ATTACHMENT 1: AFFIRMATION OF ABILITY TO MEET TECHNICAL REQUIREMENTS

Technical is the factual documentation of the firm’s ability to meet the requirements. Complete this affirmation of ability to meet technical requirements.

REQUIREMENT

QUOTER AFFIRMS

IT CAN MEET

THIS

REQUIREMENT

QUOTER AFFIRMS

IT IS UNABLE TO

MEET THIS

REQUIREMENT

1. Install two (2) new Myers WG50-43 Submersible Grinder Pump 5.0 HP 460V 3PH or approved equal pumps.

2. Any vendor-proposed equal pumps meet the following requirements:

The pumps shall be capable of delivering up to 183 gallons per minute.

The pumps shall be capable of passing ¾-inch solids.

The pumps shall be cast iron construction with stainless steel shaft.

All external nuts and bolts shall be of stainless steel.

3. Any quotes with vendor-proposed equal pumps must include the following submittals:

Submittal(s) that provided complete information on the pumps and discharge connections.

Submittals must include pump capacity, efficiency and power input curves, pump discharge connection design, construction, and materials.

4. Installation of pumps will begin within sixty

(60) days of the date of the contract and will be completed within thirty (30) days.

5. Pumps shall be installed so that they are easily removable for inspection or service. All connections to the existing control panels and piping shall be completed in a workman like manner.

6. Upon completion of pump installation, each pump will be tested for compatibility and interoperability with existing piping and control systems.