Fuel Tank Inspection at Joint Base McGuire-Dix-Lakehurst, NJ.
Solicitation number
PANNWD-25-P-0000005887
Issued by

About this file

This document is an API Standard 653 In-Service Inspection Report for Tank 2 (Facility 1841) located at Joint Base McGuire-Dix-Lakehurst, New Jersey, conducted on September 15, 2021. The comprehensive inspection report details the tank's current condition, identifying multiple required and recommended repairs across various tank components including secondary containment, shell supports, level alarm configurations, and appurtenances. Key findings include deteriorated expansion joint sealant, inadequate weld spacing in multiple areas, lack of proper grounding for the product saver tank, insufficient stairway clearances, and missing fire diamond labeling.

The inspection recommends addressing 12 required repairs and 15 recommended repairs to fully comply with UFC 3-460-01 and AW 78-24-27 standards. These recommendations range from installing reinforcement plates on shell supports and relocating water level sensors to reconfiguring level alarm assemblies and installing proper scaffold supports. The tank's shell was evaluated as having a remaining life of greater than 30 years under current conditions. The next recommended out-of-service inspection is scheduled for January 2035, with the next in-service external inspection recommended for September 2026.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers Omaha District

API 653 In-Service Inspection Report

JB McGuire-Dix-Lakehurst, NJ Tank 2 (Facility 1841)

US Army Corps of Engineers Center of Expertise for Petroleum, Oils, and Lubricants

(USACE POL-MCX)

9/15/2021

Table of Contents

ACRONYMS AND ABBREVIATIONS

GENERAL SUMMARY

INSPECTION INFORMATION

EQUIPMENT USED

STATE REGULATIONS

PREVIOUS INSPECTION DATES

RECOMMENDED FUTURE INSPECTION DATES

A. GENERAL PROJECT INFORMATION

1. API 653 Inspection

2. Site Information

B. TANK INSPECTION COMMENTS

1. Tank Construction

2. Secondary Containment

3. Tank Foundation

4. Tank Bottom

5. Tank Shell

6. Tank Floating Roof

7. Tank Fixed Roof

8. Tank Appurtenances

9. Tank Piping System

10. Fire Protection System

C. FINDINGS AND RECOMMENDATIONS

1. MANDATORY REPAIRS per API 653, UFC 3-460-01, or AW 78-24-27 Standards

2. REQUIRED REPAIRS to Fully Comply with API 653, or, Federal, State, and Local Codes

3. RECOMMENDED REPAIRS TO FULLY COMPLY WITH UFC 3-460-01, AW 78-24-27 Standards or as Part of Regular Maintenance

APPENDIX A: ENGINEERING CALCULATIONS ............................................................................................................... A-1 APPENDIX B: ENGINEERING DRAWINGS ........................................................................................................................ B-1 APPENDIX C: ENGINEERING DATA .................................................................................................................................... C-1 APPENDIX D: API 653 CHECKLISTS FOR TANK INSPECTIONS .............................................................................. D-1 APPENDIX E: PHOTOGRAPHS .............................................................................................................................................. E-1

ACRONYMS AND ABBREVIATIONS

API American Petroleum Institute

ASME American Society of Mechanical Engineers

ASNT American Society of Non-Destructive Testing

ATG Automatic Tank Gauge

BBL Barrel

CFR Code of Federal Regulations

CP Cathodic Protection

DFT Dry Film Thickness

HLA High Level Alarm

HLCS High Level Control Shutoff

HHLA High-High Level Alarm

LLA Low Level Alarm

LLLA Low-Low Level Alarm

MFL Magnetic Flux Leakage

MT Magnetic Particle Testing

NACE National Association of Corrosion Engineers

NDT Non-Destructive Testing

NFPA National Fire Protection Association

PSI Pounds per Square Inch

PT Penetrant Testing

P/V Pressure/Vacuum

RP Recommended Practice

PST Product Saver Tank

RT Radiography Testing

TML Thickness Measurement Location

TRV Thermal Relief Valve

UFC Unified Facilities Criteria

UFGS Unified Facilities Guide Specifications

ULS Ultra Low Sulfur

UT Ultrasonic Testing

VT Visual Testing

GENERAL SUMMARY

Summary of Inspection

An API Standard 653 In-Service inspection of Tank 2 (Facility 1841) at JB McGuire-Dix-Lakehurst, NJ was completed on September 15, 2021. The shell service life evaluation performed as having greater than 30 years of remaining shell life under current conditions.

Mandatory None

Short Term

1. The expansion joint sealant is deteriorated on the secondary containment floor, which may prevent containment of product as required by 40 CFR 112. The sealant is dry-rotted, cracked, and many areas have pulled away from the edges of the concrete wall plates. (Quantity: 1200 LF)

2. The containment floor has several areas of exposed cracks, which may prevent containment of product as required by 40 CFR 112. (Quantity: 470 LF)

3. The weld spacing is inadequate between the reinforcement of manhole 1 and the shell-to-bottom weld. The minimum required weld spacing is 3 inches. The weld spacing measured 2 inches.

Magnetic particle (MT) examination is required on the affected welds. (Quantity: 1 area)

4. The weld spacing is inadequate between the reinforcement of manhole 2 and the shell-to-bottom weld. The minimum required weld spacing is 3 inches. The weld spacing measured 1-1/2 inches.

Magnetic particle (MT) examination is required on the affected welds. (Quantity: 1 area)

5. The weld spacing is inadequate between the reinforcement of the 16-inch issue line and the shell-to-bottom weld. The minimum required weld spacing is 3 inches. The weld spacing measured 2 inches.

Magnetic particle (MT) examination is required on the affected welds. (Quantity: 1 area)

6. The weld spacing is inadequate between the reinforcement of the 8-inch receipt line and the shell-to-bottom weld. The minimum required weld spacing is 3 inches. The weld spacing measured 2-1/2 inches. Magnetic particle (MT) examination is required on the affected welds. (Quantity: 1 area)

7. The chime area and sealant condition could not be evaluated due to a tape covering the entire chime area from the shell to the concrete ringwall. The inspection of the chime area is part of the inspection requirements of API Standard 653. The tape covering should be removed for proper evaluation.

Note: The chime extension beyond the shell appears to be sufficient. (Quantity: 200 LF)

8. The product saver tank is not grounded or bonded as required by NFPA 30. (Quantity: 1)

9. The tank does not have an NFPA fire diamond label. (Quantity: 1)

10. The circumferential stairway has inadequate clearance between the handrail and the high level control assemblies. The existing clearance is 18-inches. 29 CFR 1910.25(d)(1) requires a minimum width of 26-inches. (Quantity: affects 8 steps)

11. The bottom step of the stairway at the base of the circumferential stairway has a 19-inch clearance between the first step and the secondary containment floor, which does not meet 29 CFR 1910 step rise and run requirements. The stairway rise measured 9 inches, and the run measured 9-1/2 inches. (Quantity: 1 concrete base)

Long Term

1. The tank does not have any anchoring. Tank anchoring is only required when required by seismic evaluation. Tank anchoring also prevents tanks from floating and causing additional damage when the berm sufficiently fills with liquid (water or fuel), and the tank does not have sufficient product.

Tanks floating off their foundations has occurred at a few military installations. (Quantity: 1 system)

2. The supports of the fire line do not have reinforcement plates on the shell. Note:Thefirelineisastub
connectionatthebermwall. (Quantity: 6 supports)

3. The supports of the high level shut-off control tubing do not have reinforcement plates on the shell.

(Quantity: 33 supports)

4. The conduit supports of the high level alarms do not have reinforcement plates on the shell.

(Quantity: 14 supports)

5. The circumferential stairway treads are welded directly to the shell. The stairway configuration is not constructed as shown in AW 78-24-27 as a free-standing stairway. (Quantity: 1 stairway)

6. The tank does not have a 36-inch upper manway and platform to access the IFR in the high leg position as shown in AW 78-24-27. (Quantity: 1)

7. The independent low level alarm assembly is constructed from 1-inch threaded stainless steel with non-lockable ball valves. The assembly is attached to the shell via threaded carbon steel weldolets.

The assembly is not welded and flanged with lockable ball valves as shown in AW 78-24-27. The assembly does not have a means to manually test the alarm sensor to ensure system operability as required for routine maintenance in accordance with UFC 3-460-03. (Quantity: 1)

8. The tank does not have an independent low-low level alarm as shown in AW 78-24-27. (Quantity: 1)

9. The tank has two separate chambers for the independent high and high-high level alarms. Both assemblies are constructed from 1-inch threaded stainless steel with non-lockable ball valves. The assemblies are attached to the shell via threaded carbon steel weldolets. The assemblies are not welded and flanged with lockable ball valves as shown in AW 78-24-27. The assemblies do not have a 1-inch stainless steel drain line to the product saver tank as shown in AW 78-24-27. The assemblies do not have a means to manually test the alarm sensors to ensure system operability as required for routine maintenance in accordance with UFC 3-460-03. (Quantity: 1 new system)

10. The high level shut-off assembly is constructed from 1-inch threaded stainless steel with no isolation valves. The assembly is attached to the shell via threaded carbon steel weldolets. The assembly is not welded and flanged with lockable ball valves as shown in AW 78-24-27. The assembly does not have a 1-inch stainless steel drain line to the product saver tank as shown in AW 78-24-27. The assembly does not have a means to manually test to ensure system operability as required for routine maintenance in accordance with UFC 3-460-03. (Quantity: 1 new system)

11. The VITO (water level) ATG is not near the center of the tank. The VITO system will only detect water until several thousand gallons of water reaches the datum plate elevation. The VITO system stilling well should be installed as close as possible to the center sump. (Quantity: 1)

12. The 8-inch sample hatch used to sample and gauge the tank is not equipped with a winch and floating seal retriever as shown in AW 78-24-27. (Quantity: 1)

13. The fixed roof does not have any scaffold cable supports. (Quantity: 2)

14. The roof circulation vents\inspection hatches cannot be opened due to seized carbon steel thumb-screw fasteners of the chains of the roof perimeter handrail. (Quantity: 4)

15. The strapping charts do not meet UFGS standards. The charts lack tank volumes below the sample gauge to the bottom of the sump and do not show the alarm setpoint heights. (Quantity: 1)

INSPECTION INFORMATION

Inspection Date: September 15, 2021 Inspection(s) Performed: API-653 In-Service Inspector(s): Wayne K. Bailey

EQUIPMENT USED

1. Equipment Type: Ultrasonic Thickness Meter

a. Manufacturer: General Electric

b. Model Number: DMS 2

c. Calibration Method: Two Point Calibration

2. Equipment Type: Surveying Tool

d. Manufacturer: Leica

e. Model Number: 3D DISTO

f. Calibration Method: Manufacturer

STATE REGULATIONS

API-653 In-Service Tank Inspections: NA API-653 Out-of-Service Tank Inspections: NA

NOTE: If there are no state regulations for tank inspections, N/A shall reside in-place of the number of years between inspections. If state regulations reside, the recommended future inspections dates shall be based on whichever is more stringent between the API inspector’s calculations and the state regulations.

PREVIOUS INSPECTION DATES

API Out-of-Service (Internal) Inspection Date: February 2015 API In-Service (External) Inspection Date: February 2015

RECOMMENDED FUTURE INSPECTION DATES

API Out-of-Service (Internal) Inspection Date: January 2035 API In-Service (External) Inspection Date: September 2026

Note:InaccordancewithUFC3‐460‐03,TheOut‐of‐Serviceinspectionintervalisevery10yearsoras
recommendedbyanappropriatelycertifiedtankinspectorinthepreviousAPI653orSTISP001inspection

report.

Signature(s):

Wayne K. Bailey, API-653 #1331

GENERAL TANK INFORMATION

ITEM DESCRIPTION

Owner US Air Force Location JB McGuire-Dix-Lakehurst Facility Number 1842 Tank Number 2 State / Country New Jersey, United States City Trenton Inspection Date September 15, 2021 Tank Manufacturer Witherup Fabrication and Erection Design Standard API Standard 650 Date of Construction 1996 Tank Contents Jet A Tank Serial Number 06291-2 Tank Diameter 63’ 0” Shell Height 56’ 3” Product Height 45’ 10” Tank Capacity 25,000 barrels Foundation Concrete Ringwall

Construction

Bottom Lap-Welded Shell Butt-Welded (Cylindrical) Floating Roof Petrex aluminum honeycomb Fixed Roof Lap-Welded

Material

Bottom Carbon Steel Shell Carbon Steel Floating Roof Aluminum Fixed Roof Carbon Steel

Cathodic Protection Impressed Current Interior Coating System Thin Film Epoxy/Polyurethane (assumed) Exterior Coating System Thin Film Epoxy/Polyurethane (assumed) Level Gauging VAREC MTG, ENRAF ATG, and VITO Water & Temp Probe Overfill Protection Mechanical Automatic Shut-Off

Piping

Receipt 8" Stainless Steel Issue 16" Stainless Steel Low Suction 4” Stainless Steel Water Draw-Off 1 Stainless Steel

Level Alarms & Controls

Description ENFAR ATG Independent High-High Level Alarm: 43’ 08-12/16” 43’ 08-12/16” High-Level Alarm: 42’ 11-00/16” 42’ 11-00/16” Low-Level Alarm: 7’ 00-00/16” Unknown Low-Low Level Alarm: 2’ 03-06/16” None High-Level Control Shut-off: Unknown

Type of Internal Floating Roof

Sealed Honeycomb Cell Floating Pan

A. GENERAL PROJECT INFORMATION

1. API 653 Inspection This project will perform API 653 inspections of various tanks at facilities throughout the United States. Additional consideration is given to federal, state, and local regulations, as well as applicable military criteria and general industry standards.

An API Standard 653 In-Service inspection was performed for Tank 2 (Facility 1841).

2. Site Information On September 15, 2021, InterSpec, LLC performed an API 653 In-Service inspection of Tank 2 (Facility 1841), located at JB McGuire-Dix-Lakehurst, NJ.

B. TANK INSPECTION COMMENTS

1. Tank Construction Tank 2 is a nominal 25,000 barrel, 63’ 0” diameter by 56’ 3” tall, Jet A, aboveground vertical storage tank. The original construction nameplate was affixed to the tank. The tank had several upgrades/repairs (no nameplates).

2. Secondary Containment 40 CFR 112.7(c) states that the entire secondary containment system, “including walls and floor, must be capable of containing oil and must be constructed so that any discharge from a primary containment system ... will not escape containment before cleanup occurs.” 40 CFR 112.8(c)(2) and 40 CFR 112.12(c)(2) state that diked areas must be “sufficiently impervious to contain oil.”

The purpose of the secondary containment requirement is to prevent discharges, as described in 40 CFR 112.1(b); therefore, effective secondary containment methods must be able to contain oil until the oil is cleaned up. The secondary containment area consists of an exposed liner covering earthen material. An informal containment evaluation was conducted. The secondary containment is of sufficient size to contain a total tank loss per UFC 3-460-01 Section 8-14.2.1, “The containment area needs to have sufficient capacity to contain the tank contents plus one foot of freeboard.” The secondary containment area does not drain properly towards the sump.

The secondary containment seams are deteriorating (separation). The secondary containment has minor exposed hairline cracks.

3. Tank Foundation The tank rests on a concrete ringwall. The tank does have an impressed current cathodic protection system. The tank does have a bottom leak detection system with three sumps. The foundation was visually evaluated during the inspection for broken concrete, spalling, cracks, and vegetation against the bottom of the tank. The tank bottom-to-ringwall sealant was not inspected due to a tape covering from the shell to the ringwall. A shell settlement survey was performed during the inspection in accordance with Appendix B of API Standard 653. Settlement results are listed in Appendix A.

4. Tank Bottom The bottom was not evaluated.

5. Tank Shell The shell is constructed of carbon steel material. The shell is a cylindrical design, butt-welded together, consisting of six (6) courses. The shell exterior has a thin film epoxy coating system. The exterior coating was inspected for disbonding, adhesion, deterioration, and discoloration; it is in satisfactory condition. The shell was evaluated for remaining metal thickness utilizing ultrasonic technology. The ultrasonic thickness measurements and thickness measurement locations (TML) are listed in the Shell Plate Thickness Measurements table in Appendix A. A shell service life evaluation performed on all shell courses shows the shell has a remaining life of greater than 30 years under current conditions. The shell service life evaluation is shown in the Shell Service Life Evaluation table in Appendix A. Roundness, peaking, and banding of the shell appear to be within the allowable tolerances of API Standard 653. The shell plumbness evaluation shows the shell to be within the allowable tolerances of API Standard 653. The shell plumbness evaluation is shown in Appendix A. The tank appears to be stable and does not appear to be in danger of overturning or buckling due to high winds or seismic conditions. The tank does not have any anchoring.

6. Tank Floating Roof The tank is equipped with an internal floating roof. The floating roof is a sealed honeycomb cell floating pan. The roof seals and opening gaskets could not be inspected since the roof circulation vents/inspection hatches could not be opened. The floating roof has a foam dam, and the seals could not be visually inspected from the internal ladder access hatch.

7. Tank Fixed Roof The fixed roof is a self-supported cone roof constructed of carbon steel material. The fixed roof has an epoxy coating system on the exterior. The exterior coating was inspected for disbonding, adhesion, deterioration, and discoloration; it is in satisfactory condition. The fixed roof was evaluated for remaining metal thickness using ultrasonic technology. The ultrasonic thickness measurements and ultrasonic thickness locations (TML) are listed in the Fixed Roof Plate Thickness Measurements table in Appendix C.

8. TankAppurtenances
Note:ThefollowingtableisanoverviewoftheappurtenancestatusregardingUFC‐3‐460‐01and
AW78‐24‐78standardsanddoesnotreflectAPIstandards,federalregulations,stateregulations,
and/orlocalregulations.

Overview of Appurtenance

Item Appurtenance

Installe d

Fully or Partiall y

Meets Curren t Design Standa rds

A. Manhole

1. 36-inch manhole located above the IFR high leg position. ☐ ☐

2. At least two (2) fixed roof manholes. ☒ ☐

3. At least two (2) 36-inch shell manholes. ☒ ☒

4. A bolted cover in the fixed roof for installation of IFR. ☒ ☒ B. Inspection Hatches

1. At least of four (4) 24-inch square inspection hatches on fixed roof with IFR (min. spacing 32 feet).

C. Ladder/Stairs

1. Internal ladders with internal floating roofs. ☒ ☒

2. Access to high level shut-off and alarms. ☒ ☐ D. Level Alarms An individual automatic level alarm system, independent of the gauging device or system. Include high, high-high, low and low-low level alarms. On aboveground tanks: provide a means to manually test each alarm sensor to ensure system operability without a full tank; locate level alarm equipment for ready access from ground level, stairway platforms, or roof access.

1. High-High Level Alarm ☒ ☐

2. High Level Alarm ☒ ☐

3. Low Level Alarm ☒ ☐

4. Low-Low Level Alarm ☐ ☐ E. Vents

1. Open atmospheric vents with weather hoods and bird screens.

2. Emergency relief venting (a floating roof or frangible joint may be used to fulfill emergency relief requirements).

F. Gauge/Gauge Hatch/Stilling Wells

1. A mechanical liquid level gauge. ☒ ☒

2. Automatic Tank Gauging (ATG) (ENRAF fuel level & VITO water level systems).

3. One 10-inch roof flanged nozzle with an 8-inch aluminum, fully slotted, stilling well for ATG near the edge of the roof near the top of the stairway platform for fuel level ATG.

Overview of Appurtenance

Item Appurtenance

Installe d

Fully or Partiall y

Meets Curren t Design Standa rds

4. One 8-inch roof flanged nozzle with a 6-inch aluminum, fully slotted, stilling well for temperature and water bottom sensor, as close to or in the tank sump as possible for water level ATG.

5. One 10-inch roof nozzle and an aluminum, slotted stilling well for gauging and sampling.

G. Piping Connection

1. Receipt Line ☒ ☒

2. Low Suction Line ☒ ☒

3. Issue Line. ☒ ☒ H. Overfill Protection

1. Overfill protection with a hydraulically operated diaphragm control valve.

I. Water Draw‐Off

1. Water draw-off system. ☒ ☒ J. Ball Joints

1. Ball joints on pipes to relieve strain caused by tank settling or seismic activity or other means.

K. Cable Supports

1. On the fixed roof of all tanks, provide two scaffold cable supports

a. Water Draw‐Off System

1) Water Draw-Off Line: The water draw-off piping consists of 1-inch stainless steel piping.

The line has two (2) 2-inch double-block and bleed valves at the shell.

2) Product Saver Tank: The product saver tank (PST) is constructed of stainless steel. The PST is not grounded.

b. Low Suction System The tank is equipped with a 4-inch low suction line.

c. Issue Line The 16-inch issue line is stainless steel. The line is protected from overpressure with a thermal relief system. The thermal relief system consists of 1-inch welded/flanged stainless steel piping and fittings.

d. Receipt Line The 8-inch receipt line is stainless steel. The line is protected from overpressure with a thermal relief system. The thermal relief system consists of 1-inch welded/flanged stainless steel piping and fittings.

e. Automatic Tank Gauging (Fuel Level) The tank is equipped with an ENRAF system for electronic fuel level gauging. The system is installed in an 8-inch slotted stainless steel stilling well.

f. Automatic Tank Gauging (Water Level) The tank is equipped with an ENRAF VITO system for electronic water level gauging. The system is installed in a slotted stainless steel stilling well. This stilling well is not located near the center sump.

g. Mechanical Tank Gauging The tank is equipped with a VAREC mechanical tape level gauge for mechanical fuel level gauging. The system is in functional condition.

h. Tank Sampling\Manual Gauging The tank is equipped with a separate stilling well for sampling and manual gauging.

i. Level Alarms\High Level Shut‐Off The ENRAF system provides low, low-low, high, and high-high level alarms. The tank is equipped with independent low, high, and high-high level alarms. The tank does not have an independent low-low level alarm.

The high level alarm assemblies and high level shut-off assembly are accessible from the circumferential stairway. The piping consists of 1-inch threaded stainless steel piping.

j. Ladder and Platforms The tank’s fixed roof is accessible by a circumferential stairway mounted on the shell of the tank. The circumferential stairway has a platform at the fixed roof. The floating roof is accessible by an internal ladder through a 36-inch hatch on the fixed roof.

k. Grounding The tank has six (6) grounding straps around the circumference of the tank.

l. Anchoring The tank is not anchored.

9. Tank Piping System Fuel is received from bulk storage and issued to hydrants.

10. Fire Protection System The fire department provides fire protection. Fire hydrants are located adjacent to the berms.

C. FINDINGS AND RECOMMENDATIONS

The following information identifies the significant findings found during the tank inspection:

1. MANDATORY REPAIRS per API 653, UFC 3‐460‐01, or AW 78‐24‐27 Standards Mandatory Repairs represent items that require immediate attention, in order to prevent imminent risk to system operators, equipment integrity, or the adjacent environment. The tank should remain out of service until these repairs are completed.

None

2. REQUIRED REPAIRS to Fully Comply with API 653, or, Federal, State, and Local Codes Recommended Repairs represent items that should be addressed in a timely manner, in order to prevent future potential risks to system operators, equipment integrity, or the adjacent environment. These items may be required by federal, state and local codes, or by military criteria.

a. SecondaryContainmentExpansionJointSealant
OBSERVATION:The expansion joint sealant is deteriorated on the secondary containment floor,

which may prevent containment of product as required by 40 CFR 112. The sealant is dry-rotted, cracked, and many areas have pulled away from the edges of the concrete wall plates.

(Quantity: 1200 LF)

CODEREFERENCE:40 CFR Sections 112.8(c)(2) and 112.12(c)(2), and UFGS 07 92 00
RECOMMENDATION:Remove the sealant/expansion joint and install new backer rods and

sealant within the containment area. The sealant shall be adequate to accommodate joint compression equal to 50 percent of the width of the joint. The backer rod shall be compressible rod stock of polyethylene foam, polyurethane foam, butyl rubber foam, or other flexible, non-absorptive material as recommended by the sealant manufacturer. Sealant shall conform to UFGS 07 92 00 Joint Sealant.

b. SecondaryContainmentHairlineCracks
OBSERVATION:The containment floor has several areas of exposed cracks, which may prevent

containment of product as required by 40 CFR 112.

CODEREFERENCE:40 CFR 112.7(c); 40 CFR 112.8(c)(2), 40 CFR 112.12(c)(2), 40 CFR 112.1(b)
RECOMMENDATION:Repair all exposed cracks in the containment floor by grinding in a V-

shape pattern with at least ¼-inch width at the surface and a depth of at least ¼-inch and sealing with flexible urethane (e.g. Sikaflex 1c) or a similar approved sealant. (Quantity: 470

LF)

c. Manhole1RepadWeldSpaceatBottom
OBSERVATION:The weld spacing is inadequate between the reinforcement of the 36-inch

manhole and the shell-to-bottom weld. The weld spacing measured 3 inches. Previous reports do not indicate any weld testing.

CODEREFERENCE:API Standard 650 Section 5.7.1.1
RECOMMENDATION:Magnetic particle (MT) examination should be performed on the
affected welds. Note:MTexaminationwillberequiredonallfutureinspectionsunless

modified. (Quantity: 1 Area)

d. Manhole2RepadWeldSpaceatBottom
OBSERVATION:The weld spacing is inadequate between the reinforcement of the 36-inch

manhole and the shell-to-bottom weld. The weld spacing measured 1.5 inches. Previous reports do not indicate any weld testing.

CODEREFERENCE:API Standard 650 Section 5.7.1.1
RECOMMENDATION:Magnetic particle (MT) examination should be performed on the
affected welds. Note:MTexaminationwillberequiredonallfutureinspectionsunless

modified. (Quantity: 1 Area)

e. IssueLineRepadWeldSpaceatBottom
OBSERVATION:The weld spacing is inadequate between the reinforcement of the 16-inch issue

line and the shell-to-bottom weld. The weld spacing measured 2 inches. Previous reports do not indicate any weld testing.

CODEREFERENCE:API Standard 650 Section 5.7.1.1
RECOMMENDATION:Magnetic particle (MT) examination should be performed on the
affected welds. Note:MTexaminationwillberequiredonallfutureinspectionsunless

modified. (Quantity: 1 Area)

f. ReceiptLineRepadWeldSpaceatBottom
OBSERVATION:The weld spacing is inadequate between the reinforcement of the 8-inch receipt

line and the shell-to-bottom weld. The weld spacing measured 2.5 inches. Previous reports do not indicate any weld testing.

CODEREFERENCE:API Standard 650 Section 5.7.1.1
RECOMMENDATION:Magnetic particle (MT) examination should be performed on the
affected welds. Note:MTexaminationwillberequiredonallfutureinspectionsunless

modified. (Quantity: 1 Area)

g. ChimeTapeCovering
OBSERVATION:The chime area and sealant condition could not be evaluated due to a tape

covering the entire chime area from the shell to the concrete ringwall. The activity reported that the tape material was installed due to failing sealant between the bottom and the ringwall.

CODEREFERENCE:API-653 Checklist Item C.1.2.1.c
RECOMMENDATION:Remove the tape material and inspect the foundation for further

recommendations. (Quantity: 200 LF)

h. ProductSaverTankGrounding
OBSERVATION:The product saver tank is not grounded.
CODEREFERENCE:NFPA 30 6.5.4.2 and AW 78-24-27 Drawing D.13 Detail 5
RECOMMENDATION:Install a grounding cable for the product recovery tank in accordance

with AW 78-24-27 Drawing D.13 Detail 5. (Quantity: 1)

i. CircumferentialStairwayClearanceatHighLevelControls
OBSERVATION:The circumferential stairway has inadequate clearance at the high level control

assemblies. The existing clearance is 18 inches. OSHA 1910.24(d) requires a minimum clearance of 26 inches.

CODE REFERENCE: OSHA 29 CFR 1910.25

RECOMMENDATION: Extend the stairway treads at the high level control assemblies to meet

the requirements of OSHA 29 CFR 1910.25. Note:Thestairtreadswerealreadyextendedat
thislocation,butmoretreadsneedtobeextended. (Quantity: 1 Area)
j. CircumferentialStairwayRisetoRunatBottom
OBSERVATION:The bottom step of the stairway at the base of the circumferential stairway has

a 19-inch clearance between the first step and the secondary containment floor, which does not meet 29 CFR 1910 step rise and run requirements. The stairway rise measured 9 inches and, the run measured 9-1/2 inches.

CODE REFERENCE: API Standard 650 Table 5.18 and OSHA 29 CFR 1910.25 RECOMMENDATION: Install a concrete landing to match the rise and run of the circumferential stairway. (Quantity: 1 concrete base)

k. NFPAFireDiamondLabel
OBSERVATION:The tank does not have an NFPA fire diamond label.
CODEREFERENCE:NFPA 30 and NFPA 704
RECOMMENDATION:Install a NFPA 704 diamond label and product label. (Quantity: 1)
l. RepairDataPlate
OBSERVATION:The tank does not have any repair data plates for the upgrades/repairs as

required by API Standard 650 Section 10.

CODEREFERENCE:API Standard 650 Section 10 and AW 78-24-27 Drawing D.11 Detail 4
RECOMMENDATION:Install data plates in accordance with API Standard 650 Section 10 and

AW 78-24-27 Drawing D.10 Detail C2. (Quantity: 1)

3. RECOMMENDEDREPAIRSTOFULLYCOMPLYWITHUFC3‐460‐01,AW78‐24‐27Standards
orasPartofRegularMaintenance

Recommended Repairs represent items that should be addressed in a timely manner, in order to prevent future potential risks to system operators, equipment integrity, or the adjacent environment.

a. TankAnchoring
OBSERVATION:The tank does not have any anchoring. Tank anchoring is only required when

required by seismic evaluation. Tank anchoring also prevents tanks from floating and causing additional damage when the berm sufficiently fills with liquid (water or fuel), and the tank does not have sufficient product. Tanks floating off their foundations has occurred at a few military installations.

CODEREFERENCE:AW 78-24-27 Drawing D.04 Details 1 and 2.
RECOMMENDATION:Install anchor chairs in accordance with AW 78-24-27 Drawing D.04

Details 1 and 2. (Quantity: 1 system)

b. FireLineShellSupports
OBSERVATION:The supports of the fire line do not have reinforcement plates on the shell.Note:
Thefirelineisastubconnectionatthebermwall.
CODEREFERENCE:AW 78-24-27 Drawing D.07 Detail 1
RECOMMENDATION:Install reinforcement plates in accordance with AW 78-24-27 Drawing

D.07 Detail 1. (Quantity: 6 supports)

c. HighLevelShut‐OffControlTubingShellSupports
OBSERVATION:The supports of the high level shut-off control tubing do not have reinforcement

plates on the shell.

CODEREFERENCE:AW 78-24-27 Drawing D.07 Detail 1
RECOMMENDATION:Install reinforcement plates in accordance with AW 78-24-27 Drawing

D.07 Detail 1. (Quantity: 33 supports)

d. HighLevelAlarmConduitShellSupports
OBSERVATION:The conduit supports of the high level alarms do not have reinforcement plates

on the shell.

CODEREFERENCE:AW 78-24-27 Drawing D.07 Detail 1
RECOMMENDATION:Install reinforcement plates in accordance with AW 78-24-27 Drawing

D.07 Detail 1. (Quantity: 14 supports)

e. CircumferentialStairwayDesign
OBSERVATION:The circumferential stairway treads are welded directly to the shell. The

stairway configuration is not constructed as shown in AW 78-24-27 as a free-standing stairway.

CODEREFERENCE:AW 78-24-27 Drawing D.11 Details 1, 2, and 4
RECOMMENDATION:Provide a circumferential stairway designed in accordance with AW 78-

24-27 Drawing D.11 Details 1, 2, and 4. (Quantity: 1 stairway)

f. UpperManhole
OBSERVATION:The tank does not have a 36-inch upper manway and platform to access the
floating roof in the high leg position. Note:Thecircumferentialstairwaydoesnothavea
platformfortherequiredlocation.
CODEREFERENCE:UFC 3-460-01 Table 8-1 Item (c) and AW 78-24-27 Drawing D.10 Details

3 and 6 RECOMMENDATION: Install a 36-inch upper manhole with platform in accordance with AW 78-24-27 Drawing D.10 Details 3 and 6. (Quantity: 1)

g. IndependentLowLevelAlarmConfiguration
OBSERVATION:The independent low level alarm assembly is constructed from 1-inch threaded

stainless steel with non-lockable ball valves. The assembly is attached to the shell via threaded carbon steel weldolets. The assembly is not welded and flanged with lockable ball valves as shown in AW 78-24-27. The assembly does not have a means to manually test the alarm sensor to ensure system operability as required for routine maintenance in accordance with UFC 3- 460-03.

CODEREFERENCE:AW 78-24-27 Drawing D.12 Detail 1
RECOMMENDATION:Replace the existing independent low level alarm assembly in

accordance with AW 78-24-27 Drawing D.12 Detail 1. (Quantity: 1)

h. IndependentLow‐LowLevelAlarmConfiguration
OBSERVATION:The tank does not have an independent low-low level alarm as shown in AW

78-24-27.

CODEREFERENCE:AW 78-24-27 Drawing D.12 Detail 1
RECOMMENDATION:Install an independent low-low level alarm assembly in accordance
with AW 78-24-27 Drawing D.12 Detail 1. Note:ReplacementoftheLLAassemblyper3.h
abovewillreconcilethisfinding. (Quantity: 1)
i. IndependentHighandHigh‐HighLevelAlarmAssemblyConfiguration
OBSERVATION:The tank has two separate chambers for the independent high and high-high

level alarms. Both assemblies are constructed from 1-inch threaded stainless steel with non-lockable ball valves. The assemblies are attached to the shell via threaded carbon steel weldolets. The assemblies are not welded and flanged with lockable ball valves as shown in AW 78-24-27. The assemblies do not have a 1-inch stainless steel drain line to the product saver tank as shown in AW 78-24-27. The assemblies do not have a means to manually test the alarm sensors to ensure system operability as required for routine maintenance in accordance with UFC 3-460-03.

CODE REFERENCE: AW 78-24-27 Drawing D.10 Detail 5, Drawing D.12 Details 2 and 3, Drawing D.13 Detail 5 RECOMMENDATION: Furnish and install new two 1-inch welded and flanged shell nozzles, two ea. test vents, 10 ea. 1-inch lockable ball valves, 1-inch drain piping with test header to/from the PST, 1 ea. 4-inch level sensor chamber with new HLA and HHLA switches, and 1 ea. HLV float chamber with HLV float pilot and 1/2-inch stainless steel tubing to/from the HLV per AW 78-24-27 Drawings D.10 Detail 5, D.12 Details 2 and 3, and D.13 Detail 5.

(Quantity: 1)

j. HighLevelShut‐OffAssemblyConfiguration
OBSERVATION:The high level shut-off assembly is constructed from 1-inch threaded stainless

steel with no isolation valves. The assembly is attached to the shell via threaded carbon steel weldolets. The assembly is not welded and flanged with lockable ball valves as shown in AW 78-24-27. The assembly does not have a 1-inch stainless steel drain line to the product saver tank as shown in AW 78-24-27. The assembly does not have a means to manually test to ensure system operability as required for routine maintenance in accordance with UFC 3-460- 03.

CODEREFERENCE:AW 78-24-27 Drawing D.12 Details 2 & 3, Drawing D.13 Detail 5
RECOMMENDATION:Furnish and install a high level shut-off assembly in accordance with
AW 78-24-27 Drawing D.12 Details 2 & 3, Drawing D.13 Detail 5. Note:Replacementofthe
HLAandHHLAassemblyper3.iabovewillreconcilethisfinding. (Quantity: 1)
k. VITO(WaterLevel)ATGDesign
OBSERVATION:The Honeywell VITO 768 Combi Temperature & Water Probe Sensor ATG

System is not near the center of the tank. The VITO system will only detect water until several thousand gallons of water reaches the datum plate elevation. The VITO system stilling well should be installed as close as possible to the center sump.

CODEREFERENCE:UFC 3-460-01 Table 8-1 item s and AW 78-24-27 Drawing D.07 Detail 3
RECOMMENDATION:Relocate the Honeywell VITO 768 Combi Temperature & Water Probe

Sensor ATG System per UFC 3-460-01 Table 8-1 item s and AW 78-24-27 Drawing D.07 Detail 3. (Quantity: 1)

l. SampleGaugeDesign
OBSERVATION:The 8-inch sample hatch used to sample and gauge the tank is not equipped

with a winch and floating seal retriever as shown in AW 78-24-27.

CODEREFERENCE:AW 78-24-27 Drawing D.07 Detail 2
RECOMMENDATION:Install a floating seal retriever and manual winch in accordance with

AW 78-24-27 Drawing D.07 Detail 2. (Quantity: 1)

m. FixedRoofScaffoldSupports
OBSERVATION:The fixed roof does not have any scaffold cable supports.
CODEREFERENCE:UFC 3-460-01 Table 8-1 Item (ff) and API Standard 650 Section 5.8.8
RECOMMENDATION:Install two (2) API scaffold supports in accordance with API Standard

650 Section 5.8.8. (Quantity: 2)

n. FixedRoofCirculationVents/InspectionHatchesConfiguration
OBSERVATION:The roof circulation vents\inspection hatches cannot be opened due to seized

carbon steel thumb-screw fasteners of the chains of the roof perimeter handrail.

CODEREFERENCE:AW 78-24-27 Drawing D.09 Detail 1
RECOMMENDATION:Replace the existing chains with 3/16-inch galvanized with one end

welded to the post and one end hocked to the other post. (Quantity: 4)

o. TankCalibrationChart
OBSERVATION:The strapping charts do not meet UFGS standards. The charts lack tank volumes

below the sample gauge to the bottom of the sump and do not show the alarm setpoint heights.

CODEREFERENCE:UFGS 33 56 21.17
RECOMMENDATION:Strap the tank at the next tank outage per UFGS 33 56 21.17 and then

reset the ATG alarm setpoint heights. (Quantity: 1)

[No photos available.]

A-1 t min t min t nom t act t prev t nom

D H

H c

G Y

T

S Y T Y T

S

E E E

E E

L r

C r

I ut

I v

Y t prev t act tmin

H DG

SE

Lr tact tmin

Cr Cr tprev tact Y Iut tact tmin Cr

Iv tact tmin

Cr

A-2

D = G = Y =

H S E t min t prev t act t prev t nom tprev tact tmin

A-3

C r L r I v I ut

C r

Corrosion Rate

A-4

Thickness tmin

A-5

A-6

A-7

S max

L D N D N Y E H

D N L Y E H L

S max

A-8

S i | U i U i-1 U i+1

S i | U i i

U i U i+1 U i-1 S i S i

R Note: Settlement evaluation must be done using the arc length method.

A-9

El ev at io ns (f ee t)

Data Points

A-10

S arc

S i

K

K

R

El ev at io ns (i nc he s)

Data Points

A-11

A-12

A-13

A-14

A-15

A-16

A-17

A-18

B-1

Remarks/Legend:

Owner/Operator:

Inspection Firm:

Date: Revision Number: Revision Date:

Drawing Title: Tank Description: Drawing Number:

JB McGuire-Dix

InterSpec LLC

09/17/21 N/A N/A

Tank 2 (Facility 1841) S-1Shell Layout

Seam #1 is the first seam left of the first manway left of the ladder in the first shell course viewing from the outside.

The number in the upper left corner of each plate identifies the plate by the course and position of the plate in that course.

10540

GRAPHIC SCALE:

Dimensions are in feet.

1-1 A

D

2-1

3-1

4-1

5-1

6-1

1-2

E F G

Overflow Vent

MTG

2-2

3-2

4-2

5-2

6-2

1 2 3

A - 36" Manhole B - 2" Water Draw-Off Line C - 2" Water Draw-Off Line D - 4" Low Suction Line E - 16" Issue Line F - 1" Low Level Alarm Assembly G - 1" Low Level Alarm Assembly

B C

WS

WS - Inadequate Weld Spacing

WS

B-2

Inspection Firm:

Date: Revision Number: Revision Date:

Drawing Title: Tank Description: Drawing Number:

InterSpec LLC

09/17/21 N/A N/A

Tank 2 (Facility 1841) S-2Shell Layout

Seam #1 is the first seam left of the first manway left of the ladder in the first shell course viewing from the outside.

The number in the upper left corner of each plate identifies the plate by the course and position of the plate in that course.

10540

GRAPHIC SCALE:

Dimensions are in feet.

1-3

H I

J

K

L M

2-3

3-3

4-3

5-3

6-3

1-4

Overflow Vent

2-4

3-4

4-4

5-4

6-4

3 4 5

H - 1" High Level Alarm Assembly I - 1" High Level Alarm Assembly J - 1" High Level Shut-Off Assembly K - 1" High Level Shut-Off Assembly L - 1" High-High Level Alarm Assembly M - 1" High-High Level Alarm Assembly

Owner/Operator:

JB McGuire-Dix

B-3

Inspection Firm:

Date: Revision Number: Revision Date:

Drawing Title: Tank Description: Drawing Number:

JB McGuire-Dix

InterSpec LLC

09/17/21 N/A N/A

Tank 2 (Facility 1841) S-3Shell Layout

Seam #1 is the first seam left of the first manway left of the ladder in the first shell course viewing from the outside.

The number in the upper left corner of each plate identifies the plate by the course and position of the plate in that course.

10540

GRAPHIC SCALE:

Dimensions are in feet.

1-5 N

Overflow Vent

2-5

3-5

4-5

5-5

6-5

1-6

2-6

3-6

4-6

5-6

6-6

5 6 7

N - 36" Manhole

WS

WS - Inadequate Weld Spacing

B-4

Inspection Firm:

Date: Revision Number: Revision Date:

Drawing Title: Tank Description: Drawing Number:

JB McGuire-Dix

InterSpec LLC

09/17/21 N/A N/A

Tank 2 (Facility 1841) S-4Shell Layout

Seam #1 is the first seam left of the first manway left of the ladder in the first shell course viewing from the outside.

The number in the upper left corner of each plate identifies the plate by the course and position of the plate in that course.

10540

GRAPHIC SCALE:

Dimensions are in feet.

1-7

O

P

Overflow Vent

2-7

3-7

4-7

5-7

6-7

7 1

O - 8" Receipt Line P - 4" Fire Line

WS

WS - Inadequate Weld Spacing

B-5

Inspection Firm:

Date: Revision Number: Revision Date:

Drawing Title: Tank Description: Drawing Number:

InterSpec LLC

09/17/21 N/A N/A

Tank 2 (Facility 1841) R-1Fixed Roof Layout

Measured Diameter is 63 feet.

Fixed roof has 32 plates.

201086420

GRAPHIC SCALE:

Dimensions are in feet.

y x

NW y x

NE

y x

SEy x

SW

XY Orientation

XY Orientation is in reference to Plan North

6 7 8

9 10 11 12

13 14 15 16

17 18 19 20

21 22 23 24

25 26 27

28 29 30 31 32

C

A - 36" Manhole w/ Sample Gauge B - Sample Gauge C - 24" Center Vent

D - 6" VITO ATG

E - 8" ENRAF ATG

F - Hatch G - Mechanical Level Gauge H - Roof Circulation Vents/Inspection Hatch I - 2" Plug J - 2" Floating Roof Anti-Rotation

Owner/Operator:

JB McGuire-Dix

I J

G

H

J

F

H

I

I

I

I

I

I I

I I

I

I

I

I

I

I

I

A

B

D

E

H

H

B-6

Company:

Drawn By:

Date: Rev. No.: Scale:

Drawing Title:

JB McGuire-Dix

InterSpec LLC

09/17/21 N/A 1/600 feet

Tank Farm Layout

Tank 2 Facility 1841

Tank 1 Facility 1842

NORTH

B-7

Company:

Drawn By:

Date: Rev. No.: Scale:

Drawing Title: Tank Description:

JB McGuire-Dix

InterSpec LLC

09/17/21 N/A 1/490 feet

Containment Layout Tank 2 (Facility 1841)

Tank 2 Facility 1841

Tank 1 Facility 1842

NORTH

The secondary containment has concrete floor with sloped concrete walls. The containment area measured 131 ft by 184 ft with 6 ft sloped walls.

Exposed Hairline Cracks Deteriorated Sealant

8" Receipt Line 16" Issue Line 4" Fire Line

PST

Drain

Heavy Exposed Hairline Cracks

B-8

C-1

C-2

C-3

C-4

C-5

C-6

C-7

D-1

D-2

D

D-3

AU

M

D-4

D-5

D-6

D-7

NOTES:

D-8

E-1

E-2

E-3

E-4

E-5

E-6

E-7

E-8

E-9

E-10

E-11

E-12

E-13

E-14

E-15

E-16

E-17

E-18

E-19

E-20

E-21

E-22

E-23

E-24

E-25

E-26

E-27

E-28

E-29

E-30

E-31

E-32

ACRONYMS AND ABBREVIATIONS
GENERAL SUMMARY
INSPECTION INFORMATION
EQUIPMENT USED
STATE REGULATIONS
PREVIOUS INSPECTION DATES
RECOMMENDED FUTURE INSPECTION DATES
A. GENERAL PROJECT INFORMATION
1. API 653 Inspection
2. Site Information
B. TANK INSPECTION COMMENTS
1. Tank Construction
2. Secondary Containment
3. Tank Foundation
4. Tank Bottom
5. Tank Shell
6. Tank Floating Roof
7. Tank Fixed Roof
8. Tank Appurtenances
9. Tank Piping System
10. Fire Protection System
C. FINDINGS AND RECOMMENDATIONS
1. MANDATORY REPAIRS per API 653, UFC 3-460-01, or AW 78-24-27 Standards
None
2. REQUIRED REPAIRS to Fully Comply with API 653, or, Federal, State, and Local Codes
a. Secondary Containment Expansion Joint Sealant
b. Secondary Containment Hairline Cracks
c. Manhole 1 Repad Weld Space at Bottom
d. Manhole 2 Repad Weld Space at Bottom
e. Issue Line Repad Weld Space at Bottom
f. Receipt Line Repad Weld Space at Bottom
g. Chime Tape Covering
h. Product Saver Tank Grounding
i. Circumferential Stairway Clearance at High Level Controls
j. Circumferential Stairway Rise to Run at Bottom
k. NFPA Fire Diamond Label
l. Repair Data Plate
3. RECOMMENDED REPAIRS TO FULLY COMPLY WITH UFC 3-460-01, AW 78-24-27 Standards or as Part of Regular Maintenance
a. Tank Anchoring
b. Fire Line Shell Supports
c. High Level Shut-Off Control Tubing Shell Supports
d. High Level Alarm Conduit Shell Supports
e. Circumferential Stairway Design
f. Upper Manhole
g. Independent Low Level Alarm Configuration
h. Independent Low-Low Level Alarm Configuration
i. Independent High and High-High Level Alarm Assembly Configuration
j. High Level Shut-Off Assembly Configuration
k. VITO (Water Level) ATG Design
l. Sample Gauge Design
m. Fixed Roof Scaffold Supports
n. Fixed Roof Circulation Vents/Inspection Hatches Configuration
o. Tank Calibration Chart