Attachment (1).pdf
PDF 14 MB Posted
- Attached to
- Alaska Aerospace Corporation Pre-Engineered Metal Building - Vehicle Integration Building
- Solicitation number
- Not on record
- Issued by
- Ketchikan Gateway Borough, Alaska
About this file
This document comprises structural design specifications and general notes for the Pacific Spaceport Complex—Alaska (PSCA) Area 3 Pad project prepared by BRPH Architects Engineers, Inc. for Alaska Aerospace Corporation. The specifications detail comprehensive requirements for cast-in-place concrete, structural steel, reinforcing steel, adhesive and mechanical anchors, and pre-engineered metal building (PEMB) design for two Vehicle Integration Buildings (VIBs) required to support launch pad operations on Kodiak Island. The project is designed to comply with the 2021 International Building Code, ASCE 7-16, ACI 318-19, AISC 360-16, and AWS welding standards. Design criteria include extreme environmental loads: 170 mph ultimate wind speed (Vasd 132 mph), 40 PSF flat roof snow load, Seismic Design Category E with a design spectral response acceleration (Sds) of 1.9, and maximum soil bearing capacity of 2,500 PSF. The structural design incorporates concrete compressive strengths ranging from 4,000 to 5,000 psi depending on exposure class and application, with detailed specifications for reinforcement placement, welding procedures, and quality control inspections. All structural work requires review, approval, and sealed certification by a Professional Structural Engineer licensed in Alaska, with shop drawings subject to engineer review prior to fabrication commencement.
Contractor responsibilities include coordination of all trades, verification of dimensions and site conditions prior to ordering materials, arrangement of pre-construction meetings with the architect/engineer, and comprehensive quality assurance through testing and special inspections. The specifications mandate compliance with ACI 301 and ACI 302.1R-15 for concrete placement and curing, AWS D1.1/D1.1M for welding standards, and RCSC-14 for structural connections. Special inspection requirements are extensive, including continuous periodic observation of concrete placement and curing, reinforcement placement, welded and bolted connections, and post-installed anchors, with all inspections documented in daily reports submitted to the building official and engineer of record. The contractor must employ AWS-certified welders, utilize pre-approved adhesive anchors with manufacturer-provided installation training, and maintain temporary construction supports and bracing as required for structural stability during erection. All construction waste removal, punch list completion, and coordination with on-site PSCA personnel are contractor responsibilities, with the contract funding derived from a U.S. Department of Defense prime contract subject to Davis-Bacon Act wage determination, Buy American provisions, specialty metals compliance, and NIST SP 800-171 cybersecurity requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 1 Pre-Engineered Metal Building ITB.pdf | ||
| 100% Revision 1 - Civil - Signed.pdf | ||
| 100% Revision 1 - Architectural - Signed.pdf | ||
| 100p Revision 1 - Structural- Signed.pdf | ||
| AAC Pre-Engineered Metal Building ITB.pdf | ||
| Attachment.pdf.crdownload | CRDOWNLOAD file | |
| Attachment.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES:
ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
THE CONTRACTOR SHALL WORK STRUCTURAL DRAWINGS TOGETHER WITH ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND CIVIL DRAWINGS AS APPLICABLE TO LOCATE DEPRESSED SLABS, SLOPES, DRAINS, REGLETS, BOLT SETTINGS, GRADES, ETC. ANY DISCREPANCIES SHALL BE CALLED TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK. DO NOT PENETRATE STRUCTURAL ELEMENTS (BEAMS, COLUMNS, WALLS, SLABS, STEEL DECKS, ETC.)
WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONNECTIONS, EMBED PLATE AND ANCHOR BOLT LOCATIONS FROM EQUIPMENT MANUFACTURER'S APPROVED DRAWINGS AND STEEL FABRICATOR'S ANCHOR BOLT AND EMBED PLATE SETTING
PLANS, WHICH HAVE BEEN APPROVED BY THE ARCHITECT/ENGINEER.
ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH PROJECT DRAWINGS AND SPECIFICATIONS2.
3.
6.
9.
1. DESIGN IS BASED ON THE APPLICABLE CODES AND STANDARDS REFERENCED IN THE DESIGN STANDARDS.
THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND CONDITIONS PRIOR TO ORDERING ANY MATERIALS AND SHALL NOTIFY THE ARCHITECT/ENGINEER IF DIFFERENT FROM WHAT IS SHOWN ON THE DRAWINGS.
4.
THE CONTRACTOR SHALL REVIEW THESE DRAWINGS AND VISIT THE PROJECT SITE BEFORE CONSTRUCTION BEGINS TO COMPARE ALL EXISTING CONDITIONS WITH WHAT IS SHOWN ON THESE DRAWINGS. IF THERE ARE CONDITIONS WHICH ARE DIFFERENT FROM WHAT IS SHOWN, THE STRUCTURAL ENGINEER OF RECORD SHALL BE NOTIFIED.
THE CONTRACTOR SHALL ARRANGE A PRE-CONSTRUCTION MEETING WITH THE ARCHITECT/ENGINEER TO ENSURE THAT THE CONTRACTOR'S UNDERSTANDING OF THESE DRAWINGS AND PLAN FOR THE WORK IS IN ACCORDANCE WITH THE DESIGN INTENT
AND TO CLARIFY ANY QUESTIONS THAT THE CONTRACTOR MAY HAVE.
7.
8.
ALL STRUCTURES ARE DESIGNED TO BE STABLE AND SELF-SUPPORTING IN THEIR COMPLETED CONSTRUCTED STATE AT THE END OF CONSTRUCTION. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCES THAT ENSURE THE STABILITY OF STRUCTURES AND ITS COMPONENTS DURING CONSTRUCTION. THIS INCLUDES BUT IS NOT LIMITED TO THE ADDITION OF SUPPORTS, BRACING, GUYS WIRES, TIE DOWNS, SHORING AND RE-SHORING. SUCH TEMPORARY SUPPORTS SHALL BE DESIGNED BY QUALIFIED REGISTERED PROFESSIONAL ENGINEERS RETAINED BY THE CONTRACTOR, IN ACCORDANCE WITH LOCAL STATUTES AND REGULATIONS. TEMPORARY SUPPORTS SHALL REMAIN THE PROPERTY OF THE CONTRACTOR AND INFORMATION RELATED TO THEM IS NOT INCLUDED IN THE CONTRACT DOCUMENTS.
5.
12. ELEVATIONS:
FINISHED GROUND FLOOR EL = 0'-0" (TYP. U.N.O.)
FINISHED GROUND FLOOR REF EL = SEE CIVIL DWGS FOR PROJECT SPECIFIC DATUM & ELEVATION
13. SHOP DRAWING SUBMITTALS:
A. CONTRACTOR SHALL SUBMIT TO BRPH FOR REVIEW SHOP DRAWINGS FOR ALL APPLICABLE TRADES IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
B. IN ORDER TO EXPEDITE REVIEW OF SHOP DRAWINGS BY BRPH AND AVOID ANY NEED FOR RE-SUBMITTAL BY THE CONTRACTOR, SUBMITTED SHOP DRAWINGS SHALL BE COMPLETE WITH ADEQUATE AND NECESSARY INFORMATION SHOWN
TO FACILITATE THEIR REVIEW.
C. CONTRACTOR SHALL REVIEW THE SHOP DRAWINGS THOROUGHLY AND VERIFY DIMENSIONS, ELEVATIONS, QUANTITIES, ETC. BEFORE SUBMITTING TO BRPH FOR REVIEW. SHOP DRAWINGS NOT REVIEWED AND MARKED APPROVED BY THE
CONTRACTOR WILL BE REJECTED AND RETURNED.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION BETWEEN SHOP DRAWINGS AND DRAWINGS OF DIFFERENT TRADES. ANY FIELD ISSUES AS A RESULT OF THE LACK OF SUCH COORDINATION SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
THAT WHICH IS REFERENCED AS BEING ON "HOLD" SHALL BE INCLUDED IN THE BID AND WORK, HOWEVER FABRICATION AND/OR
CONSTRUCTION SHALL NOT PROCEED UNTIL THE "HOLD" REFERENCE IS REMOVED.
10.
DO NOT SCALE THE STRUCTURAL DRAWINGS TO DETERMINE DIMENSIONS OR MATERIAL QUANTITIES.11.
DESIGN CRITERIA:
3. DESIGN LIVE LOADS:
DESIGN WIND LOAD: (PER ASCE 7)4.
OCCUPANCY RISK CATEGORY III
EXPOSURE CATEGORY D
ULTIMATE WIND SPEED, Vult 170 MPH
NOMINAL WIND SPEED, Vasd 132 MPH
ENCLOSURE CLASSIFICATION ENCLOSED
INTERNAL PRESSURE COEFFICIENT ±0.18
DESIGN SEISMIC LOAD: (PER ASCE 7) 6.
RISK CATEGORY III
MAPPED ACCELERATION PARAMETERS:
SITE CLASS C
SHORT DURATION DESIGN ACCELERATION, Sds 1.9
SEISMIC DESIGN CATEGORY E
DESIGN SNOW LOAD: (PER ASCE 7)5.
GROUND SNOW LOAD 30 PSF
FLAT ROOF SNOW LOAD 40 PSF
EXPOSURE FACTOR, Ce 0.8
IMPORTANCE FACTOR, I 1.1
THERMAL FACTOR, Ct 1.2
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
SEE S-006
1. DESIGN DEAD LOADS:
SEE S-006
DESIGN COLLATERAL LOADS (NOT FOR UPLIFT RESISTANCE):
SEE S-006
2.
ROOF SLOPE FACTOR, Cs 1.0
DRIFT HEIGHT SEE S-006
SS = 2.3 S1 = 1.2
SPECTRAL RESPONSE COEFFICIENTS: SDS =1.9 SD1 =1.1
SEISMIC DRIFT:
BUILDING ELEMENTS INCLUDING EXTERIOR CLADDING; STAIRS, ELEVATORS, AND MISCELLANEOUS METALS;
MECHANICAL/ELECTRICAL/PLUMBING SYSTEM SUPPORTS; INTERIOR METAL STUD FRAMING; AND ANY OTHER ELEMENTS AS REQUIRED BY THE BUILDING CODE SHALL BE DESIGNED TO ACCOMMODATE THE PRIMARY STRUCTURE STORY DRIFTS WITH ANY APPLICABLE ELEMENT-SPECIFIC MODIFICATIONS PER CHAPTER 13 OF ASCE 7.
FOUNDATIONS AND SLABS ON GROUND:
FOUNDATIONS ARE DESIGNED FOR MAXIMUM ALLOWABLE SOIL BEARING CAPACITY OF 2,500 PSF BASED ON INFORMATION AND RECOMMENDATIONS PROVIDED IN THE GEOTECHNICAL REPORT PREPARED BY SHANNON AND WILSON, DATED 5/20/2025. THIS VALUE SHALL BE VERIFIED BY A REGISTERED GEOTECHNICAL ENGINEER (OR HIS REPRESENTATIVE) PRIOR TO PLACEMENT OF
CONCRETE FOR FOOTINGS.
1.
SUBGRADE FOR ALL NEW FOUNDATIONS SHALL BE PREPARED AND COMPACTED IN ACCORDANCE WITH RECOMMENDATIONS STATED IN THE GEOTECHNICAL REPORT MENTIONED ABOVE. REFER TO GEOTECH REPORT FOR DETAILS ON LOOSE SOIL
REMOVAL, COMPACTION RECOMMENDATIONS, AND STRUCTURAL FILL REQUIREMENTS.
2.
WHERE EARTH FORMING IS USED, EXCAVATION FOR FOUNDATIONS SHOWN ON DRAWINGS SHALL NOT BE LESS THEN INDICATED FOUNDATION SIZE, NOR LARGER THAN THE INDICATED FOUNDATION SIZE BY MORE THAN 3" IN EACH DIRECTION.
3.
THE FOLLOWING LATERAL EQUIVALENT FLUID PRESSURES WERE USED FOR RETAINING STRUCTURES BASED ON TYPICAL
VALUES FOR GRAVEL BACK-FILLED WALLS.
4.
ACTIVE CONDITION
AT-REST CONDITION
PASSIVE CONDITION
SEE ARCHITECTURAL AND CIVIL DRAWINGS FOR EXTERIOR CONCRETE SLAB LAYOUTS, CONTROL JOINTS, AND ELEVATIONS.5.
PROVIDE THICKENED EDGE IN SLAB ON GROUND AT ALL EXTERIOR BUILDING DOORS AND AT EXTERIOR SLAB EDGES.6.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS FOOTINGS AND/OR MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO A UNIFORM SURFACE. FOOTING EXCAVATIONS SHALL HAVE THE SIDES AND BOTTOMS TEMPORARILY LINED WITH 6 MIL VISQUEEN IF PLACEMENT OF CONCRETE DOES NOT OCCUR WITHIN 24 HOURS OF THE
EXCAVATION OF THE FOOTING.
7.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM THOSE DESCRIBED IN THE GEOTECHNICAL REPORT SHALL BE REPORTED TO BRPH AND THE GEOTECHNICAL ENGINEER BEFORE CONSTRUCTION IS CONTINUED.
8.
REINFORCEMENT PLACEMENT SEQUENCE FOR FOOTINGS IS NOTED ONLY FOR MAJOR REINFORCEMENT BAR LAYERS. IN SPREAD FOOTINGS AND MATS THE CONTRACTOR SHALL SEQUENCE ALL OTHER BAR PLACEMENTS AS REQUIRED TO CONFORM
TO THE CONTRACT DOCUMENTS.
11.
DURING CONSTRUCTION, THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING OF WALLS WHICH ARE ULTIMATELY SUPPORTED TOP AND BOTTOM. SUCH SHORING SHALL NOT BE REMOVED UNTIL THE SUPPORTING ELEMENTS ARE IN PLACE, THE CONCRETE IN THE WALLS AND SUPPORTING ELEMENTS HAS ATTAINED THE SPECIFIED 28 DAY COMPRESSIVE STRENGTH (f'c) AND COMPACTION OF THE BACKFILL AGAINST THE WALL HAS BEEN COMPLETED.
12.
THE FLOOR SUBGRADE SHALL BE PROPERLY COMPACTED AND PROOF-ROLLED AND SHALL BE FREE OF STANDING WATER, MUD AND FROZEN SOIL.
13.
SLABS ON GROUND CONTROL JOINTS SHALL BE MADE USING A "SOFT-CUT" CONCRETE SAW AS SOON AS THE SLAB WILL SUPPORT THE WEIGHT OF THE SAW AND OPERATOR WITHOUT DISTURBING THE FINAL FINISH. THE CRACK CONTROL JOINTS SHALL BE CUT A MAXIMUM WIDTH OF 1/8 INCH AND A MINIMUM DEPTH OF 1/4 THE SLAB THICKNESS. REFER TO THE DRAWINGS FOR INFORMATION ON CONTROL JOINTS, CONSTRUCTION JOINTS, REINFORCEMENT DETAILS AND JOINT SEALANT DETAILS.
14.
WHERE THE SLAB IS TO RECEIVE SENSITIVE ARCHITECTURAL FLOOR FINISHES, ALL JOINTS IN THE SLAB CONSTRUCTION
SHALL BE PLACED TO ALIGN WITH JOINTS IN THE FLOOR FINISHES
15.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONTACTING "DIG SAFE" AS WELL AS ALL APPROPRIATE AGENCIES AND MUNICIPALITIES TO AVOID DAMAGE TO UNDERGROUND UTILITIES PRIOR TO THE START OF ANY SITE WORK.
9.
THE CONTRACTOR SHALL PROVIDE CONTINUOUS CONTROL OF THE SURFACE AND SUBSURFACE WATER DURING CONSTRUCTION SUCH THAT FOUNDATION WORK IS DONE IN THE DRY AND ON UNDISTURBED SUBGRADE MATERIAL AS
APPLICABLE.
10.
35 PCF
55 PCF
225 PCF
CONCRETE:
1.
5.
2. CONCRETE SHALL BE NORMAL WEIGHT CONCRETE EXCEPT AS NOTED. ALL CONCRETE STRENGTHS (AT 28 DAYS) SHALL BE AS
FOLLOWS:
ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM A1064 AND SHALL BE LAPPED ONE FULL MESH PANEL PLUS 2 INCHES AT
SIDES AND ENDS AND WIRED TOGETHER.
SEE CONCRETE MIX TABLE
ALL CONCRETE WORK SHALL COMPLY WITH THE LATEST ADOPTED PROVISIONS OF ACI 318, AND ACI 301 AND THE APPLICABLE
CODES AND STANDARDS REFERENCED IN THE DESIGN STANDARDS.
PERMANENTLY EXPOSED TO EARTH) 3 INCHES
SLABS (IN CONTACT WITH EARTH) 2 INCHES
FOOTINGS AND WALLS (CAST-IN-FORMS
FOOTINGS, (CAST AGAINST &
STRUCTURAL ELEMENT CLEAR COVER
CONCRETE PROTECTION FOR REINFORCING (U.N.O):
SLABS (EXPOSED TO WEATHER) 1 1/2 INCHES
4.
PERMANENTLY EXPOSED TO EARTH) 2 INCHES
3. CALCIUM CHLORIDE SHALL NOT BE USED IN ANY FORM.
6. ALL REINFORCING STEEL SHALL BE PLACED WITHIN TOLERANCES SPECIFIED IN ACI 315.
7. REINFORCING LAP SPLICE TABLE: SEE SHEET S-004
REINFORCING FOR CONTINUOUS FOUNDATIONS SHALL BE CONTINUOUS AT CORNERS AND INTERSECTIONS. PROVIDE CORNER LAP BARS AT ALL CORNERS AND INTERSECTIONS. SEE TYPICAL CORNER REINFORCING DETAIL ON DRAWINGS.
WHERE CONTINUOUS FOUNDATIONS INTERSECT COLUMN FOUNDATIONS, REBAR FROM CONTINUOUS FOUNDATION SHALL BE CONTINUOUS THROUGH 6'-0" AND SMALLER COLUMN FOUNDATIONS, AND SHALL EITHER BE CONTINUOUS THROUGH, OR EXTEND A MINIMUM OF 2'-6" (BUT NOT LESS THAN THE STRAIGHT BAR DEVELOPMENT LENGTH) INTO COLUMN FOUNDATIONS
LARGER THAN 6'-0" WIDE.
ALL REINFORCEMENT SHALL BE BENT COLD. REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT UNLESS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. HOOKS SHALL BE ACI STANDARD HOOKS IN
ACCORDANCE WITH CHAPTER IN ACI 318. SEE TABLES ON SHEET S-004.
10.
11.
IT IS PERMITTED TO SUBSTITUTE MECHANICAL SPLICES (MEETING THE REQUIREMENTS OF SECTION 25.5.7 IN ACI 318) FOR LAP SPLICES AT NO ADDITIONAL COST. MECHANICAL SPLICES SHALL DEVELOP 125% (MIN) OF THE YIELD STRENGTH OF THE
REBAR IN TENSION OR COMPRESSION.
9.
AT THE TIME CONCRETE IS PLACED, REINFORCEMENT SHALL BE FREE FROM MUD, OIL OR OTHER NONMETALLIC COATINGS
THAT DECREASE BOND.
12.
SLABS ABOVE GROUND 3/4 INCHES
PEDESTALS (TO TIES) 2 INCHES
BEAMS (TO STIRRUPS) 1 1/2 INCHES
COLUMNS ABOVE GRADE (TO TIES) 1 1/2 INCHES
WELDABLE DEFORMED REBAR (WHERE INDICATED): FY = 60 KSI (A706, GRADE 60)
DEFORMED REBAR (TYP UNO): FY = 60 KSI (A615, GRADE 60)
CHAMFER EXPOSED CORNERS OF CONCRETE CONSTRUCTION WITH STANDARD 3/4" CHAMFERS, UNO.13.
WHERE STRIP WATER STOP IS INDICATED ON DRAWINGS, WATERSTOP-RX (RX-101) BY CETCO, SWELLSTOP (3/4" x 1" BY GREENSTREAK, SF312-SYNKOFLEX WATER STOP BY HENRY COMPANY OR APPROVED EQUAL. INSTALL PER MANUFACTURE'S
INSTRUCTIONS.
14.
FOR NON-CONTACT SPLICES, THE CENTER TO CENTER SPACING OF SPLICED BARS SHALL NOT EXCEED THE LESSER OF ONE-
FIFTH THE REQUIRED LAP SPLICE LENGTH AND 6 INCHES
8.
STRUCTURAL STEEL:
CUTS, HOLES AND THEIR REINFORCEMENT (REQUIRED BY OTHER TRADES) SHALL BE SHOWN ON THE STRUCTURAL STEEL SHOP DRAWINGS AND SHALL BE MADE IN THE SHOP. FIELD BURNING OF HOLES & CUTS IN STRUCTURAL STEEL SHALL NOT BE PERMITTED EXCEPT BY WRITTEN PERMISSION FROM THE STRUCTURAL ENGINEER OF RECORD, UNLESS NOTED
OTHERWISE ON THE DRAWINGS.
13.
12.
11.
10.
9.
ALL STRUCTURAL STEEL SHALL HAVE THE FOLLOWING ASTM SPECIFICATION AND YIELD STRENGTHS UNO:
ANGLES FY = 36 KSI (A36)
ALL OTHER SHAPES (U.N.O.) FY = 36 KSI (A36)
PLATES (U.N.O) FY = 36 KSI (A36)
ALL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE LATEST EDITION OF THE AISC STEEL CONSTRUCTION MANUAL AND THE APPLICABLE CODES AND STANDARDS REFERENCED IN THE DESIGN STANDARDS.
ALL FILLET WELDS SHALL BE AS INDICATED, BUT NOT LESS THAN AISC MINIMUM. SEE CHART BELOW:
ALL WELDING ELECTRODES SHALL BE E70XX, UNO. ALL WELDING SHALL BE PERFORMED BY AWS CERTIFIED WELDERS AND
SHALL CONFORM TO AWS D1.1/D1.1M STRUCTURAL WELDING CODE - STEEL, LATEST EDITION.
THE FABRICATOR SHALL FURNISH A STRUCTURAL SUBMITTAL WHICH SHALL BE CHECKED BY THE CONTRACTOR FOR COMPLETENESS AND CONTENT PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW. THE SUBMITTAL SHOULD INCLUDE FABRICATION AND ERECTION DRAWINGS. FABRICATION SHALL NOT COMMENCE UNTIL THIS
REVIEW IS COMPLETED.
MINIMUM SIZE FOR FILLET WELDS
MATERIAL THICKNESS OF THINNER
PART JOINED (INCHES)
TO 1/4" INCLUSIVE
MINIMUM SIZE OF
FILLET WELD (INCHES)
1/8"
OVER 1/4" TO 1/2" 3/16"
OVER 1/2" TO 3/4" 1/4"
OVER 3/4" 5/16"
AFTER ERECTION, ALL STEEL SHALL BE CLEANED OF ALL RUST, LOOSE MILL, SCALE, AND OTHER FOREIGN MATERIAL.
SCUFFS AND ABRASIONS SHALL BE FIELD TOUCHED-UP.
SIZE AND SHAPE OF STRUCTURAL STEEL SHALL BE AS SHOWN ON DRAWINGS. SUBSTITUTES MAY BE USED IF PRE-
APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD.
ALL STRUCTURAL STEEL TO BE PRIMED AND PAINTED. ALL FIELD CONNECTIONS ARE TO BE PAINTED TO MATCH
ATTACHED COMPONENTS.
1. DESIGN, FABRICATION AND ERECTION OF ALL STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE LATEST ADOPTED
EDITION OF THE AISC STEEL CONSTRUCTION MANUAL.
PROVIDE 3" MINIMUM CONCRETE COVER AROUND STEEL BELOW GRADE OR COAT WITH ASPHALTIC OR BITUMASTIC PAINT.
3.
4.
5.
ALL GROUT FOR USE UNDER BEARING PLATES, LEVELING PLATES, ETC. SHALL BE PRE-MIXED, NON-SHRINK, NON-METALLIC CONFORMING TO ASTM C827. THE GROUT STRENGTH SHALL BE THE GREATER OF 8,000 PSI OR TWICE THE STRENGTH OF THE
SUPPORTING CONCRETE.
7.
8.
ALL WELDING WORK SHALL FOLLOW INFORMATION IN AN APPROVED WELDING PROCEDURE SPECIFICATION SUPPORTED BY A PRE-QUALIFICATION RECORD, FOLLOWING REQUIREMENTS IN THE CURRENT BUILDING CODE ADOPTED VERSION OF THE AMERICAN WELDING SOCIETY (AWS) D1.1 - STRUCTURAL WELDING CODE STEEL. ALL WELDING WORK SHALL BE PERFORMED BY WELDERS CERTIFIED TO PERFORM WELDING WORK IN ACCORDANCE WITH THE GOVERNING WPS.
2.
CONCRETE MIX TABLE:
CONC
MIX
TYPE INTENDED USE
EXPOSURE
CATEGORIES
AND CLASSES
COMPRESSIVE
STRENGTH
(PSI)
TEST AVG
(DAYS)
CONC
WEIGHT
MAX
W/C
RATIO
MAX
AGGREGATE
SIZE (IN)
TOTAL AIR
CONTENT
OTHER
REQ'S
A FOOTINGS F1, S0, W1, C1 4000 28 NWC 4.5 -
B.1 LAUNCH PAD F3, S0, W1, C1 5000 56 NWC 0.4 5.5
B.2 L/M RUNWAY F3, S0, W1, C1 5000 56 NWC 0.4
1 1/2"
(NOTE 1)
5.5
C INTERIOR SLABS-ON-
GRADE
F1, S0, W0, C0 4000 28 NWC 4.5
D ALL CONC EXPOSED TO
WEATHER OR DEICERS:
WALLS, CURBS,
TRENCH WALLS AND
TRENCH SLABS
F3, S0, W1, C2 4000 28 NWC 0.45 3/4,(NOTE 1) 6
E ALL CONCRETE
OTHERWISE NOT
SPECIFIED
F3, S0, W1, C1 4000 28 NWC 0.40 1" (NOTE 1) 6 -
CONCRETE MIX TABLE ABBREVIATIONS:
• F# = FREEZING AND THAWING CLASS
• S# = SULFATE CLASS
• W# = IN CONTACT WITH WATER CLASS
• C# = CORROSION PROTECTION OF REINFORCEMENT CLASS
• LWC = LIGHTWEIGHT CONCRETE
• MSS = MAXIMUM SHRINKAGE STRAIN LIMITED
• NWC = NORMAL WEIGHT CONCRETE
CONCRETE MIX NOTES:
1. AGGREGATE SIZE NOT TO EXCEED 1/5 OF NARROWEST DIMENSION BETWEEN FORMS; 1/3 OF SLAB DEPTH; OR
3/4 OF MINIMUM CLEAR SPACING BETWEEN REINFORCEMENT
2. CONCRETE MIXES FOR SLAB ON GROUND CONSTRUCTION SHALL COMPLY WITH ACI 302.1R-15, SECTION 8.9
REGARDING AGGREGATE GRADATIONS.
[MSS]
[MSS]
0.5
0.45
1 1/2"
(NOTE 1)
1 1/2"
(NOTE 1)
1" (NOTE 1)
LIMITS ON CEMENTITIOUS MATERIALS
CEMENTITIOUS MATERIALS MAXIMUM % OF TOTAL CEMENTITIOUS
MATERIAL BY MASS
FLY ASH OR OTHER POZZOLANS CONFORMING TO ASTM C618
SLAG CEMENT CONFORMING TO ASTM C989
SILICA FUME CONFORMING TO ASTM C1240
TOTAL OF FLY ASH OR OTHER POZZOLANS AND SILICA FUME
TOTAL OF FLY ASH OR OTHER POZZOLANS, SLAG CEMENT, AND SILICA FUME
AIR ENTRAINMENT NOTES:
REQUIRED ONLY WHERE CONCRETE WILL BE EXPOSED TO ENVIRONMENTAL CONDITIONS FOR EXPOSURE CLASS F1, F2, OR F3 (PER ACI 318) AND HARD TROWEL FINISH IS NOT SPECIFIED, UNLESS OTHERWISE SPECIFIED BY ARCHITECT OR ENGINEER. THE PROPER AIR ENTRAINMENT RATE IS PER THE TABLE ABOVE, COMPLIMENTED WITH THE FOLLOWING INFORMATION WITH A TOLERANCE ON THE AS- DELIVERED CONCRETE OF ± 1.5 PERCENT. THE PROPER AIR ENTRAINMENT RATE IS DEPENDENT ON THE EXPOSURE CONDITION AND THE SIZE OF THE COARSE AGGREGATE EXPRESSED AS THE MAXIMUM NOMINAL AGGREGATE SIZE. (ACI 318-14 TABLE 19.3.2.1)
EXPOSURE CLASS F1 - WHERE THE CONCRETE IN A COLD CLIMATE WILL BY ONLY OCCASIONALLY EXPOSED TO MOISTURE PRIOR TO
FREEZING AND WHERE NO DEICING SALTS ARE USED.
A. 1-1/2" OR 1" NOMINAL MAXIMUM AGGREGATE SIZE: 4.5 PERCENT
B. 3/4" NOMINAL MAXIMUM AGGREGATE SIZE: 5 PERCENT
C. 1/2" NOMINAL MAXIMUM AGGREGATE SIZE: 5.5 PERCENT
D. 3/8" NOMINAL MAXIMUM AGGREGATE SIZE: 6 PERCENT
EXPOSURE CLASS F2 & F3 - WHERE THE CONCRETE IN A COLD CLIMATE MAY BE IN ALMOST CONTINUOUS CONTACT WITH MOISTURE
PRIOR TO FREEZING AND WHERE DEICING SALTS ARE USED.
A. 1-1/2" NOMINAL MAXIMUM AGGREGATE SIZE: 5.5 PERCENT
B. 3/4" OR 1" NOMINAL MAXIMUM AGGREGATE SIZE: 6 PERCENT
C. 1/2" NOMINAL MAXIMUM AGGREGATE SIZE: 7 PERCENT
D. 3/8" NOMINAL MAXIMUM AGGREGATE SIZE: 7.5 PERCENT
B.3 SOUTH RAT SLAB F3, S0, W1, C1 5000 56 NWC 0.4
1 1/2"
(NOTE 1)
5.5 [MSS]
ADHESIVE ANCHORS:
FOR POST-INSTALLED ADHESIVE ANCHORS INTO CRACKED CONCRETE, PRODUCTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI355.4 AND ICC-ES AC308. INSTALLATION SHALL COMPLY WITH MANUFACTURE'S LATEST
ICCC-ES APPROVAL. PRE-APPROVED ADHESIVES INCLUDE:
1.
FOR POST-INSTALLED ADHESIVE ANCHORS INTO CONCRETE MASONRY, PRODUCTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. ALL MASONRY CELLS TO RECEIVE ANCHORS SHALL BE GROUTED SOLID. INSTALLATION SHALL COMPLY WITH MANUFACTURES LATEST ICCC-ES APPROVAL. PRE-APPROVED ADHESIVES
INCLUDE:
2.
FOR POST-INSTALLED ADHESIVE ANCHORS INTO BRICK MASONRY, PRODUCTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. INSTALLATION SHALL COMPLY WITH MANUFACTURES LATEST ICCC-ES
APPROVAL. PRE-APPROVED ADHESIVES INCLUDE:
3.
SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED ABOVE MAY BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD (EOR) FOR REVIEW. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS HAVING A CODE REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE APPLICATION. SUBSTITUTION REQUESTS SHALL INCLUDE CALCULATIONS DEMONSTRATING THE SUBSTITUTION IS THE EQUIVALENT CAPABLE OF ACHIEVING PERFORMANCE
VALUES OF THE PRE-APPROVED PRODUCTS.
4.
ADHESIVE ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER'S INSTRUCTIONS. THE CONTRACTOR SHALL CONTACT THE MANUFACTURER FOR PRODUCT INSTALLATION TRAINING. MANUFACTURER'S FIELD REPRESENTATIVE SHALL PROVIDE INSTALLATION TRAINING FOR ALL PRODUCTS TO BE USED, PRIOR TO COMMENCEMENT OF WORK. ONLY TRAINED INSTALLERS SHALL PERFORM POST INSTALLED ANCHOR INSTALLATION. A RECORD OF TRAINING SHALL BE KEPT ON SITE
AND BE MADE AVAILABLE TO THE EOR AS REQUESTED.
5.
INSTALLATION OF ADHESIVE ANCHORS IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION, OR OTHER CONFIGURATION THAT RESULTS IN SUSTAINED TENSION, SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI), AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI 318. PROOF OF CURRENT CERTIFICATION SHALL BE
SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
6.
ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT THE TIME OF ANCHOR
INSTALLATION, IN ACCORDANCE WITH ACI 318.
7.
A. SIMPSON STRONG-TIE SET-3G
B. HILTI HIT-RE 500 V3 SLOW CURE A (APPROVED FOR DYNAMIC LOADING)
C. HILTI HIT-HY 200 A/R V3 FAST CURE.
D. DEWALT PURE110+
E. DEWALT AC200+ FAST CURE.
A. SIMPSON STRONG-TIE SET-XP
B. HILTI HIT-HY 270
C. DEWALT AC100+GOLD
A. SIMPSON STRONG-TIE SET-3G
B. HILTI HIT-HY 270
C. DEWALT AC100+GOLD
THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL ANCHOR PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF ANCHOR
INSTALLATION.
8.
THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL ANCHOR PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF ANCHOR
INSTALLATION.
9.
ADHESIVE ANCHOR RODS SHALL BE PRECUT THREADED ROD SUPPLIED WITH NUT AND WASHER MEETING AISI 304
STAINLESS STEEL.
10.
MECHANICAL ANCHORS:
FOR POST-INSTALLED MECHANICAL ANCHORS INTO CRACKED CONCRETE, PRODUCTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI355.2 AND ICC-ES AC193. INSTALLATION SHALL COMPLY WITH
MANUFACTURE'S LATEST ICCC-ES APPROVAL. PRE-APPROVED ANCHORS INCLUDE:
1.
FOR POST-INSTALLED MECHANICAL ANCHORS INTO CONCRETE MASONRY, PRODUCTS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01 OR ICC-ES106. ALL MASONRY CELLS TO RECEIVE ANCHORS SHALL BE GROUTED SOLID. INSTALLATION SHALL COMPLY WITH MANUFACTURES LATEST ICCC-ES APPROVAL PRE-APPROVED
ANCHORS INCLUDE:
2.
SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED ABOVE MAY BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD (EOR) FOR REVIEW. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS HAVING A CODE REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE APPLICATION. SUBSTITUTION REQUESTS SHALL INCLUDE CALCULATIONS DEMONSTRATING THE SUBSTITUTION IS THE EQUIVALENT CAPABLE OF ACHIEVING PERFORMANCE
VALUES OF THE PRE-APPROVED PRODUCTS.
3.
MECHANICAL ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER'S INSTRUCTIONS. THE CONTRACTOR SHALL CONTACT THE MANUFACTURER FOR PRODUCT INSTALLATION TRAINING. MANUFACTURER'S FIELD REPRESENTATIVE SHALL PROVIDE INSTALLATION TRAINING FOR ALL PRODUCTS TO BE USED, PRIOR TO COMMENCEMENT OF WORK. ONLY TRAINED INSTALLERS SHALL PERFORM POST INSTALLED ANCHOR INSTALLATION. A RECORD OF TRAINING SHALL BE KEPT ON SITE
AND BE MADE AVAILABLE TO THE EOR AS REQUESTED.
4.
A. SIMPSON STRONG-TIE STRONG-BOLT 2
B. SIMPSON STRONG-TIE TITEN HD
C. HILTI KWIK BOLT TZ2
D. HILTI KWIK KH-EZ
E. DEWALT-STUD+ SD2
F. DEWALT SCREW-BOLT+
A. SIMPSON STRONG-TIE STRONG-BOLT 2
B. SIMPSON STRONG-TIE TITEN HD
C. HILTI KWIK BOLT 3
D. HILTI KWIK KH-EZ
E. DEWALT POWER-STUD+ SD1
F. DEWALT SCREW-BOLT+
DESIGN STANDARDS:
1. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE BUILDING CODE AND PUBLICATIONS LISTED BELOW. IN THE CASE OF
CONFLICTING REQUIREMENTS, THE BUILDING CODE SHALL GOVERN.
2. APPLICABLE CODES AND STANDARDS:
BUILDING CODE
ACI 318-19
TMS 402/602-16
RCSC-14
AISC 341-16
AISC 360-16
AISI S100-16(2020) w/S2-20
ASCE 7-16 WITH SUPPLEMENT 1
ASTM
ICC
AWS D1.1-D1.1M-2020
AWS D1.2-D1.2M-2014
AWS D1.3-D1.3M-2018
AWS D1.4-D1.4M-2018
AWS D1.8-D1.8M-2009
FM GLOBAL
SLD 45 IFS
UFC 1-200-1
UFC 3-301-01
UFC 4-010-01
KSC-STD-Z-004G
ANSI/AWC NDS-2018
AISI D100-17
AISI S240-20
INTERNATIONAL BUILDING CODE 2021 (IBC). (INCLUDING BUILDING
CODE AMENDMENTS SPECIFIC TO THE PROJECT SITE
JURISDICTION)
AMERICAN CONCRETE INSTITUTE, "BUILDING CODE REQUIREMENTS
FOR STRUCTURAL CONCRETE AND COMMENTARY"
THE MASONRY SOCIETY, "BUILDING CODE REQUIREMENTS AND
SPECIFICATION FOR MASONRY STRUCTURES"
RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS,
"SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH
BOLTS"
AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "SEISMIC
PROVISIONS FOR STRUCTURAL STEEL BUILDINGS"
AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "SPECIFICATION
FOR STRUCTURAL STEEL BUILDINGS"
AMERICAN IRON AND STEEL INSTITUTE, "NORTH AMERICAN
SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL
STRUCTURAL MEMBERS"
AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMUM DESIGN LOADS
AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER
STRUCTURES"
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM
INTERNATIONAL)
INTERNATIONAL CODE COUNCIL, INTERNATIONAL CODE COUNCIL -
EVALUATION SERVICES (ICC-ES)
AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING
CODE - STEEL"
AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING
CODE - ALUMINUM"
AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING
CODE - SHEET STEEL"
AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING
CODE - REINFORCING STEEL"
AMERICAN WELDING SOCIETY, "STRUCTURAL WELDING
CODE - SEISMIC SUPPLEMENT"
PROPERTY LOSS PREVENTION DATA SHEETS 1-28, 1-29, AND OTHER
APPLICABLE FM GLOBAL REQUIREMENTS
SPACE LAUNCH DELTA 45 INSTALLTION STANDARDS
UNIFIED FACILITIES CRITERIA, DOD BUILDING CODE
UNIFIED FACILITIES CRITERIA, STRUCTURAL ENGINEERING
UNIFIED FACILITIES CRITERIA, DOD MINIMUM ANTITERRORISM
STANDARDS FOR BUILDINGS
KSC STANDARD FOR STRUCTURAL DESIGN
NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD
CONSTRUCTION WITH 2018 NDS SUPPLEMENT
COLD FORMED STEEL DESIGN MANUAL, 17TH EDITION"
NORTH AMERICAN STANDARD FOR COLD-FORMED STEEL
STRUCTURAL FRAMING, 2020 EDITION
1. UNLESS SPECIFICALLY DETAILED ON DRAWINGS, THE FOLLOWING SHALL BE DESIGNED BY THE CONTRACTOR'S DELEGATED DESIGN ENGINEER. SHOP DRAWINGS AND CALCULATIONS FOR COMPLETE DESIGN SHALL BE PREPARED AND SUBMITTED TOGETHER FOR REVIEW BY THE ENGINEER OF RECORD AND BY THE OWNER. CALCULATIONS AND DETAILS SHALL BE SIGNED AND SEALED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE WHICH THE STRUCTURE RESIDES. BEFORE SUBMITTING TO THE ENGINEER OF RECORD, SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR FOR COMPLETENESS AND COMPLIANCE TO THE CONTRACT DOCUMENTS. SHOP DRAWINGS NOT REVIEWED BY THE CONTRACTOR WILL BE REJECTED AND RETURNED. NO FABRICATION SHALL BEGIN UNTIL THE REVIEW PROCESS OF THE SHOP DRAWINGS BY THE ENGINEER OF
RECORD IS COMPLETED, APPROVED, AND RETURNED TO THE CONTRACTOR.
DELEGATED DESIGNS:
DELEGATED DESIGN ITEMS:
A. WOOD LIGHT POLES
Architects Engineers, Inc.
www.brph.com Copyright © 2026
19020 33rd Ave W, Suite 500 Lynnwood, Washington 98036 T 425-921-3500
Alaska Business Entity Number: 56725F
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
FOR CONSTRUCTION
54321 6
A
B
C
D
E
09/24/2024
02/19/2024
Corrected office addresses removed boca
C :\U se rs
\c al tin ok
\D oc um en ts \C
_S _2
5_
C en tra l_ ca lti no k.
rv t
5/ 7/
:2
6:
P M
A R
E A
P
A D
D
C. ALTINOK
K. BANNISTER
P A
C
IF
IC
S
P A
C E
P O
R T
C O
M P
L E
X
K O
D
IA
K I S
L A
N D
A
L A
S K
A
A L A
S K
A A
E R
O S
P A
C E
C O
R P
O R
A T
IO
N
C09729.001
S-001
05/08/2026
GENERAL NOTES
BRIAN LEE SAYRE
ALASKA SE 215775
WELDED CONNECTION - PRIOR TO WELDING (TABLE N5.4-1, AISC 360-16):
ITEM
STRUCTURAL STEEL (IBC 1705.2.1)
INSPECTION ACTION INSTRUCTIONS
PERFORM OBSERVE
VERIFY WELDER QUALIFICATION RECORDS
AND CONTINUITY RECORDS
PERFORM OBSERVEMATERIAL IDENTIFICATION VERIFY TYPE AND GRADE OF MATERIAL.
PERFORM OBSERVEWELDER IDENTIFICATION A SYSTEM SHALL BE MAINTAINED BY WHICH A WELDER WHO HAS
WELDED A JOINT OR MEMBER CAN BE IDENTIFIED.
PERFORM OBSERVEFIT-UP GROOVE WELDS
VERIFY JOINT PREPARATION, DIMENSIONS, CLEANLINESS,
TACKING, AND BACKING TYPE AND FIT.
PERFORM OBSERVEACCESS HOLES VERIFY CONFIGURATION AND FINISH.
PERFORM OBSERVEFIT-UP OF FILLET WELDS
VERIFY ALIGNMENT, GAPS AT ROOT, CLEANLINESS OF STEEL
SURFACES, AND TACK WELD QUALITY AND LOCATION.
WELDED CONNECTION - DURING WELDING (TABLE N5.4-2, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVE
CONTROL AND HANDLING OF WELDING
CONSUMABLES
VERIFY PACKAGING AND EXPOSURE CONTROL.
PERFORM OBSERVE
PERFORM OBSERVE
PERFORM OBSERVE
PERFORM OBSERVE
CRACKED TACK WELDS
VERIFY THAT WELDING DOES NOT OCCUR OVER CRACKED TACK
WELDS.
ENVIRONMENTAL CONDITIONS
VERIFY WIND SPEED IS WITHIN LIMITS AS WELL AS
PRECIPITATION AND TEMPERATURE.
WPS FOLLOWED
VERIFY ITEMS SUCH AS SETTINGS ON WELDING EQUIPMENT,
TRAVEL SPEED, WELDING MATERIALS, SHIELDING GAS
TYPE/FLOW RATE, PREHEAT APPLIED, INTERPASS
TEMPERATURE MAINTAINED, AND PROPER POSITION.
WELDING TECHNIQUES
VERIFY INTERPASS AND FINAL CLEANING, EACH PASS IS WITHIN
PROFILE LIMITATIONS, AND QUALITY OF EACH PASS.
WELDED CONNECTION - AFTER WELDING (TABLE N5.4-3, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVEWELDS CLEANED
PERFORM OBSERVESIZE, LENGTH, AND LOCATION OF WELDS
PERFORM OBSERVE
PERFORM OBSERVE
PERFORM OBSERVE
PERFORM OBSERVE
VERIFY THAT WELDS HAVE BEEN PROPERLY CLEANED
WELDS MEET VISUAL ACCEPTANCE CRITERIA
ARC STRIKES
K-AREA
BACKING & WELD TABS REMOVED
PERFORM OBSERVEREPAIR ACTIVITIES
PERFORM OBSERVE
DOCUMENT ACCEPTANCE OR REJECTION OF
WELDED JOINT/MEMBER
NONDESTRUCTIVE TESTING (NDT) OF WELDED JOINTS (SECTION N5.5, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVE
COMPLETE-JOINT-PENETRATION (CJP) GROOVE
WELDS IN MATERIALS 5/16-INCH THICK OR GREATER
BOLTED CONNECTION - PRIOR TO BOLTING (TABLE N5.6-1, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVECERTIFICATIONS OF FASTENERS
BOLTED CONNECTION - DURING BOLTING (TABLE N5.6-2, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVEFASTENER ASSEMBLIES
** NOT REQUIRED IF ONLY SNUG-TIGHT JOINTS ARE SPECIFIED (PER SECTION N5.6a OF AISC 360-16).
BOLTED CONNECTION - AFTER BOLTING (TABLE N5.6-3, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVE
DOCUMENT ACCEPTANCE OR REJECTION OF
BOLTED CONNECTIONS
OTHER STEEL INSPECTIONS (SECTION N5.7 & N5.8, AISC 360-16):
ITEM INSTRUCTIONS
PERFORM OBSERVESTRUCTURAL STEEL DETAILS
ULTRASONIC TESTING SHALL BE PERFORMED ON 100% OF CJP
GROOVE WELDS SUBJECT TO TRANSVERSELY APPLIED TENSION
LOADING IN BUTT, TEE, AND CORNER JOINTS FOR STRUCTURES IN
RISK CATEGORY III OR IV, 10% IN RISK CATEGORY II, AND 0% IN
RISK CATEGORY I. TESTING RATE MUST BE INCREASED PER
SECTION N5.5f IF 5% OR MORE WELDS TESTED HAVE
UNACCEPTABLE DEFECTS. THE RATE IS PERMITTED TO BE
REDUCED PER SECTION N5.5e.
PERFORM OBSERVEWELDED JOINTS SUBJECT TO FATIGUE PER AISC 360-16, SECTION N5.5c.
PERFORM OBSERVEFASTENERS MARKED VERIFY THAT FASTENERS HAVE BEEN MARKED IN ACCORDANCE
WITH ASTM REQUIREMENTS.
PERFORM OBSERVEPROPER FASTENERS FOR JOINT
VERIFY GRADE, TYPE, AND BOLT LENGTH IF THREADS ARE
EXCLUDED FROM THE SHEAR PLANE.
PERFORM OBSERVEPROPER BOLTING PROCEDURE VERIFY PROPER PROCEDURE IS USED FOR THE JOINT DETAIL.
PERFORM OBSERVECONNECTING ELEMENTS
VERIFY APPROPRIATE FAYING SURFACE CONDITION AND HOLE
PREPARATION, IF SPECIFIED, MEET REQUIREMENTS.
PERFORM OBSERVEPRE-INSTALLATION VERIFICATION TESTING**
OBSERVE AND DOCUMENT VERIFICATION TESTING BY
INSTALLATION PERSONNEL FOR FASTENER ASSEMBLIES AND
METHODS USED.
PERFORM OBSERVEPROPER STORAGE
VERIFY PROPER STORAGE OF BOLTS, NUTS, WASHERS, AND OTHER
FASTENER COMPONENTS.
VERIFY THAT FASTENER ASSEMBLIES ARE OF SUITABLE
CONDITION, PLACED IN ALL HOLES, AND WASHERS AND NUTS ARE
POSITIONED AS REQUIRED.
PERFORM OBSERVESNUG-TIGHT PRIOR TO PRETENSIONING
VERIFY THAT JOINTS ARE BROUGHT TO SNUG-TIGHT CONDITION
PRIOR TO PRE-TENSIONING OPERATION. ALSO APPLIES TO JOINTS
SPECIFIED AS SNUG-TIGHT ONLY.
PERFORM OBSERVEFASTENER COMPONENT**
VERIFY THAT FASTENER COMPONENT NOT TURNED BY WRENCH IS
PREVENTED FROM ROTATING.
PERFORM OBSERVEPRETENSIONED FASTENERS**
VERIFY THAT FASTENERS ARE PRETENSIONED IN ACCORDANCE
WITH RCSC SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM
THE MOST RIGID POINT TOWARD THE FREE EDGES.
ALL FABRICATED STEEL OR STEEL FRAMES SHALL BE INSPECTED
TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN IN
CONSTRUCTION DOCUMENTS, SUCH AS BRACES, STIFFENERS,
MEMBER LOCATIONS, AND PROPER APPLICATION OF JOINT DETAILS
AT EACH CONNECTION.
PERFORM OBSERVEANCHOR RODS AND OTHER EMBEDMENTS
SUPPORTING STRUCTURAL STEEL
INSPECTOR SHALL BE ON THE PREMISES DURING THE PLACEMENT
OF ANCHOR RODS AND OTHER EMBEDMENTS SUPPORTING
STRUCTURAL STEEL FOR COMPLIANCE WITH CONSTRUCTION
DOCUMENTS. VERIFY THE DIAMETER, GRADE, TYPE, AND LENGTH
OF THE ANCHOR ROD OR EMBEDDED ITEM, AND THE EXTENT OR
DEPTH OF EMBEDMENT PRIOR TO PLACEMENT OF CONCRETE.
INSPECTION ACTION
INSPECTION ACTION
INSPECTION ACTION
ACCEPTANCE CRITERIA TO CONSIDER INCLUDES CRACK
PROHIBITION, WELD/BASE-METAL FUSION, CRATER CROSS
SECTION, WELD PROFILES AND SIZE, UNDERCUT, AND POROSITY.
INSPECTION ACTION
INSPECTION ACTION
INSPECTION ACTION
INSPECTION ACTION
STRUCTURAL STEEL (IBC 1705.2.1) CON'TSPECIAL CASES (IBC 1705.1.1):
ITEM FREQUENCY OF INSPECTION INSTRUCTIONS
CONTINUOUS PERIODICMATERIAL ALTERNATIVES
PER DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE OR REPORT
FROM AN ACCEPTED ACCREDITATION AGENCY (I.E. ICC-ES).
STEEL SPECIAL INSPECTIONS OF RAILING SYSTEMS SHALL BE LIMITED TO WELDING INSPECTION OF WELDS AT THE BASE OF CANTILEVERED RAIL POSTS.
PERFORM OBSERVE
FIT-UP CJP GROOVE WELDS OF HSS T-, Y-, AND
K- JOINTS WITHOUT BACKING
VERIFY JOINT PREPARATION, ALIGNMENT, GAPS AT ROOT,
CLEANLINESS, TACK QUALITY AND LOCATION.
PERFORM OBSERVE
VERIFY WELDING PROCEDURES (WPS)
AVAILABLE
PERFORM OBSERVE
VERIFY CERTIFICATIONS FOR WELDING
CONSUMABLES AVAILABLE
PERFORM OBSERVECHECK WELDING EQUIPMENT
PERFORM OBSERVE
PLACEMENT AND INSTALLATION OF STEEL
HEADED STUD ANCHORS
PERFORM OBSERVE
WELD ACCESS HOLES IN ROLLED HEAVY SHAPES
AND BUILT-UP HEAVY SHAPES
WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR
STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY
INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 INCHES OF THE
WELD
PERFORM OBSERVE
NO PROHIBITED WELDS HAVE BEEN ADDED
WITHOUT THE APPROVAL OF THE EOR
AFTER ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES ARE
WELDED, VISUALLY INSPECT THE WELD ACCESS HOLE FOR
CRACKS
** NOT REQUIRED IF ONLY SNUG-TIGHT JOINTS ARE SPECIFIED (PER SECTION N5.6a OF AISC 360-16).
PERFORM OBSERVEGALVANIZED STRUCTURAL STEEL MAIN MEMBERS
VISUALLY INSPECT EXPOSED CUT SURFACES OF GALVANIZED
STRUCTURAL STEEL MAIN MEMBERS AND EXPOSED CORNERS OF
RECTANGULAR HSS FOR CRACKS SUBSEQUENT TO GALVANIZING.
CRACKS SHALL BE REPAIRED OR THE MEMBER
SHALL BE REJECTED.
VERIFY SIZE, SPACING AND CORRECT INSTALLATION OF STUDS.
CONTINUOUS PERIODICUNUSUAL DESIGN APPLICATIONS
PER DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE OR REPORT
FROM AN ACCEPTED ACCREDITATION AGENCY (I.E. ICC-ES).
CONTINUOUS PERIODIC
MATERIALS AND SYSTEMS REQUIRED TO BE
INSTALLED IN ACCORDANCE WITH ADDITIONAL
MANUFACTURER'S INSTRUCTION THAT PRESCRIBE
REQUIREMENTS NOT CONTAINED IN THE IBC OR
REFERENCED STANDARDS
REQUIRED SPECIAL INSPECTIONS AND TEST PER IBC 2021
INDICATED ITEMS REQUIRING SPECIAL INSPECTION ARE IDENTIFIED UNDER COLUMNS "FREQUENCY OF INSPECTION" AS "PERIODIC" OR "CONTINUOUS" OR UNDER COLUMNS "INSPECTION ACTION" AS "PERFORM" OR "OBSERVE". IF NO BOX IS CHECKED, EITHER THE TASK DOES NOT EXIST OR DOES NOT
REQUIRE ANY SPECIAL INSPECTION.
STATEMENT OF SPECIAL INSPECTIONS 2021 IBC
THE OWNER SHALL HIRE AN INDEPENDENT TESTING/INSPECTION AGENCY TO PERFORM REQUIRED SPECIAL INSPECTIONS IN ACCORDANCE WITH SECTION 1704.2 OF THE INTERNATIONAL BUILDING CODE (IBC).
1.
THE STATEMENT OF SPECIAL INSPECTIONS HEREIN IS FULFILLMENT OF THE REQUIREMENTS OF IBC SECTIONS 1704
AND 1705.
2.
SPECIAL INSPECTIONS AND TESTING SHALL BE PERFORMED IN ACCORDANCE WITH THE APPROVED PLANS AND
SPECIFICATIONS, THIS STATEMENT, IBC CHAPTER 17 AND ITS REFERENCED STANDARDS.
3.
THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK FOR COMPLIANCE WITH THE JURISDICTION APPROVED PLANS, SPECIFICATIONS, AND APPLICABLE PROVISIONS OF THE IBC. THE ARCHITECT/ENGINEER'S REVIEWED SHOP DRAWINGS, AND/OR PLACEMENT DRAWINGS, MAY BE USED ONLY AS AN AID TO SPECIAL INSPECTIONS. THE DEFINITIONS FOR
ACTIONS OR FREQUENCIES OF INSPECTIONS ARE AS FOLLOWS:
4.
A. "CONTINUOUS", FULL-TIME OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL
INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.
B. "PERIODIC", INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED AND AT THE
COMPLETION OF THE WORK.
C. "OBSERVE" THESE ITEMS ON A RANDOM BASIS (AISC). OPERATIONS NEED NOT BE DELAYED PENDING THESE
INSPECTIONS.
D. "PERFORM" THESE TASKS FOR EACH BOLTED CONNECTION, WELDED JOINT, OR MEMBER (AISC).
THE SPECIAL INSPECTOR SHALL COMPLETE A DAILY REPORT FOR INSPECTIONS. THE DAILY REPORTS SHALL REMAIN AT THE JOB SITE WITH THE CONTRACTOR FOR THE BUILDING OFFICIAL'S INSPECTOR. THE REPORTS SHALL INCLUDE THE
FOLLOWING.
5.
THE INSPECTOR SHALL BRING NON-CONFORMING ITEMS TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR, AND NOTE ALL SUCH ITEMS IN THE DAILY REPORT. IF ANY ITEM IS NOT RESOLVED IN A TIMELY MANNER AND IS ABOUT TO BE INCORPORATED IN THE WORK, THE SPECIAL INSPECTORS SHALL IMMEDIATELY NOTIFY THE ENGINEER OF RECORD.
6.
THE INSPECTION AGENCY SHALL FURNISH MONTHLY REPORTS OF THE TEST AND INSPECTIONS PERFORMED DIRECTLY
TO THE BUILDING OFFICIAL, ENGINEER OF RECORD, AND/OR OTHERS AS DESIGNATED.
7.
THE INSPECTION AGENCY SHALL SUBMIT A FINAL SIGNED AND SEALED REPORT TO THE BUILDING OFFICIAL STATING THAT ALL ITEMS REQUIRING SPECIAL INSPECTIONS AND TESTING WERE FULFILLED, ALL DISCREPANCIES WERE CORRECTED OR RESOLVED, AND ALL WORK REQUIRING SPECIAL INSPECTIONS IS IN CONFORMANCE WITH THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS AND APPLICABLE CODES. ANY ITEMS UNRESOLVED OR DISCREPANCIES IN COVERAGE (I.E. MISSED INSPECTIONS, PERIODIC INSPECTIONS WHEN CONTINUOUS WAS
REQUIRED, ETC) SHALL BE SPECIFICALLY ITEMIZED IN THE REPORT.
8.
THIS STATEMENT OF SPECIAL INSPECTION HAS BEEN PREPARED BY THE ENGINEER OF RECORD WITH THE
UNDERSTANDING THAT THE BUILDING OFFICIAL WILL:
12.
A. REVIEW AND APPROVE THE QUALIFICATIONS OF THE SPECIAL INSPECTORS WHO WILL PERFORM
THE INSPECTIONS.
B. MONITOR SPECIAL INSPECTION ACTIVITIES ON THE JOB SITE TO ASSURE THAT THE SPECIAL INSPECTORS ARE QUALIFIED AND PERFORMING THEIR DUTIES AS CALLED FOR IN THE STATEMENT
OF SPECIAL INSPECTION.
C. REVIEW SUBMITTED INSPECTION REPORTS.
D. PERFORM INSPECTIONS AS REQUIRED BY THE LOCAL BUILDING CODE.
E. ISSUE CERTIFICATION OF OCCUPANCY AFTER ALL SPECIAL INSPECTION REPORTS AND THE FINAL
SPECIAL INSPECTION REPORT HAVE BEEN SUBMITTED AND ACCEPTED.
SPECIAL INSPECTION AND TEST REQUIREMENTS FOR CERTAIN BUILDING ELEMENTS IMPLIED BY THE STATEMENT OF SPECIAL INSPECTIONS YET LISTED AS EXEMPT BY IBC IS PERMITTED TO BE WAIVED WITH WRITTEN APPROVAL FROM
THE ENGINEER OF RECORD.
9.
REQUIREMENTS FOR WIND RESISTANCE:
STATEMENT OF SPECIAL INSPECTION FOR WIND RESISTANCE IS REQUIRED. (REQUIRED IN WIND EXPOSURE CATEGORY B, WHERE THE NOMINAL DESIGN WIND SPEED, Vasd IS 150 MPH OR GREATER. REQUIRED IN WIND EXPOSURE CATEGORY C OR D, WHERE THE NOMINAL DESIGN WIND SPEED, Vasd IS 140 MPH OR GREATER.)
DESCRIPTION OF MAIN WIND FORCE-RESISTING SYSTEM SUBJECT TO SPECIAL INSPECTION FOR WIND RESISTANCE:
(REQUIRED FOR SYSTEMS NOTED IN IBC SECTION 1705.12.1 AND 1705.12.2.)
LATERAL SYSTEM FOR PRE-ENGINEERED METAL BUILDING
DESCRIPTION OF WIND FORCE-RESISTING COMPONENTS SUBJECT TO SPECIAL INSPECTION FOR WIND RESISTANCE:
(REQUIRED FOR SYSTEMS AND COMPONENTS NOTED IN IBC SECTION 1705.12.3.)
COMPONENTS OF PRE-ENGINEERED METAL BUILDING
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OR FABRICATION OF A SYSTEM OR COMPONENT DESCRIBED ABOVE SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER OR THE OWNER'S AUTHORIZED AGENT PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT IN
ACCORDANCE WITH IBC 1704.4. REQUIREMENTS FOR SEISMIC RESISTANCE:
STATEMENT OF SPECIAL INSPECTION FOR SEISMIC RESISTANCE IS REQUIRED.
DESCRIPTION OF SEISMIC FORCE-RESISTING SYSTEM SUBJECT TO SPECIAL INSPECTION AND TESTING FOR SEISMIC RESISTANCE: (REQUIRED FOR SEISMIC DESIGN CATEGORIES C, D, E, OR F IN ACCORDANCE WITH IBC SECTIONS
1705.13.1 THROUGH 1705.13.3, 1705.14.1, AND 1705.14.2.)
LATERAL SYSTEM FOR PRE-ENGINEERED METAL BUILDING
DESCRIPTION OF DESIGNATED SEISMIC SYSTEMS SUBJECT TO SPECIAL INSPECTION AND TESTING FOR SEISMIC RESISTANCE: (REQUIRED FOR ARCHITECTURAL, PLUMBING, ELECTRICAL, AND MECHANICAL SYSTEMS AND THEIR COMPONENTS AND THEIR COMPONENTS THAT REQUIRE DESIGN IN ACCORDANCE WITH CHAPTER 13 OF ASCE 7, HAVE A COMPONENT IMPORTANCE FACTOR, Ip GREATER THAN ONE, AND ARE IN SEISMIC DESIGN CATEGORIES C, D, E, OR F.)
COMPONENTS OF PRE-ENGINEERED METAL BUILDING
DESCRIPTION OF ADDITIONAL SEISMIC SYSTEMS AND COMPONENTS REQUIRING SPECIAL INSPECTIONS AND TESTING:
(REQUIRED FOR SYSTEMS NOTED IN IBC SECTION 1705.13.5 THROUGH 1705.13.9.)
COMPONENTS OF PRE-ENGINEERED METAL BUILDING
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OR FABRICATION OF A SYSTEM OR COMPONENT DESCRIBED ABOVE SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER OR THE OWNER'S AUTHORIZED AGENT PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT IN
ACCORDANCE WITH IBC 1704.4.
10.
11.
A. NAME OF SPECIAL INSPECTOR AND DATE THE INSPECTION WAS PERFORMED.
B. DESCRIPTION OF THE INSPECTIONS, WITH LOCATIONS AND TESTS PERFORMED.
C. LIST OF NON-CONFORMING ITEMS.
D. HOW NON-CONFORMING ITEMS WERE RESOLVED OR UNRESOLVED.
E. LIST OF CHANGES OR CORRECTIONS TO NON-CONFORMING ISSUES AUTHORIZED BY THE ENGINEER, ARCHITECT, OR BUILDING OFFICIAL'S INSPECTORS.
Architects Engineers, Inc.
www.brph.com Copyright © 2026
19020 33rd Ave W, Suite 500 Lynnwood, Washington 98036 T 425-921-3500
Alaska Business Entity Number: 56725F
These plans are protected by Federal Copyright protection. Unauthorized use may result in an infringement action.
Offices in Melbourne, Orlando, Atlanta, Lynnwood, Charleston and Huntsville
DOCUMENT HISTORY
DRAWING NO.
TITLE
PROJECT NUMBER
DRAWN BY
DESIGNED BY
ARCH/ENGR OF RECORD
DATE
FOR CONSTRUCTION
54321 6
A
B
C
D
E
09/24/2024
02/19/2024
Corrected office addresses removed boca
C :\U se rs
\c al tin ok
\D oc um en ts \C
_S _2
5_
C en tra l_ ca lti no k.
rv t
5/ 7/
:2
6:
P M
A R
E A
P
A D
D
C. ALTINOK
K. BANNISTER
P A
C
IF
IC
S
P A
C E
P O
R T
C O
M P
L E
X
K O
D
IA
K I S
L A
N D
A
L A
S K
A
A L A
S K
A A
E R
O S
P A
C E
C O
R P
O R
A T
IO
N
C09729.001
S-002
05/08/2026
SPECIAL
INSPECTIONS
CONTINUOUS PERIODICREINFORCING BAR WELDABILITY
ITEM INSTRUCTIONS
CONTINUOUS PERIODICREINFORCING STEEL, INCLUDING PRESTRESSING
TENDONS
VERIFY WELDABILITY OF REINFORCING STEEL OTHER THAN ASTM
A706 BASED UPON CARBON EQUIVALENT AND IN ACCORDANCE
WITH AWS D1.4.
CONTINUOUS PERIODICREINFORCING BAR WELDING
VISUALLY INSPECT ALL WELDS IN ACCORDANCE WITH AWS D1.4.
VERIFY SIZE AND SPACING OF REINFORCEMENT. INSPECTION OF
SINGLE-PASS WELDS, MAXIMUM 5/16", IS PERMITTED TO BE MADE
PERIODICALLY.
VERIFY PRIOR TO PLACING CONCRETE THAT REINFORCING IS OF
SPECIFIED TYPE, GRADE, AND SIZE; THAT IT IS FREE OF OIL, DIRT
AND RUST; THAT IT IS LOCATED AND SPACED PROPERLY; THAT
HOOKS, BEND, TIES, STIRRUPS AND SUPPLEMENTAL
REINFORCEMENT ARE PLACED CORRECTLY; THAT LAP LENGTHS,
STAGGER AND OFFSETS ARE PROVIDED; AND THAT ALL
MECHANICAL CONNECTIONS ARE INSTALLED PER THE
MANUFACTURER'S INSTRUCTIONS AND/OR EVALUATION REPORT.
CONTINUOUS PERIODICCAST-IN BOLTS & EMBEDS INSPECT ANCHORS CAST IN CONCRETE.
CONTINUOUS PERIODIC
ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERS: ADHESIVE ANCHORS
INSTALLED IN HORIZONTALLY OR UPWARDLY
INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS
ANCHORS/DOWELS SHALL BE SPECIALLY INSPECTED AS REQUIRED
BY THE APPROVED ICC-ES REPORT.
CONTINUOUS PERIODICUSE OF REQUIRED MIX DESIGN
VERIFY THAT ALL MIXES USED COMPLY WITH THE APPROVED
CONSTRUCTION DOCUMENTS; ACI 318: CH 19, 26.4.3, 26.4.4; AND IBC
1904.1, 1904.2.
CONTINUOUS PERIODICCONCRETE TESTS
CONTINUOUS PERIODICCONCRETE & SHOTCRETE PLACEMENT
CONTINUOUS PERIODICCURING TEMPERATURE AND TECHNIQUES
VERIFY THAT THE AMBIENT TEMPERATURE FOR CONCRETE IS KEPT
AT > 50°F FOR AT LEAST 7 DAYS AFTER PLACEMENT. HIGH-EARLY-
STRENGTH CONCRETE SHALL BE KEPT AT >50°F FOR AT LEAST 3
DAYS. ACCELERATED CURING METHODS MAY BE USED (SEE ACI
318:26.4.7 - 26.4.9). THE AMBIENT TEMPERATURE FOR SHOTCRETE
SHALL BE >40°F FOR THE SAME PERIOD OF TIME AS NOTED FOR
CONCRETE. SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST
FOR AT LEAST 24 HOURS AFTER SHOTCRETING. ALL CONCRETE
MATERIALS, REINFORCEMENT, FORMS, FILLERS, AND GROUND
SHALL BE FREE FROM FROST. IN HOT WEATHER CONDITIONS
ENSURE THAT APPROPRIATE MEASURES ARE TAKEN TO AVOID
PLASTIC SHRINKAGE CRACKING AND THAT THE SPECIFIED
WATER/CEMENT RATIO IS NOT EXCEEDED.
CONTINUOUS PERIODICERECTION OF PRECAST CONCRETE
VERIFY THAT ALL PRECAST ELEMENTS ARE LIFTED, ASSEMBLED
AND BRACED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS.
FREQUENCY OF INSPECTION
CONCRETE CONSTRUCTION (IBC 1705.3):
PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
INSPECT CONCRETE (AND SHOTCRETE) PLACEMENT FOR PROPER
APPLICATION TECHNIQUES.
CONTINUOUS PERIODIC
ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERS: MECHANICAL ANCHORS AND
ALL OTHER ADHESIVE ANCHORS
ANCHORS/DOWELS SHALL BE SPECIALLY INSPECTED AS REQUIRED
BY THE APPROVED ICC-ES REPORT.
CONCRETE SPECIAL INSPECTIONS AND TESTS SHALL NOT BE REQUIRED FOR:
1. ISOLATED SPREAD CONCRETE FOOTINGS OF BUILDINGS THREE STORIES OR LESS ABOVE GRADE PLANE THAT ARE FULLY SUPPORTED ON EARTH OR ROCK
2. CONTINUOUS CONCRETE FOOTINGS SUPPORTING WALLS OF BUILDINGS THREE STORIES OR LESS ABOVE GRADE PLANE THAT ARE FULLY SUPPORTED ON EARTH OR ROCK WHERE
A. THE FOOTINGS SUPPORT WALLS OF LIGHT-FRAME CONSTRUCTION
B. THE FOOTINGS ARE DESIGNED IN ACCORDANCE WITH TABLE 1809.7
C. THE STRUCTURAL DESIGN OF THE FOOTING IS BASED ON A SPECIFIED COMPRESSIVE STRENGTH, F'c, NOT MORE THAN 2,500 PSI REGARDLESS OF THE COMPRESSIVE STRENGTH SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS OR USED IN THE FOOTING CONSTRUCTION
3. NONSTRUCTURAL CONCRETE SLABS SUPPORTED DIRECTLY ON THE GROUND, INCLUDING PRESTRESSED SLABS ON GRADE, WHERE THE EFFECTIVE PRESTRESS IN THE CONCRETE IS LESS
THAN 150 PSI
4. CONCRETE FOUNDATION WALLS CONSTRUCTED IN ACCORDANCE WITH TABLE 1807.1.6.2
5. CONCRETE PATIOS, DRIVEWAYS, AND SIDEWALKS ON GRADE
REFERENCED STANDARD
ACI 318: CH 20, 25.2, 25.3,
26.6.1-26.6.3
AWS D1.4, ACI 318: 26.6.4
AWS D1.4, ACI 318:26.6.4
ACI 318: 17.8.2
ACI 318: 17.8.2.4
ACI 318: 17.8.2.2
ASTM C31
ASTM C172
ACI 318: 26.5, 26.12
ACI 318: 26.5
ACI 318: 26.5.3 - 26.5.5
ACI 318: 26.9
CONTINUOUS PERIODICSTRENGTH VERIFICATION
VERIFY THAT ADEQUATE STRENGTH HAS BEEN ACHIEVED PRIOR TO
THE REMOVAL OF SHORES AND FORMS OR THE STRESSING OF
POST-TENSIONED TENDONS.
CONTINUOUS PERIODICFORMWORK
VERIFY THAT THE FORMS ARE PLACED PLUMB AND CONFORM TO
THE SHAPES, LINES, AND DIMENSIONS OF THE MEMBERS AS
REQUIRED BY THE APPROVED CONSTRUCTION DOCUMENTS.
ACI 318: 26.11.2
ACI 318: 26.11.1.2(b)
SOILS CONSTRUCTION (IBC 1705.6):
ITEM FREQUENCY OF INSPECTION INSTRUCTIONS
CONTINUOUS PERIODIC
VERIFY MATERIALS BELOW SHALLOW
FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY
CONTINUOUS PERIODIC
VERIFY EXCAVATIONS EXTEND TO PROPER DEPTH
AND HAVE REACHED PROPER MATERIAL
CONTINUOUS PERIODIC
PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS
CONTINUOUS PERIODIC
VERIFY USE OF PROPER MATERIALS, DENSITIES,
AND LIFT THICKNESSES DURING PLACEMENT AND
COMPACTION OF FILL
CONTINUOUS PERIODIC
PRIOR TO PLACEMENT OF COMPACTED FILL,
INSPECT SUBGRADE AND VERIFY THE SITE HAS
BEEN PREPARED PROPERLY
SPECIAL INSPECTIONS AND TESTS FOR ELEMENTS SUBJECT TO
WIND RESISTANCE (IBC 1705.11)
WIND-RESISTING COMPONENTS (IBC 1705.11.3)
INSPECT APPLICABLE WELDING OPERATIONS.
FASTENING OF ROOF COVERING, ROOF DECK,
AND ROOF FRAMING CONNECTIONS
CONTINUOUS PERIODIC
FASTENING OF EXTERIOR WALL COVERING
AND WALL CONNECTIONS TO ROOF AND
FLOOR DIAPHRAGMS AND FRAMING
CONTINUOUS PERIODIC INSPECT APPLICABLE FASTENING OPERATIONS.
ITEM INSTRUCTIONSFREQUENCY OF INSPECTION
STRUCTURAL STEEL INSPECTIONS AND NONDESTRUCTIVE TESTING (NDT) OF WELDED JOINTS
(IBC 1705.13.1, IBC 1705.14.1, & AISC 341-16 CHAPTER J)
ITEM INSTRUCTIONS
PERFORM OBSERVEPROTECTED ZONES VERIFY THAT NO HOLES OR UNAPPROVED ATTACHMENTS ARE MADE
WITHIN THE PROTECTED ZONE
SPECIAL INSPECTIONS AND TESTS FOR ELEMENTS SUBJECT TO
SEISMIC RESISTANCE (IBC 1705.13 & IBC 1705.14)
INSPECTION ACTION
PERFORM OBSERVE
COMPLETE-JOINT-PENETRATION (CJP) GROOVE
WELDS IN MATERIALS 5/16-INCH THICK OR GREATER
ULTRASONIC TESTING (UT) SHALL BE PERFORMED ON 100% OF CJP
GROOVE WELDS. WELD DISCONTINUITIES SHALL BE ACCEPTED OR
REJECTED ON THE BASIS OF AWS D1.1/D1.1M TABLE 6.2.
PERCENTAGE OF NDT TESTING IS PERMITTED TO BE REDUCED PER
AISC 341-16 SECTION J6.2g.
PERFORM OBSERVE
BASE METAL THICKER THAN 1-1/2-INCH LOADED IN
TENSION IN THE THROUGH-THICKNESS DIRECTION
IN TEE AND CORNER JOINTS WHERE THE
CONNECTED MATERIAL IS > 3/4 INCH AND
CONTAINS CJP GROOVE WELDS
ULTRASONIC TESTING (UT) SHALL BE PERFORMED FOR
DISCONTINUITIES BEHIND AND ADJACENT TO THE FUSION LINE. ANY
BASE METAL DISCONTINUITIES FOUND WITHIN T/4 OF THE
STEEL SURFACE SHALL BE ACCEPTED OR REJECTED ON THE BASIS
OF AWS D1.1/D1.1M TABLE 6.2 WHERE T IS THE THICKNESS OF THE
PART SUBJECTED TO THROUGH-THICKNESS STRAIN.
PERFORM OBSERVEREDUCED BEAM SECTION (RBS) REPAIR
MAGNETIC PARTICAL TESTING (MT) SHALL BE PERFORMED ON ANY
WELD AND ADJACENT AREA OF THE RBS CUT SURFACE THAT HAS
BEEN REPAIRED BY WELDING, OR ON THE BASE METAL OF THE RBS
CUT SURFACE IF A SHARP NOTCH HAS BEEN REMOVED BY GRINDING.
PERFORM OBSERVEWELD TAB REMOVAL SITES
AT THE ENDS OF WELDS WHERE WELD TABS HAVE BEEN REMOVED,
MAGNETIC PARTICAL TESTING (MT) SHALL BE PERFORMED ON THE
SAME BEAM TO COLUMN JOINTS RECEIVING ULTRASONIC TESTING
(UT). PERCENTAGE OF NDT TESTING IS PERMITTED TO BE REDUCED
PER AISC 341-16 SECTION J6.2h. MT OF CONTINUITY PLATE WELD
TAB REMOVAL SITES IS NOT REQUIRED.
MAGNETIC PARTICAL TESTING (MT) OR PENETRANT TESTING SHALL
BE PERFORMED WHEN THE FLANGE THICKNESS EXCEEDS 1 1/2
INCHES FOR ROLLED SHAPES OR WHEN THE WEB THICKNESS
EXCEEDS 1 1/2 INCHES FOR BUILT-UP SHAPES
PERFORM OBSERVE
THERMALLY CUT SURFACES OF BEAM COPES AND
ACCESS HOLES AT WELDED SPLICES AND
CONNECTIONS
PERFORM OBSERVEH-PILES
VERIFY THAT NO HOLES OR UNAPPROVED ATTACHMENTS ARE
MADE WITHIN THE PROTECTED ZONE OF PILING
CONTINUOUS PERIODIC
ANCHORAGE OF ELECTRICAL EQUIPMENT FOR
EMERGENCY OR STANDBY POWER SYSTEMS IN
SEISMIC DESIGN CATEGORY C, D, E, OR F
VERIFY THAT ANCHORAGE COMPLIES WITH APPROVED
CONSTRUCTION DOCUMENTS.
CONTINUOUS PERIODIC
CONTINUOUS PERIODIC
CONTINUOUS PERIODIC
INSTALLATION AND ANCHORAGE OF PIPING
SYSTEMS DESIGNED TO CARRY HAZARDOUS
MATERIALS AND THEIR ASSOCIATED MECHANICAL
UNITS IN SEISMIC DESIGN CATEGORY C, D, E, OR F
INSTALLATION AND ANCHORAGE OF DUCTWORK
DESIGNED TO CARRY HAZARDOUS MATERIALS IN
SEISMIC DESIGN CATEGORY C, D, E, OR F
INSTALLATION AND ANCHORAGE OF VIBRATION
ISOLATION SYSTEMS HAVING A CLEARANCE OF ≤
1/4" BETWEEN THE EQUIPMENT SUPPORT FRAME
AND RESTRAINT IN SEISMIC DESIGN CATEGORY C,
D, E, OR F
VERIFY THAT INSTALLATION COMPLIES WITH APPROVED
CONSTRUCTION DOCUMENTS AND MANUFACTURERS
RECOMMENDATIONS.
SEISMICALLY ISOLATED STRUCTURES (IBC 1705.13.8 & 1705.14.3):
CONTINUOUS PERIODIC
VERIFICATION OF TESTING PER ASCE 7-16 SECTION
17.8
VERIFY REQUIRED TESTING ACCORDING TO ASCE 7-16 SECTION 17.8
HAVE BEEN CONDUCTED.
CONTINUOUS PERIODIC
FABRICATION AND INSTALLATION OF SEISMIC
ISOLATION SYSTEM IN SEISMIC DESIGN CATEGORY
B, C, D, E, OR F
VERIFY THAT…