B-23199 Q and A - Container bid amendment.docx

DOCX document 14 KB Posted

Attached to
40' Climate Controlled Container
Solicitation number
21-506ALPLM-ALPLM-B-23199
Issued by
Illinois

About this file

This document is a bid amendment for contract B-23199, which is for the purchase of a 40' climate controlled container for the storage of microfilm by the Abraham Lincoln Presidential Library and Museum (ALPLM) in Illinois. The amendment clarifies the product requirements, specifying that a reefer container is not needed, the minimum interior width must be 7 feet, and the insulation must have a minimum R-value of 14 to maintain a temperature of 60-65 degrees and 50% relative humidity. The amendment also states that there are no specific requirements for the interior finish or the inclusion of uni-strut channel.

The related state and local contract opportunity is for the purchase of a 40' climate controlled container and optional trailer for microfilm storage. The contract is being issued by the state of Illinois. The document does not provide details on pricing, set asides, incumbents, funding, or other salient information.

View the file

Other files

File Type Posted
Standard Certifications V.18.1~94.doc DOC document
Standard Terms and Conditions~88.pdf PDF
Storage Unit specs.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bid Amendment B-23199 40’ Climate Controlled Container ALPLM Answers to Questions Received

Purpose of container:

· Temporary storage of microfilm. We do not want a reefer container.

Interior Dimensions:

· Disregard requested interior dimensions as these will vary based upon insulation. Minimum interior width must be at least 7 feet.

Studding: 2” x 2” Tube Steel, 2 ½” Steel Studs, Wooden Studs?

· Wooden studs are not acceptable Insulation: Fiberglass, Closed Cell Spray Foam, Foam Board?

· Must have minimum value of R-14, must be able to maintain temperature of 60-65 degrees and a Relative Humidity of 50% Interior Finish: OSB/FRP? Thickness?

· No requirements on interior finish, minimum interior width of 7’ must be maintained The rendering shows three horizontal rows of 7/8” closed Uni-strut along the wall and 1 5/8” Uni-strut on the ceiling. Is this to be included in the quote?

· ALPLM does not have any specific requirements for uni-struts as long as the requirements for lighting, electrical and HVAC are met.

Painting: Do you require any exterior paint? Is there a color preference?

· Not required