USArmyCorpsofEngineers
OmahaDistrict
API653Out‐of‐Service
InspectionReport
DyessAFB,TX
FacilityNumber5220
TankNumber5220

US Army Corps of Engineers Center of Expertise for Petroleum, Oils, and Lubricants

(USACEPOL‐TCX)
May11,2017

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

Table of Contents

ACRONYMS AND ABBREVIATIONS

GENERAL SUMMARY

INSPECTION DATE

STATE REGULATIONS

PREVIOUS INSPECTION DATES

RECOMMENDED FUTURE INSPECTION DATES (CALCULATIONS SHALL BE PROVIDED)

GENERAL TANK INFORMATION

A. GENERAL PROJECT INFORMATION

1. API 653 Inspection

2. Site Information

B. TANK INSPECTION COMMENTS

1. Tank Construction

2. Tank Foundation

3. Tank Bottom

4. Tank Shell

5. Tank Appurtenances

6. Tank Coating

7. Tank Piping System

8. Fire Protection System

9. Secondary Containment

10. Cathodic Protection

C. FINDINGS AND RECOMMENDATIONS

1. MANDATORY REPAIRS per API 653, UFC 3‐460‐01, or AW 78‐24‐27 Standards

2. REQUIRED REPAIRS to Fully Comply with API 653, or, Federal, State, and Local Codes

3. RECOMMENDEDREPAIRStofullycomplywithUFC3‐460‐01&AW78‐24‐27StandardsorasPartof
RegularMaintenance .................................................................................................................................................. 18

APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS ................................................................................... A‐1

APPENDIX B: 3‐D DOCUMENTATION AND ANALYSIS .................................................................................................... B‐1

APPENDIX C: API 653 CHECKLISTS FOR TANK INSPECTIONS ...................................................................................... C‐1

APPENDIX D: PHOTOGRAPHS .......................................................................................................................................... D‐1

APPENDIX E: AS‐BUILT DRAWING OF TANK 5220………………………………………………………………………………………………………….E‐1

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

ACRONYMS AND ABBREVIATIONS

API American Petroleum Institute

ASME American Society of Mechanical Engineers

ASNT American Society of Non‐Destructive Testing

ARD Anti‐rotation device

ATG Automatic Tank Gauge

BBL Barrel

CFR Code of Federal Regulations

CP Cathodic Protection

DFT Dry Film Thickness

HLA High Level Alarm

HLCS High Level Control Shutoff

HHLA High‐High Level Alarm

LLA Low Level Alarm

LLLA Low‐Low Level Alarm

MFL Magnetic Flux Leakage

MT Magnetic Particle Testing

NACE National Association of Corrosion Engineers

NDT Non‐Destructive Testing

NFPA National Fire Protection Association

PSI Pounds per Square Inch

PT Penetrant Testing

P/V Pressure/Vacuum

RP Recommended Practice

PST Product Saver Tank

RT Radiography Testing

TML Thickness Measurement Location

TRV Thermal Relief Valve

UFC Unified Facilities Criteria

UFGS Unified Facilities Guide Specifications

ULS Ultra Low Sulfur

UT Ultrasonic Testing

VT Visual Testing

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

GENERALSUMMARY
SummaryofInspection
AnAPIStandard653Out‐of‐ServiceinspectionofTank#5220(Facility5220)atDyessAirForceBase
wascompletedonMay11,2017toevaluatethetank’sintegrity,collectdata,andestablishadatabasefor
futureinspectionsandevaluations.Aservicelifeevaluationperformedonthetankshowsitashaving
greaterthan30yearsofremainingshelllifeundercurrentconditions.Thebottomlifeevaluation
performedonthetankshowsitashavinggreaterthan20yearsofremaininglifeafterpatchplaterepairs
arecompletedonthebottom.InspectionResultsarelistedinSectionC.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

INSPECTIONDATE
APIOut‐of‐Service(Internal)InspectionDate:11May2017

Equipment (s) Used:

Manufacturer:GeneralElectric
Model:DMSGo+
CalibrationMethodsUsed:ZeroingProcedure,CopperCoatingCalibrationProcedure,andTwoPoint

Calibration Procedure

Manufacturer:MFEEnterprises
Model:2412MarkI
CalibrationMethodsUsed:Sensitivityadjacentonmanufacturersuppliedtestplatewithsimulated

anomalies and notch

Manufacturer:LeicaGeosystem
Model:3DDisto
CalibrationMethodsUsed:Tiltsensorcalibrationautomaticallyperformedwithunitsetat<3°and

crosshairs calibration using target at a distance > 25 m

Inspector(s): Daniel Bailey

STATEREGULATIONS
StateRegulationforAPIIn‐ServiceTankInspectionsN/A
StateRegulationforAPIOut‐of‐ServiceTankInspectionsN/A
NOTE:Iftherearenostateregulationsfortankinspections,N/Ashallresidein‐placeofthenumberofyears
betweeninspections.Ifstateregulationsreside,therecommendedfutureinspectiondatesshallbebasedon
whicheverismorestringentbetweentheAPIinspector’scalculationsandthestateregulations.
PREVIOUSINSPECTIONDATES
APIOut‐of‐Service(Internal)InspectionDate:5January2008
APIIn‐Service(External)InspectionDate:27January2015
RECOMMENDEDFUTUREINSPECTIONDATES(CALCULATIONSSHALLBEPROVIDED)
APIOut‐of‐Service(Internal)InspectionDate:11May2037
APIIn‐Service(External)InspectionDate:11May2022
UFCOut‐of‐Service(Internal)InspectionDate:11May2027

Daniel Bailey Inspector

InterSpec,LLC
API653CertifiedInspectorNo.56207

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

GENERAL TANK INFORMATION

ITEMDESCRIPTION
OwnerDyessAirForceBase
LocationDyessAirForceBase
FacilityNumber5220
TankNumber5220
State/CountryTexas/USA
CityAbilene
InspectionDate11May2017
TankManufacturerChicagoBridge&IronCompany
DesignStandardAPI650,7thEdition
DateofConstruction1986
TankContentsJet‐A
TankSerialNumberNA
TankDiameter43’6”
ShellHeight42’3”
NormalFillLevel34’6”
NominalCapacity10,000BBL
FoundationConcreteRingwall

Construction

Bottom Lap‐Welded (Cone‐Down)

Shell Butt‐Welded (Cylindrical)

Floating Roof Steel Floating Pan

Fixed Roof Self‐Supported Cone

Material

Bottom Carbon Steel A‐36 M

Shell Carbon Steel A‐36 M

Floating Roof Carbon Steel A‐36 M

FixedRoofASTMA36
CathodicProtectionNone
InteriorCoatingSystemThinFilmEpoxy
ExteriorCoatingSystemThingFilmEpoxy/Polyurethane
LevelGaugingHoneywellEnrafATGwithVarec2500MechanicalTapeGauge
OverfillProtectionAutomaticShut‐Off(Setat37’4‐3/4”)
PipingReceipt8"CarbonSteel
Issue18"CarbonSteel
LowSuction4"CarbonSteel
WaterDraw‐Off1"CarbonSteel

Level Alarms

Low‐LowLevelAlarm:2’0‐1/8”
Low‐LevelAlarm:3’0‐3/16”
High‐LevelAlarm:37’2”
High‐LevelControlValve:37’4‐3/4”
High‐HighLevelAlarm37’6‐5/16”

Type of Internal Floating Roof

Internal Steel Floating Pan w/ Landing Actuated Vent

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

A. GENERAL PROJECT INFORMATION

1. API653Inspection
ThisprojectwillperformAPI653inspectionsofvarioustanksatfacilitiesthroughouttheUnitedStates.
Additionalconsiderationisgiventofederal,state,andlocalregulations,aswellasapplicablemilitary
criteriaandgeneralindustrystandards.

An API Standard 653 Out‐of‐Service (Internal/External) inspection was performed for Tank 5220.

2. SiteInformation
OnMay11,2017,Burns&McDonnellandoursub‐consultant(InterSpec)performedanAPI653Out‐
of‐Service(InternalandExternal)inspectionofTank5220(Facility5220)atDyessAirForceBase,
Texas.DyessAFBisa6,409acrebasewithover13,000militaryandcivilianpersonnelandishometo
the7thBombWing.ThebaseislocatedinthesouthwestcornerofAbilene,TXandisabout200miles
westofDallas.Thebaseemploysmorethan5,000people,makingitthesinglelargestemployerinthe

area.

Inadditiontobulkstorage,Tank5220isoneoffouraboveground,operatingstoragetanksforjetfuel
supportingtheinstallationfuelingneeds.

B. TANK INSPECTION COMMENTS

1. TankConstruction
Tank5220isanominal10,000BBL,43’6”diameterby42’3”tall,F‐24(JetFuel),abovegroundvertical
storagetank.ThetankwasconstructedbyChicagoBridgeandIronin1986toAPIStandard650,under
contractNo.S‐5901.ThetankhadsomemodificationstoexistingnozzlescompletedbyCAPEin2008,
underJobNo.60022.006.500.Theas‐builtdrawingsforthetankwerenotavailableforreviewatthe
timeoftheinspection,butanas‐builtdrawingwaslaterprovidedandisincludedinAppendixE.
2. TankFoundation
Thetanksitsonaconcreteringwallfoundationelevatedapproximately4"abovethecontainmentfloor.
Theringwallincludesasandfilledsupportingmediumdesignedwithaleakdetection(tell‐tale)system.
Accessiblesectionsofthefoundationwerevisuallyevaluatedduringtheinspectionforbroken
concrete,spalling,cracks,andvegetationagainstthebottomofthetank.Nospallingandvegetation
werepresent.Thefoundationtochimeinterfaceissealed.Shellsettlementsurveyswereperformed
duringtheinspectioninaccordancewithAnnexBofAPIStandard653.Settlementresultsarelistedin
AppendixA.Thereisnoindicationofsignificantsettlement.Overall,thefoundationisinsatisfactory

condition.

3. TankBottom
ThebottomisconstructedfromcarbonsteelmaterialwithASTMA36materialspecification.The
bottomisacone‐downdesign,lap‐weldedtogether,consistingoftwenty(20)plateslap‐welded
togetherandfillet‐weldedtotheshell.Thebottomhasathinfilminteriorliner.Theinteriorcoating
wasevaluatedfordis‐bonding,adhesion,deterioration,anddiscolorationandwasfoundtobemostly
insatisfactorycondition,withsomedeficiencieslistedbelow.Aclosevisualinspectionofallthe
welded‐onplateswasperformedforindicationsofcrackedwelds,crackedcoating,andcapillaryeffects

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

ofresidues.Dryfilmthickness(DFT)readingstypicallyrangedbetween12‐21mils.Withtheexception
oflocalcoatingrepairs,thetankbottomlining/coatingappearstobetheoriginalinstalledin1986.
Evaluatedthebottom,bottomwelds,andbottom‐to‐shellweldforcorrosion,withnoother
discrepanciesnoted.Performedamagneticfluxleakage(MFL)evaluationofthetankbottomto
determinetheconditionoftheunderside;ninety‐fivepluspercentwasscanned.Severalareas
indicatingundersidecorrosionwerelocatedandprovedup,seeSectionC(1)(a)belowandtheBottom
DrawinginAppendixAforlocationdata.Anultrasonicinspectionofthebottomsuggestsanoriginal
nominalthicknessof0.250".
4. TankShell
ThetankshellisconstructedofASTM36carbonsteelmaterial.Theshellisofcylindricaldesign,butt‐
weldedtogether,andconsistingoffive(5)courses.Evaluatedtheshellforplumbness,roundness,
peaking,andbanding;allofwhichwerefoundtobewithintheallowabletolerancesoftheAPIStandard
653.Visuallyinspectedboththeinteriorandexterioroftheshell.Inspectedthecoatingfordis‐
bonding,adhesion,deterioration,anddiscoloration.Thetankshellisequippedwithtwo30"manways
(oneofthembeingthe2ndcoursemanwaytoaccessthetopoftheIFR).Note:giventheIFRhighleg
position,theintermediatetankshellmanwayisobstructedbytheIFRanddoesnotprovidepractical
accesstothetopoftheIFRwhentheIFRislandedonthetankbottom.Thetankisequippedwithshell
mountedlow‐levelandhigh‐highlevelmercuryswitches,aswellasahigh‐levelshut‐off.Theshellwas
evaluatedforremainingmetalthicknessutilizingultrasonictechnology.Theultrasonicthickness
measurementsandthicknessmeasurementlocations(TML)arelistedintheShellPlateThickness
MeasurementstableinAppendixA.Aservicelifeevaluationperformedshowstheshellwithgreater
than30yearsofremaininglifeundercurrentconditions.Theengineeringcalculations,asperAPI
Standard653,fortheservicelifeevaluationareshowninAppendixAunder“ServiceLifeEvaluation.”
Thetankshellisinsatisfactorymechanicalcondition.
5. TankAppurtenances
a. InternalFloatingRoof
Thetankisequippedwithafullcontactsteelinternalfloatingpan.Theinternalfloatingroof
(IFR)islap‐weldedtogether,andconsistingofthirty(18)plateseach.ThetopIFRdeckis
accessibleviaanaccessladderfromthefixedroof.TheIFRisrestingapproximately97"
(measuredattheperimeter)abovethetankbottomandissupportedbynine(9)floating
rooflegs.A22‐inchcircularstrikerbearingplateisweldedtothetankbottomforeachIFR
supportleg.Evaluatedthestructuralintegrityofboththetopandundersideofthefloating
roof.Evaluatedtheconditionofthefloatingroofseals.TheprimaryIFRperimeterseal
(foamlog)andsecondaryperimeterseal(wiperseal)werefoundtobecompletely
deterioratedandwereremovedduringtheinspection.Sealsaroundthestillingwellsand
ladderwerealsofoundtobedeteriorated.TheIFRwasevaluatedforremainingmetal
thicknessutilizingultrasonictechnology.Theultrasonicthicknessmeasurementsand
thicknessmeasurementlocations(TML)arelistedintheShellPlateThickness
MeasurementstableinAppendixA.Measuredtheannularspaceatseverallocationsfrom
thetankbottom,andthefloatingroofisdeterminedtobeproperlycenteredinsidethetank.
TheIFRisequippedwithtwo12‐inchvacuumbreakerswithaguidedleglongenoughto

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

contactthetankbottom.Whenthelegcontactsthetankbottom,theguidedleg
mechanicallyopensthebreakerbyliftingthecoveroffthewell.
b. FixedRoof
Thefixedroofisaself‐supportedconeroof.Thefixedroofhasanepoxycoatingsystemon
theinteriorandanepoxy/polyurethaneexterior.Thecoatingwasinspectedfordis‐
bonding,adhesion,deterioration,anddiscoloration;itisinsatisfactorycondition.The
nominalthicknessofthefixedroofwas0.1875inches.Thefixedroofwasevaluatedfor
remainingmetalthicknessusingultrasonictechnology.Thefixedroofthicknessranged
fromaminimumof0.181inchestoamaximumof0.192inches.Theultrasonicthickness
measurementsandultrasonicthicknesslocations(TML)arelistedintheFixedRoofPlate
ThicknessMeasurementstableinAppendixA.Theroofhadareasofstandingwaterand
sediment,butnocoatingfailurewaspresent.

c. Gauging

Thetank’sEnrafServoATGisinstalledthroughafullyslotted8‐inchaluminumgaugewell.
Manualgaugingisperformedthroughthenon‐slotted8‐inchcarbonsteelwellattheIFR
accesshatch(onesideoftheIFRaccessladder).Thetankisalsoequippedwithafully‐
slottedaluminum8‐inchsamplegaugewellwithfloatingplug.Thetankisequippedwitha
mechanicalgaugemanufacturedbyVarec(Model2500).Thetapehasdetachedfromthe
floatingroofandisnolongerfunctioning.
d. LevelAlarms
Highandhigh‐highlevelmercuryswitchesaremountedontheshellbutarenotfully
accessibleviathecircumferentialmountedstairway.Thetankisalsoequippedwithlow
andlow‐lowlevelalarms.Automaticshut‐offisprovidedbyahigh‐levelcontrolvalvethat
actuatesahydraulicCLA‐VALcontrolvalveonthereceiptline.
e. StairsandPlatforms
Thetank’sfixedroofandinternalladderareaccessiblebyacircumferentialstairway
mountedontheshellofthetank.Thestairwaywasinspectedforcorrosionandstructural
soundness.Theoverallgeneralconditionofthestairsissatisfactory.TheIFRdeckis
accessibleviaahatchandaccessladderfromthefixedroof.Thereisalsoamanwayonthe
secondcoursetoaccesstheIFR,buttheIFRblockstheopeningwhenrestingonitslegs.The
legsoftheIFRareconfiguredtoalowlegposition,butaholeinthelegsfortheretainingpin
islackingtosecuretheleginthelowlegposition.Thestairwaywidthisextendedatthe
high‐levelalarms,butnoplatformisprovided,andthealarmsarenotaccessible.The
handrailconsistsofwelded2‐inchangle.Acoppergroundingbarforpersonnelstatic
electricdischargeismountedonthehandrail.

f. Grounding and Bonding

Therearefourgroundingcablesconnectedtolugsonthetank’sshell,andeachendis
mechanicallyfastenedtoagroundingrod.Theinternalfloatingroofisbondedtothetank.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

6. TankCoating
Theexteriorcoatingsappeartobeanepoxywithpolyurethanetopcoat.Theshell,interior,andfixed
roofarelighttanincolor.Theassociatedpipingwithinthesecondarycontainmentiscoatedwith
similartancoating.Therearenumerousexistingcoatingrepairsonthetankshell,butoverall,the
existingcoatingappearstobeinsatisfactorycondition,withminordeficienciesthatarenotedinthe
report.ThetankinternalandIFRliningappeartobeathinfilmepoxy.
7. TankPipingSystem
Thefuelisreceivedthrough8‐inchcarbonsteelpipingthatisfittedwithaninletdiffuser.Thediffuser
isrolledtoacirculartransition,withafinaloutletdiameterofNPS12.Theproductisissuedfromthe
tankthroughan18‐inchcarbonsteelpipethatextendstothecentersumpinsidethetank.Other
auxiliarypipingforthewaterdraw(NPS1)andlowsuction(NPS4)areinstalled,andbothextendto
thecentertankbottomsump.InspectedandevaluatedeachtanknozzleinaccordancewithAPI
Standards650and653.Identifiedthetypeanduseofeachshellnozzleandmeasuredthenozzleneck
thicknessonallaccessibleshellnozzles.Evaluatedallnozzlesandreinforcementplatesforleaksand

corrosion.

8. FireProtectionSystem
Thetankpreviouslyhadafoamfireprotectionsystemthathasbeenmostlyremoved.Partofthepiping
stillexistsatthetopofthetank,andtheportionwheretheverticalpipingcomingdownthetankshell
wasremoved,nowformsadeadlegthatmayexperienceacceleratedcorrosionifwaterandresiduestill
remainintheline.
9. SecondaryContainment
Thetanksitsinsideaconcretesecondarycontainmentareawithverticalslopedconcretedikewalls.
Theoveralldimensionofthesecondarycontainmentis103feetx103feetwithabermheightof
approximately60‐inches.Thesecondarycontainmentisequippedwitha24"x24"draininlet/sump
andalockeddrainvalve.Thedrainlineisa5‐inchx6‐inchovalcut‐outinthesump.Thedraininlet
washydrostaticallytestedforintegritybyfillingtheinletwithwatertoalevelatleast1‐2inchesbelow
thetopoftheinletstructure.Thetestwasheldfor2hoursandthelevelofwaterdidnotchange;thus
thetestpassed.
Thesecondarycontainmentwasvisuallyevaluatedduringtheinspectionforbrokenconcrete,spalling,
cracks,andvegetationgrowth.Afewareaswerenotedwherepipingorequipmentpenetratesthedike
floorbutarenotsealed,bringingintoquestionthepermeabilityofthesecondarycontainmentarea.
Theseareasarelistedindeficienciesbelowundermandatoryrepairs.
Aformalsecondarycontainmentevaluation,inaccordancewith40CFR112,mayberequiredinorder
tosatisfyfederal,state,andlocalrequirements.Thesecondarycontainmentisequippedwithalockable
secondarycontainmentdrainvalve.
10. CathodicProtection
Thistankcurrentlydoesnothavecathodicprotectioninstalledtoprotectthetankbottomfrom

corrosion.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

C. FINDINGS AND RECOMMENDATIONS

Thetankisgenerallynotinaccordancewithcurrentmilitarycriteriaforsomeofthetankappurtenanceand
pipingconfiguration;theserecommendationsarenotmeanttobringthetankintofullcompliancewithUFC3‐
460‐01,orAW78‐24‐27standards,butrathertoidentifytheseitemsfortheowner/user’splanedupgrades,
rehabilitation,andpriorityrepairs.Mandatoryrepairsshouldbecompletedtoassurecompliancewith
industrystandards,aswellasfederalorstatejurisdictionalrequirements.
AllrepairsandmodificationsshouldbeperformedinaccordancewithAPIstandard653,UFC3‐460‐01,DoD
StandardDesign78‐24‐27,andapplicableUFGSspecifications.
1. MANDATORYREPAIRSperAPI653,UFC3‐460‐01,orAW78‐24‐27Standards
Mandatoryrepairsrepresentitemsthatrequireimmediateattention,inordertopreventimminentrisk
tosystemoperators,equipmentintegrity,ortheadjacentenvironment.Thetankshouldremainoutof
serviceuntiltheserepairsarecompleted.
a. MFLIndications
OBSERVATION:25areasofundersidecorrosionwerelocatedduringtheMFLevaluation.Remaining
thicknessesattheseareasrangedfrom0.188inchesremainingonplate18to0.099inchesremaining
onplate3.
REFERENCE:API‐653Table4.4
RECOMMENDATION:Areaswitharemainingthicknessunder0.160incheswillneedtoberepairedin
accordancewithAPI‐6539.10inordertoreachthe20‐yearinspectionintervalandstayabovethe
remainingthicknessrequirementof0.100inchinaccordancewithAPI‐653.Corrodedareasare
indicatedonthetankbottominredpaintmarkerandalsoonthedrawinglocatedinAppendixA
(Quantity:13areaslessorequalto0.160inch,1areacurrentlyunderAPIminimumof0.100inch).

Alternatively, consider replacing the bottom in accordance with API‐653 9.10.2.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

b. FloatingRoofPerimeterSeals
OBSERVATION:Theprimaryfoamlogsealforthefloatingroofwasfoundtobesaturatedwithfuel.
Thesecondaryurethanewipersealwaswarpedandcracked/dry‐rottedinseveralareas.Bothseals
wereremovedduringtheinspectionandwillneedreplacementbeforethetankisplacedbackin

service.

REFERENCE:Theowneroroperatorshallrepairanyobservedordeterminedfailuresaccordingto
paragraphs(d)(1)and(2)of40CFR§65.43forfacilitieswhoelecttocontrolstoragevessel
regulatedmaterialemissionsbyusingafixedroofandaninternalfloatingroof.NoteUFGS3356
13.13Section2.13.2.7,requiresflexibledoublewipersqueegeesealsmadeofclosedcellcast
urethane.Foamfilledcoated‐fabricsealsshallnotbeaccepted.(AdditionalrequirementsUFC3‐460‐
1Section8‐8.3,API650AppendixH)
RECOMMENDATION:InstallanewdoublewiperperimeterIFRseal.Thecurrentconfigurationwasa
rimmountedprimaryperimeterfoamlogsealandsecondaryperimeterwiperseal.Thenew
perimetersealshouldbedesignedtoeliminatethepresenceofair‐vapormixtureunderthefloating
roof.TheIFRsealshall,ataminimum,meetthespecificationsandtheintentofthelatesteditionof
APIStandard650,AnnexH.
c. SecondaryContainmentPipingSeals
OBSERVATION:Severalofthepenetrationsthroughthedikefloorforthe18‐inchissuelinesupports
and8‐inchreceiptpipingsupports(receiptpipingfromtank5018thatpassesthrough5220
containment)arenotsealed.Lackofproperpipesealscallsintoquestiontheintegrityofthe

containment.

REFERENCE:40CFRSection112
RECOMMENDATION:Sealtheareaswherepipingpenetratesthedikefloor.Sealantsshouldbesilicone
orureaurethanecompoundsthatconformtoFederalSpecTT‐S‐00230C,unlessanothermaterialis
requiredforcompatibilitywiththestoredmaterials.(Quantity:8areasnotsealed).

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

d. SpiralStairwayInitialStep
OBSERVATION:Thefirststepforthespiralstairwaymeasured15.25‐inchesofftheground.Thisposes
asafetyhazardforpersonnelusingthestairway.
REFERENCE:1910.25(c)(2)
RECOMMENDATION:Installaconcreteapproachstepatthebaseonthestairway,tomeetthestairway
riserheightrequirementsofOSHA.
e. WeldSpacingonTankBottom
OBSERVATION:ThreeareasofinadequateweldspacinginaccordancewithAPI‐653Figure9.13were
notedonthetankbottom.API‐653requiresaspacingoftwo‐inchesintheseareas.Areasaremarked
inthebottomdrawinginAppendixC.
REFERENCE:API‐653Figure9.13,API6539.10.3.1
RECOMMENDATION:Itisdeterminedthisisanas‐builtarrangementofthetankbottomandno
changesarerequiredatthistime.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

2. REQUIREDREPAIRStoFullyComplywithAPI653,or,Federal,State,andLocalCodes
Recommendedrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,inorderto
preventfuturepotentialriskstosystemoperators,equipmentintegrity,ortheadjacentenvironment.
Theseitemsmayberequiredbyfederal,state,andlocalcodesorbymilitarycriteria.
f. GasketsforRoofAccessHatches
OBSERVATION:Thegasketmaterialforthetwo30”x30”accesshatchesismissingordeteriorated.
REFERENCE:API‐653C.2.7.1(d)
RECOMMENDATION:Replacethegasketsatthe30”x30”accesshatches.InaccordancewithAPI‐650,
gasketmaterialshallbeeithersilicone,Buna‐N,orureaurethanemeetingASTMC509orFederal
SpecZZ‐R‐765C,unlessanothermaterialisrequiredforcompatibilitywiththestoredproduct.
g. CenterRoofVentScreen
OBSERVATION:Thescreenmeshforthe24‐inchcenterventonthefixedroofistoofine.
REFERENCE:API6505.8.5
RECOMMENDATION:Replacethefinemeshscreeninthe24‐inchcenterventwitha½‐inchcorrosion
resistantbirdscreeninaccordancewithAPI‐650.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

h. WeldFailureCenterVent
OBSERVATION:Lackoffusiontypeweldfailurewasnotedonthe24‐inchcenterventnozzletore‐pad
weldonthefixedroof.
REFERENCE:API6507.2.1.1
RECOMMENDATION:Removeandre‐weldthesectionoffailedweldonthe24‐inchcenterventnozzle
tore‐padweldonthefixedroof.
i. Interiorreinforcementpads
OBSERVATION:Therearenoreinforcementpadsunderthesupportsforthe18‐inchissueline,4‐inch
lowsuctionline,anti‐rotationdevices,andIFRaccessladder/gaugesupportsinsidethetank.
REFERENCE:API653C.2.3(l)
RECOMMENDATION:Installcircularweldedsupportpadsunderthesupportsforthe18‐inchissueline,
4‐inchlowsuctionline,anti‐rotationdevices,andIFRaccessladder/manualgaugesupportsinside
thetank.Andadjustandadjustsupportforequalloading.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

j. InteriorLowSuctionSupport
OBSERVATION:The4‐inchlowsuctionlineisnotcompletelyrestingononeofitssupportsinsidethe
tank.Thiscouldcausefatiguetypeweldcrackingatthepipe‐to‐shellweldduetocyclicstresses.The
supportheightisadjustable.
REFERENCE:API650E.7.3
RECOMMENDATION:Adjustthesupportasnecessarytoadequatelysupportthepipe.
k. HorizontalTRV’s
OBSERVATION:Thermalreliefvalvesforthe18‐inchissueand8‐inchreceiptlinesaremounted
horizontally.TRV’sshouldbemountedvertically.ATRVmountedinanon‐verticalorientationmay
notperformasexpected;theseattightness,operation,andsetpressureofthevalvemaybeaffected.
TheTRVslacklockableisolationvalves,testconnections,andflange,etc.
REFERENCE:API53013.1
RECOMMENDATION:ReinstalltheTRV’sinaverticalposition;adherencetoAW‐78‐24‐27iscovered
underanotheritem.ItisrecommendedtoupgradetoallUFCandAWcomplianceupgradesasnoted
insection3.j,whileperformingtheseAPIcompliancerepairs.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

l. ManwayDavitArms
OBSERVATION:The(2)30‐inchmanwaysonthetankshelldonothavedavitarmsinstalledtohelp
withthesaferemovalofthecovers.API‐650requiresdavitarmsformanwaysweighing75lbsor

more.

REFERENCE:API6505.8.3.5
RECOMMENDATION:Installdavitarmsontheshellmanways.AdherencetoAW‐78‐24‐27iscovered
underanotheritem.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

3. RECOMMENDEDREPAIRStofullycomplywithUFC3‐460‐01&AW78‐24‐27Standardsoras
PartofRegularMaintenance
Recommendedrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,inorderto
preventfuturepotentialriskstosystemoperators,equipmentintegrity,ortheadjacentenvironment.
a. StandingWateronFixedRoof
OBSERVATION:Severalareasindicatingstandingwaterwerenotedontheroof.Coatingwasstillintact
attheseareas.
REFERENCE:GeneralMaintenance
RECOMMENDATION:Reshapetheroofplatestoencouragedrainingorperiodicallysweepwateroffthe
roofafterprecipitation.
b. HingedCirculationVents
OBSERVATION:Thefivecirculationventslocatedalongtheperimeterofthefixedroofarenothinged
toallowforvisualinspectionofthefloatingroofseals.
REFERENCE:AW78‐24‐27DrawingD.09Detail1
RECOMMENDATION:Installatleastfourhingedcirculationventsalongtheperimeterofthefixedroof,
toallowforvisualinspectionofthefloatingroofsealsinaccordancewithAW78‐24‐27DrawingD.09
Detail1.Existingnon‐hingedventsmaybeabletobemodifiedwithhingestomeetthecriteria.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

c. FixedRoofRailing
OBSERVATION:Therailingontopofthefixedroofcutsacrossthecenteroftheroofanddoesnotgo
aroundtheentireperimeter.
REFERENCE:General/Safety
RECOMMENDATION:InstallanOSHAcompliantsafetyrailingaroundtheentireperimeterofthefixed

roof.

d. StillingWells
OBSERVATION:Thestillingwellforthemanualgauge(sideofIFRaccessladder)isconstructedof
carbonsteelandisnotslotted.ThestillingwellfortheVitoprobeisnotslotted.
REFERENCE:AW28‐24‐27DrawingD.07,UFC3‐460‐018‐8.3(a)
RECOMMENDATION:Installanaluminumslottedstillingwellforthe2‐inchVitoprobe.Discontinueuse
ofthe8‐inchmanualgaugewell(sideofIFRaccessladder)asmeasurementstakenthroughtheun‐
slottedwellmaynotaccuratelyreflecttheactuallevelofproductinthetank.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

e. MechanicalTapeGauge
OBSERVATION:Themechanicaltapegauge(Varec2500)tapeisdetachedfromtheIFRtankandhas
disconnectedfromthefloatingroof.Activityreportsthatthisgaugehashadseveralproblemsover
theyears.
REFERENCE:GeneralMaintenance
RECOMMENDATION:ItisunderstoodaseparatecontractexiststorebuildtheVarecgauge.Itis
recommendedtoreattachthetapetotheIFRinaccordancewithVarec’srecommendationand
rebuildthegaugewhilethetankisoutofserviceorreplacethemechanicalgaugewithanewgauge.
f. InteriorIssueLine
OBSERVATION:The18‐inchissuelineinsidethetankisnotflangedatthetankshell,extendsallthe
waytothecentersump(nothalf‐radius),andhasnoanti‐vortexplateinstalled.
REFERENCE:AW78‐24‐27DrawingD.08Detail4
RECOMMENDATION:Installaflangeatthetankshell,cutbacktohalfthetankradius,andinstallan
anti‐vortexplateonthe18‐inchissuelineonthetankinteriorinaccordancewithAW78‐24‐27
DrawingD.08Detail4.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

g. Manual/SampleGaugeWellBase
OBSERVATION:ThebaseofthemanualandsamplegaugestillingwellsarenotinaccordancewithAW
78‐24‐27DrawingD.07Detail2.Thereisnodatumplatelevelwiththebottomoftheshell.Thebolt
holesarenotslottedtoallowslightverticalmovement.
REFERENCE:AW78‐24‐27DrawingD.07Detail2andAPI650H5.1.5.
RECOMMENDATION:Modifythebasesofthemanualandsamplegaugestillingwellsinaccordance
withAW78‐24‐27DrawingD.07Detail2.
h. InteriorSupportDesign
OBSERVATION:ThesupportsontheinsideofthetankarenotdesignedinaccordancewithAW78‐24‐
27DrawingD.08Detail6.TherearenolooselyinstalledTefloncoatedU‐bolts.Abrasivecoating
failurewasnotedatoneofthediffusersupports.
REFERENCE:AW78‐24‐27DrawingD.08Detail6
RECOMMENDATION:InstallinternalpipesupportsinaccordancewithAW78‐24‐27DrawingD.08
Detail6.Repairthecoatingfailureonthediffuser,causedbytherubbingsupport.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

i. IFRManwayAccess
OBSERVATION:AccessthroughtheIFRmanwayonthe2ndcourseisblockedbytheIFR,whentheroof
isrestingonhighlegs.TheheightoftheIFRinsidethetankwas8‐feetattheperimeter.
REFERENCE:General
RECOMMENDATION:Adjusttheheightofthefloatingrooflegs,sothatmanwayaccesstothetopofthe
floatingroofcanbeachieved.EnsuretheroofmeetsallheightrequirementsofAPI‐650,UFC3‐460‐
01,andAW78‐24‐27afterrepair.ModificationstotheexistingIFRlegwouldincludeprovidingalow
legpositionandholesforretainingpins.
j. InteriorCoating
OBSERVATION:Minorareasofcoatingfailurewerenotedinsidethetank:Twosmallholidaysonplate
15,oneofthesupportpadsfortheVitoprobe,minorareasinsidethesump,andontheIFRlegstriker
plates,wherethelegmakescontactwiththeplate.Theexistinginternalliningappearstobethe
originallininginstalledin1986.
REFERENCE:General,API652(LiningsofAbovegroundPetroleumStorageTankBottoms).
RECOMMENDATION:Mechanicallycleanandrecoattheareasofcoatingfailureinsidethetank.Repairs
shouldbeaccomplishedusingatwopartepoxyinaccordancewithmilitarystandards.
Asthetypical,servicelifeofathinfilmepoxytankliningcanlastover20years,andthelinginTank
5220appearstobe31yearsoldwiththeexceptionoflocalcoatingrepairs,itissuggested
considerationbegiventoreplacingthetankbottomliningonly.Productsidetankbottomcorrosion
canbeaggressivewherewateristrappedoraccumulatingandcoatingfailureexist.Workshall
conformtoUFGS099713.17.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

k. CrackedConcreteSupportBase
OBSERVATION:Twooftheconcretebasesforsupportsonthe18‐inchissuelineand8‐inchreceipt
linehavecrackedandfallenapart.Thisdoesnotaffecttheintegrityofthepipingorcontainment.
REFERENCE:General
RECOMMENDATION:Repairorreplacetheconcretebaseatthepipesupportsonthe18‐inchissueline
and8‐inchreceiptline;wherefailed,removeandreplacewithnon‐shrinkgroutinaccordancewith
militarystandards.(Quantity:totalofthreelocations,twoonthe18‐inchissuepipingandone
adjacenttothe8‐inchtankfillnozzle).
l. ThermalReliefValve/Piping
OBSERVATION:Thermalreliefpipingforthe18‐inchissuelineand8‐inchreceiptlinearenotdesigned
inaccordancewithAW78‐24‐27DrawingD.10Detail4.Thepipinghasunionandnotflanged
connections,isnotstainlesssteel,hasViso‐Floglasssightindicators,doesnothavelockableball
valvesontheinletandoutletsideofthevalve,doesnothavea“T”fortestingthevalveinthesystem,
andthevalveshavenoindicationofcalibrationpostedonthevalve.
REFERENCE:AW78‐24‐27DrawingD.10Detail4.UFC3‐460‐01Section3‐3.1.2(j).
RECOMMENDATION:DesignTRVpipingthatisinaccordancewithAW78‐24‐27DrawingD.10Detail4.
Calibratethevalvesannuallyandpostacalibrationstickeronthevalve.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

m. ExteriorCoatingFailure
OBSERVATION:Coatingfailurewasnotedonthetankshellbehindconduit/junctionboxesforthe
issuelineelectronicvalveandlow‐levelalarm,onthelow/high‐levelalarmsensorheads,andonthe
platformfortheIFRmanway.Theplatformholdswaterattheperimeterandisexperiencing
acceleratedcorrosionduetothis.
REFERENCE:GeneralMaintenance
RECOMMENDATION:Mechanicallycleanandrecoatareasofcoatingfailureonthetankexterior.
CoatingrepairsshouldbemadeconformingtoUFGS099713.27.SealweldperAPI6505.1.3.7along
withcoatingrepairsconformingtoUFGS099713.27and099713.17.

n. Manways

OBSERVATION:UFC3‐460‐01currentlyrequirestwo36‐inchmanwaysalongthefirstcourse180
degreesapartandone36‐inchmanwaylocated3.5‐feetabovetheIFRonhighlegstoaccessthetop
oftheIFRforinspection/maintenance.Thetankcurrentlyhasone30‐inchmanwayonthefirst
courseandone30‐inchmanwayfortheIFR.
REFERENCE:UFC3‐460‐01Table8‐1(fandc).
RECOMMENDATION:Install36‐inchmanwaysinaccordancewithUFC3‐460‐01.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

o. WaterDraw/LowSuction
OBSERVATION:The4‐inchlowsuctionlinedoesnothaveaDBBvalveastheskinvalvetothetankand
isnotdesignedinaccordancewithAW78‐24‐27.Thelowsuctionlineshouldbetiedintothetank’s
issueline.Note:the4‐inchlowsuctionlineislocated90‐degreesaroundthetankshellfromthe18‐
inchissuenozzle.Thewaterdraw‐offpipingdoesnothaveaDBBvalveastheskinvalvetothetank.
Theexistingproductsavertankandexternalwaterdraw‐offpipinghavebeendisconnectedfromthe
tankasapartofanotherproject.Itisourunderstandinganotherprojectisperformingupgradesto
bringtheproductsavertankintoconformancewithcurrentmilitarystandards.Itissuggestedthe1”
waterdraw‐offnozzleinclude2”by1”eccentricreducers(flatonbottom)ontheinletandoutletofa
new2”doubleblockandbleed(DBB)plugvalveonthe1”existingwaterdraw‐offlineadjacenttothe
tankshellwiththeinstallationofthenewproductsavertank(currentlyonsite).Provideanew8‐
inchDBBplugvalveontheinletoftheexisting8‐inchhighlevelcontrolvalve(HLCV)inaccordance
withcurrentmilitarystandard(AW78‐24‐27).
REFERENCE:AW78‐24‐27DrawingG.05
RECOMMENDATION:Designlow‐suctionwithaDBBvalve,TRVandpiping,andtiedintotheissueline
inaccordancewithAW78‐24‐27.Ensurethatnewinstallationoftheproductsavertankandwater
draw‐offsystemmeetstherequirementsandintentofthelatesteditionofAW78‐24‐27andUFC3‐

460‐01.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

p. AFFFPipingDeadLeg
OBSERVATION:TheabandonedAFFFpipingatthetopofthetankformsadeadlegwhereithasbeen
blindedoff.Thisareaisdifficulttoaccessforinspectionandcouldbeexperiencingaccelerated
corrosionifanymoistureistrappedinside.
REFERENCE:GeneralMaintenance(removingtheunnecessarypipingwilleliminatemaintenance).
RECOMMENDATION:ItisrecommendedtocompletelyremovetheAFFFpipingifitwillnolongerbe
used.Ataminimum,considerremovingthedeadlegandleavingthepipingflush.
q. ExternalPipingSupports
OBSERVATION:TheTeflonmaterialbetweenthepipingandsupportsforallexternalsupportshas
deterioratedorismissing(includingsisterTank5218pipingsupportswithinTank5220’s
containmentarea)andshouldbereplaced
REFERENCE:GeneralMaintenance,UFC3‐460‐01FacilityPlate020
RECOMMENDATION:ReplaceandsecuretheTeflonmaterialbetweenthepipingandsupportforall
externalpipingsupports.(Quantity:21).Workshallincludelocalpipecoatingrepairsatallpipe
supportsinaccordancewith099713.27.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

r. LowandHigh‐LevelAlarms
OBSERVATION:Thelow/loworlow‐lowlevelandhighandhigh‐highlevelswitchesarenot
designed/constructedinaccordancewithUFC3‐460‐01andAW78‐24‐27.Pipingshouldbestainless
steelwithflangedfittings,andalarmsshouldbeaccessiblefortestingwiththetankempty,and
lockableballvalvesshouldbeprovidedtopreventinadvertentopening,especiallyontothefloating
roof(Approximately200gallonsoffuelwereremovedfromthetopofthefloatingroofduringthe
inspection;thespillagewascausedbyinadvertentopeningofanunlockedballvalveontheHLA).
REFERENCE:UFC3‐460‐01Table8‐1,AW78‐24‐27DrawingD.12
RECOMMENDATION:Designlowandhighandhigh‐highlevelswitchesinaccordancewithAW78‐24‐
27DrawingD.12.DesignaplatformsupportasshowninAW78‐24‐27DrawingD.11Detail1forthe
high‐levelalarm/shut‐offpiping,soitisaccessibleformaintenanceandtesting.(Currentlynot
reachablefromstairway)Installlocksinballvalvestopreventaccidentalopening.Providesolenoid
valveandnewstainlesssteelpilottubingonexistinghighlevelcontrolvalve(HLCV)inaccordance
withcurrentmilitarystandards.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

s. TankGroundingLugs
OBSERVATION:Thetankgroundingstrapsareboltedtothetankshellandhavenoreinforcement
platesorgroundingluginstalled,asshowninAW78‐24‐27DrawingED.02Detail2.
REFERENCE:AW78‐24‐27DrawingED.02Detail2.(SeealsoAPI650Section5.8.11.3)
RECOMMENDATION:Exothermicallyweldthegroundingcablestothelugandinstallreinforcementat
theshell,inaccordancewithAW78‐24‐27DrawingED.02Detail2.Note:ifrepairsareelectednotto
bedone,thepaintshouldberemovedwherethecableboltstothelug,toprovideabetterconnection
toground.
t. CorrosionatPipingSupportstoContainmentInterface
OBSERVATION:Coatingfailureandcorrosionwasnotedatoneofthesupportsforthe18‐inchissue
line,whereitpenetratesthecontainmentfloor(3rdsupportfromtankshell)
REFERENCE:General
RECOMMENDATION:Repairthefailedcoatingatthepipesupport;sealantofsupporttocontainment
flooriscoveredunderanotheritem.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

u. CathodicProtection
OBSERVATION:ThetankisnotequippedwithacathodicprotectionsysteminaccordancewithUFC3‐
460‐01Sections2‐13.1and8‐8.5,andAW78‐24‐27DrawingD.15.
REFERENCE:UFC3‐460‐01Sections2‐13.1and8‐8.5,andAW78‐24‐27DrawingD.15.
RECOMMENDATION:InstallacathodicprotectionsysteminaccordancewithUFC3‐460‐01Sections2‐
13.1and8‐8.5,andAW78‐24‐27DrawingD.15.Note:ANACECertifiedCorrosionExpertshould
designthecathodicprotectionsystemperUFC3‐460‐01.NOPHOTOAVAILABLE.

API 653 Out‐of‐Service Inspection Report Dyess AFB, Texas

APPENDIX A: ENGINEERING CALCULATIONS AND DRAWINGS

A.1BOTTOMSERVICELIFEEVALUATION
A.2SHELLSERVICELIFEEVALUATION
A.3SHELLSETTLEMENTEVALUATION
A.4ULTRASONICUTDATA
A.5BOTTOMLAYOUTDRAWING
A.6SHELLLAYOUTDRAWING
A.7FIXEDROOFLAYOUTDRAWING
A.8FLOATINGROOFLAYOUTDRAWING
A.9FLOATINGROOFGAPMEASUREMENTS
A.10CONTAINMENTLAYOUTDRAWING
A.11OSHAACCESSSTRUCTUREREPORT

Shannon T Gray Typewritten Text A-1

Present Condition:

1) In-Service Interval of Operation (years to next internal inspection)

No Yes No No

MRT = 0.1 inches

RT ip = 0.25 inches

RT bc 0.099 inches

StP r = 0 inches/year

UP r = 0.004871 inches/year

Therefore, the in-service interval of operation (years to next internal inspection) is:

Bottom Service Life Evaluation (Before Repair)

Containment of Bottom:

Bottom Leak Detection:

Cathodic Protection:

Bottom Coated:

O r = -0.2 years

*The MFL unit used for scanning the bottom does not have a threshold set point. This unit visually displays all anomalies. The confidence level of this unit diminishes greatly for underside pitting/corrosion that is less than 0.020 inches in depth, based on company experience. No significant underside corrosion was detected.

Therefore, RT bc is established at 0.355 inches (original thickness of 0.375 inches minus 0.020 inches).

0.099 - 0.1 0 + 0.004871

**Since StP r = 0 and UP r = 0; use StP r + UP r = 0.0002 inches/year for calculation purposes.

= O r

Bottom Service Life Evaluation (Before Repair)

2) Projected Thickness Chart and Graph

Year Thickness MRT

1986 0.250 0.1 2017 0.099 0.1 2022 0.075 0.1 2027 0.050 0.1 2037 0.002 0.1 2047 -0.047 0.1

*based on same service and corrosion rates.

Nominal:

Current Lowest Remaining Thickness:

Anticipated Thickness (5 yrs)*:

Anticipated Thickness (10 yrs)*:

Anticipated Thickness (20 yrs)*:

Anticipated Thickness (30 yrs)*:

0.000

0.050

0.100

0.150

0.200

0.250

0.300

1986 1993 2000 2007 2014 2021 2028 2035

In ch es

Year

Projected Thickness Graph

Thickness MRT

1) In-Service Interval of Operation (years to next internal inspection)

No Yes No No

MRT = 0.1 inches

RT ip = 0.25 inches

RT bc 0.16 inches

StP r = 0 inches/year

UP r = 0.002903 inches/year

Therefore, the in-service interval of operation (years to next internal inspection) is:

O r = 20.6 years

*The MFL unit used for scanning the bottom does not have a threshold set point. This unit visually displays all anomalies. The confidence level of this unit diminishes greatly for underside pitting/corrosion that is less than 0.020 inches in depth, based on company experience. No significant underside corrosion was detected.

Therefore, RT bc is established at 0.355 inches (original thickness of 0.375 inches minus 0.020 inches).

0.16 - 0.1 0 + 0.002903

**Since StP r = 0 and UP r = 0; use StP r + UP r = 0.0002 inches/year for calculation purposes.

= O r

Bottom Service Life Evaluation (After Repair)

Containment of Bottom:

Bottom Leak Detection:

Cathodic Protection:

Bottom Coated:

Where:

t min = minimum acceptable shell thickness for each course, in inches; however, t min shall not be less than 0.1 inch for any tank course.

t nom = nominal shell thickness, in inches.

t act = current measured shell thickness, excluding pits and corrosion, in inches.

t prev = previous measured shell thickness, excluding pits and corrosion or t nom , in inches.

D = nominal diameter of the tank, in feet.

H = height from the bottom of the shell course under considerations to the established maximum liquid level, in feet.

H c = calculated safe fill height, in feet, for the current product.

G = specific gravity of the contents.

Y = specified minimum yield strength of the plate; use 30,000 pounds per square inch if not known

(N/A for riveted tanks).

T = smaller of the specified minimum tensile strength of the plate or 80,000 pounds per square inch;

use 55,000 psi if not known (N/A for riveted tanks).

S = The maximum allowable stress, in pounds per square inch. For welded tanks, use the smaller of

0.80Y or 0.429T for the bottom and the second course or the smaller of 0.88Y or 0.472T for all other courses. For riveted tanks, use S =21,000 psi. For elevated temperatures above 200OF, the maximum allowable stress shall be the smaller of 2/3 the minimum yield strength multiplied by the M-factor (M) of API Standard 650 Appendix M or the product design stress value listed in Table M-1a or M-1b of API Standard 650.

E = original joint efficiency for the tank. Use Table 4-2 from API Standard 653 if original E is unknown; E =1.0 when evaluating the retirement thickness in a corroded plate, when away from welds or joints by at least the greater of one inch or twice the plate thickness. For riveted tanks, use E =1.0 for shell plates when greater than 6 inches from rivets; use the value of E from API Standard 653 Table 4-3 when within 6 inches of rivets.

L r = remaining life of the shell, in years.

C r = shell corrosion rate, in inches per year.

I ut = inspection interval for the next ultrasonic inspection, in years (not to exceed 15 years).

I v = inspection interval for the next visual external inspection, in years (not to exceed 5 years).

Y = years between the previous measured shell thickness (t prev ) and the current measured shell thickness (t act ), in years.

The maximum inspection intervals are determined by the most restrictive shell course in regard to the remaining life and the corrosion rate calculations for each shell course using the following formulas:

Shell Service Life Evaluation tmin =

2.6(H−1)DG

SE

Lr = tact − tmin

Cr Cr = tprev − tact

Y Iut = tact − tmin 2Cr

Iv = tact − tmin

4Cr

Bottom Service Life Evaluation (After Repair)

2) Projected Thickness Chart and Graph

Year Thickness MRT

1986 0.250 0.1 2017 0.160 0.1 2022 0.145 0.1 2027 0.131 0.1 2037 0.102 0.1 2047 0.073 0.1

*based on same service and corrosion rates.

Anticipated Thickness (20 yrs)*:

Anticipated Thickness (30 yrs)*:

Nominal:

Current Lowest Remaining Thickness:

Anticipated Thickness (5 yrs)*:

Anticipated Thickness (10 yrs)*:

0.000

0.050

0.100

0.150

0.200

0.250

0.300

1986 1993 2000 2007 2014 2021 2028 2035

In ch es

Year

Projected Thickness Graph

Thickness MRT

1) Minimum Required Thickness

D = 43.5 feet

G = 0.79

Y = 31 years

Course No.

Plate Specification

Course Height…