This is a structural design analysis document for an over-height detection system prepared by the Kentucky Transportation Cabinet, District 5, for Jefferson County in Louisville. The project involves the design and analysis of a 21.50-foot vertical pole (Pole A) with two mast arms extending 35 feet in length at a height of 19 feet, along with associated luminaire arms and custom attachments. The over-height detection equipment attachment measures 102.3 inches in length and 36.0 inches in width with a 2.3-inch thickness and weighs 500 pounds. The analysis was completed on July 22, 2021, using AASHTO 6th Edition (2013) standards with a basic wind speed of 90 mph and an importance factor of 0.87.
The structural design calculations indicate maximum axial loads of 5,542.65 pounds, maximum shear of 1,610.98 pounds, and a calculated moment of 71.49 k-ft for Pole A. The foundation design specifies a 36-inch diameter foundation with 12.5 feet of soil volume (3.3 cubic yards) and 6.0 feet of rock volume (1.6 cubic yards) at level ground with a 2:1 slope condition. Vertical reinforcement consists of #8 bars (13 total) with #4 spiral ties at 12-inch pitch. The analysis was performed by Ted Swansegar of the Kentucky Department of Transportation and is based on program calculations developed by Florence and Hutcheson, Inc.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment B Shock Hazard Sticker.pdf | ||
| Attachment D Handhole.pdf | ||
| Attachment A Annual_Affidavit_Rev__August_2020.pdf | ||
| Final_RFB_605_2200000056_1_SO_FORM.PDF | ||
| Bid Sheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
District: 5
County: jefferson
City: louisville
Permit Num:
PM Name:
Project Num: Author: Swansegar, Ted (ted.swansegar@ky.gov)
File Name: D5 overheightdetection
Code Version: AASHTO 6th Edition (2013)
Created: 7/22/2021 2:00:00 PM
Last Edited: 7/22/2021 2:09:00 PM
I. Project Data Used Custom Attachments Data
Department:
Basic Wind Speed: 90.00
Wind Importance: 0.87
Velocity Conversion: 0.93
Ice Load Pressure: Gust Effect: 1.14
II. Design Assumptions 3.00
III. Mast Arm
Disclaimer: The contents of this program were developed for use by Florence and Hutcheson, Inc. The calculations derived from said program should not be used for any application without examination and verification of its accuracy and suitability for such application by professionally qualified personnel. Florence and Hutcheson, Inc. assumes no liability or responsibility for and makes no representations or warranties as to the applicability or suitability of these results and anyone making use thereof or relying thereon assumes all risk and liability arising from such use or reliance. This program does not constitute a standard, specification or regulation.
Pole A
Page 1 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM
Salsa Design Analysis (Detail Version)
Pole Attachments Pole Name Height (ft) Align (deg) Length (in) Width (in) Thickness (in) Weight
(lbs) Drag
IV. Pole Inputs
Vertical Pole Info Pole Height
(ft) Base (in) Top (in) Thickness
(in) Cd Directionality
Coefficient
A 21.50 18.50 15.49 0.37 0.79 0.95
Mast Arms Length
(ft) Height
(ft) Seg1
Length (ft)
Seg1 Base (in)
Seg1 Taper
Seg1 Thickness
(in)
Seg2 Base (in)
Seg2 Taper
Seg2 Thickness
(in)
35.0000 19.0000 N/A 13.7500 0.1400 0.2500 N/A 0.1400 N/A
35.0000 19.0000 N/A 13.7500 0.1400 0.2500 N/A 0.1400 N/A
Luminaire Arms Length
(ft) Height
(ft) Seg1
Length (ft)
Seg1 Base (in)
Seg1 Taper
Seg1 Thickness
(in)
Seg2 Base (in)
Seg2 Taper
Seg2 Thickness
(in)
Arms & Arm Attachments Arm Arm Attachment Pole Name Length (ft) Height
(ft) Align (deg)
Type Length (in)
Width (in)
Thickness (in)
Weight (lbs)
Drag Distance (ft)
A overheight 35.0 19.0 0.0 User - Custom
102.3 36.0 2.3 500.0 1.1 30.0
A overheight 35.0 19.0 90.0 User - Custom
102.3 36.0 2.3 500.0 1.1 30.0
Page 2 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM
VII. Pole Results
Axial (lb) Shear (lb) Calculated Moment (k-ft)
Group I 4,481.03 0.00 43.15
Group II 4,481.03 1,610.98 70.07
Group III 5,542.65 1,144.99 71.49
Pole A
0.00
0.00
0.00
Torsion (k-ft)
Page 3 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM
VIII. Design Summary
Pole Loads Pole
Number Max Axial (lb) Max Shear
(lb) Calculated
Moment (k-ft) Torsion (k-ft)
A 5,542.65 1,610.98 71.49 0.00
Foundation Design Level Ground 2:1 Ground Slope Vertical Bars Ties or Spiral
Pole Number
Diameter (inches)
Soil (feet) Volume
(CY)
Rock (feet)
Volume
(CY)
Soil (feet) Volume
(CY)
Rock (feet)
Volume
(CY)
Size Total Size Pitch
A 36.0 12.5 3.3 6.0 1.6 13.50 3.5 6.00 1.6 #8 13 #4 12.00
Page 4 of 4AnalysisDetail(RC1)7/22/2021 2:09:46 PM