This is a pricing template and vendor quote form (Attachment C) for RFP 506995 requesting a single line item for a Vertiv APM2 modular three-phase uninterruptible power supply (UPS) system. The requested equipment is a 100 kVA/kW capacity unit configured with 480V-480V three-phase wiring, 60 Hz input to 50 Hz output conversion, and front-to-top airflow design with top fan exhaust and top cable entry. The system includes two monitoring card slots with factory-installed network card (IS-UNITY-DP) for SNMP, Modbus, and BACnet interfacing plus a relay contact interface kit (IS-RELAY) for alarm signal outputs including on-battery, low-battery, on-bypass, UPS fault, and summary alarm functions.
The Vertiv Liebert APM2 specified is a transformer-free, modular UPS offering efficiency up to 97.5% in double conversion mode and up to 99% in eco-mode, with UL and cUL listing to UL Standard 1778 5th Edition and a 65 kAIC interrupting rating. Key features include unity power factor rating, load power factor support from 0.5 leading/lagging to unity, seamless operation to 50°C with auto-derating above 40°C, hot-swappable modules, continuous duty static bypass switch, dry contact inputs/outputs for external device monitoring and control, generator load control capability, automatic retransfer functionality, 9-inch backlit LCD display, waveform capture capability, and casters with leveling feet. The system includes three integrated internal breakers (RIB, BIB, MIB) within the UPS cabinet. The manufacturer is listed as Gwyn Sales Inc., and the part number is 56SA100NNN4NSG6. The template includes blank fields for vendor name, quote number, date, unit price, total price, lead time, and country of origin.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment C- RFP506995
Vendor Name Quote Number Date
Line Item Item Description Part Number Manufacturer Quantity Unit Price Total Price Lead Time Country of Origin
1.0 Vertiv APM2 Vertiv Liebert APM2 Modular Three Phase VAC UPS System consisting and configured as follows: System Input/Output Voltage and Wiring: 480V-480V 3W + G, Configured Capacity Rating kVA,kW: 100kVA/kW, Nameplate Capacity Rating kVA,kW: 100: 100kVA/kW, Redundant N+1 Power Module: Not Included, UPS Native Voltage/Wiring: 480V 3W + G, 60 Hz input to 50 Hz output, Input type: Single Input, Airflow: Front to Top Airflow- includes top fan exhaust, Cable Entry: Top.
Wiring Cabinet or Attached Ancillary required for bottom entry, Two Monitoring Card Slots: IS-UNITY-DP / IS-RELAY (IS-UNITY- DP: network card factory installed for SNMP, Modbus, BACnet interfacing to building Management Systems and environmental sensor support; IS-RELAY: Intellislot Relay Contact Interface Kit; P/N: IS-RELAY; Provides relay contact signals for "On Battery", "Low Battery", "On Bypass", "UPS Fault", "Summary Alarm"). Vertiv Liebert APM2 Standard Features Include: Transformer-Free Modular and Scalable Architecture - Efficiency up to 97.5% in double conversion mode, UL and cUL Listed to UL Standard 1778 5th Edition, IP 20 rated enclosure, 65kAIC Rating - Provides interrupting rating and labeling of 65kA, Unity Power Factor Rating - Delivers more usable power per kVA, Load Power Factor Support - Supports loads 0.5 leading and lagging to unity without de-rating, Energy Optimization Mode (Eco-Mode) up to 99% efficiency, Dynamic online mode up to 98.8% efficiency, Flexible energy storage (battery) technologies, High capacity rated battery charger, Latest generation three-level IGBT topology with Silicon Carbide converters, hot swappable HMI, bypass, power, and internal battery modules allow service while under operation to protect critical load from bypass, Seamless operation up to 50C° with auto-derating above 40C°, Continuous Duty Static Bypass Switch, Input Contacts - Dry contacts are available for functions including monitoring external breakers, on-generator signal, and other functions, Output Contacts - Dry contacts are available for functions including a permissive signal to maintenance bypass SKRU, to trip external breakers, and other functions, Generator Load Control - Suppresses battery charging reducing power demand by an external signal. Shifts unit from Eco Mode to double conversion (if applicable), and synchronizes the inverter output with the bypass, Automatic retransfer - Provides return to inverter power after an overload, DSP based controls - Provides digital control of power conversion and system operation, Large intuitive 9” Backlit LCD HMI display - Monitors power conversion, UPS operation and utility conditions including maintenance bypass when provided, Waveform capture on UPS input power for troubleshooting and analysis, Temperature-Compensated Charging/Battery Load Test, Front only service access, Local and Remote Emergency Power Off (EPO), Casters and leveling feet, Suitable for against the wall with standard top fan airflow.Internal Input and Output Breakers The solution includes the following features: Breaker Configuration: Three (3) breakers- (RIB, BIB, MIB) Cabinet Location: UPS Cabinet Integrated, Cabinet Size (Width): UPS Cabinet Integrated or domestic equivalent
56SA100NNN4NSG6 Gwyn Sales Inc. 1