Attachment C - Line 1.pdf
PDF 223 KB Posted
- Attached to
- D5 Mast Arm Pole - REBID
- Solicitation number
- RFB 605 2200000178 2
- Issued by
- Bath County, Kentucky
About this file
This is a design analysis report prepared by the Kentucky Department of Transportation, District 5, for an overheight detection structure in Jefferson County, Louisville. The project involves the structural analysis and design of a signal pole assembly with two 35-foot mast arms positioned at different alignments (0 degrees and 90 degrees) mounted at a height of 19 feet on a 21.5-foot vertical pole. The analysis was conducted using AASHTO 6th Edition (2013) standards and accounts for environmental factors including a basic wind speed of 90 mph, wind importance factor of 0.87, and a gust effect factor of 1.14. The pole structure is designed to support custom arm attachments weighing 500 pounds each with dimensions of 102.3 inches in length and 36 inches in width, positioned 30 feet from the pole base.
The design analysis determined maximum structural loads for Pole A, including a maximum axial load of 5,542.65 pounds, maximum shear of 1,610.98 pounds, and a calculated moment of 71.49 kip-feet with zero torsion. The foundation design specifies a 36-inch diameter foundation with 12.5 feet of soil depth and 6 feet of rock depth, requiring a total volume of 3.3 cubic yards of soil and 1.6 cubic yards of rock. Vertical reinforcement consists of thirteen number 8 bars with number 4 ties at 12-inch pitch spacing. The analysis was completed on July 22, 2021, with the disclaimer that these calculations were developed by Florence and Hutcheson, Inc., and require verification by professionally qualified personnel before application.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
District: 5
County: jefferson
City: louisville
Permit Num:
PM Name:
Project Num: Author: Swansegar, Ted (ted.swansegar@ky.gov)
File Name: D5 overheightdetection
Code Version: AASHTO 6th Edition (2013)
Created: 7/22/2021 2:00:00 PM
Last Edited: 7/22/2021 2:09:00 PM
I. Project Data Used Custom Attachments Data
Department:
Basic Wind Speed: 90.00
Wind Importance: 0.87
Velocity Conversion: 0.93
Ice Load Pressure: Gust Effect: 1.14
II. Design Assumptions 3.00
III. Mast Arm
Disclaimer: The contents of this program were developed for use by Florence and Hutcheson, Inc. The calculations derived from said program should not be used for any application without examination and verification of its accuracy and suitability for such application by professionally qualified personnel. Florence and Hutcheson, Inc. assumes no liability or responsibility for and makes no representations or warranties as to the applicability or suitability of these results and anyone making use thereof or relying thereon assumes all risk and liability arising from such use or reliance. This program does not constitute a standard, specification or regulation.
Pole A
Page 1 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM
Salsa Design Analysis (Detail Version)
Pole Attachments Pole Name Height (ft) Align (deg) Length (in) Width (in) Thickness (in) Weight
(lbs) Drag
IV. Pole Inputs
Vertical Pole Info Pole Height
(ft) Base (in) Top (in) Thickness
(in) Cd Directionality
Coefficient
A 21.50 18.50 15.49 0.37 0.79 0.95
Mast Arms Length
(ft) Height
(ft) Seg1
Length (ft)
Seg1 Base (in)
Seg1 Taper
Seg1 Thickness
(in)
Seg2 Base (in)
Seg2 Taper
Seg2 Thickness
(in)
35.0000 19.0000 N/A 13.7500 0.1400 0.2500 N/A 0.1400 N/A
35.0000 19.0000 N/A 13.7500 0.1400 0.2500 N/A 0.1400 N/A
Luminaire Arms Length
(ft) Height
(ft) Seg1
Length (ft)
Seg1 Base (in)
Seg1 Taper
Seg1 Thickness
(in)
Seg2 Base (in)
Seg2 Taper
Seg2 Thickness
(in)
Arms & Arm Attachments Arm Arm Attachment Pole Name Length (ft) Height
(ft) Align (deg)
Type Length (in)
Width (in)
Thickness (in)
Weight (lbs)
Drag Distance (ft)
A overheight 35.0 19.0 0.0 User - Custom
102.3 36.0 2.3 500.0 1.1 30.0
A overheight 35.0 19.0 90.0 User - Custom
102.3 36.0 2.3 500.0 1.1 30.0
Page 2 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM
VII. Pole Results
Axial (lb) Shear (lb) Calculated Moment (k-ft)
Group I 4,481.03 0.00 43.15
Group II 4,481.03 1,610.98 70.07
Group III 5,542.65 1,144.99 71.49
Pole A
0.00
0.00
0.00
Torsion (k-ft)
Page 3 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM
VIII. Design Summary
Pole Loads Pole
Number Max Axial (lb) Max Shear
(lb) Calculated
Moment (k-ft) Torsion (k-ft)
A 5,542.65 1,610.98 71.49 0.00
Foundation Design Level Ground 2:1 Ground Slope Vertical Bars Ties or Spiral
Pole Number
Diameter (inches)
Soil (feet) Volume
(CY)
Rock (feet)
Volume
(CY)
Soil (feet) Volume
(CY)
Rock (feet)
Volume
(CY)
Size Total Size Pitch
A 36.0 12.5 3.3 6.0 1.6 13.50 3.5 6.00 1.6 #8 13 #4 12.00
Page 4 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM