Attachment J1a - DWH Drawings.pdf
PDF 5 MB Posted
- Attached to
- David Wayne Hooks (DWH) REPAIR TOWER AND BASE BUILDING WATER DAMAGE CAUSED BY HURRICANE HARVEY
- Solicitation number
- Not on record
About this file
This package of documents defines the scope of work for repairs to the air traffic control tower and base building at David Wayne Hooks Memorial Airport in Houston, Texas due to water damage from Hurricane Harvey. The Federal Aviation Administration is seeking contractors to repair the tower, cab, and base building, replace damaged ceilings, lights, flooring, and remove and replace plumbing in the tower shower. Drawings and specifications are provided to guide electrical, mechanical and architectural repairs. The pre-bid site visit is mandatory due to construction scope. Work hours will be coordinated to avoid impacts to air traffic operations, and all work must comply with FAA standards and specifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DRAWING NO
DESIGNED
REVIEWED BY
/2
:3
:4
M P lo tt e d b y S
R V
-C
-E
O
APPROVED
w h -d -a tc t-e .d g
8 234567
TRANSFORMER
WATERTIGHT
WEATHERPROOF
WIREGUARD
WATT
VOLT-AMPERE
VOLT
UNINTERRUPTIBLE POWER SUPPLY
UNDERWRITERS LABORATORY
UNDERGROUND
TYPICAL
TOWER
TRANSIENT VOLTAGE SURGE PROTECTION
TELCO TERMINAL BOARD
TERMINAL BLOCK
SWITCHBOARD
SWITCH
STAINLESS STEEL
SIGNAL REFERENCE GROUND GRID
SINGLE POINT GROUND
SECONDARY
ROOM
RAPID START
ROOT MEAN SQUARE
RIGID METAL CONDUIT
RECEPTACLE
POLYVINYL CHLORIDE
POTENTIAL TRANSFORMER
PRIMARY
PHASE
POWER FACTOR
PULL BOX
POLE
OVERLOAD
OWNER FURNISH & OWNER INSTALL
NOT TO SCALE
NON-TRIP
NORMALLY OPEN - DE-ENERGIZED
NATIONAL ELECTRICAL MNFGR'S ASSOC.
NATIONAL ELECTRICAL CODE - NFPA 70
NORMALLY CLOSED - DE-ENERGIZED
NEUTRAL
MICROWAVE OVEN
MULTIPLEXER
MULTIPOINT GROUND
MAIN LUGS ONLY
METAL HALIDE
MAIN DISTRIBUTION PANEL
MOTOR CONTROL CENTER
LOCAL AREA NETWORK
KILOWATT HOUR
KILOWATT
KILO-VOLT-AMP
KILOVOLT
THOUSAND CIRCULAR MILS
JB
HZ
HV
HPS
HP
HOA
HID.
HH
G/R
G/Y
G/O
GI
GRS
GFIP
GFE
GFR
GFCI
FSD
FMC
FLA
FACP
FA
EMT
E/G
DWG
DISC.
DC
CU
COMM
CCT
CFCI
CCMS
CB
BRITE
BKBD
BFG
BFF
BC
BATT.
AWG
AUX
AUTO.
ATS
ATC
ASR
ARTS
AIC
AFG
AFF
AF
AC
NOTE : ALL ABBREVIATIONS NOT NECESSARILY USED
XFMR
WT
WP
WG
W
VA
UPS
UL
UG
TYP
TWR
TVSS
TTB
TB
SWBD
SW
SS
SRGG
SPG
SEC
RM
RS
RMS
RMC
REC
PVC
PT
PRI
PH
PF
PB
OL
OFOI
NTS
NT
N.O.
NEMA
NEC
NC
N
MW
MUX
MPG
MLO
MH
MDP
MCC
LAN
KWH
KW
KVA
KV
KCM
JUNCTION BOX
HERTZ
HIGH VOLTAGE
HIGH PRESSURE SODIUM
HORSEPOWER
HAND-OFF-AUTOMATIC
HIGH INTENSITY DISCHARGE
HAND HOLE
GREEN INSULATION WITH RED TRACER
GREEN INSULATION WITH YELLOW TRACER
GREEN INSULATION WITH ORANGE TRACER
GREEN INSULATED
GALVANIZED RIGID STEEL (CONDUIT)
GROUND FAULT INTERRUPTION PROTECTION
GOVERNMENT FURNISHED EQUIPMENT
GROUND FAULT RELAY
FAULT CIRCUIT INTERRUPTER
GROUND
FIRE SMOKE DAMPER
FLEXIBLE METAL CONDUIT
FULL LOAD AMPERES
FIRE ALARM CONTROL PANEL
FIRE ALARM
FUSE
ELECTRICAL METALLIC TUBING
ENGINE GENERATOR
DRAWING
DISCONNECT
DIRECT CURRENT
COPPER
COMMUNICATIONS
CIRCUIT
CONTRACTOR FURNISHED AND INSTALLED
CENTRAL CONTROL MONITORING SYSTEM
CIRCUIT BREAKER
CONDUIT
BRIGHT RADAR INDICATOR
BACKBOARD
BELOW FINISHED GRADE
BELOW FINISHED FLOOR
BARE COPPER
BATTERY
AMERICAN WIRE GAUGE
AUXILIARY
AUTOMATIC
AUTOMATIC TRANSFER SWITCH
AIR TRAFFIC CONTROL
AIRPORT SURVEILLANCE RADAR
AUTOMATED RADAR TERMINAL SYSTEM
AMPS INTERRUPTING CAPACITY
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AMPS - FRAME
ALTERNATING CURRENT
AMPERES
THERMOSTAT
HANDICAPPED DOOR OPERATOR
NOTE : ALL SYMBOLS NOT NECESSARILY USED
ELECTRICAL PANEL
FEEDER DESIGNATION
DUPLEX RECEPTACLE
GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLE
TWIST-LOCK RECEPTACLE
FLOOR OUTLET WITH DEVICE INDICATED
EQUIPMENT CONNECTION
DISCONNECT SWITCH & EQUIPMENT CONNECTION
MOTOR STARTER
MOTOR
JUNCTION BOX
J 8" x 8" JUNCTION BOX
ELECTRICAL DISTRIBUTION PANEL
DOUBLE DUPLEX RECEPTACLE
GFI
J
T
14.
13.
12.
11.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
DWH-D-ATCT-E015
DWH-D-ATCT-E014
DWH-D-ATCT-E013
DWH-D-ATCT-E012
DWH-D-ATCT-E011
DETAILS, ELECTRICAL
CAB & CAB ROOF LEVEL PLANS, ELECTRICAL
FLOOR PLANS, ELECTRICAL
FIRST FLOOR PLAN ELECTRICAL
DRAWING LIST, SYMBOL LEGEND AND ABBREVIATIONS
DISCONNECTS, PRINT LABELS AND AFFIX THEM ON DISCONNECTS ETC.
CONTRACTOR SHALL CALCULATE THE ARC FLASH LEVEL ON ALL NEW
HVAC EQUIPMENT.
CONTRACTOR SHALL WRITE LOCKOUT TAGOUT PROCEDURES FOR ALL NEW
LABELS FOR ALL PANELS WHETHER WORKED ON OR NOT.
CONTRACTOR SHALL PROVIDE TYPED PANEL DIRECTORIES AND IDENTIFYING
USED RIGID STEEL CONDUITS IN THE MECHANICAL AND ELECTRICAL ROOMS.
SERVICING THE TOWER.
OF THE FIRE ALARM SYSTEM. CONTACT THE FIRE ALARM COMPANY
DEVICES ARE PLACED THE CONTRACTOR SHALL DO A COMPLETE TEST
AFTER ALL THE ELECTRICAL WORK IS COMPLETE AND ALL FIRE ALARM
IN THE WORK AREA SHALL HAVE DUST COVERS DURING WORK.
ALL FIRE ALARM SMOKE DETECTORS, CONTROLLERS ETC. SMOKE DETECTORS
CONTRACTOR SHALL REMOVE AND REINSTALL APPROPRIATELY AND RECONNECT
PROVIDE A PLAN FOR APPROVAL.
TRADES TO SEE HIS SEQUENCE WOULD NOT AFFECT OTHER TRADES.
THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER
ON/OFF WITHOUT FAA TECHNICIAN BEING PRESENT.
FITS IN EXISTING SPACES. THE CONTRACTOR SHALL NOT TURN ANY BREAKER
CONTRACTOR'S RESPONSIBILITY TO ASSURE THAT ALL NEW EQUIPMENT
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS. IT SHALL BE THE
THERE SHALL BE NO WORK DONE DURING THE FAA MORATORIUM DATES.
REQUIREMENTS.
FOR CLEANUP. THIS SCHEDULE SHALL CHANGE ACCORDING TO AIR TRAFFIC
TO 6:00 AM. WORK SHALL BE COMPLETED BY 5:30 AM LEAVING 30 MINUTES
AND ANY TYPE OF POWER INTERRUPTION SHALL BE DONE FROM 12:00 PM
ALL ELECTRICAL WORK INVOLVING TURNING OFF OF PANELS, CUT OVERS
LATEST REGULATIONS AND SUBMIT A MANIFEST TO THAT AFFECT TO FAA.
CONTRACTOR SHALL DISPOSE OFF ALL LIGHT FIXTURES ACCORDING TO
REQUIRED FOR CONNECTING THESE LIGHTS.
TO EXISTING CIRCUITS. PROVIDE ANY ADDITIONAL CONDUIT AND WIRE
THE LIGHTING FIXTURE SCHEDULE AND FLOOR PLANS. CONNECT LIGHTS
CONTRACTOR TO PROVIDE AND INSTALL ALL LIGHT FIXTURES SHOWN IN
CODES.
FAA-STD-1217G, FAA-STD-019F LATEST EDITION OF NEC AND ALL LOCAL
ALL ELECTRICAL WORK SHALL BE DONE ACCORDING TO FAA STANDARDS
THE BASIS OF DESIGN FOR THIS DISTRIBUTION SYSTEM IS SQUARE D.
ELECTRICAL GENERAL NOTES:
SYMBOL LEGEND
POWER
ELECTRICAL DRAWING LISTABBREVIATIONS
IS
U
11/30/2019
THOMAS R. CLAYTON
MGR: ENGINEERING - FORT WORTH
AA
HOUSTON
ADWH-D-ATCT-E011
ATCT
HURRICANE HARVEY WATER DAMAGE REPAIRS
DRAWING LIST, SYMBOL LEGEND
AND ABBREVIATIONS
-a tc t-e
TERMINAL
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
-B
IL
DAVID WAYNE HOOKS MEMORIAL AIRPORT
THIS DRAWING PRODUCED ON ASW REGION CAD SYSTEM
AZIZ ABBAS
PROJECT ENGINEER
1705988
A 08/24/2023 DESCOPED REVISIONS-AS BUILT 1705988 09/15/2023 JV
TX
dwh-d-atct-e011
TYPE DESCRIPTION MANUFACTURER
2' x 4' RECESSED LED FIXTURE
LIGHTING FIXTURE SCHEDULE
NOTE:
1. CONTRACTOR TO VERIFY ALL QUANTITIES, VOLTAGES, PART NUMBERS AND TRIMS.
DOOR LED LIGHT
2' x 4' SURFACE LED FIXTURE
COLUMBIA
COLUMBIA
RIVERPATH 23" LED 49946OZLED (BRONZE)
LEPC-24-35MLG-LL-EU
LEPC-24-35MLSM-LL-EUB
C COLUMBIA LEPC-14-35MLG-LL-EUC
D 1' x 4' SURFACE LED FIXTURE COLUMBIA LEPC-14-35MLSM-LL-EU
PART NUMBER
1' x 4' RECESSED LED FIXTURE
RECESSED LED FIXTURE LOTUS LED LIGHTS
OF CEILING
TRIM TO MATCH COLOR
LD4S-30K-4S-SR-BT
LD4S-30K-4S-SR-WT
H SUPERBRIGHT LED VTWJ-X20JAR TYPE LIGHT FIXTURE
J LENSED STRIPLIGHT COLUMBIA LCL4-35ML-EU
2 2
3 3
FACP
JJJ
D C
DC FACP
BASE BUILDING
LINK
LINK CORRIDOR TO BASE BUILDING
CEILING FAN LOCATIONS
SCALE: 1/4" = 1'-0"
REFLECTED CEILING PLAN BASE BUILDING
FIRST FLOOR LINK
LIGHTING PLAN FIRST FLOOR ATCT
:5 lo tt e
-a tc t-e
ENTIRE BASE BUILDING AND TOWER LINK.
REPLACE ONLY NON WORKING LIGHT FIXTURES AT THE
EDITION OF NEC AND ALL LOCAL CODES.
FAA STANDARD FAA-STD-1217G, FAA STD-19F, LATEST
ALL ELECTRICAL WORK SHALL BE DONE ACCORDING TO
SYMBOLS, ELECTRICAL DRAWING LIST AND ABBREVIATIONS.
SEE DRAWING DWH-D-ATCT-E011 FOR GENERAL NOTES,
SEALED BY THE CONTRACTOR WHO HAS CURRENT ROOF WARRANTY.
E014 AND DETAILS 2/E015, 3/E015 AND 7/E015. THE ROOF SHALL BE
ELECTRODE SYSTEM. SEE LIGHTNING PROTECTION NOTES ON SHEET
CADWELD IT TO THE NEAREST GROUND ROD OF EXISTING EARTH
ROUTE IT OUTSIDE NEAR THE CORNER OF THE BUILDING AND
THROUGH THE BUILDING. INSTALL A NEW MAIN DOWN CONDUCTOR,
REMOVE THE LIGHTENING PROTECTION DOWN CONDUCTOR GOING
INSTALL TWO LUTRON DIMMERS ONE FOR THREE LIGHTS.
LED LIGHT FIXTURE SEE LIGHTING FIXTURE SCHEDULE THIS SHEET.
USE EXISTING SWITCH/CONTROLS.
DOOR LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE THIS SHEET.
HANG AT 12 FEET AFF.
ON THIS SHEET FOR DETAILS. PROVIDE WITH HANGING OPTIONS.
LENSED LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE
BRACKETS ETC. TO INSTALL DUE TO TYPE OF CEILINGS.
THIS SHEET FOR DETAILS. THESE LIGHTS WILL NEED ADDITIONAL
1X4 LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE ON
FOR DETAILS
INSTALL 2x4 LIGHT FIXTURE SEE LIGHTING FIXTURE SCHEDULE
4' 8'04'
GENERAL NOTES:
NOTES BY SYMBOL:
ADWH-D-ATCT-E012
FIRST FLOOR PLAN
ELECTRICAL
-a tc t-e
A 08/24/2023 DESCOPED REVISIONS-AS BUILT 1705988 09/15/2023 JV
dwh-d-atct-e012
(TYP)
EEE
E E E
NATCA
B B
A A
C C
FF F
J J s
SF-1
SECOND LEVEL PLAN ELECTRICAL
THIRD LEVEL PLAN ELECTRICAL
JUNCTION LEVEL FLOOR PLAN ELECTRICAL
:1 lo tt e
-a tc t-e
TOWER SHAFT.
REPLACE ONLY NON WORKING LIGHT FIXTURES IN
SCHEDULE.
SEE DRAWING DWH-D-ATCT-E012 FOR LIGHTING FIXTURE
ABBREVIATIONS.
SYMBOLS, ELECTRICAL DRAWING LIST, AND
ROW OF DOWN LIGHTS.
DETAILS. PROVIDE AND INSTALL ONE LUTRON DIMMER FOR EACH
LED DOWN LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE FOR
BY MECHANICAL CONTRACTOR. SEE MECHANICAL SCHEDULES.
INSTALL SWITCHES FOR VANITY LIGHT, HEATER AND FAN SUPPLIED
DRAWING DWH-D-ATCT-E012 FOR DETAILS.
1x4 RECESSED LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE
DRAWING DWH-D-ATCT-E012 FOR DETAILS.
2x4 SURFACE LIGHT FIXTURE. SEE LIGHTING FIXTURE SCHEDULE ON
#54105 BLACK COLOR. COORDINATE LOCATION WITH AIR TRAFFIC/SSC.
FAN CASABLANCA FAN CO. 54" CALEDONIA, LOW PROFILE MODEL
REPLACE EXISTING CEILING FAN WITH COMMERCIAL GRADE CEILING
SCHEDULE ON DRAWING DWH-D-ATCT-E012 FOR DETAILS.
INSTALL 2x4 RECESSED LIGHT FIXTURE SEE LIGHTING FIXTURE
ADWH-D-ATCT-E013
HURRICANE HARVEY WATER DAMAGE REPAIR
FLOOR PLANS
-a tc t-e
THIS DRAWING PRODUCED ON ASW REGION MICROSTATION SYSTEM
A 08/23/2023 DESCOPED REVISIONS AS-BUILT 1705988 09/15/2023 JV
dwh-d-atct-e013
10 TYP OF 4.
HANDRAIL
RING. ON CATWALK
EQUALIZATION
POTENTIAL
SEE DETAIL9/E015
TYP OF 4 PLACES.
AHU
ON FIRST FLOOR
TO PANEL 'MDP'
3#3, #10 G, 1 1/2"C
CAB FLOOR PLAN ELECTRICAL
CAB ROOF PLAN ELECTRICAL
CAB ROOF AND CAT WALK LEVEL LIGHTNING PROTECTION
:2 lo tt e
-a tc t-e
SCHEDULE.
SEE DRAWING DWH-D-ATCT-E012 FOR LIGHTING FIXTURE
SYMBOLS, ELECTRICAL DRAWING LIST AND ABBREVIATIONS.
ON/OFF SWITCH. ADD DIMMER FOR NEW CAN LIGHTS HERE.
REPLACE FOUR EXISTING DIMMERS WITH LUTRON DIMMERS WITH
TO THE FOUR MAIN DOWN CONDUCTORS. SEE DETAIL 9/E015.
CONNECT THE CATWALK HANDRAIL POTENTIAL EQUALIZATION RING
PARAPET COUNTERPOISE WITH A MINIMUM OF #2 AWG.
BOND THE ROOF TOP UNIT ON TWO OPPOSITE SIDES WITH THE CAB
SEE DETAIL 9/E015.
FOUR DOWN CONDUCTORS FROM THE LIGHTNING AIR TERMINALS.
ALL MATERIAL SHALL BE CLASS I. CONNECT THE COUNTERPOISE TO
PLACE A COUNTERPOISE ON THE SECOND RAIL OF THE CAB PARAPET.
COUNTERPOISE SEE DETAIL 1/E015 AND 7/E015.
GROUND ROD AND EXOTHERMICALLY WELD TO THE EXISTING
GROUND ROD CANNOT BE LOCATED INSTALL A 3/4"x10'-0" COPPER
THE EXISTING TOWER COUNTERPOISE. TYPICAL OF 4. IF EXISTING
EXISITNG GROUND ROD THAT IS EXOTHERMICALLY WELDED TO
CONDUCTOR SHALL ENTER THE GROUND AND BE WELDED TO AN
NO LESS THAN 18" ABOVE GROUND LEVEL. THE 4/0 AWG COPPER
CONDUCTOR BY BURNDY YGHC-C PRIOR TO ENTERING GROUND AT
DOWN CONDUCTORS SHALL BE CONNECTED TO 4/0 AWG COPPER
THE TOWER CAB METAL STRUCTURE.
IN PVC SCHEDULE 40 CONDUIT WHERE IT COMES IN CONTACT WITH
THRU THE GRATE. SEE DETAIL 9/E015. DOWN CONDUCTOR SHALL BE
THE GRATE AT FOUR PLACES WHERE THE DOWN CONDUCTORS PASS
CONDUCTOR SHALL PASS THRU THE CATWALK GRATE FLOOR. BOND
OF THE TOWER AND SHALL BE SUPPORTED EVERY 3 FEET. THE DOWN
CONDUCTOR FROM THE LIGHTNING ROD DOWN TO THE EXTERIOR
5/E015 AND 9/E015. RUN CLASS II MAIN COPPER LIGHTNING DOWN
AND INSTALL A 1/2"x3'-0" LIGHTNING TERMINAL ON TOP. SEE DETAILS
INSTALL A NEW 15 FOOT 2 1/2" OR 3" (MATCH EXISTING) GI PIPE POST
BREAKER FOR THE NEW ROOF TOP UNIT.
PANEL 'A' ON THE GROUND FLOOR WITH A 3P-60 AMP HACR TYPE
REPLACE THE EXISTING BREAKER FOR THE ROOF TOP UNIT IN
AFFIX ARC FLASH LABEL.
ON THE UNIT AS SHOWN FOR THE ROOF TOP UNIT. PRINT AND
NEMA 4X STAINLESS STEEL HEAVY DUTY DISCONNECT MOUNTED
PROVIDE POWER TO SQUARE D 3P-60 AMP, NON FUSED,
BEEN REPLACED.
FIXTURES IN THE CAB CEILING AFTER THE CEILING GRID HAS
REINSTALL THE EXISTING COOPER LIGHTING PINHOLE LIGHT
WITH AIR TRAFFIC/SSC.
PROFILE MODEL # 54105 BLACK COLOR. COORDINATE LOCATION
CEILING FAN CASABLANCA FAN CO. 54" CALEDONIA, LOW
REPLACE ONE EXISTING CEILING FAN WITH COMMERCIAL GRADE
EXISTING 1x4 LIGHT FIXTURE.
SWITCH FOR THESE FIXTURES. USE SAME CIRCUIT AS THE
FIXTURE SCHEDULE. PROVIDE AND INSTALL NEW DIMMER
INSTALL TWO LED DOWN LIGHT FIXTURES 'E'. SEE LIGHTING
REMOVE 1x4 LIGHT FIXTURE.
REPLACE RECEPTACLE WITH A WEATHERPROOF GFCI RECEPTACLE.
JAR TYPE LIGHT FIXTURE 'H', SEE LIGHTING FIXTURE SCHEDULE.
REPLACE EXISTING JAR TYPE FIXTURE WITH A NEW LED
ONLY BE USED FOR UNDERGROUND I.E. ON GROUND RODS.
WITH BURNDY TYPE YGHC-C HYTAP CONNECTORS. EXOTHERMIC WELDS SHALL
ALL ABOVE GROUND LIGHTNING PROTECTION CONNECTIONS SHALL BE DONE
REFER TO DWG DWH-D-ATCT-E15 FOR DETAILS.
PROVIDE A TOTAL OF FOUR DOWN CONDUCTORS FOR TOWER.
WITH APPLICABLE CODE REQUIREMENTS INCLUDING FAA-STD-19F.
DIMENSIONS AND SITE CONDITIONS AND PROVIDE SYSTEMS THAT COMPLY
INTENDED TO SHOW BASIC SYSTEM DESIGN. CONTRACTOR SHALL VERIFY
THE DESIGN SHOWN FOR THESE SYSTEMS ARE SCHEMATIC AND ARE
BE BONDED TO THE SYSTEM IN ACCORDANCE WITH UL96A REQUIREMENTS.
METAL BODIES WITHIN 6'-0" OF THE LIGHTNING PROTECTION SYSTEM SHALL
GUARDS SHALL EXTEND 6'-0" ABOVE AND 1'-0" BELOW GRADE LEVEL.
1" SCHEDULE 80 PVC GUARDS SHALL BE PROVIDED FOR DOWN CONDUCTORS.
LESS THAN 8 INCHES.
ANGLE OF LESS THAN 90 DEGREES, NOR SHALL IT HAVE A BEND RADIUS OF
NO BEND IN A MAIN OR BONDING CONDUCTOR SHALL FORM AN INCLUDED
DOWN CONDUCTORS SHALL FOLLOW THE MOST DIRECT DOWNWARD COURSE.
AS DEFINED BY NFPA 780 UNLESS OTHERWISE SHOWN.
AND BONDING) SHALL BE CLASS I MAIN SIZED COPPER CONDUCTORS
ALL CONDUCTORS USED IN LIGHTNING PROTECTION SYSTEM (MAIN
SURFACES.
SURFACES. ALUMINUM COMPONENTS ONLY SHALL BE USED ON ALUMINUM
COPPER LIGHTNING COMPONENTS SHALL NOT BE MOUNTED ON ALUMINUM
WITH ALL FAA STANDARDS INCLUDING FAA-STD-19F.
INSTALLATION SHALL EXCEED NFPA 780 REQUIREMENTS AND COMPLIES
COMPLETION.
UL MASTER LABEL SHALL BE FURNISHED TO THE OWNER UPON
OF UNDERWRITERS LABORATORIES - LATEST EDITION. THE
REQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS, UL96A"
THE COMPLETED INSTALLATION SHALL MEET THE "INSTALLATION
12.
LIGHTNING PROTECTION NOTES:
ADWH-D-ATCT-E014
CAB & CAB ROOF FLOOR PLANS
-a tc t-e dwh-d-atct-e014
NOTE 1 (TYP)
USE CADWELD TYPE "GY"
FOR ADDITIONAL CONNECTIONS
CADWELD TYPE "GT".
CABLE
PROVIDE SEAL AROUND
RIGID PVC CONDUIT.
2" SCHEDULE 80
PER 1000')
14 AWG WIRES - 375 LBS.
CONDUCTOR (28 STRANDS OF
COPPER LIGHTNING
NO. 10-28C, CLASS II
EVERY 3'-0" MAX.
CABLE FASTENER
COPPER ADHESIVE
NO. 50-262C,
NO.10-28C, CLASS II
PIPE CLAMP
NO.40-354C, TINNED BRONZE
VERTICAL BASE
NO.30-12CVERT, BRASS
50H2
LBS. PER 1000')
OF 14 AWG WIRES - 375
CONDUCTOR (28 STRANDS
NO. 10-28C, CLASS II
HL
H250
ALL DETAILS NOT NECESSARILY APPLICABLE.
ALL AIR TERMINALS SHALL BE SHARP TIP TYPE.
TO PREVENT MOISTURE SEEPAGE PAST THE CONDUIT OR SEAL.
INSTALLED USING WATERPROOFING TREATMENT AND MATERIALS
ALL CONDUITS AND SLEEVES PENETRATING FLOORS SHALL BE
TYPE OR APPROVED EQUAL.
CADWELD OR THOMPSON CATALOG NUMBERS ARE INDICATIVE OF
TYPICAL OF 4
NEW 15'-0" GI AIR TERMINAL SUPPORT.
HYTAP CONNECTORS
BURNDY TYPE YGHC-C
HYTAP CONNECTORS
BURNDY TYPE YGHC-C
SYMBOL
CABLE
THROUGH
CONDUCTOR TO EES
4/0 AWG COPPER
EXOTHERMICALLY WELD
BUILDING
CABLE AWAY FROM THE
SUPPORT TO HOLD THE
SURFACES. PROVIDE CABLE
CABLE TO ANY ALUMINUM
DO NOT ATTACH COPPER
NOTE 1, (TYP)
CAT NO. 246
THOMPSON
GROUND GUARD
GROUND LEVEL
AT NOT LESS THAN 18" ABOVE
COPPER GROUND CONDUCTOR
CAT. NO. 28R TO A 4/0 AWG
COPPER CABLE THOMPSON
CONNECTOR TO CONNECT
USE BURNDY YGHC-C TYPE
HYTAP CONNECTOR
USE BURNDY YGHC-C TYPE
NO.10-28C, CLASS II
ON THE MULLION
RUN THE DOWN CONDUCTOR
TYPICAL OF FOUR PLACE
THE CATWALK GRATE FLOOR
THE MAIN DOWN CONDUCTOR UNDER
EQUALIZATION RING ON THE RAIL TO
CONNECT THE CATWALK POTENTIAL
SUPPORT EVERY THREE FEET
ON THE SIDE OF THE TOWER
RUN THE DOWN CONDUCTOR
AIR TERMINAL
ON BASE BUILDING ROOF
EXISTING AIR TERMINAL
THROUGH CABLE
3/4"x10'-0" COPPER CLAD ROD
SYMBOL
COPPER AIR TERMINAL
SHARP TIPPED SOLID
NO.20-5824C, 5/8"x3'-0"
CATWALK GUARD RAIL
COPPER AIR TERMINAL
SHARP TIPPED SOLID
NO.20-5824C, 5/8"X24"
FASTENERS
WITH STAINLESS STEEL
UNIVERSAL BASE MOUNTED
NO.30-12CU, BRONZE
IN
L
STRAP TYPE PIPE CLAMP
NO.40-XXXC, TINNED BRONZE
CABLE TO FLAT METAL CLAMP
NO.40-213C, BRONZE
CONNECTOR
NO.40-211BM, BIMETAL BRONZE BONDING PLATE
NO.40-217CT, TINNED
GROUND ROD DETAIL
E015
AIR TERMINAL SUPPORT
CAB ELEVATION
MAIN CONDUCTOR SUPPORT
AIR TERMINAL SUPPORT
MAIN CONDUCTOR PASSING THRU PARAPET
DETAIL
DETAIL
TYPICAL BONDING DETAILS
NOTES:
:0 lo tt e
-a tc t-e
ADWH-D-ATCT-E015
DETAILS
-a tc t-e dwh-d-atct-e015
:5 lo tt e
-a tc t-g
HOUSTON, HARRIS COUNTY, TEXAS
AIR TRAFFIC CONTROL TOWER AND BASE BUILDING
HURRICANE HARVEY WATER DAMAGE REPAIR
Y
E R Y
LEN
ILLO
R E A U X
R
IR
EAGLE LN
THORA RD
T OF TRANSPO
T A
IO
IC
OF
STATES
IT
TM
EN
AVIA
LAR
TRAT
SI
NI
VICINITY MAP
07/27/2019
ADWH-D-ATCT-G008
CC
SP
COVER SHEET AND VICINITY MAP
-a tc t-g
SAMUEL PEREZ
A 08/24/2023 DESCOPED REVISIONS AS-BUILT 1705988 09/15/2023 JV
dwh-d-atct-g008 lo tt e
-a tc t-g
A004
A002
A001
A001
GENERAL NOTES: SYMBOLS LEGEND MATERIALS LEGEND
MINERAL/CERAMIC WOOL
ACOUSTICAL CEILING TILE
STEEL
ALUMINUM
BLANKET INSULATION
FIRE-STOP MORTAR
GYPSUM BOARD
PLYWOOD
EXISTING CONSTRUCTION TO REMAIN
NEW FIRE RATED PARTITION
PLYWOOD FLOOR
OR DEMOLITION
NEW CONSTRUCTION
FIRE EXTINGUISHER
PARTITION TYPE
DOOR NUMBER
NOTE NUMBER
DETAIL IS DRAWN
SHEET ON WHICH
OR LETTER
DETAIL INDICATION
WALL SECTION IS DRAWN
DETAIL NUMBER
WALL SECTION NUMBER
WALL SECTION INDICATION
ELEVATION IS DRAWN
ELEVATION NUMBER
ELEVATION INDICATION
SECTION IS DRAWN
BUILDING SECTION INDICATION
SECTION NUMBER
PERMITS, LICENSES AND TAXES
ENVIRONMENTAL PROTECTION
THE CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE AND LOCAL LAWS
AND REGULATIONS CONTROLLING POLLUTION OF THE ENVIRONMENT. HE
SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT POLLUTION OF STREAMS,
LAKES, PONDS, AND RESERVOIRS WITH FUELS, OILS, BITUMENS, CHEMICALS
OR OTHER HARMFUL MATERIALS AND TO PREVENT POLLUTION OF THE ATMOSPHERE
FROM PARTICULATE AND GASEOUS MATTER.
SANITARY, HEALTH AND SAFETY PROVISIONS
THE CONTRACTOR SHALL PROVIDE AND MAINTAIN IN A NEAT, SANITARY CONDITION
SUCH ACCOMMODATIONS FOR THE USE OF HIS EMPLOYEES AS MAY BE NECESSARY TO
COMPLY WITH THE REQUIREMENTS OF THE STATE AND LOCAL BOARD OF HEALTH, OR
ATTENTION IS DIRECTED TO FEDERAL, STATE AND LOCAL LAWS, RULES AND
REGULATIONS CONCERNING CONSTRUCTION SAFETY AND HEALTH STANDARDS. THE
CONTRACTOR SHALL NOT REQUIRE ANY WORKER TO WORK IN SURROUNDINGS OR UNDER
CONDITIONS WHICH ARE UNSANITARY, HAZARDOUS OR DANGEROUS TO HIS HEALTH OR
SAFETY.
UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL REMOVE FROM THE SITE ALL
EMPLOYED BY HIM.
SURPLUS MATERIALS, AND EQUIPMENT BELONGING TO HIM, OR SUBCONTRACTORS
OTHER JURISDICTIONS.
THE CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT, MATERIALS AND
INSTALLATION WORK ARE COORDINATED WITH AND ARE COMPATIBLE WITH THE
ARCHITECTURAL, ELECTRICAL, AND CIVIL PLANS.
WORKING HOURS. THIS CONSISTS OF ELECTRICAL, AND OTHER UTILITIES.
ANY CONSTRUCTION PURPOSE. PARTIAL WORK SHALL BE INSTALLED AFTER NORMAL
BIDDING. ELECTRICAL SERVICE SHALL NOT BE SHUT DOWN OR INTERRUPTED FOR
SITE VISIT IS MANDATORY DUE TO NUMEROUS CONSTRUCTION ITEMS PRIOR TO
WORK WILL NOT BE ALLOWED TO INTERFERE WITH AIR TRAFFIC
CAB HOURS OF OPERATION ARE 7 A.M. TO 10 PM.
OPERATIONS. WORK IN THE CAB SHALL BE PERFORMED FROM 10:15 PM TO 6:15 A.M.
9125 BOUDREAUX ROAD TOMBALL, TEXAS 77379
COORDINATING AGENCIES
ATCT ADDRESS
CONTROL TOWER. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL,
EQUIPMENT AND TRANSPORTATION NECESSARY TO CONSTRUCT ALL ELEMENTS OF A
COMPLETE FACILITY AS SHOWN IN THE PLANS, INCLUDING, BUT NOT LIMITED TO,
THE FOLLOWING:
ALL WORK SHALL BE COORDINATED THROUGH CONTRACTING OFFICE REPRESENTATIVE SO
NOT TO DISRUPT OPERATIONS OF THE CONTROL TOWER.
B. ALL OTHER MISCELLANEOUS ITEMS SHOWN ON THE DRAWING OR
DESCRIBED IN THE SPECIFICATIONS.
EXPEDITIOUS AND DILIGENT PERFORMANCE OF THE WORK.
FEES, AND TAXES AND GIVE ALL NOTICES NECESSARY FOR THE LAWFUL,
THE CONTRACTOR SHALL OBTAIN ALL PERMITS AND LICENSES, PAY ALL CHARGES,
THESE DRAWINGS DEFINE THE WATER DAMAGE REPAIRS AT AN AIRPORT TRAFFIC
A. REPAIR TOWER AND BASE BUILDING WATER DAMAGE CAUSED BY HURRICANE HARVEY.
3. AT MANAGER - KENNETH RODRIGUEZ (281) 376-7309
2. DWH SSC MANAGER - PATRICIA NAVARRO (281) 784-7661
1. FAA REPRESENTATIVE - JENNIFER VANDENBROOK (224) 545-1575
DRAWING NUMBERS TITLE
INDEX OF DRAWINGS
DWH-D-ATCT-G008
DWH-D-ATCT-G009
DWH-D-ATCT-A014
DWH-D-ATCT-A016
SW-D-9229-A1
SW-D-9229-A2
D-6208A A-1
D-6208A A-5
DWH-D-ATCT-E011
DWH-D-ATCT-E012
DWH-D-ATCT-E013
DWH-D-ATCT-E014
COVER SHEET AND VICINITY MAP
INDEX OF DRAWINGS, SYMBOLS/MATERIALS LEGENDS AND GENERAL NOTES
CAB ROOF PLAN
CAB ROOF PLANS AND BASE BUILDING DETAILS
TOWER FLOOR PLANS
CAB FLOOR, WINDOW, CEILING AND ROOF PLANS
LOW ACTIVITY LEVEL, ADMINISTRATIVE BASE BUILDING, PLANS AND SCHEDULES
LOW ACTIVITY LEVEL, EQUIPMENT ROOM ADDITION, PLAN AND SCHEDULES
DRAWING LIST, SYMBOL LEGEND AND ABBREVIATIONS
FLOOR PLANS, ELECTRICAL
CAB & CAB ROOF PLANS, ELECTRICAL
DWH-D-ATCT-E015 DETAILS, ELECTRICAL
FIRST FLOOR PLAN, ELECTRICAL
COME BACK THROUGH THE FLOOR.
1. REMOVE SHOWER ON 4TH FLOOR OF TOWER. MAKE SURE DRAIN IS CAPPED, SO NO GASSES
MECHANICAL NOTES:
07/27/2019
ADWH-D-ATCT-G009
CC
SP
INDEX OF DRAWINGS, SYMBOLS/MATERIALS LEGENDS
AND GENERAL NOTES
-a tc t-g
SAMUEL PEREZ
A 08/24/2023 DESCOPED REVISIONS AS-BUILT 1705988 09/15/2023 JV
dwh-d-atct-g009
GLASS
WIRE
3'-0"
4"6"
3'-0"
NO. NAME
ASSISTANT
MANAGEMENT
WOMEN BATHROOM
MEN BATHROOM
BREAKROOM
CONF/TRAINING
QATS
MANAGER
AIR TRAFFIC
HALL
BA
*WATER PROOF
*WATER PROOF
REMARKSCEILINGWALLSBASEFLOORROOM NAME
NO.
HEIGHTMAT'L
ATC 8'-0"GWBGWBGWBGWBRBCPT
8 HALL
CHIEF
EPDS
UNASSIGNED
MEN
WOMEN
SECRETARY
FRAMEDOOR
SET
HDM
DOOR SIZENO.
DOOR
LABEL
DET
SIGN
REMARKS
9/A-4
B 1-1/23'-0"x7'-0"1
7 3'-0"x7'-0"
3'-0"x7'-0"
TYPE MAT'L FIN. MAT'L DET NO. SHT NO.FIN.
A-47P-2HMS-1WDA3
12 B
B WD
WD
WD S-1
S-1
S-1 HM
HM
HM P-2
P-2
P-2 8
8 A-4
A-4
CPT-1 RB-1 WC-1 P-1 P-1 P-1
GWB*CTCTCTCTCTCT
CT-1
CT
VCT
VCT-1
CPT
CPT-1
CPT-1 RB-1
RB
RB-1
CT
CT-1 CT-1 CT-1 CT-1 CT-1 P-1
8'-0"
8'-0"ATC
P-1
GWB*CTCTCTCT
CT-1 CT-1 CT-1 CT-1
GWBGWBGWBGWB
GWB
WC-1
P-1 P-1 P-1
WC-1
1 2 3 4
DOOR TYPES
ROOM ORIENTATION
REFLECTED CEILING PLAN
ROOM SCHEDULE
ROOM FINISH AND DECORATING SCHEDULE
DOOR SCHEDULE
CONSTRUCTION NOTES:
BUILDING STATISTICS
ARCHITECTURAL GENERAL NOTES
ITEM
ROOM: 4
FLOORING. REFER TO DRAWING D-6208A A-5 (FLOOR PLAN).
REMOVE WOOD FLOORING AND INSTALL NEW CERAMIC
REFER TO DRAWING D-6206A A-5 (REFLECTED CEILING PLAN).
TOWER TOWER LINK. (CEILING TILE 2'X'4' ARMSTRONG 3155 WHITE).
MOUNTED LIGHT FIXTURES AT THE ENTIRE BASE BUILDING AND
BUILDING AND TOWER LINK. REPLACE NON WORKING 2'X4' CEILING
REPLACE CEILING TILES WHERE DAMAGE OR MISSING IN BASE
WITH NEW.
WINDOW GASKETS. REPLACE 1 GLASS IN AT MANAGER OFFICE
RESEAL ALL BASE BUILDING WINDOWS AND REPLACE ALL OUTSIDE
PROCESS AND CONSTRUCTION PHASE.
AND MOVE ALL THE FURNITURE DURING THE PAINTING
THE CONTRACTOR SHALL PROVIDE TEMPORARY STORAGE4
SIZE COLOR LOCATION PART NO.
1-800-537-9527
ROPPE
TOE BASE 5/8
STANDARD
BASE
VINYL WALL CHAMELEON
VINYL WALL BASE
BASE BLDG 624
FINISH SCHEDULE
WALL PAINT BEHR MARQUEE HARVEST BROWN
BASE BLDG/ 710D-4
VINYL TILE TRAFFIC MASTER 12"x12"
STICK VINYL TILE)
(THICK PEEL AND
BEIGE SLATE TOWER LINK
1003051951
STORE SKU:
A4272051
MODEL NO.
VINYL TILE TRAFFIC MASTER 12"x12"
1001565526
STORE SKU:
A4260051
MODEL NO.
STICK VINYL TILE)
(THICK PEEL AND
DARK GRAY SLATE
AREA
STAIRWELL
CARPET
@SHAWINC.COM
TOM VARDELL
214-537-8466
1-800-241-4692
COMMERCIAL
PLILADELPHIA
ASHLAR OR BRICK
QUARTER TURN,
MONOLITHIC,
METHOD:
INSTALLATION
CARPET PLANKS
COLOR: SCHOLARLY
STYLE: PRAISE
BASE BLDG/
82705
COLOR: SCHOLARLY
54882
STYLE: PRAISE
PAINT BEHR MARQUEE PURE EARTH
MANAGER OFFICE
AIR TRAFFIC PPU7-5
PAINT BEHR MARQUEE PURE EARTH PPU7-5SUPERVISOR OFFICE
9"x36"
COLOR: BEIGE
STYLE: MATTE BREAKROOM
832-445-0800
NO.888369134693
ROBERT'S FLOORING
OTHER VENDOR:
FLOOR & DECOR
100503457
TILE
PORCELAIN
PORCELAIN TILE
WOOD PLANK
BRADFORD NATURAL
VALLEY RIDGE
MANUFACTURER
BRICK
ASHLAR
MONOLITHIC
1/4 TURN
FLOOR PLAN
9/A-4
D C
EE
A A
CEILING FAN LOCATIONS
F F
BREAKROOM
EQUIPMENT ROOM
SOUND WALL
AF OFFICE
CBI ROOM AT MANAGER
MEN
WOMEN
SECRETARY
/4
5'-1 1/2"8'-8"1'-9"4'-5"5'-6.8"12'-8.7"30'-6.9"
68'-10"
.3
.5
.9
.8
24'-8.9" 18'-0.3" 9'-2.3" 13'-9.4"
13'-4.7"
.7
20'-0.4"18'-0.7"
7'-0.3" 6'-10.7"
3'-2.2"3'-2.2" 3'-2.2"
3'-2.2" 3'-2.2"
3'-2.2"
3'-2.2"4'-0.8" 3'-6.4"
ARE FIRE-TREATED.
OTHER CONSTRUCTION IN EXTERIOR, OR FIRE RATED WALLS,
ALL WOOD USED FOR BLOCKING, NAILERS, FRAMING OR
COMBUSTIBLE MATERIAL.
OPENINGS AROUND PENETRATIONS ARE FILLED WITH NON-
TIGHT TO THE WALL OR ROOF MATERIAL. ALL CRACKS AND
FROM FLOOR SLAB TO ROOF CONSTRUCTION ABOVE AND FITS
FIRE-RATED PARTITIONS EXTENDS FROM WALL TO WALL AND
OF CMU AND TO FACE OF STUDS.
FACE OF INSULATED PANEL, CENTERLINE OF COLUMNS, FACE
ALL DIMENSIONS, UNLESS OTHERWISE NOTED, ARE TO
DESIGN LOADS: SEE STRUCTURAL GENERAL NOTES.
BUILDING GROSS AREA: (64'-7 3/4" x 25'-11 3/4") = 1680 SF
BUILDING HEIGHT: ONE STORY (12'-7")
OCCUPANCY CLASSIFICATION: GROUP B-2 (OFFICE BUILDING)
OF THE LATEST EDITION OF THE UNIFORM BUILDING CODE.
WITH ALL CRITERIA ESTABLISHED THEREBY AND WITH REQ'RS
NON-COMBUSTIBLE) CONSTRUCTION. THE BUILDING COMPLIES
CONSTRUCTION CLASSIFICATION IS TYPE II-N (UNPROTECTED
THE BUILDING. RESEAL AROUND ALL EXTERIOR DOORS AND OPENINGS.
EXTERIOR DOORS ATO PREVENT WIND-DRIVEN RAIN FROM ENTERING
REPLACE FULL EXTERIOR SEAL OF DOOR AND THRESHOLD TO ALL 5
lo tt e
-6 a -a -1
04/30/1985
LARRY LANGWELL
PEH
TOMBALL
RBC
LAM
LOW ACTIVTY LEVEL
ADMINISTRATIVE BASE BUILDING
PLANS AND SCHEDULES
a -a -1
TECHNICAL OPERATIONS
CENTRAL SERVICE AREA FORT WORTH, TX
THIS DRAWING PRODUCED ON THE ASW RO REGION MICROSTATION SYSTEM
W. DONALD SIWNNEY
B 11/21/2005 EQUIP RM ADDITION AS-BUILT PER F.ODANGA 109738 08/20/2005 MAM
C 06/10/2019 AS-BUILT (M. MOLINAR; JON 61034). 1705988 08/20/2005 MAM
D 08/24/2023 CONSTRUCTION (S. PEREZ). 1705988 06/10/2019 SP
E 08/24/2023 DESCOPED REVISIONS 1705988 09/15/2023 JV
d-6208a-a-1
EL 0'-0"
FLOOR LINE
BLOCK
SPLASH
DOWNSPOUT
STUCCO
GUTTER
AWNING
(1) - 6'-0"x4'-6"
(1) - 5'-10"x4'-6"
ADDITION ORIGINAL
CMU
FURRING
1x3 WOOD
1/2" GWB
6"
8'-0"6'-0"
38"
0 1
A 10
8 1
SEALANT AS REQD
WITH ACOUSTICAL
SOUND WALL
CABINETS
FOR KITCHEN
SEE DWG A-6
27'-0"
7'-9 1/2"
2'-0" 3'-10"
18'-2"
3'-4"
16'-3 1/2" 3'-4 1/2" 1'-6"
19'-8 1/4"
NAME
MENS
BREAK ROOM
HALL
EQUIPMENT9
8A
DOOR NO. DOOR SIZE
SET
HDM
TYPE MAT'L
DOOR
FIN. MAT'L FIN.
FRAME
DET NO. SHT NO.
LABEL
DET
SIGN
EQUIP. ROOM9/A-420 MINA-4
A-47A, 7B
7A,7B
8A, 8BMATCH DOOR NO.4
BRONZE/ANODIZED
BRONZE/ANODIZEDAL.
AL.
STEELMATCH DOOR NO.4
CLEAR/ANODIZED
BRONZE/ANODIZEDAL. GLAZED
AL. GLAZED
WDA
B3'-6"x7'-0"
3'-0"x7'-0"8
9 EQUIPMENT ROOM
BREAK ROOM
ROOM NAME FLOOR BASE
21 3 4
WALLS CEILING
MAT'L HEIGHT
P-4
STRUCTURE
ROOF DECKVARIES
8'-0"ATC
ATC-2
EXP
P-4P-4
P-3
GWBGWB
P-4P-4
GWBGWB
P-4RB-3
RB-2
RBSVT
SVT-1
VCT
VCT-3
PARTITION TYPE-C DOOR TYPE
REFERENCE
ROOM ORIENTATION
DOOR SCHEDULE
ROOM FINISH AND DECORATING SCHEDULE
ROOM SCHEDULE
ELL AND ENDING AT 12" FROM BUILDING AND AFF.
1-1/2" SCH 40 PVC CONDUIT WITH A SWEEP
CAPPED UNDERGROUND BEYOND THE SIDEWALK.
(4) - 4" PVC, 1-1/2" COATED RGSC SWEEP ELBOWS
FIRE EXTINGUISHER.
FIRE EXTINGUISHER.
THE EXPANDED PORTION OF THE BREAK ROOM.
PLYWOOD OVER GLASS FIBER INSULATION ATOP
SEE DRAWING SW-D-10539-C1.
TWO 1-1/2" PVC COATED RGC TO THE TOWER.
4"x4" WIREWAY WITH HINGED TOP COVER.
2"x12" CABLE TRAY
2"x12" CABLE LADDER
(4) - 4" PVC COATED RGC 24"1
CONSTRUCTION NOTE:
NOTES:
ELEVATION
NOT TO SCALEA-5
FLOOR PLAN
(REFLECTED CEILING PLANS).
ARMSTRONG 3155 WHITE). REFER TO DRAWING D-6208A A-5
BASE BUILDING AND TOWER LINK. (CEILING TILE 2'x4'
2'x4' CEILING MOUNTED LIGHT FIXTURES AT THE ENTIRE
BASE BUILDING AND TOWER LINK. REPLACE NON WORKING
REPLACE CEILING TILES WHERE DAMAGED OR MISSING IN
lo tt e a -a -5
04/15/2004
MARK G. STACK
PLATFORM MANAGER, ANI-640
MAM
LOW ACTIVITY LEVEL
EQUIPMENT ROOM ADDITION
PLAN AND SCHEDULES
a -a -5
MARCO A. MOLINAR
PROJECT ENGINEER, ANI-640
109738
A 11/21/2005 EQUIP RM ADDITION AS-BUILTS PER F.ODANGA 109738
B 02/06/2007 AS-BUILT (M. MOLINAR; JON 61034). 109738 08/20/2005 MAM
C 06/10/2019 CONSTRUCTION (S. PEREZ). 1705988 06/10/2019 SP
D 08/24/2023 DESCOPED REVISIONS 1705988 09/15/2023 JV
d-6208a-a-5
UP
DAMPER
MOTOR OPERATED
24"x24"LOUVER WITH
ENTRANCE
40' TOWER
WALLS IN
COMPLETE
PROVIDE
IG
STAIRWELL NO.1
IG
BATTERY RACKS
CHARGERS
BATTERY
2" HIGH CURB
MAIN PANEL
MDP
PANEL A
SINK
1 1/2" C POWER
OPERATED DAMPER
WITH MOTOR
24"x24"LOUVER
ROOF DRAIN
(1) 2 1/4" COPPER
PVC DRAIN
(3) 1" COPPER
BLOCK
SPLASH
CONC
PRECAST
FAN
EXHAUST
CLCLCL
2'-8"
6'-6" 5'-3"
7'-1"3'-4"7'-1"
5'-5"
17'-6"
EQUIPMENT
ESU
NATCA ROOM
2ND FLOOR
6/A7 (TYPICAL)
BRACE - SEE DET
DIAGONAL WALL
INTERFERENCE WITH
LOCATED TO AVOID
SEE DET 6/A7
AIR CONDITIONER
CHASE
10E
DOWN
X
METAL SHELF
MIRROR WITH
18"x24"
HOLDER
TOWEL
WC
PAPER HOLDER
6'-5"
FINISHED FLOOR
AT 11'-4" ABOVE
CABLE TRAY
AS REQD (TYP)
LEVELING SUPPORTS
DOOR BELOW STARS
2'-0"x2'-6" ACCESS
PANEL
DC
PANEL
AC
BOX
DEMARCATION
TELCO
CHASE
6E
RAILING
STAIRWELL NO.2
ABOVE
CAB WALL
OUTLINE OF
FAN
EXHAUST
OUTLINE OF CATWALK ABOVE
HEIGHT OF FITTING
DETERMINED BY
FITTING; LOCATION
FOR AIR GAP
ACCESS PANELCHASE
RCU
FIDO
MPX10E
AS REQUIRED (TYP)
LEVELING SUPPORTS
RAILING8
A B
BASE BUILDING
LINK
STORAGE
CLOSET
STAIR NO.1
FACPDC
TOWER LINK
JUNCTION LEVEL
C-3 LEVEL: JUNCTION ROOM.
C-2 LEVEL: ELECTRONIC ROOMS & FILE ROOM.
C-2A LEVEL: NATCA OFFICE & ATC SUPPLY ROOM.
GROUND LEVEL: CABLE TRAY AREA (NEXT TO ESU ROOM)
TO ELECTRICAL DRAWINGS FOR DETAILS.
AND REPLACE ALL CEILING TILES AND REPLACE NON WORKING LIGHT FIXTURES. REFER
AND LIGHT FIXTURES IN CAB AND JUNCTION ROOM. FOR REST OF TOWER SHAFT REMOVE
REMOVE AND REPLACE EXISTING CEILING GRID, CEILING TILES, 2'x4' CEILING MOUNTED
UTILITY
TELCO ROOM
SCALE: 3/8" = 1'-0"A1
C-3 LEVEL
5C-2 LEVEL
C-2A LEVEL
A1A5
A5
FILE
ELECTRONIC
3RD FLOOR
SHOWER
JUNCTION
TOILET
2'-9"
SUPPLY
SCALE: 3/8" = 1'-0"
4' 6'2'02'
BLACK 24" x 24" x 1").
BPSM2824BK COLORATION SQUARE TEGULAR 2824
ONLY NATCA OFFICE. (ARMSTRONG CALLA ITEM
WITH WHITE GRID).
ARMSTRONG 3155 WHITE WITH STANDARD WHITE GRID), (ARMSTRONG CALLA ITEM
EXISTING CEILING (SMOKE DETECTORS, FIRE ALARM HORN STROBE). (CEILING TILE 2'x4'
CONTRACTOR SHALL REMOVE AND RE-INSTALL ALL EQUIPMENT ATTACHED TO THE
REMOVE EXISTING DRYWALL PARTITION.
CAP DRAIN AND SUPPLY WATER.
REMOVE EXISTING FIBERGLASS SHOWER.
REMOVE CEILING TILE & SUSPENSION SYSTEM.
C-3 LEVEL SHOWER ROOM:
:0 lo tt e
-9
-a
12/02/1974
ROGER F. BECK
CHIEF OF BRANCH, ASW-440
TOWER FLOOR PLANS
ROBERT J. REHAGEN
CHIEF OF SECTION, ASW-441
D 08/20/2012 ROOF REPLACEMENT AND TWR SHAFT MOD PROJ 908408
E 01/21/2014 AS-BUILT (C. LAY-SOK; JON 20449). 908408 01/21/2014 SP
F 06/10/2019 CONSTRUCTION (S. PEREZ). 1705988 06/10/2019 JV
G 08/24/2023 DESCOPED REVISIONS 1705988 09/15/2023 JV
sw-d-9229-a1
Q
CONTROL CAB
WITH RE. REFER TO ELECTRICAL DRAWING FOR DETAILS.
PROVIDE AND INSTALL NEW CEILING FANS. COORDINATE LOCATION
CEILING SHALL BE COVERED WITH THIS INSULATION.
CEILING TILES. INSULATION SHALL BE 24"x48". THE ENTIRE CAB
PROVIDE AND INSTALL R-19 BATT INSULATION ON TOP OF THE
SUBMIT PRODUCT DATA FOR APPROVAL PRIOR TO CONSTRUCTION.
B. ARMSTRONG PRELUDE XL 15/16" EXPOSED TEE IN TECH BLACK.
TEGULAR 2820 BLACK 24"x24"x1".
A. ARMSTRONG CALLA ITEM 2820BK COLORATIONS SQUARE
FURNISH AND INSTALL NEW CEILING TILES AND SUSPENSION SYSTEM.
DEMOLISH ALL EXISTING CEILING TILE AND SUSPENSION SYSTEM.
W8x10
EXISTING
3/8" PLATE
WELD (4 SIDES)
1/4" FILLET
4"x4"x1/8" TUBE
WELD (4 SIDES)
1/4" FILLET
PLATE
7"x7"x3/8"
DIAMETER
0.5"
R=0.25"
.2
4"
5'-10 3/8"
/8
4'-7 1/16"
HANDRAIL
5"
SPECIFIED
ROOFING AS
PLATFORM
DUCKBOARD
TURNED 90 DEGREES
PLATFORM AND
A/C UNIT
HATCH
ROOF
ELECTRICAL DRAWINGS
3 PLACES, TYP, SEE
OBSTRUCTION LIGHT
SEE DET 3/A7
SCUPPER
OVERFLOW
SEE ELEC DWGS
TYP 3 PLACES
AIR TERMINAL,
PROTECTION
LIGHTNING
TYP, SEE
DUCKBOARD
6'-9" 6'-9"
3'-9"
4'-6"
11'-10 1/16"
9"
SEE DWG A7 FOR WINDOW DETAILS
GLASS
1" INSULATED
AND SILL
WELDED TO HEAD
MULLION S4x7.7
FROM CONTRACT
CARPET DELETED
(BY OTHERS)
CONSOLE EQUIPMENT
TUBE 6x3
5'-11" 11'-10"
23'-8"
5'-11"
SHADE POCKET
SUPPLY GRILL
OVER CEILING TILES
R-19 BATT INSULATION
GRILL 24"x48"
RETURN AIR
OPENING FOR HOIST HOOK
PROVIDE GROMMETTED
INSTALL CEILING FAN
B-21
B-1
B-19 B-19
SUPPORT (TYP)
ARTICULATING ARM
6 1
AP
PR
OX
7'-
6"
(T
YP
2'-0" 2'-0"
24"
5"
1/ 2"
4" 2'-4 1/2"
DETAILS
SEE STR DWGS FOR
CATWALK AND RAILING
DRAWINGS
SPECIFICATIONS AND CONSOLE LAYOUT
A PARTICULAR SITE - SEE CONTRACT
FOR CONSOLE LAYOUT VARIATIONS AT
OUTLINE OF TOWER BELOW
(BY OTHERS)
CONSOLE EQUIPMENT
SEE 5/A6
HATCH,
FLOOR
MET WALL
3'-0" HIGH
UNIT
CONVENIENCE
LADDER
HATCH
LADDER
5 1/8" 2'-6"
/8
9'-4"
18'-8"
SCALE: 3/8" = 1'-0"
4' 6'2'02'
CONTROL CAB WINDOW PLAN
SCALE: 3/8" = 1'-0"A2
2 ARTICULATING ARM MOUNTING TUBE
NOT TO SCALEA2
ROOF PLAN
INSTALLED GLASS OPENING DIMENSIONS
NOT TO SCALEA2
SYSTEM.
SHALL BE DONE AFTER THE INSTALLATION OF CEILING GRID
SATISFACTORY OPERATION AND USE OF THE LADDER. THIS WORK
COMPONENTS, ACCESSORIES AND CONTROL REQUIRED FOR
TELESCOPING LADDER WITH SPECIAL DEEP STEEL FRAME. PROVIDE THE
REMOVE EXISTING TELESCOPING LADDER AND REPLACE WITH A NEW
FLOOR PLAN-CONTROL CAB
TYP COL 2 6x3 1/2
M2
WITH NEW.
REPLACE ALL FLOORING IN TOWER CAB AND JUNCTION FLOOR LEVEL6.
M2 lo tt e
12/02/1974
RGOGER F. BECK
MANAGER OF BRANCH, ASW-440
CAB FLOOR, WINDOW, CEILING
AND ROOF PLANS
ROBERT J. REHAGEN
CHIEF OF SECTION, ASW-441
109738
B 11/21/2004 AS BUILT PER FRED ODANGA. 109738 08/20/2005 MAM
C 02/06/2007 AS-BUILT (M. MOLINAR; JON 61034). 1705988 08/20/2005 MAM
D 06/10/2019 CONSTRUCTION (S. PEREZ). 1705988 06/10/2019 SP
E 08/24/2023 DESCOPED REVISIONS 1705988 09/15/2023 JV
sw-d-9229-a2
File details come from the government source that posted it. Updated .