This document appears to be architectural plans and drawings for the Woodrow Wilson Keeble Memorial Health Care Center USP Compliance project. The plans include details on the building layout, life safety, demolition, mechanical, electrical, and plumbing systems for the Pharmacy and Ambulance Garage areas. The project is located in Sisseton, South Dakota and is being managed by the Indian Health Service, a civilian agency under the Department of Health and Human Services. The construction is classified as Type II-B and will involve demolition, carpentry, finishes, and new mechanical, electrical, and plumbing work. The solicitation number is 75H701-24-R-00028 and the total project area is approximately 4,674 square feet. No additional details on the procurement process, response dates, award information, or pricing terms are provided in this document.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER ARCHITECT
DSGW Architects
2 West First St. Suite 201
Duluth, MN 55802
Phone: 218-740-3632
Contact: Ryan Turner Email: rturner@dsgw.com
STRUCTURAL ENGINEER
IHS Woodrow Wilson Keeble Memorial
Health Care Center
100 Lake Traverse Drive Sisseton, SD 57262
Phone: 605-377-8823
Contact: jarret Coon
Email: jarret.coon@ihs.gov
MECH/ELECT. ENGINEER
Northland Consulting Engineers
102 S. 21st Avenue West Suite 1
Duluth, MN 55806
Phone: 218-727-5995
Fax: 218-727-7779
Contact: Jon Aamodt
Email: jon@nce-duluth.com
EDI-Dolejs
1112 N 5th Street
Minneapolis, MN., 55411
Phone: 612-343-5965
Contact:
Email: email address
Project Team
EARTH
COMPACT FILL/SAND
POROUS FILL/GRAVEL
FACE BRICK
CMU
CONCRETE
RIGID INSULATION
BATT INSULATION
STUD WALL/METAL
PLYWOOD
GYPSUM BOARD
FINISHED WOOD
CONT. ROUGH WOOD
WOOD BLOCKING
Materials
Symbols
DETAIL
NUMBER
SHEET
NUMBER
AREA TO BE
DETAILED OR
ENLARGED
ACTUAL NORTH
(IF DIFFERENT)
REVISION TYPE
SHEET NUMBER
SECTION NUMBER
A8.1
MATCH LINE
SHEET
NUMBER
ELEVATION
NUMBER
A7.2
NORTH ARROW
DETAIL REFERENCESECTION REFERENCE
REVISION IDENTIFICATIONTITLE MARKER
ROOM IDENTIFICATION
ROOM NAME
ROOM NUMBER
DOOR TAG
BREAKLINE
ELEVATION REFERENCE
WALL TAGWINDOW TAG
ELEVATION LABEL MATCHLINE IDENTIFICATION NOTE IDENTIFICATION
(LEADER
OPTIONAL)
A7.1
A5.1
TOILET
ROOM
T.O. STL.
100'-0"
VIEW TITLE
VIEW SCALE
W205
1A S
I
5A
SEQUENTIAL
INDICATOR
APPROXIMATE
THICKNESS IN INCHES
N
(WHEN REQ'D)
REPRESENTS NEW
DOOR
REPRESENTS
EXISTING DOOR
TO REMAIN
REPRESENTS
EXISTING DOOR
TO BE REMOVED.
WALLS WITH
HATCH
INDICATE NEW
CONSTRUCTION
WALLS SHADED
GRAY INDICATE
EXISTING TO
REMAIN
DASHED LINES
INDICATE WALLS
& ITEMS TO BE
REMOVED.
PLAN NORTH
REVISION NUMBER
Star Indicates Project Location
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:41 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A0.1
Title Sheet
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
Sheet Index
Location Map
0-Cover Sheet
A0.1 Title Sheet
2-Architectural
A1.1 Life Safety Plan & Summary
A1.3 Demo Plan
A2.1 Ambulance Garage
A2.2 Pharmacy
A3.1 First Floor RCP
A4.1 Schedules and Types
A7.1 Interior Elevations
A8.1 Details
3-Mechanical
M0.1 MECHANICAL TITLE SHEET
M1.1 Pharmacy - Mechanical Demolition
M1.2 Ambulance Garage - Mechanical Demolition
M2.1 Pharmacy - Fire Protection
M2.2 Ambulance Garage - Fire Protection
M3.0 Pharmacy - Underfloor Plumbing
M3.1 Pharmacy - Plumbing
M4.1 Pharmacy - Piping
M4.2 Ambulancy Garage - Piping
M5.1 Pharmacy - HVAC
M5.2 Ambulance Garage - HVAC
M6.1 Mechanical Shedules
M7.1 Mechanical Details
4-Electrical
E0.1 ELECTRICAL TITLE SHEET
E1.1 Pharmacy - Electrical Demolition
E1.2 Ambulance Garage - Electrical Demolition
E2.1 Pharmacy - Lighting
E2.2 Ambulance Garage - Lighting
E3.1 First Floor Plan - power & Systems
E3.2 Pharmacy - power & Systems
E3.3 Ambulance Garage - Power & Systems
E4.1 Schedules - Electrical
E4.2 Schedules - Electrical
E5.1 Details - Electrical
Abbreviations
Project Number:
Woodrow Wilson Keeble Memorial Health Center USP Compliance
100 Lake Traverse Drive Sisseton, SD 57262
IHS Project # HHSI102201800141 022003.00
Architectural General Notes
LAM LAMINATE
LVT LUXURY VINYL TILE
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
PC PRECAST
PLAM / P.LAM. PLASTIC LAMINATE
PLYWD PLYWOOD
PNT PAINT
PTD PAPER TOWEL DISPENSER
RCP REFLECTED CEILING PLAN
REF REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RTU ROOF TOP UNIT (MECH.)
S.SPLASH SIDESPLASH
SACT SUSPENDED ACOUSTICAL CEILING TILE
SCHED SCHEDULE
SD SOAP DISPENSER
SEAL SEALANT
SF SQUARE FOOT (FEET)
SIM SIMILAR
SIP STRUCTURAL INSULATED (OR INSULATING)
PANEL
SPEC SPECIFICATION
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
STL STEEL
STRUCT STRUCTURAL CONSULTANT
T.O. TOP OF
TRTD TREATED
TYP TYPICAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WD WOOD
SV SHEET VINYL
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECT
B.O. BOTTOM OF
B.SPLASH BACKSPLASH
BLKG BLOCKING
C-TOP COUNTERTOP
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CPT CARPET
CT CERAMIC TILE
D DEEP
DIM DIMENSION
DISP DISPENSER
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
ELEC ELECTRICAL
EQ EQUAL
EQUIP / EQPT. EQUIPMENT
EXST / EX. / EXIST. EXISTING
F.T. FIRE TREATED
F.V. FIELD VERIFY
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FLR FLOOR
FRP FIBERGLASS REINFORCED PANEL
FUR FURRING
GALV GALVANIZED
GLAZ GLAZING
GYP. BD. / G.BD / GBD GYPSUM BOARD
HM HOLLOW METAL
HT HEIGHT
ICF INSULATED (OR INSULATING) CONCRETE FORM
INSUL INSULATION
1. General Notes apply to all drawing sheets.
2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen conditions, discrepancies, errors, or inconsistencies.
3. Work shall be done in accordance with all rules and regulations of all applicable safety and building codes. The General Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections during the course of the project.
4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property, public thoroughfares, etc. Maintain all required exits during construction.
5. All materials and systems shall be installed as per manufacturer's specifications and all construction shall be of industry standard or better.
6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to a change in the scope of work.
7. In the event of conflict between data shown on drawings and data shown in the Specification, the Work of greater quality or quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted. Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is discovered.
8. Immediately notify Architect of any long lead items that will affect the completion date
9. All wood in contact with concrete or concrete block to be pressure treated - typical.
10. Provide metal backing and / or treated wood blocking for all wall mounted equipment (grab bars, toilet room accessories, TV mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.
11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code.
Fireproof any new penetrations required by the work. Refer to code summary for ratings.
12. All exposed metal to receive paint unless otherwise noted
13. All adjacent dissimilar materials to receive caulking, including equipment mounted to walls
14817
1" = 100'-0"
Location êÉîáëáçå=L áëëìÉ åçK Ç~íÉ ^aa N OMOPLMTLOS
9'-0"7'-6"
20'-0"
8'-6"
16'-0"
26'-8"
18'-9"
24'-0"
Life Safety Legend
BUILDING EXIT
ACCESSIBLE FEATURE
ROOM OCCUPANCY LOAD
EXIT SIGNAGE
EMERGENCY LIGHTING
1 HOUR FIRE BARRIER
(EXIT ENCLOSURE OR SHAFT)
1 HOUR FIRE BARRIER
(OTHER)
2 HOUR FIRE BARRIER
(EXIT ENCLOSURE OR SHAFT)
2 HOUR FIRE BARRIER
(OTHER)
SMOKE RESISTANT
PARTITION
FIRE WALL
1 HOUR FIRE PARTITION
MAX EXIT ACCESS TRAVEL POINT
EXIT NODE
DISTANCE BETWEEN NODES
15'-0"
(XX' MAX EXIT ACCESS)
EGRESS PATH
FIRE EXTINGUISHER
(WALL HUNG)
FIRE EXTINGUISHER
WITH CABINET
FEX
FEC
E
12'-0"
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:43 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A1.1
Life Safety Plan & Summary
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
1 : 100
Pharmacy Code Plan
14817
1 : 100
Ambulance Bay Code Plan
Life Safety Analysis
PROJECT:
PROJECT NUMBER:
LOCATION:
ARCHITECT:
PREPARED BY:
OCCUPANCY:
CONST. TYPE:
OCCUPANT LOAD:
CODE(S) USED:
NEW
REMODEL
ADDITION
SPRINKLED
FIRE ALARM SYSTEM
Is This a Nonseperated Occupancy?
Is This a Seperated Occupancy?
OCCUPANCY
BASIC ALLOWABLE FOOTPRINT
ACTUAL FOOTPRINT
PROJECT AREA
ALLOWABLE HEIGHT
ACTUAL NUMBER OF STORIES
NO
YES
YES
YES
YES
YES
NO
B
92,000 sf
86,616 sf
4,674 sf
75'
IHS Woodrow Willson Keeble Memorial Health Center USP Compliance
020053.00
Sisseton, SD 57262
DSGW Architects
B (Pharmacy)
II-B
International Building Code, 2018 Edition
Building Element
Fire-Resistive Rating (Table 601/602) structural Frame exterior
Interior Bearing Walls
Nonbearing Walls exterior
Interior
Floor Construction
Roof Construction
Type ii-b
0 hr (exist)
0 hr (exist)
0 hr (exist)
0 hr (exist)
0 hr (exist)
0 hr (exist)
0 hr (exist)
0 hr (exist)
X < 30
X </= 30 êÉîáëáçå=L
C1
C1
C1
C1
C1C1
C1
D2
W6
W1
W1
W1
W1
W1
W1
D4
D2
D4
P3
D2
P3
F3
F1
F1
F1
F3
F1
W9
W9
F1
W1
F3
F3
F3
F3
F3
R2
R3 R3
R3
R3
R3
R2
R2
R2
R2R2
R2
R2
R2
Z1Z3
W6
G3 G3
W1 W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1 W1
W1
W1
D4
W1
D2
D4
D4
D4
C1
W3 G4
W1
D5D5
D2
D2
W6
D4
Z4 Z4 Z4 Z4
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:46 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A1.3
Demo Plan
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
Demo Plan Notes C1 DEMO & REMOVE EXISTING CASEWORK INCLUDING ANY UPPER OR LOWER CABINETS AND SHELVES, COUNTER, PLUMBING FIXTURES AND WALL MOUNTED ACCESSORIES (REMOVE APPLIANCES IF APPLICABLE)
D2 DEMO & REMOVE EXISTING INTERIOR DOOR, FRAME & HARDWARE; INFILL W/WALL TYPE TO MATCH
D4 DEMO & REMOVE EXISTING INTERIOR DOOR, FRAME & HARDWARE. REPLACE W/NEW SIMILAR SIZED DOOR, FRAME &
HARDWARE; VERIFY SIZE- SEE SCHEDULE
D5 DEMO & REMOVE EXISTING EXTERIOR DOOR, FRAME, & HARDWARE INCLUDING GLAZING SYSTEM IF APPLICABLE;
INFILL W/WALL TYPE TO MATCH
F1 DEMO & REMOVE EXISTING CARPET FLOORING & BASE AS APPLICABLE; PREP FLOOR FOR NEW FINISHES
F3 DEMO & REMOVE EXISTING VCT FLOORING & BASE WHERE APPLICABLE; PREP FLOOR FOR NEW FINISHES
G3 DEMO & REMOVE EXISTING EXTERIOR WINDOW, FRAME, & HARDWARE; INFILL W/WALL TYPE TO MATCH
G4 DEMO & REMOVE EXISTING GLAZING AND REPLACE WITH BALLISTIC GLASS AS SPECIFIED
P3 DEMO & REMOVE EXISTING SINK, FAUCET, & PLUMBING ROUGH-IN ALONG W/ANY WALL MOUNTED SHELVES OR
ACCESSORIES
R2 DEMO & REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE & GRID
R3 DEMO & REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE. REPLACE WITH NEW TILE
W1 DEMO & REMOVE EXISTING INTERIOR WALL-FEILD VERIFY EXIST. CONSTRUCTION
W3 DEMO & REMOVE PORTION OF EXISTING EXTERIOR MASONRY WALL TO CREATE NEW WINDOW OPENING
W6 DEMO & REMOVE PORTION OF EXISTIN WALL TO CREATE NEW DOOR OPENING. PATCH FLOOR AS REQ'D
W9 DEMO & REMOVE EXISTING VWC AND PREP FOR NEW WALL FINISH
Z1 REMOVE & SALVAGE EXISTING MOUNTED SIGNAGE; REINSTALL AS DIRECTED BY OWNER
Z3 DEMO & REMOVE EXISTING HIGH DENISTY SHELVING
Z4 DEMO & REMOVE EXISTING BALLARDS
Demo General Notes
1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.
2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.
3. Demolition notes without leaders indicate that the note applies to the entire room.
4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.
5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.
6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).
7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.
8. Prep floors as needed for new finishes.
9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.
10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.
11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.
12. Verify any items to be retained for owners use prior to removal.
13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.
1/4" = 1'-0"
Pharm. Demo Plan
14817
1/4" = 1'-0"
Amb Bay Demo Plan
/8
/4
/4
/8
12'-3 1/8"
A2.1
Flex Space
Cooridoor
Office 1
Office 2
Office 3
Office 4
Office 5
Work Room
Office 6
Office 7
9'-4 5/8"4'-11"
1SY
1SY
1SY
2A
1SY
1SY
1SY
1SY
1SY
1SY
2A
2A 2A 2A
2A
1SY
2A
2A
2A
2A
2A
2A
2A
2A
2A
2A
2A2A
1SY
A2.1
3'-7 1/2" 6'-0 5/8"4'-2 1/8" 4'-1 5/8" 5'-6"
9'-8 3/4"
AL-W1 AL-W1 AL-W1 AL-W1
8A
7A
2'-0" 1'-9" 1"
2'-0" 1'-9" 1"1"2'-8 7/8"
INFILL WITH BRICK TO MATCH EXISTING
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
8'-0"
A2.1
SACT, SEE RCP
S E
E R
C P
5/8" GYP. BD OVER 2x4
WOOD STUD FRAMING
SEE WALL TYP
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:50 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A2.1
Ambulance Garage
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
1/4" = 1'-0"
Ambulance Garage
Floor Plan General Notes A Interior dimensions are to finished face of stud wall, face of masonry walls, to centerline of columns or to other grid points unless otherwise noted. Dimensions labeled as CLEAR or CLR indicate minimum distance to finished face of walls. Dimensions are to finished face of existing walls if applicable.
B All interior door frames to be 4" from adjacent wall or centered between walls unless otherwise noted.
C Furniture & equipment shown is for reference only and is not included in the contract.
D Coordinate size and location of all duct and shaft openings in walls and floors with MEP consultant.
E Fire rated walls are indicated on the Life Safety Plan.
F All partitions are type "SC" unless noted otherwise
G Provide a corner guard where symbol is shown at a wall corner
1. General Notes apply to all drawing sheets.
2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen conditions, discrepancies, errors, or inconsistencies.
3. Work shall be done in accordance with all rules and regulations of all applicable safety and building codes. The General Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections during the course of the project.
4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property, public thoroughfares, etc. Maintain all required exits during construction.
5. All materials and systems shall be installed as per manufacturer's specifications and all construction shall be of industry standard or better.
6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to a change in the scope of work.
7. In the event of conflict between data shown on drawings and data shown in the Specification, the Work of greater quality or quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted. Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is discovered.
8. Immediately notify Architect of any long lead items that will affect the completion date
9. All wood in contact with concrete or concrete block to be pressure treated - typical.
10. Provide metal backing and / or treated wood blocking for all wall mounted equipment (grab bars, toilet room accessories, TV mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.
11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code.
Fireproof any new penetrations required by the work. Refer to code summary for ratings.
12. All exposed metal to receive paint unless otherwise noted
13. All adjacent dissimilar materials to receive caulking, including equipment mounted to walls
1/4" = 1'-0"
Work Room N 1/8" = 1'-0"
ROLLING SERVICE DOOR INFILL
1/4" = 1'-0"
Level 1 Amb. Bay RCP
AMBULANCE BAY ROOM FINISH SCHEDULE
NO. NAME
FLOOR WALL FINISH CEILING
NOTESFINISH BASE NORTH EAST SOUTH WEST MAT'L FINISH
101 Flex Space VCT-1 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
102 Cooridoor CPT-1 RBR PNT-1 PNT-1 PNT-1 PNT-1 SACT
103 Work Room CPT-1 RBR PNT-1 PNT PNT PNT SACT
104 Office 1 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
105 Office 2 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
106 Office 3 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
107 Office 4 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
108 Office 5 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
109 Office 6 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
110 Office 7 CPT-2 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
DOOR AND FRAME SCHEDULE - AMBULANCE GARAGE
DOOR FRAME
FIRE LABEL
HDW.
NO. NOTESNO. WIDTH HEIGHT TYPE TYPE
DETAIL
HEAD JAMB SILL
101 4'-0" 7'-0" A -- 10
102 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
104 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 11
105 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
106 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
107 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
108 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
109 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
110 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 04
RCP General Notes
1. Coordinate final locations of ceiling mounted equipment w/ owner and architect.
2. See M&E drawings for lighting, grills, and diffuser locations.
3. Suspended acoustical ceiling tile grid is to be centered in rectangular room or centered between the longest walls of irregularly shaped rooms unless otherwise noted.
4. Verify gypsum board control joint locations with architect prior to installation.
5. Ceiling heights indicated are from finished floor of current level shown.
1 1/2" = 1'-0"
Bulkhead
REF.
R E
F
R E
F
REF.
9'-6"
8'-8 1/2"
5'-9 1/8"6'-4 7/8"6'-10 3/4"
340 SF
WAITING
RX111
OFFICE
RX109
COUNS.
RX108
CONTROLLED
SUBSTANCES
RX103
Office
RX105
PHARMACY
RX102
STAFF
ENTRY
RX101
A7.1
A7.16.
A7.1
A7.1
8.
SCA
RX112A
SY
SY
3.
R X
R X
A
COUNS.
RX112
A7.1
5.
1SY
1SY
8'-10 3/4"
RX114
NO WORK
14'-3 3/4"
SC
SC
A8.1
NO WORK
SO
A7.1
4.
14'-3 3/4"
/4
/8
A7.1
10.
A7.1
A7.1 17
10'-0"
A7.1
1"
A7.1
9.
E Q
E Q
A7.1 12
HAZ STOR
RX113
A7.1
11.
2'-1"
1'-6"
Office
RX104
ANTI
RX106
HOOD
RX107
COUNS.
RX110
RX108A
R X
B
RX109
RX111
RX106
R X
R X
R X
B
RX113B
RX113A
/8
7'-8 3/4"
/2
/2
/4
R X
B
/2
6'-2 7/8"
5'-5 7/8"
5'-0"
/4
/8
/8
/8
/2
1SY
1SY
1SY
1SY
5C
6A
SCA
5C
5C
1SY
RX110A
2'-9" 3'-0"
RX110B
0"
A8.1
3'-9 3/8"
6'-0 7/8"
A7.1
COUNTER B
8'-4"
3'-3 1/8"
14'-6"
AL-W1 AL-W1
A L-
W
'-1
8"
10'-0"
6 3/4"
1SY
SCA
SCA
HM-W3
HM-W3
WORK STATIONS TO BE
SYSTEMS FURNITURE
SUPPLIED
AND INSTALLED IN THIS
CONTRACT
3'-0"
A8.1
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:54 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A2.2
Pharmacy
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
14817
1. General Notes apply to all drawing sheets.
2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen conditions, discrepancies, errors, or inconsistencies.
3. Work shall be done in accordance with all rules and regulations of all applicable safety and building codes. The General Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections during the course of the project.
4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property, public thoroughfares, etc. Maintain all required exits during construction.
5. All materials and systems shall be installed as per manufacturer's specifications and all construction shall be of industry standard or better.
6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to a change in the scope of work.
7. In the event of conflict between data shown on drawings and data shown in the Specification, the Work of greater quality or quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted. Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is discovered.
8. Immediately notify Architect of any long lead items that will affect the completion date
9. All wood in contact with concrete or concrete block to be pressure treated - typical.
10. Provide metal backing and / or treated wood blocking for all wall mounted equipment (grab bars, toilet room accessories, TV mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.
11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code.
Fireproof any new penetrations required by the work. Refer to code summary for ratings.
12. All exposed metal to receive paint unless otherwise noted
13. All adjacent dissimilar materials to receive caulking, including equipment mounted to walls
Floor Plan General Notes A Interior dimensions are to finished face of stud wall, face of masonry walls, to centerline of columns or to other grid points unless otherwise noted. Dimensions labeled as CLEAR or CLR indicate minimum distance to finished face of walls. Dimensions are to finished face of existing walls if applicable.
B All interior door frames to be 4" from adjacent wall or centered between walls unless otherwise noted.
C Furniture & equipment shown is for reference only and is not included in the contract.
D Coordinate size and location of all duct and shaft openings in walls and floors with MEP consultant.
E Fire rated walls are indicated on the Life Safety Plan.
F All partitions are type "SC" unless noted otherwise
G Provide a corner guard where symbol is shown at a wall corner
1/4" = 1'-0"
New Pharm.
êÉîáëáçå=L
9'-0"
14'-8 5/8"
/8
1'-3"
8'-11"
9'-0"
9'-0"
9'-0"
9'-0"8'-0"
9'-0"
9'-0"
9'-0"
9'-0"
/8
7'-4"
1'-3"
'-3
1'-6"
1'-6"
9'-0"
9'-0"
9'-0"
7'-0"
9'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
7'-0"
7'-2"
7'-0"
7'-0"
7'-0"
A8.1
A8.1
/4
8'-8 1/2"
7'-0"
7'-0"
7'-2 5/8"
9'-0"
COUNS.
RX112
HAZ STOR
RX113
Office
RX104
Office
RX105
ANTI
RX106
HOOD
RX107
CONTROLLED
SUBSTANCES
RX103
PHARMACY
RX102
COUNS.
RX110
OFFICE
RX109
COUNS.
RX108
STAFF
ENTRY
RX101
WAITING
RX111
PHARMACY
RX102
PHARMACY
RX102
/4
2'-5 3/4"
Reflected Ceiling Plan Legend
GYPSUM BOARD
SACT-1
2'-0" X 2'-0" SUSPENDED
ACOUSTICAL CEILING TILE
AND GRID
SACT-2
WASHABLE 2'-0" X 2'-0"
SUSPENDED ACOUSTICAL
CEILING TILE AND GRID
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:55 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A3.1
First Floor RCP
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
RCP General Notes
1. Coordinate final locations of ceiling mounted equipment w/ owner and architect.
2. See M&E drawings for lighting, grills, and diffuser locations.
3. Suspended acoustical ceiling tile grid is to be centered in rectangular room or centered between the longest walls of irregularly shaped rooms unless otherwise noted.
4. Verify gypsum board control joint locations with architect prior to installation.
5. Ceiling heights indicated are from finished floor of current level shown.
1 : 50
Pharmacy RCP
Door Types
TYPE "A" TYPE "B" TYPE "C" TYPE "D"
7"
6"
6"6"
2'-0"
6" 6"
G9
G9
G2
**ALL NEW DOORS
ARE TO BE SOLID
CORE WOOD.
SPECIES AND COLOR
TO MATCH EXISTING.
SEE SPEC.**
Frame Types
HM-F1
Hollow Metal
FRAME WIDTH IS 2" UNLESS OTHERWISE DIMENSIONED. FRAME DEPTH TO
MATCH WALL THICKNESS PER INDUSTRY STANDARDS UNLESS OTHERWISE
NOTED. SEE DETAILS.
HM-Fx Insulated
Hollow Metal
SEE SCHED
S E
E S
C H
E D
U
LE
SEE SCHED
S E
E S
C H
E D
U
LE
AL-F1
Aluminum -
Thermally Broken
SEE SCHED
S E
E S
C H
E D
U
LE
5/8" GYP. BD. EA. SIDE
MTL. STUD @ 16" O.C. FILL
W/ BATT INSUL. SEE WALL
TYPES
CONT. SEALANT
BOTH SIDES
H.M. FRAME
DOOR PANEL; SEE TYPES
MTL. STUD CHANNEL - SEE
STRUCT. FOR LINTEL
CONT. SEALANT BOTH SIDES
H.M. FRAME
DOOR PANEL; SEE TYPES
METAL STUDS @ 16" O.C.
FILL W/BATT INSUL; SEE
WALL TYPES
STL. ANCHORS (3 PER JAMB,
FLOOR CLIP EA. JAMB)
METAL STUDS (2)
5/8" GYP. BD. BOTH SIDES
Glazing Types
G2: 1/4" TEMPERED, CLEAR GLAZING
G9: BALLISTIC GLAZING
Window Types
HM-W1
FRAME WIDTH IS 2" UNLESS OTHERWISE DIMENSIONED. FRAME DEPTH TO MATCH WALL
THICKNESS PER INDUSTRY STANDARDS UNLESS OTHERWISE NOTED. SEE DETAILS.
3'-4"
HM-W3HM-W2
3'-0"
G9 G2
G9
S E
E E
LE
V
A
TI
O N
S
3'-0"
AL-W1
4'-0"
G9
Wall Types
SCA
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
OPTION "A" ONLY
3.5" METAL STUB AT 1'-3.75" O.C. TO
1/2" ABOVE CEILING W/ ACOUSTICAL
INSULATION W/ 1/8" GWB BOTH
SIDES. PROVIDE ACOUSTICAL
INSULATION 2'-0" ON BOTH SIDES OF
PARTITION ABOVE CEILING
S6CA
3.5" METAL STUDS AT 1'-3.75" O.C.
INSULATION W/ 1/8" GWB BOTH SIDES.
PROVIDE ACOUSTICAL INSULATION 2'-0"
ON BOTH SIDES OF PARTITION ABOVE
CEILING
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
1SA
3 5/8" METAL STUD
@ 16" O.C.
BATT INSULATION
OPTION "A" ONLY
3.5" METAL STUDS AT 1'-3.75" O.C.
W/ 1/8" FR GWB BOTH SIDES W/
ACOUSTICAL INSULATION TO
SECURE
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE SCHEDULE
5/8" GYP.BD.
NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED
4 7/8" 4 7/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SY
SAY
S6AY
3.5" METAL STUD AT 1'-3.75" O.C. W/
1/8" GWB BOTH SIDES TO STRUCTURE.
DIAMOND SECURITY MESH ATTATCHED
TO ONE SDE OF STUD.
3.5" METAL STUD AT 1'-3.75 O.C. W/
ACOUSTICAL INSUKATION W/ 1/8" GWB
BOTH SIDES TO STRUCTURE. DIAMOND
SECURITY MESH ATTATCHED TO ONE SIDE
OF STUD.
6" METAL STUDS AT 1'-3.75" O.C. W/
ACOUSTICAL INSULATION W/ 1/8" GWB BOTH
SIDES TO STRUCTURE. dIAMOND SECURITY
MESH ATTATCHED TO ONE SIDE OF STUD.
NON-RATED PARTITION ONE HOUR FIRE RATING
UL DES NO. U465
S
3.5" METAL STUB AT 1' 3.75" O.C. W/
1/2" GWB BOTH SIDES TO
STRUCTURE
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD.
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
OPTION "O" - ONE GWB FACE ONLY
SO
3.5" METAL STUDS AT 1'-3.75" O.C.
W/ 1/8" FR GWB ONE FACE ONLY
SC
3.5" METAL STUB AT 1'-3.75" O.C. TO
1/2" ABOVE CEILING W/ 1/8" GWB
BOTH SIDES 1SY
3.62" METAL STUDS AT 1'-3.75" O.C.
W/ 1/8" FR GWB BOTH SIDES TO
STRUCTURE WITH DIAMOND
SECURITY MESH ATTACHED TO ONE
SIDE OF STUD
ROOF OR FLOOR
STRUCTURE
7A
6" METAL STUD @
16" O.C.
BATT INSULATION
METAL STUD WALL TO
STRUCTURE
6" METAL STUD
CHANNEL
6" METAL STUD
DEFLECTION TRACK
BASE - SEE SCHEDULE
ROOF OR FLOOR
STRUCTURE
5/8" GYP.BD.
ACOUSTIC SEALANT
EA. SIDE
ACOUSTIC SEALANT
CLG WHERE APPLICABLE;
SEE RCP
7 1/4"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
CLG WHERE
APPLICABLE; SEE RCP
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
1 5/8" METAL STUD
@ 16" O.C.
1 5/8" METAL STUD
CHANNEL
1 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE SCHEDULE
5/8" GYP.BD.
2A
FURRING OVER
EXISTING WALL TO
STRUCTURE
Exterior Wall Assemblies
6" MTL STUD
1.2" RIGID INSULATION
2" AIR SPACE
FACE BRICK
1/2" GYP SHEATHING
BRICK TIE
5/8" GYP
BATT INSULATION
VAPOR BARRIER
BUILDING FELT
1.2" RIGID INSULATION
2" AIR SPACE
1/2" GYP SHEATHING
FACE BRICK
BUILDING FELT
8" CMU
AMBULANCE BAY WALL INFILLPHARMACY WINDOW INFILL
** FIELD VERIFY**
** FIELD VERIFY**
5/8" GYP
VAPOR BARRIER
6" MTL STUD AND BATT
INSULATION
SHEETING
BRICK TIES
BUILDING FELT
MORTAR GUARD
FACE BRICK W/ FULL
HEAD WEAPS
THRU WALL FLASHING
LEDGE ANGLE
SHEET MTL CLOSURE
2 10 BLOCKING
SEALANT BOTH SIDES
ALUMINUM WDW
** FIELD VERIFY**
SILL AND TRIM
2x6
BLOCKING
ALUMINUM FRAMING
SEALANT W/ BACKER
ROD
MEMBRANE
FLASHING
BRICK SILL
SEALANT W/ BACKER ROD
METAL DRIP EDGE
GROUT FILL
ELASTOMERIC FLASHING
8" STUD WITH BATT INSULAION
SEE BRICK INFILL FOR MORE DETAIL
BRICK TIES
** FIELD VERIFY**
THRU WALL FLASHING
8" CMU W/ WEEPS
2x10 BLOCKING
MORTAR GUARD
SEALANT W/ BACKER ROD
MTL DRIP EDGE
ALUMINUM FRAMING
** FIELD VERIFY**
SELF ADHESIVE
MEMBRANE FLASHING
8" CMU
2 x10 BLOCKING
SEALANT BOTH SIDES
SILL BELOW
WOOD BLOCKING
** FIELD VERIFY**
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:09:58 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A4.1
Schedules and Types
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
1 1/2" = 1'-0"
HM Door Head @ Metal Stud Wall 1 1/2" = 1'-0"
HM Door Jamb @ Metal Stud Wall
PHARMACY ROOM FINISH SCHEDULE
NO. NAME
FLOOR WALL FINISH CEILING
NOTESFINISH BASE NORTH EAST SOUTH WEST MAT'L FINISH
RX101 STAFF ENTRY SV COVE PNT-3 PNT-3 PNT-3 PNT-3 SACT
RX102 PHARMACY SV COVE PNT-1 PNT-1 PNT-1 PNT-1 SACT
RX103 CONTROLLED SUBSTANCES SV COVE PNT-1 PNT-1 PNT-1 PNT-1 SACT
RX104 Office VCT-1 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
RX105 Office VCT-1 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
RX106 ANTI SV COVE PNT-1 PNT-1 PNT-1 PNT-1 SACT washable
RX107 HOOD SV COVE PNT-1 PNT-1 PNT-1 PNT-1 SACT washable
RX108 COUNS. SV COVE PNT-3 PNT-3 PNT-3 PNT-3 SACT
RX109 OFFICE VCT-1 RBR PNT-2 PNT-2 PNT-2 PNT-2 SACT
RX110 COUNS. SV COVE PNT-3 PNT-3 PNT-3 PNT-3 SACT
RX111 WAITING VCT-1 RBR PNT-3/VWC PNT-3/VWC PNT-3/VWC PNT-3/VWC SACT
RX112 COUNS. SV COVE PNT-3 PNT-3 PNT-3 PNT-3 SACT
RX113 HAZ STOR SV COVE PNT-1 PNT-1 PNT-1 PNT-1 SACT
DOOR AND FRAME SCHEDULE - PHARMACY
DOOR FRAME
FIRE LABEL
HDW.
NO. NOTESNO. WIDTH HEIGHT TYPE TYPE
DETAIL
HEAD JAMB SILL
RX101A 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 02
RX101B 3'-0" 7'-0" D HM-F1 1/A4.1 2/A4.1 08
RX104 3'-0" 7'-0" B HM-F1 1/A4.1 2/A4.1 04
RX105 3'-0" 7'-0" B HM-F1 1/A4.1 2/A4.1 04
RX106 3'-0" 7'-0" D HM-F1 1/A4.1 2/A4.1 01
RX107 3'-0" 7'-0" D HM-F1 1/A4.1 2/A4.1 01
RX108A 3'-0" 7'-0" B HM-F1 1/A4.1 2/A4.1 02
RX108B 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 05
RX109 3'-0" 7'-0" B HM-F1 1/A4.1 2/A4.1 04
RX110A 3'-0" 7'-0" B HM-F1 1/A4.1 2/A4.1 02
RX110B 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 03
RX111 6'-0" 7'-0" C HM-F1 1/A4.1 2/A4.1 -- 09
RX112A 3'-0" 7'-0" B HM-F1 1/A4.1 2/A4.1 02
RX112B 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 06
RX113A 3'-0" 7'-0" D HM-F1 1/A4.1 2/A4.1 07
RX113B 3'-0" 7'-0" A HM-F1 1/A4.1 2/A4.1 -- 07
RX114 3'-0" 7'-0" D HM-F1 1/A4.1 2/A4.1 02
1 1/2" = 1'-0"
Head Detail @ Brick
1 1/2" = 1'-0"
Sill Detail @ Brick
1 1/2" = 1'-0"
Head Detail @ CMU
1 1/2" = 1'-0"
Jamb Detail @CMU
NOT USED NOT USED
êÉîáëáçå=L
ADA LOCKER
STAFF LOCKERS
1'-0"
9'-0"
SLANTED TOP
1'-9"
PRINTER
DRAWER
SOFFIT
VALANCE
KNEE SPACE
W/ CENTER
PANEL
KNEE SPACE
W/ CENTER
PANEL
KNEE SPACE
W/ CENTER
PANEL
1'-9" 2'-6" 2'-6" 2'-6" 2'-6" 1'-9"
P-LAM CTOP
2'-8" 2'-0" 2'-9" 2'-0" 2'-9 1/4"
24" D PLAM BASE CAB
15" D PLAM
WALL CABINETS
OPEN TO OTHER SDE
A8.1
KNEE
SPACE
TACK-ABLE SURFACE
W/ FRAME SURROUND
/4
1'-6" 2'-5 3/4" 2'-0"
PRINTER DRAWER
SOFFITT
2'-6" 2'-6" 2'-6" 1'-3"
1"
P-LAM CTOP
24" D PLAM BASE CAB
15" D PLAM
WALL CABINETS
A8.1
LIGHT VALLANCE
2'-9"
OVER-SINK
EYE WASH
R.O. FILLER
SOFFIT
PT DISP.
4'-0"
1'-6"
24" D PLAM BASE
CAB.
P-LAM CTOP
SOAP DISP.
15" D PLAM WALL CAB
FILLER PANEL
FILLER PANEL
MED PICK UP
STOR.
A8.1
7'-11 1/2"
1'-9" 2'-6" 2'-6" 2'-6"
PRINTER DRAWER
SOFFIT
OPEN TO OTHER SDE LIGHT VALANCE
KNEE SPACE
W/ CENTER
PANEL
KNEE SPACE
W/ CENTER
PANEL
KNEE SPACE
W/ CENTER
PANEL
P-LAM CTOP
1'-9"2'-8"2'-0"2'-9"2'-0"2'-9 1/4"
" 24" D PLAM BASE CAB
15" D PLAM
WALL CABINETS
A8.1
5'-4"5'-5 1/8"
LOCKED
NARCOTICS
CABINET
KNEE SPACE KNEE
SPACE
24"D PLAM
DRAWERS
1'-9"3'-6 1/2" 3'-2 3/8"2'-0"
PLAM C TOP
2'-0" 2'-9"
3'-0" 3'-0"
5'-6 1/8"
4'-3 1/8"
24" D PLAM
CABINET
15" D PLAM
WALL CABINET
PLAM C TOP
FIREPROOF
CABINET
PT DISP.
EYE WASH
SOAP DISP.
1'-3" 2'-6"
24" D PLAM BASE CAB
15" D WALL CABINETS
C TOP, BSP,SSP
2'-1" 1'-9" 1'-9"2'-2"
2'-0" 2'-0" 2'-0"
MED STORAGE
24" D PLAM
OPEN SHELVING
A8.1
Sim
2'-0"
2'-0" 2'-0" 1'-6"
2'-0"2'-8" 2'-8"
2'-6"2'-0"2'-6"
PRINTER
DRAWER
SOFFIT
VALANCE
KNEE SPACE
P-LAM CTOP
15" D PLAM
WALL CABINETS
TACK-ABLE SURFACE
W/ FRAME SURROUND
KNEE SPACE
1'-3" 2'-6" 2'-9" 2'-0"
1'-3" 2'-6" 2'-9" 2'-0"
15" D PLAM
WALL CAB.
PT DISP.
SOAP DISP.
PLAM CTOP,
BSP, SSP
24" D PLAM
BASE CAB.
VERT GB
FILER PANEL
FILER PANEL WORK STATIONS TO BE
SYSTEMS FURNITURE
SUPPLIEDAND INSTALLED
IN THIS CONTRACT
2'-0"1'-9" 2'-0"
15" D WALL SHELVING
OPEN TO OTHER SIDE
24" D PLAM
BASE CAB
MED SHELVING
24" D OPEN
BASE SHELVING
PLAM C TOP
2'-9"2'-9"
A8.1
Sim
3'-0"1'-3"1'-9"2'-1"
15" D WALL SHELVING
OPEN TO OTHER SIDE
MED SHELVING
24" D PLAM
BASE CAB
24" D OPEN
BASE SHELVING
PLAM C TOP
2'-0"2'-0"2'-0"2'-0"
" 5
A8.1
Sim
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:10:02 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A7.1
Interior Elevations
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
1/4" = 1'-0"
Staff Entry - E 1/4" = 1'-0"
3.
East Island - S
1/4" = 1'-0" 5.
Controlled Substance 1/4" = 1'-0"
6.
Counter D Sink
1/4" = 1'-0" 8.
Med. Storage
1/4" = 1'-0" 4.
East Island - N
14817
1/4" = 1'-0" 9.
Patient Side Disp 1/4" = 1'-0"
10.
Provider Side Disp.
1/4" = 1'-0" 11.
Haz Med Receiving 1/4" = 1'-0"
Haz Med Sink
1/4" = 1'-0"
Anti Room North 1/4" = 1'-0"
Anti Room East
1/4" = 1'-0"
Counter C
1/4" = 1'-0"
Disp. South 1/4" = 1'-0"
Center Work Station
1/4" = 1'-0"
Counter B Back - Side2 1/4" = 1'-0"
Counter B Back2
LVL 3 BALLISTIC WINDOW
W/ SPEAK AROUND
LVL 3 BALLISTIC
PACKAGE RECEIVER
SOAP DISP.
PT DISP.
PLAM C TOP BSP, SSP
24" D PLAM
BASE CAB.
LVL 3 BALLISTIC
PACKAGE RECEIVER
LVL 3 BALLISTIC WINDOW
W/ SPEAK AROUND
êÉîáëáçå=L
ADJUSTABLE PLAM OVER 3/4"
SUBSTRATE SHELVES
6" STEEL STUDS WITH 6" BATT INSULATION
RIGID INSULATION
PRECAST CONCRETE SILL
5/8" GWB
VAPOR BARRIER
1/2" SHEATHING
BUILDING FELT
BRICK TIES
FACE BRICK
MORTAR GUARD
WEEPS
SEALANT W/ BACKER ROD
THRU WALL FLASHING
SACT, SEE RCP
SEE WALL TYP
3'-0"
S E
E R
C P
LIGHT VALANCE
SACT, SEE RCP
SACT, SEE RCP
SEE WALL TYP
S E
E R
C P
SACT, SEE RCP
S E
E R
C P
SACT, SEE RCP
SEE WALL TYPE
S E
E R
C P
SACT, SEE RCP
3 5/8" MTL STUD
WALL
S E
E R
C P
S E
E N
O
TE
A B
O V
E
TYPICAL FIXTURES AND ACCESSORIES MOUNTING HEIGHTS
SOAP DISPENSER
FOR SIDE APPROACH
4'-0" CLEAR FLR. SPACE
M A
X
H T.
C
O U
N
TE
R S
S E
E N
O
TE
A B
O V
E
PAPER TOWEL DISPENSERS
KNEE CLEARANCE TOE CLEARANCE
KNEE CLEARANCE
TOE CLEARANCE
MIN
11"
25" MAX
17" - 25"
6" MAX
MIN
8"
M
IN
F.E.C.
RECESSED F.E.C. MOUNT
CONTROLS @ 40" A.F.F.
FIRE EXTINGUISHER CABINET
FRONT VIEW
M A
X
O P
E R
A B
LE
P
A R
TS
O P
E R
A B
LE
P
A R
TS
M
IN
COUNTER
W/ BACK
SPLASH
S E
E T
A B
LE
.6 D
IM
B
NOTE: TO OPERABLE PART OF PTD & HAND DRYERS
WITHOUT COUNTER OR OBSTRUCTION TYPICAL:
48" MAX FORWARD APPROACH & SIDE APPROACH
(A) MAX
S E
E T
A B
LE
.6
(B
M A
X
M A
X R
E A
C H
D
E P
TH
A
M A
X R
E A
C
E
IG
H T
(B
0.5" 48"
2" 46"
5" 42"
6" 40"
9" 36"
11" 34"
TABLE 603.6
PAPER TOWEL DISPENSER FRONT VIEW @
COUNTER OR LAVATORY IN TOILET &
BATHING ROOMS (HAND DRYER SIM.)
BASE AS
SCHEDULED
24" D BASE CAB:
INCLINE OPEN
DRAWERS W/
ADJUSTABLE
VERTICAL
DIVIDERS
PLAM INTERIOR
PULLOUT PLAM
SHELF
BASE AS SCHEDULED
COORDINATE W/ ELEC.
FOR OUTLETS
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
1/17/2024 8:10:04 AM
022003.00
Author
Checker
01/12/2024
Woodrow Wilson Keeble Memorial Health Center USP Compliance
A8.1
Details
100 Lake Traverse Drive Sisseton, SD 57262 IHS Project #
HHSI102201800141
3/4" = 1'-0"
Adjust. Shelving 3/4" = 1'-0"
Window Infill
14817
1 1/2" = 1'-0"
TYP. OVER COUNTER SOFFT DETAIL
1 1/2" = 1'-0"
RECEPTION SOFFIT DETAIL
1 1/2" = 1'-0"
Typ. Lg. Bulkhead Dtl 3/4" = 1'-0"
TYP. Soffit
1/2" = 1'-0"
Fixture Mounting Heights
3/4" = 1'-0"
CABINET MED STORAGE
1 1/2" = 1'-0"
Printer Drawer êÉîáëáçå=L
MECHANICAL SHEET INDEX
CONTROL VALVE
THREE WAY MOTORIZED
SOLENOID VALVE
PRESSURE REDUCING VALVE
MOTORIZED CONTROL VALVE
TYPE (SEE SCHEDULE)
TYPE (SEE SCHEDULE)
MECHANICAL EQUIPMENT FOR REFERENCE
INFORMATION)
(REFER TO OTHER DISCIPLINE FOR ADDITIONAL
MECHANICAL EQUIPMENT TAG
PIPE SLOPE TAG
PIPE INVERT ELEVATION TAG
BELOW GROUND PIPING
45 DEGREE TEE
REDUCING 45 DEGREE TEE
PIPE TEE
PIPE DROP
PIPE RISE
PLUMBING FIXTURE
PLUMBING FIXTURE TAG
DRAIN TAG
TYPE (SEE SCHEDULE)
ROOF DRAIN FIXTURE
DRAIN SIZE
FLOOR DRAIN FIXTURE
DRAIN SIZE
DRAIN TAG
EXISTING MECHANICAL EQUIPMENT
PIPE SIZE TAG (DIAMETER)
ABOVE GROUND PIPING
TYPE (SEE SCHEDULE)
BUTTERFLY VALVETHREE WAY VALVE
MANUAL SWITCH
TEMPERATURE SENSOR
THERMOSTAT
PIPING BEING DEMOLISHEDDUCT BEING DEMOLISHED
EQUIPMENT ABBREVIATIONS
WATER HEATERWH
WATER FLOW MEASURING STATIONWFMS
UNIT VENTILATORUV
UTILITY SETUS
UNIT HEATERUH
SUMP PUMPSP
SUPPLY FANSF
SEWAGE EJECTOR PUMPSEP
SOUND ATTENUATORSAT
SHOCK ABSORBERSA
ROOFTOP UNITRTU
RETURN/EXHAUST FANRE
POWER WALL FANPWF
POWER ROOF VENTILATORPRV
PROPELLER FANPF
INLINE CENTRIFUGALILC
HEAT RECOVERY UNITHRU
HEAT PUMP UNITHPU
HEAT EXCHANGERHX
HEATING WATER PUMPHWP
HUMIDIFIERH
GRAVITY ROOF VENTILATORGRV
GREASE INTERCEPTORGI
FIRE PUMPFP
FAN COIL UNITFCU
ELECTRIC WATER HEATEREWH
EXPANSION TANKET
ELECTRIC DUCT COILEDC
EXHAUST FANEF
DOMESTIC WATER CIRCULATING PUMPDCP
DUCT MOUNTED COILDC
DOMESTIC WATER BOOSTER PUMPDBP
CHILLED WATER PUMPCHWP
CONDENSER WATER PUMPCWP
CABINET UNIT HEATERCUH
COOLING TOWERCT
CONDENSATE RETURN UNITCRU
CHILLERCH
CHEMICAL FEEDER PUMPCFP
CHEMICAL FEEDERCF
CABINET FANCF
BOILERB
AIR SEPARATORAS
AIR HANDLING UNITAHU
AIR FLOW MEASURING STATIONAFMS
AIR COOLING CONDENSING UNITACCU
AIR COOLED CONDENSERACC
AIR CONDITIONING UNITAC
AREA NOT IN CONTRACT
ITEM TO BE DEMOLISHED
CHECK VALVE
BALL VALVE
BALANCING DEVICE
FLOW MEASURING AND
DOMESTIC WATER METER
EXISTING PIPE TAG
NUMBER OF SLOTS
SLOT LENGTH
TYPE (SEE SCHEDULE)
CFM
LINEAR DIFFUSER TAG
ROUND DUCT SIZE TAG (DIAMETER)
MECHANICAL EQUIPMENT
LINEAR DIFFUSER
RETURN/EXHAUST INLETSUPPLY OUTLET
TEMPERATURE & HUMIDITY SENSOR
SENSOR
NITROGEN DIOXIDE SENSOR
HUMIDITY SENSOR
HUMIDISTAT
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
COMBINATION FIRE/SMOKE DAMPER
BACKDRAFT DAMPER
MANUAL BALANCING DAMPER
MOTORIZED DAMPER
SMOKE DAMPER
FIRE DAMPER
MECHANICAL ABBREVIATIONS
WATERWTR
WIRE MESH SCREENWMS
WALL HYDRANT / WATER HEATERWH
WALL CLEAN OUTWCO
WATER CLOSETWC
WET BULBWB
SANITARY WASTEW
VENT THROUGH ROOFVTR
VOLUME DAMPERVD
VARIABLE AIR VOLUMEVAV
VENTV
URINALUR
UNIT HEATERUH
UNDERGROUNDUG
UNDER FLOOR DUCTUFD
TYPICALTYP
TELL-TALE FLOOR DRAINTTFD
TEMPERATURE SENSORTS
TRENCH DRAINTD
TEMPERATURE DIFFERENCETD
THERMOSTATT
STRUCTURALSTRUCT
STEAMSTM
SQUARE FEETSQ FT
SPECIFICATIONSPEC
STATIC PRESSURESP
SLEEVESLV
SIMILARSIM
STORM DRAINSD
SECURITY BARSSB
SANITARYSAN
SUPPLY AIRSA
RAIN WATERRW
REVOLUTIONS PER MINUTERPM
ROOMRM
REHEAT COILRHC
RETURN IN COVERRIC
RELATIVE HUMIDITYRH
REGISTERREG
RECIRCULATIONRECIRC
ROOF DRAINRD
REFLECTED CEILING PLANRCP
RETURN AIRR/A
POLY VINYL CHLORIDEPVC
POUNDS PER SQUARE INCH GAUGEPSIG
POUNDS PER SQUARE INCH ABSOLUTEPSIA
POWER ROOF VENTILATORPRV
PLUMBINGPLBG
PRESSURE DROPPD
OVERFLOW ROOF DRAINORD
OVERFLOWOF
OUTSIDE AIROA
NOT TO SCALENTS
NORMALLY OPENNO
NOT IN CONTRACTNIC
NORMALLY CLOSEDNC
MISCELLANEOUSMISC
MINIMUMMIN
MANHOLEMH
MANUFACTURERMFR
MECHANICALMECH
ONE THOUSAND CUBIC FEETMCF
ONE THOUSAND BTU PER HOURMBH
LEAVING WATER TEMPERATURELWT
LINEAL FOOTLF
LAVATORYLAV
LEAVING AIR TEMPERATURELAT
POUNDLB
INVERTINV
HYDRANTHYD
HOT WATERHW
HEATING VENTILATION & AIR CONDITIONINGHVAC
HEATERHTR
HEATINGHTG
HORSEPOWERHP
HOPPER DRAINHD
HOSE BIBBHB
GREASE WASTEGW
GRILLEGR
GALLONS PER MINUTEGPM
GALLONS PER HOURGPH
GALLONGAL
GAGE/GAUGEGA
FIN TUBE RADIATIONFTR
FOOTINGFTG
FLOAT & THERMOSTATIC STEAM TRAPF & T
FOOT/FEETFT
FIRE/SMOKE DAMPERFSD
FLOOR SINKFS
FEET PER SECONDFPS
FEET PER MINUTEFPM
FLEXIBLEFLEX
FLOOR DRAINFD
FAHRENHEITF
EXPANSIONEXP
EXISTINGEXIST
EXHAUSTEXH
ENTERING WATER TEMPERATUREEWT
ELECTRIC WATER COOLEREWC
EQUIPMENTEQUIP
EQUALEQ
EXPLOSION PROOFEP
EXHAUST FANEF
EQUIVALENT DIRECT RADIATIONEDR
ENTERING AIR TEMPERATUREEAT
EACHEA
DISTILLED WATERDW
DRAWINGDWG
DOWNDN
DAMPERDMPR
DEIONIZED WATERDI
DIAMETERDIA
DRINKING FOUNTAINDF
DRY BULBDB
COLD WATERCW
CHECK VALVECV
CENTER LINECL
CONVECTORCONV
CONTRACTORCONTR
CONDENSATECOND
COMBINATIONCOMB
CLEAN OUTCO
CEILINGCLG
CIRCULATING HOT WATERCHW
CUBIC FEET PER MINUTECFM
CUBIC FEET PER HOURCFH
CONSTANT FLOW CONTROL VALVECFCV
HUNDRED CUBIC FEETCCF
CATCH BASINCB
BACKWATER VALVEBWV
BRITISH THERMAL UNITS PER HOURBTUH
BRITISH THERMAL UNITSBTU
BELOW FINISHED FLOORBFF
ACID RESISTANT WASTEAW
ACID RESISTANT VENTAV
ADJUSTABLE SPEED CONTROLLERASC
AIR SEPARATORAS
ARCHITECTARCH
ACCESS PANELAP
ACOUSTIC LINERAL
ANNUAL FUEL UTILIZATION EFFICIENCYAFUE
ABOVE FINISHED FLOORAFF
AREA DRAINAD
(TYPICAL FOR ALL EXISTING TAGS)
EXISTING MECHANICAL EQUIPMENT TAG
MECHANICAL EQUIPMENT TAG
HVAC SYMBOLS
POINT WHERE NEW CONNECTS TO EXISTING
ROOM NAME AND NUMBER
GENERAL MECHANICAL SYMBOLS
REVISION NUMBER - SHOWN ON PLANS
NUMBER OF DETAIL ON SHEET
NUMBER OF SHEET WHERE DETAIL APPEARS
SQUARE DUCT SIZE TAG (WIDTH / HEIGHT)
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
EXISTING DUCT TAG
CONTINUATION SYMBOL
KEYNOTE
CFM
GRILLES, REGISTERS, AND DIFFUSERS TAG
PLUMBING AND PIPING SYMBOLS
CD-125
48" x (2) 3/4" SLOTS
LSD-500
Space
XXX-X
XXX-X
XXX-X
WH-1
4" ORD-1
6" FD-2
4" RD-1
16"Ø
FS
BD
M
S
F
(E)
16/8
16/8
X" V UP THRU FLOOR
PROPANE GASPG
1/4" / 12" SLOPE
INV. ELEV:94' - 11"
REFRIGERANT-HOT GASREF-HG
4"4"
4"
2"
PLUG
CAP
2"
REFRIGERANT-SUCTION
REFRIGERANT-LIQUID
REF-S
REF-L
STORM DRAINAGE-OVERFLOW
STORM DRAINAGE
STEAM
SOLAR HOT WATER SUPPLY
SOLAR HOT WATER RETURN
SANITARY SEWER
SANITARY VENT
PUMP DISCHARGE
OIL WASTE
OIL VENT
NATURAL GAS
HEATING WATER SUPPLY
HEATING WATER RETURN
GREASE WASTE
GREASE VENT
DOMESTIC HOT WATER-CIRCULATING 140°
DOMESTIC HOT WATER-CIRCULATING
DOMESTIC HOT WATER 140°
DOMESTIC HOT WATER
DOMESTIC COLD WATER-SOFT
DOMESTIC COLD WATER-HARD
DOMESTIC COLD WATER-FILTERED
DOMESTIC COLD WATER
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CONDENSATE RETURN
CONDENSATE DRAINAGE
COMPRESSED AIR
COMBINATION WASTE & VENT
CHILLED WATER SUPPLY
CHILLED WATER RETURNCHWR
(E)
ORWL
RWL
STM
SHWS
SHWR
W
V
PD
OW
OV
G
HWS
HWR
GW
GV
RHW 140°
RHW
HW 140°
HW
SOFT
HARD
F-CW
CW
CWS
CWR
CDR
CD
CA
CWV
CHWS
SH
SWHS
TNO2
TSCO
THCO2
EXISTINGEX or EX.
M0.1 Mechanical Title Sheet
M1.1 Pharmacy - Mechanical Demolition
M1.2 Ambulace Garage - Mechanical Demolition
M2.1 Pharmacy - Fire Protection
M2.2 Ambulance Garage - Fire Protection
M3.0 Pharmacy - Underfloor Plumbing
M3.1 Pharmacy - Plumbing
M4.1 Pharmacy - Piping
M4.2 Ambulance Garage - Piping
M5.1 Pharmacy - HVAC
M5.2 Ambulance Garage - HVAC
M6.1 Mechanical Schedules
M7.1 Mechanical Details
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ f=ÜÉêÉÄó=ÅÉêíáÑó=íÜ~í=íÜáë=éä~åI= ëéÉÅáÑáÅ~íáçåI=çê=êÉéçêí=ï~ë= éêÉé~êÉÇ=Äó=ãÉ=çê=ìåÇÉê=ãó= ÇáêÉÅí=ëìéÉêîáëáçå=~åÇ=íÜ~í=f=~ã=~= Çìäó=iáÅÉåëÉÇ=mêçÑÉëëáçå~ä= båÖáåÉÉê=ìåÇÉê=íÜÉ=ä~ïë=çÑ=íÜÉ= pí~íÉ=çÑ=pçìíÜ=a~âçí~K
MECHANICAL DRAWINGS
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
IHS Project # GP19S1079C8
07/22/2022
EDI-DOLEJS #20-072
Woodrow Wilson Keeble Memorial Health Care
Center USP Compliance 100 Lake Traverse Drive
Sisseton, SD 57262
14204
MIKE DOLEJS
AE
MD
020053.00
Woodrow
Wilson
Keeble
Memorial
Health Care
Center USP
Compliance
M0.1
Mechanical
Title Sheet
100 Lake Traverse Drive
Sisseton, SD 57262 êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
01/12/2024
T
T
T
PLAN NOTES
GENERAL NOTES
P
K1 k
J.8
J.7
J.6
J.4
J.3
J
H.7
H.6
H.2
H
18.9 19 20 21 22
CAP
13 8
4 4 4
HP-6
HP-12
5 5
EDC
HP-8
HP-6
EDH-3 7
4 4
9 9
HP-13
HP-5
9 9
EDC
SF-1
FILTER BOX
EDH-1
UP TO OUTDOOR
AIR GOOSENECK
ON ROOF
UP TO EF-14
ON ROOF
11 11
4 4
CAP
CAP
CAP
8 8
HP-6
EDH
EDC
1. DISCONNECT AND REMOVE EXISTING PLUMBING
FIXTURE, VERIFY EXISTING LOCATION. REFER TO SHEET
M3.1 FOR NEW WORK.
2. DISCONNECT AND REMOVE EXISTING PLUMBING
FIXTURE AND HOT AND COLD WATER BACK TO MAINS.
VERIFY EXISTING LOCATIONS, REFER TO SHEET M3.1
FOR NEW WORK.
3. DISCONNECT EXISTING TEMPERATURE SENSOR. REFER
TO SHEET M4.1 FOR NEW WORK.
4. DISCONNECT AND REMOVE EXISTING GRILLE,
REGISTER, DIFFUSER AND FLEX DUCT. ASSOCIATED
DUCTWORK TO REMAIN. REFER TO SHEET M5.1 FOR
NEW WORK. SEAL UNUSED DUCT OPENINGS AT MAINS
AIR TIGHT.
5. DISCONNECT AND REMOVE EXISTING HEAT PUMP AND
ASSOCIATED ELECTRICAL DUCT COIL, DUCTS, GRILLES,
REGISTERS, DIFFUSERS, AND BRANCH PIPING. REFER
TO SHEET M4.1 AND M5.1 FOR NEW WORK.
6. DISCONNECT AND REMOVE EXISTING ELECTRICAL
DUCT COIL, IN-LINE SUPPLY FAN, FILTER BOX AND
ASSOCIATED DUCTWORK. PATCH ROOF OPENING.
7. EXISTING HEAT PUMP, ELECTRIC DUCT COIL AND
ASSOCIATED DUCTWORK AND PIPING TO REMAIN.
8. ELECTRIC BASEBOARD TO REMAIN.
9. DISCONNECT AND REMOVE EXISTING OUTDOOR AIR
DUCTS AND CAP BRANCH CONNECTIONS AT MAIN.
REFER TO SHEET M5.1 FOR NEW WORK.
10. DISCONNECT EXISTING OUTDOOR AIR DUCT.
11. DISCONNECT AND REMOVE EXISTING TRANSFER DUCT.
12. DISCONNECT AND REMOVE EXISTING EXHAUST DUCT
AND ASSOCIATED HANGERS AND SUPPORT BACK TO
MAIN DUCT THRU THE ROOF AND CAP. HOOD WILL BE
REMOVED BY OTHERS. REFER TO SHEET M5.1 FOR
NEW WORK.
13. DISCONNECT AND REMOVE EXISTING BASEBOARD AND
CONTROLS.
14. EXISTING TRANSFER GRILLE AND ASSOCIATED DUCT
TO REMAIN.
15. DISCONNECT AND REMOVE EXHAUST FAN ON THE
ROOF. PROTECT ROOF CURB FOR REUSE. REFER TO
SHEET M5.1 FOR NEW WORK.
16. DISCONNECT AND REMOVE EXISTING CABINET UNIT
HEATER.
17. VERIFY EXISTING HEAT PUMP LOCATION. RELOCATE
EXISTING HEAT PUMP IF PRESENT LOCATION
CONFLICTS WITH NEW INTERIOR PARTITION.
COORDINATE RELOCATION WITH ARCHITECT AND
OWNER.
18. VERIFY EXISTING ELECTRIC DUCT HEATER LOCATION.
RELOCATE EXISTING DUCT HEATER IF PRESENT
LOCATION CONFLICTS WITH NEW INTERIOR PARTITION.
COORDINATE RELOCATION WITH ARCHITECT AND
OWNER.
19. DISCONNECT EXISTING REVERSE OSMOSIS WATER
CONDITIONING EQUIPMENT AND PROTECT FOR
REINSTALLATION. REFER TO SHEET M3.1 FOR NEW
WORK.
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO
COMMENCING WORK. FIELD VERIFY LOCATIONS AND
SIZES OF DUCTWORK, PIPING AND EQUIPMENT TO BE
REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES ( WALLS, FLOORS,
AND/OR CEILINGS) AS REQUIRED TO PERFORM WORK.
PATCHING SHALL MATCH SURROUNDING SURFACES.
D. DISCONNECTED EQUIPMENT SHALL BE REMOVED. NO
EQUIPMENT SHALL BE ABANDONED IN PLACE.
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ f=ÜÉêÉÄó=ÅÉêíáÑó=íÜ~í=íÜáë=éä~åI= ëéÉÅáÑáÅ~íáçåI=çê=êÉéçêí=ï~ë= éêÉé~êÉÇ=Äó=ãÉ=çê=ìåÇÉê=ãó= ÇáêÉÅí=ëìéÉêîáëáçå=~åÇ=íÜ~í=f=~ã=~= Çìäó=iáÅÉåëÉÇ=mêçÑÉëëáçå~ä= båÖáåÉÉê=ìåÇÉê=íÜÉ=ä~ïë=çÑ=íÜÉ= pí~íÉ=çÑ=pçìíÜ=a~âçí~K
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
07/22/2022
EDI-DOLEJS #20-072
14204
MIKE DOLEJS
AE
MD
020053.00
Woodrow
Wilson
Keeble
Memorial
Health Care
Center USP
Compliance
M1.1
Pharmacy -
Mechanical
Demolition
100 Lake Traverse Drive
Sisseton, SD 57262
NORTH
0 4' 8'2' 1/4" = 1'-0"M1.1
1 Pharmacy - Mechanical Demolition êÉîáëáçå=L
GENERAL NOTES
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO
COMMENCING WORK. FIELD VERIFY LOCATIONS AND
SIZES OF DUCTWORK, PIPING AND EQUIPMENT TO BE
REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES ( WALLS, FLOORS,
AND/OR CEILINGS) AS REQUIRED TO PERFORM WORK.
PATCHING SHALL MATCH SURROUNDING SURFACES.
D. DISCONNECTED EQUIPMENT SHALL BE REMOVED. NO
EQUIPMENT SHALL BE ABANDONED IN PLACE.
DISCONNECT AND REMOVE EXISTING
ELECTRIC UNIT HEATER AND ASSOCIATED
CONTROLS, HANGERS AND SUPPORTS IN
ITS ENTIRETY (TYP. OF 4)
DISCONNECT AND REMOVE
EXISTING EXHAUST FAN AND
ASSOCIATED CONTROLS,
DAMPERS, HANGERS AND
SUPPORTS IN ITS ENTIRETY.
PATCH AND SEAL EXISTING ROOF
OPENING MATCHING SUROUNDING
AREAS
DISCONNECT AND REMOVE EXISTING
INTAKE LOUVER AND ASSOCIATED DUCTS,
DAMPER, GRILLES, CONTROLS, HANGERS
AND SUPPORTS IN ITS ENTIRETY. PATCH
EXISTING WALL OPENING MATCHING
SOURROUNDING AREAS
DISCONNECT AND REMOVE
EXISTING THERMOSTAT
ÉåêáÅÜáåÖ ÅçããìåáíáÉë íÜêçìÖÜ ~êÅÜáíÉÅíìêÉ f=ÜÉêÉÄó=ÅÉêíáÑó=íÜ~í=íÜáë=éä~åI= ëéÉÅáÑáÅ~íáçåI=çê=êÉéçêí=ï~ë= éêÉé~êÉÇ=Äó=ãÉ=çê=ìåÇÉê=ãó= ÇáêÉÅí=ëìéÉêîáëáçå=~åÇ=íÜ~í=f=~ã=~= Çìäó=iáÅÉåëÉÇ=mêçÑÉëëáçå~ä= båÖáåÉÉê=ìåÇÉê=íÜÉ=ä~ïë=çÑ=íÜÉ= pí~íÉ=çÑ=pçìíÜ=a~âçí~K
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869
ÇìäìíÜ=G=îáêÖáåá~G=íïáå=ÅáíáÉë ïïïKÇëÖïKÅçã
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
07/22/2022
EDI-DOLEJS #20-072
14204
MIKE DOLEJS
AE
MD
020053.00
Woodrow
Wilson
Keeble
Memorial
Health Care
Center USP
Compliance
M1.2
Ambulace
Garage -
Mechanical
Demolition
100 Lake Traverse Drive
Sisseton, SD 57262
8' 16'4'0 1/4" = 1'-0"M1.2
1 Ambulance Garage - Mechanical Demolition
NORTH
êÉîáëáçå=L
PLAN NOTES
P
K1 k
J.8
J.7
J.6
J.4
J.3
J
H.7
H.6
H.2
H
18.9 19 20 21 22
DISP.
RX108
DISP. DIA.
RX109
HSKP
N11
PHARMACY
RX102
TOILET
N12
TOILET
X08
TOILET
X09
HAZ STOR
RX113
DISP.
RX110
PCC SUP.
P05
WAITING
RX111
OFFICE
RX105
STAFF ENTRY
RX101
CONTROLLED
SUBSTANCES
RX103
DISP.
RX112
OFFICE
RX104
PHARMACY
RX102
ANTI
RX106
1. MODIFY EXISTING FIRE PROTECTION IN THIS AREA.
DISCONNECT AND REMOVE EXISTING FIRE PROTECTION
SPRINKLER HEADS/PIPING/ESCUTCHEONS AS NECESSARY
TO ACCOMMODATE RENOVATION WORK. PROVIDE
ADDITIONAL…