This file comprises design and construction specifications for the Area 3 Pad-D launch site at the Pacific Spaceport Complex on Kodiak Island, Alaska, prepared by BRPH Architects Engineers & Consultants for Alaska Aerospace Corporation. The project involves design and reconfiguration of Pad-D from a 100 feet by 100 feet gravel site to an expanded 240 feet by 560 feet pad, including extensive concrete design for commodity pads, runways, launch pad, deluge catchment trench, utilidors, and building foundations. The scope encompasses design of a Vertical Integration Building (VIB) as a pre-engineered metal building with associated utilities, supporting infrastructure for water storage, deluge tanks, communications, electrical, compressed air, power generation, and launch support elements. The specifications include detailed requirements for hollow metal doors and frames, overhead coiling doors, door hardware, joint sealants, and metal building systems complying with the 2021 International Building Code and ASCE 7 standards. The design is issued for construction as of May 8, 2026, with comprehensive shop drawings and specifications organized across architecture, civil, electrical, mechanical, plumbing, and structural disciplines totaling 73 sheets.
The specifications establish requirements for structural steel framing, metal roof and wall panels, foamed-insulation-core metal wall panels, metal soffit panels, thermal insulation, and personnel doors and frames fabricated to withstand extreme environmental conditions including 160 mph wind loads and 40 PSF snow loads. All materials including cold-rolled steel sheet, hot-rolled steel sheet, metallic-coated steel sheet, and mineral-fiber insulation must comply with referenced ASTM and ANSI standards. The project mandates factory-applied finishes, with shop primers and baked-on factory finishes selected by the architect from manufacturer's full ranges. Installation requirements include field quality control inspections, mockup approval, proper handling and storage to prevent damage or deformation, and coordination with civil, mechanical, and electrical work. Preinstallation meetings are required to review construction methods, structural load limitations, schedule coordination, and weather impacts. The contract requires a single-source manufacturer for each component type, with all structural designs reviewed, signed, and stamped by a professional engineer licensed in Alaska.
Text of this file
ARCHITECT, ENGINEERS & CONSULTANTS
VICINITY MAP
LOCATION MAP
NEW CONSTRUCTION
DESCRIPTION OF WORK
DELEGATED DESIGN / DEFERRED SUBMITTALS
THE SCOPE OF WORK FOR THIS PROJECT WILL INCLUDE THE DESIGN AND RECONFIGURATION OF THE AREA 3, PAD-D LAUNCH SITE AS PART OF THE PACIFIC SPACEPORT COMPLEX ON KODIAK ISLAND, ALASKA FOR ALASKA AEROSPACE CORPORATION. THE PROJECT WILL INCLUDE THE
FOLLOWING DESIGN SCOPE:
• THE SITE CIVIL CONFIGURATION AND DEVELOPMENT OF PAD D FROM A 100FT X 100FT GRAVEL SITE TO AN EXPANDED 240FT X 560FT PAD.
a. SITE WORK WILL INCLUDE EXTENSIVE CONCRETE DESIGN INCLUDING COMMODITY PADS, RUNWAYS, LAUNCH PAD, DELUGE
CATCHMENT TRENCH, UTILIDORS, AND BUILDING FOUNDATIONS.
• THE DESIGN OF THE VERTICAL INTEGRATION BUILDING (VIB) THAT WILL BE ASSOCIATED WITH PAD D. THE VIB WILL BE A PRE-ENGINEERED
METAL BUILDING WITH ASSOCIATED UTILITIES.
• SUPPORTING INFRASTRUCTURE FOR WATER STORAGE AND DELUGE TANKS, COMMUNICATIONS, ELECTRICAL, COMPRESSED AIR, POWER
GENERATION, AND OTHER LAUNCH SUPPORT ELEMENTS.
a. THE VIB WILL INCLUDE LOCATING CONNEX STYLE CONTAINERS FOR ELECTRICAL HOUSING, AIR COMPRESSOR, AND OTHER
COMMODITY STORAGE.
THIS PACKAGE WILL BE FOR THE PRE-ENGINEERED METAL BUILDING BID SET AND ASSOCIATED STRUCTURAL CONCRETE. ADDITIONALLY, THE
PACKAGE WILL INCLUDE SITE CONCRETE DESIGN INTENDED FOR EARLY BID.
ARCHITECTURE
BRPH
19020 33RD AVE W,
SUITE 500
LYNNWOOD, WA 98036
KEN LOWERY
425.760.6343 klowery@brph.com www.brph.com
ISSUE FOR CONSTRUCTION
05/08/2026
NOT TO SCALE
NOT TO SCALE
STRUCTURAL
BRPH
19020 33RD AVE W,
SUITE 500
LYNNWOOD, WA 98036
BRIAN SAYRE
360.589.2904 bsayre@brph.com www.brph.com
PROJECT MANAGER
BRPH
19020 33RD AVE W,
SUITE 500
LYNNWOOD, WA 98036
CHARLES MANNO
206.858.1685 cmanno@brph.com www.brph.com
MECHANICAL/ PLUMBING
BRPH
5700 NORTH HARBOR CITY BLVD
SUITE 400
MELBOURNE, FL 32940
DANIEL QUINONES
321.247.2307 dquinones@brph.com www.brph.com
ELECTRICAL
BRPH
19020 33RD AVE W,
SUITE 500
LYNNWOOD, WA 98036
SUSAN SCHILLER
206.499.2506 sschiller@brph.com www.brph.com
CIVIL
BRPH
5700 NORTH HARBOR CITY BLVD
SUITE 400
MELBOURNE, FL 32940
321.408.8423
JENNIFER HARVIN
jharvin@brph.com www.brph.com
THE FOLLOWING BUILDING COMPONENTS, EQUIPMENT OR SYSTEMS REQUIRE DELEGATED DESIGN SERVICES PROVIDED BY AN OUTSIDE DESIGN PROFESSIONAL. SHOP DRAWINGS FOR THESE WILL BE SUBMITTED TO THE BUILDING OFFICIAL AFTER REVIEW AND APPROVAL FROM THE DESIGNER
OF RECORD.
• PRE-ENGINEERED METAL BUILDING
1. INSULATED METAL WALL PANELS
2. METAL ROOF PANELS
• COLD-FORMED STEEL FRAMING
• SNOW GUARDS
NORTH
NORTH
PROJECT SITE
PROJECT SITE
A K
AF AL
T S
TA
E O
49 TH
S
Kenneth M Lowery No.14640
R EG IST ER ED P R O F E S S I O N A L A R CH IT
ECT
Architects Engineers, Inc.
www.brph.com Copyright © 2026
19020 33rd Ave W | Suite 500 Lynnwood | Washington | 98036 425-921-3500
Alaska Business Entity Number: 56725F
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
ISSUE FOR CONSTRUCTION
54321 6
A
B
C
D
E
U :\R ev it
P ro je ct
F ile s\
\C
_A _2
5_
C en tr al
_c ko tr lik
.r vt
5/ 8/
0:
:0
A
M
A R
E A
P
A D
D
BRPH
C. KOTRLIK
P A
C
IF
IC
S
P A
C E
P O
R T
C O
M P
L E
X
K O
D
IA
K I S
L A
N D
A
L A
S K
A
A L A
S K
A A
E R
O S
P A
C E
C O
R P
O R
A T
IO
N
C09729.001
G-001
05/08/2026
COVER SHEET
KEN LOWERY
AK NO. 14640
ALASKA AEROSPACE CORPORATION
PACIFIC SPACEPORT COMPLEX, KODIAK ISLAND, ALASKA
AREA 3 PAD D
ARCHITECTURE
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
LS-001 CODE SUMMARY 05/08/2026 No
A-101 FLOOR PLAN 05/08/2026 No
A-191 ROOF PLAN 05/08/2026 No
A-201 ELEVATIONS 05/08/2026 No
A-301 BUILDING SECTIONS 05/08/2026 No
A-501 DETAILS 05/08/2026 No
Total Sheets: 6CIVIL
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
B-100 TEST PIT LOCATIONS (FOR REFERENCE ONLY) 05/08/2026 No
B-101 TEST PIT LOGS (FOR REFERENCE ONLY) 05/08/2026 No
C-001 CIVIL GENERAL NOTES, LEGEND & ABBREVIATIONS 05/08/2026 No
C-101 DEMOLITION PLAN 05/08/2026 No
C-121 SITE PLAN 05/08/2026 No
C-141 GRADING & DRAINAGE PLAN 05/08/2026 No
C-161 UTILITY PLAN 05/08/2026 No
C-400 CROSS SECTIONS 05/08/2026 No
C-401 CROSS SECTIONS 05/08/2026 No
C-501 SITE DETAILS 05/08/2026 No
C-502 UTILITY DETAILS 05/08/2026 No
C-503 JOINTING DETAILS 05/08/2026 No
C-700 JOINTING PLAN 05/08/2026 No
Total Sheets: 13
ELECTRICAL
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
E-001 ELECTRICAL LEGEND & ABBREVIATIONS 05/08/26 No
E-002 ELECTRICAL SPECIFICATIONS 05/08/26 No
E-101 ELECTRICAL PLAN 05/08/26 No
EL-101 ELECTRICAL LIGHTING PLAN 05/08/26 No
E-121 SITE PLAN 05/08/26 No
E-122 SITE GROUNDING 05/08/26 No
E-123 SITE LIGHTNING PROTECTION 05/08/26 No
E-401 ENLARGED ELECTRICAL PLANS 05/08/26 No
E-402 ENLARGED ELECTRICAL PLAN 05/08/26 No
E-403 ENLARGED GROUNDING PLAN 05/08/26 No
E-501 ELECTRICAL DETAILS 05/08/26 No
E-502 HAZARDOUS AREAS 05/08/26 No
E-503 AREA WARNING LIGHTS 05/08/26 No
E-504 ELECTRICAL DETAILS 05/08/26 No
E-505 ELECTRICAL DETAILS 05/08/26 No
E-601 ONE LINE DIAGRAM 05/08/26 No
E-602 CONDUIT ONE-LINES WITH LENGTHS 05/08/26 No
E-701 PANEL SCHEDULES 05/08/26 No
E-702 PANEL SCHEDULES 05/08/26 No
Total Sheets: 19
GENERAL
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
G-001 COVER SHEET 05/08/2026 No
G-002 ABBREVIATIONS, SYMBOLS, GENERAL NOTES 05/08/2026 No
G-003 SPECIFICATIONS 05/08/2026 No
G-004 SPECIFICATIONS 05/08/2026 No
Total Sheets: 4
MECHANICAL
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
M-001 LEGENDS & GENERAL NOTES 05/08/2026 No
M-002 GENERAL NOTES 05/08/2026 No
M-101 HVAC FLOOR PLAN 05/08/2026 No
M-401 MECHANICAL ENLARGED PLANS 05/08/2026 No
M-501 MECHANICAL DETAILS 05/08/2026 No
M-601 MECHANICAL SCHEDULES 05/08/2026 No
M-701 MECHANICAL CONTROL DIAGRAMS 05/08/2026 No
Total Sheets: 7
STRUCTURAL
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
S-001 GENERAL NOTES 05/08/2026 No
S-002 SPECIAL INSPECTIONS 05/08/2026 No
S-003 SPECIAL INSPECTIONS 05/08/2026 No
S-004 ABBREVIATIONS, LEGENDS & SPLICE TABLES 05/08/2026 No
S-005 WIND LOAD TABLES 05/08/2026 No
S-006 GRAVITY LOAD TABLES 05/08/2026 No
S-007 PEMB REQUIREMENTS 05/08/2026 No
S-008 CONCRETE SPECS 05/08/2026 No
S-100 SITE PLAN 05/08/2026 No
S-101 VIB SLAB & FOUNDATION PLANS 05/08/2026 No
S-130 LAUNCH PAD & TRENCHES SLAB PLAN 05/08/2026 No
S-131 EAST COMMODITY PAD SLAB PLAN 05/08/2026 No
S-132 WEST COMMODITY PAD SLAB PLAN 05/08/2026 No
S-133 SOUTH RAT SLAB 05/08/2026 No
S-500 SECTIONS & DETAILS 05/08/2026 No
S-501 SECTIONS & DETAILS 05/08/2026 No
S-502 SECTIONS & DETAILS 05/08/2026 No
S-503 SECTIONS & DETAILS 05/08/2026 No
S-504 SECTIONS & DETAILS 05/08/2026 No
S-505 SECTIONS & DETAILS 05/08/2026 No
S-601 SCHEDULES 05/08/2026 No
S-610 MATERIAL TAKEOFFS 05/08/2026 No
Total Sheets: 22
PLUMBING
SHEET
NO. SHEET NAME
SHEET
ISSUE DATE
CURRENT
REVISION
CURRENT
REVISION
DATE CURRENT REVISION DESCRIPTION
CURRENT
REVISION
ISSUED
P-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES 05/08/2026 No
P-101 PLUMBING PLAN 05/08/2026 No
P-121 SITE PLAN 05/08/2026 No
P-401 PLUMBING ENLARGED PLANS 05/08/2026 No
P-501 PLUMBING DETAILS 05/08/2026 No
P-502 PLUMBING TANK DETAILS 05/08/2026 No
P-601 PLUMBING SCHEDULES 05/08/2026 No
P-901 PLUMBING SCHEMATIC RISERS 05/08/2026 No
Total Sheets: 8
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR VERIFYING SITE, FIELD AND BUILDING CONDITIONS ASSOCIATED WITH THIS WORK PRIOR TO SUBMITTING BIDS AND COMMENCING WORK. IF THERE ARE ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS, CONFER WITH CONSTRUCTION MANAGER AND ARCHITECT/ENGINEER FOR RESOLUTION.
2. ADDITIONS/ALTERATIONS PROJECTS: THE DESIGN DEPICTED HEREIN IS BASED ON INFORMATION (AS-BUILTS, RECORD DRAWINGS, SURVEY, GEOTECHNICAL SERVICES, ETC.) PROVIDED BY THE OWNER OR OTHERS. UNLESS OTHERWISE DIRECTED BY THE CONTRACT, ANY VERIFICATION OF THIS INFORMATION IS LIMITED TO FIELD OBSERVATION; UNKNOWN CONDITIONS MAY EXIST THAT WILL ONLY BE REVEALED AS THE CONTRACTOR’S WORK PROGRESSES. GIVEN THE NATURE OF THESE PROJECTS, THE CONTRACTOR SHOULD ANTICIPATE THE NEED FOR ADJUSTMENTS TO THE DESIGN AS UNKNOWN
CONDITIONS ARE DISCOVERED DURING CONSTRUCTION.
3. CONTRACTOR SHALL FURNISH ALL ADDITIONAL DATA AND DOCUMENTATION TO SECURE ALL REQUIRED PERMITS AND SHALL
COORDINATE THIS DATA WITH THE CONSTRUCTION DOCUMENTS WHERE REQUIRED.
4. ALL DETAILS AND SECTIONS SHOWN IN THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO SIMILAR CONDITIONS ELSEWHERE ON THE PROJECT, EXCEPT WHERE INDICATED BY A DIFFERENT DETAIL.
5. CONTRACTOR TO PROVIDE COMPLETE AND WORKING MEP/FP/IT SYSTEMS IF INDICATED IN ANY PORTION OF THE DRAWINGS.
6. PLANS WHICH APPEAR AS BACKGROUNDS ON ENGINEERING DRAWINGS ARE FOR THE PURPOSE OF ILLUSTRATING GENERAL SPACE CONFIGURATION ONLY AND SHALL NOT BE USED FOR PORTIONS OF THE WORK OTHER THAN THAT PERTAINING TO
THE TITLE OF EACH SHEET.
7. AROUND ALL EXPOSED PIPES, CONDUIT OR DUCTS, INSTALL ENCLOSURES OF THE SAME MATERIAL AND FINISH AS ADJACENT
WORK, UNLESS NOTED OTHERWISE.
8. PROVIDE AND INSTALL ALL NECESSARY SUPPORT, BLOCKING, ANCHORING AND BRACING FOR ELECTRIC LIGHT FIXTURES, CHANDELIERS, OPERABLE PARTITIONS, TOILET PARTITIONS, MECHANICAL EQUIPMENT, PIPES, DUCTWORK, CABLE TRAYS, OTHER UTILITY APPURTENANCES, AND SIMILAR MISC. METALS NOTED OR IMPLIED IN THE CONTRACT DOCUMENTS.
9. ANY SURFACES OR AREAS NOT CLEARLY DEFINED OR INDICATED BY FINISH SCHEDULE SHALL BE OF SAME MATERIAL AND
FINISH AS SURFACES OR AREAS OF SIMILAR USE ELSEWHERE.
10. FINISHES SHOWN IN SCHEDULE TO EXTEND OVER, UNDER AND BEHIND CABINETS, COUNTERS, EQUIPMENT, FURNISHINGS, CHALK AND TACK BOARDS, RACKS, AND FIXTURES APPROXIMATELY 1"-2", WALLS BEHIND SAME TO BE FILLED AND PRIMED.
11. WALL FINISHES SHALL INCLUDE ALL PROJECTIONS, RECESSES, COLUMNS, ENCLOSURES AND BULKHEADS.
12. EXTERIOR PERIMETER OF ALL WINDOWS, DOOR FRAMES, LOUVERS OR OTHER ITEMS INSERTED IN AN EXTERIOR WALL SHALL
BE SEALED WEATHER TIGHT WHETHER INDICATED ON DRAWINGS OR NOT.
13. SEE STRUCTURAL DRAWINGS FOR LOCATIONS OF ALL VERTICAL AND HORIZONTAL MASONRY WALL REINFORCEMENT.
14. FIELD CHECK ALL ROUGH AND/OR FINISH DIMENSIONS FOR ACCURATE FITTING OF EQUIPMENT, CABINETS, COUNTERS, FIXTURES AND ACCESSORIES BEFORE FABRICATION. PROVIDE AND INSTALL ALL NECESSARY FILLERS, SCRIBE STRIPS, PANELS, BASES OR TRIM TO COMPLETE AND FINISH INSTALLATIONS.
15. CONSULT PLUMBING, ELECTRICAL AND MECHANICAL DRAWINGS FOR LOCATIONS AND DESCRIPTION OF ACCESS PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, REGISTERS, PANELS, VALVE CABINETS, DRINKING FOUNTAINS, ETC.
16. ALL SWITCHES, OUTLETS, THERMOSTATS, CLOCKS, SPEAKERS, FLAG POLE HOLDERS OR OTHER WALL MOUNTED DEVICES OR CONTROLS SHALL BE INSTALLED IN LOCATIONS WHICH ARE UNOBSTRUCTED BY CABINETS, COUNTERS, RACKS, FIXTURES, CHALK AND TACK BOARDS, FURNISHINGS OR EQUIPMENT. ITEMS INTENDED FOR WALL MOUNTING SHALL NOT BE INSTALLED ON, THROUGH OR INTO ANY OTHER EQUIPMENT UNLESS SPECIFICALLY CALLED FOR. VERIFY MOUNTING HEIGHTS WITH ADA
REQUIREMENTS.
17. PROVIDE AND INSTALL ALL NECESSARY HARDWARE, BRACKETS, BRACING, ANCHORING, INSERTS, BLOCKING, FURRING OR OTHER SUPPLEMENTARY ITEMS NEEDED FOR COMPLETE INSTALLATION OF EQUIPMENT, CABINETS, FIXTURES, ACCESSORIES, CCTV, INTERCOM, PROJECTORS, ETC.
ABBREVIATIONS
VENTED RUBBER BASEVRB
STAINED CONCRETESTN CONC
RUBBER TILE OR ROLL FLOORINGRUB
SUSPENDED ACOUSTICAL
CEILING TILE
WINDOW
ATHLETIC WOOD FLOORING
WATERPROOFING
WAINSCOT
WIRE MESH
WALL HYDRANT
WELDED WIRE FABRIC
WALL THICKNESS
WEATHERSTRIP
WASHER
WP
WSH
WSCT
WWF
WT
WSP
WDFLR
WM
WH
WIN
WATER CLOSET
WOODWD
WC
WITH
WEST
W/
W
VENEERED PLASTER (TEXTURED)
VINYL STRAIGHTVS
VPT
VENEERED PLASTER (SMOOTH)VPS
VENTILATINGVENT
VANITY
VINYL COVEVC
VAN
UNFIN UNFINISHED
UNEXCAVATEDUNEX
UNDERGROUNDUG
TWF THROUGH-WALL FLASHING
TOILET PARTITIONTP
TOP OF WALLTOW
TACKBOARD
TOILETTLT
TKBD
TEXTURES
THRESHOLDTH
TEX
TEMPORARY
TEMPERATURE or TEMPEREDTEMP
TEMPY
TOILET ACCESSORIESTA
SHEET VINYL
SHEET VINYL COVE
SEAMLESS VINYL COVE BASE
SANITARY WASTE LEADER
SOUTHWESTSW
SWL
SVCB
SVC
SV
STAINED
STAGGERED
STAINED BLOCK
SOUND TRANSMISSION CLASSSTC
STBLK
STAG
ST
SPECIAL FINISHSPF
SEALANT
SEALER
SOUND
SPACES
SPECIAL COATINGSPCT
SP
SND
SLR
SLNT
SCORED JOINTSJ
SOUND BATT INSULATIONSI
SHOWERSHWR
SHELF / SHELVESSH
SLIDING GLASS DOORSGD
SERVICE SINKSERV SK
SOUTHEAST
SECTIONSECT
SE
SB SPLASH BLOCK
SOUND ATTENUATION BLANKETSAB
RF
RT RIGHT
ROUNDRND
RMV REMOVED
RESILIENT FLOOR
RIGHT HAND
RIGID INSULATION
RH
RI
REV REVISION / REVISED
REM REMOVABLE
RECTANGULARRECT
REC RECESSED
REFLECTED CEILING PLANRCP
RBR RUBBER
RADIUSRAD., R
PKT POCKET
QUANTITYQTY
PAINTED
PAVEMENT
PTD
PVMT
POLISH
PORCELAIN TILE
PRIME PAINTPP
POR
POL
PANELPNL
PLUMBINGPLBG
PLAM PLASTIC LAMINATE
PARTICLE BOARD
PRECAST CONCRETE
PEGBOARDPGBD
PCC
PBD
P PAINT
OPT
OVHG OVERHANG
OPTIONAL
OH
OUTSIDE FACE
OVERHEAD
OF
OUT TO OUT
OVERALLOA
O/O
NW
NE NORTHEAST
NORTHWEST
NRC NOISE REDUCTION COEFFICIENT
NON-RATED
NO APPLIED FINISHNAP
N/R
MICROWAVEMW
MUL MULLION
MORTARMTR
MEETINGMTG
METAL STUDMS
MAPLEMP
MILLWORKMLWK
MLDG MOLDING
METAL LINEAR CEILINGMLC
MOUNTING HEIGHTMH
MANUFACTURINGMFG
MEMBRANEMEMB
MEDICINE CABINETMC
MARCITE
MACHINE
MAR
MACH
MARBLEM
LW LAMINATED WOOD
LVR LOUVER
LTG LIGHTING
LSC NFPA LIFE SAFETY CODE
LAMINATED PLASTICLP
LONGITUDINAL
LEFT HAND
LONG
LH
POUNDSLBS or (#)
LATITUDINALLAT
L LEFT
KNOCKDOWNKD
JOISTJST
INSIDE DIAMETER
INSULATED GLASS
INCHES
INFORMATION
IMPACT RESISTANTIR
INFO
IN
IG
ID
HOT WATER HEATERHWH
HP HORSE POWER
HNDRL HANDRAIL
HDWD HARDWOOD
HEADERHDR
HEADHD
GT GROUT
GRILLEGRL
GR GRADE
GC GENERAL CONTRACTOR
GRAB BARGB
FIRE EXTINGUISHER CABINET
FIXTUREFXT
FURRINGFUR'G
FOOD SERVICE EQUIPMENT
FULL SIZE
FSE
FS
FIREPROOFFPRF
FACE OF WALL
FACE OF STUDS
FOW
FOS
FLEXIBLEFLEX
FABRIC
FURNISHED BY OWNER
FACE BRICKFBR
FBO
FAB
EXTRUDEDEXTD
ELECTRIC WATER HEATEREWH
ENTRANCE
EQUALEQ
ENT
ENCLOSUREENCL
EXISTING GRADEEG
EXTERIOR CEMENT BOARDECB
EACH FACEEAF
DW
DYR DRYER
DISHWASHER
DR DOOR
DP DAMPPROOFING
DISP DISPENSER
DF DRINKING FOUNTAIN
DECIBELDB
CTSK COUNTER SINK
CENTERCTR
CASEWORKCSWK
COPINGCPG
CORRIDORCORR
CONFERENCECONF
CLEANOUTCO
CLASSROOMCLRM
CAST IN PLACECIP
CHALKBOARDCHBD
CORNER GUARDCG
BETWEENBTW
BS BOTH SIDES
BRK BRICK
BOT
BP BYPASS
BOTTOM
BONDBND
BUILDING LINEBL
BKS BACKSPLASH
BIFOLDBF
ACOUS
ADJUST
AHU
ALT
AP
ACOUSTICAL
ADJUSTABLE
AIR HANDLING UNIT
ALTERNATE
ACCESS PANEL
AWC
ASSY ASSEMBLY
ACOUSTICAL WALL COVERING
ASPHALTASPH
AFF ABOVE FINISHED FLOOR
SQ
STOR
STL
STD
SST, SS
SQ IN
SF
TV
TEL, TELE
TECH
SYS
SACT
SUSP
STRUCT
HIGH
HOLLOW METAL
HIGH POINT
HOLLOW CORE
HEIGHT
HARDWARE
INVERT
INTERIOR
INSULATION
HOUR
HORIZONTAL
HOSE BIBB
HEATING/VENTILATION/AIR COND
TELEVISION
TELEPHONE
TECHNICAL
SYSTEM
SUSPENDED
STRUCTURAL
STORAGE
STEEL
STANDARD
STAINLESS STEEL
SQUARE INCHES
SQUARE FEET
SQUARE
TOP
T.O.
TOF
TOC
T & B
TC
T/
T
THRU
UR
UON
UL
UC
TYP
TOS
LABORATORY
KNOCK OUT
JANITOR CLOSET
JANITOR
JOINT
LOW POINT
LONG LEG VERTICAL
LONG
LIGHT WEIGHT
LAVATORY
LAMINATE
LONG LEG HORIZONTAL
LIGHT WEIGHT CONCRETE
V
VT
VGWB
VCT
VEST
VERT
VTR
VB
W/O
VWC
MEZZANINE
METAL
MECHANICAL
MAXIMUM
MATERIAL
MASONRY OPENING
MANUFACTURER
MAINTENANCE
NORTH
NOMINAL
MOUNTED
MISCELLANEOUS
MIRROR
MINIMUM
MILITARY
MOISTURE RESISTANT
METAL BUILDING MANUFACTURER
TOP OF
VINYL WALL COVERING
VINYL TILE
VINYL COVERED GYPSUM WALLBOARD
VINYL COMPOSITION TILE
VESTIBULE
VERTICAL
VENT THRU ROOF
VAPOR BARRIER
VINYL
URINAL
UNDERWRITERS LABORATORY
UNLESS OTHERWISE NOTED
UNDERCUT
TYPICAL
TOP OF STEEL
TOP OF FOOTING
TOP OF CONCRETE
TOP AND BOTTOM
TOP CHORD
TREAD
THROUGH
WITHOUT
THICKTHK
HGT
HVAC
HDW
H
HC
HM
HP
HORIZ
HB
HR
INT
INSUL
INV
BEAM
BEARINGBRG
BM
JAN
JT
KO
LAB
LAV
LG
LWC
LLV
LLH
LP
LAM
BOLT
BUILDING
BRONZE
BOARD
BOTTOM OF
CARPET
CABINET
BLDG
BRZ
BLT
BD
B.O.
CAR
CAB
CENTERLINE
CEMENT
CEILING
CHANNEL
LCCL,
CEM PLAS
CEM
CLG
C
CLR
CT
C TO C
CCB
CLEARANCE, CLEAR
CERAMIC TILE
CENTER TO CENTER
CEMENT PLASTER
CONCRETE BLOCK
MFR
MATL
MO
MECH
MEZZ
MTL
MAX
MIN
MTD
MISC
MR
MBM
N
NOM
MIL
COMBINATION
COLUMN
COURSE
CONNECTION
CONCRETE
COMB
COL
CRC
CRS
CONST
CONN
CMU
CONC
CONTRACTOR
CONTINUOUS
DETAIL
DEPARTMENT
COORDINATE
CFE
CONTR
CONT
CJ
DET
DEPT
COORD
CONTRACTOR FURNISHED EQUIP
CONSTRUCTION, CONTROL JOINT
CONSTRUCTION
CONCRETE MASONRY UNIT
COLD ROLLED CHANNEL
CLOSETCLOS
BLOCK (ING)BLK
MIR, M
MAINT
LT WT
JAN CLOS
OPENING
ON CENTER
OFFICE
NUMBER
NOT TO SCALE
NOT IN CONTRACT
NOT APPLICABLE
PAIR
OUTSIDE DIAMETER
OUNCE
OPPOSITE HAND
OPPOSITE
PAINTED GYPSUM WALLBOARD
PAINTED CONCRETE MASONRY UNIT
POUND
POLYVINYL CHLORIDE
PLYWOOD
PLATE
PLACES
PLASTER, PLASTIC
RISER, RADIUS
RECEPTACLE
QUARRY TILE
PROJECT
PRESSURE TREATED
PREFABRICATED
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
PARTITION
ROOM
ROOF DRAIN
RETURN AIR
REQUIREMENT
REQUIRED
REINFORCING
REFRIGERATOR
REFERENCE
SPECIFICATIONS
SOLID CORE
SIMILAR
SHEET
SEALED CONCRETE
SCHEDULE
SOUTH
ROUGH OPENING
NIC
NA
#NO,
NTS
OFF
OPNG
OC
OPP
OD
OZ
PCMU
PR
PGWB
DOOR GRILLE
DOUBLE
DIMENSION
DIAMETER
DOWN
DRAWING
DOWNSPOUT
DG
DBL
DIM
DIA,
DWG
DS
DN
DO
EAST
EACH
ELECTRIC (AL)
ENGINEER
ELEVATOR
ELEVATION
E
ELEC
EA
ENGR
ELEV
EL
EWC ELECTRIC WATER COOLER
DOOR OPENING
PLAS
PL
PLCS
LB, #
PVC
PSI
PSF
PT
PROJ
QT
R
RCPT
EXPANSION
EXISTING
EXHAUST FAN
EXHAUST
EXTERIOR
EXP
EXIST
EF
EXH
EXT
EJ, EXP JT
FINISH
FEET, FOOT
FE
FIN
FT
FED SPEC
FR
FHR
FHC
FEC
FM
FIRE RESISTANT (RATED)
FIRE HOSE RACK
FIRE HOSE CABINET
FIRE EXTINGUISHER
FEDERAL SPECIFICATIONS
FACTORY MUTUAL
EXPANSION JOINT
EQUIPMENTEQUIP, EQMT
REF
REQD
REINF
RA
RM
RD
REQT
S
SIM
SHT
SPEC
SC
RO
FOOTING
FLUORESCENT
FLOOR DRAIN
FLOOR
FURNISH
FOUNDATION
FLUOR
FTG
FLD, FD
FL
FURN
FDN
GLASS
GENERATOR
GALVANIZED
GYPSUM
GROUND
GOVERNMENT
GL
GEN
GALV STL
GALV
GYP
GND
GFE
GOVT
GAGEGA
GOVERNMENT FURNISHED EQUIPMENT
GALVANIZED STEEL
GYPSUM WALLBOARDGWB
FLASHINGFLASH'G
S CONC
SCHED
REFR, REFRIG
PREFAB
PLWD,PLYWD
PTN, PART
OPP HAND
DIAGONALDIAG
PJ PRECAST WALL JOINT
ADA AMERICANS W/ DISABILITIES ACT
ABOVE
ACOUSTIC PANEL CEILING
AIR CONDITIONING
ARCHITECT/ENGINEER
ACCESS FLOOR
ANOD
APPROX
A/E
ARCH
ANODIZE
APPROXIMATE
ARCHITECT
AT
A/C
AL, ALUM
AB
L
ABV
APC
AF
ALUMINUM
ANCHOR BOLT
ANGLE
ALASKA AEROSPACE CORPORATIONAAC
A101
A101
1 REF
R E
F
1 REF
R E
F
0-S6AX
SECTION MARKER
EXTERIOR ELEVATION MARKER
INTERIOR ELEVATION MARKER
FLOOR ELEVATION SYMBOL
SYMBOLS LEGEND
DETAIL CALLOUT MARKER
SPOT ELEVATION SYMBOL
STRUCTURAL GRID MARKER
PARTITION TAG
DOOR NUMBER TAG
ROOM TAG
ROOM NAME
101A
ROOM NAME
101A
150 SF
SECTION NUMBER ON SHEET
SHEET NUMBER ON WHICH
SECTION IS DRAWN
SECTION NUMBER ON SHEET
SHEET NUMBER ON WHICH
SECTION IS DRAWN
SECTION NUMBER ON SHEET
SHEET NUMBER ON WHICH
SECTION IS DRAWN
GLASS TYPE TAG
SECTION NUMBER ON SHEET
SHEET NUMBER ON WHICH
DETAIL IS DRAWN
A101
SIM
OVD
A101
SIM REVISION CLOUDS
FIRE RATED PARTITION
REVISION NUMBER DELTA
CLOUDED REVISION
OPENING
EARTH
TYPICAL METAL STUD PARTITION
CONCRETE
METAL-LARGE SCALE
WOOD-ROUGH
INSULATION (LOOSE OR BATT)
TYPICAL MASONRY WALL
RIGID INSULATION
2 HOUR SEPARATION ASSEMBLY
OR FIRE PARTITION
1 HOUR SEPARATION ASSEMBLY
OR FIRE PARTITION
L05
LOUVER TAG
CURTAIN WALL / WINDOW WALL SYSTEM TAG
KEYNOTE TAGS
NEW
CONSTRUCTION
EXISTING
G2
DRAWING TITLE
DRAWING NUMBER
DRAWING SCALE
DRAWING TITLE
FLOOR PLAN
1 1/8" = 1'-0"
A
A
1t
1/ 4"
M A
X
MAXIMUM VERTICAL
LEVEL CHANGE
WALKING SURFACE
A117.1 §303.2
MAXIMUM BEVELED
LEVEL CHANGE
IN WALKING SURFACE
A117.1 §303.3
1/ 4"
M A
X
1/ 2'
M A
X
1/ 4"
M A
X
1/ 4"
M A
X
1/ 2'
M A
X
4' - 0"
2'
CLEAR FLOOR OR
GROUND SPACE
A117.1 §305.3
2' - 7"
M A
X 2'
4'
2'
M A
X 1'
"4' - 0"
3' - 0"
M O
R E
T H
A N
M O
R E
T H
A N
5' - 0"
MANEURVERING CLEARANCES IN
AN ALCOVE FORWARD APPROACH
A117.1 §305.5-305.7
MANEUVERING CLEARANCES IN
AN ALCOVE PARALLEL APPROACH
A117.1 §305.5-305.7
SHALLOW ALCOVES
FORWARD APPROACH
A117.1 §305.7.1
DEEP ALCOVES
PARALLEL APPROACH
A117.1 §305.7.2
4' - 0"
2'
2' - 7"
M A
X 2'
4'
2'
M A
X 1'
"4' - 0"
3' - 0"
M O
R E
T H
A N
M O
R E
T H
A N
5' - 0"
48" MIN CLEAR 48" MIN CLEAR 48" MIN CLEAR48" MIN CLEAR 48" MIN CLEAR 48" MIN CLEAR
PULL SIDE
PUSH
SIDE48
M
IN
M
IN
PULL SIDE
Y
PUSH
SIDE
MIN.
22"
' M
IN
IF
D O
O R
M
IN
H A
S B
O T
H A
C
LO
S
E R
A
L A
T C
H
NOTE: X = 36" MIN.
IF Y = 60"
X = 42" MIN.
IF Y = 54"
PULL SIDE
NOTE: Y = 54" MIN
IF DOOR HAS
CLOSER
NOTE: X - 48" MIN
IF DOOR HAS
CLOSERPUSH
SIDE
LATCH APPROACH
24"
24"
Y
8"
M
IN
X
2" M
IN
HINGE APPROACH
MINIMUM DOOR WIDTH
CLEAR
32" MIN.
FRONT APPROACH
12" MIN
36" MIN.
32" MIN.
' M
IN
CLEAR WIDTH OF AN
ACCESSIBLE ROUTE
A117.1 §403.5
BOTTOM OF
ANY OBSTRUCTION
G R
E A
T E
R
O
R
C
LE
A R
4" MAX
LIMITS OF PROTRUDING OBJECTS
A117.1 §307.2
36" MIN.
32" MIN.
' M
IN
G R
E A
T E
R
O
R
C
LE
A R
4" MAX
CIRCULAR TURNING SPACE
A117.1 §304.3.1
MIN.
1' - 0"
MIN.
3' - 0"
MIN.
1' - 0"
M
IN
M
IN
60" MIN.
M
IN
M
IN
36" MIN. 36" MIN.X = 48" MIN.
T-SHAPED TURNING SPACE
A117.1 §304.3.2
CLEAR WIDTH AT TURN
A117.1 §403.5.2
Y
8"
M
IN
36" MIN. IF Y = 60" MIN.
42" MIN.
36" MIN. IF Y = 60" MIN.
42" MIN.
X = LESS THAN 48"
TURNS AROUND AN OBJECT
(WHEN X < 48")
67" DIA
MIN.
1' - 0"
MIN.
3' - 0"
MIN.
1' - 0"
M
IN
M
IN
60" MIN.
M
IN
M
IN
36" MIN. 36" MIN.X = 48" MIN.
Y
8" M
IN
36" MIN. IF Y = 60" MIN.
42" MIN.
36" MIN. IF Y = 60" MIN.
42" MIN.
X = LESS THAN 48"
A K
AF AL
T S
TA
E O
49 TH
S
Kenneth M Lowery No.14640
R EG IST ER ED P R O F E S S I O N A L A R CH IT
ECT
Architects Engineers, Inc.
www.brph.com Copyright © 2026
19020 33rd Ave W | Suite 500 Lynnwood | Washington | 98036 425-921-3500
Alaska Business Entity Number: 56725F
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
ISSUE FOR CONSTRUCTION
54321 6
A
B
C
D
E
U :\R ev it
P ro je ct
F ile s\
\C
_A _2
5_
C en tr al
_c ko tr lik
.r vt
5/ 8/
0:
:1
A
M
A R
E A
P
A D
D
BRPH
C. KOTRLIK
P A
C
IF
IC
S
P A
C E
P O
R T
C O
M P
L E
X
K O
D
IA
K I S
L A
N D
A
L A
S K
A
A L A
S K
A A
E R
O S
P A
C E
C O
R P
O R
A T
IO
N
C09729.001
G-002
05/08/2026
ABBREVIATIONS,
SYMBOLS,
GENERAL NOTES
KEN LOWERY
AK NO. 14640
1/4" = 1'-0"A5
CLEAR FLOOR OR
GROUND SPACE
1/4" = 1'-0"B3
DOOR IN SERIES AND GATES IN SERIES
1/4" = 1'-0"A4
TURNING SPACE
1/4" = 1'-0"A3
MANEUVERING CLEARANCES AT MANUAL
SWINGING DOORS AND GATES
1/4" = 1'-0"B4
MINIMUM CLEAR PASSAGE AND
PROTRUDING OBJECTS
1 1/2" = 1'-0"B5
CHANGED IN LEVELS
0 2' 4' 8' 12'
1/4" = 1'-0"
0 1/2' 1' 1 1/2' 2'
1 1/2" = 1'-0"
SECTION 07 92 00 - JOINT SEALANTS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Silicone joint sealants.
2. Latex joint sealants.
3. Acoustical joint sealants.
1.2 ACTION SUBMITTALS
A. Product Data: For each joint-sealant product indicated.
B. Samples for Initial Selection: Manufacturer's standard color charts consisting of strips of cured sealants showing the full range of colors available for each product exposed to view.
C. Joint-Sealant Schedule: Include the following information:
1. Joint-sealant application, joint location, and designation.
2. Joint-sealant manufacturer and product name.
3. Joint-sealant formulation.
4. Joint-sealant color.
1.3 INFORMATIONAL SUBMITTALS
A. Product Certificates: For each kind of joint sealant and accessory, from manufacturer.
1.4 CLOSEOUT SUBMITTALS
A. Manufacturers' special warranties.
B. Installer's special warranties.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Authorized representative who is trained and approved by manufacturer.
B. Testing Agency Qualifications: Qualified in accordance with ASTM C1021 to conduct the testing indicated.
1.6 FIELD CONDITIONS
A. Do not proceed with installation of joint sealants under the following conditions:
1. When ambient and substrate temperature conditions are outside limits permitted by joint-sealant manufacturer
2. When joint substrates are wet.
3. Where joint widths are less than those allowed by joint-sealant manufacturer for applications indicated.
4. Where contaminants capable of interfering with adhesion have not yet been removed from joint substrates.
1.7 WARRANTY
A. Special Installer's Warranty: Installer agrees to repair or replace joint sealants that do not comply with performance and other requirements specified in this Section within specified warranty period.
1. Warranty Period: Two years from date of Substantial Completion.
B. Special Manufacturer's Warranty: Manufacturer agrees to furnish joint sealants to repair or replace those joint sealants that do not comply with performance and other requirements specified in this Section within specified warranty period.
1. Warranty Period: Five years from date of Substantial Completion.
C. Special warranties specified in this article exclude deterioration or failure of joint sealants from the following:
1. Movement of the structure caused by stresses on the sealant exceeding sealant manufacturer's written specifications for sealant elongation and compression.
2. Disintegration of joint substrates from causes exceeding design specifications.
3. Mechanical damage caused by individuals, tools, or other outside agents.
4. Changes in sealant appearance caused by accumulation of dirt or other atmospheric contaminants.
PART 2 - PRODUCTS
2.1 SOURCE LIMITATIONS
A. Obtain joint sealants from single manufacturer for each sealant type.
2.2 JOINT SEALANTS, GENERAL
A. Compatibility: Provide joint sealants, backings, and other related materials that are compatible with one another and with joint substrates under conditions of service and application, as demonstrated by joint-sealant manufacturer, based on testing and field experience.
B. Stain-Test-Response Characteristics: Where sealants are specified to be non-staining to porous substrates, provide products that have undergone testing according to ASTM C 1248 and have not stained porous joint substrates indicated for Project.
C. Colors of Exposed Joint Sealants: As selected by Architect from manufacturer’s full range.
2.3 SILICONE JOINT SEALANTS
A. Silicone, S, NS, 100/50, NT: Single-component, nonsag, plus 100 percent and minus 50 percent movement capability, nontraffic-use, neutral-curing silicone joint sealant; ASTM C920, Type S, Grade NS, Class 100/50, Use NT.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Adfast.
b. GE Construction Sealants; Momentive Performance Materials Inc.
c. Sika Corporation - Building Components.
2.4 LATEX JOINT SEALANTS
A. Acrylic Latex: Acrylic latex or siliconized acrylic latex, ASTM C834, Type OP, Grade NF.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Adfast.
b. Everkem Diversified Products, Inc.
c. Franklin International.
d. PPG Paints; PPG Industries, Inc.
e. Pecora Corporation.
f. Sherwin-Williams Company (The).
g. Tremco Incorporated.
2.5 JOINT-SEALANT BACKING
A. Sealant Backing Material, General: Nonstaining; compatible with joint substrates, sealants, primers, and other joint fillers; and approved for applications indicated by sealant manufacturer based on field experience and laboratory testing.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Adfast.
b. Alcot Plastics Ltd.
c. Construction Foam Products; a division of Nomaco, Inc.
d. Master Builders Solutions; brand of MBCC Group.
B. Cylindrical Sealant Backings: ASTM C1330, Type C (closed-cell material with a surface skin), Type O (open-cell material), Type B (bicellular material with a surface skin), or any of the preceding types, as approved in writing by joint-sealant manufacturer for joint application indicated, and of size and density to control sealant depth and otherwise contribute to producing optimum sealant performance.
C. Bond-Breaker Tape: Polyethylene tape or other plastic tape recommended by sealant manufacturer for preventing sealant from adhering to rigid, inflexible joint-filler materials or joint surfaces at back of joint. Provide self-adhesive tape where applicable.
2.6 MISCELLANEOUS MATERIALS
A. Primer: Material recommended by joint-sealant manufacturer where required for adhesion of sealant to joint substrates indicated, as determined from preconstruction joint-sealant-substrate tests and field tests.
B. Cleaners for Nonporous Surfaces: Chemical cleaners acceptable to manufacturers of sealants and sealant backing materials, free of oily residues or other substances capable of staining or harming joint substrates and adjacent nonporous surfaces in any way, and formulated to promote optimum adhesion of sealants to joint substrates.
C. Masking Tape: Non-staining, nonabsorbent material compatible with joint sealants and surfaces adjacent to joints.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine joints indicated to receive joint sealants, with Installer present, for compliance with requirements for joint configuration, installation tolerances, and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Surface Cleaning of Joints: Clean out joints immediately before installing joint sealants to comply with joint-sealant manufacturer's written instructions and the following requirements:
1. Remove all foreign material from joint substrates that could interfere with adhesion of joint sealant, including dust, paints (except for permanent, protective coatings tested and approved for sealant adhesion and compatibility by sealant manufacturer), old joint sealants, oil, grease, waterproofing, water repellents, water, surface dirt, and frost.
2. Clean porous joint substrate surfaces by brushing, grinding, mechanical abrading, or a combination of these methods to produce a clean, sound substrate capable of developing optimum bond with joint sealants. Remove loose particles remaining after cleaning operations above by vacuuming or blowing out joints with oil-free compressed air. Porous joint substrates include the following:
a. Concrete.
3. Remove laitance and form-release agents from concrete.
4. Clean nonporous joint substrate surfaces with chemical cleaners or other means that do not stain, harm substrates, or leave residues capable of interfering with adhesion of joint sealants. Nonporous joint substrates include the following:
B. Joint Priming: Prime joint substrates where recommended by joint-sealant manufacturer or as indicated by preconstruction joint-sealant-substrate tests or prior experience. Apply primer to comply with joint-sealant manufacturer's written instructions. Confine primers to areas of joint-sealant bond; do not allow spillage or migration onto adjoining surfaces.
C. Masking Tape: Use masking tape where required to prevent contact of sealant or primer with adjoining surfaces that otherwise would be permanently stained or damaged by such contact or by cleaning methods required to remove sealant smears. Remove tape immediately after tooling without disturbing joint seal.
3.3 INSTALLATION OF JOINT SEALANTS
A. General: Comply with joint-sealant manufacturer's written installation instructions for products and applications indicated, unless more stringent requirements apply.
B. Sealant Installation Standard: Comply with recommendations in ASTM C1193 for use of joint sealants as applicable to materials, applications, and conditions indicated.
C. Install sealant backings of type indicated to support sealants during application and at position required to produce cross-sectional shapes and depths of installed sealants relative to joint widths that allow optimum sealant movement capability.
1. Do not leave gaps between ends of sealant backings.
2. Do not stretch, twist, puncture, or tear sealant backings.
3. Remove absorbent sealant backings that have become wet before sealant application, and replace them with dry materials.
D. Install bond-breaker tape behind sealants where sealant backings are not used between sealants and backs of joints.
E. Install sealants using proven techniques that comply with the following and at the same time backings are installed:
1. Place sealants so they directly contact and fully wet joint substrates.
2. Completely fill recesses in each joint configuration.
3. Produce uniform, cross-sectional shapes and depths relative to joint widths that allow optimum sealant movement capability.
F. Tooling of Nonsag Sealants: Immediately after sealant application and before skinning or curing begins, tool sealants in accordance with requirements specified in subparagraphs below to form smooth, uniform beads of configuration indicated; to eliminate air pockets; and to ensure contact and adhesion of sealant with sides of joint.
1. Remove excess sealant from surfaces adjacent to joints.
2. Use tooling agents that are approved in writing by sealant manufacturer and that do not discolor sealants or adjacent surfaces.
3. Provide concave joint profile in accordance with Figure 8A in ASTM C1193 unless otherwise indicated.
4. Provide flush joint profile in accordance with Figure 8B in ASTM C1193.
5. Provide recessed joint configuration of recess depth and in accordance with Figure 8C in
ASTM C1193.
a. Use masking tape to protect surfaces adjacent to recessed tooled joints.
3.4 CLEANING
A. Clean off excess sealant or sealant smears adjacent to joints as the Work progresses by methods and with cleaning materials approved in writing by manufacturers of joint sealants and of products in which joints occur.
3.5 PROTECTION
A. Protect joint sealants during and after curing period from contact with contaminating substances and from damage resulting from construction operations or other causes so sealants are without deterioration or damage at time of Substantial Completion. If, despite such protection, damage or deterioration occurs, cut out, remove, and repair damaged or deteriorated joint sealants immediately so installations with repaired areas are indistinguishable from original work.
END OF SECTION 07 92 00
SECTION 08 11 13 - HOLLOW METAL DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Standard hollow metal doors and frames.
1.2 DEFINITIONS
A. Minimum Thickness: Minimum thickness of base metal without coatings in accordance with NAAMM- HMMA 803 or ANSI/SDI A250.8.
1.3 ACTION SUBMITTALS
A. Product Data:
1. Standard hollow metal doors and frames.
B. Product Data Submittals: For each product.
1. Include construction details, material descriptions, core descriptions, and finishes.
C. Shop Drawings: Include the following:
1. Elevations of each door type.
2. Details of doors, including vertical- and horizontal-edge details and metal thicknesses.
3. Frame details for each frame type, including dimensioned profiles and metal thicknesses.
4. Locations of reinforcement and preparations for hardware.
5. Details of each different wall opening condition.
6. Details of electrical raceway and preparation for electrified hardware, access control systems, and security systems.
7. Details of anchorages, joints, field splices, and connections.
8. Details of accessories.
9. Details of moldings and removable stops.
D. Product Schedule: For hollow-metal doors and frames, prepared by or under the supervision of supplier, using same reference numbers for details and openings as those on Drawings. Coordinate with final door hardware schedule.
1.4 QUALITY ASSURANCE
A. Source Limitations: Obtain hollow metal work from single source from single manufacturer.
B. Egress Door Inspector Qualifications: Inspector for field quality-control inspections of egress door assemblies is to meet the qualifications set forth in NFPA 101, Section 7.2.1.15.4 and the following:
1. Door and Hardware Institute Egress Door Assembly Inspector (FDAI) certification.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Deliver hollow-metal doors and frames palletized, packaged, or crated to provide protection during transit and Project-site storage. Do not use nonvented plastic.
1. Provide additional protection to prevent damage to factory-finished units.
B. Deliver welded frames with two removable spreader bars across bottom of frames, tack welded to jambs and mullions.
C. Store hollow metal work under cover at Project site. Place in stacks of five units maximum in a vertical position with heads up, spaced by blocking, on minimum 4-inch-high wood blocking. Do not store in a manner that traps excess humidity.
1. Provide minimum 1/4-inch space between each stacked door to permit air circulation.
1.6 PROJECT CONDITIONS
A. Field Measurements: Verify actual dimensions of openings by field measurements before fabrication.
PART 2 - PRODUCTS
2.1 HOLLOW METAL DOORS AND FRAMES
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
1. Ceco Door Products; an Assa Abloy Group company.
2. Curries Company; an Assa Abloy Group company.
3. Fleming Door Products Ltd.; an Assa Abloy Group company.
4. Steelcraft; an Ingersoll-Rand company.
5. Trudoor
6. Others as approved by Architect.
2.2 MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A1008/A1008M, Commercial Steel (CS), Type B; suitable for exposed applications.
B. Hot-Rolled Steel Sheet: ASTM A1011/A1011M, Commercial Steel (CS), Type B; free of scale, pitting, or surface defects; pickled and oiled.
C. Metallic-Coated Steel Sheet: ASTM A653/A653M, Commercial Steel (CS), Type B.
D. Inserts, Bolts, and Fasteners: Hot-dip galvanized in accordance with ASTM A153/A153M.
E. Mineral-Fiber Insulation: ASTM C665, Type I (blankets without membrane facing); consisting of fibers manufactured from slag or rock wool; with maximum flame-spread and smoke-developed indexes of 25 and 50, respectively; passing ASTM E136 for combustion characteristics.
2.3 STANDARD HOLLOW METAL DOORS
A. General: Provide doors of design indicated, not less than thickness indicated; fabricated with smooth surfaces, without visible joints or seams on exposed faces unless otherwise indicated. Comply with
ANSI/SDI A250.8.
1. Design: Flush panel.
2. Core Construction: Manufacturer's standard kraft-paper honeycomb, polystyrene, polyurethane, polyisocyanurate, mineral-board, or vertical steel-stiffener core.
3. Vertical Edges for Single-Acting Doors: Manufacturer's standard.
a. Beveled Edge: 1/8 inch in 2 inches.
4. Vertical Edges for Double-Acting Doors: Round vertical edges with 2-1/8-inch radius.
5. Top and Bottom Edges: Closed with flush or inverted 0.042-inch-thick, end closures or channels of same material as face sheets.
6. Tolerances: Comply with SDI 117, "Manufacturing Tolerances for Standard Steel Doors and Frames."
B. Exterior Doors: Face sheets fabricated from cold-rolled steel sheet. Provide doors complying with requirements indicated below by referencing ANSI/SDI A250.8 for level and model and ANSI/SDI A250.4 for physical performance level:
1. Level 1 and Physical Performance Level C (Heavy Duty), Model 1 (Full Flush).
a. Width: 1-3/4 inches.
b. Face: Metallic-coated steel sheet, minimum thickness of 0.032 inch.
C. Fabricate concealed stiffeners and hardware reinforcement from either cold- or hot-rolled steel sheet.
2.4 STANDARD HOLLOW METAL FRAMES
A. General: Comply with ANSI/SDI A250.8 and with details indicated for type and profile.
B. Interior Frames: Fabricated from cold-rolled steel sheet.
1. Fabricate frames with mitered or coped corners.
2. Fabricate frames as full profile welded unless otherwise indicated.
3. Frames for Borrowed Lights: Same as adjacent door frame.
4. Metallic-coated steel sheet, minimum thickness of 0.042 inch.
C. Hardware Reinforcement: Fabricate according to ANSI/SDI A250.6 with reinforcement plates from same material as frames.
2.5 FRAME ANCHORS
A. Jamb Anchors:
1. Type: Anchors of minimum size and type required by applicable door and frame standard, and suitable for performance level indicated.
2. Quantity: Minimum of three anchors per jamb, with one additional anchor for frames with no floor anchor. Provide one additional anchor for each 24 inches of frame height above 7 feet.
3. Post-installed Expansion Anchor: Minimum 3/8-inch-diameter bolts with expansion shields or inserts, with manufacturer's standard pipe spacer.
B. Floor Anchors: Provide floor anchors for each jamb and mullion that extends to floor.
C. Floor Anchors for Concrete Slabs with Underlayment: Adjustable-type anchors with extension clips, allowing not less than 2-inch height adjustment. Terminate bottom of frames at top of underlayment.
D. Material: ASTM A879/A879M, Commercial Steel (CS), 04Z coating designation; mill phosphatized.
1. For anchors built into exterior walls, steel sheet complying with ASTM A1008/A1008M or ASTM A1011/A1011M; hot-dip galvanized in accordance with ASTM A153/A153M, Class B.
2.6 FABRICATION
A. Fabricate hollow metal work to be rigid and free of defects, warp, or buckle. Accurately form metal to required sizes and profiles, with minimum radius for thickness of metal. Where practical, fit and assemble units in manufacturer's plant. To ensure proper assembly at Project site, clearly identify work that cannot be permanently factory assembled before shipment.
B. Tolerances: Fabricate hollow metal work to tolerances indicated in SDI 117.
C. Hollow-Metal Frames: Fabricate in one piece except where handling and shipping limitations require multiple sections. Where frames are fabricated in sections, provide alignment plates or angles at each joint, fabricated of metal of same or greater thickness as frames.
1. Provide countersunk, flat- or oval-head exposed screws and bolts for exposed fasteners unless otherwise indicated.
2. Door Silencers: Except on weather-stripped frames, drill stops to receive door silencers as follows. Keep holes clear during construction.
a. Single-Door Frames: Drill stop in strike jamb to receive three door silencers.
b. Double-Door Frames: Drill stop in head jamb to receive two door silencers.
E. Hardware Preparation: Factory prepare hollow-metal doors and frames to receive templated mortised hardware, and electrical wiring; include cutouts, reinforcement, mortising, drilling, and tapping in accordance with ANSI/SDI A250.6, the Door Hardware Schedule on Drawings, and templates.
1. Reinforce doors and frames to receive nontemplated, mortised, and surface-mounted door hardware.
2. Comply with BHMA A156.115 for preparing hollow-metal doors and frames for hardware.
2.8 STEEL FINISHES
A. Prime Finish: Clean, pretreat, and apply manufacturer's standard primer.
1. Shop Primer: Manufacturer's standard, fast-curing, lead- and chromate-free primer complying with ANSI/SDI A250.10; recommended by primer manufacturer for substrate; compatible with substrate and field-applied coatings despite prolonged exposure.
B. Factory Finish: Clean, pretreat, and apply manufacturer's standard two-coat, baked-on finish consisting of prime coat and thermosetting topcoat, complying with ANSI/SDI A250.3.
1. Color and Gloss: As selected by Architect from manufacturer's full range.
PART 3 - EXECUTION
3.1 PREPARATION
A. Remove welded-in shipping spreaders installed at factory. Restore exposed finish by grinding, filling, and dressing, as required to make repaired area smooth, flush, and invisible on exposed faces. Touch up factory-applied finishes where spreaders are removed.
B. Drill and tap doors and frames to receive non-templated, mortised, and surface-mounted door hardware.
3.2 INSTALLATION
A. Install hollow-metal doors and frames plumb, rigid, properly aligned, and securely fastened in place.
Comply with approved Shop Drawings and with manufacturer's written instructions.
B. Hollow-Metal Frames: Comply with ANSI/SDI A250.11.
1. Set frames accurately in position; plumbed, aligned, and braced securely until permanent anchors are set. After wall construction is complete, remove temporary braces without damage to completed Work.
a. Where frames are fabricated in sections, field splice at approved locations by welding face joint continuously; grind, fill, dress, and make splice smooth, flush, and invisible on exposed faces. Touch-up finishes.
b. Install frames with removable stops located on secure side of opening.
2. Floor Anchors: Secure with post-installed expansion anchors.
a. Floor anchors may be set with power-actuated fasteners instead of postinstalled expansion anchors if so indicated and approved on Shop Drawings.
3. Installation Tolerances: Adjust hollow-metal frames to the following tolerances:
a. Squareness: Plus or minus 1/16 inch, measured at door rabbet on a line 90 degrees from jamb perpendicular to frame head.
b. Alignment: Plus or minus 1/16 inch, measured at jambs on a horizontal line parallel to plane of wall.
c. Twist: Plus or minus 1/16 inch, measured at opposite face corners of jambs on parallel lines, and perpendicular to plane of wall.
d. Plumbness: Plus or minus 1/16 inch, measured at jambs at floor.
C. Hollow-Metal Doors: Fit and adjust hollow-metal doors accurately in frames, within clearances specified below.
1. Non-Fire-Rated Steel Doors: Comply with ANSI/SDI A250.8.
SECTION 08 11 13 - HOLLOW METAL DOORS AND FRAMES (cont.)
3.3 FIELD QUALITY CONTROL
A. Inspection Agency: Owner will engage a qualified inspector to perform inspections and to furnish reports to Architect.
B. Inspections:
1. Egress Door Inspections: Inspect each door equipped with panic hardware, each door equipped with fire exit hardware, each door located in an exit enclosure, each electrically controlled egress door, and each door equipped with special locking arrangements in accordance with NFPA 101, Section 7.2.1.15.
C. Repair or remove and replace installations where inspections indicate that they do not comply with specified requirements.
D. Reinspect repaired or replaced installations to determine if replaced or repaired door assembly installations comply with specified requirements.
3.4 REPAIR
A. Prime-Coat Touchup: Immediately after erection, sand smooth rusted or damaged areas of prime coat and apply touchup of compatible air-drying, rust-inhibitive primer.
B. Metallic-Coated Surface Touchup: Clean abraded areas and repair with galvanizing repair paint in accordance with manufacturer's written instructions.
C. Factory-Finish Touchup: Clean abraded areas and repair with same material used for factory finish in accordance with manufacturer's written instructions.
D. Touchup Painting: Cleaning and touchup painting of abraded areas of paint are specified in painting Sections.
END OF SECTION 08 11 13
SECTION 08 33 23 - OVERHEAD COILING DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Insulated service doors.
B. Related Requirements:
1. Section 13 34 19 “Metal Building Systems”
1.2 ACTION SUBMITTALS
A. Product Data: For each type and size of overhead coiling door and accessory.
B. Shop Drawings: For each installation and for special components not dimensioned or detailed in manufacturer's product data.
1. Include points of attachment and their corresponding static and dynamic loads imposed on structure.
2. Include diagrams for power, signal, and control wiring.
C. Samples: For each exposed product and for each color and texture specified.
1.3 INFORMATIONAL SUBMITTALS
A. Sample warranty.
1.4 CLOSEOUT SUBMITTALS
A. Special warranty.
B. Maintenance data.
C. Record Documents: List of door numbers and applicable room name and number to which door accesses.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer for both installation and maintenance of units required for this Project.
1.6 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of doors that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Two years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS, GENERAL
A. Source Limitations: Obtain overhead coiling doors from single source from single manufacturer.
1. Equal to Overhead Door Company, 625 Series Insulated.
2. Obtain operators and controls from overhead coiling door manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Accessibility Standard: Comply with applicable provisions in the USDOJ's "2010 ADA Standards for Accessible Design" and ICC A117.1.
B. Structural Performance, Exterior Doors: Capable of withstanding the following design wind loads:
Second option in "Design Wind Load" Subparagraph below is minimum design pressure advertised by manufacturers.
1. Design Wind Load: As indicated on Drawings.
2. Testing: According to ASTM E330/E330M .
C. Windborne-Debris Impact Resistance: Provide impact-protective overhead coiling doors that pass ASTM E1886 missile-impact and cyclic-pressure tests according to ASTM E1996 for Wind Zone 3 for basic protection.
1. Large-Missile Test: For overhead coiling doors located within 30 ft. (9.1 m) D. Seismic Performance: Overhead coiling doors withstand the effects of earthquake motions determined according to ASCE/SEI 7.
2.3 DOOR ASSEMBLY - OHCD
A. Insulated Service Door: Overhead coiling door formed with curtain of interlocking metal slats.
B. Operation Cycles: Door components and operators capable of operating for not less than 50,000.
C. Insulated Door Curtain R-Value: R-7.7.
D. Insulated Door Assembly U-Factor: U-0.31.
E. Door Curtain Material: Galvanized steel.
F. Door Curtain Slats: Flat profile slats of 2-5/8-inch (67-mm) center-to-center height.
1. Insulated-Slat Interior Facing: Metal.
G. Bottom Bar: Two angles, each not less than 1-1/2 by 1-1/2 by 1/8 inch (38 by 38 by 3 mm) thick;
fabricated from hot-dip galvanized steel and finished to match door.
H. Curtain Jamb Guides: Galvanized steel with exposed finish matching curtain slats.
I. Hood: Match curtain material and finish.
1. Mounting: Between Pre-engineered metal building jambs or as indicated on the drawings.
J. Locking Devices: Equip door with slide bolt for padlock, and chain lock keeper.
K. Manual Door Operator: Chain-hoist operator.
L. Electric Door Operator:
1. Equal to Overhead Door Company RHX Series.
2. Usage Classification: Standard duty, up to 25 cycles per hour and up to 90 cycles per day.
3. Safety: Listed according to UL 325 by a qualified testing agency for commercial or industrial use.
4. Motor Exposure: Interior.
5. Motor Electrical Characteristics:
a. Horsepower: 1 hp.
b. Voltage: As indicated on Electrical Drawings.
6. Emergency Manual Operation: Chain type.
7. Obstruction-Detection Device: Automatic photoelectric sensor.
8. Control Station(s): Interior mounted.
M. Curtain Accessories: Equip door with weatherseals, astragal, automatic-closing device.
N. Door Finish:
1. Aluminum Finish: Anodized color as selected by Architect from full range of industry colors and color densities.
2. Baked-Enamel or Powder-Coated Finish: Color as selected by Architect from manufacturer's full range.
3. Factory Prime Finish: Manufacturer's standard color.
4. Interior Curtain-Slat Facing: Match finish of exterior curtain-slat face.
2.4 MATERIALS, GENERAL
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.5 DOOR CURTAIN MATERIALS AND CONSTRUCTION
A. Door Curtains: Fabricate overhead coiling-door curtain of interlocking metal slats, designed to withstand wind loading indicated, in a continuous length for width of door without splices.