Attachment_ CRCBF-04 Station Service Transformer SECTION 1000.pdf
PDF 104 KB Posted
- Attached to
- CRCBF-04 Station Service Transformer
- Solicitation number
- 69CRC-S1962
- Issued by
- Clark County, Nevada
About this file
This document is a technical specification for substation voltage transformers requested as part of the CRCBF-04 Station Service Transformer contract opportunity issued by the Colorado River Commission of Nevada (CRCNV). The contract requires the supply of single-phase, oil-immersed, self-cooled voltage transformers with a 230kV nominal system voltage, 133kV primary line-to-ground voltage, and 120/240V secondary voltage ratings. The transformers must meet IEEE and NEMA standards and be regularly manufactured by an established supplier with at least 3 years of proven reliable service in outdoor substation use. The contract covers the jurisdictions of Clark County and the City of Las Vegas in Nevada.
The specification outlines the required submittals, including detailed drawings, and notes that the transformer installation and assembly will be performed by others. The transformers must be delivered to the site in open-top trucks or trailers protected by tarpaulin. Any errors, discrepancies, or shipping damage must be corrected immediately at the supplier's expense to avoid delays in construction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 1000
33 71 26 26 TND
Voltage Transformers
33 71 26.26 - 1
33 71 26.26 TND.DOCX 12/03/2013
SECTION 33 71 26.26 – VOLTAGE TRANSFORMERS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes the individual specifications and requirements for substation voltage transformers to be furnished by this contract. Quantities as indicated on the Drawings.
B. Erection and assembly required at the Job Site will be performed by others.
C. Items furnished under this Section shall comply with the requirements of Division 01.
1.02 REFERENCE STANDARDS:
A. Design, construct, test, and assemble all equipment and materials in conformance with the latest revisions and supplements of all applicable NEMA, IEEE, ASTM, and OSHA standards including, but not limited to, the following:
1. Institute of Electrical and Electronics Engineers (IEEE):
a. C2 - National Electrical Safety Code.
b. C57.13 - Requirements for Instrument Transformers.
c. C57.13.2 - Conformance Test Procedures for Instrument Transformers.
d. C57.13.3 - Guide for Grounding of Instrument Transformer Secondary Circuits and
Cases.
e. C57.19.00 - General Requirements and Test Procedure for Power Apparatus
Bushings.
f. C57.19.01 - Performance Characteristics and Dimensions for Outdoor Apparatus
Bushings.
g. C57.98 - Guide for Transformer Impulse Tests.
2. National Electrical Manufacturers Association (NEMA):
a. EI 21.2 - Instrument Transformers for Revenue Metering (125-kV BIL through
350-kV BIL).
3. American Society for Testing and Materials (ASTM):
a. A6 - Rolled Structural Steel Bars, Plates, Shapes, and Sheet Piling.
b. A108 - Steel Bars, Carbon and Alloy, Cold Finished.
c. A123 - Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products.
d. A143 - Safeguarding Against Embrittlement of Hot-Dip Galvanized Structural Steel
Products and Procedure for Detecting Embrittlement.
e. A153 - Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
f. A370 - Test Methods and Definitions for Mechanical Testing of Steel Products.
g. A394 - Steel Transmission Tower Bolts, Zinc-Coated and Bare.
h. B8 - Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.
i. B188 - Seamless Copper Bus Pipe and Tube.
j. B211 - Aluminum and Aluminum-Alloy Bars, Rods, and Wire.
k. B232 - Concentric-Lay-Stranded Aluminum Conductors, Coated Steel-Reinforced
(ACSR).
l. B236 - Aluminum Bars for Electrical Purposes (Bus Bars).
m. B317 - Aluminum-Alloy Extruded Bar, Rod, Tube, Pipe, and Structural Profiles for
Electrical Purposes (Bus Conductors).
4. Occupational Safety and Health Act (OSHA).
B. Acceptable manufacturers are listed in PART 2. Other manufacturers than those listed may be employed with the approval of the Owner and if the item to be furnished conforms to this Specification.
C. Experience:
SECTION 33 71 26.26 – VOLTAGE TRANSFORMERS: CONTINUED
33 71 26.26 - 2
12/03/2013 33 71 26.26 TND.DOCX
1. The manufacturer of each item of equipment or material furnished shall be regularly engaged in the fabrication of the item and it shall have an acceptable history of satisfactory, reliable service in outdoor substation use for a period of at least three years under comparable environmental conditions.
2. Newly developed equipment with less than three years actual service will be considered from established manufacturers only if it has been adequately tested, meets the requirements of this contract, and is approved by the Owner.
1.03 COMPLIANCE SUBMITTAL:
A. Submit as specified in Division 01.
B. Furnish the following types of drawings:
1. Furnish Drawings necessary for design, erection, installation, and operation of all equipment and materials furnished including, but not limited to, the following:
a. Complete drawings and descriptive bulletins for installation, adjustment, testing, maintenance, and operation of all equipment including bus weldments, connectors, insulators, corona fittings, etc.
b. General outline, nameplate, and internal wiring drawings of all equipment.
c. Schematic diagrams showing all external electrical connection terminal numbers.
d. Bushing and insulator outline drawings.
e. Drawings showing additional detail if requested by the Owner or otherwise required for installation and maintenance.
2. Standard drawings of equipment which do not indicate clearly the exact size, model number, and optional items to be furnished will be returned to the Supplier for this information before review by the Owner.
PART 2 - EQUIPMENT
2.01 VOLTAGE TRANSFORMERS:
A. Ratings:
1. Nominal system voltage (kV): 230.
2. Primary line-to-ground voltage (kV): 133.
3. Basic impulse level (kV): 900.
4. Frequency (Hz): 60.
5. Secondary voltage ratings (V): 120/240.
6. Minimum thermal rating (KVA): 50.
B. Type and Design:
1. Single-phase.
2. Oil immersed and self-cooled.
3. Color of bushing porcelain shall be ANSI 70 Gray.
4. Color of base housing shall be ANSI 70 Gray.
5. Furnish all standard accessories including oil, lifting eyes, terminal connectors, secondary junction boxes, oil level gauge, and provisions for mounting and grounding.
C. Acceptable Manufacturers:
1. ABB Power T&D Company, Inc.
2. Associated Engineering.
3. Electromagnetic Industries, Inc.
4. Trench Electric.
5. Ritz.
SECTION 33 71 26.26 – VOLTAGE TRANSFORMERS: CONTINUED
33 71 26.26 - 3
33 71 26.26 TND.DOCX 12/03/2013
PART 3 - EXECUTION
3.01 FIELD SERVICES:
A. Correction of errors, discrepancies, or omissions shall be made immediately upon notification from the resident Owner in order to prevent delay of construction. All corrections resulting from errors, discrepancies, shipping damage, etc., approved by the Owner to avoid delay in construction and required for the installation and proper use of equipment shall be paid for by the Supplier.
3.02 SHIPMENT:
A. All voltage transformers shall be delivered to the Site in open top trucks or trailers protected by tarpaulin to facilitate unloading by crane.
END OF SECTION 33 71 26.26