This document contains data and specifications for chemicals and water treatment services required at the Northport VA Medical Center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 is soliciting proposals for water treatment of four cooling towers with a total capacity of 2,800 tons and recirculation rate of 3,150 gallons per minute, closed chill water systems with a volume of 55,000 gallons and makeup of 100,000 gallons per year, and steam systems producing 90 million pounds of steam annually with 5 million gallons of makeup water per year at 50% hardness of 1-150 parts per million. Bidders must provide details on proposed chemicals including active components, dosages, costs, and testing limits for corrosion inhibitors, biocides, scale controls, oxygen scavengers, alkalis, and neutralizing amines to treat the described water systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24223Q0795 0001.docx | DOCX document | |
| Site Visit Info NP updated 6-8-2023.docx | DOCX document | |
| E a - VHA Directive 1810 - Boiler and Boiler Plant Operations _ 2018-09-11.pdf | ||
| G 2021.02.22 Standard Document - Cooling Tower Water Systems.pdf | ||
| F Cooling Tower Pages from Directive 1061 D 2021-02-16.pdf | ||
| 36C24223Q0795_1.pdf | ||
| QASP Northport VA MC.pdf | ||
| PAST PERFORMANCE QUESTIONNAIRE.docx | DOCX document | |
| TECHNICAL QUESTIONNAIRE.docx | DOCX document | |
| Wage Determination 2015-4157 Rev.20.pdf | ||
| LIMITATIONS ON SUBCONTRACTING CERTIFICATION.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT D
DATA FOR CHEMICALS TO BE PROVIDED
AND TYPICAL OPERATING DATA AND WATER QUALITY DATA
I CHEMICALS – Bidders shall complete all data requested for all chemicals proposed to be used. Add additional pages if necessary.
COOLING TOWERS
| 1 |
| Corrosion Inhibitor |
Name
Generic Type
Active Components, % ppm Product in Circulating Water
Dosage, lbs./1000 Gallons of Bleed
Test type and limits
Delivered cost/lb.
Package size
| 2 |
| Biocide |
Name
Generic Type - Liquid Bromine
Active Components, % ppm Product in Circulating Water
Dosage, lbs./1000 Gallons of Volume
Dosage, lbs./1000 Gallons of Bleed
Frequency of application
Test type and limits
Delivered cost/lb.
Package size
| 3 |
| Biocide |
Name
Generic Type
Active Components, % ppm Product in Circulating Water
Dosage, lbs./1000 Gallons of Volume
Dosage, lbs./1000 Gallons of Bleed
Frequency of application
Test type and limits
Delivered cost/lb.
Package size
CLOSED SYSTEMS
CHILLER WATER
Corrosion Inhibitor
Name
Generic Type
Active Components, % ppm Product in Circulating Water
Dosage, lbs./1000 Gallons of Volume
Test type and limits
Delivered cost/lb.
Package size
STEAM SYSTEMS
Scale Control
Generic Type
Active Components, % ppm Product per ppm Hardness ppm Product in Boiler
Dosage rate, lbs. per Million lbs. Feedwater
Test type and limits
Delivered cost/lb.
Package size
Oxygen Scavenger
Generic Type
Active Components, % ppm Product per ppm Oxygen ppm Product per ppm Residual
Dosage rate, ppm
Test type and limits
Delivered cost/lb.
Package size
| 7 |
| Alkali |
Generic Type
Active Components, % ppm Product per ppm Boiler Alkalinity ppm Product per ppm Residual
Dosage rate, ppm
Test type and limits
Delivered cost/lb.
Package size
| 8 |
| Neutralizing Amine |
Generic Type
Active Components, % ppm Product per ppm Feedwater Alkalinity
Dosage rate, ppm
Test type and limits
Delivered cost/lb.
Package size
II BASIS FOR CALCULATIONS
| Number of Cooling Towers |
| 4 |
| Tons |
| 2,800 |
| Recirc Rate, gpm |
| 3,150 |
| Bleed off Rate, gpy |
| 17 million gpy |
| Cycles |
| 4 |
| Winter Volume, gal |
| 12,000 |
| Summer Volume, gal |
| 12,000 |
CLOSED SYSTEMS
| Chill volume, gal |
| 55,000 |
| Chill makeup, gpy |
| 100,000 |
STEAM SYSTEMS
| Steam produced, lbs./yr. |
| 90 million lb./yr |
| Makeup, gal/yr. |
| 5 million gpy |
| % Makeup |
| 50 |
| Makeup Temperature, °F |
| 212+ |
| Feedwater hardness, ppm |
| 1-150 |
| Operating period, days |
| 365 |
IV RAW WATER ANALYSIS
| Chemical Parameter |
| Typical Concentration |
| Total Hardness as CaCO3 |
| 50 to 100 ppm |
| Calcium Hardness as CaCO3 |
| 25 – 50 ppm |
| Conductivity, micromhos |
| 200-300 umhos/cm |
| Silica, as SiO2 |
| NA |
| Sulfate as SO4 |
| 15-20 ppm |
| Chloride as NaCl |
| 15-30 ppm |