This is a detailed engineering design document for the City of Thousand Oaks Municipal Service Center Generator Replacement project, prepared by KEWO Engineering Corporation. The project involves replacing an existing 60kW natural gas generator with a new 120kW natural gas generator and installing a new 120/208V service switchboard at the Municipal Service Center located at 1993 Rancho Conejo Boulevard. The design includes comprehensive plans for demolition of existing equipment, new site layout, electrical and gas piping configurations, foundation details, and conduit plans. The design is a 100% design submittal following multiple California building, electrical, and energy codes, including the 2022 California Building Code, California Electrical Code, and South Coast AQMD Rule 1110.2.
The project scope includes removing the existing generator, gas meter, and associated infrastructure, and installing a new generator with enhanced capacity, a new switchboard with features like load sharing, synchronizing, motorized circuit breakers, and paralleling controls. The design also provides for future battery energy storage system (BESS) infrastructure, with conduit stubouts and space allocation. The new generator will have a 120kW/150kVA capacity with 1800 CFH natural gas consumption, and the switchboard will be a 1600A, 120/208V, 3-phase, 4-wire system with 65kAIC rating. The design emphasizes coordination with Southern California Edison, SoCalGas, and adherence to strict engineering and safety standards, including seismic considerations and utility interface requirements.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET INDEX
SHT. NO. DESCRIPTION
NOTICE TO CONTRACTOR:
NOTICE TO CONTRACTOR:
CONTRACTOR SHALL POSSES A VALID CLASS "A" GENERAL ENGINEERING LICENSE
LESS THAN TWO DAYS NOR MORE THAN SEVEN DAYS PRIOR TO CONSTRUCTION.
UNDERGROUND ALERT FOR LOCATION OF EXISTING UNDERGROUND UTILITIES NO
IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO CALL THE USA
TO EXISTING UTILITIES DURING CONSTRUCTION
THE CONTRACTOR SHALL ASSUME SOLE RESPONSIBILITY FOR ANY DAMAGE DONE
VICINITY MAP
NO SCALE
PUBLIC WORKS DEPARTMENT
101 FREEW
AY
FR
EEW
A Y
F R
E E
W A
Y
R D
RD.
R D
W
ES
TL
AK
E
RD.
OAKS
OLS
EN
RD.
E R
B E S
M O
O R
P A
R K
BLVD.
LYNN
RD.
LYN
N
HILLCREST
DR.
HILLCREST
D R
THOUSAND
BLVD.
BORCHARD
RD.
R
AN
C H
O
C O
N E J
O B
L V
D
KANAN
R D
J A
N S S
ARBOLES
AVENIDA
DE
LOS
R E
IN
O
R D
W E
N D
Y D
R
POTRERO
RD.
CITY COUNCIL
CITY ENGINEER
PUBLIC WORKS DIRECTOR
MIKE TAYLOR
CITY MANAGER
ANDREW P. POWERS
PROJECT
SITE
AL ADAM
C. TIE GUTIERREZ
BOB ENGLER
DAVID NEWMAN, MAYOR
TITLE SHEET
GENERAL NOTES
CONDUIT PLAN
PROJECT SITE
PUBLIC UTILITIES WITHIN CITY OF THOUSAND OAKS
WATER:
WASTEWATER:
TELEPHONE:
GAS:
CABLE TV:
FIBER:
ELECTRICITY:
NADER HEYDARI
TED GERBER
NO SCALE
SITE MAP
805- 432-5750
EMANUAL BARAJAS
NEWBURY PARK, CA 91320
2439 W HILLCREST DRIVE
CALIFORNIA AMERICAN WATER
805-449-5033
PATRICK McCULLOCH
THOUSAND OAKS, CA 91362
2100 EAST THOUSAND OAKS BOULEVARD
CITY OF THOUSAND OAKS
805-445-9116
CAMARILLO, CA 93012
201 FLYNN ROAD
JASON EISEL
FRONTIER
213-231-5629
BEN PENA
SIMI VALLEY, CA 93065
977 CHAMBERS LANE
SOUTHERN CALIFORNIA GAS COMPANY
805-494-7013
BOB MIGLIORE
THOUSAND OAKS, CA 91361
3589 FOOTHILL DRIVE
SOUTHERN CALIFORNIA EDISON COMPANY
800-654-3110
FIBER DIG
CANONSBURG, PA 15317
1500 CORPORATE DRIVE
CROWN CASTLE FIBER
805-626-8231
ERIC PINGREE
VENTURA, CA 93003
2525 KNOLL DRIVE
SPECTRUM
EXISTING SITE PLAN - DEMOLITION
NEW SITE PLAN7
NATURAL GAS PIPING PLAN10
FOUNDATION DETAILS11
EXISTING AERIAL - DEMOLITION
SINGLE LINE DIAGRAM - DEMOLITION
SINGLE LINE DIAGRAM - NEW
MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
1993 RANCHO CONEJO BLVD
ELEVATIONS & DETAILS
CI 5585
SPECIFICATION NO. 2025/2026 - 01
SHEET 1 OF 11
TITLE SHEET
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
PROJECT AREA PROJECT DESCRIPTION
GENERAL NOTES
GENERAL
MATERIALS AND EQUIPMENT
CONDUIT TRENCHING
AREA
PROJECT
PROPERTY INFORMATION
APPLICABLE CODES AND STANDARDS
THOUSAND OAKS, CA 91320
1993 RANCHO CONEJO BLVD.ADDRESS:
AREA
PROJECT
ORDERING ANY MATERIALS OR EQUIPMENT.
CONTRACTOR SHALL PROVIDE SUBMITTALS BEFORE 3.
OCCUPATIONAL SAFETY HEALTH ADMINISTRATION (OSHA).
LABORATORY (NRTL) ACCREDITED BY THE UNITED STATES
OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING
ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, 2.
OTHERWISE NOTED.
AND FURNISHED AND INSTALLED BY CONTRACTOR UNLESS
ALL WORK/MATERIALS SHOWN ON PLANS SHALL BE NEW 1.
CONTRACTOR SHALL MAINTAIN A CLEAN WORKSITE.8.
CONSTRUCTION.
STRUCTURES DAMAGED BY THE CONTRACTOR DURING
CONTRACTOR’S EXPENSE, ANY EQUIPMENT OR
CONTRACTOR SHALL REPAIR AND/OR REPLACE, AT 7.
JURISDICTION FOR ANY INSPECTIONS.
CONTRACTOR SHALL NOTIFY AUTHORITY HAVING 6.
ORDINANCES, AND REQUIREMENTS.
COMPLETED IN ACCORDANCE WITH APPLICABLE CODES,
CONTRACTOR SHALL ENSURE THAT ALL WORK IS 5.
PERMIT HAS BEEN ISSUED.
NOT AUTHORIZE ANY WORK TO BE PERFORMED UNTIL A
APPROVAL OF THESE PLANS BY THE CITY ENGINEER DOES 4.
IMPROVEMENTS.
PRIOR TO CONSTRUCTION OF THE PROPOSED
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS 3.
FOR THE FITTING OF ALL EQUIPMENT AND MATERIALS.
CLEARANCES AND SHALL ASSUME FULL RESPONSIBILITY
AND VERIFY ALL DIMENSIONS, SIZES, AND REQUIRED
APPROXIMATE. CONTRACTOR SHALL CAREFULLY CHECK
ALL EQUIPMENT LOCATIONS ON DRAWINGS ARE 2.
REGULATIONS AND/OR BUILDING CODES.
CONTRACTOR FROM COMPLYING WITH THE LAWS,
AND/OR DESIGN INFORMATION THAT PREVENTS
THE DRAWINGS, SPECIFICATIONS, AND FIELD CONDITIONS;
ENGINEER OF RECORD OF ANY DISCREPANCIES BETWEEN
CONTRACTOR SHALL IMMEDIATELY NOTIFY OWNER AND 1.
DAMAGING ANY UTILITY LINE.
INSTALLATION OF THE ELECTRICAL EQUIPMENT TO AVOID
HAND DIG ALL UTILITIES IN CLOSE PROXIMITY TO THE 6.
NATIVE BACKFILL OR 2-SACK SLURRY.
BACKFILL WITH 95% MINIMUM RELATIVE COMPACTED 5.
CONDUIT.
INSTALL METALLIC WARNING TAPE MINIMUM 12” ABOVE 4.
INSTALLATIONS AND RATED FOR 90°C CONDUCTORS.
UNLESS OTHERWISE NOTED, LISTED FOR UNDERGROUND
UNDERGROUND CONDUITS SHALL BE PVC SCHEDULE 40, 3.
CONDUIT BURIAL DEPTH SHALL BE 24”.
REQUIREMENTS PURSUANT TO CEC 300.5. MINIMUM
TRENCHING SHALL COMPLY WITH MINIMUM COVER 2.
ANY EXCAVATION.
ALERT (USA) TWO (2) WORKING DAYS PRIOR TO BEGINNING
CONTRACTOR SHALL NOTIFY UNDERGROUND SERVICE 1.
DISTRIBUTION AND BRANCH CIRCUITRY SYSTEM.
SHALL NOT EXCEED 5% WITHIN THE ENTIRE ELECTRICAL
BUILDING CODE. THE MAXIMUM FEEDER VOLTAGE DROP
VOLTAGE DROP SHALL COMPLY WITH 2022 CEC AND LOCAL 6.
UNLESS OTHERWISE NOTED.
ALL CABLES SHALL BE THHN/THWN-2 OR XHHW-2 90°C, 5.
UNLESS OTHERWISE NOTED.
BASED ON THHN/THWN-2 AND XHHW-2 COPPER CABLES,
ALL CONDUIT SIZES AND CONDUCTOR AMPACITIES ARE 4.
ALL NEW STUB CONDUITS SHALL HAVE BUSHING ON END.3.
CABLES.
NECESSARY TO FACILITATE PULLING AND INSTALLATION OF
INSTALL CONDULETS AND INTERMEDIATE PULLBOXES AS 2.
NOT SUBJECT TO PHYSICAL DAMAGE.
EMT CONDUITS ALLOWED FOR ALL OTHER EXPOSED AREAS
AREAS SUBJECT TO PHYSICAL DAMAGE, SHALL BE GRC.
EXPOSED CONDUITS ALONG FLOOR SURFACE, OR ANY 1.
INSTALL SPARE CONDUTIS FROM (N) SWITCHBOARD 'MSA' FOR FUTURE BESS.9.
INSTALL NEW CABLES FROM (N) GENERATOR TO (E) ATS.8.
INSTALL NEW CABLES FROM (N) GENERATOR TO (N) SWITCHBOARD 'MSA'.7.
INTERCEPT (E) CONDUITS TO (E) SWITCHBOARD 'MSB' AND ROUTE TO (N) SWITCHBOARD 'MSA'.6.
COORDINATE WITH SCE AND INTERCEPT (E) SERVICE CONDUITS. INSTALL NEW CONDUITS AND CABLES TO (N) SERVICE SWITCHBOARD 'MSA'.5.
INTERCEPT EXISTING CONDUITS FROM (E) SCE TRANSFORMER AND INSTALL FEEDER FROM (N) SWITCHBOARD 'MSA' TO (E) SWITCHBOARD 'MSB'.4.
PROCURE AND INSTALL (N) 120/208V 1600A SERVICE SWITCHBOARD 'MSA' AND ASSOCIATED FOUNDATION, CONDUITS, AND CABLES.3.
COORDINATE WITH SOCALGAS AND REPLACE GAS REGULATOR AND METER, AS NEEDED, PER SOCALGAS REQUIREMENTS.2.
PROCURE AND INSTALL (N) 120KW NATURAL GAS GENERATOR AND ASSOCIATED FOUNDATION, GAS PIPING, CONDUITS, AND CABLES.1.
INSTALL:
REMOVE EXISTING CURB ALONG NORTH.2.
REMOVE (E) 60KW NATURAL GAS GENERATOR AND ASSOCIATED FOUNDATION, GAS PIPING, AND CABLES.1.
REMOVE:
REPLACE EXISTING 60KW NATURAL GAS GENERATOR WITH NEW 120KW NATURAL GAS GENERATOR; AND INSTALL NEW 120/208V SERVICE SWITCHBOARD.
SOUTH COAST AQMD RULE 1110.2
NFPA 37
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN)
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA ELECTRICAL CODE (CEC)
2022 CALIFORNIA BUILDING CODE (CBC)
2022 CALIFORNIA ADMINISTRATIVE CODE
SHEET 2 OF 11
GENERAL NOTES
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
G N
SWBD 'MSB', 1600A, 120/208V, 3PH-4W, 65KAIC
16KV
SCE UTILITY SERVICE
M
G
120/208V, 3PH 4W
60KW
NATURAL GAS
BACKUP GENERATOR
PNL 'E'
A
A
600A
3PH-4W
480Y/277V
600A
'DPV-1'
50KW
'INV-1'
50KW
'INV-2'
50KW
'INV-3'
50KW
'INV-4'
50KW
'INV-5'
33KW
'INV-6'
359.1KW-DC, 855 MODULES
MISSION SOLAR, MSE-420-SX6W (420W)
283KW-AC, 480VAC, 1000VDC
SMA SUNNY TRIPOWER CORE1
480Y/277V, 3PH-4W
208V 3PH-3W
500KVA
'XFMR-1'
1600AS/1400AF
208VAC
'ADC-1'
SOLAR PV CARPORT
ATS
CABLES TO ATS.
REMOVE AND REPLACE EXISTING GENERATOR 2.
'MSA'.
INTERCEPT CONDUITS FOR NEW SWITCHBOARD
TRANSFORMER AND SWITCHBOARD 'MSB'.
REMOVE EXISTING CABLES BETWEEN SCE 1.
CONDUITS & CABLES
REPLACE POWER AND CONTROL CABLES.-
REUSE ATS WITH NEW GENERATOR.-
(E) AUTOMATIC TRANSFER SWITCH, CUMMINS3.
#259000-081080.
SCE TO REMOVE EXISTING METER -
REMOVE NEUTRAL-GROUND BONDING JUMPER.-
(E) SWITCHBOARD 'MSB'.2.
ASSOCIATED CABLES & WIRING.
REMOVE EXISTING GENERATOR AND -
(E) STANDBY GENERATOR, NATURAL GAS, 60KW1.
EQUIPMENT
16KV-120/208V
XFMR
SCE
SHEET 3 OF 11
SINGLE LINE DIAGRAM - DEMOLITION
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
16KV
SCE UTILITY SERVICE
G N
A
SWBD 'MSB', 1600A, 120/208V, 3PH-4W, 65KAIC
G
M
G N
SPD
SWBD 'MSA', 1600A, 120/208V, 3PH-4W, 65KAIC
UGPS MTR & MAIN DISTRIBUTION
A
FUTURE BESS
[F U
T
480V
500KWH
[FUT] BESS
480-120/208V
[FUT] 'XFMR-B'1800 CFH
120/208V, 3PH 4W
120KW/150KVA
NATURAL GAS
STANDBY GENERATOR
PNL 'E'
600A
3PH-4W
480Y/277V
600A
'DPV-1'
50KW
'INV-1'
50KW
'INV-2'
50KW
'INV-3'
50KW
'INV-4'
50KW
'INV-5'
33KW
'INV-6'
359.1KW-DC, 855 MODULES
MISSION SOLAR, MSE-420-SX6W (420W)
283KW-AC, 480VAC, 1000VDC
SMA SUNNY TRIPOWER CORE1
480Y/277V, 3PH-4W
208V 3PH-3W
500KVA
'XFMR-1'
1600AS/1400AF
208VAC
'ADC-1'
A
SOLAR PV CARPORT
CLOSE
REMOTE
1600A
CONT.
GEN
CONT.
MG
CONT.
MG
A
A
ATS
A
ONLY BE AT NEW SWBD 'MSA'.
NEUTRAL-GROUND BONDING JUMPER SHALL -
NEC REQUIREMENTS.
INSTALL TWO (2) GROUNDING ELECTRODES PER -
GROUNDING SYSTEM.4.
REPLACE POWER AND CONTROL CABLES.-
REUSE ATS WITH NEW GENERATOR.-
(E) AUTOMATIC TRANSFER SWITCH, CUMMINS3.
REQUIREMENTS.
CLOSED-TRANSITION AND ISLANDING
COORDINATE WITH SCE FOR -
ENERGY REDUCTION MAINTENANCE SWITCH-
SHUNT TRIP CIRCUIT BREAKERS FOR SWBD 'MSB'-
REMOTE CLOSE/OPEN MAIN CIRCUIT BREAKER-
1600A, 120/208V, 3PH-4W, 65KAIC
SWITCHBOARD 'MSA'2.
LOAD SHARING-
SYNCHRONIZING-
MOTORIZED CIRCUIT BREAKER-
PARALLELING CONTROLS-
SEISMIC BRACING-
WEATHER PROTECTED ENCLOSURE-
0.8PF, 120/208V, 3PH-4W, 1800CFH
STANDBY GENERATOR, NATURAL GAS, 120KW, 1.
EQUIPMENT
S H
U N
T T
R
IP
A
S P
A C
E
INTERCEPT EXISTING CONDUITS.
(3) 4"C: SPARE
(3) 4"C: 4#400 + 1#2/0 GND7.
(1) 1": ATS CONTROLS
(1) 2": 4#2/0 + 1#4GND 6.
(4) 4"C: FUTURE BESS. CAP BELOW GROUND.5.
(1) 1"C: CONTROLS & COMMS4.
(2) 1"C: AUX POWER3.
(2) 4"C: 4#300 + 1#1 GND2.
(6) 4"C: PER SCE1.
CONDUITS & CABLES
16KV-120/208V
XFMR
SCE
200A
120/208V
PNLBD
SHEET 4 OF 11
SINGLE LINE DIAGRAM - NEW
D
IS
T M
A
IN
M E
T E
R
U G
P S
P N
L E
EX. CONDUITS TO SCE
EX. (6) 4"C TO SWBD 'MSB'
EX. 2" NAT GAS PIPE
EX. 1" NAT GAS PIPE
EX. 2"C TO ATS
GAS SEWER
SEWER
SEWER
WATER
COMM
AIRCOMM
COMM
COMM
EX. STRIPING
EX. GUTTER
SCALE: 1/4" = 1'
5 10
LIGHTING
ELECTRICAL
LIGHTING
LIGHTING
ELECTRICAL
ELECTRICAL
ELECTRICAL
A T S
9'-0"19'-0"
(E) BOLLARDS
ELECTRICAL CONDUITS. REFER TO NEW SITE PLAN.
NORTH. PROTECT IN PLACE EXISTING GAS PIPE AND
PAVEMENT. CURB ISLAND WILL BE EXTENDED 9FT
REMOVE NORTH CURB, BOLLARDS AND ACC 5.
SEE NEW CONDUIT PLAN.
CONDUIT WILL BE INTERCEPTED BY (N) SWBD 'MSA'.
REMOVE PORTION OF CONDUIT TO TRANSFORMER. 4.
TO AUTOMATIC TRANSFER SWITCH.
REMOVE AND REPLACE CABLES FROM GENERATOR 3.
THROAT STABILIZER
1.5" NPT PORT, 5"-9" WC, 3/4" ORIFICE,
BELGAS REGULATOR #P202S-14-009-0-B-4-D-0-
PSIG, 1200 kPa
#053141-001, 1500 CFH MAX, 42.5 m/h MAX, 175
DRESSER ROOTS GAS METER #15C175, B/M
GAS METER #16183365-
REMOVE GAS METER, REGULATOR AND PIPING.2.
CUMMINS ONAN #60ENA
PULLBOX SHALL BE PROTECTED IN PLACE.
ELECTRICAL CONDUIT AND WIRING. ADJACENT
GENERATOR, CONCRETE FOUNDATION, GAS PIPING,
REMOVE 60KW/75KVA, 120/208V NATURAL GAS 1.
NOTES:
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET 5 OF 11
EXISTING SITE PLAN - DEMOLITION
D
IS
T M
A
IN
M E
T E
R
U G
P S
P N
L E
EX. CONDUITS TO SCE
EX. (6) 4"C TO SWBD 'MSB'
EX. 2" NAT GAS PIPE
EX. 1" NAT GAS PIPE
EX. 2"C TO ATS
GAS SEWER
SEWER
SEWER
WATER
COMM
AIRCOMM
COMM
COMM
EX. STRIPING
EX. GUTTER
SCALE: 1/4" = 1'
5 10
LIGHTING
ELECTRICAL
LIGHTING
LIGHTING
ELECTRICAL
ELECTRICAL
ELECTRICAL
A T S
9'-0"19'-0"
(E) BOLLARDS
ELECTRICAL CONDUITS. REFER TO NEW SITE PLAN.
NORTH. PROTECT IN PLACE EXISTING GAS PIPE AND
PAVEMENT. CURB ISLAND WILL BE EXTENDED 9FT
REMOVE NORTH CURB, BOLLARDS AND ACC 5.
SEE NEW CONDUIT PLAN.
CONDUIT WILL BE INTERCEPTED BY (N) SWBD 'MSA'.
REMOVE PORTION OF CONDUIT TO TRANSFORMER. 4.
TO AUTOMATIC TRANSFER SWITCH.
REMOVE AND REPLACE CABLES FROM GENERATOR 3.
THROAT STABILIZER
1.5" NPT PORT, 5"-9" WC, 3/4" ORIFICE,
BELGAS REGULATOR #P202S-14-009-0-B-4-D-0-
PSIG, 1200 kPa
#053141-001, 1500 CFH MAX, 42.5 m/h MAX, 175
DRESSER ROOTS GAS METER #15C175, B/M
GAS METER #16183365-
REMOVE GAS METER, REGULATOR AND PIPING.2.
CUMMINS ONAN #60ENA
PULLBOX SHALL BE PROTECTED IN PLACE.
ELECTRICAL CONDUIT AND WIRING. ADJACENT
GENERATOR, CONCRETE FOUNDATION, GAS PIPING,
REMOVE 60KW/75KVA, 120/208V NATURAL GAS 1.
NOTES:
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET 6 OF 11
EXISTING AERIAL - DEMOLITION
LOCATION
BESS
[FUT]
SCALE: 1/4" = 1'
5 10
U G
P S
M A
IN
M E
T E
R D
IS
T D
IS
T
A T S
28'-0"
TYP.
D
IS
T M
A
IN
M E
T E
R
U G
P S
P N
L E
BACKFILL AREA WITH COMPACTED SOIL.-
PLANTER CURB DETAIL. SEE SHEET 9 DETAIL 3.
REFER TO CITY STANDARD PLATE NO. 8-2 FOR -
MATCH EXISTING CURB.-
CURBED ISLAND. EXTEND NORTH 9-FT.6.
MATCHING BOLLARD COVERS.
AND MATCH EXISTING SPACING. INSTALL
6" BOLLARDS. LOCATE BOLLARDS AS REQUIRED 5.
REPLACE POWER AND CONTROL CABLES.-
REUSE ATS WITH NEW GENERATOR.-
(E) AUTOMATIC TRANSFER SWITCH, CUMMINS4.
CLEARANCES TO ADJACENT EQUIPMENT.
REQUIRED ELECTRICAL AND WORKING
VALVE, AND PIPING AS NECESSARY TO PROVIDE
MECHANICAL DRAWINGS. RELOCATE GAS METER,
INSTALL NEW GAS METER, VALVE, AND PIPING. SEE 3.
LOAD SHARING-
SYNCHRONIZING-
MOTORIZED CIRCUIT BREAKER-
PARALLELING CONTROLS-
SEISMIC BRACING-
WEATHER PROTECTED ENCLOSURE-
0.8PF, 120/208V, 3PH-4W, 1800CFH
STANDBY GENERATOR, NATURAL GAS, 120KW, 2.
LSIG-
ENERGY REDUCTION MAINTENANCE SWITCH-
ELECTRICALLY OPERATED CIRCUIT BREAKERS-
1600A, 120/208V, 3PH-4W, 65KAIC
SWITCHBOARD 'MSA'1.
EQUIPMENT
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET 7 OF 11
NEW SITE PLAN
(6) 4"C
2" NAT GAS
P N
L E
U G
P S
M A
IN
M E
T E
R
D
IS
T
EX. CONDUITS TO SCE
1"C CONTROLS
(2) 1"C AUX PWR
(2) 4"C PWR
(2) 1"C
(4) 4"C
GAS SEWER
SEWER
SEWER
WATER
COMM
AIRCOMM
COMM
COMM
SCALE: 1/4" = 1'
5 10
U G
P S
M A
IN
M E
T E
R D
IS
T D
IS
T
LIGHTING
LIGHTING
LIGHTING
ELECTRICAL
EX. STRIPING
EX. GUTTER
EX. 1" NAT GAS PIPE
EX. (6) 4"C TO SWBD 'MSB'
EX. 2"C TO ATS
ELECTRICAL
ELECTRICAL
ELECTRICAL
A T S
(E) BOLLARDS
LOCATION
BESS
[FUT]
1"C CTL
2"C PWR
(6) 4"C
COMMUNICATIONS.
480V POWER, 120V AUX, CONTROLS &
CONDUITS FOR FUTURE BESS.4.
ROOM.
PNL 'E' VIA (E) 2"C FROM PULLBOX TO ELECTRICAL
PULLBOX. CONDUIT WILL BE UTILIZED TO FEED (E)
INSTALL (N) 2"C FROM (N) GENERATOR TO (E) 3.
SWBD 'MSA' WILL FEED (E) SWBD 'MSB'.
INTERCEPT CONDUITS FROM (E) SWBD 'MSB'. (N) 2.
ROUTING.
WITH SCE FOR CONDUIT REQUIREMENTS AND
TRANSFORMER TO (N) SWBD 'MSA'. COORDINATE
INTERCENT CONDUITS FROM UTILITY 1.
NOTES:
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET 8 OF 11
CONDUIT PLAN
120 KW
GENERATOR
NAT GAS
1 2ELEVATION (VIEW NORTH)ELEVATION (VIEW WEST)
120 KW
GENERATOR
NAT GAS
SCALE: 1/4" = 1' SCALE: 1/4" = 1'
XFMR
SCESWBD 'MSA'
3MEDIAN / PLANTER CURB STANDARD
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
No. E19688
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
L A
CIRTC
E
L
E
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET 9 OF 11
ELEVATIONS & DETAILS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
No. M37237
L A
CINAH
C
E
M
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
REGULATOR
FROM GAS UTILITY
G
1.5" 1.5"
1.5"
1"
1.5"
2"
1.5"
1"
2"
FROM GAS UTILITY
NEW NATURAL GAS RISER NEW NATURAL GAS PIPING PLAN
(N) METER
(N) SEISMIC GAS SHUT-OFF
(N) 2" NAT GAS PIPE MIN 24" BELOW GRADE
(N) 2" NAT GAS PIPE
(N) METER
(N) 2" NAT GAS PIPE MIN 24" BELOW GRADE
(N) 2" NAT GAS PIPE
(N) FLEXIBLE GAS PIPE
(N) FLEXIBLE GAS PIPE
(N) SEISMIC GAS SHUT-OFF
COORDINATE WITH GAS UTILITY FOR REQUIRED SIZE.
PACIFIC SEISMIC PRODUCTS #303/314, OR EQUAL.
SOUTH COAST AQMD RULE 1110.2-
NFPA 37-
2022 CALIFORNIA ENERGY CODE-
2022 CALIFORNIA PLUMBING CODE-
2022 CALIFORNIA ELECTRICAL CODE-
2022 CALIFORNIA BUILDING CODE-
CODE SUMMARY:
PROTECT IN PLACE EXISTING GAS LINE TO REMAIN.7.
SUBSTITUTIONS OF EQUIPMENT AND MATERIALS.
COORDINATION OF ALL MANUFACTURER
CONTRACTOR SHALL BE RESPONSBILE FOR THE 6.
INTERFERENCE WITH ELECTRICAL EQUIPMENT.
ALL NATURAL GAS PIPING SHALL AVOID 5.
PLACING OF EQUIPMENT AND PIPING.
CONTRACTOR IS RESPONSIBLE FOR THE CORRECT
GENERAL LOCATION OF EQUIPMENT AND PIPING.
THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW 4.
AND PROJECT MAANGER PRIOR TO CONSTRUCTION.
ALL UNDERGROUND PIPING WITH THE ENGINEER
CONTRACTOR SHALL COORDINATE PLACEMENT OF 3.
TO CONSTRUCTION.
PROJECT MANAGER OF ANY DISCREPANCIES PRIOR
AND IMMEDIATELY NOTIFY THE ENGINEER AND
LOCATIONS AND ELEVATIONS OF IMPROVEMENTS
CONTRACTOR SHALL FIELD VERIFY EXACT 2.
LOAD AND REQUIRED PRESSURE.
REGULATOR SIZE TO MEET TOTAL CONNECTED
UTILITY PROVIDER FOR REQUIRED GAS METER AND
CONTRACTOR SHALL COORDINATE WITH GAS 1.
GENERAL NOTES
SCALE: 1/2" = 1'
(E) LIGHT POLE
(E) BOLLARD
(E) ELEC PULLBOX
LOCATION
BESS
[FUT]
INLET WITHIN 24" OF INLET, IF REQUIRED
REDUCE GAS PIPING TO MATCH GENERATOR
NOTE:
MIN CAPACITY: TBD BY CONTRACTOR
REGULATOR
LOCATION.
PROVIDE TRACER WIRE TERMINATED IN ACCESSIBLE 4.
OR 6" SEPARATION IF PERPENDICULAR.
SEPARATION FROM ELECTRICAL WHEN PARALLEL
BURRY MINIMUM 24" BELOW GRADE. MAINTAIN 18" 3.
ASTM A53 SCHEDULE 40 STEEL.
GROUND PE TRANSITION FITTING TO THREADED
CASING VENTED ABOVE GRADE. PROVIDE ABOVE
INLET. ASTM A53 SCHEDULE 40 BLACK STEEL
FACTORY FABRICATED AND LEAK TESTED, SDR 11
ANODELESS SERVICE-LINE RISERS:2.
DIMENSIONS.
(ASTM 2683) OR BUTT FUSION TYPE MATCHING PIPE
ASTM D2513 POLYETHYLENE WITH SOCKET FUSION 1.
BELOW GRADE NATURAL GAS PIPING:
COATED.
HANGERS SHALL BE HOT DIPPED GALVANIZED
SHALL BE COMPATIBLE WITH PIPING. EXTERIOR
MAXIMUM 8-FOOT INTERVALS. HANGER MATERIAL
PIPING 2" AND SMALLER SHALL BE SUPPORTED AT
HANGERS/SUPPORTS:5.
INCLUDE TAMPERPROOF LOCKING FEATURE.
PRESSURE RATING. EXTERIOR VAVLES SHALL
B16.33 AND IAS-LISTED BRONZE BODY AND 125 PSIG
NPS 2" AND SMALLER SHALL COMPLY WITH ASME
VALVES:4.
GASES INSIDE THE PIPE MATERIALS.
RESISTANT TO CHEMICAL CONSTITUENTS OF THE
SEAL THREADED JOINTS WITH NON-HARDENING &
ASME B1.20.1
THREADED ENDS:3.
GROUND JOINT AND THREADED ENDS.
ASME B16.39 CLASS 150 MALLEABLE IRON WITH
UNIONS:2.
PROTECTION.
EPOXY PAINT, OR EQUAL MEANS FOR CORROSION
PRIMED AND PAINTED WITH TWO COATS OF YELLOW
EXPOSED SCHEDULE 40 STEEL PIPE SHALL BE
TAPE RATED FOR NATURAL GAS. ALL EXTERIOR
FOR THREADED FITTINGS USE JOINT COMPOUND OR
MALLEABLE IRON THREADED FITTINGS.
ASTM A53 SCHEDULE 40 BLACK STEEL PIPING WITH 1.
ABOVE GRADE GAS PIPING:
NATURAL GAS PIPING PLAN
SHEET 10 OF 11
120 KW
GENERATOR
NAT GAS
1 SCALE: 1/4" = 1' 2GENERATOR FOUNDATION DETAIL SWITCHBOARD FOUNDATION DETAIL
12'-0"
SCALE: 1" = 1'
C O
V E
R C
O N
C
M
IN
GENERATOR
C O
V E
R C
O N
C
M
IN
PRINCIPAL REINFORCING
TIE OR STIRRUP
MAX OFFSET BEND
NOTE: ALL BENDS SHALL BE MADE COLD
GOVERNING EDITION.
ACI-318 CODE
NOTE: FOR D ETC SEE
6d (3" MIN)
(2.5" MIN)
4d
Dd d
D d
D
4BAR BENDS
12'-0"
FOR ACTUAL DIMENSIONS
REFER TO MANUFACTURER DRAWINGS
CONDUIT STUB-UP AREA
C
PAD
C
PAD
FOR ACTUAL DIMENSIONS
REFER TO MANUFACTURER DRAWINGS
CONDUIT STUB-UP AREAS
CONCRETE.
SECURED IN POSITION PRIOR TO PLACING
OTHER CONCRETE INSERTS SHALL BE WELL
ALL REINFORCING BARS, ANCHOR BOLTS AND 7.
CONCRETE NOT TO EXCEED 115 PCF.
ASTM C-330. DRY WEIGHT OF LIGHTWEIGHT
CONCRETE AGGREGATES SHALL CONFORM TO
CONFORM TO ASTM C-33. LIGHT WEIGHT
NORMAL WEIGHT CONCRETE AGGREGATES SHALL 6.
C-150, TYPE I OR TYPE II, LOW ALKALI.
PORTLAND CEMENT SHALL CONFORM TO ASTM 5.
28 DAYS.
MINIMUM COMPRESSIVE STRENGTH of 4000 PSI AT
ALL STRUCTURAL CONCRETE SHALL HAVE A 4.
ACI 304 AND CONTRACT DOCUMENTS.
PLACEMENT OF CONCRETE SHALL CONFORM TO 3.
CONFORM TO C-94.
CONCRETE MIXING OPERATION, ETC., SHALL 2.
MODIFICATIONS AS NOTED.
REINFORCED CONCRETE, ACI 318, WITH
THE 'BUILDING CODE REQUIREMENTS FOR
CONCRETE CONSTRUCTION SHALL CONFORM TO
ALL PHASES OF WORK PERTAINING TO THE 1.
CONCRETE
SHOWN IN APPROVED DETAILS.
PROVIDE MINIMUM EMBEDMENT OF ANCHORS AS 4.
ANCHOR LOCATIONS.
LOCATE REINFORCEMENT AND CONFIRM FINAL 3.
RECOMMENDATIONS.
REPORT AND PER MANUFACTURER'S
INSTALLED IN ACCORDANCE WITH EVALUATION
ANCHORS INSTALLED INTO CONCRETE SHALL BE 2.
LOCATIONS ON ENCLOSURE PRIOR TO INSTALLING.
FIELD VERIFY AND MEASURE EXACT ANCHOR 1.
ANCHORS
WITHOUT OWNER'S REPRESENTATIVE'S APPROVAL.
CONSTRUCTION DOCUMENTS ARE NOT ALLOWED
PRODUCTS OR MATERIALS SPECIFIED ON THE
PROCEEDING WITH THE WORK. SUBSTITUTIONS OF
REPRESENTATIVE FOR REVIEW/APPROVAL BEFORE
DRAWINGS SHALL BE SUBMITTED TO THE OWNER'S
ANY DEVIATION FROM THE APPROVED SET OF 7.
PROCEEDING WITH THE WORK.
WITH THE OWNER'S REPRESENTATIVE BEFORE
CONFLICTS ON THE CONSTRUCTION DOCUMENTS
THE CONTRACTOR SHALL RESOLVE ANY 6.
IMPACT THE WORK.
CONDITIONS AND PHYSICAL SURROUNDINGS WILL
DETERMINE THE EXTENT TO WHICH THOSE
SCOPE OF WORK TO EXISTING CONDITIONS AND
SCOPE OF WORK. VISIT THE SITE TO RELATE THE
DRAWINGS TO IDENTIFY THE EXTENT OF THE
CONTRACTOR SHALL CAREFULLY REVIEW THE 5.
LAYOUT AND OPENINGS.
MANUFACTURER EQUIPMENT DRAWINGS FOR
REFERENCE ELECTRICAL CONDUIT DRAWINGS AND 4.
SCALED DRAWINGS.
DIMENSIONS SHALL TAKE PRECEDENCE OVER 3.
FROM THE OWNER'S REPRESENTATIVE.
FROM THE DESIGN WITHOUT WRITTEN DIRECTION
THE OWNER'S REPRESENTATIVE. DO NOT DEVIATE
CONFLICT WITH THE CONTRACT DOCUMENTS TO
OF ACCURACY. REPORT CONDITIONS THAT
PRESENT KNOWLEDGE, BUT WITHOUT GUARANTEE
TO EXISTING CONDITIONS REPRESENTS THE
INFORMATION SHOWN ON THE DRAWINGS RELATED 2.
DISCREPANCIES OR INCONSISTENCIES.
REPRESENTATIVE SHALL BE NOTIFIED OF ANY
PRIOR TO CONSTRUCTION. THE OWNER'S
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS 1.
GENERAL NOTES:
THE FINAL IN-PLACE INSPECTION IS MADE.
ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN 7.
ALL REINFORCING BAR BENDS SHALL BE MADE COLD.6.
FACILITATE FIELD PLACEMENT OF REINFORCING STEEL AND CONCRETE.
TYPICAL CONDITIONS THAT ARE PROPOSED IN PLACEMENT DRAWINGS TO
CONTRACTOR SHALL NOTIFY ENGINEER OF ANY ADJUSTMENTS FROM 5.
TRADE STANDARDS.
COVERAGE REQUIRED BY STRUCTURAL DETAILS, APPLICABLE CODE AND
QUANTITY, SPACING, SIZE, CLEARANCES, LAPS, INTERSECTIONS AND
PREPARE DETAILED PLACEMENT DRAWINGS OF ALL CONDITIONS SHOWING
DRAWINGS SHOW TYPICAL REINFORCING CONDITIONS. CONTRACTOR SHALL 4.
KSI, OR EQUIVALENT.
REINFORCING STEEL IN FOUNDATIONS SHALL CONFORM TO ASTM A615, 60 3.
EQUIPMENT.
ANCHORS. MEASURE AND VERIFY EXACT ANCHOR LOCATIONS ON
CONTRACTOR SHALL DETAIL AND PLACE REINFORCING STEEL TO AVOID 2.
AND THE W.C.R.S.I., OR AS MODIFIED BY THE CONSTRUCTION DOCUMENTS.
PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION' BY THE C.R.S.I.
REINFORCED CONCRETE' (ACI 318), AND THE 'MANUAL OF STANDARD
CONFORMANCE WITH THE 'BUILDING CODE REQUIREMENTS FOR
ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN 1.
REINFORCING STEEL
AND LOCATIONS.
VERIFY AND MEASURE ENCLOSURE CONDUIT AND/OR BLOCKOUT DIMENSIONS
DIMENSIONS. VERIFY DIMENSIONS WITH MANUFACTURER DRAWINGS. FIELD
REFER TO EQUIPMENT MANUFACTURER DRAWINGS FOR DETAILS AND 9.
CONSTRUCTION SHALL BE REMOVED.
ALL ABANDONED FOOTINGS, UTILITIES, ETC., THAT INTERFERE WITH NEW 8.
CONSTRUCTION.
LOCATE AND PROTECT EXISTING UTILITIES TO REMAIN DURING AND/OR AFTER 7.
ON DRAWINGS.
FOOTINGS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN 6.
ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED.5.
GOVERNING AGENCY PRIOR TO PLACING THE CONCRETE AND REINFORCING.
EXCAVATION AND COMPACTING IF REQUIRED SHALL BE APPROVED BY THE 4.
WATER FROM FOUNDATION EXCAVATIONS PRIOR TO PLACING CONCRETE.
WATER, GROUND WATER OR SEEPAGE. REMOVE LOOSE SOIL AND STANDING
CONTRACTOR SHALL PROVIDE DE-WATERING OF EXCAVATIONS FROM SURFACE 3.
CONSTRUCTION.
INCLUDING LAGGING, SHORING, UNDERPINNING AND PROTECTION OF EXISTING
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR EXCAVATION PROCEDURES 2.
FOOTING DESIGN IS BASED ON ALLOWABLE SOIL PRESSURE OF 2000 PSF.1.
FOUNDATIONS AND SITE WORK
STRONG-BOLT 2 SS, STB2SS
STRONG-BOLT 2 SS, STB2SS
W/ #4@12" OC EW T&B (f'c=4000PSI)
12" THICK CONCRETE FOUNDATION PAD
W/ #4@12" OC EW T&B (f'c=4000PSI)
12" THICK CONCRETE FOUNDATION PAD
BASE SHALL BE COMPACTED AND LEVEL.
SOIL W/ MINIMUM 95% COMPACTION.
CRUSHED AGGREGATE BASE ON COMPACTED
BASE SHALL BE COMPACTED AND LEVEL.
SOIL W/ MINIMUM 95% COMPACTION.
CRUSHED AGGREGATE BASE ON COMPACTED
1'-0"
BOLLARD
ROUNDED CONCRETE TOP
2% SLOPE
CONCRETE FOOTING
M A
T C
H E
X
IS
T
IN
G
SMOOTH TROWEL FINISH.
CONC SLAB ON GRADE.
SMOOTH TROWEL FINISH.
CONC SLAB ON GRADE.
3/4" CHAMFERED EDGES.3/4" CHAMFERED EDGES.
PRIME AND PAINT YELLOW
CONCRETE FILLED BOLLARD
SWITCHBOARD
CONCRETE THICKNESS AND MINIMUM ANCHOR EDGE DISTANCES.
AS NEEDED FOR SELECTED EQUIPMENT. MAINTAIN MINIMUM
NOTE: CONTRACTOR SHALL ADJUST FOUNDATION LENGTH & WIDTH
CONCRETE THICKNESS AND MINIMUM ANCHOR EDGE DISTANCES.
AS NEEDED FOR SELECTED EQUIPMENT. MAINTAIN MINIMUM
NOTE: CONTRACTOR SHALL ADJUST FOUNDATION LENGTH & WIDTH
CITY OF THOUSAND OAKS DWG. _________
CITY OF THOUSAND OAKSCITY OF THOUSAND OAKS
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV.SYMBOL DESCRIPTION OF CHANGEUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG
DATEENGINEERING DIVISION MANAGER
DATE
REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
Know what'sbelow.
Callbefore you dig.
IW
AP
BK0
KEWO
ENGINEERING
CORPORATION
07/14/25
07/14/25
07/14/25
07/14/25
TED GERBER, CITY ENGINEER
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
N G
T E
A
NRO
A
ET
FO LCA FI
ST
I E
G S
R
I
E N E
I R
EED
R
RO
P
ISSFE NA
O
L
O W
EK .B N
AI
R B
No. C79923
LIVIC
100% DESIGN SUBMITTAL.
25-016A
CI 5585 MUNICIPAL SERVICE CENTER GENERATOR REPLACEMENT
SHEET 11 OF 11
FOUNDATION DETAILS