AU UH Animation Lab_Dwgs_approved (sm).pdf

PDF 2 MB Posted

Attached to
AU ANIMATION LAB
Solicitation number
PE-51200-RFQ-2027-000000041
Issued by
Richmond County, Georgia

About this file

AU UH Animation Lab Project Summary

This document set comprises 100% Construction Document (CD) drawings and specifications for the AU-SC UH Animation Lab project at Augusta University's Summerville Campus, located at 2500 Walton Way, Augusta, Georgia 30904. The project involves the conversion of existing classroom space (Room 249) totaling 956 square feet into an animation laboratory within University Hall. The scope of work encompasses architectural finishes, mechanical, electrical, plumbing, and fire protection modifications to accommodate the new laboratory design. The project is classified as Business Occupancy (Type B) with a calculated occupant load of 7 persons and is designed as a Type IB, fully sprinklered building. Key specifications include the installation of new gypsum drywall partitions (PT-1A1 and PT-2 types), acoustical ceiling tiles and grid, updated HVAC terminal units with digital controls, fire suppression system rework, and comprehensive electrical modifications including new lighting fixtures, data/voice outlets, fire alarm components, and access control systems. Construction documents are dated April 10, 2026, with final approval from the State Fire Marshal dated May 7, 2024.

The project requires compliance with the 2024 International Building Code, 2024 International Fire Code, 2023 National Electrical Code, 2024 NFPA 101 Life Safety Code, NFPA 13 Sprinkler Standards, and Georgia State Fire Marshal requirements as of February 19, 2026. The contractor must maintain negative static pressure throughout demolition and construction activities in the laboratory space, with ICRA air calculation requirements specifying 1,530 to 1,721 CFM depending on ceiling configuration, or alternatively provision of HEPA air scrubbers. Fire protection specifications require white concealed quick-response extended coverage sprinklers rated for intermediate temperature activation. HVAC work includes installation of VAV terminal units (Trane VCWF-08 models) with hydronic heating coils and electronic controls integrated with the existing Johnson Controls Metasys system. Testing, adjusting, and balancing must be performed by AABC or NEBB certified contractors, with all data and communications wiring requiring Enhanced Category 6E certification testing per TIA/EIA 568-C.2-1 standards. The contractor shall obtain all necessary permits and inspections, provide as-built drawings, and furnish three sets of maintenance and operating instructions prior to final project acceptance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION:

UNIVERSITY HALL

PLAN NORTH

AREA OF WORK:

956 SF

O

T R

I

EG

S

STA

TE

H

DE AR RE C

CT

ETI

A O

ROBERT L. MAULDIN

GF E

I

RG

oI NC EAT .I

RE

T C

F

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

PR

IN

TE

D

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

04/10/2026

4/

/2

9:

:0

A M

Z

A ct iv e_

Pr oj ec ts

\2

Pr oj ec ts \2

5-

A U

-S C \2

5-

.0

A U

-S C U

H A ni m at io n La b\ D

R A W

IN

G

S \0

0% C

D s\

-1

1.

0% .r vt

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026

G0.1DA

25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

INDEX

100% CD

INDEX OF DRAWINGS

X WINDOW TYPE

INTERIOR

EXTERIOR

ELEVATION SYMBOL

ELEVATION SYMBOL

SECTION SYMBOL

T.O. SLAB

DOOR NUMBER

ROOM NAME

ROOM NUMBER

DETAIL NUMBER

DETAIL NUMBER

CROSS REFERENCE SHT #

DETAIL NUMBER

CROSS REFERENCE SHT #

DETAIL NUMBER

STORAGE

2104A

CROSS REFERENCE SHT #

CROSS REFERENCE SHT #

DETAIL

SYMBOL

A1.1

DRAWING TITLE

A1.1

SCALE:

A1.1

A1.1

A1.1

0'-0"

ELEVATION MARK

ELEVATION HEIGHT

GENERAL LEGEND

AU-SC UH ANIMATION LAB.

AUGUSTA UNIVERSITY

2500 WALTON WAY, AUGUSTA, GA 30904

SITE PLAN

INDEX

G0.1 INDEX

G0.2 EGRESS PLAN AND CODE ANALYSIS

ARCHITECTURAL

A0.1 DEMOLITION AND CONSTRUCTION SAFEGUARDING

PLAN

A1.1 FLOOR PLAN AND ELEVATIONS

A1.2 REFLECTED CEILING PLAN

A1.3 EQUIPMENT AND FURNITURE PLAN

FIRE PROTECTION

FP1.1 FIRE PROTECTION

MECHANICAL

M0.1 HVAC PLANS

M1.1 HVAC SCHEDULES, FMS SUMMARY, DETAILS,

NOTES AND LEGEND

M2.1 HVAC SPECIFICATIONS

ELECTRICAL

E1.0 LEGEND, NOTES, DETAILS, SCHEDULE AND SPECS

E1.1 ELECTRICAL SPECIFICATIONS

E2.1 ELECTRICAL DEMOLITION AND LIGHTING PLAN

E3.1 ELECTRICAL POWER PLAN

E4.1 MECHANICAL POWER AND SYSTEMS PLAN

E5.1 ELECTRICAL DETAILS

A AMPERAGE

ACM ASBESTOS CONTAINING MATERIAL

A/C AIR CONDITIONER

A.F.F. ABOVE FINISH FLOOR

ALT. ALTERNATE

AL. ALUMINUM

@ AT

ATC ACOUSTICAL TILE CEILING

AWG. AVERAGE WIRE GAUGE

BD. BOARD

BOT, B/ BOTTOM

BRG. BEARING

BTUH BRITISH THERMAL UNIT/ HOUR

B.W. BOTH WAYS

CARP. CARPET

CFM CUBIC FEET PER MINUTE

CJ. CONSTRUCTION JOINT

CENTER LINE

CL CLEARANCE

CONT. CONTINUOUS

C.T. CERAMIC TILE

DIA. DIAMETER

DN DOWN

DTL. DETAIL

E.C. ELECTRICAL CONDUIT

EF. EXHAUST FAN

EPT. ENAMEL PAINT

E.W. EACH WAY

E.S. EACH SIDE

EWC ELECTRICAL WATER COOLER

EXP. EXPANSION

EXT. EXTERIOR

F.D. FLOOR DRAIN

F.E. FIRE EXTINGUISHER

FEC. FIRE EXTINGUISHER CABINET

F.F.L. FINISH FLOOR LEVEL

ABBREVIATIONS

FIN. FINISH

FLR. FLOOR

FT. FOOT

F.V. FIELD VERIFY

G. GROUND

GA. GAUGE

G.C. GENERAL CONTRACTOR

GPDW GYPSUM DRYWALL

GPM GALLONS PER MINUTE

H/C HANDICAP

H.M. HOLLOW METAL

H.P. HORSE POWER

HVAC HEAT'G, VENT'G & AIR COND.

I.D. INSIDE DIAMETER

INSUL. INSULATION

INT. INTERIOR

IN.W.C. INCHES OF WATER COLUMN

JT. JOINT

LGMF LIGHT GAUGE METAL FRAMING

MDF MEDIUM DENSITY FIBER BOARD

M.O. MASONRY OPENING

M/R MOISTURE RESISTANT

MTL METAL

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

N.I.C. NOT IN CONTRACT

O.A. OUTSIDE AIR

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

O.H. OVERHEAD

P POLE

PB PARTICLE BOARD

PCPL PORTLAND CEMENT PLASTER

PL. PLATE

PLAM PLASTIC LAMINATE

PLYWD. PLYWOOD

P.T. PRESSURE TREATED

PVC. POLYVINYL CHLORIDE

Q.T. QUARRY TILE

R. RADIUS

R.C.P. REINFORCED CONCRETE PIPE

R.D. ROOF DRAIN

RDL. ROOF DRAIN LINE

REF. REFERENCE

REINF. REINFORCING

RPM. REVOLUTIONS PER MINUTE

SAT. SUSPENDED ACOUSTICAL TILE

S.C. SOLID CORE

S.H. SPRINKLER HEAD

SHT. SHEET

SIM. SIMILAR

S.P. STATIC PRESSURE

S.S. STAINLESS STEEL

STD. STANDARD

STL. STEEL

STR. STRUCTURAL

TEMP. TEMPERED

T/ TOP

T/F TOP OF FOOTING

THOLD. THRESHOLD

T/J TOP OF JOIST

TRANSL. TRANSLUCENT

TYP. TYPICAL

U.N.O. UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILE

W/ WITH

W/O WITHOUT

WD. WOOD

WM WATER METER

W/P WATERPROOF

WV WATER VALVE

W.W.F. WELDED WIRE FABRIC

CL

PLAN NORTH

1. CONTRACTOR SHALL VISIT THE PROJECT SITE

PRIOR TO BIDDING TO REVIEW EXISTING

CONDITIONS. BID SHALL REFLECT ALL COSTS

AFFECTING THE SCOPE OF WORK AND

EXISTING CONDITIONS.

2. DO NOT SCALE DRAWINGS TO LOCATE WALLS,

DOORS, CEILING GRID, EQUIPMENT, ETC.

GENERAL NOTE

25154

ELECTRICAL DESIGN

C O N S U L T A N T S

AUGUSTA OFFICE -

ELECTRICAL ENGINEERS

PROJECT #:

edc1973.com

MECHANICAL: MARTIN FORD, P.E.

J. BRIAN MESSER, P.E.

PLUMBING: JOE POWELL, P.E.

PFA ENGINEERING, INC.

1201 BROAD STREET, SUITE 3A, AUGUSTA, GA 30901

PHONE: (706) 722-3959 FAX: (706) 724-5127

www.pfaengineering.com

#25-117-UHAU PROJECT NUMBER

- SUMMERVILLE CAMPUS

KM

ARCHITECTS, INC.

ARCHITECT:

2KM ARCHITECTS, INC.

529 GREENE ST.

PH. 706.736.3333

FX. 706.736.7100

EMAIL: mail@2kmarchitects.com

ROBERT L. MAULDIN NCARB, AIA

REVISIONS

# DATE DESCRIPTION

APPROVED

STATE FIRE MARSHAL

SUBJECT TO FINAL FIELD INSPECTION

Final approval subject to noted comments and field inspection based on NFPA Standards and

Georgia Accessibility Code.

05/07/2024

BY:

DATE:

Mi-Jung Kim

May 14, 2026

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

ON THE CONSTRUCTION SITE AT ALL TIMES.

VIOLATORS SUBJECT TO CIVIL PENALTIES.

THIS OFFICE SHALL BE NOTIFIED IN WRITING

AT LEAST 21 DAYS PRIOR TO 80% AND 100%

COMPLETION FOR INSPECTIONS

FIRE STOPPING REQUIREMENT

Penetrations thru rated walls and floors shall be sealed with a material capable of preventing the passage of flames and hot gasses when subjected to the requirements of the Test Standard specific for Fire Stops ASTM-E-814.

SPRINKLER CONTRACTOR SHALL HAVE

CERTIFICATE OF COMPETENCY FROM

GEORGIA FIRE MARSHAL'S OFFICE.

SPRINKLER SHOP DRAWINGS SHALL

BE SUBMITTED TO GEORGIA FIRE

MARSHAL'S OFFICE FOR REVIEW

AND APPROVAL PRIOR TO INSTALLATION.

SUBJECT TO CIVIL PENALTIES.

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

ON THE CONSTRUCTION SITE AT ALL TIMES.

VIOLATORS SUBJECT TO CIVIL PENALTIES.

ELEV NO. 1

LEGEND:

EXISTING WALL / PARTITION

F.E.C. EXISTING FIRE

EXTINGUISHER CABINET

EXISTING 2-HR FIRE / SMOKE BARRIER

AREA OF WORK

EGRESS ROUTE

NEW WALL / PARTITION

PLAN NORTH

AREA OF WORK:

956 SF

CLASSROOM

CORRIDOR

STAIR#2

STAIR#1

MAX DIST.136'-9"

NETWORK

ELECTRICAL

STAIR#3

STAIR#4

F.

E.

C

F.E.C.F.E.C.

E.

F.

C

O

T R

I

EG

S

STA

TE

H

DE AR RE C

CT

ETI

A O

ROBERT L. MAULDIN

GF E

I

RG

oI NC EAT .I

RE

T C

F

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

PR

IN

TE

D

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

04/10/2026

4/

/2

:5 0:

A

M Z

A ct iv e_

Pr oj ec ts

\2

Pr oj ec ts \2

5-

A U

-S C \2

5-

.0

A U

-S C U

H A ni m at io n La b\ D

R A W

IN

G

S \0

0% C

D s

(C

LO

S

ED

-1 1.

0%

.r vt

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026

G0.2DA

25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

EGRESS PLAN AND

CODE ANALYSIS

100% CD

PLAN NORTH

OCCUPANCY LOAD FACTOR

OCCUPANCY

SF/ PERSON - GA (NFPA 101 2024)

ABBREV. TYPE

B BUSINESS 150

OCCUPANCY LOAD (BY AREA)

ROOM NO. NAME OCCUPANCY OCCUPANCY TYPE AREA OCCUPANCY LOAD NUMBER

(GA) CALCULATED OCCUPANCY (GA)

249 ANIMATION

LAB. B BUSINESS 956 SF 150 7

A. PROJECT SCOPE SUMMARY:

1. THE PURPOSE OF THIS PROJECT IS TO CONVERT EXISTING CLASSROOM SPACE INTO AN ANIMATION LAB.

2. SCOPE OF WORK INCLUDES ARCHITECTURAL FINISHES, CHANGES TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION TO ACCOMMODATE NEW DESIGN.

3. MEANS OF EGRESS ARE NOT AFFECTED BY THIS PROJECT.

B. GROSS RENOVATION AREA:

1. AREA AFFECTED

C. OCCUPANCY (NFPA 101-2024)

1. CLASSIFICATION (6.1.5)

2. OCCUPANT LOAD (AFFECTED AREA)

(TABLE 7.3.1.2)

D. BUILDING CONSTRUCTION (IBC 2024)

1. NUMBER OF FLOORS

2. TYPE OF CONSTRUCTION

E. MEANS OF EGRESS (NFPA 101-2024)

1. CLEAR CORRIDOR WIDTH (38.2.3.4) = 44"

2. DOORS IN THE MEANS OF EGRESS (38.2.2.2)

3. DEAD END CORRIDOR LIMIT (38.2.5.2.1) = 50'

4. TRAVEL DISTANCE TO EXITS (38.2.6.3)

(300'-0" MAX, FULLY SPRINKLERED)

F. SPRINKLERS (NFPA 101-2024)

G. DETECTION, ALARM, AND COMMUNICATIONS

SYSTEMS (NFPA 101-2024)

H. PORTABLE FIRE EXTINGUISHERS (NFPA 101-2024)

J. HAZARD OF CONTENTS (NFPA 101-2024)

K. INTERIOR FINISH (NFPA 101- 2024) (TBL A10.2.2)

1. EXITS - CLASS A OR B

2. ACCESS TO EXITS - CLASS A OR B

3. OTHER SPACES - CLASS A OR B

4. FLOOR FINISH - CLASS I OR II

B.1. 956 S.F.

C.1. EXISTING BUSINESS

C.2. BY USE = 21 OCCUPANTS

BY AREA = 7 OCCUPANTS

D.1. THREE (EXISTING)

D.2. TYPE IB, FULLY SPRINKLERED

E.1. COMPLIANT (EXISTING)

E.2. COMPLIANT

E.3. NONE CREATED

E.4. 136'-9" FROM MOST REMOTE POINT IN

A ROOM TO AN EXIT

F1. FULLY SPRINKLERED FACILITY

G.1. EXISTING

H.1. PROVIDED

J.1. EXISTING BUSINESS /

ORDINARY HAZARD (6.2.2.3)

K.1. NOT AFFECTED

K.2. PROVIDED

K.3. PROVIDED

K.4. PROVIDED

CODE ANALYSIS

APPLICABLE CODE W/ GEORGIA AMENDMENTS

SPECIAL NOTES:

1. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS, OR ANY OTHER WALLS REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS, SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING IN CONCEALED SPACES. LETTERING TO BE 3" IN HEIGHT (MIN.); 3/8" IN WIDTH/ STROKE (MIN.); IN CONTRASTING COLOR; WITHIN 15 FEET OF THE END OF EACH WALL; AND AT INTERVALS NOT EXCEEDING 30 FEET (HORIZONTAL). WORDING TO IDENTIFY THE APPROPRIATE RATING (I.E. "1-HR FIRE", "1-HR FIRE/SMOKE", ETC.) FOLLOWED BY "PROTECT ALL OPENINGS". THE

ABOVE IS AN OVERVIEW. SEE CURRENT IBC, SECTION 703.7 FOR FULL DESCRIPTION.

SCALE: 1/16"= 1'-0"

32'8'0 16'

120-3-3 STATE MINIMUM FIRE SAFETY STANDARDS (EFFECTIVE 02/19/2026)

120-3-20 2015 RULES AND REGULATION OF THE STATE OF GEORGIA - ACCESS TO AND USE OF PUBLIC FACILITIES BY

HANDICAPPED PERSONS

ADA 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

IBC 2024 INTERNATIONAL BUILDING CODE (W/ GA AMENDMENTS 2026)

IFC 2024 INTERNATIONAL FIRE CODE

IMC 2024 INTERNATIONAL MECHANICAL CODE (W/ GA AMENDMENTS 2026)

IFGC 2024 INTERNATIONAL FUEL GAS CODE (W/ GA AMENDMENTS 2026)

IEBC 2018 INTERNATIONAL EXISTING BUILDING CODE (W/ GA AMENDMENTS 2021)

IECC 2015 INTERNATIONAL ENERGY CONSERVATION CODE (W/ GA AMENDMENTS 2020, 2022, 2023)

NFPA 10 2022 STANDARD FOR PORTABLE FIRE EXTINGUISHERS (PER 120-3-3)

NFPA 13 2022 STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS (PER 120-3-3)

NFPA 25 2023 STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS

(PER 120-3-3)

NFPA 70 2023 NATIONAL ELECTRICAL CODE (NEC) (W/ GA AMENDMENTS 2026)

NFPA 72 2022 NATIONAL FIRE ALARM CODE(PER 120-3-3)

NFPA 90A 2024 STANDARD FOR THE INSTALLATION OF AIR CONDITIONING & VENTILATING SYSTEMS (PER 120-3-3)

NFPA 101 2024 LIFE SAFETY CODE (PER 120-3-3)

NFPA 241 2022 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, & DEMOLITION OPERATIONS (PER 120-3-3)

O.C.G.A. 50-8-18 ENERGY EFFICIENCY AND SUSTAINABLE CONSTRUCTION ACT 2008

SCALE: 1/16" = 1'-0"

2 EGRESS PLAN AND CODE ANALYSIS - LEVEL 2

REVISIONS

# DATE DESCRIPTION

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

EXISTING CONSTRUCTION

KEY:

TO BE DEMOLISHED

FIRE RETARDANT BARRIER

PLAN NORTH

AREA OF WORK:

956 SF

CONTRACTOR SHALL EITHER:

A. EXHAUST AIR DIRECTLY TO OUTDOORS TO MAINTAIN A NEGATIVE 0.01 INCH W.C. PRESSURE DIFFERENTIAL

B. PROVIDE A COMBINATION OF EXHAUST AND HEPA FILTER AIR SCRUBBERS

7,648 CUBIC FEET (W/ CEILING)

9'-0" AVG HEIGHT (W/O CEILING)

956 SQUARE FOOTAGE

8'-0" AVG HEIGHT (W/ CEILING)

8,664 CUBIC FEET (W/O CEILING)

ICRA AIR CALCULATION

AIR EXCHANGE REQUIREMENTS

12 REQUIRED AIR CHANGES

0.01 PRESSURE DIFFERENTIAL IN W.C.

1,721 CFM REQUIRED (W/O CEILING)

1,530 CFM REQUIRED (W/ CEILING)

HEPA AIR SCRUBBER REQUIREMENTS

2500 AIR SCRUBBER CFM

1 REQUIRED AIR SCRUBBERS (W/O CEILING)

1 REQUIRED AIR SCRUBBER (W/ CEILING)

2.9500 2.9610

2.2300 2.2600

ANIMATION

LAB.

2.9100

O

T R

I

EG

S

STA

TE

H

DE AR RE C

CT

ETI

A O

ROBERT L. MAULDIN

GF E

I

RG

oI NC EAT .I

RE

T C

F

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

PR

IN

TE

D

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

04/10/2026

4/

/2

9:

:0

A M

Z

A ct iv e_

Pr oj ec ts

\2

Pr oj ec ts \2

5-

A U

-S C \2

5-

.0

A U

-S C U

H A ni m at io n La b\ D

R A W

IN

G

S \0

0% C

D s\

-1

1.

0% .r vt

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026

A0.1TR/DA

25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

DEMOLITION AND

CONSTRUCTION

SAFEGUARDING

PLAN

100% CD

1. CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ALL MATERIALS WHICH ARE NOT SPECIFICALLY NOTED

TO BE EITHER RE-USED OR TURNED OVER TO THE OWNER.

2. SEE MECHANICAL, FIRE PROTECTION AND ELECTRICAL DRAWINGS FOR ADDITIONAL NOTES.

3. ALL SLAB PENETRATIONS TO EITHER BE FILLED SOLID WITH CONCRETE, OR IF RE-USED, SEALED WITH A

FIRE SEALANT SYSTEM PER SPECIFICATIONS.

4. SEE A1.1 FOR FUTURE LOCATIONS OF DOORS, FRAMES, PARTITIONS, OPENINGS, ETC. VERIFY ALL FUTURE

WORK PRIOR TO DEMOLITION ACTIVITIES.

5. CONTRACTOR TO FOLLOW ALL OSHA SAFETY STANDARDS FOR REMOVAL AND DISPOSAL OF MATERIALS.

6. DO NOT SCALE DRAWINGS TO LOCATE WALLS, DOORS, CEILING GRID, EQUIPMENT, ETC.

GENERAL NOTES

DEMOLITION NOTES

DIVISION 9 - FINISHES DEMO

2.9100 REMOVE SHEET ROCK AND INSULATION WITHIN ROOM AND DISPOSE.

2.9500 REMOVE EXISTING 2' X 2' ACOUSTICAL CEILING TILE AND GRID AND

DISPOSE.

2.9610 REMOVE EXISTING FLOORING AND BASE AND DISPOSE. PREP FOR NEW

FLOORING.

DIVISION 23 - HVAC DEMO

2.2300 SEE MECHANICAL DRAWINGS FOR DEMOLITION WORK.

DIVISION 26 - ELECTRICAL DEMO

2.2600 SEE ELECTRICAL DRAWINGS FOR DEMOLITION WORK.

XX.XXXX

1. FIRE-RETARDANT DUST BARRIER TO BE TRI-SYNERGY FLEXIBLE FILM DURA SKRIM 2 FR SURFACE COVER (1-800-446-6076) OR APPROVED EQUAL, WHERE APPROPRIATE. CONFIRM WITH OWNER FOR LOCATIONS OF

GPDW BARRIERS FOR PROJECT.

2. FIRE RETARDANT DUST BARRIER TO BE MOUNTED ON ZIP WALL EXPANDABLE POLES (1-800-446-6076) OR

APPROVED EQUAL OF LGMF.

3. FIRE RETARDANT DUST BARRIER TO BE SEALED/ TAPED CONTINUOUSLY FROM FLOOR TO CEILING. IF CEILING TILE IS REMOVED, SEAL/TAPE TO DECK. TAPE TO BE POLIKEN #225 (1-800-446-6076) OR APPROVED EQUAL.

4. CONTRACTOR TO USE TRI-SYNERGY STICKY MATS (1-800-446-6076) OR APPROVED EQUAL FOR DUST CONTROL AT A MINIMUM. CONTRACTOR SHALL CREATE AN ANTE-ROOM BETWEEN THE CONSTRUCTION AREA AND THE ADJACENT OPERATIONAL AREA. STICKY MATS, OR APPROVED EQUAL, SHALL BE LOCATED AND CLEANED DAILY;

CARPET MAY BE SUBSTITUTED ON THE CONSTRUCTION AREA SIDE. THERE WILL BE NO EXCEPTIONS WITHIN THE

ANTE-ROOM.

5. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN CONSTRUCTION SAFEGUARDS AT ALL TIMES. THE OWNER MAY STOP THE WORK AT ANY TIME IF SAFEGUARDS ARE NOT MAINTAINED. THIS WILL BE AT NO COST TO

THE OWNER.

6. ALL CONSTRUCTION MUST FOLLOW THE OWNER'S ESTABLISHED INTERIM LIFE SAFETY POLICIES.

7. THE AREA OF WORK MUST MAINTAIN NEGATIVE STATIC PRESSURE AND MUST BE MAINTAINED DURING ALL

DEMOLITION/CONSTRUCTION ACTIVITIES.

8. ALL DUCT WORK AND PIPING ENTERING THE BUILDING MUST BE CLEANED INSIDE AND OUT PRIOR TO ENTERING THE BUILDING. ANY DUCT OR PIPING STORED IN AN EXPOSED LOCATION MUST HAVE ENDS CAPPED.

9. CAP ALL DUCTS THAT ARE OPENED IN DEMO WITH PLASTIC AND DUCT TAPE TO PREVENT TRANSFER TO OTHER

AREAS.

10. UNPROTECTED OPENINGS TO THE OUTSIDE ARE STRICTLY FORBIDDEN.

11. CONTRACTOR TO PROPOSE BARRIER LOCATIONS FOR OWNER APPROVAL. SOME BARRIERS HAVE BEEN

SUGGESTED FOR CLARITY.

CONSTRUCTION SAFEGUARDING GENERAL NOTES:

SCALE: 1/4" = 1'-0"

01 DEMOLITION AND CONSTRUCTION SAFEGUARDING PLAN

SCALE: 1/4"= 1'-0"

8'0 4'1'

PLAN NORTH

SPECIAL NOTES:

A. CONTRACTOR TO CONFIRM DURATION OF TEMPORARY BARRIERS.

B. ADJACENT DEPARTMENTS WILL REMAIN OPERATIONAL DURING DEMOLITION/CONSTRUCTION ACTIVITIES.

CONTRACTOR SHALL CLEAN ALL DEBRIS AND DUST FROM CORRIDORS AT THE END OF WORKING HOURS.

REVISIONS

# DATE DESCRIPTION

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

1. SEE MECHANICAL, FIRE PROTECTION, AND ELECTRICAL DRAWINGS FOR ADDITIONAL NOTES.

2. DOORS TO BE +/- 6" FROM ADJACENT WALL UNLESS NOTED OTHERWISE.

3. DO NOT SCALE DRAWINGS TO LOCATE WALLS, DOORS, CEILING GRID, EQUIPMENT, ETC.

EXISTING CONSTRUCTION

KEY:

NEW CONSTRUCTION

SCALE: 1/8"= 1'-0"

16'4'0 8'

PT-1A1 - 3 5/8" PARTITION.

- GPDW ONE SIDE ONLY.

- SOUND ATTENUATED GPDW.

- EXTEND NEW CONSTRUCTION TO

DECK OR COMPLETELY FILL.

EXISTING OPENING.

- EXTEND ACOUSTICAL INSULATION TO

4" ABOVE HIGHEST CEILING.

- SEAL BOTTOM WITH NON-HARDENING,

PERMANENT, RESILIENT ACOUSTICAL

SEALANT.

SEE

PLAN

SEE

PLAN

PT-2

NEW GPDW

NEW

INSULATION

EXISTING

LGMF

EXISTING

GPDW

NEW 31/2"

INSULATION

5/8" GPDW

3 5/8" LGMF, 20 GA.

- EXISTING WALL.

- GPDW ONE SIDE ONLY.

- SOUND ATTENUATED GPDW.

- EXTEND NEW CONSTRUCTION TO

DECK OR COMPLETELY FILL

EXISTING OPENING.

- EXTEND ACOUSTICAL INSULATION TO

4" ABOVE HIGHEST CEILING.

- SEAL BOTTOM WITH NON-HARDENING,

PERMANENT, RESILIENT ACOUSTICAL

SEALANT.

PLAN NORTH

AREA OF WORK:

956 SF

8.720

9.510

9.512 9.910

23.000

ANIMATION

LAB.

A1.1

A1.1

A1.1

A1.1

26.0009.514

PT-1A1PT-2

PT-2 PT-2

PT-2

PT-2

249 249A

28.150

PT-2

SN1

SN2

28.150

8.720

F.V.

26'-6"

F.V.

23'-3"

249 249A

F.V.

16'-3"

F.V.

15'-5"

26'-6" (F.V.)

DISPLAY DISPLAYGLASS

BOARD

CLEQ. EQ.

4" 4"

O

T R

I

EG

S

STA

TE

H

DE AR RE C

CT

ETI

A O

ROBERT L. MAULDIN

GF E

I

RG

oI NC EAT .I

RE

T C

F

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

PR

IN

TE

D

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

04/10/2026

4/

/2

9:

:0

A M

Z

A ct iv e_

Pr oj ec ts

\2

Pr oj ec ts \2

5-

A U

-S C \2

5-

.0

A U

-S C U

H A ni m at io n La b\ D

R A W

IN

G

S \0

0% C

D s\

-1

1.

0% .r vt

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026

A1.1TR/DA

25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

FLOOR PLAN AND

ELEVATIONS

100% CD

FINISH NOTES

SPECIAL NOTES (SN#)

GENERAL NOTES

PLAN NORTH

FINISH SCHEDULE

R

EV

IS

IO

N

ROOM NO. SPACE

FL

O

O R

B A

S E

W A

LL

S

C

EI

LI

N

G

CLG.

HT. NOTES

249 ANIMATION LAB. 1 A 1 A * * MATCH EXISTING

FLOORING WALLS

1 1 PAINT GPDW (EGGSHELL)

BASE CEILINGS

A 4" RUBBER 2'X2' ATC "A"- HIGH NRC

MATERIAL SCHEDULE

A

FNA. PROVIDE ADA COMPLIANT TRANSITION STRIP AT INTERSECTION OF DISSIMILAR FLOORING.

FNB. ALL CEILING HEIGHTS TO MATCH EXISTING UNLESS NOTED OTHERWISE.

FNC. PAINT WALL AFFECTED BY MINOR PATCHING TO MATCH EXISTING WHERE NOTED. PAINT TO NEAREST INSIDE

OR OUTSIDE CORNER.

SN1 PATCH, REPAIR, AND LEVEL CONCRETE SUBFLOOR.

SN2 ALL FINISHES TO BE SELECTED BY OWNER (PDC)

PARTITION NOTES

1. ALL DIMENSIONS SHOWN FROM FACE OF FRAMING.

2. AT PARTITIONS WHICH DO NO EXTEND TO STRUCTURE, PROVIDE METAL STUD KICKERS, STAGGERED IN

ALTERNATING DIRECTIONS, AT 48" O.C. KICKERS ALSO REQUIRED AT EACH DOOR JAMB.

3. SEAL SOUND ATTENUATED PARTITIONS AT INTERSECTIONS WITH OTHER NEW MATERIALS (FLOORS, DECKS, PARTITIONS, PIPES, CONDUITS, ETC. THIS IS TO INCLUDE AT TOP AND SIDES. SEE SPECIFICATIONS FOR

SEALANTS INCLUDING THOSE FOR BOTH FIRE-RATED AND ACOUSTICAL ASSEMBLIES.

4. PROVIDE SLIP TRACKS AT HEAD OF PARTITIONS WHICH EXTEND TO UNDERSIDE OF ROOF DECK.

5. GPDW PARTITIONS TO RECEIVE LEVEL 4 FINISH WITH USG FIRST COAT PRIMER.

CONSTRUCTION NOTES

DIVISION 8 - OPENINGS

8.720 CLEAN EXISTING DOOR AND FRAME SURFACES. PRIME AND PAINT FRAME.

DIVISION 9 - FINISHES

9.510 INSTALL NEW FLOORING AND WALL BASE AS SCHEDULED.

9.512 INSTALL NEW 2' X2' ATC AND GRID AS SCHEDULED.

9.514 INSTALL SOUND-ATTENUATING GPDW AND INSULATION. PENETRATIONS AND ELECTRICAL DEVICES

TO BE SEALED. INSTALL SOUND SEALANT AT JOINTS.

9.910 PREP, PRIME, AND PAINT ALL GPDW WALLS.

DIVISION 23 - HVAC

23.000 SEE MECHANICAL DRAWINGS FOR ADDITIONAL WORK.

DIVISION 26 - ELECTRICAL

26.000 SEE ELECTRICAL DRAWINGS FOR ADDITIONAL WORK.

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28.150 INSTALL NEW CARD READER TO EXISTING DOOR.

XX.XXX

PARTITION TYPES

SCALE: 1/4" = 1'-0"

1 FLOOR PLAN

CARPET TILES

DOOR SCHEDULE

R

EV

IS

IO

N

DOOR NO.

DOOR GLASS FRAME FRAME DETAILS

LABEL SET REMARKS

WIDTH HEIGHT THICK TYPE FINISH SIZE G. TYPE F. TYPE MATERIAL HEAD JAMB SILL

249 3'-0" 7'-0" 1 3/4" EXIST - - - - - - - - - 1 CLOSER, ACCESS CONTROLS

249A 3'-0" 7'-0" 1 3/4" EXIST - - - - - - - - - 1 CLOSER, ACCESS CONTROLS

SCALE: 1/4" = 1'-0"A1.1

2 ELEVATION LOOKING EAST

SCALE: 1/4" = 1'-0"A1.1

3 ELEVATION LOOKING NORTH

SCALE: 1/4" = 1'-0"A1.1

4 ELEVATION LOOKING SOUTH

SCALE: 1/4" = 1'-0"A1.1

5 ELEVATION LOOKING WEST

ACOUSTICAL PANEL NOTES:

1. ACOUSTICAL PANELS TO BE MOUNTED ON "Z" CLIPS PER SPECIFICATIONS.

2. ACOUSTICAL PANELS TO BE FIELD CUT BY MANUFACTURE'S APPROVED INSTALLER, CUT EDGES TO BE FABRIC

WRAPED. OPENINGS TO BE CUT FOR RECEPTACLES, WALL MOUNTS , ETC. ELECTRICAL INSTALLATION TO BE

COORDINATED WITH PANEL INSTALLATION AND EQUIPMENT REQUIREMENTS.

3. FINISHES TO BE SELECTED BY OWNER (PDC).

SEE ACOUSTICAL PANEL NOTESSEE ACOUSTICAL PANEL NOTES

SEE ACOUSTICAL PANEL NOTES SEE ACOUSTICAL PANEL NOTES

REVISIONS

# DATE DESCRIPTION

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

RCP LEGEND:

NEW 2X2 ACOUSTICAL CEILING TILE

AND SUSPENDED GRID

GPDW CEILING/BULKHEAD

2 X 4 LIGHT FIXTURE; SEE ELECTRICAL

NEW CEILING OUTLINE

HVAC SUPPLY; SEE MECHANICAL

HVAC RETURN; SEE MECHANICAL

EXIT LIGHT; SEE ELECTRICAL

SPRINKLER HEAD; SEE FIRE PROTECTION DRAWINGS

EXISTING CEILING OUTLINE

EXISTING WALL OUTLINE

PLAN NORTH

AREA OF WORK:

956 SF

EXISTING BULKHEAD

ANIMATION

LAB.

10'-1"

SN2

10'-1"

SN2

SN1

SN1

O

T R

I

EG

S

STA

TE

H

DE AR RE C

CT

ETI

A O

ROBERT L. MAULDIN

GF E

I

RG

oI NC EAT .I

RE

T C

F

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

PR

IN

TE

D

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

04/10/2026

4/

/2

9:

:0

A M

Z

A ct iv e_

Pr oj ec ts

\2

Pr oj ec ts \2

5-

A U

-S C \2

5-

.0

A U

-S C U

H A ni m at io n La b\ D

R A W

IN

G

S \0

0% C

D s\

-1

1.

0% .r vt

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026

A1.2TR/DA

25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

REFLECTED CEILING

PLAN

100% CD

PLAN NORTH

SN1 USE 2'X4' A.T.C. AND CUT TO FIT WHERE NEEDED.

SN2 MATCH EXISTING CEILING HEIGHT.

SPECIAL NOTES (SN #'S)

SCALE: 1/4" = 1'-0"

1 REFLECTED CEILING PLAN

SCALE: 1/4"= 1'-0"

8'0 4'1'

REVISIONS

# DATE DESCRIPTION

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

PLAN NORTH

AREA OF WORK:

956 SF

M1

D1

M1

C1 C1C1 C1C1 C1

C1

C1

C1C1

C1

C1C1C1C1C1C1C1C1

P1

ANIMATION

LAB.

W1

W1

C1

/2

TA1

TA1

CH1CH1

DK1

DK1

CH1CH1CH1

CH1 CH1 CH1 CH1 CH1 CH1

CH1

CH1

CH1

CH1

CH1

CH1

CH1CH1CH1

CH1

CH1

CH1CH1CH1CH1

CH1CH1CH1CH1

DK1

DK1DK1

DK1 DK1 DK1

DK1

CH1 CH1 CH1 CH1 CH1

DK1

ANIMATION

LAB.

O

T R

I

EG

S

STA

TE

H

DE AR RE C

CT

ETI

A O

ROBERT L. MAULDIN

GF E

I

RG

oI NC EAT .I

RE

T C

F

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

PR

IN

TE

D

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

04/10/2026

4/

/2

9:

:0

A M

Z

A ct iv e_

Pr oj ec ts

\2

Pr oj ec ts \2

5-

A U

-S C \2

5-

.0

A U

-S C U

H A ni m at io n La b\ D

R A W

IN

G

S \0

0% C

D s\

-1

1.

0% .r vt

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026

A1.3TR/DA

25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

EQUIPMENT AND

FURNITURE PLAN

100% CD

PLAN NORTH

EQUIPMENT SCHEDULE

R

EV

IS

IO

N

ITEM

NO. ITEM DESCRIPTION MANUFACTURER MODEL NO.

DIMENSIONS

DATA POWER E.

POWER NOTES

W

ID

TH

D

EP

TH

H

EI

G H

T

C1 DESKTOP COMPUTER X X C

D1 GLASS BOARD

M1 MONITOR SHARP PN-M652 4'-9 1/2" 2'-6" 1'-8" X X

P1 PODIUM SPECTRUM INDUSTRIES INC.

HONORS LECTERN

3'-2" 2'-6" 2'-10" X X

W1 WALL MOUNT CHIEF LEGRAND 3'-6" 1 3/4" 1'-8"

A. ALL EQUIPMENT SUPPLIED AND INSTALLED BY OWNER UNLESS NOTED.

B. CONTRACTOR TO PROVIDE ALL BLOCKING/SUPPORT FOR WALL AND/OR CEILING MOUNTED ITEMS LISTED.

CONTRACTOR TO REVIEW ALL SUPPORTS WITH OWNER AND ARCHITECT (IN FIELD) PRIOR TO INSTALLATION OF

GPDW.

C. CPU INCLUDES TOWER, MONITORS, MOUSE, KEYBOARD, TABLET, ETC.

NOTES:

SCALE: 1/4" = 1'-0"

1 EQUIPMENT PLAN

SCALE: 1/4" = 1'-0"

2 FURNITURE PLAN

SCALE: 1/4"= 1'-0"

8'0 4'1'

SCALE: 1/4"= 1'-0"

8'0 4'1'

PLAN NORTH

FURNITURE SCHEDULE

R

EV

IS

IO

N

ITEM

NO. ITEM DESCRIPTION MANUFACTURER

MODEL #

DIMENSIONS

DATA POWER NOTES

W

ID

TH

D

EP

TH

H

EI

G H

T

CH1 CHAIR, TASK

DK1 DESK, ANIMATION

TA1 TABLE, CONFERENCE

A. ALL FURNITURE SUPPLIED AND INSTALLED BY OWNER UNLESS NOTED.

REVISIONS

# DATE DESCRIPTION

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT APPLY TO THIS SECTION.

1.2 SUMMARY

A. PROVIDE COMPLETE, OPERATIONAL FIRE SPRINKLER SYSTEM. INCLUDE FIRE-SUPPRESSION PIPING AND

EQUIPMENT FOR THE FOLLOWING SYSTEM TYPES:

1. WET-PIPE, FIRE-SUPPRESSION SPRINKLERS, INCLUDING PIPING, VALVES, SPECIALTIES, AND

AUTOMATIC SPRINKLERS.

1.3 SYSTEM PERFORMANCE REQUIREMENTS

A. DESIGN SPRINKLERS AND OBTAIN APPROVAL FROM AUTHORITIES HAVING JURISDICTION.

B. DESIGN SPRINKLER PIPING FOR LIGHT HAZARD.

C. COMPONENTS AND INSTALLATION: CAPABLE OF PRODUCING PIPING SYSTEMS WITH 175-PSIG

MINIMUM WORKING-PRESSURE RATING, UNLESS OTHERWISE INDICATED.

1.4 SUBMITTALS

A. PRODUCT DATA: FOR THE FOLLOWING:

1. PIPE AND FITTING MATERIALS AND METHODS OF JOINING FOR SPRINKLER PIPING.

2. PIPE HANGERS AND SUPPORTS.

3. SPRINKLERS, ESCUTCHEONS, AND GUARDS. INCLUDE SPRINKLER FLOW CHARACTERISTICS,

MOUNTING, FINISH, AND OTHER PERTINENT DATA.

B. SPRINKLER PIPING DRAWINGS: SUBMIT WORKING PLANS AND EQUIPMENT INFORMATION, PREPARED

ACCORDING TO NFPA 13, TO AUTHORITIES HAVING JURISDICTION FOR REVIEW. INCLUDE HYDRAULIC

CALCULATIONS, IF APPLICABLE.

C. REVIEW OF SUBMITTALS DOES NOT RELIEVE THE CONTRACTOR OF ANY OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. FAILURE BY THE ENGINEER TO DOCUMENT ERRORS AND OMISSIONS IN THE CONTRACTOR'S SUBMITTALS DURING THE ENGINEER'S SUBMITTAL REVIEW DOES NOT CONSTITUTE A

WAIVER OF ANY OF THE REQUIREMENTS OF THE ORIGINAL CONTRACT DOCUMENTS.

D. FIELD TEST REPORTS AND CERTIFICATES: INDICATE AND INTERPRET TEST RESULTS FOR COMPLIANCE

WITH PERFORMANCE REQUIREMENTS AND AS DESCRIBED IN NFPA 13. INCLUDE CONTRACTOR'S

MATERIAL AND TEST CERTIFICATE FOR ABOVEGROUND PIPING.

E. MAINTENANCE DATA: FOR EACH TYPE OF SPRINKLER SPECIALTY TO INCLUDE IN MAINTENANCE

MANUAL.

1.5 QUALITY ASSURANCE

A. INSTALLER QUALIFICATIONS: AN EXPERIENCED INSTALLER WHO HAS DESIGNED AND INSTALLED

FIRE-SUPPRESSION PIPING SIMILAR TO THAT INDICATED FOR THIS PROJECT AND OBTAINED DESIGN

APPROVAL AND INSPECTION APPROVAL FROM AUTHORITIES HAVING JURISDICTION.

B. MANUFACTURER QUALIFICATIONS: FIRMS WHOSE EQUIPMENT, SPECIALTIES, AND ACCESSORIES ARE LISTED BY PRODUCT NAME AND MANUFACTURER IN UL'S "FIRE PROTECTION EQUIPMENT DIRECTORY" AND FM'S "FIRE PROTECTION APPROVAL GUIDE" AND THAT COMPLY WITH OTHER REQUIREMENTS

INDICATED.

C. SPRINKLER COMPONENTS: LISTING/APPROVAL STAMP, LABEL, OR OTHER MARKING BY A TESTING

AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.

D. NFPA STANDARDS: EQUIPMENT, SPECIALTIES, ACCESSORIES, INSTALLATION, AND TESTING COMPLYING

WITH NFPA 13.

1.6 LAYOUT AND COORDINATION

A. LAYOUT BASIS:

1. THE EQUIPMENT LISTED ON THE DRAWINGS AND IN THE SPECIFICATIONS HAS BEEN USED FOR THE

PHYSICAL ARRANGEMENT OF THE FIRE SPRINKLER SYSTEMS. WHEN EQUIPMENT LISTED AS

ACCEPTABLE, EQUAL OR EQUIPMENT WHICH HAS RECEIVED "PRIOR APPROVAL" IS USED, IT SHALL

BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE STRUCTURAL, ELECTRICAL, SERVICE

CLEARANCES, OR OTHER CHANGES REQUIRED TO ACCOMMODATE THE SUBSTITUTED EQUIPMENT.

CHANGES SHALL BE MADE AT NO ADDITIONAL COST TO THE OWNER. SUBMIT A LIST OF REQUIRED

CHANGES ALONG WITH ALL PRIOR APPROVAL REQUESTS AND SHOP DRAWING SUBMITTALS.

2. THE CONTRACT DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT OF ALL FIRE SPRINKLER WORK. THEY DO NOT SHOW IN DETAIL ALL OFFSETS, FITTINGS AND TRANSITIONS.

EXAMINE DRAWINGS, INVESTIGATE SITE CONDITIONS TO BE ENCOUNTERED AND ARRANGE WORK

ACCORDINGLY. FURNISH ALL OFFSETS AND TRANSITIONS REQUIRED.

3. CHECK SPACE LIMITATIONS AND VERIFY ELECTRICAL REQUIREMENTS BEFORE ORDERING ANY FIRE SPRINKLER EQUIPMENT OR MATERIALS. PLACE LARGE EQUIPMENT INSIDE THE BUILDING PRIOR TO

THE ERECTION OF EXTERIOR WALLS WHERE EQUIPMENT CANNOT ENTER FINISHED BUILDING

OPENINGS.

B. COORDINATION: FIRE SPRINKLER WORK SHALL BE COORDINATED WITH THAT OF OTHER TRADES TO AVOID CONFLICT. THE CONTRACTOR SHALL STUDY ALL PLANS AND SPECIFICATIONS FOR THIS PROJECT AND SHALL NOTIFY THE DESIGN PROFESSIONAL OF ANY CONFLICT BETWEEN WORK UNDER DIVISION 21 AND WORK UNDER OTHER DIVISIONS OF THE PROJECT. PARTICULAR ATTENTION SHALL BE GIVEN TO INTERFERENCE BETWEEN PIPING, ELECTRICAL INSTALLATIONS, STRUCTURAL SYSTEMS, BUILDING

OPENINGS AND DUCTWORK.

C. OPERATION AND MAINTENANCE INSTRUCTIONS:

1. PROVIDE AN ELECTRONIC (PDF FORMAT) DOCUMENT CONTAINING ALL OF THE OPERATION AND

MAINTENANCE MANUALS FOR FIRE SPRINKLER EQUIPMENT UTILIZED AND FIRE SPRINKLER TESTS PERFOMED ON THE PROJECT AS SPECIFIED IN THIS AND OTHER SECTIONS OF THE SPECIFICATIONS.

2. THE O&M DOCUMENT SHALL INCLUDE A COVER PAGE INDICATING THE PROJECT NAME, PROJECT

NUMBER, LEAD DESIGN PROFESSIONAL, MECHANICAL DESIGN PROFESSIONAL, AND PROJECT

OWNER.

3. THE DOCUMENT SHALL INCLUDE A TABLE OF CONTENTS WITH ELECTRONIC TABS THAT LINK TO

EACH OF THE EQUIPMENT SECTIONS IN THE DOCUMENT.

4. PROJECT-SPECIFIC MODEL AND SERIAL NUMBER INFORMATION SHALL BE SHOWN ON THE LEAD

PAGE OF EACH EQUIPMENT SECTION IN THE MANUAL.

5. THE MANUAL SHALL INCLUDE DOCUMENTATION CONFIRMING REGISTRATION OF EXTENDED

WARRANTIES WITH THE EQUIPMENT MANUFACTURER. THIS DOCUMENTATION SHALL INCLUDE

EQUIPMENT SERIAL NUMBERS AND DATES OF WARRANTY START.

6. THE DOCUMENT SHALL BE SUBMITTED TO THE OWNER AND THE DESIGN TEAM AT LEAST 15 DAYS

PRIOR TO THE SCHEDULED SYSTEMS/EQUIPMENT MAINTENANCE TRAINING.

1.7 PERMITS

A. OBTAIN ALL NECESSARY PERMITS AND INSPECTIONS REQUIRED FOR THE INSTALLATION OF THIS WORK

AND PAY ALL CHARGES INCIDENT THERETO. DELIVER TO THE DESIGN PROFESSIONAL ALL CERTIFICATES

OF INSPECTION ISSUED BY AUTHORITIES HAVING JURISDICTION.

B. FIRE MARSHAL SUBMITTAL FEES AND ALL OTHER CHARGES FOR WORK UNDER THIS DIVISION SHALL BE

PAID BY THE CONTRACTOR.

1.8 SEQUENCING AND SCHEDULING

A. COORDINATE MECHANICAL EQUIPMENT INSTALLATION WITH OTHER BUILDING COMPONENTS.

B. ARRANGE FOR CHASES, SLOTS, AND OPENINGS IN BUILDING STRUCTURE DURING PROGRESS OF

CONSTRUCTION TO ALLOW FOR MECHANICAL INSTALLATIONS.

C. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET SLEEVES IN

POURED-IN-PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS AS THEY ARE CONSTRUCTED.

D. SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATIONS OF MECHANICAL MATERIALS AND

EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. COORDINATE INSTALLATION OF LARGE EQUIPMENT

REQUIRING POSITIONING PRIOR TO CLOSING IN THE BUILDING.

E. COORDINATE CONNECTION OF ELECTRICAL SERVICES.

F. COORDINATE CONNECTION OF MECHANICAL SYSTEMS WITH EXTERIOR UNDERGROUND AND

OVERHEAD UTILITIES AND SERVICES. COMPLY WITH REQUIREMENTS OF GOVERNING REGULATIONS, FRANCHISED SERVICE COMPANIES, AND CONTROLLING AGENCIES.

1.9 INTERRUPTION OF EXISTING SERVICES

A. EXERCISE CARE SO AS NOT TO CUT ANY EXISTING UTILITIES OR SERVICES. WHERE AN EXISTING UTILITY

LINE OR SERVICE LINE IS CUT IT SHALL BE REPAIRED TO "LIKE-NEW" CONDITION. INTERRUPTION OF

SERVICE SHALL NOT BE MADE WITHOUT PRIOR WRITTEN PERMISSION OF THE OWNER.

B. FIRE SUPPRESSION SYSTEM MUST REMAIN IN SERVICE DURING CONSTRUCTION. ARRANGE WITH THE

OWNER WELL IN ADVANCE OF SHUTDOWNS REQUIRED FOR TIE-INS. SHUTDOWNS SHALL BE MADE

AFTER NORMAL OCCUPANCY HOURS IF SO DIRECTED BY THE OWNER. NO ADDITIONAL MONIES WILL BE

PAID FOR AFTER-HOURS SHUTDOWNS.

1.10 EXTRA MATERIALS

A. FURNISH SPRINKLER CABINETS: FINISHED, WALL-MOUNTING STEEL CABINET AND HINGED COVER, WITH

SPACE FOR A MINIMUM OF SIX SPARE SPRINKLERS PLUS SPRINKLER WRENCH. INCLUDE THE NUMBER OF SPRINKLERS REQUIRED BY NFPA 13 AND WRENCH FOR SPRINKLERS. INCLUDE SEPARATE CABINET

WITH SPRINKLERS AND WRENCH FOR EACH TYPE OF SPRINKLER ON PROJECT.

1.11 CODES AND STANDARDS

A. MECHANICAL INSTALLATIONS SHALL CONFORM TO THE CURRENT EDITION (RECOGNIZED BY THE STATE)

OF THE FOLLOWING, IN ADDITION TO ANY PREVIOUSLY MENTIONED CODES AND STANDARDS.

7. THE INTERNATIONAL BUILDING CODE.

8. THE INTERNATIONAL FIRE PROTECTION CODE.

9. NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.

10. NFPA 25 STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE

PROTECTION SYSTEMS.

PART 2 - PRODUCTS

2.1 PIPES AND TUBES

A. STANDARD-WEIGHT STEEL PIPE: ASTM A 53, ASTM A 135, OR ASTM A 795; SCHEDULE 40 IN NPS 2 AND

SMALLER.

B. SCHEDULE 10 STEEL PIPE: ASTM A 135 OR ASTM A 795, SCHEDULE 10 IN NPS 2-1/2 AND LARGER.

2.2 PIPE AND TUBE FITTINGS

A. CAST-IRON FITTINGS AND FLANGES: ASME B16.1.

B. MALLEABLE-IRON THREADED FITTINGS: ASME B16.3.

C. STEEL, THREADED COUPLINGS: ASTM A 865.

D. STEEL WELDING FITTINGS: ASTM A 234/A 234M, ASME B16.9, OR ASME B16.11.

E. STEEL FLANGES AND FLANGED FITTINGS: ASME B16.5.

F. STEEL, GROOVED-END FITTINGS: UL-LISTED AND FM-APPROVED, ASTM A 47 (ASTM A 47M), MALLEABLE

IRON OR ASTM A 536, DUCTILE IRON; WITH DIMENSIONS MATCHING STEEL PIPE AND ENDS FACTORY

GROOVED ACCORDING TO AWWA C606.

2.3 JOINING MATERIALS

A. STEEL, KEYED COUPLINGS: UL 213 AND AWWA C606, FOR STEEL-PIPE DIMENSIONS. INCLUDE ASTM A

536, DUCTILE-IRON HOUSING, RUBBER GASKETS, AND STEEL BOLTS AND NUTS.

2.4 SPRINKLERS

A. AUTOMATIC SPRINKLERS: WITH INTERMEDIATE TEMPERATURE CLASSIFICATION RATED ELEMENT

COMPLYING WITH UL199.

B. SPRINKLER TYPES, FEATURES, AND OPTIONS INCLUDE THE FOLLOWING:

1. CONCEALED CEILING SPRINKLERS, INCLUDING COVER PLATE.

PART 3 - EXECUTION

3.1 DEMOLITION

A. WHERE PIPE OR EQUIPMENT TO REMAIN IS DAMAGED OR DISTURBED, REMOVE DAMAGED PORTIONS

AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY.

B. ABANDONED WORK: CUT AND REMOVE PIPE ABANDONED IN PLACE, 2 INCHES BEYOND THE FACE OF

ADJACENT CONSTRUCTION. CAP PIPING AND PATCH SURFACE TO MATCH EXISTING FINISH.

C. REMOVAL: REMOVE INDICATED EQUIPMENT AND PIPING FROM THE PROJECT SITE UNLESS NOTED

OTHERWISE.

D. TEMPORARY DISCONNECTION: REMOVE, STORE, CLEAN, REINSTALL, RECONNECT, AND MAKE

OPERATIONAL EQUIPMENT INDICATED FOR RELOCATION.

E. REMOVE ALL HANGERS, SUPPORTS AND ANCHORS ASSOCIATED WITH FIRE SPRINKLER ITEMS. PATCH

SURFACES TO MATCH ADJACENT FINISHES.

3.3 ERECTION OF METAL SUPPORTS AND ANCHORAGE

A. CUT, FIT, AND PLACE MISCELLANEOUS METAL SUPPORTS ACCURATELY IN LOCATION, ALIGNMENT, AND

ELEVATION TO SUPPORT AND ANCHOR MECHANICAL MATERIALS AND EQUIPMENT.

3.4 PIPING APPLICATIONS

A. WET-PIPE SPRINKLERS: USE THE FOLLOWING:

1. NPS 1-1/4 AND LARGER: SCHEDULE 10 STEEL PIPE WITH PLAIN ENDS, STEEL WELDING FITTINGS, AND WELDED JOINTS.

2. NPS 2 AND SMALLER: STANDARD-WEIGHT STEEL PIPE WITH THREADED ENDS, CAST- OR

MALLEABLE-IRON THREADED FITTINGS, AND THREADED JOINTS.

3. NPS 1-1/4 AND LARGER: SCHEDULE 10 STEEL PIPE WITH ROLL-GROOVED ENDS; STEEL,

GROOVED-END FITTINGS; AND GROOVED JOINTS.

3.5 JOINT CONSTRUCTION

A. STEEL-PIPING, GROOVED JOINTS: USE SCHEDULE 40 STEEL PIPE WITH CUT OR ROLL-GROOVED ENDS

AND SCHEDULE 30 OR THINNER STEEL PIPE WITH ROLL-GROOVED ENDS; STEEL, GROOVED-END

FITTINGS; AND STEEL, KEYED COUPLINGS. ASSEMBLE JOINTS WITH COUPLINGS, GASKETS, LUBRICANT, AND BOLTS ACCORDING TO COUPLING MANUFACTURER'S WRITTEN INSTRUCTIONS.

B. DISSIMILAR-PIPING-MATERIAL JOINTS: CONSTRUCT JOINTS USING ADAPTERS OR COUPLINGS

COMPATIBLE WITH BOTH PIPING MATERIALS.

3.6 WATER-SUPPLY CONNECTION

A. CONNECT SPRINKLER PIPING TO EXISTING SPRINKLER SUPPLY PIPING.

3.7 PIPING INSTALLATION

A. USE APPROVED FITTINGS TO MAKE CHANGES IN DIRECTION, BRANCH TAKEOFFS FROM MAINS, AND

REDUCTIONS IN PIPE SIZES.

B. HANGERS AND SUPPORTS: COMPLY WITH NFPA 13 FOR HANGER MATERIALS. INSTALL ACCORDING TO

NFPA 13 FOR SPRINKLER PIPING.

C. INSTALL PIPING WITH GROOVED JOINTS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.

CONSTRUCT RIGID PIPING JOINTS, UNLESS OTHERWISE INDICATED.

D. FIRE BARRIER PENETRATIONS: MAINTAIN INDICATED FIRE RATING OF WALLS, PARTITIONS, CEILINGS, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE PENETRATIONS WITH U.L. LISTED FIRESTOPPING

SEALANT SYSTEM.

3.8 SPECIALTY SPRINKLER FITTING INSTALLATION

A. INSTALL SPECIALTY SPRINKLER FITTINGS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.

3.9 SPRINKLER APPLICATIONS

A. GENERAL: Q.R. CONCEALED SPRINKLERS.

3.10 SPRINKLER INSTALLATION

A. INSTALL SPRINKLERS IN SUSPENDED CEILINGS IN CENTER OF ACOUSTICAL PANELS AND TILES.

3.11HANGER AND SUPPORT INSTALLATION

A. GENERAL: COMPLY WITH NFPA 13, NFPA 14, MSS SP-69 AND SP-89. INSTALL HANGERS, SUPPORTS, CLAMPS, AND ATTACHMENTS AS REQUIRED TO PROPERLY SUPPORT PIPING FROM BUILDING

STRUCTURE

3.12 CONNECTIONS

A. CONNECT WATER SUPPLIES TO SPRINKLERS

3.13ERECTION OF METAL SUPPORTS AND ANCHORAGE

A. CUT, FIT, AND PLACE MISCELLANEOUS METAL SUPPORTS ACCURATELY IN LOCATION, ALIGNMENT, AND

ELEVATION TO SUPPORT AND ANCHOR MECHANICAL MATERIALS AND EQUIPMENT.

B. FIELD WELDING: COMPLY WITH AWS D1.1 "STRUCTURAL WELDING CODE--STEEL."

3.14 FIELD QUALITY CONTROL

A. FLUSH, TEST, AND INSPECT SPRINKLER PIPING ACCORDING TO NFPA 13.

B. REPORT TEST RESULTS PROMPTLY AND IN WRITING TO THE DESIGN PROFESSIONAL AND AUTHORITIES

HAVING JURISDICTION.

3.15 PROTECTION

A. PROTECT SPRINKLERS FROM DAMAGE UNTIL MATERIAL COMPLETION.

3.16 COMMISSIONNG

A. VERIFY THAT SPECIFIED TESTS OF PIPING ARE COMPLETE.

B. VERIFY THAT DAMAGED SPRINKLERS AND SPRINKLERS WITH PAINT OR COATING NOT SPECIFIED ARE

REPLACED WITH NEW, CORRECT TYPE.

C. VERIFY THAT SPRINKLERS ARE CORRECT TYPES, HAVE CORRECT FINISHES AND TEMPERATURE RATINGS, AND HAVE GUARDS AS REQUIRED FOR EACH APPLICATION.

D. FILL WET-PIPE SPRINKLER PIPING WITH WATER.

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026 25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

100% CD

REVISIONS

# DATE DESCRIPTION

FP1.1

FIRE PROTECTION

PLOT DATE:

FILENAME:

PLOT SCALE:

AU

G

U

ST

A, G

A

(7

) 7

-3

CO

PY

RI

G

HT

PF

A

EN

G

IN

EE

RI

N G

, I N

C.

04/09/26

25096FP1

1 = 96

JCP

JCP

FP1.1

FIRE PROTECTION DEMOLITION PLAN

SCALE: 1/8" = 1'-0"

FP1.1

FIRE PROTECTION NEW WORK PLAN

SCALE: 1/8" = 1'-0"

FIRE PROTECTION NOTES

EXISTING CLASSROOM BUILDING IS PROTECTED BY A WET PIPE

SPRINKLER SYSTEM.

REWORK SPRINKLER SYSTEM IN RENOVATED SPACES IN

ACCORDANCE WITH THE FOLLOWING:

· 2022 EDITION NFPA 13

· 2026 EDITION GEORGIA FIRE CODE 120-3-3

IN NEW CEILINGS, INSTALL WHITE CONCEALED QUICK

RESPONSE EXTENDED COVERAGE SPRINKLERS RATED FOR

INTERMEDIATE TEMPERATURE ACTIVATION.

REFER TO NFPA 25 REGARDING PRE-PLANNED SYSTEM

IMPAIRMENTS FOR CORRECTIONS, ALTERATIONS OR

IMPROVEMENTS.

PROVIDE SHOP DRAWINGS AND EQUIPMENT SUBMITTALS FOR

REVIEW BY ENGINEER, AHJ AND OWNER.

EXACT LOCATION, ARRANGEMENT, AND SIZES SHALL BE

VERIFIED ON THE JOB BEFORE PROCEEDING WITH ANY NEW

WORK. EXACT LOCATIONS AND ROUGHING REQUIREMENTS

FOR ALL FIXTURES AND EQUIPMENT SHALL BE DETERMINED

FROM APPROVED MANUFACTURER'S SHOP DRAWINGS.

PARTICULAR ATTENTION SHALL BE DIRECTED TO FIXTURES OR

EQUIPMENT FURNISHED UNDER OTHER DIVISIONS.

PROVIDE SLEEVES FOR PIPES PASSING THRU FLOORS,

MASONRY WALLS AND FIRE OR SMOKE PARTITIONS. PACK

ANNULAR SPACE BETWEEN PIPE WITH MATERIAL APPROVED

IN U.L. BUILDING DIRECTORY.

GENERAL

ALL AREAS ARE LIGHT HAZARD UNLESS NOTED OTHERWISE

ORDINARY HAZARD - GROUP 1

HAZARD CLASSIFICATION

REWORK EXISTING

SPRINKLER SYSTEM TO

CONFORM TO NEW

CEILING, LIGHTING

AND DUCTWORK

CONFIGURATIONS

REWORK EXISTING

SPRINKLER SYSTEM TO

CONFORM TO NEW

CEILING, LIGHTING

AND DUCTWORK

CONFIGURATIONS

PLAN NORTH

EXISTING 02/26/2025 FIRE PUMP TEST

APPROX LOCATION OF

EXISTING EXT

COVERAGE SPRINKLER

(TYPICAL) ANIMATION LAB

(C0MPUTER LAB)

C0MPUTER LAB

AREA OF WORK

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

KM

ARCHITECTS, INC.

DATE

DRAWING NO.

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026 25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

100% CD

REVISIONS

# DATE DESCRIPTION

ANIMATION

LAB.

ANIMATION

LAB.

PLAN NORTH

M101

HVAC DEMOLITION PLAN

SCALE: 1/4" = 1'-0"

M101

HVAC NEW WORK PLAN

SCALE: 1/4" = 1'-0"

M0.1WDP

HVAC PLANS

18X14

12X12

X1

T 4-41

EXIST. 18X14

EXIST. 12X12

EX

IS

T.

6X

PLOT DATE:

FILENAME:

PLOT SCALE:

AU

G

U

ST

A, G

A

(7

) 7

-3

CO

PY

RI

G

HT

PF

A

EN

G

IN

EE

RI

N G

, I N

C.

04/09/26 25096M1 1 = 48

JBM/WDP

DEMOLITION NOTES

(THIS SHEET ONLY):

REMOVE AIR DEVICE AND ASSOCIATED RUNOUT TO THE

EXTENTS NECESSARY FOR THE INSTALLATION OF NEW

AS SHOWN ON NEW WORK PLAN.

REMOVE RETURN GRILLE. REPLACE WITH NEW AS

SHOWN ON NEW WORK PLAN.

REMOVE TERMINAL UNIT AND ASSOCIATED

THERMOSTAT. REMOVE HOT WATER COIL PIPING TRIM.

KEY NOTES (THIS SHEET ONLY):

FURNISH TRANSITION IF REQUIRED TO CONNECT NEW

RUNOUT TO EXISTING DUCTWORK.

INSTALL NEW GRILLE IN EXISTING RETURN PLENUM.

FURNISH CLEANING AND REPAINTING OF INTERIOR OF

EXISTING PLENUM IF REQUIRED.

CONNECT NEW COIL TRIM FOR REPLACEMENT

TERMINAL UNIT TO EXISTING HOT WATER RUNOUTS.

EX

IS

T.

8X

EX

IS

T.

2X

34X24 F/O 40X24 F/O

TU4-40

TU4-42

EX

IS

T.

6X

EX

IS

T.

4X

TU4-56

D

14X14

X1 c A

N E c A

N E c A c A c A

N

E

N E

N E

N E

D c A c A c A c A

T 4-56

T 4-41

N

E TU4-41

34X24 F/O 40X24 F/O

TU4-40

TU4-42

EX

IS

T.

6X

EX

IS

T.

4X

TU4-413

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

KM

DATE

DRAWING NO.

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026 25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

100% CD

REVISIONS

# DATE DESCRIPTION

M1.1

HVAC SCHEDULES,

FMS SUMMARY,

DETAILS, NOTES

AND LEGEND

PLOT DATE:

FILENAME:

PLOT SCALE:

AU

G

U

ST

A, G

A

(7

) 7

-3

CO

PY

RI

G

HT

PF

A

EN

G

IN

EE

RI

N G

, I N

C.

04/09/26 25096M1 1 = 48

JBM/WDP

NOT TO SCALE

FLEXIBLE ROUND DUCT CONNECTION DETAIL

APPLY DUCT INSULATION TO ELBOW

48" (MAXIMUM)

3" MIN. (TYP.)

ROUND NECK EXTENSION

OR SQUARE TO ROUND

ADAPTER WITH ROUND

NECK EXTENSION.

CEILING

INSULATED FLEXIBLE DUCT

SHEET METAL DUCT

M1.1

THROAT OF DIFFUSER

MASTIC JOINT AROUND

GLASSFAB AND

SHEET METAL 90° ELBOW.

SEAL CONNECTION PER DUCT

MANUFACTURER'S INSTALLATION

INSTRUCTIONS (TYPICAL)

FACTORY-INSTALLED, MOLDED,

INSULATED BACKPAN WITH FOIL SKRIM

VAPOR BARRIER

SEAL FLEX TO INSULATION

IN ACCORDANCE WITH

SPECIFICATIONS. (TYP.)

NYLON STRAP APPLIED

TO INNER FLEX LINER

WITH TENSIONING TOOL.

NOT TO SCALE

SUPPLY DUCT TAKE-OFF FITTING DETAIL

RECTANGULAR DUCT

1" STAND-OFF BRACKET

FOR INSULATION

MANUAL VOLUME DAMPER

CROWN NO. 306 ADJUSTABLE

TAKE-OFF FITTING (RECTANGULAR

TO ROUND). CROWN NO. 305 FOR

ROUND TO ROUND.

CLINCH LOCK (TYPICAL)

AI

R

FL

O

W

M1.1

SEE DETAILS FOR

LOW PRESSURE

DUCT CONSTRUCTION.

TO TERMINAL BOX.

CONICAL TAKEOFF

TRUNK DUCT WITH

MEDIUM PRESSURE

DUCT SIZE SHOWN ON PLANS

PROVIDE TRANSITION TO

LOW

PRESSURE

DUCT

MVD

CROWN 306 TAKEOFF

TO GRILLE

MANUAL VOLUME

DAMPER

PRE-INSULATED

FLEXIBLE DUCT

SUPPORT UNIT FROM STRUCTURE

ABOVE WITH THREADED ROD OR

STEEL STRAP.

(MAX 48" LENGTH)

VAV TERMINAL BOX DETAIL

NOT TO SCALE

M1.1

CFMCFM

5.0

WPD (FT. WG)

MODEL NO.

TRANE

VCWF-08

CONN.

NECK

VALVE

AIR

8"ø

HYDRONIC HEAT

GPM

0.87.8

MBH(1)

0.2

APD

MIN.DESIGN

PRIMARY AIR VALVE

TU4-41

ITEM

-- VAV TERMINAL UNIT SCHEDULE --

(3)

(1) MAX. IN. WG @ DESIGN CFM.

(2) COOLING ONLY.

(3) DUCT RUNOUTS SHALL BE NECK SIZE UNLESS INDICATED OTHERWISE.

REMARKS

(IN.)

-- AIR DISTRIBUTION SCHEDULE --

A

MARK TYPE FINISH OBDNECK

CONNECTION

(1) NO.

UNLESS NOTED

REMARKS (2)

D

CEILING

DIFFUSER 8"ø NO 24 X 24 PANEL

22" X 22" NORETURN/EXHAUST

CEILING

PRICE

SCD-4C

80MANUFACTURER'S

STANDARD FINISH

MANUFACTURER'S

STANDARD FINISH

WITH BORDER FRAME

24 X 24 PANEL

(1) DUCT RUNOUT SIZE SAME AS NECK CONNECTION SIZE, UNLESS NOTED OTHERWISE.

(2) PROVIDE LAY-IN TYPE FOR T-BAR CEILINGS AND SURFACE TYPE FOR ALL OTHER CEILINGS. REFER TO

ARCHITECTURAL FINISH SCHEDULE FOR CEILING TYPES.

(3) PROVIDE WITH REMOVABLE CORE (RC) AND MOLDED, INSULATED BACKPAN WITH FOIL SKRIM VAPOR

BARRIER.

ROOM OFFSET

ROOM TEMPERATURE

XDAMPER

TYPICAL TERMINAL UNIT

SUMMARY

INPUT/OUTPUT

FMS

ALARM ENERGY MGMT.DDCANALOGBINARYANALOGBINARY

SOFTWAREINPUTSOUTPUTS

N O

TE

S

FA

N

S

YN

CH

RO

N

IZ

AT

IO

N

EC

O N

O M

IZ

ER

RE

SE

T O

PT

IM

IZ

AT

IO

N

DE

M

AN

D

LI

M

IT

/C

YC

LE

DA

Y/

N

IG

HT

S

ET

BA

CK

O

PT

IM

U M

S

TA

RT

/S

TO

P

TI

M

E

SC

HE

DU

LE

S

/S

PR

O

P.

IN

TE

G

RA

L

PR

O

PO

RT

IO

N

AL

RU

N

T

IM

E

TO

TA

LI

ZA

TI

O N

HI

/L

O L

IM

IT

ST

AT

U S/

IN

TE

RL

O

CK

VO

LU

M

E (C

FM

PR

ES

SU

RE

RE

LA

TI

VE

H U

M

ID

IT

Y

TE

M

PE

RA

TU

RE

PU

LS

E

CO

N

TA

CT

AL

AR

M

C O

N

TA

CT

AU

X.

C

O N

TA

CT

DI

FF

. P

RE

SS

U

RE

S

W

IT

CH

DD

C

CO

N

TR

O

L

SE

TP

O

IN

T

AD

JU

ST

O

PE

N /C

LO

SE

EN

AB

LE

/D

IS

AB

LE

ST

AR

T/

ST

O

P

X X X

AIRFLOW X

DISCHARGE AIR TEMPERATURE X

NOT TO SCALE

EXHAUST/RETURN GRILLE CONNECTION DETAILS

6" HIGH FROM

TOP OF "T-BAR"

SIZES.

SEE DRAWINGS FOR

SHEET METAL DUCT.

GRILLE

LAY-IN

GRILLE

SURFACE MOUNTED

SQUARE ELBOW WITH TURNING VANES

CAN FULL SIZE OF LAY-IN

EXH./RETURN GRILLE.

CONST. OF 22 GA. SHEET

METAL & PAINT INSIDE

FLAT BLACK

ATTACH CAN TO "T-BAR"

SCREWS (2 EACH SIDE)

CEILING

CEILING

WITH SHEET METAL

M1.1

PAINT INSIDE OF TRANSITION,

DUCT AND VISIBLE PORTION OF

ELBOW FLAT BLACK.

TRANSITION FROM

DUCT TO GRILLE

WITH SHEET METAL

DUCTWORK.

HVAC NOTES:

NOT ALL EXISTING WORK IS SHOWN, AND THAT SHOWN IS IN ITS APPROXIMATE LOCATION AND ARRANGEMENT. EXACT LOCATION, ARRANGEMENT, AND SIZES SHALL BE VERIFIED ON THE JOB BEFORE

STARTING ANY NEW WORK.

COORDINATE THE INSTALLATION OF WORK UNDER THIS DIVISION WITH THAT OF OTHER TRADES TO

PROVIDE THE BEST ARRANGEMENT OF PIPING, DUCTWORK, AND EQUIPMENT.

PIPING, DUCTWORK, AND EQUIPMENT IS SHOWN IN ITS GENERAL LOCATION UNLESS DIMENSIONED.

ARRANGE PIPING AND DUCTWORK TO CLEAR STRUCTURAL MEMBERS, PIPING AND LIGHT FIXTURES.

EXACT LOCATION OF GRILLES AND CEILING OUTLETS SHALL BE DETERMINED ON THE JOBSITE.

COORDINATE WITH LIGHTS, SPRINKLER HEADS, AND OTHER CEILING APPURTENANCES TO PROVIDE A UNIFORM AND SYMMETRICAL APPEARANCE. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS AND

DETAILS.

PROVIDE FLEXIBLE DUCT CONNECTIONS TO ALL AIR HANDLING EQUIPMENT.

HVAC LEGEND

SYMBOL DESCRIPTION

T THERMOSTAT 4'-0" A.F.

c CUBIC FEET PER MINUTEor CFM

M-1 SHEET NO.

DETAIL NO 1/M-1

SUPPLY DIFFUSER

RETURN OR EXHAUST GRILLE

MANUAL VOLUME DAMPERor MVD

AIR DEVICE

NECK CONNECTION SIZE

A

N

E NEW TO EXISTING CONNECTION

SQUARE ELL WITH SINGLE THICK TURNING VANES

WDP

BALANCING VALVE

SEE PLANS FOR SIZES.

MAV

COIL

45 DEGREE

ELBOW (TYP.)

STRAINER WITH

BLOW-OFF VALVE.

2-WAY CONTROL VALVE.

TEMPERATURE/PRESSURE

TEST FITTINGS

PIPE WATER COILS FOR COUNTER-FLOW.

(ENTERING WATER CONTACTS LEAVING AIR.)

UNION OR FLANGE (TYP.)

SHUTOFF VALVE

(TYP.)

DRAIN VALVE WITH

THREADED CAP OR PLUG.

WATER COIL CONN. DETAIL (2-WAY VALVE)

SCHEMATIC

FURNISH FULL SIZED

HEADER FOR COILS WITH

MULTIPLE CONNECTIONS.

X

XXX

LOCATE UNIONS OR FLANGES

TO ALLOW FOR COIL

REMOVAL. (TYP.)

(TYP. FOR TU4-41)

EXIST. HWS&R MAINS,

N E

-- VCCF-1212"ø ----0.0501400TU4-56 (2)

REHEAT CONTROL VALVE X X (1)

(1) TU4-41 ONLY

A COMPLETE SET OF APPROVED PLANS AND

SPECIFICATIONS SHALL BE MAINTAINED

H.V.A.C. SPECIFICATIONS KM

DATE

DRAWING NO.

KEY PLAN:

529 GREENE ST. AUGUSTA, GA. 30901

(706) 736 3333 - FAX (706) 736 7100

This document is property of 2KM Architects, Inc. The unauthorized reproduction, copying, or otherwise use of this document is strictly prohibited and any infringement thereupon may be subject to legal action

Copyright © 2026, 2KM Architects, Inc.

DRAWN BY

PROJECT NO.

PAPER

ISSUE

24"x36"

FOR

DRAWING TITLE

AU-SC UH

ANIMATION LAB.

AUGUSTA

UNIVERSITY

04/10/2026 25-11.03

2500 WALTON WAY, AUGUSTA, GA 30904

100% CD

REVISIONS

# DATE DESCRIPTION

M2.1

HVAC

SPECIFICATIONS

PLOT DATE:

FILENAME:

PLOT SCALE:

AU

G

U

ST

A, G

A

(7

) 7

-3

CO

PY

RI

G

HT

PF

A

EN

G

IN

EE

RI

N G

, I N

C.

04/09/26 25096M1 1 = 48

JBM/WDP

WDP

GENERAL PROVISIONS

1. THE GENERAL REQUIREMENTS OF THIS CONTRACT ARE PROVIDED IN THE ARCHITECTURAL SPECIFICATIONS

IN ADDITION TO THE REQUIREMENTS OF THIS DOCUMENT.

2. MECHANICAL INSTALLATIONS SHALL CONFORM TO THE CURRENT EDITION OF THE FOLLOWING, INCLUDING

ANY STATE AMENDMENTS WHERE APPLICABLE:

a. THE INTERNATIONAL BUILDING CODE.

b. THE INTERNATIONAL MECHANICAL CODE.

c. THE INTERNATIONAL PLUMBING CODE.

d. THE INTERNATIONAL FIRE PROTECTION CODE.

e. THE STATE ENERGY CODE.

f. NFPA STANDARD 70, NATIONAL ELECTRIC CODE.

g. NFPA STANDARD 90A, INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS.

h. NFPA STANDARD 101, CODE FOR SAFETY TO LIFE FOR FIRE IN BUILDINGS AND STRUCTURES.

3. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND INSPECTIONS REQUIRED FOR THE

INSTALLATION OF THIS WORK AND PAY ALL CHARGES INCIDENT THERETO.

4. SUBMITTALS: PROVIDE SUBMITTALS PER THE REQUIREMENTS OF THIS CONTRACT FOR MATERIALS, EQUIPMENT AND SERVICES SPECIFIED HEREIN.

a. ELECTRICAL COORDINATION: IN ADDITION TO SUBMITTAL REQUIREMENTS INCLUDED IN THIS CONTRACT, SUBMIT A DOCUMENT APPROVED BY THE PROJECT ELECTRICAL CONTRACTOR CERTIFYING THAT ALL MECHANICAL EQUIPMENT BEING FURNISHED MECHANICAL COMPLIES WITH THE ELECTRICAL

CHARACTERISTICS OF THE SOURCE POWER WHICH WILL BE FURNISHED UNDER ELECTRICAL.

b. MODEL NUMBERS LISTED ON THE MECHANICAL CONTRACT DOCUMENTS SHALL NOT BE CONSTRUED

TO INDICATE ELECTRICAL CHARACTERISTICS. ELECTRICAL CHARACTERISTICS OF MECHANICAL

EQUIPMENT SHALL BE AS INDICATED ON THE ELECTRICAL CONTRACT DOCUMENTS.

c. REVIEW OF SUBMITTALS DOES NOT RELIEVE THE CONTRACTOR OF ANY OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. FAILURE BY THE ENGINEER TO DOCUMENT ERRORS AND OMISSIONS IN

THE CONTRACTOR'S SUBMITTALS DURING THE ENGINEER'S SUBMITTAL REVIEW DOES NOT

CONSTITUTE A WAIVER OF ANY OF THE REQUIREMENTS OF THE ORIGINAL CONTRACT DOCUMENTS.

5. CONTRACTOR QUALIFICATIONS: HVAC SUBCONTRACTOR SHALL HAVE A CURRENT CLASS II CONDITIONED AIR CONTRACTORS LICENSE FOR THE STATE IN WHICH THE PROJECT IS BEING CONSTRUCTED. THE SUBCONTRACTOR SHALL HAVE AS PART OF THE FIRM A SERVICE DEPARTMENT QUALIFIED TO SERVICE ALL SYSTEMS INSTALLED IN THE PROJECT OR HAVE A WRITTEN AGREEMENT WITH A SERVICE AGENCY QUALIFIED TO PROVIDE SUCH SERVICE. THE SERVICE DEPARTMENT OR AGENCY SHALL BE ON CALL AT ALL HOURS. THE SUBCONTRACTOR SHALL HAVE INSTALLED AT LEAST (WITHIN THE LAST FIVE YEARS) THREE (3)

HYDRONIC WATER SYSTEMS OF AT LEAST 150-TONS IN SIZE.

6. SUBSTITUTION PROCEDURES/PRIOR APPROVAL REQUESTS: REQUESTS FOR THE USE OF MATERIALS OR EQUIPMENT MANUFACTURERS NOT LISTED SHALL BE PER THE REQUIREMENTS OF THIS CONTRACT.

7. LAYOUT AND COORDINATION:

a. THE EQUIPMENT LISTED ON THE DRAWINGS AND IN THE SPECIFICATIONS HAS BEEN USED FOR THE

PHYSICAL ARRANGEMENT OF THE MECHANICAL SYSTEMS. WHEN EQUIPMENT LISTED AS ACCEPTABLE, EQUAL OR EQUIPMENT WHICH HAS RECEIVED "PRIOR APPROVAL" IS USED, IT…

This is the start of the file's text. The full file is on GovTribe.