Attachment C- 656-22-341__25_19_Drawings_Rev A_20260212- 3.26.pdf

PDF 7 MB Posted

Attached to
656-22-341 Conduct Substation Upgrade Federal contract opportunity
Solicitation number
36C26326B0024
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23

About this file

This document is a set of construction drawings for an electrical substation upgrade project at the St. Cloud VA Medical Center (VAHCS) in St. Cloud, Minnesota, identified as VAMC Project #656-22-341. The drawings were prepared by Valhalla Engineering Group, LLC and issued on January 18, 2024.

The project involves the conduct of electrical substation upgrades, encompassing demolition and replacement of multiple pad-mounted transformers across the facility. Key work includes isolating and removing existing transformers ranging from 30 kVA to 750 kVA at 13.8 kV primary with secondary voltages of 208/120V, 240/120V, and 480/277V, then installing replacement units with comparable or upgraded specifications. The construction documents include site plans divided into seven sections (A through G), electrical symbols and abbreviations, demolition site plans, new installation site plans, substation power and one-line diagrams, and detailed specifications for transformer installations. Critical requirements include coordination with the VHA Contracting Officer Representative (COR) for outages, retention of existing conductors and connectors for reconnection to new equipment, protection of existing pads where indicated, installation of anti-ram rated vehicle bollards at specified locations, and compliance with the 2023 National Electrical Code. The substation upgrades involve replacement of a 5,000 kVA primary substation transformer with a 6,000 kVA unit, with provisions for maintaining loop continuity during demolition and construction phases. An alternate is included that deducts all work associated with Transformer TF-50, suggesting this as an optional scope modification.

View the file

Other files for this federal contract opportunity

Other files attached to 656-22-341 Conduct Substation Upgrade, newest first.
File Type Posted
36C26326B0024_1 4.6.2026.pdf PDF
Attachment B- Wage Determination.pdf PDF
Attachment F - Questions Request Form - 1 page.pdf PDF
Attachment A- Final SOW Conduct Substation Upgrade 3.26.docx DOCX document
Attachment D- 656-22-341__25_19_Specs_RA 3.26.pdf PDF
Attachment E - Limitations on Subcontracting - 2 Pages.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VESTIBULE

DN

DN

DN

FD

DN

FB

FB

FB

FB

FB

FB

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDING 51

C

16"

20"

12"

3"

8"

C

1B

CORRIDOR LINK

1A

SIGNSIGN

TP TP

.3

.33

SN

T

SHEET INDEX

ST CLOUD HEALTH CARE SYSTEM

ST CLOUD, MN

VAMC PROJECT #: 656-22-341

CONDUCT ELECTRICAL SUBSTATION UPGRADE

Plan North

Plan North

11651

11128

1A

AREA OF WORKVICINITY MAP

BIO

GI001

N/A

MMMRA1/18/2024

COVER SHEET

VEG 23.09

656-22-341

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

ARCHITECT/ENGINEERS:

STAMP:

CONSTRUCTION

DOCUMENTS

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

8' 4'

1/8

1'

8' 4'

2'

1/4

1'

8'

4'

3/1 6"

1'

6' 4'

2'

3/8

1' 4'

2' 1'

1/2

1'

3' 2'

1'

3/4

1' 2'

1' 6"

1"

1'

1'- 6"

1' 6"

1 1

/2"

1' 9"

6" 3"

3"

1'

1"

0'

1"

1"

1"

1"

1/3 2"

1'

8'

1/1 6"

1'

5'

3/3 2"

1'

7'- 6"

5'

1"

5'

Drawing Title

APPROVED: ASSISTANT CHIEF ENGINEER

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: CHIEF OF POLICE

APPROVED: DIRECTOR FMS DATE: APPROVED: SAFETY MANAGER DATE:

APPROVED: GEMS COORDINATOR

APPROVED: PROJECTS SECTION MANAGER

APPROVED: SERVICE LINE DIRECTOR

DATE:

DATE:

DATE: APPROVED: INFECTION CONTROL NURSE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE:

APPROVED: ASSOCIATE HEALTH CARE SYSTEM DIRECTOR

DATE:

DATE:

DATE:APPROVED: EMS MANAGER

APPROVED: OIT MANAGER DATE:

DATE:

DATE:

APPROVED: PROJECT COR DATE:

APPROVED: M/O MANAGERAPPROVED: CHIEF OF STAFF

APPROVED: NURSE EXECUTIVE

DATE:

DATE:

SHEET LIST TABLE

SHEET NUMBER SHEET TITLE

GI001 COVER SHEET

GI002 SITE PLAN

E-001 ELECTRICAL SYMBOLS, NOTES, AND ABBREVIATIONS

ED101 DEMO SITE PLAN SECTION A

ED102 DEMO SITE PLAN SECTION B

ED103 DEMO SITE PLAN SECTION C

ED104 DEMO SITE PLAN SECTION D

ED105 DEMO SITE PLAN SECTION E

ED106 DEMO SITE PLAN SECTION F

ED107 DEMO SITE PLAN SECTION G

ES101 SITE PLAN SECTION A

ES102 SITE PLAN SECTION B

ES103 SITE PLAN SECTION C

ES104 SITE PLAN SECTION D

ES105 SITE PLAN SECTION E

ES106 SITE PLAN SECTION F

ES107 SITE PLAN SECTION G

EP101 SUBSTATION POWER PLAN

EP601 SUBSTATION ONE-LINE DIAGRAM

EP602 POWER ONE-LINE DIAGRAM

EK501 ELECTRICAL DETAILS

EK502 TRANSFORMER SCHEDULE

SUBSTATION

Pl an

N or th Tr ue N or th

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/128" = 1'-0" 32' 64' 128' 256' 512'0

SITE PLAN1

GI002

N/A

MMMRA1/18/2024

SITE PLAN

X

SECTION A

SECTION BSECTION CSECTION E

SECTION F SECTION D

SECTION G

ED101

EP101

ED103

EP103

ED104

EP104

ED105

EP105

ED106

EP106

ED107

EP107

ED102

EP102

E-001

N/A

MMMRA1/18/2024

ELECTRICAL SYMBOLS

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

A REVISION A

REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

2.12.2026

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026

R

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

REQ REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

S

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SES SERVICE ENTRANCE SECTION

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

T

TEL TELEPHONE

TM THERMAL MAGNETIC

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

U

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V

V VOLT

VA VOLT-AMPERE

VAR VOLT-AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VOLT VOLTAGE

W

W WATT

WH WATER HEATER

WP WEATHERPROOF

X

XFER TRANSFER

XFMR TRANSFORMER

J

J-BOX JUNCTION BOX

K

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAH KILOVOLT-AMPERE PER HOUR

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

L

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

M

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MEP MECHANICAL ELECTRICAL & PLUMBING

MFR MANUFACTURER

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

N

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

O

OC ON CENTER

OCP OVERCURRENT PROTECTION

OD OUTSIDE DIAMETER

OL OVERLOAD

P

P POLE

PA PUBLIC ADDRESS

PB PULLBOX OR PANEL BOARD

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

D

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

E

EC ELECTRICAL CONTRACTOR

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EST ESTIMATED

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXST EXISTING

F

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIXT FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

G OR GND ELECTRICAL GROUND

GC GENERAL CONTRACTOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

H

HD HEAVY DUTY

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

I

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH

AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IOM INSTALLATION AND OPERATION MANUAL

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

1P SINGLE POLE

1PH SINGLE PHASE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3P THREE POLE

3PH THREE PHASE

4/C FOUR-CONDUCTOR

4W FOUR WIRE

A

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT / ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT OR ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY

CONTROL, OR AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE-HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

B

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BYPASS

C

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA OR CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED / CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED / OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COAX COAX CABLE

COINC COINCIDENT

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONN CONNECTED

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

ELECTRICAL ABBREVIATIONS

SWITCH, NORMALLY CLOSED FLOAT

SWITCH, NORMALLY CLOSED FOOT OPERATED

SWITCH, NORMALLY CLOSED LIMIT

SWITCH, NORMALLY CLOSED TEMPERATURE

ACTIVATED

SWITCH, NORMALLY OPEN FLOAT

SWITCH, NORMALLY OPEN TEMPERATURE ACTIVATED

DELTA CONNECTION

TRANSFORMER

GROUNDED WYE CONNECTION

PULL BOX

PRESSURE SWITCH-CLOSE ON INCREASE

PRESSURE SWITCH-OPEN ON INCREASE

MANHOLE

JUNCTION BOX

TRANSFORMER AND WORKING CLEARANCE, PLAN

EARTH GROUND

BRANCH CIRCUIT HOMERUN. ONE SEPARATE GREEN

GROUNDING CONDUCTOR SHALL BE PROVIDED FOR

EACH HOMERUN; NOT SHOWN

RIGID CONDUIT LINE

SUBSTATION

DIRECT BURIAL CABLE

POWER DUCT

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

SWITCH, NORMALLY OPEN TIME DELAY

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

MEDIUM-VOLTAGE OIL CIRCUIT BREAKER

MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

FUSIBLE LINK

GENERATOR, POWER

BATTERY

CAPACITOR

RELAY; LETTER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE

51 = AC-TIME OVERCURRENT

67 = AC-DIRECTIONAL OVERCURRENT

86 = LOCK OUT

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED, VAV

POTHEAD

STRESS CONE

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

ELECTRICAL SYMBOLS - POWER PLAN

RC

DB

P

A

V

W

WH

T

S

HVS

LVS

P T

J

PB

P

A. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE 2023 NATIONAL

ELECTRICAL CODE AND THE REQUIREMENTS OF THE VHA.

B. COORDINATE ALL OUTAGES WITH VHA COR PER SPECIFICATION 00 01 10 PRIOR TO

WORK BEING DONE.

OR

NEW - EXISTING AND DEMO LINE TYPES

NEW LINE TYPE

EXISTING LINE TYPE

DEMO HATCH

ELECTRICAL SYMBOLS ELECTRICAL GENERAL NOTES

26-SF 3

H4

H7 A

DETAIL REFERENCE

DRAWING NUMBER WHERE SHOWN

SECTION REFERENCE

EQUIPMENT TAG

DRAWING NUMBER WHERE DRAWN

CONNECT TO EXISTING*

LIMIT OF DEMOLITION*

GENERAL SYMBOLS AND TAGS

DEMOLISHED EQUIPMENT (SHAPE VARIES,

REF: SYMBOLS, TAGS, & NOTES)

(E) EXISTING COMPONENT

(X) DEMOLISHED COMPONENT

## GENERAL EQUIPMENT FURNISHED BY

OTHERS, COORDINATE WITH ASSOCIATED

TRADES FOR POWER AND/OR TELECOM

CONNECTIONS PER MFR INSTRUCTIONS

NEW EQUIPMENT (SHAPE VARIES, REF:

SYMBOLS, TAGS, & NOTES. SCHEDULED

ITEMS ARE NEW UNO)

P1

3 APPROXIMATE VIEWING DIRECTION

PHOTO OR AXONOMETRIC VIEW NUMBER

DRAWING NUMBER WHERE SHOWN

*SINGLE SYMBOL MAY APPLY

TO BANKS OF SIMILAR CONDUIT

KEYNOTE00

EXISTING UNDERGROUND ELECTRICAL

A. PORTIONS OF THE ELECTRICAL DISTRIBUTION REQUIRING OUTAGE SHALL BE ISOLATED

FROM THE REST OF THE SYSTEM PRIOR TO WORK. COORDINATE OUTAGES WITH THE

VA AND FOLLOW VA SEQUENCE DIAGRAMS FOR SYSTEM ISOLATION. FOLLOW ALL

LOCK-OUT TAG-OUT PROCEDURES INDICATED WITHIN THE SPECIFICATIONS AND AS

DIRECTED BY THE SITE.

B. CONTRACTOR TO VERIFY EXISTING PRIMARY AND SECONDARY EXISTING

TRANSFORMER CONNECTOR TYPES. REPLACEMENT EQUIPMENT SHALL BE

CONFIGURED WITH THE SAME CONNECTORS AS THE PREVIOUS INSTALLATION.

DEMOLITION GENERAL NOTES

A. A SURVEY FOR EXISTING UNDERGROUND UTILITIES WHEREVER UNDERGROUND WORK

IS TO BE PERFORMED. CARE SHOULD BE TAKEN NOT TO DAMAGE EXISTING

UNDERGROUND INSTALLATIONS. UTILIZE EXCAVATION METHODS APPROPRIATE FOR

THE JOB WHICH CAN PREVENT INADVERTENT DAMAGE, SUCH AS HYDROVAC

EXCAVATION, FOR EXISTING UNDERGROUND UTILITIES.

POWER GENERAL NOTES

A

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION A1

ED101

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION A

1. ISOLATE AND REMOVE EXISTING 112.5KVA, 13800-208/120V RADIAL,

PAD MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND

RETAIN CONDUCTORS AND CONNECTORS FOR RECONNECT.

RETAIN EXISTING PAD.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL

TEMPORARY OR PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES

REQUIRED FOR COMPLETE TRANSFORMER INSTALLATION AND

OPERATION THAT ARE DAMAGED DURING DEMOLITION SHALL BE

REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE VHA.

X

TF-57

S-18

109 57

T 1

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION B1

ED102

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION B

1. ISOLATE AND REMOVE 300KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN

CONDUCTORS AND CONNECTORS FOR RECONNECT. RETAIN

EXISTING PAD.

2. ISOLATE AND REMOVE 75KVA, 13800-240/120V RADIAL, PAD MOUNT

TRANSFORMER. DISCONNECT TRANSFORMER AND PROTECT AND

RETAIN CONDUCTORS AND CONNECTORS FOR RECONNECT.

DEMOLISH EXISTING PAD/BOX.

3. ISOLATE AND REMOVE 30KVA, 13800-208/120V RADIAL, PAD MOUNT

TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN

CONDUCTORS AND CONNECTORS FOR RECONNECT. RETAIN

EXISTING PAD.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL

TEMPORARY OR PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES

REQUIRED FOR COMPLETE TRANSFORMER INSTALLATION AND

OPERATION THAT ARE DAMAGED DURING DEMOLITION SHALL BE

REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE VHA.

X

TF-10

TF-94

TF-111

TF-115

S-1

S-2

S-3

S-3A

T

T

T

TF-9

T

T

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION C1

ED103

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION C

1. ISOLATE AND REMOVE 750KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN

CONDUCTORS AND CONNECTORS FOR RECONNECT. RETAIN

EXISTING PAD.

2. ISOLATE AND REMOVE 150KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND

PROTECT AND RETAIN CONDUCTORS AND CONNECTORS FOR

RECONNECT. DEMOLISH EXISTING PAD/BOX.

3. ISOLATE AND REMOVE 225KVA, 13800-480/277V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN

CONDUCTORS AND CONNECTORS FOR RECONNECT. RETAIN

EXISTING PAD.

4. ISOLATE AND REMOVE 500KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN

CONDUCTORS AND CONNECTORS FOR RECONNECT. RETAIN

EXISTING PAD.

5. ISOLATE AND REMOVE 75KVA, 13800-208/120V RADIAL, PAD MOUNT

TRANSFORMER. DISCONNECT TRANSFORMER AND PROTECT AND

RETAIN CONDUCTORS AND CONNECTORS FOR RECONNECT.

DEMOLISH EXISTING PAD/BOX.

6. ISOLATE AND REMOVE 225KVA, 13800-480/277V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND

PROTECT AND RETAIN CONDUCTORS AND CONNECTORS FOR

RECONNECT. DEMOLISH EXISTING PAD/BOX.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL

TEMPORARY OR PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES

REQUIRED FOR COMPLETE TRANSFORMER INSTALLATION AND

OPERATION THAT ARE DAMAGED DURING DEMOLITION SHALL BE

REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE VHA.

X

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

A

A

A REVISION A 2.12.2026

TF-1

TF-1A

TF-1B

TF-1C

TF-2A

TF-3

TF-4A

TF-5

TF-7

TF-8

TF-28

TF-59

TF-95

TF-118

TF-4B

S-5 S-6

S-7

S-8

S-14

S-15

S-15A

S-16 S-17

37 69

1A

I.T.

TT

T

T

TF-88

T T

T

T T

T

T

T

T

TF-2

TF-4

T

T

T

T

T

2 3

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION D1

ED104

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION D

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. SHEET INDICATES EXISTING TRANSFORMER AND LOOP LOCATION.

NO WORK ON THIS SHEET.

TF-PG-1

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION E1

ED105

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION E

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL

TEMPORARY OR PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES

REQUIRED FOR COMPLETE TRANSFORMER INSTALLATION AND

OPERATION THAT ARE DAMAGED DURING DEMOLITION SHALL BE

REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE VHA.

1. ISOLATE AND REMOVE 500KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND

PROTECT AND RETAIN CONDUCTORS AND CONNECTORS FOR

RECONNECT. DEMOLISH EXISTING PAD/BOX.

X

TF-29

TF-48A

TF-48

TF-49

S-11

S-12

S-12A

S-13

T101

T

TF-88

T

T

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION F1

ED106

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION F

1. ISOLATE AND REMOVE 500KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN

CONDUCTORS AND CONNECTORS FOR RECONNECT. RETAIN

EXISTING PAD.

2. ISOLATE AND REMOVE 500KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. DISCONNECT TRANSFORMER AND

PROTECT AND RETAIN CONDUCTORS AND CONNECTORS FOR

RECONNECT. DEMOLISH EXISTING PAD/BOX.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL

TEMPORARY OR PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES

REQUIRED FOR COMPLETE TRANSFORMER INSTALLATION AND

OPERATION THAT ARE DAMAGED DURING DEMOLITION SHALL BE

REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE VHA.

X

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026

A

REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

A

A REVISION A 2.12.2026

TF-50

TF-51A

TF-51B

TF-116

S-9

S-10

S-11

TF-UNKNOWN

T

T

T

T

T1

Deduct: Alternate 1 - Base bid less all work associated with Transformer TF-50

VHASTCSchraC2 Rectangle

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

DEMO SITE PLAN SECTION G1

ED107

N/A

MMMRA1/18/2024

DEMO SITE PLAN SECTION G

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. SHEET INDICATES EXISTING TRANSFORMER AND LOOP LOCATION.

NO WORK ON THIS SHEET.

X

TF-96

TF-114

S-9A

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION A1

ES101

N/A

MMMRA1/18/2024

SITE PLAN SECTION A

1. PROVIDE REPLACEMENT 112.5KVA, 13800-208/120V, RADIAL, PAD-MOUNT,

TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING PAD. RECONNECT

EXISTING CONNECTORS RETAINED DURING DEMOLITION TO NEW

TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR ADDITIONAL

INFORMATION.

2. PROVIDE PASSIVE, ANTI-RAM RATED VEHICLE BOLLARDS. DETERMINE THE

LOCATION OF EXISTING SITE UTILITIES PRIOR TO EXCAVATING OR DRIVING OF

BOLLARD COMPONENTS. BOLLARDS LOCATED WITHIN THE WORKING SPACE OF

ELECTRICAL EQUIPMENT SHALL BE REMOVEABLE. PLACE BOLLARDS A

MINIMUM OF 3 FEET AWAY FROM TRANSFORMER PAD. AVOID PLACING

BOLLARDS WITHIN EXISTING WALKWAYS. SPACING BETWEEN BOLLARDS NOT

TO EXCEED 5 FEET. COORDINATE FINAL PLACEMENT OF BOLLARDS WITH COR

IN THE FIELD. SEE SHEET EK501 FOR ADDITIONAL BOLLARD INFORMATION.

EQUIVALENT ANTI-RAM RATED SUBSTITUTIONS MAY BE ACCEPTED.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL TEMPORARY OR

PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES REQUIRED FOR

COMPLETE TRANSFORMER INSTALLATION AND OPERATION THAT ARE

DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED AT NO

ADDITIONAL COST TO THE VHA.

D. TRANSFORMER SYMBOL IS DIAGRAMMATIC AND NOT INDICATIVE OF ACTUAL

SIZE.

E. DO NOT CREATE ANY SPLICES ON OR OTHERWISE MODIFY EXISTING MEDIUM

VOLTAGE (MV) CABLES. EQUIPMENT SHALL BE LOCATED AND PLACED IN THE

FIELD FOR REUSE OF MV CABLES OF EXISTING LENGTHS. MODIFICATION OF

480V LINE-TO-LINE AND LOWER SYSTEMS ARE PERMITTED.

X

TF-57

S-18

109 57

T 1

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION B1

ES102

N/A

MMMRA1/18/2024

SITE PLAN SECTION B

1. PROVIDE REPLACEMENT 300KVA, 13800-208/120V, RADIAL, PAD-MOUNT,

TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

2. PROVIDE REPLACEMENT 75KVA, 13800-240/120V, RADIAL, PAD-MOUNT,

TRANSFORMER. PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD

AS INDICATED ON THE DRAWINGS AND PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS. INTERCEPT AND EXTEND SECONDARY

CONDUCTORS INTO SECONDARY OPENING / COMPARTMENT AS REQUIRED

FOR NEW PAD CONFIGURATION. MOUNT TRANSFORMER TO NEW PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

3. PROVIDE REPLACEMENT 30KVA, 13800-208/120V, RADIAL, PAD-MOUNT,

TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

4. PROVIDE PASSIVE, ANTI-RAM RATED VEHICLE BOLLARDS. DETERMINE THE

LOCATION OF EXISTING SITE UTILITIES PRIOR TO EXCAVATING OR DRIVING

OF BOLLARD COMPONENTS. BOLLARDS LOCATED WITHIN THE WORKING

SPACE OF ELECTRICAL EQUIPMENT SHALL BE REMOVEABLE. PLACE

BOLLARDS A MINIMUM OF 3 FEET AWAY FROM TRANSFORMER PAD. AVOID

PLACING BOLLARDS WITHIN EXISTING WALKWAYS. SPACING BETWEEN

BOLLARDS NOT TO EXCEED 5 FEET. COORDINATE FINAL PLACEMENT OF

BOLLARDS WITH COR IN THE FIELD. SEE SHEET EK501 FOR ADDITIONAL

BOLLARD INFORMATION. EQUIVALENT ANTI-RAM RATED SUBSTITUTIONS

MAY BE ACCEPTED.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL TEMPORARY OR

PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES REQUIRED FOR

COMPLETE TRANSFORMER INSTALLATION AND OPERATION THAT ARE

DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED AT NO

ADDITIONAL COST TO THE VHA.

D. TRANSFORMER SYMBOL IS DIAGRAMMATIC AND NOT INDICATIVE OF ACTUAL

SIZE.

E. DO NOT CREATE ANY SPLICES ON OR OTHERWISE MODIFY EXISTING MEDIUM

VOLTAGE (MV) CABLES. EQUIPMENT SHALL BE LOCATED AND PLACED IN THE

FIELD FOR REUSE OF MV CABLES OF EXISTING LENGTHS. MODIFICATION OF

480V LINE-TO-LINE AND LOWER SYSTEMS ARE PERMITTED.

X

TF-10

TF-94

TF-111

TF-115

S-1

S-2

S-3

S-3A

T

T

T

TF-9

T

T

EP101

an

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION C1

ES103

N/A

MMMRA1/18/2024

SITE PLAN SECTION C

1. PROVIDE REPLACEMENT 750KVA, 13800-208/120V, RADIAL, PAD-MOUNT,

TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

2. PROVIDE REPLACEMENT 150KVA, 13800-208/120V RADIAL, PAD MOUNT

TRANSFORMER. PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD

AS INDICATED ON THE DRAWINGS AND PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS. INTERCEPT AND EXTEND SECONDARY

CONDUCTORS INTO SECONDARY OPENING / COMPARTMENT AS REQUIRED

FOR NEW PAD CONFIGURATION. MOUNT TRANSFORMER TO NEW PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

3. PROVIDE REPLACEMENT 225KVA, 13800-480/277V RADIAL, PAD MOUNT

TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

4. PROVIDE REPLACEMENT 500KVA, 13800-208/120V RADIAL, PAD MOUNT

TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

5. PROVIDE REPLACEMENT 75KVA, 13800-208/120V RADIAL, PAD MOUNT

TRANSFORMER. PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD

AS INDICATED ON THE DRAWINGS AND PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS. INTERCEPT AND EXTEND SECONDARY

CONDUCTORS INTO SECONDARY OPENING / COMPARTMENT AS REQUIRED

FOR NEW PAD CONFIGURATION. MOUNT TRANSFORMER TO NEW PAD.

RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

6. PROVIDE NEW 300KVA, 13800-480/277V RADIAL, PAD MOUNT

TRANSFORMER. PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD

AS INDICATED ON THE DRAWINGS AND PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS. INTERCEPT AND EXTEND CONDUCTORS

INTO OPENING / COMPARTMENT AS REQUIRED FOR NEW PAD

CONFIGURATION. MOUNT TRANSFORMER TO NEW PAD. RECONNECT

EXISTING CONNECTORS RETAINED DURING DEMOLITION TO NEW

TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

7. PROVIDE PASSIVE, ANTI-RAM RATED VEHICLE BOLLARDS. DETERMINE THE

LOCATION OF EXISTING SITE UTILITIES PRIOR TO EXCAVATING OR DRIVING

OF BOLLARD COMPONENTS. BOLLARDS LOCATED WITHIN THE WORKING

SPACE OF ELECTRICAL EQUIPMENT SHALL BE REMOVEABLE. PLACE

BOLLARDS A MINIMUM OF 3 FEET AWAY FROM TRANSFORMER PAD. AVOID

PLACING BOLLARDS WITHIN EXISTING WALKWAYS. SPACING BETWEEN

BOLLARDS NOT TO EXCEED 5 FEET. COORDINATE FINAL PLACEMENT OF

BOLLARDS WITH COR IN THE FIELD. SEE SHEET EK501 FOR ADDITIONAL

BOLLARD INFORMATION. EQUIVALENT ANTI-RAM RATED SUBSTITUTIONS

MAY BE ACCEPTED.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL TEMPORARY OR

PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES REQUIRED FOR

COMPLETE TRANSFORMER INSTALLATION AND OPERATION THAT ARE

DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED AT NO

ADDITIONAL COST TO THE VHA.

D. TRANSFORMER SYMBOL IS DIAGRAMMATIC AND NOT INDICATIVE OF ACTUAL

SIZE.

E. DO NOT CREATE ANY SPLICES ON OR OTHERWISE MODIFY EXISTING MEDIUM

VOLTAGE (MV) CABLES. EQUIPMENT SHALL BE LOCATED AND PLACED IN THE

FIELD FOR REUSE OF MV CABLES OF EXISTING LENGTHS. MODIFICATION OF

480V LINE-TO-LINE AND LOWER SYSTEMS ARE PERMITTED.

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

A

A

A REVISION A 2.12.2026

TF-1

TF-1A

TF-1B

TF-1C

TF-2A

TF-3

TF-4A

TF-5

TF-7

TF-8

TF-28

TF-59

TF-95

TF-118

TF-4B

S-5 S-6

S-7

S-8

S-14

S-15

S-15A

S-16 S-17

37 69

1A

I.T.

TT

T

T

TF-88

T T

T

T T

T

T

T

T

TF-2

TF-4

T

T

T

T

T 5

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION D1

ES104

N/A

MMMRA1/18/2024

SITE PLAN SECTION D

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. SHEET INDICATES EXISTING TRANSFORMER AND LOOP LOCATION.

NO WORK ON THIS SHEET.

TF-PG-1

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION E1

ES105

N/A

MMMRA1/18/2024

SITE PLAN SECTION E

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL TEMPORARY OR

PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES REQUIRED FOR

COMPLETE TRANSFORMER INSTALLATION AND OPERATION THAT ARE

DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED AT NO

ADDITIONAL COST TO THE VHA.

D. TRANSFORMER SYMBOL IS DIAGRAMMATIC AND NOT INDICATIVE OF ACTUAL

SIZE.

E. DO NOT CREATE ANY SPLICES ON OR OTHERWISE MODIFY EXISTING MEDIUM

VOLTAGE (MV) CABLES. EQUIPMENT SHALL BE LOCATED AND PLACED IN THE

FIELD FOR REUSE OF MV CABLES OF EXISTING LENGTHS. MODIFICATION OF

480V LINE-TO-LINE AND LOWER SYSTEMS ARE PERMITTED.

1. PROVIDE REPLACEMENT 500KVA, 13800-208/120V, RADIAL, PAD MOUNT

TRANSFORMER. PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD AS

INDICATED ON THE DRAWINGS AND PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. INTERCEPT AND EXTEND SECONDARY CONDUCTORS INTO

SECONDARY OPENING / COMPARTMENT AS REQUIRED FOR NEW PAD

CONFIGURATION. MOUNT TRANSFORMER TO NEW PAD. RECONNECT EXISTING

CONNECTORS RETAINED DURING DEMOLITION TO NEW TRANSFORMER

BUSHINGS. REFER TO DETAIL SHEET EK501 FOR ADDITIONAL INFORMATION.

X

TF-29

TF-48A

TF-48

TF-49

S-11

S-12

S-12A

S-13

T101

T

TF-88

T

T

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION F1

ES106

N/A

MMMRA1/18/2024

SITE PLAN SECTION F

1. PROVIDE REPLACEMENT 500KVA, 13800-208/120V RADIAL, PAD

MOUNT TRANSFORMER. MOUNT NEW TRANSFORMER TO EXISTING

PAD. RECONNECT EXISTING CONNECTORS RETAINED DURING

DEMOLITION TO NEW TRANSFORMER BUSHINGS. REFER TO

DETAIL SHEET EK501 FOR ADDITIONAL INFORMATION.

2. PROVIDE NEW 750KVA, 13800-208/120V RADIAL, PAD MOUNT

TRANSFORMER. PROVIDE AND ORIENT NEW PRECAST

TRANSFORMER PAD AS INDICATED ON THE DRAWINGS AND PER

THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. INTERCEPT

AND EXTEND PRIMARY CONDUCTORS INTO OPENING /

COMPARTMENT AS REQUIRED FOR NEW PAD CONFIGURATION.

MOUNT TRANSFORMER TO NEW PAD. RECONNECT EXISTING

CONNECTORS RETAINED DURING DEMOLITION TO NEW

TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL

TEMPORARY OR PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES

REQUIRED FOR COMPLETE TRANSFORMER INSTALLATION AND

OPERATION THAT ARE DAMAGED DURING DEMOLITION SHALL BE

REPAIRED OR REPLACED AT NO ADDITIONAL COST TO THE VHA.

D. TRANSFORMER SYMBOL IS DIAGRAMMATIC AND NOT INDICATIVE

OF ACTUAL SIZE.

E. DO NOT CREATE ANY SPLICES ON OR OTHERWISE MODIFY

EXISTING MEDIUM VOLTAGE (MV) CABLES. EQUIPMENT SHALL BE

LOCATED AND PLACED IN THE FIELD FOR REUSE OF MV CABLES

OF EXISTING LENGTHS. MODIFICATION OF 480V LINE-TO-LINE AND

LOWER SYSTEMS ARE PERMITTED.

X

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026

A

REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

A

A REVISION A 2.12.2026

TF-50

TF-51A

TF-51B

TF-116

S-9

S-10

S-11

TF-UNKNOWN

T

T

T

T

T1

Deduct: Alternate 1 - Base bid less all work associated with Transformer TF-50

N or th Tr ue N or th

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

1/32" = 1'-0" 8' 16' 32' 64' 128'0

SITE PLAN SECTION G1

ES107

N/A

MMMRA1/18/2024

SITE PLAN SECTION G

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

B. SHEET INDICATES EXISTING TRANSFORMER AND LOOP LOCATION.

NO WORK ON THIS SHEET.

X

TF-96

TF-114

S-9A

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

EP101

N/A

MMMRA1/18/2024

SUBSTATION POWER PLAN

NO SCALE

PRIMARY SUBSTATION ELEVATION PLAN3

NO SCALE

ALTERNATE SUBSTATION ELEVATION PLAN2

2' 4' 8' 16' 32'

1/8" = 1'-0"

PRIMARY SUBSTATION POWER PLAN1

EP101

EP101

No rth

A. REFER TO EP602 FOR MORE INFORMATION.

X

SUBSTATION

PREFERED

UTILITY

BREAKER

N/C

ALTERNATE

UTILITY

BREAKER

N/O

CONTROL

PANEL

T1

PREFERED

UTILITY

BREAKER

N/C

ALTERNATE

UTILITY

BREAKER

N/O

CONTROL

PANEL

T2

EX

IS

TI

NG

R

OA

D

SUBSTATION

SG1 T1 SG3

SG2 T2 SG4

SOURCE TRANSFER SWITCH #2 (ST2)

XCEL PRIMARY FEEDER (BY UTILITY)

XCEL ALTERNATE FEEDER (BY UTILITY)

CHAIN LINK FENCE

SITE LIGHT POLES, TYP

SOURCE TRANSFER SWITCH #1 (ST1)

SUBSTATION CONCRETE PAD

TO SWITCH 1

TO SWITCH 18

7'-0" 7'-0" 7'-0"

7'-0" 7'-0" 7'-0"

CHAIN LINK GATE

NO SCALE

SUBSTATION NEW SUBSTATION ONE-LINE DIAGRAM2

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

EP601

N/A

MMMRA1/18/2024

SUBSTATION ONE-LINE DIAGRAM

NO SCALE

SUBSTATION DEMO SUBSTATION ONE-LINE DIAGRAM1

1. ISOLATE AND REMOVE EXISTING 5,000KVA, 34500-13800V, PAD MOUNT

TRANSFORMER. DISCONNECT TRANSFORMER AND RETAIN CONDUCTORS AND

CONNECTORS FOR RECONNECT. RETAIN EXISTING PAD.

2. PROVIDE REPLACEMENT 6,000KVA, 34500-13800V, PAD-MOUNT, TRANSFORMER.

MOUNT NEW TRANSFORMER TO EXISTING PAD. RECONNECT EXISTING

CONNECTORS RETAINED DURING DEMOLITION TO NEW TRANSFORMER

BUSHINGS.

3. THE Y-Y NEUTRALS ARE CONNECTED AND SHARE ONE GROUND.

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL TEMPORARY OR

PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES REQUIRED FOR

COMPLETE TRANSFORMER INSTALLATION AND OPERATION THAT ARE

DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED AT NO

ADDITIONAL COST TO THE VHA.

D. PHASE DEMOLITION OF THE TRANSFORMERS SUCH THAT ONE SUBSTATION

TRANSFORMER ALWAYS REMAINS IN SERVICE DURING THE DURATION OF

CONSTRUCTION.

E. RETAIN ALL GROUNDING CONDUCTORS, EXCEPT AS EXPLICITLY INDICATED ON

THE DRAWINGS, FOR RECONNECTION TO GROUNDING TERMINALS ON THE NEW

EQUIPMENT AS INDICATED BY THE MANUFACTURER.

A REVISION A

REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

2.12.2026

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026

A

ALTERNATE

FEEDER

T1

6000KVA

>6.5%Z 34500-13800V

T2

6000KVA

>6.5%Z 34500-13800V

PRIMARY /

PREFERRED

FEEDER

SG1

MAIN

SG2

MAIN 51/5051/50

CAPACITOR

BANK FILTER

SG1-ST2

MAIN

51/50 51/50

CAPACITOR

BANK FILTER

SG2-ST1

MAIN

51/5051/50

SG1

13800V

SG2

13800V

TO SWITCH S-18 TO SWITCH S-1

ST2

13800V

ST1

13800V

AUTO

THROWOVER

CONTROLS

AUTO

THROWOVER

CONTROLS

SG1-ST1

MAIN

SG2-ST2

MAIN

N.O.N.C.

M

SM-5-80E FUSED

SERVICE DISCONNECT

M

SM-5-80E FUSED

SERVICE DISCONNECT

A

000_MR_SG1

SEL SEL 351-6

000_MB_SG1

GE VB1-13.8-500

1200AF

A

000_MR_SG1

SEL SEL 351-6

000_MB_SG1

GE VB1-13.8-500

1200AF

A

000_MR_ST2 MAIN

SEL SEL 351-7

000_MB_ST2 MAIN

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

A

000_SW_SG2-ST2000_SW_SG1-ST2

000_MR_ST2 MAIN (ALT)

SEL SEL 351-7

000_MB_ST2 MAIN (ALT)

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

000_MR_ST1 MAIN ALT

SEL SEL 351-7

000_MB_ST2 MAIN

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

000_MR_ST1 MAIN

SEL SEL 351-7

000_MB_ST1 MAIN

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

000_SW_SG1-ST1 000_SW_SG2-ST1

A

AA

ALTERNATE

FEEDER

SG1

MAIN

SG2

MAIN

PRIMARY /

PREFERRED

FEEDER

51/5051/50

CAPACITOR

BANK FILTER

SG1-ST2

MAIN

51/50 51/50

CAPACITOR

BANK FILTER

SG2-ST1

MAIN

51/5051/50

SG1

13800V

T1

5000KVA

6.6%Z 34500-13800V

T2

5000KVA

6.6%Z 34500-13800V

SG2

13800V

TO SWITCH S-18 TO SWITCH S-1

ST2

13800V

ST1

13800V

AUTO

THROWOVER

CONTROLS

AUTO

THROWOVER

CONTROLS

SG1-ST1

MAIN

SG2-ST2

MAIN

1 1

N.O.N.C.

000_MR_SG1

SEL SEL 351-6

000_MB_SG1

GE VB1-13.8-500

1200AF

A

000_MR_ST2 MAIN

SEL SEL 351-7

000_MB_ST2 MAIN

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

A

000_SW_SG2-ST2

M

SM-5-80E FUSED

SERVICE DISCONNECT

M

SM-5-80E FUSED

SERVICE DISCONNECT

AA

000_MR_SG1

SEL SEL 351-6

000_MB_SG1

GE VB1-13.8-500

1200AF

A

000_SW_SG1-ST2

000_MR_ST2 MAIN (ALT)

SEL SEL 351-7

000_MB_ST2 MAIN (ALT)

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

000_MR_ST1 MAIN ALT

SEL SEL 351-7

000_MB_ST2 MAIN

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

000_MR_ST1 MAIN

SEL SEL 351-7

000_MB_ST1 MAIN

EATON/CUTLER-HAMMER

150 VCP-W-1000

1200AF

000_SW_SG1-ST1 000_SW_SG2-ST1

A

AA

NO SCALE

POWER ONE-LINE DIAGRAM1

KEYNOTES

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

EP602

N/A

MMMRA1/18/2024

POWER ONE-LINE DIAGRAM

A. REFER TO SHEET E-001 FOR ELECTRICAL SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

B. COORDINATE WITH THE VHA COR A TIME FOR A POTENTIAL TEMPORARY OR

PARTIAL OUTAGE.

C. CONDUCTOR, CONNECTORS, PADS, AND OTHER ANCILLARIES REQUIRED FOR

COMPLETE TRANSFORMER INSTALLATION AND OPERATION THAT ARE

DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED AT NO

ADDITIONAL COST TO THE VHA.

D. RETAIN ALL GROUNDING CONDUCTORS, EXCEPT AS EXPLICITLY INDICATED ON

THE DRAWINGS, FOR RECONNECTION TO GROUNDING TERMINALS ON THE NEW

EQUIPMENT AS INDICATED BY THE MANUFACTURER.

E. TRANSFORMER IMPEDANCE VALUES SHALL BE AS CLOSE TO BUT NOT LESS

THAN INDICATED ON THE ONE-LINE.

1. REPLACE EXISTING TRANSFORMER IN KIND AS INDICATED ON THE ONE LINE

DIAGRAM. ISOLATE POWER TO THE TRANSFORMER FROM THE SWITCH

CABINET. MAINTAIN LOOP CONTINUITY AT ALL TIMES DURING DEMOLITION AND

CONSTRUCTION. REFER TO THE 'ED' AND 'ES' SERIES DRAWINGS FOR

ADDITIONAL INFORMATION ON TRANSFORMER DEMOLITION AND

REPLACEMENT.

2. REPLACE EXISTING TRANSFORMER WITH NEW TRANSFORMER AS INDICATED

ON THE ONE LINE DIAGRAM. ISOLATE POWER TO THE TRANSFORMER FROM

THE SWITCH CABINET. MAINTAIN LOOP CONTINUITY AT ALL TIMES DURING

DEMOLITION AND CONSTRUCTION. REFER TO THE 'ED' AND 'ES' SERIES

DRAWINGS FOR ADDITIONAL INFORMATION ON TRANSFORMER DEMOLITION

AND REPLACEMENT.

3. PROVIDE 2000A SECONDARY DISCONNECT INTEGRAL TO TRANSFORMER

COMPARTMENT. REFER TO SPEC 26 12 19

4. PROVIDE NEW 300KVA, 13800-480/277V RADIAL, PAD MOUNT TRANSFORMER.

PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD AS INDICATED ON

THE DRAWINGS AND PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

INTERCEPT AND EXTEND CONDUCTORS INTO OPENING / COMPARTMENT AS

REQUIRED FOR NEW PAD CONFIGURATION. MOUNT TRANSFORMER TO NEW

PAD. RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

5. PROVIDE NEW 750KVA, 13800-208/120V RADIAL, PAD MOUNT TRANSFORMER.

PROVIDE AND ORIENT NEW PRECAST TRANSFORMER PAD AS INDICATED ON

THE DRAWINGS AND PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

INTERCEPT AND EXTEND CONDUCTORS OPENING / COMPARTMENT AS

REQUIRED FOR NEW PAD CONFIGURATION. MOUNT TRANSFORMER TO NEW

PAD. RECONNECT EXISTING CONNECTORS RETAINED DURING DEMOLITION TO

NEW TRANSFORMER BUSHINGS. REFER TO DETAIL SHEET EK501 FOR

ADDITIONAL INFORMATION.

6. THE Y-Y NEUTRALS ARE CONNECTED AND SHARE ONE GROUND.

112111

1 1

1 1 1

A

A

A

A

A

A

A REVISION A

REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026

AAA

A A

A

AA

A REVISION A 2.12.2026

6 6 6 6

6 6

6 6

TF-94

30 kVA

3.21 %Z 13800-208/120 V

BUILDING 94

TF-10

75 kVA

1.6 %Z 13800-240/120 V

BUILDING 10 AND 11

TF-9

300 kVA

5.5 %Z 13800-208/120 V

BUILDING 9

T-111 500 kVA

4.94 %Z 13800-208/120 V

BUILDING 111

T-115 300 kVA

4.5 %Z 13800-480/277 V

BUILDING 115

TF-28

750 kVA

5.75 %Z 13800-208/120 V

BUILDING 28

TF-2A

225 kVA

5.51 %Z 13800-480/277 V

BUILDING 28

TF-2

150 kVA

4.2 %Z 13800-208/120 V

BUILDING 28

TF-1

750 kVA

5.96 %Z 13800-208/120 V

BUILDING 1

MSB-1

TF-1C

500 kVA

5.3 %Z 13800-208/120 V

BUILDING 1

CHILLER

TF-1B

750 kVA

5.75 %Z 13800-480/277 V

BUILDING 1

MRI

TF-1A

500 kVA

6.81 %Z 13800-208/120 V

BUILDING 1A

TF-3

300 kVA

4.2 %Z 13800-208/120 V

BUILDING 3

TF-116

1000 kVA

5.75 %Z 13800-480/277 V

BUILDING 116

TF-114

750 kVA

5.75 %Z 13800-480/277 V

BUILDING 114 BUILDING 96

TF-51A

500 kVA

5.5 %Z 13800-208/120 V

BUILDING 51

TF-51B

750 kVA

5.73 %Z 13800-480/277 V

BUILDING 51

TF-50

750 kVA

7.47 %Z 13800-208/120 V

BUILDING 50

TF-49

750 kVA

5.75 %Z 13800-480/277 V

BUILDING 49

TF-48

500 kVA

5.1 %Z 13800-208/120 V

BUILDING 48

TF-48A

750 kVA

5.59 %Z 13800-480/277 V

BUILDING 48

TF-29

500 kVA

4.49 %Z 13800-208/120 V

BUILDING 29

TF-95

225 kVA

4.4991 %Z 13800-208/120 V

BUILDING 95

TF-88

75 kVA

4.08 %Z 13800-208/120 V

BUILDING 88

TF-4

500 kVA

5.41 %Z 13800-208/120 V

BUILDING 4

TF-5

150 kVA

4.2 %Z 13800-208/120 V

BUILDING 5

TF-4B

750 kVA

5.0 %Z 13800-480/277 V

BUILDING 4

TF-4A

750 kVA

5.0 %Z 13800-480/277 V

BUILDING 4

TF-7

500 kVA

5.3 %Z 13800-208/120 V

BUILDING 7

TF-59

300 kVA

4.09 %Z 13800-480/277 V

BUILDING 59

TF-8

150 kVA

4.2 %Z 13800-208/120 V

BUILDING 8

TF-118

750 kVA

5.0 %Z 13800-480/277 V

BUILDING 118

TF-57

112.5 kVA

4.9 %Z 13800-208/120 V

BUILDING 57

TF-96

75 kVA

3.2 %Z 13800-208/120 V

TO SUBSTATION

ST2

TO SUBSTATION

ST1

10A 60A 20A 35A 20A 15A

60A 80A 60A

25A 20A 80A 60A

20A 15A 6A

A A A A A

A

A A A

A A

Deduct: Alternate 1 - Base bid less all work associated with Transformer TF-50

EK501

MMMRA1/18/2024

ELECTRICAL DETAILS

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

Date:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

CONDUCT ELECTRICAL

SUBSTATION UPGRADE

VAHCS 4801 VETERANS DRIVE, ST CLOUD, MN 56303

656-22-341

VEG 23.09

CONSTRUCTION

DOCUMENTS

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

NO SCALE

TYPICAL PADMOUNT TRANSFORMER9

NO SCALE

UD PRIMARY CABLE

METALLIC TAPE SHIELD CABLE7 NO SCALE

ACCESSORIES FOR USE

WITH 15kV LOADBREAK FITTINGS8

NO SCALE

TYPICAL 13800V PRIMARY PAD-MOUNTED TRANSFORMER3NO SCALE

TYPICAL 13800V PRIMARY PAD-MOUNTED TRANSFORMER INSTALL1 NO SCALE

200 AMP LOADBREAK CABLE

TERMINATOR/APPARATUS CONNECTOR2

NO SCALE

PIPE BOLLARD - REMOVEABLE4 NO SCALE

DUCTBANK - TRENCH CUT6NO SCALE

PIPE BOLLARD - STANDARD5

A

A

A REVISION A

REVISION A WAS COMPLETED UNDER

THE SUPERVISION OF TIMOTHY JAMES

MUECK.

2.12.2026

A

REVISION STAMP

A

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature:

Typed or Printed Name: TIMOTHY JAMES MUECK

Date: License Number: 625032.12.2026

A

NOTE:

1. MINIMUM BENDING RADIUS IS 12 TIMES CABLE OUTSIDE DIAMETER.

UNCOATED CONDUCTOR

EXTRUDED SEMICONDUCTING EPR

STRAND SCREEN

EPR INSULATION

EXTRUDED SEMICONDUCTING EPR

INSULATION SCREEN

COPPER TAPE SHIELD

JACKET

HORIZONTAL TYPE

VERTICAL TYPE

GROUND CONNECTOR

SELECT EITHER VERTICAL OR HORIZONTAL TYPE TO BEST FIT EACH APPLICATION.

6' FLEX. CU CABLE

GROUNDING ELBOW (BRIGHT YELLOW COLOR)

DEADEND RECEPTACLE

WITH GROUND LEAD

NOTE:

1. SEE SPECIFICATIONS FOR MATERIAL COLORS AND MANNER OF INSTALLATION.

8.3/15KV PORTABLE FEED THRU OR GROUNDING DEVICE

6'

MI

N

6' MIN

CONNECT TO TRANSFORMER ENCLOSURE GROUND LUGS

CONNECT TO NEUTRAL

PRI…