This document is an attachment containing fire hydrant inspection, maintenance, and testing data for a U.S. Department of Veterans Affairs (VA) facility in Northport, NY.
The attachment documents six fire hydrants (FH11, FH22, FH27, FH36, FH42, and FH18) with inspection forms completed on April 12-13, 2023 by Inspector Edward Springer Jr. Each hydrant entry includes a location map with yellow highlighting, detailed inspection checklists covering visibility/accessibility, barrel condition, outlet conditions, maintenance status, and fire flow test data. Key deficiencies identified include: FH11 with a leaking base requiring work order EW230413-016; FH22 unable to shut down (work order EW230413-015); FH36 unable to close at street valve (work order EW230413-014); and FH18 in need of relocation to a grass area. Fire flow test data classifies hydrants by class (AA, A, B, or C) based on gallons per minute (gpm) capacity, with static pressure, residual pressure, and flow pressure measurements documented. The attachment also includes three fire valve replacement requirements: FV30 serving FH42 adjacent to Building 16, FV83 serving FH36 adjacent to Building 203, and FV84 serving Fire Hydrant 20 adjacent to Building 16. Two post indicator valves (PIV12 at Building 8 and PIV13 near Building 36) are also documented with location maps and utility line identification.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FH11 - Previously known as Hydrant # 10 (Corner of Bldg 61 )
ATTACHMENT C.
Campus Hydrants, PIVs and Hydrant Flow Testing
FH22 - Previously known as Hydrant # 11 (Between Bldg 62, 63)
FH27 - front of generator building 219
FH36 - Previously known as Hydrant # 35 (Rear corner of Bldg 203)
VHANOPKOLMAJ
Stamp
FH 42 - Previously known as Hydrant # 34 (Corner of Bldg 13 & 36)
FH18 - Previously known as Hydrant # 22 (Rear corner of Bldg 11. Relocate this hydrant to grass area file:///S:/Engineering%20Svc%20(138)/PROJECTS/WORKING%20FILES/Active%20Projects/632-22-118%20Evaluate%20Water%20System/300%20Deliverables/340%20Drawings/346%20CD%20dwgs/received_10-15-2025/100%25%20SET_selected_2025-11-13_03-20-06pm/620_632-22-118_COMBINED_20251009.pdf
FV30 – Fire Valve serving Fire Hydrant 42 needs to be replaced. Adjacent to Bldg 16
FV83 – Fire Valve serving Fire Hydrant 36 needs to be replaced. Adjacent to Bldg 203
FV84 – Fire valve serving Fire Hydrant 20 needs to be replace. Adjacent to Bldg 16.
PIV13- Near building 36
PIV12 - Building # 8 Post indicator valve