Attachment_C_Single_Phase_Simplex_Control.pdf
PDF 5 MB Posted
- Attached to
- Villa Substation Oil Containment
- Solicitation number
- 2022-IFB-LM-224
- Issued by
- Los Angeles County, California
About this file
The document is an Installation and Operation Manual for the See Water, Inc. Oil Smart® Single Phase Simplex Control Panel (OSSIM-30), designed for electric utilities and other industrial applications requiring water removal from oil-containing environments. The manual provides comprehensive technical details for a control panel system that can differentiate between water and oil, preventing oil discharge during pumping operations. The OSSIM-30 is specifically engineered to help companies comply with Elevator Code ASME A17.1 and state/federal regulations, featuring a NEMA 4X rated enclosure, remote monitoring dry contacts, and alarm systems that activate when oil or high water levels are detected.
The control panel supports single-phase pumps with full load amp ratings between 0-16.0 FLA, operates on 120/208/240VAC, and includes customizable options such as pump exerciser functionality, circuit breakers, cycle counters, and elapsed time meters. The system comes with an Oil Smart® Pump Switch and Liquid Smart® Alarm Sensor, which use sensor technology to prevent pumping oil and provide visual and audible alarms for high oil or water conditions. The product is UL and CSA certified, designed for applications like elevator sumps, electric utilities, transformer containment areas, and manufacturing facilities, with a 5-year warranty that covers defects in material and workmanship when installed according to manufacturer specifications.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Your Trusted Source for Quality Control Panels.
Single Phase Simplex Control Panel Installation and Operation Manual
OSSIM-30
SEE WATER, INC.
Panel Installation:
1. Caution: To maintain the NEMA 4X rating, make all wiring connections with seal tight cable grips or conduit connections.
2. Run pump cable and Oil Smart® cables through conduit. Make field connections as shown on wiring schematic.
3. Run power line conductor through conduit. Wire to terminals per enclosed schematic.
4. Branch circuit protection to be provided by installer.
5. Panel circuit breakers are closed
6. Mount Oil Smart® pump switch and Liquid Smart® alarm sensor with provided mounting hardware to pump discharge pipe. The ‘OFF’ sensor of the Oil Smart® pump switch shall be positioned at least 3” above the impeller of the pump.
7. Mounting of the Liquid Smart® Sensor is application driven and is to be placed where a high liquid is deemed necessary. The Liquid Smart® Sensor is typically mounted 3” - 6” above the Oil Smart® Pump Switch.
8. Connect service conductors 120/208/240VAC to proper location
Enclosure Mounting: NEMA 4X RATED
Mounting Brackets - A mounting bracket and screw pack are provided with the premium enclosures. To assemble, turn the enclosure upside down on a flat surface, place the mounting bracket over the square boss either horizontally or vertically, and fasten the mounting bracket with the 1/4”-20 x 0.5 SS, countersunk phillips drive screws or vertically, with the mounting brackets in any config., using any acceptable fastening technique.
Covers/Doors - Covers/doors have a gasket pre-assembled to seal against the base.
Note: The control panel should not be mounted in a location that may be subject to submersion.
Additional Panel Options:
28 - Power on Dry Contact
• Normally open 60V AC/DC
DPR - Pump Run Dry Contact
• Normally open 60V AC/DC
24 - Pump Exerciser
• Auto cycles pumps daily, weekly or monthly.
Run Time Options:
• Position A: 50ms (DIP Switch 1,2, and 3)
• Position B: 100ms
• Position C: 4s
• Position D: 8s
Remote Monitoring Dry Contacts:
1. Normally Open dry contacts for high oil, high water, and general high liquid alarm.
Oil Smart® Simplex System: 120/208/240VAC The Oil Smart® OSSIM-30 System incorporates pump controls and alarm sensors that differentiate between oil and water, allowing companies to responsibly discharge the water without the risk of pumping oil. Installation of the OSSIM-30 keeps companies in compliance with Elevator Code ASME A17.1 and State/Federal regulations while reducing the risk of adverse publicity, fines, and expensive cleanup cost.
Model FLA Range
OSSIM-30 (0.0-16.0 FLA)
OSSIM-30-CB (0.0-16.0 FLA)
www.seewaterinc.com
951.487.8073 • 888.733.9283 • info@seewaterinc.com
22220 Opportunity Way, Suite 101 • Riverside, CA 92518
Page 1-3 IM 752 REV. 11/18
SEE WATER, INC.
Sequence of Operation:
Sump Cover
Check Valve
Pump Stop Pump Start
High Liquid Alarm
Typical Installation of Oil SmartÒ Simplex Control Panel
Oil SmartÒ Simplex Control Panel Liquid SmartÒ Alarm Sensor Oil SmartÒ Pump Switch Submersible Pump #1
Normal Condition (Water Only) When water comes in contact with the short (on) sensor, the pump will turn
on. The pump will remain on until water clears the long (off) sensor.
Oil Present Condition If oil comes in contact with the (on) sensor, the pump will not turn on.
Operation of Oil Smart®
Water (Oil Present Condition) If the water level rises enough to contact the (on) sensor under the oil layer, the pump will turn on and remain on until the (off) sensor clears
WATER
WATER
OIL
LAYER
WATER
OIL
LAYER
WATER
OIL
LAYER
WATER
OIL
LAYER
Operation of Liquid Smart®
High Water Level When water comes in contact will both sensors, the white water indicator on the front panel will illuminate. This condition will turn on the red beacon alarm light and sound the alarm buzzer.
High Oil Level If oil comes in contact with both sensors, the yellow oil indicator on the front panel will illuminate. This condition will turn on the red beacon alarm light and sound the alarm buzzer.
Single Phase Simplex Control Panel Installation and Operation Manual
OSSIM-30
Testing:
Oil Smart® Pump Switch Testing:
• Place your thumb on the short stainless steel sensor of the Oil Smart® Pump Switch, and the pump will turn on. While touching the short ‘ON’ sensor, touch the long ‘OFF’ sensor with your fingers; remove your thumb from the short ‘ON’ sensor and begin to move your fingers down the ‘OFF’ sensor simulating water being pumped down. Once fingers are removed from ‘OFF’ sensor, the pump will turn off.
• Optional: Fill the sump area with ground water, when water reaches the ‘ON’ sensor, the pump will turn on and remain on until water clears the ‘OFF’ sensor.
Liquid Smart® Alarm Testing:
• Submerge both sensors in oil and the yellow oil indicator on the front panel will illuminate. To test water sensor, submerge both sensor in ground water and the white water light will illuminate.
• Both test will illuminate the 360 degree visible beacon and sound an 85 decibel at 10’ buzzer.
www.seewaterinc.com
951.487.8073 • 888.733.9283 • info@seewaterinc.com
Page 2-3 IM 752 REV. 11/18
SEE WATER, INC.
Notes:
Troubleshooting:
Caution: before checking electrical connections within the control or attempting to replace any components, turn off all branch circuits supplying power to the main control panel.
Pump control does not activate the pump or pump does not run
• Verify polarity is correct.
• Confirm all connections are tight and secure.
• White plastic case must be kept clean. Clean with household rubbing alcohol and rag.
• Keep control 1” - 2” clear of any metallic material. Mount to PVC pipe or if mounted to metal pipe, make sure to mount with See Water® quick mount PVC bracket.
Alarm will NOT activate
• Confirm separate 120VAC power to circuit board J1-6 and J1-7. Power can be jumpered from incoming voltage if needed.
• Check for any visual damage to optic or stainless steel sensor on the Liquid Smart® Sensor.
Preventive Maintenance
• The Oil Smart® Pump Switch and Liquid Smart® Sensor must be kept clean. If the switches are submerged during install or maintenance, clean the white plastic case with rubbing alcohol. Consistent inspection and preventive maintenance ensures longevity and proper operation of components.
Warranty:
See Water® Inc. warrants that products of its manufacture are free from defects in material and workmanship for a period of 5 years from the date of purchase. This date shall be determined by the date on the invoice and the serial number on the product.
Replacement of the product is at the discretion of See Water® Inc. This warranty is valid when the product is installed in compliance with the manufacturer’s installation instructions.
The manufacturer’s obligation under this warranty shall be limited to the repair or replacement of any parts found by the manufacturer to be defective, provided that the product is returned to See Water’s factory, postage prepaid with proof of original purchase included.
The manufacturer of this warranty shall not be liable under this warranty if the product has not been properly installed;
any alterations/additions/changes to the product will result in a void warranty. Failure to properly install and test this prod-uct can result in personal injury or equipment malfunction.
See Water, Inc. shall not be liable for any loss, damage or expenses from installation or use of its products.
Single Phase Simplex Control Panel Installation and Operation manual
OSSIM-30
www.seewaterinc.com
951.487.8073 • 888.733.9283 • info@seewaterinc.com
Page 3-3 IM 752 REV. 11/18
L1
TB1
MOTOR ON
CR1
PUMP ON
LT1
G
TB1
TB1
TB1
CR1
TB1
TB1
PUMP
MOT1
GND
OIL SMART
WATER PUMP SWITCH
BRN
WHT
BLK
1 2
SILENCE
PB1
1 2
TEST
PB2
OIL
LT3
Y
WATER
LT4
W
BEACON
BE1
R
BUZZER
B1
ALARM
DRY CONTACT
OIL
DRY CONTACT
WATER
DRY CONTACT
COMMON
60V AC/DC, 1A
AUTO
HAND
OFF
TG1
J1
ALARM
OIL SMART
NEGATIVE
OPTICAL SENSOR
SW2
SW2
SW1
SW1
B3A
B3B
BZ
SMART SWITCH
BZ
POSITIVE
LIQUID SMART
ALARM SENSOR
BLU
RED
WHT
GRN
POWER ON
LT2
G
120/240VAC
NEUTRAL
L2 GNDN
TB1
TB1
FIELD WIRING CONNECTIONS
1 2 3 4 5 6
J1
7 8 9 10 11
B L U E
R E D
W H I T E
G R E E N
LIQUID SMART
ALARM SENSOR
- OPTICAL
SENSOR
SMART
SWITCH
C O M M O N
N O R M A L L Y
O P E N
N O R M A L L Y
O P E N
60V
AC/DC
1 AMP
DRY CONTACTS
OIL ALARMWATER
N O R M A L L Y
O P E N
1 2 3 4 5 6
TB1
7 8
120/208/240VAC
1-PHASE, 60Hz
M
PUMP
L
L
N
FOR 120V OPERATION, DO
NOT CONNECT L2. FOR
208/240V OPERATION,
REMOVE JUMPER BETWEEN
TERMINALS 2 AND 3. NEUTRAL
IS REQUIRED AT TERMINAL 3.
B R O W N
B L A C K
W H I T E
OIL SMART
WATER PUMP SWITCH
T
T
L I N E
N E U T R A L
120/240VAC
1-PHASE, 60Hz
SCALE SHEET
SIZE DWG NO. PART NO. REV
REVISIONS
ZONE REV DESCRIPTION DATE APPROVED
TITLE:
DATE:
DATE:
THIS DRAWING CONTAINS
PROPRIETARY INFORMATION
AND SHALL NOT BE USED
OR DISCLOSED WITHOUT
PRIOR WRITTEN
AUTHORIZATION.
DRAWN BY:
APPROVED BY:
FIELD WIRING TORQUE SPECS.
TERMINAL BLOCK UT 2,5
5 IN-LB
TERMINAL BLOCK UT 4
7 IN-LB
TERMINAL BLOCK UT 6
15 IN-LB
TERMINAL BLOCK UT 10
15 IN-LB
TERMINAL BLOCK UT 16
25 IN-LB
TERMINAL BLOCK UT 35
30 IN-LB
TS1, TS2, J2 & J3 PCB
5 IN-LB
TRANSFORMER H1F, H2F & H3F
15 IN-LB
TRANSFORMER H1, H2 & H3
10 IN-LB
M.D. VLS3P16-63 R1
16 IN-LB
M.D. VLS3P63-125 R1
45 IN-LB
M.D. LK4JU3CN 100A
36 IN-LB
M.D. LK4MU3N 200A
200 IN-LB
USE COPPER CONDUCTORS ONLY.
TEMPERATURE RATING OF CONDUCTORS IS TO BE:
60°C (140°F) FOR UNDER 100A.
75°C (167°F) FOR OVER 100A.
BRANCH CIRCUIT PROTECTION SHALL BE PROVIDED BY THE
INSTALLER: MUST BE SIZED ACCORDING TO PUMP/MOTOR
MANUFACTURING SPECIFICATIONS.
VERIFY CORRECT OPERATION OF CONTROL PANEL AFTER
INSTALLATION IS COMPLETE.
DASHED LINE INDICATES
FIELD WIRING.
A
RELOCATION OF CONTROL WIRING AFTER CIRCUIT BREAKER
9/18/16
B
FIELD WIRING CHANGE FOR ALARM BOARD POWER CIRCUIT
8/1/17
C
ADJUSTMENT OF CR1 TERMINALS
8/22/17
D
RELOCATION OF POWER ON LIGHT WIRING
8/31/17
E
REMOVED CB1
9/22/17
F
UPDATED TITLE BLOCK
4/16/20
AO
MM 6/30/14
MM 6/30/14
OSSIM-30
CONTROL SCHEMATIC
B 1511 OSSIM-30 F
NONE 1 OF 1
F N A M E
O S S I M
R E V D A T E
OIL SMART® SIMPLEX CONTROL PANEL OSSIM-30
Overview:
Features:
Applications:
Printed in U.S.A. C491-REV-0220
The Oil Smart® OSSIM-30, when combined with a manual sump pump, will automatically pump water without the risk of pumping oil into the environment. The system will alert in the event of a high oil or high water condition. Installation of the OSSIM-30 allows you to comply with Elevator Code ASME A17.1 and state/federal regulations while reducing the risk of adverse publicity, fines and expensive cleanup costs.
• Includes Oil Smart® pump control and Liquid Smart® alarm sensor with 20′ Cords
• Heavy duty polycarbonate indoor/outdoor NEMA 4X rated enclosure with stainless steel lockable latch
• Pump control and alarm components differentiate between oil and water
• Pump control visible indicators: Pump hand-off-auto (H.O.A.)
switch, green Pump Run light and green Power On light
• Alarm visible indicators: Red beacon alarm light, yellow light for oil, white light for water, alarm test and silence buttons
• Alarm horn sounds at 85 decibels at 10 feet
• Remote monitoring dry contacts: Oil, Water and High Liquid
• Panel and controls: UL listed for the United States and
Canada
• Elevator sumps
• Electric utilities (substations, power plants, underground vaults and transformer barriers)
• Manufacturing facilities
• Any application where there is a need to remove water while containing oil
OIL SMART® SIMPLEX CONTROL PANEL OSSIM-30
Simplex Single Phase: 120/208/240VAC
OSSIM-30 0-16.0 FLA
Models Pump Full Load Amp Rating
Custom Options:
AF
C
CB
CC
DPR
E
ET
MD
S3
= Pump Exerciser - Auto Cycles Pump(s) Daily, Weekly or Monthly = Alarm Flasher = Additional Cord Length Greater than 20’* = Circuit Breaker = Cycle Counter w/ LCD Display and Reset = Dry Contact for Pump Run = 50Hz Configuration = Elapsed Time Meter w/ LCD Display and Reset = Main Disconnect = No Sensors Included
*Additional cord length greater than 20’. Specify after C.
Example: (OSSIM-30-C50) Indicates 50’ cord lengths for all components.
Typical Installation of Oil Smart® Simplex Control Panel
Oil Smart® Simplex Control Panel
Liquid Smart® Alarm Sensor
Oil Smart® Pump Switch
Submersible Pump #1
OIL
LAYER
WATER
OIL
LAYER
Normal Condition (Water Only) When water comes in contact with the short (on) sensor, the pump will turn
on. The pump will remain on until water clears the long (off) sensor.
Oil Present Condition If oil comes in contact with the (on) sensor, the pump will not turn on.
Operation of Oil Smart®
Water (Oil Present Condition) If the water level rises enough to contact the (on) sensor under the oil layer, the pump will turn on and remain on until the (off) sensor clears of water.
OIL
LAYER
WATER
OIL
LAYER
Operation of Liquid Smart®
High Water Level When water comes in contact will both sensors, the white water indicator on the front panel will illuminate. This condition will turn on the red beacon alarm light and sound the alarm buzzer.
High Oil Level If oil comes in contact with both sensors, the yellow oil indicator on the front panel will illuminate. This condition will turn on the red beacon alarm light and sound the alarm buzzer.
Printed in U.S.A.
Your Trusted Source for Quality Control Panels.
www.seewaterinc.com
951.487.8073 • 888.733.9283 • info@seewaterinc.com
USE COPPER CONDUCTORS ONLY.
TEMPERATURE RATING OF CONDUCTORS IS TO BE 60°C (167°F).
BRANCH CIRCUIT PROTECTION SHALL BE PROVIDED BY THE
INSTALLER: MUST BE SIZED ACCORDING TO PUMP/MOTOR
MANUFACTURING SPECIFICATIONS.
VERIFY CORRECT OPERATION OF CONTROL PANEL AFTER
INSTALLATION IS COMPLETE.
11.13"
5.63"
The See Water, Inc. Oil Smart® System is the recognized solution for electric utilities. Utility Oil Smart Systems allow water to be pumped from transformer oil containment areas and underground vaults without the risk of pumping oil.
www.seewaterinc.com
• EPA SPCC & IEEE 980 Compliant
• Complete Utility Packaged Pumping System
• UL & CSA Certified
Features
©2018 See Water Inc. All Rights Reserved.
Oil Smart®
Electric Utility Systems
151 = 1/3 HP
152 = 4/10 HP
153 = 1/2 HP
Pump Model
OSS20PBPR6
OSSIM
OSSIM-30
OSSIM-TP-1
OSD1P
Pump Comparison Chart
Model HP Amps Volts-Phase Type
1/3
4/10
1/2
8.5
10.5
115-1
115-1
115-1
Cast Iron
Cast Iron
Cast Iron
208, 240, 480VAC, Three-Phase Pump/Controls Available
• OSSIM-TP-1 Upgraded Simplex Kit
| • | Rated for 120/208/240VAC single phase |
| • | Controls a single phase pump up to 28 FLA |
| • | Outdoor/Indoor NEMA 4X enclosure |
| • | Upgraded pump protection: motor protective |
switch
| • | Remote monitoring dry contacts |
| • | Includes Oil Smart® Pump Switch & Liquid |
Smart® Alarm Sensor
• OSSIM-30 Simplex Kit
• Controls one 120/208/240VAC pump up to
16 FLA
• Outdoor/Indoor 10″x8″x4″ NEMA 4X enclosure
| • | Alarm Visual Indicators |
| • | Remote monitoring dry contacts |
| • | Includes Oil Smart® Pump Switch & Liquid |
Smart® Alarm Sensor
GALLONS
LITERS
TO
TA
L D
YN
AM
IC
H
EA
D
FE
ET
ME
TE
RS
FLOW PER MINUTE
60 70
360320
80 90 100
PUMP PERFORMANCE CURVE
MODEL 151/152/153
• OSS20PBPR6 Plug & Play Kit
| • | Directly controls sump pumps 0 to 1 hp |
| • | Quick and easy installation |
| • | No panel required |
| • | Rated for 120VAC |
| • | Standard 20’ cord with pigtail connection |
| • | Rated for 120/208/240VAC single phase |
| • | Outdoor/Indoor NEMA 4X enclosure |
| • | Controls two single phase pumps up to 28 |
FLA
• Two pump alternation and high demand two pump operation
• Upgraded pump protection: motor protectectiveswitches included for both pumps
• OSD1P Duplex Kit
4 15/16
11 11/16
3 7/8
6 7/32
4 5/8
3 7/8
3 7/8 12 1/8
5 3/8
1 1/2" NPT
3 7/8
6 7/32
4 5/8
3 7/8
3 7/8
Model 152/153
Model 151
C US
698A 508A
See Water’s Oil Smart® Electric Utility Kits are specifically designed for transformer containment vaults where there is a need to pump water without the risk of pumping hydrocarbons. Oil Smart® systems are the proven solution for the proper evacuation of water while complying with state and federal regu-latory requirements (EPA SPCC & IEEE 980). The utility kits come complete with an Oil Smart® pump controller and fractional horsepower pump.
Pump Features
| • | Made of durable cast iron |
| • | Automatic reset thermal over load |
protected
| • | Non-clogging vortex impeller |
| • | Model 151 - 1/3 HP Passes 1/2” |
spherical soilds
• Model 152 - .4 HP Passes 3/4” spherical soilds
• Model 153 - 1/2 HP Passes 3/4” spherical soilds
• CSA Certified C/US Tested to UL Standard CSA22.2 No. 108
Pump Information
© 2018 See Water® Inc, All rights reserved. Oil Smart® is a registered trademark of See Water® Inc.
See Water® Inc.
22220 Opportunity Way, Suite. 101 | Riverside, CA 92518 Telephone: (888) 733-9283 | Fax: (951) 487-0557 www.seewaterinc.com
| 1. Installation Brochure - OSSIM-30 |
| 2.Schematic - OSSIM-30 revF |
| Sheets and Views |
| 2.Schematic - OSSIM-30 revF-1 |
| 3. Catalog - OSSIM-30 |
| 4. Product Layout Drawing - OSSIM-30 |
| Utility Brochure Capability |
File details come from the government source that posted it. Updated .