ATTACHMENT B MAINTENANCE SCHEDULE.xlsx
XLSX spreadsheet 14 KB Posted
- Solicitation number
- 36C24822Q0751
About this file
This document contains a maintenance schedule for reverse osmosis water systems at various Department of Veterans Affairs facilities in Florida. It lists 15 locations with water treatment equipment from manufacturers like Culligan, Ameriwater, and Nalco. Monthly, quarterly, semi-annual, and annual maintenance is outlined for items like filters, resin, tanks, and ultraviolet lights. The related federal contract opportunity is for reverse osmosis water system maintenance with solicitation number 36C24822Q0751 from the VA Veterans Health Administration VISN 8. The description notes maintenance of reverse osmosis water systems, with responses due for the indefinite delivery, indefinite quantity contract. Key details on products, services, and locations are provided in the maintenance schedule attachment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ATTACHMENT H MAINTENANCE SCHEDULE AMENDMENT 0001.xlsx | XLSX spreadsheet | |
| ATTACHMENT F GOVERNMENT RESPONSE AMENDMENT 0001.docx | DOCX document | |
| 36C24822Q0751 0001.docx | DOCX document | |
| ATTACHMENT G PRICE COST SCHEDULE AMENDMENT 0001.docx | DOCX document | |
| ATTACHMENT E PAST PERFORMANCE QUESTIONNAIRE.docx | DOCX document | |
| ATTACHMENT D CONTRACTOR REQUEST FOR INFORMATION.docx | DOCX document | |
| ATTACHMENT C AAMI TIR34 2014 r2017.pdf | ||
| 36C24822Q0751_1.docx | DOCX document | |
| WAGE DETERMINATION.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Maintenance Schedule
| Facility | Location Room# | Equipment | Model# | Serial# | Description | MONTHLY: 1. Change Pre-Filters & Resin 2. Change DI Exchange Tanks 3. Carbon & Water Softener Inspections | Monthly TIR 34 AAMI Tests | QUARTERLY Utility Water AAMI TIR 34 and Standard | QUARTERLY Critical Water AAMI TIR 34 | QUARTERLY Endotoxin Critical Water AAMI TIR 34 | QUARTERLY Bacteria Critical Water AAMI TIR 34 | SEMI-ANNUALLY: 1. Change Sub Micron Filter | ANNUALLY: 1. Repair/Maintain UV Lite 2. Loop Disinfect RO System 3. Sanitization | |
| OVAMC Lake Nona | Bldg. 1 | |||||||||||||
| 0E306-01 | Culligan Water | 1020677 | V1147366 | Vacuum head 48.1 cubic feet metal tanks. (3 EA) | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Nona | Bldg. 2 1H301-02 | Culligan Reverse Osmosis System | 7F0S4-316-2.5F-6P-PE | V11442927 | Electronic unit, 1500 gallons water storage tank. | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | |
| OVAMC Lake Nona | Bldg. 2 1H301-02 | Culligan Water Softener System | 1021126 | VP11005165 | Vacuum head 42.4 cubic feet depth tanks (3 EA), Electronic head 29.4 cubic feet softener tanks (4 EA)., and Vacuum head 29.4 cubic feet carbon vacuum tanks (3 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | |
| OVAMC Lake Nona | Bldg. 2 3K912A-02 | Ameriwater Reverse Osmosis System | HCR02 | 50060 | Enclosed reverse osmosis mini-unit, 5 gallons water storage tank. | 1,2,3 | 1 EA | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | |
| OVAMC Lake Nona | Bldg. 5 | |||||||||||||
| 1B402-05 | Culligan Water Softener System | HI-FLO 3E | VP11000605 | Electronic head 7.56 cubic feet softener tanks (2 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Nona | Bldg. 7 | |||||||||||||
| 1A112-07 | Culligan Water Softener System | HI-FLO 3E | 6488127-080118-0003 | Electronic head 7.56 cubic feet softener tanks (3 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Nona | Bldg. 9 | |||||||||||||
| 1B203-09 | Culligan Water Softener System | HI-FLO 3E | VP11000603 | Electronic head 7.56 cubic feet softener tanks (2 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Nona | Bldg. 11 | |||||||||||||
| 1A0607 | Culligan Water Softener System | HI-FLO 3E | 02286042-021511-0008 | Electronic head 7.56 cubic feet softener tanks (2 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Nona | Bldg. 13 | |||||||||||||
| 1C120-13 | Marlo Water Softener System | MGT-210-2-TW/ADD NORK W/SALT | EP-150210-001-1 | Electronic head 15.71 cubic feet softener tanks (2 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Nona | Bldg. 14 Fisher House Mechanical Room | Culligan Water Softener System | 1028301 | VC20474071 | Electronic 5.5 cubic feet softner tank (1 EA) | 3 | 0 | 0 | 0 | 0 | 0 | Yes | 1,2,3 |
| OVAMC Lake Baldwin | Bldg. 500 | |||||||||||||
| M-Deck | Ameriwater Reverse Osmosis System | HC-20157 | 50150 | Enclosed RO mini-unit, 55 & 500 gallons water storage tanks. | 1,2,3 | 1 EA | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Baldwin | Bldg. 500 | |||||||||||||
| M-Deck | Culligan Water Softener System | 1024393 | VL17269003 | Electronic head, 12.43 cubic feet softener tanks (2 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 | ||
| OVAMC Lake Baldwin | Bldg. 502 02-502 | Nalco Water Softener System | Ultra-Treat MD-9000 | 262635 | Electronic head 5.79 cubic feet water softener tanks (2 EA). | 1,2,3 | 0 | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 |
| Viera VA Healthcare Center | Bldg. 1 | |||||||||||
| C409 | Getinge Reverse Osmosis System | M-4800 | 94800204 | Enclosed RO mini-unit, 55 gallons water storage tanks. | 1,2,3 | 1 EA | 1 EA | 1 EA | 1 EA | 1 EA | Yes | 1,2,3 |
Coarse Premium Solar Salt
| Location | Apr-22 | May-22 | Jun-22 | Jul-22 | Aug-22 | Sep-22 | Oct-22 | Nov-22 | Dec-22 | Jan-23 | Feb-23 | Mar-23 | Total |
| OVAMC Lake Nona | 242 | 242 | 242 | 242 | 242 | 242 | 242 | 242 | 242 | 242 | 242 | 242 | 2904 |
| OVAMC Lake Baldwin | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 780 |
| Viera VA Healthcare Center | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
File details come from the government source that posted it. Updated .