B.01 Attachemnt 2 - Purchase Description - GroE VLA Battery.pdf

PDF 1 MB Posted

Attached to
Big Cliff Battery Bank Replacement Federal contract opportunity
Solicitation number
W9127N23Q0121
Issued by
Department of the Army Corps of Engineers Engineering District Portland

About this file

This purchase description outlines requirements for a stationary vented lead acid battery bank for the Big Cliff Dam project. The battery bank must consist of 58 2V cells with a minimum 338AhC10 capacity. It must meet standards for seismic certification, spill containment, and have a 25-year design life. The purchase includes the battery bank, certified seismic rack, and spill containment system. Delivery is required to the USACE office in Mill City between 6am-5pm Monday through Friday. Invoices should be submitted electronically to the designated USACE Finance Center email, copying additional USACE contacts. The related federal contract opportunity is solicitation number W9127N23Q0121 for the Big Cliff Battery Bank Replacement project managed by the Department of the Army Corps of Engineers Portland District.

View the file

Other files for this federal contract opportunity

Other files attached to Big Cliff Battery Bank Replacement, newest first.
File Type Posted
Attachment 3 Question Answer..pdf PDF
Attachment 4 Existing Battery setup.pdf PDF
B.01 Attachment 1 - Provisions and Clauses.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PURCHASE DESCRIPTION (PD): Stationary GroE (Pure Lead/Plante Positive) Vented Lead Acid (VLA) Battery

FOR: US Army Corps of Engineers, Portland District, Willamette Valley & Rogue River Project (CENWP-ODVR)

DESCRIPTION: The stationary GroE VLA Battery, with certified seismic rack and spill control system, is required as part of Big Cliff Dam’s 125VDC system. The battery, with seismic rack and spill containment system, shall consist of 58 2V cells and conform to the standards of Unified Facilities Criteria (UFC) 3-520-05 (Dated 2020), American National Standards Institute (ANSI) 9540:2023, Institute of Electrical and Electronics Engineers (IEEE) 450-2020, IEEE 484-2019, IEEE 1375, International Electrotechnical Commission (IEC) 60896-11, National Fire Protection Association (NFPA) 1, NFPA 853, German institute for Standardization (DIN) 40738 and their respective references. The battery must have a nominal capacity of at least 338AhC10. Battery design life must be at least 25 years. The battery bank design and protection shall meet or exceed the requirements within the above references, with UFC 3-520-05 superseding all in any case of conflict. The battery bank shall be supplied with all necessary inter-cell connectors and terminal lugs, bolts, and plates necessary for the complete assembly.

Markings shall be provided according to ANSI 9540:2023. The battery cell container shall be transparent, styrene acrylonitrile (SAN) plastic, with flame retardant jar covers.

The below supplies shall come with all standard commercial warranties, instructions, manuals, guides, literature, product sheets, procedure guides, etc.

SUPPLIES:

Line Item Quantity 0001 Stationary 58-cell 2V GroE VLA

Battery with a nominal capacity of at least 338AhC10

0002 Certified Seismic Battery Rack 1 0003 Spill Containment System 1

DELIVERY INFORMATION:

Mon-Fri (6:00am-5:00pm) Ship to:

US Army Corps of Engineers (USACE) Attn: Ceyel Clark Detroit Dam 40990 Hwy 22, Mill City, OR 97360

Point of Contact: Ceyel Clark, Ceyel.P.Clark@usace.army.mil, 541-294-3549 Please also cc: Steve Gardner, Steven.R.Gardner@usace.army.mil, (503) 897-4453

INVOICE SUBMITTAL:

Upon satisfactory completion of delivery, please submit an electronic PDF invoice to USACE Millington (the USACE Finance Center) via email address:

cefc-g2invoices@usace.army.mil

Attachment 2: Purchase Description

Please cc: Quenton Chocktoot, Quenton.P.Chocktoot@usace.army.mil & Ceyel Clark, Ceyel.P.Clark@usace.army.mil

CONTRACT ADMINISTRATION:

Contract will be administered by:

US Army Corps of Engineers (USACE), Portland District Attn: Contracting Division PO Box 2946 Portland, Oregon 97208-2946\

POC: Nathean Stoner, Nathean.W.Stoner@usace.army.mil & Carl Schmurr, Carl.R.Schmurr@usace.army.mil

Attachment 2: Purchase Description

File details come from the government source that posted it. Updated .