Attachment B -Specifications.docx

DOCX document 13 KB Posted

Attached to
Vertical Turbine Pump Assembly for LDWF
Solicitation number
3000026921
Issued by
East Baton Rouge Parish, Baton Rouge City, Louisiana

About this file

This is a specifications document for a Vertical Turbine Pump Assembly procurement bid (RFX No. 3000026921) issued by Louisiana Department of Wildlife and Fisheries (LDWF). The project requires a single 50 HP Vertical Turbine Pumping Assembly engineered to deliver 3,000 gallons per minute at 44 feet of total dynamic head operating at 1,185 RPM. The pump assembly shall feature a single-stage open lineshaft wet pit configuration with a 1.5-inch diameter left-hand lineshaft and 10-inch stickup, coupled with a fabricated or cast discharge head optimized for a Vertical Hollow Shaft driver. The specification also requires a Vertical Hollow Shaft, Totally Enclosed Fan Cooled premium efficient electric motor rated for 50 HP continuous output at 1,185 RPM, powered by a 3-phase, 460-480 volt 60 Hz electrical supply. All equipment must maintain continuous duty rating up to 3,300 feet altitude in maximum ambient temperatures of 40 degrees Celsius and must match existing pump geometry and dimensions for proper installation.

The Variable Frequency Drive controller must be a solid-state PWM frequency inverter with a minimum 50 HP (37 kW) continuous capacity, 65 Amp continuous output current rating, and minimum UL Type 1/IP20 indoor enclosure. The VFD shall include internal harmonic control via DC link choke or 3% line reactor, along with software protections for dry-run prevention, loss-of-prime sensing, and controlled soft deceleration to prevent water hammer stress. Bidders must include shipping terms and costs in their final price, with a maximum lead time guarantee of 22 weeks. The equipment must be compatible with existing infrastructure as shown in the referenced Attachment C.

View the file

Other files

File Type Posted
3000026921.pdf PDF
Attachment A - Standard Terms and Conditions - Pages 1-9.docx DOCX document
Attachment C - Image - Page 1.docx DOCX document
Attachment D - Online Bidding Instructions - Pages 1-10.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment B – Specifications RFX No: 3000026921 Title: Vertical Turbine Pump Assembly for LDWF

EQUIPMENT PROCUREMENT BID SPECIFICATION REQUEST

Project Requirement Baseline: 50 HP Vertical Turbine Pumping Assembly

1. CORE SYSTEM DESIGN & OPERATING POINT

Bidders shall provide equipment engineered to meet or exceed the following continuous hydraulic operational baseline:

Design Flow Rate
Total Dynamic Head (TDH)
Synchronous Operating Speed
3,000 Gallons Per Minute (GPM)
44 Feet (Bowl Performance Minimum)
1,185 RPM Continuous

2. MECHANICAL PUMP CONSTRUCTION & MATERIALS

· Pump Configuration: Single-stage Open Lineshaft (OLS) Wet Pit Vertical Industrial Turbine pump assembly.

· Lineshafting: 1-1/2 inch diameter lineshaft, 10 Threads Per Inch (TPI) Left-Hand (LH) configuration with 10-inch stickup.

· Discharge Head: Fabricated or cast head optimized for a Vertical Hollow Shaft (VHS) driver.

3. MOTOR & DRIVER SPECIFICATIONS

· Driver Profile: Vertical Hollow Shaft (VHS), Totally Enclosed Fan Cooled (TEFC) premium efficient electric motor.

· Power / Speed: Rated for 50 Horsepower (HP) continuous output operating at a nameplate speed of 1,185 RPM.

· Electrical Grid: 3-Phase, 460-480 Volt input supply line at 60 Hz electrical service.

· Standard Safeguards: Equipped with an integrated Non-Reverse Ratchet (NRR), internal anti-condensation space heaters, Normally Closed (N/C) over-temperature winding thermostats, a motor steady bushing, and premium shaft grounding protection rings to isolate bearing housings from parasitic voltage shaft currents.

· Environment Bounds: Full continuous duty output rating stable up to 3,300 feet altitude in a +40°C maximum ambient environment.

· Geometry and Dimensions: Pump must match existing pump geometry and dimensions to ensure proper fit and fuction.

4. VARIABLE FREQUENCY DRIVE (VFD) CONTROLLER

· Capacity Baseline: Solid-state, PWM (Pulse-Width Modulation) frequency inverter engineered specifically for variable torque centrifugal pumping environments. Continuous drive capacity must be rated for a minimum of 50 HP (37 kW) with a 65 Amp continuous output current profile.

· Enclosure Frame: Minimum UL Type 1 / IP20 indoor chassis layout (or integrated within a secondary conditioned enclosure if outdoor).

· Harmonic Control: Equipped with an internal DC (Direct Current) link choke or a minimum 3% line reactor to restrict line-side harmonic feedback.

· Pump Protections: Software must include specialized application macros including dry-run protection, loss-of-prime sensing, and controlled dual-ramp soft deceleration profiling to actively eliminate downstream water hammer pipelines stress.

5. PROJECT EXECUTION, TELEMETRY, & DELIVERY

· Shipping Mandate: All bids must specify shipping terms and calculate shipping into final price.

· Delivery Windows: Final proposals must state lead time guarantees. The project benchmark target is set to a maximum of 22 weeks.

· Product must fit the existing infrastructure in place. See Attachment C- Image – Page 1.

File details come from the government source that posted it. Updated .