Attachment - VA 541-23-202 Bid Issue Combined Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25026B0010
About this file
This document is a comprehensive set of architectural and engineering design drawings for a roof replacement project at the Louis Stokes Cleveland Veterans Affairs Medical Center, Building 6, located at 10701 East Boulevard, Cleveland, Ohio 44106. The project number is 541-23-202 and was issued on September 26, 2023.
The scope of work involves the complete replacement of the Learning Exchange roof, including demolition of the existing EPDM roofing system and installation of a new modified SBS bituminous roofing system with 1/4-inch cover board over existing insulation. Key deliverables include architectural demolition and construction plans, roof plans at 3/16-inch scale, detailed sections and flashing details, architectural elevations showing existing building materials and door locations requiring protection, and an electrical lightning protection plan. The design accommodates specific load requirements including live loads of 100 PSF with 2,000-pound concentrated loads, roof live loads of 20 PSF, snow loads of 16.8 PSF on flat roofs with drift surcharge of 23.1 PSF, and wind speeds of 120 MPH ultimate design. The project includes coordination of existing mechanical equipment (RTUs), rooftop utilities, and lightning protection systems, with most equipment and piping remaining in place during construction. Construction staging requires temporary fencing with gates, covered walkway protection, and coordination of material movement and equipment placement. The drawings specify aluminum coping and edge strips, new wood blocking, new roof drains and flashings, pitch pocket details, and fall protection anchors. A bid deduct alternate is included for substituting EPDM membrane roofing in lieu of the modified SBS bituminous system for the main and high roof areas, excluding the low-radius roof section.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
TITLE SHEET AND DRAWING INDEX BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26
GI001
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
LOUIS STOKES CLEVELAND VAMC
NORTH ARROW
DETAIL NUMBER
DETAIL IDENTIFIER
DETAIL TITLE NUMBER /
SHEET REF NUMBER
SECTION IDENTIFIER
SHEET REF NUMBER
DETAIL
IDENTIFIER
SHEET REF
NUMBER
DETAIL SECTION IDENTIFIER
VIEWING
DIRECTION
VIEW TITLE
BUILDING/WALL SECTION CUT
EXTERIOR ELEVATION
DETAIL SECTION CUT
DETAIL CALLOUT
DRAWING SYMBOLS
N
INTERIOR ELEVATION
DD###
DD###
X
DD###
X
SCALE: 1'-0" = 1'-0"
DETAIL TITLEX
1 / DD###
DD###
X
DD###
X
TRUE NORTH
PLAN NORTH
VIEWING
DIRECTION
SHEET REF NUMBER
SHEET REF NUMBER
BLDG 6
N
N
WADE PARK AVE
EA
ST
B
LV
D
MAGNOLIA DRIVE
E
5T H
ST
RE
ET
E
8T H
ST
RE
ET
EAST BLVD
DRAWING LIST
DRAWING NUMBER DRAWING TITLE
GENERAL
GI001 TITLE SHEET AND DRAWING INDEX
GI002 GENERAL NOTES AND LEGENDS
GC101 PROJECT STAGING PLAN
ARCHITECTURAL
AD101 ARCHITECTURAL DEMOLITION - BLDG 6 ROOF PLAN
AD501 ARCHITECTURAL DEMOLITION SECTIONS & DETAILS
A-101 ARCHITECTURAL - BLDG 6 ROOF PLAN
A-102 ARCHITECTURAL - BLDG 6 ROOF PLAN BID DEDUCT ALTERNATE
A-201 ARCHITECTURAL ELEVATIONS
A-501 ARCHITECTURAL SECTIONS & DETAILS
A-502 ARCHITECTURAL SECTIONS & DETAILS
ELECTRICAL
EG101 ELECTRICAL LIGHTNING PROTECTION PLAN
9/26/2023
MULTICORELINK:DWG-23101-GI002.REVX GENERAL NOTES AND LEGENDS-DWG-23101-GI002.REVX GENERAL NOTES AND LEGENDS MULTICORELINK:DWG-23101-GI002.REVX GENERAL NOTES AND LEGENDS-DWG-23101-GI002.REVX GENERAL NOTES AND LEGENDS MULTICORELINK:DWG-23101-GC101.REVX PROJECT STAGING PLAN-DWG-23101-GC101.REVX PROJECT STAGING PLAN MULTICORELINK:DWG-23101-GC101.REVX PROJECT STAGING PLAN-DWG-23101-GC101.REVX PROJECT STAGING PLAN MULTICORELINK:DWG-23101-AD101.REVX ARCHITECTURAL DEMOLITION - BLDG 6 ROOF PLAN-DWG-23101-AD101.REVX ARCHITECTURAL DEMOLITION - BLDG 6 ROOF PLAN MULTICORELINK:DWG-23101-AD101.REVX ARCHITECTURAL DEMOLITION - BLDG 6 ROOF PLAN-DWG-23101-AD101.REVX ARCHITECTURAL DEMOLITION - BLDG 6 ROOF PLAN MULTICORELINK:DWG-23101-AD501.REVX ARCHITECTURAL DEMOLITION SECTIONS & DETAILS-DWG-23101-AD501.REVX ARCHITECTURAL DEMOLITION SECTIONS & DETAILS MULTICORELINK:DWG-23101-AD501.REVX ARCHITECTURAL DEMOLITION SECTIONS & DETAILS-DWG-23101-AD501.REVX ARCHITECTURAL DEMOLITION SECTIONS & DETAILS MULTICORELINK:DWG-23101-A-101.REVX ARCHITECTURAL - BLDG 6 ROOF PLAN-DWG-23101-A-101.REVX ARCHITECTURAL - BLDG 6 ROOF PLAN MULTICORELINK:DWG-23101-A-101.REVX ARCHITECTURAL - BLDG 6 ROOF PLAN-DWG-23101-A-101.REVX ARCHITECTURAL - BLDG 6 ROOF PLAN MULTICORELINK:DWG-23101-A-102.REVX ARCH PLAN - BLDG 6 ROOF PLAN BID DEDUCT ALT-DWG-23101-A-102.REVX ARCH PLAN - BLDG 6 ROOF PLAN BID DEDUCT ALT MULTICORELINK:DWG-23101-A-102.REVX ARCH PLAN - BLDG 6 ROOF PLAN BID DEDUCT ALT-DWG-23101-A-102.REVX ARCH PLAN - BLDG 6 ROOF PLAN BID DEDUCT ALT MULTICORELINK:DWG-23101-A-201.REVX ARCHITECTURAL ELEVATIONS-DWG-23101-A-201.REVX ARCHITECTURAL ELEVATIONS MULTICORELINK:DWG-23101-A-201.REVX ARCHITECTURAL ELEVATIONS-DWG-23101-A-201.REVX ARCHITECTURAL ELEVATIONS MULTICORELINK:DWG-23101-A-501.REVX ARCHITECTURAL SECTIONS & DETAILS-DWG-23101-A-501.REVX ARCHITECTURAL SECTIONS & DETAILS MULTICORELINK:DWG-23101-A-501.REVX ARCHITECTURAL SECTIONS & DETAILS-DWG-23101-A-501.REVX ARCHITECTURAL SECTIONS & DETAILS MULTICORELINK:DWG-23101-A-502.REVX ARCHITECTURAL SECTIONS & DETAILS-DWG-23101-A-502.REVX ARCHITECTURAL SECTIONS & DETAILS MULTICORELINK:DWG-23101-A-502.REVX ARCHITECTURAL SECTIONS & DETAILS-DWG-23101-A-502.REVX ARCHITECTURAL SECTIONS & DETAILS MULTICORELINK:DWG-23101-EG101.REVX ELECTRICAL LIGHTNING PROTECTION PLAN-DWG-23101-EG101.REVX ELECTRICAL LIGHTNING PROTECTION PLAN MULTICORELINK:DWG-23101-EG101.REVX ELECTRICAL LIGHTNING PROTECTION PLAN-DWG-23101-EG101.REVX ELECTRICAL LIGHTNING PROTECTION PLAN AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
A/E DESIGN, REPLACE
AutoCAD SHX Text
LEARNING EXCHANGE ROOF
AutoCAD SHX Text
10701 EAST BLVD
AutoCAD SHX Text
CLEVELAND, OH 44106
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
GENERAL NOTES AND LEGENDS BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26
GI002
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
ROOF DRAIN
VENT PIPE
VENTILATION HOOD WITH CURB
ROOF OR SMOKE HATCH
ARCHITECTURAL GENERAL NOTES:
1. THE CONTRACTOR SHALL COORDINATE ALL WORK ASSOCIATED WITH THIS PROJECT WITH THE SUB-CONTRACTORS, TO
PROVIDE A COMPLETE AND FINISHED PROJECT.
2. THIS FACILITY IS OCCUPIED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND METHODS OF
CONSTRUCTION AND SHALL BE RESPONSIBLE TO THE VA COR FOR PROVIDING A SAFE WORK ENVIRONMENT DURING THE CONSTRUCTION PERIOD. THE CONTRACTOR SHALL ENSURE THE SAFETY OF PATIENTS AND VA STAFF IS NOT
COMPROMISED DUE TO ANY CONSTRUCTION RELATED ACTIVITIES.
3. ALL MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS AND
RECOMMENDATIONS.
4. DIMENSIONS AND DETAILS ARE BASED ON THE BEST AVAILABLE INFORMATION AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING FIELD DIMENSIONS BEFORE ORDERING MATERIALS AND PREFABRICATED ITEMS.
5. ALL WORK SHALL BE PERFORMED IN THE BEST AND MOST PROFESSIONAL MANNER BY CONTRACTOR SKILLED IN THEIR
RESPECTIVE TRADES.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTING AND CORRECTING HIS/HER OWN WORKMANSHIP.
7. ALL WORKMANSHIP AND MATERIALS, UNLESS CARRYING A GUARANTEE BY A MANUFACTURER FOR A LONGER PERIOD
OF TIME SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR PER CONTRACT AND FAR REGULATIONS AS STIPULATED
BY THE CONTRACTING OFFICER.
8. THE CONTRACTOR SHALL VISIT THE SITE TO VERIFY FIELD CONDITIONS.
9. THE CONTRACTOR SHALL MAKE EVERY EFFORT TO PREVENT THE SPREAD OF DUST, SMOKE, FUMES, ETC., THROUGHOUT THE BUILDING AND NEIGHBORHOOD. PROTECT ALL AIR INTAKES WITH CHARCOAL FILTERS FOR ROOF
APPLICATIONS.
10. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY SERVICES INCLUDING, ADEQUATE LIGHTING, WATER, TOILETS, POWER, HEAT, ETC. AS REQUIRED FOR WORKMAN, MATERIAL INSTALLATION, WORK PROTECTION, ETC. OR AS
DISCUSSED AND ALLOWED BY THE VA COR.
11. THE CONTRACTOR SHALL PROVIDE THE VA COR A COMPLETE MAINTENANCE & OPERATIONAL INSTRUCTIONS IN BOTH
WRITTEN & VERBAL FORM FOR ALL CONTRACTOR PROVIDED EQUIPMENT.
12. THE CONTRACTOR SHALL REVIEW ALL CONSTRUCTION DOCUMENTS AND NOTIFY THE VA COR OF ANY INACCURACIES OR DISCREPANCIES IN THE DOCUMENTS AND IN FIELD CONDITIONS SHOWN ON THE DRAWINGS IN A TIMELY MANNER.
13. THE CONTRACTOR SHALL PERFORM ALL WORK IN STRICT ACCORDANCE WITH ALL FEDERAL CODES, RULES, REGULATIONS AND ORDINANCES INCLUDING, BUT NOT LIMITED TO, THE INTERNATIONAL ENERGY CONSERVATION CODE, THE INTERNATIONAL BUILDING CODE, AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) AND OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) WHETHER OR
NOT INFORMATION AND/OR WORK IS SPECIFICALLY SHOWN ON THE DRAWINGS.
14. THE CONTRACTOR SHALL BE AWARE THAT THE EXISTING FACILITY HAS THE POTENTIAL OF HAVING OTHER
CONSTRUCTION PROJECTS GOING ON AT THE SAME TIME. COORDINATE WITH VA COR.
15. THE CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL MATERIAL DELIVERIES WITH VA COR AND VA STAFF IN CHARGE OF THE LOADING DOCK. NO CONTRACTOR MATERIAL WILL BE STORED ON OR AROUND LOADING DOCK UNLESS
AUTHORIZED BY THE VA COR. THE VA WILL NOT RECEIVE CONTRACTOR MATERIAL.
16. CONTRACTOR TO PROVIDE MULTIPLE CHUTES TO CONVEY CONSTRUCTION WASTE FROM ROOF DOWN TO GROUND LEVEL. CONTRACTOR TO PROVIDE TEMPORARY WASTE RECEPTACLES UNDER OUTPUT OF CHUTES TO TRANSPORT WASTE BETWEEN CHUTES AND DUMPSTER. PROTECT ALL AREAS THAT TEMPORARY WASTE RECEPTACLES TRAVERSE.
WASTE SHALL NOT PILE UP ON LOWER ROOFS OR GROUND. IMMEDIATELY RELOCATE WASTE TO DUMPSTER. NO
CHUTES ARE ALLOWED FOR ASBESTOS CONTAINING MATERIAL.
17. STOCK PILING OF NEW ROOFING MATERIALS ON EXISTING AND NEW ROOF AREAS IS NOT PERMITTED.
18. ALL NEW WOOD BLOCKING SHALL BE PRESSURE TREATED AND FIRE RETARDANT WITH STAMP SHOWN.
19. CONTRACTOR SHALL SUBMIT A PLAN TO THE COR WITHIN 10 CALENDAR DAYS OF THE NTP FOR EACH OF THE
FOLLOWING: STAGING AREA IN PARKING LOT L AS WELL AS THE SCAFFOLDING, ELECTRIC WINCH HOIST, DUMPSTER
AND CHUTE AREA FOR EACH PHASE OF WORK.
20. CONTRACTOR TO PROVIDE FIRE PREVENTION PLAN TO VA COR FOR REVIEW AND APPROVAL.
21. ALL LIFE-SAFETY SYSTEMS SHALL REMAIN OPERATIONAL THROUGHOUT THE DURATION OF THE PROJECT. ANY
INTERRUPTION OF THE LIFE-SAFETY SHALL BE COORDINATED WITH THE COR AHEAD OF TIME.
22. THE CONTRACTOR WILL FOLLOW THE REQUIREMENTS SPELLED OUT ON THE HOT WORK PERMIT AND SAFETY
PROTOCOLS WHILE PERFORMING HOT WORK.
23. CONTRACTOR SHALL SUBMIT SCAFFOLDING SHOP DRAWINGS FOR EACH LOCATION SIGNED AND SEALED BY A PE. EACH
DRAWING IS TO BE SIGNED AND SEALED.
24. THE CONTRACTOR SHALL PROVIDE WRITTEN NOTIFICATION TO THE CONTRACTING OFFICER'S REPRESENTATIVE THIRTY
(30) CALENDAR DAYS IN ADVANCE OF THE DATE WHICH THE SPECIAL INSPECTION IS REQUIRED TO TAKE PLACE ON.
25. THE CONTRACTOR TO SUBMIT A PLAN TO PROTECT ODORS FROM ENTERING ANY OUTSIDE AIR INTAKES IN THE VICINITY
OF CONSTRUCTION ACTIVITIES.
26. ROOFING SEASON: PERFORM WORK BETWEEN APRIL 15 AND NOVEMBER 30, UNLESS OTHERWISE APPROVED BY COR.
27. PHASING: SEQUENCE WORK SO TRAFFIC ON NEWLY COMPLETED ROOFING WORK IS MINIMIZED.
28. ROOF PROTECTION: PROTECT ALL EXISTING AND NEW ROOFING WHEN MOVING OR STORING MATERIALS. STORAGE SHALL BE
DISTRIBUTED TO PREVENT CONCENTRATED LOADS FROM BEING APPLIED TO ROOF STRUCTURE.
29. ROOF ACCESS: PROVIDE SCAFFOLDING, PLATFORMS, RAMPS, AND BRIDGING FOR WORKER ACCESS, MATERIAL DELIVERY, AND
DEBRIS REMOVAL. PROVIDE DEBRIS CHUTE FROM ROOF TO DUMPSTER ON GROUND LEVEL. REMOVE DEBRIS FROM ROOF ON A
DAILY BASIS.
30. CRANE LIFTS: PERFORM OFF-HOURS OR WEEKENDS AT NO ADDITIONAL COST TO THE VA.
31. HVAC SYSTEM SHUTDOWNS: PROVIDE AT LEAST TWO WEEK ADVANCE NOTICE FOR SHUTDOWNS. ALL SHUTDOWN WORK SHALL BE
OFF-HOURS OR WEEKENDS AT NO ADDITIONAL COST TO THE VA.
32. PIPING,CONDUIT,CABLES,LIGHTNING PROTECTION: REINSTALL USING ATTACHMENT METHODS/ANCHORS THAT DO NOT PENETRATE
NEW ROOF MEMBRANE OR FLASHING.
AREA BOUNDARY
RD
AT LIGHTNING ROD
GND GROUND CONDUCTOR
DEMOLITION
E ELECTRIC
LINE TYPES:
SYMBOLS & LEGEND
SYMBOL DESCRIPTION
AREA OF COVERED WALKWAY CANOPIES.
CONSTRUCTION FENCING AND GATE PER SPEC REQUIRED.
CRICKET SLOPE - 1/4" PER FOOT = MAXIMUM OVERALL THICKNESS.
SADDLE SLOPE - 1/4" PER FOOT = MAXIMUM OVERALL THICKNESS.
ROOF SLOPE - 1/4" PER FOOT FLAT ROOF AREAS MIN.
HIGH POINT INSULATION THICKNESS. X = APPROXIMATE THICKNESS BASED UPON
AN AVERAGE R VALUE PRESCRIBED IN THE SPECIFICATIONS AND THE INDICATED
ROOF SLOPE. FIELD VERIFY ALL VALUES.
LOW POINT INSULATION THICKNESS. X = APPROXIMATE THICKNESS BASED UPON
AN AVERAGE R VALUE PRESCRIBED IN THE SPECIFICATIONS AND THE INDICATED
ROOF SLOPE. FIELD VERIFY ALL VALUES.
DEMOLISH/REMOVE
L
ABBREVIATION MEANING
A/E ARCHITECT/ENGINEER
ACT ACOUSTICAL CEILING TILE
ADJ ADJACENT, ADJOINING, OR ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ALT ALTERNATE
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
AUX AUXILIARY
AVG AVERAGE
BD BOARD
BKG BACKING
BLDG BUILDING
BM BEAM OR BENCHMARK
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRDG JST BRIDGING JOIST
BRG BEARING
BRG PL BEARING PLATE
BSMT BASEMENT
BTWN BETWEEN
CBB CEMENTITIOUS (BACKER) BOARD
CJ CONSTRUCTION JOINT OR CONTROL JOINT
CL CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONSTR CONSTRUCTION
CONTR CONTRACTOR
CONT CONTINIOUS
CT CERAMIC TILE
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL DIAGRAM
DIAG DIAGRAM DIAGONAL
DIFF DIFFERENCE OR DIFFUSER
DIM DIMENSION
DOC DOCUMENT
DN DOWN
DR DOOR, DRAIN, OR DRIVE
DS DOWNSPOUT
EA EACH
EPS EXPANDED POLYSTYRENE BOARD
EQ EQUAL
EW EACH WAY
EXIST EXISTING
EXP EXPANSION OR EXPOSED
EXP BT EXPANSION BOLT
EXT EXTERIOR, EXTERNAL, OR EXTINGUISHER
EXT GR EXTERIOR GRADE
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FINISH
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FLR FLOOR
FLR FIN FLOOR FINISH
FRMG FRAMING
FT FEET OR FOOT
FTG FOOTING
ABBREVIATION MEANING
GALV GALVANIC OR GALVANIZED
GRTG GRATING
GSB GYPSUM SHEATHING BOARD
GWB GYPSUM WALL BOARD
GYP GYPSUM
GYP BD GYPSUM BOARD
HDR HEADER
HM HOLLOW METAL
HORIZ HORIZONTAL
HOSP HOSPITAL
HP HIGH POINT
HT HEIGHT
INSUL INSULATION
LP LOW POINT
MAT MATERIAL
OC ON CENTER
OFD OVERFLOW DRAIN
PRELIM PRELIMINARY
PT PAINT, PNEUMATIC TUBE, OR PRESSURE
PTD PAINTED
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REQD REQUIRED
RET RETARDANT
RHWS ROUND HEAD WOOD SCREW
RL ROOF LEADER
RO ROUGH OPENING
SAN SANITARY
SIM SIMILAR
SPEC SPECIFICATION
SPKLR SPRINKLER
STD STANDARD
STL PL STEEL PLATE
STRUCT STRUCTURAL
STRUCT STL STRUCTURAL STEEL
SUSP CLG SUSPENDED CEILING
SYS SYSTEM
TBD TO BE DETERMINED
TO TOP OF ___
TO FDN TOP OF FOUNDATION
TYP TYPICAL
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
WD WOOD
WP WATERPROOF
LIGHT FIXTURE, WALL MOUNTED
HP
19" HIGH POINT MARKER
GENERAL DRAWING SYMBOLS:
X KEYED NOTE
ARCHITECTURAL SYMBOLS:
ELECTRICAL SYMBOLS:
LOW POINT MARKER
LP
5"
FULL DOWNLEAD TO GROUND
DESIGN DATA:
IN ITS COMPLETED STATE, AE DESIGN SERVICES FOR ROOF REPLACEMENT BUILDING 6
FOR THE CLEVELAND VA MEDICAL CENTER IS DESIGNED FOR THE FOLLOWING
SURCHARGE LOADS. DO NOT EXCEED STATED SURCHARGE LOADS.
1. DEAD LOAD: STRUCTURE SELF WEIGHT
2. LIVE LOAD: 100 PSF
2000LB. CONCENTRATED
3. ROOF LIVE LOAD : 20 PSF
4. SNOW LOAD: FLAT ROOF SNOW LOAD Pf = 16.8 PSF GROUND SNOW LOAD Pg = 20 PSF SNOW EXPOSURE FACTOR Ce = 1.0 SNOW LOAD IMPORTANCE FACTOR Is = 1.2 THERMAL FACTOR Ct = 1.0 DRIFT SURCHARGE Pd = 23.1 PSF DRIFT WIDTH w = 5'-6"
5. WIND LOAD : ULTIMATE DESIGN WIND SPEED, Vult = 120 MPH NOMINAL DESIGN WIND SPEED, Vasd = 93 MPH
RISK CATEGORY IV
IMPORTANCE FACTOR, Iw = 1.00
WIND EXPOSURE CATEGORY, B
INTERNAL PRESSURE COEFFICIENT, GCpi = +/-0.18
COMPONENTS AND CLADDING WIND PRESSURES
6. SEISMIC LOAD :
RISK CATEGORY IV
IMPORTANCE FACTORS, Ie = 1.50
SOIL SITE CLASS = C
MAPPED SPECTRAL ACCELERATIONS/RESPONSES
Ss = 0.222 S1 = 0.054
SDS = 0.193
SD1 = 0.054
SEISMIC DESIGN CATEGORY = C
SEISMIC RESISTING SYSTEM = SEISMIC DEMAND ON
NONSTRUCTURAL COMPONENTS
COMPONENT AMPLIFICATION FACTOR, ap = 2.5 COMPONENT RESPONSE MODIFICATION FACTOR, Rp = 1.5
EQUIVALENT LATERAL FORCE METHOD
HORIZONTAL FORCE, Fph = 0.193 x SELF WEIGHT VERTICAL FORCE, Fpv = ± 0.039 x SELF WEIGHT
X COLUMN CENTER LINE
BLDG 6
Zone Net Pressure, p (psf) Net Pressure, p (psf)
A -50 15
B -50 15
C -37 15
D -37 15
E -31 15
GENERAL DEMOLITION NOTES:
1. EXISTING MECHANICAL EQUIPMENT, VENTS, PIPING, CONDUIT, EXHAUSTS, DUCTWORK SHALL EITHER BE LEFT IN PLACE
OR TEMPORARILY RELOCATED FOR DEMOLITION/RE-ROOFING/FLASHINGS WORK TO BE EXECUTED IN ACCORDANCE WITH THE DETAILS PROVIDED. ELECTRICAL AND MECHANICAL EQUIPMENT REQUIRING TEMPORARY SHUTDOWN AND RE-START SHALL BE NOTED ON THE EQUIPMENT SCHEDULES PROVIDED ON DRAWINGS. COORDINATE THOSE
SHUTDOWNS WITH THE CLEVELAND VA.
2. REMOVE ALL EXISTING ROOFING MATERIALS AT EACH ROOF AREA AS IDENTIFIED IN THE EXISTING ROOF TYPES ON EACH DEMOLITION PLAN, TO EXISTING INSULATION WHICH IS TO REMAIN. REMOVALS SHALL INCLUDE ALL BASE FLASHINGS, METAL FLASHINGS AND OTHER MATERIALS ASSOCIATED WITH THE ROOF AND IN ACCORDANCE WITH THE
DETAILS.
3. IF ANY PREVIOUSLY-UNIDENTIFIED OR OTHERWISE UNANTICIPATED SUSPECT MATERIALS IS IDENTIFIED DURING CONSTRUCTION, STOP WORK AND NOTIFY THE OWNER OR THEIR REPRESENTATIVE FOR FURTHER DIRECTION. UNDER NO CIRCUMSTANCES SHALL THE CONTRACTOR COLLECT AND/OR ANALYZE BULK SAMPLES OF SUSPECT MATERIALS
WITHOUT THE APPROVAL OF THE VA.
4. THE CONTRACTOR SHALL REPLACE ANY EXISTING FIRESTOPPING WHICH WAS DISLODGED OR DAMAGED DURING
CONSTRUCTION.
X x x x x
HP
19"
LP
5"
ABBREVIATIONS
CODE SUMMERY:
1. THE BUILDING CONFORMS TO THE REQUIREMENTS OF THE 2018 IBC AND LATEST AMENDMENTS.
2. OCCUPANCY GROUP; B BUSINESS
3. FIRE RESISTANT RATING - SPRINKLERED, AS PER TABLE 601 NONE OF THE STRUCTURAL MEMBERS
ARE REQUIRED TO BE FIRE PROTECTED.
4. FIRE RESISTANT WOOD IS NOT REQUIRED FOR THE ROOF BLOCKING AS PER IC 2018 AS PER 60.1
THROUGH 6031.3, ROOF COVERING MATERIALS THAT ARE RATED A, B, AND C.
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
X
X
X
XXX
STAGING AREA 1
TEMPORARY FENCE
WITH GATES
TEMPORARY
FENCE
BLDG 6
WADE PARK AVE
E 105TH STREET
MAGNOLIA DRIVE
VISITOR/PATIENT
PARKING GARAGE
EMPLOYEE
PARKING
GARAGE
X X
X X
X X
X
X X X X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
PROJECT STAGING PLAN BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26
GC101
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 1"=50'
PROJECT STAGING PLAN1
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. CONTRACTOR RESPONSIBLE FOR ALL MEANS AND METHODS, MOVEMENT OF MATERIAL,
SAFETY PRECAUTIONS, STORAGE, AND MAINTENANCE OF EXITS FROM THE BUILDING.
3. NOTIFY THE VA IN WRITING OF ALL SHUTDOWNS FOR EQUIPMENT, CELL SERVICES,
RADIO SERVICES, ETC. PER THE GUIDELINES SET FORTH ON THE DRAWINGS AND
SPECIFICATIONS.
4. CONTRACTOR IS TO SUBMIT A STAGING PLAN FOR EACH PHASE AT THE START OF THE
CONSTRUCTION PROJECT (WITHIN 10 CALENDAR DAYS OF THE NTP).
5. GAS POWERED EQUIPMENT IS NOT PERMITTED ON THIS PROJECT, THIS INCLUDES, BUT
NOT LIMITED TO WINCHES, LIFTS, ETC., WHICH SHALL BE ELECTRIC.
6. CONTRACTOR'S VEHICLES SHALL NOT BE IDLING WITHIN 50 FEET OF ANY OUTSIDE AIR
INTAKE.
7. ENSURE THAT FREE ACCESS FROM THE STREET FOR FIRE HYDRANTS AND THE
SPRINKLER SYSTEM FIRE DEPARTMENT CONNECTION IS MAINTAINED AT ALL TIMES. ADD
NECESSARY GUIDANCE AND DETAILS TO THE DRAWINGS TO ENSURE TEMPORARY
FENCING DOES NOT OBSTRUCT THESE ITEMS.
KEYED NOTES
1 TEMPORARY FENCING TO BE 8' HIGH CHAIN LINK WITH LOCKABLE SWING GATES AND
LOCKABLE PEDESTRIAN GATES AS REQUIRED.
2 PROVIDE COVERED TEMPORARY PROTECTION TO MAINTAIN PATHWAY FROM BUILDING
DURING CONSTRUCTION, REFER TO SECTION 01 35 26 SAFETY REQUIREMENTS.
3 TRASH CHUTE AND DUMPSTER.
4 MAINTAIN A MINIMUM OF 5 FT BETWEEN THE CURB AND THE FENCE TO PROVIDE A SAFE
ACCESS FOR PEDESTRIANS.
5 CONTRACTOR TO VERIFY WEIGHT CAPACITY OF ROOF AND MATERIAL PLACEMENTS
PRIOR TO USING ROOF AS A STAGING AREA.
6 CONTRACTOR TO PROVIDE FLAGMAN AT SIDEWALK WHEN STAGING AREA IS BEING
LOADED WITH MATERIALS.
SYMBOLS & LEGEND
SYMBOL DESCRIPTION
CONSTRUCTION FENCING AND GATE PER SPEC REQUIRED.
MATERIALS MOVEMENT POSSIBLE CRANE LOCATION OR MATERIALS
CONVEYOR (PER CONTRACTORS MEANS AND METHODS).
AREA OF COVERED WALKWAY CANOPIES. REFER TO DRAWING A-001 FOR
CLOSURES, AND SAFETY PROCEDURES.
X
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
N
LX.2.2 LX.3LX.21.6LX.1.4LX.1 LX.4 LX.5 A 5.4 LX.5.8 LX.6 B
6.36.24.115.9
LX.A
LX.A.4
A.4.1
LX.A.7
LX.B
LX.B1
LX.B.3
LX.B.4
LX.B.9
LX.B.5
LX.C
LX.2.2 LX.3LX.21.6LX.1.4LX.1 LX.4 LX.5 A 5.4 LX.5.8 LX.6 B
6.36.24.115.9
LX.A
LX.A.4
A.4.1
LX.A.7
LX.B
LX.B1
LX.B.3
LX.B.4
B.7
LX.B.9
LX.B.5
LX.C
9 TYP
13131313
115'-9"16'-4"
143'-1"
11'-1"
'-4
'-3
'-0
'-6
10'-8" 128'-5"
139'-0"
'-0
'-9
5'-
3"
'-6
6'- 8"
8'-0"
1/4"/FT
1/4"/FT
1/4 "/F
T
1/4 "/F
T
1/4 "/F
T
RTU-1 RTU-2 RTU-3 RTU-4
LOW ROOF,
NOT IN CONTRACT
1/4"/FT
1/4"/FT
1/4"/FT
1/4"/FT
17 5
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
AD501
1'-1 1/2"
1'- 1 1
/2"
1'-1 1/2"
1'- 1 1
/2"
1'-1 1/2"
1'- 1 1
/2"
1'-1 1/2"
1'- 1 1
/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL DEMOLITION -
BLDG 6 ROOF PLAN
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26
AD101
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 3/16" = 1'-0"
ARCHITECTURAL DEMOLITION - BLDG 6 ROOF PLAN1
KEYPLAN
BLDG 6
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. UNITS ARE TO REMAIN IN USE DURING CONSTRUCTION.
3.
UNITS ARE NOT TO BE DISCONNECTED TO ALLOW FOR ROOFING INSTALL. NO
TEMPORARY SUPPORTS NEEDED FOR UNITS. PIPING DOES NOT NEED TO BE
DISCONNECTED.
4. PROTECT ALL EXISTING CONDITIONS THAT ARE TO REMAIN DURING CONSTRUCTION.
KEYED NOTES
1 REMOVE GRAVEL STOP.
2 ROOF HATCH AND CURB TO REMAIN. REMOVE ROOF HATCH GUARDRAIL,GUARDRAIL
DOOR, AND FLASHING. STORE GUARDRAIL AND DOOR FOR REUSE.
3 REMOVE FLASHING AT FAN ROOF CURB.
4 DURING CONSTRUCTION RELOCATE SATELLITE AND ELECTRICAL CONNECTION BOX
ON 32'x32' METAL STAND SUPPORT BALLASTED WITH (8) BLOCKS. NOTE THAT THESE
UNITS INCLUDE ELECTRICAL WIRING ON RUBBER CONDUIT BLOCKS.
5 REMOVE EPDM ROOFING AND COVER BOARD, INSULATION TO REMAIN. REFER TO
DETAIL 9/AD501
6 REMOVE REGLET FLASHING AT BASE OF WALL AT HIGH-LOW CONDITION.
7 REMOVE FLASHING AT WASTE VENT PIPES. REFER TO DETAIL 3/AD501
8 REMOVE ROOF DRAIN, FLASHING, AND STRAINER. ROOF DRAIN PIPING TO REMAIN.
REFER TO DETAIL 2/AD501.
9 REMOVE PITCH POCKETS AT SCREEN WALL COLUMN SUPPORTS. REFER TO DETAIL
8/AD501
10 REMOVE FLASHING AT VENT FLUE, PIPE TO REMAIN. REFER TO DETAIL 11/AD501
11 REMOVE FLASHING. CURB TO REMAIN. REFER TO DETAIL 15/AD501
12 OWNER TO REMOVE TEMPORARY STORAGE SHED AND THE CONTENTS FROM THE
ROOF. THIS STORAGE SHED IS NOT ATTACHED TO THE ROOF.
13 REMOVE FLASHING FROM EQUIPMENT CURBS. WOOD BLOCKING, CURBS AND
EQUIPMENT TO REMAIN IN PLACE. REFER TO 10/AD501.
14 REMOVE ROOF SCUPPER.
15 ROOF SUPPORTS FOR PIPES AND CONDUITS TO REMAIN. PROVIDE ADDITIONAL
SUPPORTS AS REQUIRED DURING CONSTRUCTION.
16 LOOSE CABLES TO EXISTING ROOF EQUIPMENT TO REMAIN.
17 REMOVE ROOF CRICKET.
18 REMOVE ROOF INSULATION BACK FROM EDGE AS REQUIRED FOR NEW WOOD
BLOCKING.
19 REMOVE INSULATION AT NEW FALL PROTECTION ANCHORS.
20 EXTERIOR WALL AROUND PERIMETER.
21 PROTECT ROOF HATCH OPENING PRIOR TO GUARDRAILS GETTING INSTALLED.
22 STRUCTURE AND DECK IS FLAT, INSULATION IS TAPERED.
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text N
REMOVE GRAVEL STOP
1 1/2" METAL DECK ON
STRUCTURAL STEEL
STRUCTURAL STEEL
REMOVE 2X PT WOOD BLOCKING
WITH ALUMINUM WRAP
CAST STONE
REMOVE FASCIA TRIM
INSULATION TO REMAINREMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
VARIES
REMOVE PORTION OF INSULATION
REQUIRED FOR NEW PT WOOD
BLOCKING. SEE 8/A-501
6"+/-
SEALANT AND BACKER ROD
TO BE REMOVED
WITH FASCIA TRIM
REMOVE 2X PT WOOD BLOCKING
WITH ALUMINUM WRAP
STRUCTURAL STEEL
1 1/2" METAL DECK
ON STRUCTURAL STEELEXTENDED JOIST SEAT
REMOVE GRAVEL STOP
REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
INSULATION TO REMAIN
6"+/-
REMOVE PORTION OF INSULATION
REQUIRED FOR NEW PT WOOD
BLOCKING. SEE 8/A-501
EXISTING CAST IRON DRAIN
BOWL AND LEADER PIPE
MECHANICAL WATERTIGHT
CONNECTION SEAL
REMOVE ALUMINUM
STRAINER DOME
REMOVE METAL STUD WITH
SELF-LOCKING NUT
REMOVE ALUMINUM
CLAMPING RING
INSULATION
TO REMAIN
4" DIA. O.D. ROOF
DRAIN
EXISTING 1 1/2"
METAL DECK
REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
RETROFIT DRAIN BODY
DRAIN AND STRAINER
TO BE REMOVED
REMOVE SEALANT,
SURFACE MOUNTED
REGLET RECEIVER,
ALUMINUM SPRING,
LOCK FLASHING,
MEMBRANE FLASHING
EXISTING STONE MASONRY EXISTING STONE MASONRY
REMOVE SEALANT,
ALUMINUM REGLET,
ALUMINUM SPRING,
LOCK FLASHING, AND
MEMBRANE FLASHING
1/4" SLOPE
EXISTING 1 1/2" METAL
DECK TO REMAIN
REMOVE 1/4" COVER BOARD
AND ROOF MEMBRANE
ROOF INSULATION TO REMAIN,
EXISTING STRUCTURE SLOPES
TO LOW AREAS UNLESS
OTHERWISE NOTED ON PLAN
PE
NE
TR
AT
IO
N
REMOVE PVC FLASHING
6" REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
TRESPA PANEL BEYOND
REMOVE 2X PT WOOD BLOCKING
WITH ALUMINUM WRAP
REMOVE GRAVEL STOP
1 1/2" METAL DECK ON
STRUCTURAL STEEL
STRUCTURAL STEEL
REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
INSULATION TO REMAIN
1 5/8"
REMOVE PORTION OF INSULATION
REQUIRED FOR NEW PT WOOD
BLOCKING. SEE 8/A-501
6"+/-
SEALANT AND BACKER ROD
TO BE REMOVED
WITH FASCIA TRIM
REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
1/2" STONE TILE VENEER
STRUCTURAL STEEL
1 1/2" METAL DECK
ON STRUCTURAL STEEL
STEEL CHANNEL TO
REMAIN OVER STEAM BEAM
REMOVE FLASHING
AND COUNTER FLASHING
INSULATION TO REMAIN
1'- 0"
2"
2"
UNIT FLASHING
REMOVE COUNTER-FLASHING
REMOVE 1/4" COVER BOARD
AND ROOF MEMBRANE
REMOVE FLASHING
EXISTING 1 1/2" METAL DECK
EXISTING 1 1/2" METAL DECK
REMOVE BAND
FLUE PIPE TO REMAIN
REMOVE 1/4" COVERBOARD
AND ROOF MEMBRANE
INSULATION TO REMAIN
REMOVE FLASHING
EXISTING WATER SHROUD
REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
REMOVE PITCH POCKETS
6x6 COLUMN TO REMAIN
EXISTING 1 1/2" METAL DECK
INSULATION TO REMAIN
REMOVE AIR TERMINAL
BASE FROM ROOF
REMOVE POURABLE SEALANT
REMOVE AIR TERMINAL
REMOVE 1/4" COVER BOARD
AND ROOF MEMBRANE
REMOVE GROUND WIRE
CONNECTIONS FROM ROOF
8"
MI
N
REMOVE MEMBRANE FLASHING
EXISTING WOOD BLOCKING
EXISTING CURB 3" MIN
EXISTING ROOF HATCH
REMOVE 1/4" COVER BOARD
AND ROOF MEMBRANE
EXISTING SHEET METAL COVER TO REMAIN
REMOVE FASTENERS AS REQUIRED
EXISTING WOOD BLOCKING TO REMAIN
REMOVE FLASHING
EXISTING ROOF EQUIPMENT
REMOVE 1/4" COVER BOARD
AND ROOF MEMBRANE
EXISTING INSULATION
8"
MI
N
EXISTING WOOD BLOCKING
EXISTING CURB
REMOVE 1/4" COVER
BOARD AND ROOF
MEMBRANE
REMOVE FLASHING
LIFT UP PLASTIC COVER
AND REMOVE CURB FLASHING
METAL EXHAUST FAN COVER TO BE
REMOVED AND REINSTALLED
EXISTING 1 1/2"
METAL DECK
REMOVE FLASHING
REMOVE 1/4" COVER BOARD
AND ROOF MEMBRANE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL DEMOLITION
SECTIONS & DETAILS
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26
AD501
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 1"=1'-0"
RETROFIT ROOF DRAIN DETAIL2
1/AD101
SCALE: NTS
TYPICAL COUNTER FLASHING DETAIL1
SCALE: NTS
TYPICAL ROOF ASSEMBLY DETAIL9
SCALE: NTS
TYPICAL ROOF VENT DETAIL3
SCALE: 3" = 1'-0"
ROOF EDGE SECTION5
1/AD101
SCALE: 3" = 1'-0"
ROOF EDGE SECTION6
1/AD101
SCALE: 3" = 1'-0"
ROOF EDGE SECTION7
1/AD101
SCALE: 1 1/2" = 1'-0"
ROOF- WALL INTERSECTION DETAIL4
1/AD101
SCALE: 3"= 1'-0"
EQUIPMENT CURB FLASHING DETAIL10
1/AD101
SCALE: 3" = 1'-0"
HOT STACK/FLUE PIPE PENETRATION DETAIL11
1/AD101
SCALE: 3" = 1'-0"
PITCH POCKET DETAIL AT COLUMN BASE8
1/AD101
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2 ALL MATERIALS SHALL REMAIN UNLESS NOTED TO BE REMOVED.
SCALE: NTS
TYPICAL LIGHTNING ROD DETAIL12 SCALE: 3"=1'-0"
ROOF HATCH FLASHING DETAIL13
1/AD101
SCALE: 3"=1'-0"
EQUIPMENT RAIL CURB DETAIL14
1/AD101
SCALE: NTS
TYPICAL ELECTRICAL BOX CURB FLASHING DETAIL15
SCALE: 3"= 1'-0"
FAN UNIT CURB DETAIL16
1/AD101
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
115'-9"16'-4"
143'-1"
11'-1"
'-4
'-3
'-0
'-6
10'-8" 128'-5"
139'-0"
'-0
'-9
5'-
3"
'-6
6'- 8"
8'-0"
9 TYP
1111 11
6 1
1/4"/FT
1/4"/FT
1/4 "/F
T
1/4"/FT
1/4 "/F
T
1/4 "/F
T
RTU-1 RTU-2 RTU-3 RTU-4
LOW ROOF,
NOT IN CONTRACT
LINE OF LOWER
ROOF BELOW
1/4"/FT
1/4"/FT
1/4"/FT
21 22
21 22
21 22
21 22
36'-0" 32'-0"
24'-0" 24'-0"
'-0
'-0
'-0
'-0
HP
HP
HP
HP
LP
LP
HP
HP
HP
HP
A-501
A-501
A-501
A-502
A-501
A-502
A-501
A-501
A-501
A-501
A-501
A-502
A-502
A-501
A-502
A-501
A-501
A-501
A-501
A-501
24 24
1'-1 1/2"
1'- 1 1
/2" 1'-
1 1 /2"
1'-1 1/2"
1'-1 1/2"
1'- 1 1
/2"
1'- 1 1
/2"
1'-1 1/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL - BLDG 6 ROOF
PLAN
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26 A-101
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 3/16" = 1'-0"
ARCHITECTURAL PLAN-BLDG 6 ROOF PLAN1
KEYPLAN
BLDG 6
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. WOOD BLOCKING TO REMAIN UNLESS NOTED OTHERWISE.
KEYED NOTES
1 NEW ALUMINUM COPING. REFER TO DETAILS 8/9/10/A501.
2 REINSTALL ROOF HATCH,GUARDRAILS, AND DOOR. REFER TO 5/A501.
3 EXISTING ROOF FAN AND CURBS, FLASH NEW ROOF INTO EXISTING CURB. REFER TO
DETAIL 8/A502.
4 RELOCATE SATELLITE AND ELECTRICAL CONNECTION BOX ON 32"x32" METAL STAND
SUPPORT BALLASTED WITH (8) BLOCKS. NOTE THAT THESE UNITS INCLUDE
ELECTRICAL WIRING ON RUBBER CONDUIT BLOCKS.
5 NEW FLASHING AND COUNTER FLASHING AT HIGH-LOW CONDITION. REFER TO DETAIL
2/A502.
6 NEW MODIFIED SBS BITUMINOUS ROOFING SYSTEM AND COVERBOARD OVER
EXISTING INSULATION. REFER TO DETAIL 3/A502.
7 NEW FLASHING AT WASTE VENT PIPES REFER TO DETAIL 2/A501.
8 NEW ROOF DRAIN, FLASHING, AND STRAINER, CONNECT INTO EXISTING DRAIN PIPING.
REFER TO DETAIL 1/A501.
9 PITCH POCKETS AT SCREEN WALL COLUMN SUPPORTS. REFER TO DETAIL 7/A502.
10 EXISTING A/C CURB RAILS, FLASH INTO NEW ROOF. REFER TO DETAIL 7/A501.
11 NEW CURB FLASHING AT HVAC EQUIPMENT. THE ROOF CURBS ARE TO REMAIN.
REFER TO DETAIL 6/A501.
12 NEW ALUMINUM ROOF SCUPPER. REFER TO DETAIL 5/A502.
13 REINSTALL TEMPORARY SUPPORTS TO ALLOW EXISTING PIPE AND ELECTRICAL
CONDUIT SUPPORTS TO REST ON ROOF.
14 FLASH EXISTING ELECTRICAL CURB BOX. REFER TO DETAIL 6/A501.
15 FLASHING INTO FLUE PIPE. REFER TO DETAIL 3/A501.
16 LOOSE CABLES TO EXISTING ROOF EQUIPMENT TO REMAIN.
17 NEW ROOF CRICKETS.
18 EXISTING MECHANICAL SCREEN WALL TO REMAIN.
19 NEW SQUARE ALUMINUM DOWNSPOUT TO LOWER ROOF
20 NEW CONCRETE SPLASH BLOCK. REFER TO DETAIL 6/A502.
21 FALL PROTECTION ANCHOR. REFER TO DETAIL 1/A-502.
22 CONTRACTOR TO COORDINATE CEILING ACCESS WITH VA PERSONNEL FOR FALL
PROTECTION ANCHOR INSTALLATION.
23 PERIMETER HIGH POINT.
24 EXTERIOR WALL AROUND PERIMETER.
25 PROTECT ROOF HATCH OPENING PRIOR TO GUARDRAILS GETTING REINSTALLED.
26 WALKING PAD 36" WIDE UNLESS OTHERWISE NOTED.
27 CENTER WALKING PATH THROUGH OPENING .
28 STRUCTURE IS FLAT.
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text N
6.36.24.115.9
LX.A
LX.A.4
A.4.1
LX.A.7
LX.B
LX.B1
LX.B.3
LX.B.4
B.7
LX.B.9
LX.B.5
LX.C
115'-9"16'-4"
143'-1"
11'-1"
'-4
'-3
'-0
'-6
10'-8" 128'-5"
139'-0"
'-0
'-9
5'-
3"
'-6
6'- 8"
8'-0"
1/4"/FT1/4"/FT
1/4 "/F
T
1/4 "/F
T
1/4 "/F
T
RTU-1 RTU-2 RTU-3 RTU-4
LOW ROOF,
NOT IN CONTRACT
1/4"/FT
1/4"/FT
1/4"/FT
1/4"/FT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL - BLDG 6 ROOF
PLAN BID DEDUCT ALTERNATE
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26 A-102
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 3/16" = 1'-0"
ARCHITECTURAL PLAN- BLDG 6 ROOF PLAN BID DEDUCT ALTERNATES1
KEYPLAN
BLDG 6
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. THE CONTRACTOR IS TO PERFORM WORK SO AS NOT TO VOID THE WARRANTY OF THE
EXISTING ROOF SYSTEM TO REMAIN.
ALTERNATE NUMBER - 1
SUBSTITUTE EPDM MEMBRANE ROOFING SYSTEM IN LIEU OF THE MODIFIED SBS
BITUMINOUS ROOF SYSTEM AS DESCRIBED IN DETAIL IN THE SPECIFICATIONS. THIS
WILL INCLUDE THE MAIN ROOF, AND THE HIGH ROOF AT THE NORTHWEST PORTION OF
THE BUILDING. THE LOW RADIUS ROOF AT THE SOUTH EAST PORTION OF THE
BUILDING IS NOT TO BE INCLUDED AND NOT IN THIS CONTRACT. THE ROOF DETAILS
ON A-501, A-502, AND A-503 SHOULD BE USED AS A GUIDE FOR THE EPDM ROOFING
FLASHING AND OTHER CONSTRUCTION DETAILS.
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text N
FINISHED SECOND FLOOR
TOP OF PERIMETER STEEL
FINISHED FIRST FLOOR
100.00'
114.00'
128.17'
TOP OF STEEL
137.75'
6.3
6.2LX.5.8
5.95.4LX.5LX.4LX.3LX.21.6LX.1 A B4.11
EXISTING CAST STONE VENEER
EXISTING MECHANICAL SCREEN
EXISTING FACE BRICK
APPROXIMATE FINISH GRADE
EXISTING WINDOWSEXISTING ALUMINUM/GLASS
CURTAIN WALL SYSTEM
EXISTING OPENING AT
MECHANICAL SCREEN
FINISHED FIRST FLOOR
100.00'
FINISHED SECOND FLOOR
114.00'
TOP OF PERIMETER STEEL
128.71'
TOP OF STEEL
137.75'
6.3
6.2 LX.5.8LX.6
5.9 5.4 LX.5 LX.4 LX.3 LX.2 1.6 LX.1
LX.1.4
LX.2.2AB 4.11
APPROXIMATE FINISH GRADE
EXISTING CAST STONE VENEEREXISTING ALUMINUM/GLASS
CURTAIN WALL SYSTEM
EXISTING MECHANICAL SCREEN
EXISTING FACE BRICK
EXISTING DOOREXISTING DOOREXISTING DOOR
FINISHED FIRST FLOOR
100.00'
FINISHED SECOND FLOOR
114.00'
TOP OF PERIMETER STEEL
128.71'
TOP OF STEEL
137.75'
LX.A A.4.1 LX.B LX.CB.7
EXISTING WINDOWS
EXISTING FACE BRICK
EXISTING MECHANICAL SCREEN
EXISTING CAST STONE VENEER
EXISTING ALUMINUM/GLASS
CURTAIN WALL SYSTEM
APPROXIMATE FINISH GRADE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL ELEVATIONS BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26 A-201
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 1/8" = 1'-0"
NORTH ELEVATION1
SCALE: 1/8" = 1'-0"
WEST ELEVATION2
SCALE: 1/8" = 1'-0"
EAST ELEVATION3
KEYPLAN
BLDG 6
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2.
BUILDING ELEVATIONS ARE PRIMARILY PROVIDED TO SHOW THE EXISTING MATERIALS
AND THE DOORS INTO THE BUILDING WHICH WILL NEED TO BE PROTECTED DURING
CONSTRUCTION. REFER TO STAGING PLAN FOR DOOR PROTECTION DETAILS.
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
RETROFIT DRAIN BODY
REPLACE DRAIN AND
STRAINER
MECHANICAL WATERTIGHT
CONNECTION SEAL
NEW ALUMINUM
STRAINER DOME
NEW METAL STUD WITH
SELF-LOCKING NUT
NEW ALUMINUM CLAMPING
RING
EXISTING INSULATION
4" DIA O.D.
ROOF DRAINS
EXISTING 1 1/2"
METAL DECK
30"x30", 2.5 LB-4LB LEAD OR COPPER FLASHING SET ON THE
FINISHED ROOF IN ELEVATE MULTI-PURPOSE MB
FLASHING CEMENT(PRIME TOP SURFACE BEFORE STRIPPING)
REFER TO ROOF ASSEMBLY
FOR ROOF DETAILS
MODIFIED SBS BITUMINOUS
ROOF SYSTEM (TYPICAL BASE BID)
MODIFIED BITUMEN GRANULE
SURFACED CAP SHEET PROTECTION
LAYER ADHERED IN MULTI-PURPOSE
MB FLASHING CEMENT
OR HEAT WELDED
MODIFIED SBS BITUMINOUS
ROOF SYSTEM POURABLE SEALANT
REATTACH GROUND
WIRE TO ROOF
REINSTALL AIR TERMINAL
PROVIDE SIMILAR ATTACHMENT FOR CABLES
EXISTING INSULATION
8 1 /16
"M
IN
MODIFIED BITUMEN GRANULE
SURFACED CAP SHEET
EXISTING WOOD BLOCKING
EXISTING CURB
RUN FLASHING OVER CURB
NEW 1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS
ROOF SYSTEM
3" MIN
FASTEN 8" O.C.
EXISTING ROOF HATCH
REINSTALL ROOF HATCH SAFETY
RAILS AND DOOR 3 SIDES OF ROOF HATCH
4" MIN 2" MIN
2" M
IN
LIQUID FLASHING
(30 MIL WET THICKNESS)
FABRIC FLASHING
FLASHING FABRIC
LIQUID FLASHING
(30 MIL WET THICKNESS)
SBS PREMIUM CAP SHEET
BASE AND PLY SHEETS
6 " M
IN
2"
M
IN
PE
NE
TR
AT
IO
N
2"
2"
1'- 0"
6" MIIN
ELEVATE AP SEALANT
UNIT COUNTERFLASHING (EXISTING)
3" (76 mm) COUNTER-FLASHING EXTENDER-FASTEN 12" (305 mm) O.C. WITH ELEVATE FASTENER & SEALING WASHER
PREPARE SUBSTRATE AS REQUIRED PRIOR
TO APPLICATION OF AC PRIMER & AC FAST FR
(1) PLY MEMBRANE FLASHING EXTEND 12" MINIMUM
HORIZONTALLY ONTO ELEVATE MODIFIED BITUMEN ROOF MEMBRANE
CONTINUOUS BEAD OF SEALANT REQUIRED IF GAP
BETWEEN EDGE OF MODIFIED MEMBRANE & WALL
GREATER THAN 1/16" (TYPICAL)
ASSURE FULL CONTACT OF BOTH LAYERS WITH
SUBSTRATE & FULL SATURATION OF AC FLEECE 120
CONTINUOUS 4" WIDE STRIP OF FLASHING
MEMBRANE AT WALL TO DECK TRANSITION
NEW 1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS
ROOF SYSTEM
EXISTING 1 1/2" METAL DECK
INSTALL NEW BAND
FLUE PIPE TO REMAIN
NEW 1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS
ROOF SYSTEM
INSULATION TO REMAIN
NEW FLASHING
CAULK OVER BAND
6"
EXISTING WATER SHROUD
1'- 0"
M
IN
3" MIN
EXISTING ROOF EQUIPMENT
EXISTING SHEET METAL COVER TO REMAIN
1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS
ROOF SYSTEM
FLASHING
MODIFIED BITUMEN CAP SHEET
UNSCREW METAL FLASHING,
INSTALL NEW FLASHING UNDER
METAL FLASHING
NEW HIGH-DOMED, CAPPED, GASKETED
FASTENERS AS REQUIRED
EXISTING WOOD BLOCKING TO REMAIN
STRUCTURAL STEEL
EXISTING 2x8 PT WOOD BLOCKING
CAST STONE
NEW ALUMINUM WRAP
ON FASCIA AND SOFFIT
NEW 1/4" COVER BOARD AND MODIFIED
SBS BITUMINOUS ROOF, EXTEND
MEMBRANE TO EDGE STRIP
NEW 3" CANT STRIP
NEW ALUMINUM COPING AND
CONTINUOUS EDGE STRIP
TOP OF NEW BLOCKING
PROVIDE WOOD BLOCKING TO
MATCH TOP OF FASCIA BOARD
NEW 2x10 PT WOOD BLOCKING
SEALANT
(2) NEW 2x10 PT WOOD BLOCKING
ROOF TO TERMINATE AT FACE
VARIES
9 1 /2"
1'- 0 1
/2"
NEW 2x6 PT WOOD BLOCKING
1 1/2" METAL DECK ON
STRUCTURAL STEEL
EXISTING INSULATION
PROVIDE ANCHORAGE IN MULTIPLE LAYERS
NEW SEALANT AND
BACKER ROD
STRUCTURAL STEEL
1 1/2" METAL DECK
ON STRUCTURAL STEELEXTENDED JOIST SEAT
NEW ALUMINUM WRAP
ON FASCIA AND SOFFIT
EXISTING INSULATION
NEW 1/4" COVER BOARD AND MODIFIED
SBS BITUMINOUS ROOF, EXTEND
MEMBRANE TO EDGE STRIPNEW 3" CANT STRIP
NEW ALUMINUM COPING AND
CONTINUOUS EDGE STRIP
(2) NEW 2x10 PT WOOD BLOCKING
TOP OF NEW BLOCKING
NEW 2x6 PT WOOD
BLOCKING
PROVIDE WOOD BLOCKING
TO MATCH TOP OF FASCIA BOARD
SEALANT
NEW 2x10 PT WOOD BLOCKING
1'- 0 1
/2"
9 1 /2"
PROVIDE ANCHORAGE IN MULTIPLE LAYERS
ROOF TO TERMINATE AT FACE
2 1/4"x8" CURTAIN WALL SYSTEM
NEW 2x10 PT WOOD BLOCKING
1 1/2" METAL DECK ON
STRUCTURAL STEEL
STRUCTURAL STEEL
NEW ALUMINUM WRAP
ON FASCIA AND SOFFIT
EXISTING INSULATION
NEW 1/4" COVER BOARD AND MODIFIED
SBS BITUMINOUS ROOF, EXTEND
MEMBRANE TO EDGE STRIP
NEW 3" CANT STRIP
(2) NEW 2x10 PT WOOD BLOCKING
TOP OF NEW BLOCKING
NEW 2x6 PT WOOD BLOCKING
PROVIDE WOOD BLOCKING
TO MATCH TOP OF FASCIA BOARDSEALANT
NEW ALUMINUM COPING AND
CONTINUOUS EDGE STRIP
1'- 0 1
/2"
TRESPA PANEL WALL SYSTEM 1 5/8"
9 1 /2"
PROVIDE ANCHORAGE IN MULTIPLE LAYERS
NEW SEALANT AND
BACKER ROD
ROOF TO TERMINATE AT FACE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL SECTIONS &
DETAILS
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26 A-501
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: 1"=1'-0"
RETROFIT ROOF DRAIN DETAIL1
1/A-101
SCALE: NTS
TYPICAL LIGHTNING ROD DETAIL4 SCALE: 3"= 1-0"
ROOF HATCH FLASHING DETAIL5
1/A-101
SCALE: 3"=1'-0"
ROOF VENT DETAIL2
1/A-101
SCALE: 3"= 1'-0"
EQUIPMENT CURB FLASHING DETAIL6
1/A-101
SCALE: 3"=1'-0"
HOT STACK/FLUE PIPE FLASHING DETAIL3
1/A-101
SCALE: 3"= 1'-0"
EQUIPMENT RAIL CURB DETAIL7
1/A-101
SCALE: 3"= 1'-0"
ROOF EDGE SECTION8
1/A-101
SCALE: 3"= 1'-0"
ROOF EDGE SECTION9
1/A-101
SCALE: 3"= 1'-0"
ROOF EDGE SECTION10
1/A-101
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. ALL MATERIALS ARE NEW UNLESS NOTED AS EXISTING.
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING ROOF INSULATION
STRUCTURAL STEEL
1 1/2" METAL DECK
ON STRUCTURAL STEEL
STRUCTURAL STEEL "C"
CHANNEL ON BEAM
NEW FLASHING AND COUNTER FLASHING
SEALANT OVER COUNTER FLASHING
EXISTING STONE VENEER
STEEL BEAM EXISTING 1 1/2" SLOPED
METAL DECK
EXISTING INSULATIONNEW 1/4" COVER BOARD
AND MODIFIED SBS
BITUMINOUS ROOF 1/4"/FT
EXISTING METAL DECK IS FLAT
AT NEW HIGH ROOF
3" MINIMUM
1/8" MINIMUM
BLEED-OUT REQUIRED
NEW 1/4" COVER BOARD
AND MODIFIED SBS
BITUMINOUS ROOF
NEW MULTI-PURPOSE
FLASHING CEMENT
NEW INTERPLY FLASHING
NEW ALUMINUM COPING AND EDGE STRIP
ALL SHEET METAL IS TO BE INSTALLED PER SMACNA GUIDELINES
NEW CANT STRIP
THIS IS A GENERAL INSTALLATION DETAIL,
FOLLOW MANUFACTURES INSTRUCTIONS
CONTINUOUS GRAVEL OVER CANT STRIP
CONTINUE OVER CANT STRIP
20"
12"
3"
12"
1/2" 9" 1/2"
CONCRETE
DIMENSIONS MAY VARY
10"
3" WIDE ROOF FLANGE
7"
24"
ALUMINUM ROOF SCUPPER
4"x4" DOWNSPOUT CONNECTION
REFER TO SECTION FOR
FLASHING OVER FLANGE
1"
4"
ISOMETRIC
DOWNSPOUT NOT SHOWN FOR CLARITY
ROOFING MEMBRANE
NEW STORM WATER
COLLECTOR BOX AND
DOWNSPOUT
3" MIN 3" MIN 3" MIN
PRIME FLANGE & SET IN ELEVATE
MULTI-PURPOSE MB FLASHING CEMENT
MODIFIED BITUMEN ROOF
FASTENERS AT 3"
O.C. STAGGERED INTERPLY
/16
7"
DETAIL 8/A501 BEYOND
NEW PT BLOCKING AND FASCIA
1 1/2" METAL DECK
ON STRUCTURAL STEEL
NEW 1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS ROOF
EXISTING INSULATION
SECTION
HOLD OFF DOWNSPOUT BRACKET
(2) TYP
TOP OF SCUPPER
NEW 2x6 TREATED WOOD BLOCKING
NEW ALUMINUM WRAP ON FASCIA
AND SOFFIT
NEW PITCH POCKETS
6x6 COLUMN TO REMAIN
EXISTING 1 1/2" METAL DECK
INSULATION TO REMAIN
NEW 1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS
ROOF SYSTEM
EXISTING SCREEN PANELS
VA
IR
ES HEIGHT VARIES FROM 6"
AT HIGH ROOF TO 1 1/2"
AT LOW ROOF
FLASH PITCH POCKETS
INTO ROOF
8" MI
N
METAL EXHAUST FAN COVER TO BE
REMOVED AND REINSTALLED
HPR FLASHING FASTENED 8" OC
HPR MODIFIED MEMBRANE
FLASHING PLY 9" MINIMUM ON
FIELD
BASE FLASHING PLY 6"
MINIMUM ON FIELD
EXISTING 1 1/2"
METAL DECK
INSTALL FLASHING
UNDER FAN BASE
PREMOLDED PIPE SEAL
INNER CUT OFF MASTIC
BASIS OF DESIGN "FRONTLINE
ANCHOR 70870-L16FL
LAP SEALANT
CAP SPLICE
SPLICING CEMENT
1'- 6"
6 3 /8"
MI
N
CONNECTION POINT FALL PROTECTION ANCHOR 18" HIGH 4"
Ø SCH 40 PIPE WITH PLATE ON BOTTOM
THROUGH BOLTED TO PLATE BELOW
(8) 1/2" HEX NUT THROUGH BOLTED
TO BOTTOM OF DECK WITH LOCK
NUTS AND WASHERS
11"x11x5/8" THICK PLATE
ATTACHED TO ANCHOR
REMOVE INSULATION AT NEW FALL
PROTECTION ANCHORS, REPLACE WITH
NEW INSULATION. APPROXIMATELY 2'x2'
EXISTING INSULATION
8"
MI
N NEW CANT STRIP
MODIFIED BITUMEN GRANULE
SURFACED CAP SHEET
EXISTING WOOD BLOCKING
EXISTING CURB
BEND FLASHING OVER THE TOP OF
THE CURB AND REINSTALL COVER
NEW 1/4" COVER BOARD AND
MODIFIED SBS BITUMINOUS
ROOF SYSTEM
3" MIN
REFASTEN WITH SCREWS
(2) ON EACH SIDE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECTURAL SECTIONS &
DETAILS
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26 A-502
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
SCALE: NTS
TYPICAL ROOF ASSEMBLY DETAIL3SCALE: 1-1/2" = 1'-0"
ROOF- WALL INTERSECTION DETAIL2
1/A101 SCALE: NTS
TYPICAL EDGE FLASHING4
SCALE: NTS
TYPICAL ROOF SCUPPER DETAIL5 SCALE: 1 1/2"= 1'-0"
SPLASH BLOCK DETAIL6
1/A101
SCALE: NTS
TYPICAL PITCH POCKET DETAIL AT COLUMN BASE7
SCALE: 3"= 1'-0"
FAN UNIT CURB DETAIL8
1/A101
SCALE: 1-1/2"=1'-0"
FALL PROTECTION TIE DOWN DETAIL1
1/A-101
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. ALL MATERIALS ARE NEW UNLESS NOTED AS EXISTING.
SCALE: NTS
TYPICAL ELECTRICAL BOX CURB FLASHING DETAIL9
9/26/2023
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GN
D
GN
D
GN
D
GND
GND GND
GND
GND GND GND GND GND GND GND GND GND GND
GN
D
GN
D
GN
D
GND
GN
D
GND GND GND GND GND GND GND GND GND GND GND GND GND GND
GN
D
GN
D
GND
GN
D
GN
D
GN
D
GND
AT
AT
AT
AT
AT
AT
AT
AT AT
AT
AT
AT
AT
AT
AT AT AT AT AT AT
ATATATATAT
GND GND GND GND GND GND
GND
GND
GND
GND
GND
GND
GND
GND
GND GND
GN
D
GN
D
LX.2.2 LX.3LX.21.6LX.1.4LX.1 LX.4 LX.5 A 5.4 LX.5.8 LX.6 B
6.36.24.115.9
LX.A
LX.A.4
A.4.1
LX.A.7
LX.B
LX.B1
LX.B.3
LX.B.4
B.7
LX.B.9
LX.B.5
LX.C
GN
D
GND
GN
D
GN
D
GND
34 2
2 2 2
RTU-1 RTU-2 RTU-3 RTU-4
LOW ROOF,
NOT IN CONTRACT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ELECTRICAL LIGHTNING
PROTECTION PLAN
BID ISSUE DOCUMENTS
A/E DESIGN, REPLACE LEARNING
EXCHANGE ROOF
10701 EAST BLVD.
CLEVELAND, OHIO 44106
2023/09/26
EG101
541-23-202
GHR LAJ
REV 0 - BID ISSUE DOCUMENTS 2023-09-26
GENERAL NOTES
1. SEE GI002 FOR NOTES AND LEGENDS.
2. REATTACH ALL (AT) AIR TERMINALS, LIGHTNING PROTECTION CABLES, SPLICES,
PLATES, ETC. TO THE NEW ROOF.
3. RTU-1 THROUGH 4 HAS (2)…
This is the start of the file's text. The full file is on GovTribe.