Text version
EMSL Analytical, Inc.
464 McCormick Street San Leandro, CA 94577
Tel/Fax: (510) 895-3675 / (510) 895-3680 http://www.EMSL.com / sanleandrolab@emsl.com
092308256EMSL Order:
Customer ID: LASS75
Customer PO:
Project ID:
Attention: Phone:Gary Mott (530) 595-6220
Fax:Lassen Volcanic National Park (530) 595-3272
Received Date:PO Box 100 04/12/2023 9:00 AM
Analysis Date:Mineral, CA 96063 04/15/2023
Collected Date: 04/06/2023 - 04/10/2023
Project: QUARTERS 16, MINERAL HEADQUARTERS DISTRICT , QTRS 17 AND DRAKESBAD
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
092308256-0001
None DetectedGypsum
Non-fibrous (Other)
80%
17%
Cellulose3%White
Non-Fibrous
Homogeneous
DRAKESBAD CABIN
SHEETROCK
2-Linoleum Flooring
092308256-0002
25% ChrysotileMatrix
Non-fibrous (Other)
60%
10%
Cellulose5%Gray/Tan
Fibrous
Homogeneous
LINOLEUM
FLOORING, QTRS.
This is a composite result of both vinyl and backing layer
2-Mastic
092308256-0002A
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Yellow
Non-Fibrous
Homogeneous
LINOLEUM
FLOORING, QTRS.
092308256-0003
None DetectedNon-fibrous (Other)5%Cellulose95%Brown
Fibrous
Homogeneous
CEILING TILE,
QTRS. 17
092308256-0004
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Beige
Non-Fibrous
Homogeneous
WINDOW GLAZING,
QTRS 17
092308256-0005
None DetectedMatrix
Non-fibrous (Other)
80%
20%
Beige
Non-Fibrous
Homogeneous
WINDOW GLAZING,
QTRS 16
Analyst(s)
Stacy Trinh Le (6) Cecilia Yu, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc San Leandro, CA NVLAP Lab Code 101048-3, WA C884
Initial report from: 04/15/2023 14:44:49