulation concealed in Wall Chases
Damaged 60 LF Friable
11 Throughout 1st and 2nd Floor Stairwells Glue to Vinyl Stair Treads Damaged 160 SF Non-Friable
12 1st Floor Boiler Closet Transite Board Wall and Ceiling Panels Damaged 35 SF Non-Friable
13 Attic Tar Paper assoc. with Attic Fiberglass Insulation Damaged 3,100 SF Non-friable
14 Building Exterior Vapor Barrier behind Wood Shake Siding Damaged 5,250 SF Non-friable
Building 9
Building Roof, including Overhangs Roofing Tar, Tar Paper Damaged 5,000 SF Non-Friable
Demolish building with ACM in place
Building is structurally compromised; all materials should be removed as contaminated ACM
Bldg. Sub-totals 42,365 SF
560 LF
Previous Quantities 6,114 SF
16 Throughout 1st and 2nd Floor 12”x12” Floor Tiles and 9”x9” Floor Tiles and assoc. Mastics, Carpet Glue Damaged Non-friable Class II Work –
Non-Friable
Building 10
Throughout 1st and 2nd Floor Vapor Barrier under Wood Flooring (between layers of wood floor) Damaged
4,400 SF
Non-friable Class II Work – Non-Friable
Remove carpet, wood floor between vapor barrier and top floor tiles as contaminated ACM
CACO ACM Inspection Inventory Page 2 of 16
Line # Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
18 Building 10 Throughout 1st and 2nd Floors, Attic, Exterior Braided Wiring Insulation Damaged 500 LF Non-Friable Class II Work –
Non-Friable
19 Throughout 1st and 2nd Floor Bathrooms
Ceramic Wall Tile and Floor Tile Grout/Mortar/Backing Damaged 750 SF Friable Class I Work – Full containment
20 Throughout 1st and 2nd Floor Bathrooms
Tar Paper under Ceramic Floor Tiles Damaged 220 SF Non-friable Class II Work –
Non-Friable
Throughout 1st and 2nd Floor
(Hallways, Stairwells, Offices)
Glue behind Wall Paneling Damaged 3,200 SF Non-friable Class II Work – Non-Friable
22 Throughout 1st and 2nd Floor Sheetrock Walls and Ceilings & Assoc. Joint Compound Damaged 12,000 SF Friable Class I Work – Full containment
23 1st and 2nd Floor Bathrooms Wall and Ceiling Plaster (2 coats) Damaged 2,000 SF Friable Class I Work – Full containment
24 1st and 2nd Floor Bathrooms Aircell Pipe & Fittings
Insulation concealed in Wall Chases
Damaged 60 LF Friable Class I Work – Full containment
25 Throughout 1st and 2nd Floor Stairwells Glue to Vinyl Stair Treads Damaged 160 SF Non-Friable Class II Work –
Non-Friable
26 1st Floor Boiler Closet Transite Board Wall and Ceiling Panels Damaged 35 SF Non-Friable Class II Work –
Non-Friable
27 Attic Tar Paper assoc. with Attic Fiberglass Insulation Damaged 3,100 SF Non-friable Class II Work –
Non-Friable Under loose FG attic insulation
28 Building Exterior Vapor Barrier behind Wood Shake Siding Damaged 5,250 SF Non-friable Class II Work –
Non-Friable
29 Building Roof, including Overhangs Roofing Tar, Tar Paper Damaged 5,000 SF Non-Friable Class II Work –
Non-Friable
Bldg. Sub-totals 42,365 SF
560 LF
Previous Quantities
6,114 SF (If assumed typical by Bldg. 9)
30 Building 11 Throughout 1st and 2nd Floor 12”x12” Floor Tiles and 9”x9” Floor Tiles and assoc. Mastics, Carpet Glue Damaged Non-friable Class II Work –
Non-Friable
31 Throughout 1st and 2nd Floor Vapor Barrier under Wood Flooring (between layers of wood floor) Damaged
4,400 SF
Non-friable Class II Work – Non-Friable
Remove carpet, wood floor between vapor barrier and top floor tiles as contaminated ACM
32 Throughout 1st and 2nd Floors, Attic, Exterior Braided Wiring Insulation Good 500 LF Non-Friable Class II Work –
Non-Friable
33 Throughout 1st and 2nd Floor Bathrooms
Ceramic Wall Tile and Floor Tile Grout/Mortar/Backing Damaged 750 SF Friable Class I Work – Full containment
34 Throughout 1st and 2nd Floor Bathrooms
Tar Paper under Ceramic Floor Tiles Good 220 SF Non-friable Class II Work –
Non-Friable
CACO ACM Inspection Inventory Page 3 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
35 Building 11 Throughout 1st and 2nd Floor
(Hallways, Stairwells, Offices)
Glue behind Wall Paneling Damaged 3,200 SF Non-friable Class II Work – Non-Friable
36 Throughout 1st and 2nd Floor Sheetrock Walls and Ceilings & Assoc. Joint Compound Damaged 12,000 SF Friable Class I Work – Full containment
37 1st and 2nd Floor Bathrooms Wall and Ceiling Plaster (2 coats) Good 2,000 SF Friable Class I Work – Full containment
38 1st and 2nd Floor Bathrooms Aircell Pipe & Fittings
Insulation concealed in Wall Chases
Good 60 LF Friable Class I Work – Full containment
39 Throughout 1st and 2nd Floor Stairwells Glue to Vinyl Stair Treads Good 160 SF Non-Friable Class II Work –
Non-Friable
40 1st Floor Boiler Closet Transite Board Wall and Ceiling Panels Good 35 SF Non-Friable Class II Work –
Non-Friable
41 2nd Floor Bathroom Sink Undercoating Damaged 15 SF Non-friable Class II Work – Non-Friable
42 Attic Tar Paper assoc. with Attic Fiberglass Insulation Damaged 3,100 SF Non-friable Class II Work –
Non-Friable Under loose FG attic insulation
43 Building Exterior Vapor Barrier behind Wood Shake Siding Damaged 5,250 SF Non-friable Class II Work –
Non-Friable
44 Building Roof, including Overhangs Roofing Tar, Tar Paper Good 5,000 SF Non-Friable Class II Work –
Non-Friable
Bldg. Sub-totals 42,380 SF
560 LF
Previous Quantities
6,114 SF (If assumed typical by Bldg. 9)
45 Building 12 Throughout 1st and 2nd Floor 12”x12” Floor Tiles and 9”x9” Floor Tiles and assoc. Mastics, Carpet Glue
Good/ Damaged Non-Friable Class II Work –
Non-Friable
46 Throughout 1st and 2nd Floor Vapor Barrier under Wood Flooring (between layers of wood floor) Damaged
4,400 SF
Non-friable Class II Work – Non-Friable
Remove carpet, wood floor between vapor barrier and top floor tiles as contaminated ACM
47 Throughout 1st and 2nd Floors, Attic, Exterior Braided Wiring Insulation Good 500 LF Non-Friable Class II Work –
Non-Friable
48 Throughout 1st and 2nd Floor Bathrooms
Ceramic Wall Tile and Floor Tile Grout/Mortar/Backing Damaged 750 SF Friable Class I Work – Full containment
49 Throughout 1st and 2nd Floor Bathrooms
Tar Paper under Ceramic Floor Tiles Damaged 220 SF Non-friable Class II Work –
Non-Friable
50 Throughout 1st and 2nd Floor Sheetrock Walls and Ceilings & Assoc. Joint Compound Damaged 12,000 SF Friable Class I Work – Full containment
51 Throughout 1st and 2nd Floor Tar Paper assoc. with Bldg.
Fiberglass Wall Insulation Damaged 5,250 SF Non-Friable Class II Work –
Non-Friable
52 1st and 2nd Floor Hallways, CFO Room Glue behind Wall Paneling Damaged 3,200 SF Non-Friable Class II Work –
CACO ACM Inspection Inventory Page 4 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
53 1st and 2nd Floor Bathrooms Wall and Ceiling Plaster (2 coats) Damaged 2,000 SF Friable Class I Work – Full containment
54 1st and 2nd Floor Bathrooms Ceramic Wall Tile Grout/Mortar/Backing Damaged 1,000 SF Non-Friable Class II Work –
Non-Friable
55 1st and 2nd Floor Bathrooms Aircell Pipe & Fittings Insulation concealed in Wall Chases Damaged 60 LF Friable Class I Work – Full containment
56 1st and 2nd Floor Stairwells Glue to Vinyl Stair Treads Damaged 160 SF Non-Friable Class II Work – Non-Friable
57 1st Floor Boiler Closet Transite Board Wall and Ceiling Panels Damaged 35 SF Non-Friable Class II Work –
Non-Friable
58 Attic Tar Paper assoc. with Attic Fiberglass Insulation Damaged 3,100 SF Non-friable Class II Work –
Non-Friable Under loose FG attic insulation
59 Building Exterior Vapor Barrier behind Wood Shake Siding Damaged 5,250 SF Non-friable Class II Work –
Non-Friable
Building 12
Building Roof, including Overhangs Roofing Tar, Tar Paper Damaged 5,000 SF Non-Friable Class II Work –
Non-Friable
Bldg. Sub-totals 42,365 SF
560 LF
Previous Quantities
6,114 SF (If assumed typical by Bldg. 9)
61 Building 18 - Dining Hall
Service/Dining Area, Offices
9”x9” Floor Tiles and assoc.
Mastic, Carpet Mastic Damaged 2,700 SF Non-friable Class II Work –
Non-Friable Remove carpet as contaminated ACM
62 Service Area, Kitchens, Bathroom, Utility Rm.
Ceramic Floor Tile Mortar/Backing Damaged 1,850 SF Non-friable Class II Work –
Non-Friable
63 Throughout Electrical Wiring Insulation Damaged 600 LF Non-friable Class II Work – Non-Friable
64 Kitchens 2’x4’ Suspended Ceiling Tiles Damaged 900 SF Friable Class I Work – Full containment
65 Kitchens, Bathroom, Utility Rm.
Sheetrock Ceiling and assoc.
Joint Compound Damaged 710 SF Friable Class I Work – Full containment
66 Kitchens, Bathroom Ceramic Wall Tile Mortar/Glue Damaged 2,300 SF Non-friable Class II Work –
Non-Friable
67 Kitchen Main Panel Arc Shields Damaged 2 SF Non-friable Class II Work – Non-Friable
68 Kitchens Fiberboard Ceiling Glue, above 2’x4’ Ceiling Tiles Damaged 630 SF Non-friable Class II Work –
Non-Friable
69 Dining and Service areas Tar Paper assoc. with Fiberglass Ceiling Insulation Damaged 2,400 SF Non-friable Class II Work –
Non-Friable
70 Office 1, Dining/Service areas
Sheetrock Walls and assoc.
Joint Compound Damaged 2,450 SF Friable Class I Work – Full containment
71 Exterior Vapor Barrier behind Wood Siding Damaged 3,600 SF Non-friable Class II Work –
CACO ACM Inspection Inventory Page 5 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
72 Roof Roof Shingles and Tar Paper Damaged 5,400 SF Non-friable Class II Work – Non-Friable
Building 18 - Dining Hall Roof Roof Flashing at Chimney Damaged 4 SF Non-friable Class II Work –
Non-Friable
Bldg. Sub-totals 22,946 SF
600 LF
Previous Quantities
2,545 SF
50 LF
Theater Area, Office 1, Office 2, Office 3, Janitor’s Closet
9”x9” Floor Tiles, Brown (2 layers separated by plywood) & Associated Black Mastic
Good 1,200 SF Non-Friable Class II Work – Non-Friable
Remove plywood as contaminated ACM
75 Men’s and Ladies’ Bathrooms
12”x12” Floor Tiles, Tan and Associated Mastic Over
Brown Floor Tiles (2 layers separated by plywood)
Good 160 SF Non-Friable Class II Work – Non-Friable
Remove plywood as contaminated ACM
76 Floors Throughout Yellow Carpet Glue
Associated with Burgundy Carpet
Good 1,200 SF Non-Friable Class II Work – Non-Friable
Remove carpet as contaminated ACM
77 Crawl Space Under Ladies’ Bathroom, Bathroom Walls
Aircell Pipe & Fittings Insulation Damaged 33 LF Friable Class I Work – Full containment
78 Crawl Space Under Ladies’ Bathroom
Pipe Insulation Debris And Contaminated Soil Damaged 20 SF Friable Class I Work – Full containment
79 Exterior Roof 3-Tab Roof Shingles And Associated Cements Damaged 1,600 SF Non-Friable Class II Work –
Non-Friable
80 Sound-Proofed Room Walls Yellow Glue to Wood Panels Good 180 SF Non-Friable Class II Work – Non-Friable
81 Sound-Proofed Room Walls 1’x1’ Textured Tiles & Associated Black Glue Dots Good 180 SF Non-Friable Class II Work –
Non-Friable
82 Attic Backing to Fiberglass Insulation Damaged 1,350 SF Non-Friable Class II Work –
Non-Friable
Exterior, Windows, Openings Between Window and Wood Frame
Window Caulking, Gray Damaged 20 Openings;
510 LF Non-Friable Class II Work –
Non-Friable
84 Exterior Walls under Shakes Tar Paper Vapor Barrier Good 2,500 SF Good Class II Work – Non-Friable
Building 22 - HQ (Theater)
Walls and Ceilings Throughout
Sheetrock & Associated Joint Compound Good 3,800 SF Friable Class I Work – Full containment
Bldg. Sub-totals 12,190 SF
543 LF
Previous Quantities
2,265 SF
243 LF
CACO ACM Inspection Inventory Page 6 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
86 Building 23 - Dorm Throughout All building materials are contaminated ACM Significantly
Damaged 35,000 SF Friable/Non -friable
Demolish with asbestos in place
Building is structurally compromised; all building materials should be removed as contaminated
ACM
Bldg. Sub-totals 35,000 SF Previous Quantities
25,710 SF
900 LF
87 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
88 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
89 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
90 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
91 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
92 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
93 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
94 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
95 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
96 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 201
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
5-23-22 Investigation by
WSP
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
98 Building 202 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
99 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
100 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
101 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
102 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
CACO ACM Inspection Inventory Page 7 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
103 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
104 Building 202 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
105 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
106 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
107 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
108 Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
109 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
110 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
111 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
112 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
113 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
114 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
115 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
116 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
117 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
118 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 203
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (Assumed Typical for all similar)
CACO ACM Inspection Inventory Page 8 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
120 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
121 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
122 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
123 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
124 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
125 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
126 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
127 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
128 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
129 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 204
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
131 Building 205 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
132 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
133 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
134 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
135 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
136 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
137 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
138 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
139 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
CACO ACM Inspection Inventory Page 9 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
140 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 205
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
142 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
143 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
144 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
145 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
146 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
147 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
148 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
149 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
150 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
151 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 206
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
153 Building 207 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
154 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
155 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
156 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
157 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
158 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-
CACO ACM Inspection Inventory Page 10 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
159 Building 207 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
160 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
161 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
162 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
163 Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
164 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
165 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
166 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
167 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
168 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
169 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
170 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
171 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
172 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
173 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 208
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
175 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
176 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
Building 209
Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-
CACO ACM Inspection Inventory Page 11 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
178 Building 209 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
179 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
180 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
181 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
182 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
183 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
184 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
185 Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
186 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
187 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
188 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable 189 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
190 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
191 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
192 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
193 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
194 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
195 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 210
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
CACO ACM Inspection Inventory Page 12 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
197 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
198 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
199 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
200 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
201 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
202 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
203 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
204 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
205 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
206 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 211
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
208 Building 212 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
209 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
210 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
211 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
212 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
213 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
214 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
215 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
216 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-
CACO ACM Inspection Inventory Page 13 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
217 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 212
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
219 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
220 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
221 Throughout 9”x9” Floor Tiles & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
222 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable Class II - Non-friable
223 Kitchen, Bathroom Aircell Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
224 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Damaged 300 SF Non-Friable Class II - Non-friable
225 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
226 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
227 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
228 Exterior Tar Paper behind Wood Shakes Siding Damaged 1,500 SF Non-Friable Class II - Non-friable
Building 213
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
230 Building 214 Throughout, Walls and Ceiling
Sheetrock and Associated Joint Compound Damaged 4,400 SF Non-Friable Class I - Friable, Full Containment
231 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Good Non-Friable Class II - Non-friable
232 Throughout 9”x9” Floor Tiles & Associated Black Mastic Good
1,200 SF
Non-Friable Class II - Non-friable
233 Kitchen Sink Undercoat, White Good 6 SF Non-Friable Class II - Non-friable
234 Kitchen, Bathroom Aircell Pipe Insulation Good 60 LF Friable Class I - Friable, Full Containment
235 Bathroom Ceramic Wall Tile and Floor Tile Grout & Backing Good 300 SF Non-Friable Class II - Non-
CACO ACM Inspection Inventory Page 14 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
236 Building 214 Perimeter of Slab Transite Air Conduits within Slab Good 125 LF Non-Friable Class II - Non-friable
237 Throughout Braided Wiring Insulation Good 1,200 LF Non-Friable Class II - Non-friable
238 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 3,000 SF Non-Friable Class II - Non-friable
239 Exterior Tar Paper behind Wood Shakes Siding Good 1,500 SF Non-Friable Class II - Non-friable
240 Exterior, Roof Roofing Tar & Tar Paper Good 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 12,306 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
Walls and Ceilings
Throughout, Including Attached Garage
Sheetrock & Associated Joint Compound Damaged 5,100 SF Friable Class I - Friable, Full Containment
242 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Damaged Non-friable Class II - Non-friable
243 Throughout 9”x9” Floor Tiles, Gray & Associated Black Mastic Damaged
1,200 SF
Non-Friable Class II - Non-friable
244 Kitchen, Bathroom Aircell Pipe Insulation Damaged 66 LF Friable Class I - Friable, Full Containment
245 Bathroom Ceramic Tile Grout & Backing Damaged 440 SF Non-Friable Class II - Non-friable
246 Perimeter of Slab Transite Air Conduits within Slab Damaged 150 LF Non-Friable Class II - Non-friable
247 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
248 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 4,620 SF Non-Friable Class II - Non-friable
249 Exterior Tar Paper under Shakes Damaged 1,815 SF Non-Friable Class II - Non-friable
Building 215
Exterior, Roof Roofing Tar & Tar Paper Damaged 2,010 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 15,185 SF
1,332 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
Walls and Ceilings
Throughout, Including Attached Garage
Sheetrock & Associated Joint Compound Damaged 4,400 SF Friable Class I - Friable, Full Containment
252 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Good Non-friable Class II - Non-friable
Building 216
Throughout 9”x9” Floor Tiles, Gray & Associated Black Mastic Good
1,100 SF
Non-Friable Class II - Non-
CACO ACM Inspection Inventory Page 15 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
254 Building 216 Kitchen, Bathroom Aircell Pipe Insulation Good 60 LF Friable Class I - Friable, Full Containment
255 Bathroom Ceramic Tile Grout & Backing Good 400 SF Non-Friable Class II - Non-friable
256 Perimeter of Slab Transite Air Conduits within Slab Good 125 LF Non-Friable Class II - Non-friable
257 Throughout Braided Wiring Insulation Good 1,200 LF Non-Friable Class II - Non-friable
258 Throughout - Outer Walls, and Attic Floor
Fiberglass Insulation w/ Black Glue Backing Damaged 4,200 SF Non-Friable Class II - Non-friable
259 Exterior Tar Paper under Shakes Good 1,650 SF Non-Friable Class II - Non-friable
260 Exterior, Roof Roofing Tar & Tar Paper Good 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 13,650 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
Walls and Ceilings
Throughout, Including Attached Garage
Linoleum Floor Sheeting & Associated Yellow Mastic Damaged Non-Friable Class II - Non-friable
262 Throughout 9”x9” Floor Tiles, Gray & Associated Black Mastic Damaged
1,050 SF
Non-Friable Class II - Non-friable
263 Throughout Sheetrock & Associated Joint Compound Damaged 4,400 SF Friable Class I Work – Full
Containment
264 Rear Entryway 9”x9” Floor Tiles, Gray-Blue & Associated Black Mastic Damaged 100 SF Non-Friable Class II - Non-friable
265 Kitchen, Bathroom Pipe Insulation Damaged 60 LF Friable Class I - Friable, Full Containment
266 Bathroom Ceramic Tile Grout & Backing Damaged 400 SF Non-Friable Class II - Non-friable
267 Perimeter of Slab Transite Air Conduits within Slab Damaged 125 LF Non-Friable Class II - Non-friable
268 Throughout Braided Wiring Insulation Damaged 1,200 LF Non-Friable Class II - Non-friable
269 Garage, Outer Walls, Attic Fiberglass Insulation w/ Black Glue Backing Damaged 4,200 SF Non-Friable Class II - Non-friable
270 Exterior Tar Paper under Shakes Damaged 1,650 SF Non-Friable Class II - Non-friable
Building 217
Exterior, Roof Roofing Tar & Tar Paper Damaged 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 15,032 SF
1,385 LF
Previous Quantities
6,016 SF (assumed typical)
CACO ACM Inspection Inventory Page 16 of 16
# Building Location Material Description Material
Condition
Total Quantity of
ACM
Friability Removal
Methodology Notes
Walls and Ceilings
Throughout, Including Attached Garage
Sheetrock and Associated Joint Compound Damaged 4,400 SF Friable Class I - Friable, Full Containment
273 Throughout Linoleum Floor Sheeting, Tan & Associated Yellow Mastic Good Non-Friable Class II - Non-friable
274 Throughout 9”x9” Floor Tiles, Tan & Associated Black Mastic Good
1,000 SF
Non-Friable Class II - Non-friable
275 Kitchen, Bathroom Aircell Pipe Insulation Good 60 LF Friable Class I - Friable, Full Containment
276 Bathroom Ceramic Tile Grout & Backing Good 400 SF Non-Friable Class II - Non-friable
277 Perimeter of Slab Transite Air Conduits within Slab Good 125 LF Non-Friable Class II - Non-friable
278 Throughout Braided Wiring Insulation Good 1,200 LF Non-Friable Class II - Non-friable
279 Garage, Outer Walls, Attic Fiberglass Insulation w/ Black Glue Backing Damaged 4,200 SF Non-Friable Class II - Non-friable
280 Exterior Tar Paper under Shakes Good 1650 SF Non-Friable Class II - Non-friable
Building 218
Exterior, Roof Roofing Tar & Tar Paper Good 1,900 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 15,032 SF
1,385 LF
Previous Quantities
6,080 SF (from Bldg.
203 typical)
HIGHLANDS CENTER BUILDING TOTALS 470,794 SF
28,260 LF
Previous Quantities
164,352 SF
1,193 LF
CACO ACM Inspection Inventory Page 1 of 8
Summary of Visual Inspection Results and Previously-completed Reports for Asbestos Containing Materials (ACM)
Line # Building Location Material Description Material
Condition Total Quantity of ACM Friability Removal Methodology Notes
1 Throughout Sheetrock Walls and Ceiling & Assoc. Joint Compound Damaged 4,200 SF Friable
2 Throughout Main Floor Linoleum Flooring and assoc.
Glue Damaged 1,600 SF Non-Friable
3 Throughout Main Floor Window Glazing Damaged 750 LF Non-Friable
4 Throughout Main Floor Vapor Barrier assoc. with Wood Floor Damaged 1,600 SF Non-Friable
5 Living Room Fireplace and Chimney Brick Mortar Damaged 200 SF Friable
Class I - Friable, Full Containment all interior due to contaminated debris throughout
6 Building Exterior Vapor Barrier behind Exterior Wood siding Damaged 1,600 SF Non-Friable Class II - Non-friable
7 Roof Roofing Shingles & Tar Paper Damaged 1,800 SF Non-Friable Class II - Non-friable
Audubon House, 44 Tomahawk
Trail, Eastham, MA
Shed Roof Shingles Damaged 220 SF Non-Friable Class II - Non-friable
Building partially collapses/ structurally compromised;
basement inaccessible
Building Sub-totals 11,220 SF
750 LF
Previous Quantities N/A No ACM found per info.
provided by NPS
9 Throughout Sheetrock Walls and Ceiling & Assoc. Joint Compound Damaged 8,200 SF Friable
10 Throughout Brick Mortar Damaged 1,400 SF Friable
11 Kitchen Linoleum Sheet Flooring & Associated Yellow Mastic Damaged 20 SF Non-Friable
12 Bathrooms Throughout Ceramic Tile Grout & Backing Damaged 120 SF Non-Friable
13 Throughout, Including Foundation CMU & Mortar Damaged 900 SF Friable
14 Throughout Tar Paper assoc. with Fiberglass Insulation Damaged 2,000 SF Non-Friable
15 2nd Floor Bathroom Caulking, White Damaged 22 LF Non-Friable
16 Kitchen Sink Undercoat, White Damaged 6 SF Non-Friable
Class I - Friable, Full Containment all interior due to contaminated debris throughout
Aiken Cottage, 85 North Pamet Rd, Truro, MA
Windows Throughout Window Glazing, Gray Damaged 800 LF Non-Friable Class II - Non-friable
CACO ACM Inspection Inventory Page 2 of 8
# Building Location Material Description Material
Condition Total Quantity of ACM Friability Removal Methodology Notes
18 Building Exterior Vapor Barrier behind Exterior Wood siding Damaged 2,100 SF Non-Friable Class II - Non-friable
19 Building Roof Roof Shingles and Tar Paper Damaged 2,200 SF Non-Friable Class II - Non-friable
Aiken Cottage, 85 North Pamet Rd, Truro, MA
Shed Roof Roof Shingles and Tar Paper Damaged 400 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 17,346 SF
822 LF
Previous Quantities N/A No ACM found per info.
provided by NPS
21 Throughout Roof Remains, Black Severely Damaged 10 CF Friable Class I - Friable, Full
Containment
22 Rear of Footprint, Sump Pit CMU Mortar Damaged 80 CF Friable Class I - Friable, Full Containment
Brennan House Foundation, Private Way 59 Newcomb Hollow Rd, Wellfleet, MA Footprint Center at Fireplace &
Chimney Brick Mortar Damaged 240 SF Friable Class I - Friable, Full Containment
Bldg. Sub-totals 240 SF
90 CF
Previous Quantities N/A No ACM found per info.
provided by NPS
24 Throughout Original House (not addition)
9”x9” Floor Tile and assoc.
Mastic Damaged 660 SF Non-Friable
25 Throughout Original House (not addition)
Sheetrock Walls and Ceiling & Assoc. Joint Compound Damaged 1,300 SF Friable
26 Throughout Original House (not addition) Vapor Barrier under Wood Floor Damaged 660 SF Non-Friable
27 Throughout Original House (not addition)
Vapor Barrier behind Exterior Wood siding Damaged 1,100 SF Non-Friable
28 Roof Roof Shingles and Roof Paper Damaged 1,250 SF Non-Friable
Heath House, 8 Coast Guard
Terrace, Truro, MA
Original House Fireplace/Chimney Brick Mortar Damaged 120 SF Friable
Demolish with asbestos in place
Building is structurally compromised; all building materials should be removed as contaminated ACM
Bldg. Sub-totals 5,090 SF Previous Quantities N/A Floor determined ACM, with no quantity
30 Throughout 9”x9” Floor Tiles, Red & Associated Black Mastic Good 550 SF Non-Friable Class II - Non-friable
31 Throughout 1’x1’ Ceiling Tiles, White (2 Layers) Good 600 SF Friable Class I - Friable, Full
Containment 32 Throughout Window Glazing Damaged 75 LF Non-Friable Class II - Non-friable
33 Roof Roof Shingles and Roof Paper Good 625 SF Non-Friable Class II - Non-friable
Lorenzen House, 4 Coast Guard Terrace, Truro, MA
Building Exterior Vapor Barrier behind Exterior Wood siding Good 1,100 SF Non-Friable Class II - Non-friable
35 Bldg. Sub-totals 2,875 SF
75 LF
Previous Quantities N/A Floor determined ACM, with no quantity
CACO ACM Inspection Inventory Page 3 of 8
# Building Location Material Description Material
Condition Total Quantity of ACM Friability Removal Methodology Notes
36 Throughout 1st and 2nd Floor Linoleum Floor and assoc. Glue Damaged 1,750 SF Non-Friable
37 Throughout 1st and 2nd Floor Sheetrock Walls and Ceiling & Assoc. Joint Compound Damaged 5,700 SF Friable
38 Throughout Electrical Wiring Insulation Damaged 300 LF Non-Friable
39 Throughout 1st and 2nd Floor Vapor Barrier under Wood Floor Damaged 1,750 SF Non-Friable
40 1st and 2nd Floor Fireplace/Chimney Brick Mortar Damaged 600 SF Friable
41 Basement Cinderblock Mortar Damaged 800 SF Friable
Class I - Friable, Full Containment all interior due to contaminated debris throughout
42 Building Exterior Vapor Barrier behind Exterior Wood siding Damaged 2,200 SF Non-Friable Class II - Non-friable
43 Building Exterior Window Glazing Damaged 320 LF Non-Friable Class II - Non-friable
Moran House, 19 Tomahawk Trail, Eastham, MA
Roof Roof Shingles and Roof Paper Damaged 1,200 SF Non-Friable Class II - Non-friable
Bldg. Sub-totals 14,000 SF
620 LF
Previous Quantities N/A No ACM found per info.
provided by NPS
45 Throughout Basement, 1st and 2nd Floor
Sheetrock Walls & Assoc. Joint Compound Damaged 3,700 SF Friable
Throughout Basement and 2nd Floor, 1st Floor Bathroom 1, Kitchen, Bedrooms 1, 2, 3
Sheetrock Ceiling & Assoc. Joint Compound Damaged 1,900 SF Friable
47 1st Floor Living/Dining Area Mortar assoc. with Terra Cotta Floor Tiles Damaged 380 SF Friable
48 1st Floor Living Room Mortar assoc. with Fireplace/Chimney Damaged 150 SF Friable
49 Throughout Basement, 1st Floor, 2nd Floor
Tar Paper assoc. with Fiberglass Attic and Ceiling Insulation Damaged 2,500 SF Non-Friable
50 Throughout 1st Floor, except Living/Dining Area
Linoleum Flooring and assoc.
Glue Damaged 1,200 SF Non-Friable
51 Throughout 1st Floor, 2nd Floor, Basement
Va…