B01.01_Attachment A - Drawings for Description of Requirement (DOR).pdf
PDF 2 MB Posted
- Attached to
- Precast Concrete Components C-Channels and Slabs Federal contract opportunity
- Solicitation number
- W912HZ26QA015
About this file
This document is a set of technical drawings for precast concrete components to be delivered to Fort Polk, Louisiana. The drawings provide detailed specifications for five distinct concrete product types: a 6-inch-thick C-Channel, a 9-inch-thick tall C-Channel, a floor isolation slab, a floor bearing pad, and a 9-inch-thick short C-Channel.
The 6-inch C-Channel (Drawing A) requires concrete with minimum 4,500 psi compression strength at 28 days, ASTM A615 Grade 60 reinforcement, total weight of 8,500 pounds with four lifting points each with minimum 1,500 lbs tension capacity, and chamfered edges with 2-inch [13mm] recommendation. The 9-inch tall C-Channel (Drawing B) specifies 4,500 psi concrete strength, ASTM A615 Grade 60 reinforcement, total weight of 13,000 pounds with four lifting points each with minimum 1,500 lbs tension capacity, and chamfered 2-inch edges. The floor isolation slab (Drawing C) requires 4,500 psi concrete, ASTM A615 Grade 60 #4 reinforcement bars, total weight of 4,300 pounds with four lifting points each with minimum 2,200 lbs tension capacity, and includes 1-inch schedule 40 PVC pipe thru-holes. The floor bearing pad (Drawing D) specifies 4,500 psi concrete, ASTM A615 Grade 60 #4 reinforcement, total weight of 1,100 pounds with four lifting points each with minimum 600 lbs tension capacity, and 1-inch schedule 40 PVC pipe thru-holes. The 9-inch short C-Channel (Drawing E) requires 6,000 psi 28-day compressive strength, ASTM A-615 Grade 60 reinforcement, and four lifting points each with minimum 6,000 lbs tension capacity. All products require minimum 1-inch [13mm] clear cover for reinforcement, prohibit welding or torch-cutting, and mandate adequate reinforcement securing to prevent movement during concrete placement.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment C- Technical Questions and Answers for 26QA015 (17 Mar).pdf | ||
| Attachment C - Technical Questions and Answers.pdf | ||
| Attachment B - Quote Submission Form (Amendment 0002).pdf | ||
| Attachment A - DOR Drawings (Amendment 0002).pdf | ||
| B01.01_Solicitation Amendment W912HZ26QA0150002 SF 30.pdf | ||
| B01.01_Solicitation Amendment W912HZ26QA0150001 SF 30.pdf | ||
| B01.01_Attachment B - Quote Submission Form.pdf | ||
| B01.01_Solicitation - W912HZ26QA015.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT A – DRAWINGS
for
Description of Requirements for Precast Concrete C-Channel(s) and Slab(s) delivered to Fort Polk, LA
6-inch-thick C-Channel (Sheet 1 of 3) – DRAWING A
6-inch-thick C-Channel (Sheet 2 of 3) – DRAWING A
6-inch-thick C-Channel (Sheet 3 of 3) – DRAWING A
9-inch-thick, TALL, C-Channel (Sheet 1 of 3) – DRAWING B
9-inch-thick, TALL, C-Channel (Sheet 2 of 3) – DRAWING B
9-inch-thick, TALL, C-Channel (Sheet 3 of 3) – DRAWING B
Floor Isolation Slab (Sheet 1 of 4) – DRAWING C
Floor Isolation Slab (Sheet 2 of 4) – DRAWING C
Floor Isolation Slab (Sheet 3 of 4) – DRAWING C
Floor Isolation Slab (Sheet 4 of 4) – DRAWING C
Floor Bearing Pad (Sheet 1 of 4) – DRAWING D
Floor Bearing Pad (Sheet 2 of 4) – DRAWING D
Floor Bearing Pad (Sheet 3 of 4) – DRAWING D
Floor Bearing Pad (Sheet 4 of 4) – DRAWING D
9-inch-thick, SHORT, C-Channel (Sheet 1 of 5) – DRAWING E
9-inch-thick, SHORT, C-Channel (Sheet 2 of 5) – DRAWING E
9-inch-thick, SHORT, C-Channel (Sheet 3 of 5) – DRAWING E
9-inch-thick, SHORT, C-Channel (Sheet 4 of 5) – DRAWING E
9-inch-thick, SHORT, C-Channel (Sheet 5 of 5) – DRAWING E