Attachment B Current Damper Inventory Tracker.xlsx

XLSX spreadsheet 5 MB Posted

Attached to
J041--Service - Fire Damper Inspection - SF IDIQ - Ordering Periods 09-30-2025
Solicitation number
36C26325Q1047
Issued by

About this file

This document is an Excel spreadsheet tracking fire, smoke, and fire/smoke dampers for the Sioux Falls VA Healthcare System, containing an inventory of 571 total damper entries across multiple buildings. The comprehensive tracker details each damper's location, type, status, inspection results, and specific characteristics such as size, orientation, and testing outcomes, with most dampers categorized as active fire, smoke, or fire/smoke dampers.

The associated federal contract opportunity (Solicitation Number: 36C26325Q1047) seeks a service agreement for fire damper inspection and testing at the Sioux Falls VA Healthcare System. The pre-solicitation involves field verification, inspection, and testing of active and abandoned fire, smoke, and combination fire/smoke dampers according to NFPA 80 requirements. The contractor will be responsible for documenting findings, updating spreadsheets and drawings, installing access panels, and potentially performing repairs. The contract includes multiple contract line items (CLINs) for different services such as field verification, damper testing, access panel installation, and parts repair, with work to be performed Monday through Friday during business hours, excluding federal holidays.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table 1

Fire, Smoke, & Fire/Smoke Damper Testing, Tracking, and InventorySum of All Damper Type Counts in table571TOTAL Damper Entries571
Location: SFVAHCSDamper Type Count (ALL Buildings)378Dampers that require inspection.FL = Removal/Replace Fus. Link

PDA = Removed Pwr at Damper FA = Via Fire Alarm Activation AP = Access Panel Available NAP = No Access Panel

CR = Can't ReachACP = Accuator Closed Position CT = Can't Test
AOP = Accuator Open Position Open = Damper Visibly Open Closed = Damper Visibly Closed Inspected By: Ryan Henglefelt DATEs of inspection 9/16/2019 Thur 9/20/2019Inspection: Fire & Fire/Smoke Damper Testing

Frequency: 6 year Code REF: NFPA 80 Article 19.5 2019 Addition NFPA 80 Article 19.5.1.3 2019 Addition NFPA 105 Article 7.6 2019 Addition Inspection: Fire & Fire/Smoke Damper TestingFL = Removal/Replace Fus. LinkACP = Accuator Closed Position CT = Can't Test AOP = Accuator Open Position Open = Damper Visibly Open Closed = Damper Visibly Closed Inspected By: xxxxxxxxx DATEs of inspection PDA = Removed Pwr at Damper FA = Via Fire Alarm Activation AP = Access Panel Available NAP = No Access Panel CR = Can't Reach Frequency: 6 year Code REF: NFPA 80 Article 19.5 xxxx Addition NFPA 80 Article 19.5.1.3 xxxx Addition NFPA 105 Article 7.5.2 xxxx Addition

Address: 2501 W. 22nd St.Active Fire229Abandoned - Fire35Not Required Active Combination Fire/Smoke Dampers20
City/State/Zip: SF, SD 57105Active Smoke16Not required Active Fire Damper95Not required Disabled Smoke Dampers2
Contact: Sioux FallsActive Fire/Smoke98Not Required Active Smoke Damper25Not required Disabled Fire/Smoke Dampers0
Blanks (D, F, G)0Demolished - All Dampers510
BuildingRoom NumberDamper
NumberDamper
TypeDescription/Location: (Notes: AP, NAP, etc.) or Justification for RemovalDamper required?Damper StatusDate Damper put into serviceAdded to "SFVA Dampers" dwgFusible Link
Test MethodNon-Fusible Link
Test MethodPre-Test
Position (Open/Closed)Test
Position (Open/Closed)Post-Test
Position (Open/Closed)Test
ResultDeficiencesCorrective Action TakenDate
CorrectedTest
ResultDeficiencesCorrective Action TakenDate
CorrectedILSM IN Place?
1307D-1-G-001Fire6" round horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307AYesActiveXFLN/AOpenClosedOpenPass6" round horizontalN/A
1307D-1-G-002Fire6x6 horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307AYesActiveXFLN/AOpenClosedOpenPass6x6 horizontalN/A
1307D-1-G-003Fire6" round horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307AYesActiveXFLN/AOpenClosedOpenPass6" round horizontalN/A
1307D-1-G-004Fire6" round horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307AYesActiveXFLN/AOpenClosedOpenPass6" round horizontalN/A
1307D-1-G-005Fire6x6 horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307AYesActiveXFLN/AOpenClosedOpenPass6x6 horizontalN/A
1307BD-1-G-005AFire/SmokeRoom 307B (AP)YesActiveXN/AFAOpenClosedOpenFail/PASSActivated key switch alarm sent but no reaction from
actuator used magnet alarm sent but no reaction from actuatorTested Okay -W/O 10245404911/8/19
1307BD-1-G-005BFire/SmokeRoom 307B (AP)YesActiveXN/AFAOpenClosedOpenFail/PASSActivated key switch alarm sent but no reaction from actuator used magnet alarm sent but no reaction from
actuatorTested Okay -W/O 10245404911/8/19
1307DD-1-G-006Fire6" round. Room 307D (AP)YesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1307DD-1-G-007Fire6/6. Room 307D (AP)YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1307CD-1-G-008Fire6/6. Room 307C (AP)YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1301D-1-G-009Fire6" round. Room 301 (AP)YesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1336D-1-G-010FireRoom 336 (AP)YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1336BD-1-G-010AFire6" round. Room 336B (AP) *Update to 336A?YesActiveXFLN/AOpenOpenOpenFail/PASS6" round Broken LinksReplaced Links & Tests Okay Now -W/O 10275658912/9/19
1315D-1-G-011Fire6/6. Room 315 (AP) (access through vent cover)YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1318D-1-G-012Fire6" round. Room 318 (AP)YesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1308D-1-G-013FireRoom 308 (AP)YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1308D-1-G-014FireRoom 308 (AP)YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1308D-1-G-014AFire/SmokeRoom 308 (AP)YesActiveXN/AFAOpenClosedOpenFail/PASSActivated key switch alarm sent no reaction at actuator used magnet tripped alarm no reaction from actuatorTested Okay -W/O 10245404911/8/19
1308D-1-G-014BFire/SmokeRoom 308 (AP)YesActiveXN/AFAOpenOpenOpenFail/PASSActivated key switch alarm sent no reaction at actuator used magnet alarm no reaction from actuatorTested Okay -W/O 10245404911/8/19
1307CD-1-G-015Fire6" round. Room 307C (AP)YesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1306D-1-G-016Fire6/6. Room 306 (AP)YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1306D-1-G-017Fire6" round. Room 306 (AP)YesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1304D-1-G-018Fire6" round. Room 304 (AP)YesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1304D-1-G-019FireRoom 304 (AP) 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1309D-1-G-020FireRoom 309 (AP).YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1309D-1-G-021FireRoom 309 (AP)YesActiveXFLN/AOpenClosedOpenPassUse mirror to see hard access door tight to gridN/A
1302D-1-G-022FireRoom 302 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1302D-1-G-023FireRoom 302 (AP) 6/6YesActiveXFLN/AOpenClosedOpenFail/PASS6x6 radiant link brokeRelaced Links and Tests Okay -W/O 010245404943805
1311D-1-G-024FireRoom 311 (AP) (access through vent cover) 310? Don't see one in 311 on plans. Horizontal 6/6.YesActiveXFLN/AOpenClosedOpenPassHorizontal 6x6N/A
1318D-1-G-025FireRoom 318 (AP) horizontal.YesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1333D-1-G-026FireRoom 333 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1332D-1-G-027FireRoom 332 (AP)YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1332D-1-G-028FireRoom 332 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1330D-1-G-029FireRoom 330 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1330D-1-G-030FireRoom 330 (AP). 6" ROUNDYesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1320D-1-G-031FireRoom 320 (AP)YesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1320D-1-G-032FireRoom 320 (AP)YesActiveXFLN/AOpenClosedOpenFail/PASSBroken link radiant damperReplaced Links & Tests Okay -W/O 10275658912/9/19
1321D-1-G-033FireRoom 321 (AP). HorizontalYesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1321D-1-G-034FireRoom 321 (AP). Use mirror.YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1333D-1-G-035FireRoom 333 (AP). Use mirror.YesActiveXFLN/AOpenClosedOpenPassUse mirror to see hard access door tight to gridN/A
1331D-1-G-036FireRoom 331 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1327D-1-G-037FireRoom 327 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" round limited accessN/A
1327D-1-G-038FireRoom 327 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1303D-1-G-039FireRoom 303 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1329D-1-G-040FireRoom 329 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" round very limited accessN/A
1329D-1-G-041FireRoom 329 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1331D-1-G-042FireRoom 331 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1319D-1-G-043FireRoom 319 (AP). HorizontalYesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1319D-1-G-044FireRoom 319 (AP). horizontalYesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1326D-1-G-045FireRoom 326 (AP). 8" roundYesActiveXFLN/AOpenClosedOpenPass8" roundN/A
1322D-1-G-046FireRoom 322 (AP). Horizontal.YesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1322D-1-G-047FireRoom 322 (AP). Use mirror.YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1325D-1-G-048FireRoom 325 (AP) *Only 2 dampers shown in 325 on dwg - need to locate 3rd in field. HorizontalYesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1323D-1-G-049FireRoom 323 (AP). Use mirrorYesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1323D-1-G-050FireRoom 323 (AP). Horizontal.YesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1326D-1-G-051FireRoom 326 (AP). 8" roundYesActiveXFLN/AOpenClosedOpenPass8" roundN/A
1325D-1-G-052FireRoom 325 (AP) *Only 2 dampers shown in 325 on dwg - need to locate 3rd in field horizontal.YesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1325D-1-G-052AFireRoom 325 (AP) *Only 2 dampers shown in 325 on dwg - need to locate 3rd in field. Use mirror.YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1324D-1-G-053FireRoom 324 (AP). HorizontalYesActiveXFLN/AOpenClosedOpenPassHorizontalN/A
1324D-1-G-054FireRoom 324 (NAP)YesActiveXFLN/AOpenClosedOPFail/PASSNo access panel -Access Panel Needed. Access panel is too far down from damper location needs moved to see damper or use camera in ductwork to see. There is damper access - HVAC noted that the screw holding the elbow can be removed which provides access.Accessed from ductwork bottom side of damper. Maximo service request #3557575.1/7/25
1305D-1-G-055FireRoom 305 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" round limited accessN/A
1305D-1-G-056FireRoom 305 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1328D-1-G-057FireRoom 328 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1328D-1-G-058FireRoom 328 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" round limited accessN/A
1335D-1-G-059FireRoom 335 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1335D-1-G-060FireRoom 335 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1301D-1-G-061FireRoom 301 (MH Check In) (AP). Use mirror.YesActiveXFLN/AOpenClosedOpenPassUse mirror to seeN/A
1303D-1-G-062FireRoom 303 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1334D-1-G-063FireRoom 334 (AP). 6/6YesActiveXFLN/AOpenClosedOpenPass6x6N/A
1334D-1-G-064FireRoom 334 (AP). 6" roundYesActiveXFLN/AOpenClosedOpenPass6" roundN/A
1206D-1-G-065Fire/SmokeHall By Room 206 (NAP) Corr. 251A?. 8" round.YesActiveXN/AFAOpenOpenOpenFail/PASS8" round - NAP - damper is in the middle of the hallway with flex going out one end to a RGD switch triggers alarm
but no movement from actuatorTests Okay -W/O 10245404911/8/19
1209D-1-G-066Fire/SmokeHall By Room 209 (NAP) Corr. 251?. 8" round.YesActiveXN/AFAOpenOpenOpenFail/PASS8" round - NAP - damper is completely on the outside of
the hallway 6" from the wall, key switch activates alarm but actuator does not moveTests Okay -W/O 10245404911/8/19
1113D-1-G-067FireFloor south sideYesActiveXYes
1113D-1-G-068FireFloor south sideYesActiveXYes
1113D-1-G-069FireFloor south sideYesActiveXYes
1113D-1-G-070FireFloor south sideYesActiveXYes
1113D-1-G-071FireFloor south sideYesActiveXYes
1113D-1-G-072FireFloor south sideYesActiveXYes
1113D-1-G-073FireFloor south sideYesActiveXYes
1113D-1-G-074FireFloor south sideYesActiveXYes
1113D-1-G-075FireFloor south sideYesActiveXYes
1113D-1-G-076FireFloor south sideYesActiveXYes
1113D-1-G-077FireFloor south sideYesActiveXYes
1113D-1-G-078FireFloor south sideYesActiveXYes
1113D-1-G-079FireFloor south side - Return 12/12YesActiveXYes
1113D-1-G-080FireFloor south side - Return 12/12YesActiveXYes
1113D-1-G-081FireFloor south side - Return 12/12YesActiveXYes
1113D-1-G-082FireFloor North SideYesActiveXYes
1113D-1-G-083FireFloor North SideYesActiveXYes
1113D-1-G-084FireFloor North SideYesActiveXYes
1113D-1-G-085FireFloor North SideYesActiveXYes
1113D-1-G-086FireFloor North SideYesActiveXYes
1113D-1-G-087FireFloor North SideYesActiveXYes
1113D-1-G-088FireFloor North SideYesActiveXYes
1113D-1-G-089FireFloor North SideYesActiveXYes
1113D-1-G-090FireFloor North SideYesActiveXYes
1113D-1-G-091FireFloor North SideYesActiveXYes
1113D-1-G-092FireFloor North SideYesActiveXYes
1113D-1-G-093FireFloor North SideYesActiveXYes
1113D-1-G-094FireFloor North Side - Return 12/12YesActiveXYes
1113D-1-G-095FireFloor North Side - Return 12/12YesActiveXYes
1113D-1-G-096FireFloor North Side - Return 12/12YesActiveXYes
1009AD-1-G-097Fire/Smoke6/6 OA duct. East wall.YesActiveXFailInaccessibleYes
1009AD-1-G-098Fire/Smoke6/6 EA duct. East WallYesActiveXFailInaccessibleYes
1117D-1-G-099Fire/Smoke10/8 OA. Access panel in west wall.YesActiveXFailTripped detector but didn't activate damper - alarm company to check wiring & programmingYes
1117D-1-G-100Fire/Smoke12/8 EA duct. Access panel in west wall.YesActiveXFailTripped detector but didn't activate damper - alarm company to check wiring & programmingYes
1117D-1-G-101Fire/Smoke12/8 OA duct. West wall, south end. Ceiling light restricts accessibility. Dev 109 Triggers this damper.YesActiveXFailTripped detector but didn't activate damper - alarm company to check wiring & programming.Yes
1117D-1-G-102Fire/Smoke12/8 EA duct. West wall, north end. Ceiling light restricts accessibility. Dev 110 Triggers this damper.YesActiveXFailTripped detector but didn't activate damper - alarm company to check wiring & programming.Yes
1118D-1-G-103Fire/Smoke6/6 OA Duct. East wall.YesActiveXFailNot accessibleYes
1118D-1-G-104Fire/Smoke6/6 EA duct. East WallYesActiveXFailNot accessibleYes
1244AD-1-G-105Fire/Smoke6/6 OA duct. East wall.YesActiveXFailInaccessibleYes
1244AD-1-G-106Fire/Smoke6/6 EA duct. East Wall.YesActiveXFailInaccessibleYes
1244D-1-G-107Fire/Smoke6/6 OA duct. West wall, south end. Dev 126 Triggers this damper.YesActiveXPassYes
1244D-1-G-108Fire/Smoke8/6 EA duct. West wall, north end.Dev 127 Triggers this damperYesActiveXPassYes
1360D-1-G-109Fire/Smoke6/6 EA duct. Access panel in east wall.YesActiveXPassYes
1360D-1-G-110Fire/Smoke6/6 OA duct. Access panel in east wall.YesActiveXPassYes
1312AD-1-G-111Fire/SmokeNo damper at this location. Construction documents show 4th damper that does not exist.NoDemolishedXN/AN/AYes
1312AD-1-G-112FireWall Transfer grille east.YesActiveXFailNot connectedYes
1312AD-1-G-113FireWall Transfer grille east.YesActiveXFailNot connectedYes
1312AD-1-G-114FireTransfer fan. East wall.YesActiveXFailNot connectedYes
1360D-1-G-115Fire/Smoke6/6 EA duct. East wall. Dev #139 or #140 Triggers this damper.YesActiveXFailInaccessibleYes
1360D-1-G-116Fire/Smoke6/6 OA duct. East wall. Dev #139 or #140 Triggers this damper.YesActiveXFailInaccessibleYes
1358AD-1-G-117Fire/Smoke6/6 OA duct. East wall. Dev 132 Triggers this damper.YesActiveXFailOperated, but no accessibility.Yes
1358AD-1-G-118Fire/Smoke6/6 EA duct. East wall. Dev 133 Triggers this damper.YesActiveXFailDid not operate, no accessibility.Yes
1355D-1-G-119Fire/Smoke6/6 OA duct. NW corner of room.YesActiveXFailNo access, operated but no visualYes
1355D-1-G-120Fire/Smoke8/8 EA duct. NW corner of room.YesActiveXFailNo access, operated but no visualYes
1407AD-1-G-121Fire/Smoke6/6 OA duct. East wall.YesActiveXFailNo access. Question of if these are required - is this a chase?Yes
1407AD-1-G-122Fire/Smoke6/6 EA duct. East wall.YesActiveXFailNo access. Question of if these are required - is this a chase?Yes
1411BD-1-G-123FireTransfer. West wall.YesActiveXFailNo way to actuate, no fusible link, not connectedYes
1411BD-1-G-124FireTransfer. North wall.YesActiveXFailNo way to actuate, no fusible link, not connectedYes
1404D-1-G-125Fire/Smoke28/12 OA duct. NW corner of room.YesActiveXFailInaccessibleYes
1404D-1-G-126Fire/Smoke28/12 EA duct. NW corner of room.YesActiveXFailInaccessibleYes
1ELEV-JD-1-G-127SmokeSmoke Damper not required evaluated by Vanguard contractor since no codes require them dated 2025/4/2. See RE: SIOUX FALLS VAMC – PRIORITY ONE PROJECTS: FIRE AND SMOKE DAMPER DECOMMISIONING report saved with JC files.NoActiveXFailDampers not listed, not connected to power or alarm interfaceYes
1410D-1-G-128Fire/Smoke8/6 EA duct. East wall.YesActiveXPassYes
1410D-1-G-129Fire/Smoke8/6 OA duct. East wall.YesActiveXPassYes
1ELEV-KD-1-G-130SmokeSmoke Damper not required evaluated by Vanguard contractor since no codes require them dated 2025/4/2. See RE: SIOUX FALLS VAMC – PRIORITY ONE PROJECTS: FIRE AND SMOKE DAMPER DECOMMISIONING report saved with JC files.NoActiveXFailDampers not listed, not connected to power or alarm interfaceYes
1ELEV-LD-1-G-131SmokeSmoke Damper not required evaluated by Vanguard contractor since no codes require them dated 2025/4/2. See RE: SIOUX FALLS VAMC – PRIORITY ONE PROJECTS: FIRE AND SMOKE DAMPER DECOMMISIONING report saved with JC files.NoActiveXFailDampers not listed, not connected to power or alarm interfaceYes
1206D-1-G-132FireYesActiveXYes
1206D-1-G-133FireYesActiveXYes
1251D-1-G-134FireYesActiveXYes
1251D-1-G-135FireYesActiveXYes
1238D-1-G-136SmokeYesActiveXYes
1237D-1-G-137SmokeYesActiveXYes
1226D-1-G-138SmokeYesActiveXYes
1226D-1-G-139SmokeYesActiveXYes
1226D-1-G-140SmokeYesActiveXYes
1349D-1-G-141Fire/SmokeYesActiveXYes
1348D-1-G-142Fire/SmokeYesActiveXYes
1324D-1-G-143Fire/SmokeYesActiveXYes
1325D-1-G-144Fire/SmokeDuct Chase into attic above room listedYesActiveXYes
1350D-1-G-145Fire/SmokeDuct Chase into attic above room listedYesActiveXYes
1219BD-1-G-146FireAbandoned. Closed 3/18/25. Duct is capped. 16/4.YesAbandonedXYes
1219BD-1-G-147FireAbandoned. Closed 3/18/25. Duct is capped. 27/7.YesAbandonedXYes
1219BD-1-G-148FireAbandoned. Closed 3/18/25. Duct is capped. 16/4.YesAbandonedXYes
1250D-1-G-149FireAbandoned. Duct is capped. Access door on bottom of duct but inaccessible (it's above a hard deck). 31/8.YesAbandonedXYes
1207D-1-G-150FireDemolished. 16/4. FireNoDemolishedXYes
1207D-1-G-151FireDemolished. 24/7. FireNoDemolishedXYes
1207D-1-G-152FireDemolished. 16/4. FireNoDemolishedXYes
1322BD-1-G-153FireDemolished. 20/14.NoDemolishedXYes
1350D-1-G-154FireDamper in attic. Damper is open but inaccessible. Ductwork is capped & sealed at top.YesAbandonedXYes
1350D-1-G-155FireDemolished. 16/12. FireNoDemolishedXYes
1317D-1-G-156FireDemolished. 22/18. FireNoDemolishedXYes
1317D-1-G-157FireDemolished. 32/8. FireNoDemolishedXYes
1348D-1-G-158FireDemolished. 20/14. FireNoDemolishedXYes
1307FD-1-G-159FireDemolished. 14/17. Fire Duct capped at damperNoDemolishedXYes
1307ED-1-G-160FireDemolished. 24/7. FireNoDemolishedXYes
1351D-1-G-161FireDemolished. 14/14. Fire Duct capped at damperNoDemolishedXYes
53179A-53D-53-001FireElectrical closet removed. Unsure if damper remains.Damper Not required at this locationNoActiveX
54201D-54-G-001Fire22" dia SA duct. North of AHU.YesActiveJun-25X
54201D-54-G-002Fire20/18 RA duct. NE of AHU.YesActiveJun-25X
54201D-54-G-003Fire/Smoke12" dia SA duct. South of Elec 202-54 in truss space outside mechanical rooms.YesActiveJun-25X
54201D-54-G-004Fire/Smoke16/16 RA duct. South of Elec 202-54 in truss space outside mechanical rooms.YesActiveJun-25X
54201D-54-G-005Fire20/18 RA duct. SE of AHU.YesActiveJun-25
54201D-54-G-006Fire22" dia duct. SW of AHU.YesActiveJun-25X
54201D-54-G-007Fire10/10 RA duct. SW of AHU.YesActiveJun-25X
54201D-54-G-008Smoke10/8 SA duct. Enters into stair 200.YesActiveJun-25X
54124AD-54-G-009Fire/Smoke10/8 SA duct. Between bath 124 and den 121.YesActiveJun-25X
54100AD-54-G-010Fire/Smoke16/12 SA duct. Between corridor 100A and walkway 100.YesActiveJun-25X
54111D-54-G-011Fire/Smoke8/8 RA duct. Betewen 109A and 111.YesActiveJun-25X
54122D-54-G-012Fire14/10 EA Duct. Between 110 and 122.YesActiveJun-25X
5435D-5-G-001Fire/SmokeRoom 435 Ceiling (AP) (test duct smoke on AHU 32 in attic)YesActiveXN/AFAOpenClosedOpenPassN/A
5435D-5-G-002Fire/SmokeRoom 435 Ceiling (AP) (test duct smoke on AHU 32 in attic)YesActiveXN/AFAOpenClosedOpenFail/PASSUsed magnet alarm sent but no reaction from actuatorTests Okay -See W/O 10245404912/3/19
5337D-5-G-003Fire/Smoke20/14 EA Duct. West side of chase. Hall outside Room 337 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5337D-5-G-004Fire/Smoke20/14 EA Duct. North side of chase. Hall outside Room 337 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5336D-5-G-005Fire/Smoke28/14 SA west side chase. Hall outside Room 336 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5336D-5-G-006Fire/SmokeSA duct. North side of Chase. Hall outside Room 336 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5334D-5-G-007Fire/Smoke46/16 RA duct. West side of chase. Hall outside Room 334 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSDamper over hard lid -Access panel needed.Access panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5331ED-5-G-008Fire/SmokeHall outside Room 331E (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSDamper over hard lid -Access panel needed Access panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5309D-5-G-008AFire/Smoke20/20 SA Duct. Room 309 (AP)YesActiveXN/AFAOpenClosedOpenFail/PASSActuator not functioning (Noted on wrong floor)Tests Okay -W/O 10245404911/20/19
5309D-5-G-008BFire/Smoke18/12 RA Duct. Middle duct. Room 309 (AP)YesActiveXN/AFAOpenClosedOpenFail/PASSRetaining angles not covering wall hole, damper actuator not
functioning (Noted on wrong floor). Duct work Needs Patch Work Around It.Tests Okay -W/O 102454049. Confirmed patch work completed and retaining angles present 1/7/2025.11/20/19
5309D-5-G-008CFire/Smoke18/12 RA Duct. East duct. Room 309 (AP)YesActiveXN/AFAOpenClosedOpenFail/PASSActuator not functioning (Noted on wrong floor)Tests Okay -W/O 10245404911/20/19
5333D-5-G-008DFire/SmokeOxygen 333YesActiveXN/AAlarmNAPFail/PASSFound to be an extra. Access panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5228CD-5-G-009Fire/Smoke16/16 EA Duct. Hall outside Room 228C (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel needed -See printsContractor installed access panels Aug. 2022, credit card PO PX2493. JCI inspected and passed inspection Aug. 2022. Tests okay. Maximo service request #3557575.1/7/20251/7/25
5233D-5-G-010Fire/Smoke28/18 SA duct. Hall outside Room 233 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5233D-5-G-011Fire/Smoke32/14 RA duct. Hall outside Room 233 (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5227DD-5-G-011AFire/SmokeRoom 227D (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel or inspection opening needed at this locationTests okay. Maximo service request #3557575. Installed access port for camera.1/7/25
5226AD-5-G-012Fire/SmokeHall behind exit sign by 226A (NAP)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel needed. Damper requires repairs. Binding as tested on 1/7/2025.Carpenter shop assigned service request to install access panel coordinating with HVAC 1/15/2025.1/28/25
5209D-5-G-012AFire/SmokeRoom 209 (AP but can't see louvers)YesActiveXN/AFANAPNAPNAPFail/PASSAccess panel needed -See printsContractor installed access panels Aug. 2022, credit card PO PX2493. JCI inspected and passed inspection Aug. 2022. Tests okay. Maximo service request #3557575.
5145D-5-G-013FireHall outside Room 147 (AP) Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveDemolision part of EHRM? ConfirmXFLN/AOpenClosedOpenPassVertical 10x10 -Access panel neededN/A
5145D-5-G-014FireHall outside Room 147 (AP)Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveDemolision part of EHRM? ConfirmXFLN/AOpenClosedOpenPassVertical 10x10N/A
5145D-5-G-015FireHall outside Room 147 (AP). Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveDemolision part of EHRM? ConfirmXFLN/AOpenClosedOpenPassVertical 10x10N/A
5145D-5-G-016FireRoom 145 (AP). Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveDemolision part of EHRM? ConfirmXFLN/AOpenClosedOpenPassVertical 10x10N/A
5175D-5-G-017FireHall outside Room 175 (AP). Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveDemolision part of EHRM? ConfirmXFLN/AOpenClosedOpenPassVertical 10x10N/A
5102D-5-G-018FireHall outside Room 102 30/10 RA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveX??OpenClosedOpenPassVertical 10x30 - Very limited accessN/A
5134D-5-G-019FireHall outside Room 134 (AP) (shut unit down) 48/10 RA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 10x48 - Small Access doorN/A
5133D-5-G-020FireHall outside Room 133 (AP) (shut unit down) 36/18 RA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 18x36N/A
5133D-5-G-021FireInside Room 133 (AP) (shut unit down) 24/14 SA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 14x24 - Very limited accessN/A
5110D-5-G-022FireHall outside Room 110 (AP) (Shut unit down) 10" DIA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical round 12x12N/A
5110D-5-G-023FireHall outside Room 110 (AP) (Shut unit down) 30/18 SA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 18x24N/A
5109D-5-G-024FireInside Room 109 (AP) 8" dia duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical round 8"N/A
5105D-5-G-025FireInside Room 105 (AP) (shut unit down). 6/12 vertical. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 6x12N/A
5105D-5-G-026FireInside Room 105 (AP) (shut unit down). 6" round. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical round 6"N/A
5105D-5-G-027FireInside Room 105 (AP) (shut unit down). 8" round. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical round 8"N/A
5105D-5-G-027AFireInside Room 105 (AP) (shut unit down). Vertical 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 10x10N/A
5126AD-5-G-028FireRoom 126A By AHU 9 (AP) (shut unit down) (lift up to reset) horizontal 16/20.NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 16x20N/A
5126AD-5-G-029FireRoom 126A By AHU 9 (AP) (shut unit down) (lift up to reset). Horizontal 16/20.NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 16x20N/A
5126AD-5-G-030FireRoom 126A By AHU 9 (AP) (shut unit down) (lift up to reset). Horizontal 16/20.NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 16x20N/A
5126AD-5-G-031FireRoom 126A By AHU 9 (AP) (shut unit down) (lift up to reset)NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 16x20N/A
5126AD-5-G-032FireRoom 126A By AHU 9 (AP) (shut unit down) (lift up to reset). Horizontal 14/20.NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 14x20 - Very limited accessN/A
5126AD-5-G-033FireRoom 126A By AHU 9 (AP) (shut unit down) (lift up to reset) horizontal 14/20NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 14x20 - Very limited accessN/A
5126AD-5-G-034FireRoom 126A By AHU 9 (AP) (when shut unit down water floods flr) 18/24NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 18x24 - Very limited accessN/A
5126AD-5-G-035FireRoom 126A By AHU 9 (AP) (when shut unit down water floods flr) 18/24NoDemolishedxFLN/AOpenClosedOpenPassHorizontal 18x24 - Very limited accessN/A
5193AD-5-G-036FireRoom 193A (AP). 16/24 vertical.Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 16x24 - Very limited accessN/A
5193AD-5-G-037FireRoom 193A (AP). Vertical 16/26. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 16x26N/A
5193AD-5-G-038FireRoom 193A (AP). 10/12 vertical. Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 10x12 - Poor placementN/A
5193AD-5-G-039FireRoom 193A (AP). 10/12 vertical. Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 10x12 - Very limited accessN/A
5E124D-5-G-040FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 10/10 limited access.YesActiveXFLN/AOpenClosedOpenPassHorizontal 10x10 - Very limited accessN/A
5E124D-5-G-041FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x20 - 8x8 Access DoorN/A
5E124D-5-G-042FireRoom E124 back wall behind AHU's (NAP) (shut unit down). Horizontal 18/20.YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x20 - 8x8 Access DoorN/A
5E124D-5-G-043FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/17.YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x17N/A
5E124D-5-G-044FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/17.YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x17N/A
5E124D-5-G-045FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/24YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x24 - Very limited accessN/A
5E124D-5-G-046FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x20 - Very limited accessN/A
5E124D-5-G-047FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x20 - Very limited accessN/A
5E124D-5-G-048FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20.YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x20 - Very limited accessN/A
5E124D-5-G-049FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/23.YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x23 - Very limited accessN/A
5E124D-5-G-050FireRoom E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/23.YesActiveXFLN/AOpenClosedOpenPassHorizontal 18x23 - Very limited accessN/A
5F02D-5-G-051Fire/SmokeCorridor F02 By the exit sign in Oncology South (AP) (shut AHU off). Vertical. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXN/AFAOpenClosedOpenFail/PASSVertical - Used magnet alarm sent but no reaction from actuator used key switch alarm sent no reaction from actuatorTests Okay -W/O 10245404911/20/19
5F02D-5-G-051AFire/SmokeCorridor F02 By the exit sign in Oncology North (AP) (shut AHU off). Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXN/AFAOpenClosedOpenFail/PASSVertical - Used magnet alarm sent but no reaction from actuator used key switch alarm sent no reaction from actuatorTests Okay-W/O 10245404911/20/19
52020BD-5-G-052Fire/SmokeHall outside Room 2025 East Side (AP). 36/20. horizontal. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXN/AFAOpen?OpenFail/PASSHorizontal (main) 36X20 - No retaining angle nor reaction from actuator on magnet or key switch. -Air Handling Unit No Shut Down -Doesn't Stay Lit. Need to repair damper power and retest and install retaining angle. Damper requires repairs. Damper not moving. Working to get quote from JCI to correct1/7/2025. Work planned for week of 3/17/2025.- Johnson Controls fixed the programming and now the damper closes when duct smoke detector is activated and also shuts down AHU 42. 3-18-2025 VA Work Order #125662070 & PO: PA5828Fire caulk installed. Tests okay on 1/7/2025. Maximo service request #3557575.3/18/25
52025D-5-G-053Fire/SmokeRoom 2025 West Side (AP). Vertical 18/28. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXN/AFAOpenClosedOpenFail/PASSVertical 18x28 - No retaining angle wrong - Damper didn’t close. Need Retaining angle installed at this location.Tests Okay. Retaining angles present during observations 1/7/2025. Maximo service request #3557575.1/7/25
52025D-5-G-053AFire/SmokeRoom 2025 East Side (AP). Horizontal 8/8.Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXN/AFAOpenOpenOpenFail/PASSHorizontal 8x8 - No retaining angles -No Duct Smoke. Need Retaining angle installed at this location. Damper does close when duct smoke in hallway alarms (Dev 121). Duct smoke is not required on exhaust duct per NFPA 90A, 2024 addition, 11.4.2.3.Fire caulk installed. Tests okay on 1/7/2025. Maximo service request #3557575.1/23/25
52020CD-5-G-053BFire/SmokeHall 2020C North Side of Fire Doors (AP) (Shut unit down). E503. vertical.NoActiveXN/AFAOpenClosedOpenPassVertical - No retaining anglesN/A
51012D-5-G-054Fire/SmokeRM 1012 By AHU 42 (AP). Vertical 16/26.YesActiveXN/AFAOpenClosedOpenPassVertical 16x26N/A
51012D-5-G-055Fire/SmokeRM 1012 By AHU 42 (AP). Vertical 12/14.YesActiveXN/AFAOpenClosedOpenFail/PASSVertical 12x14 - Investigate actuator power to it when alarm
sent but does not function properly. Damper must be binding which isn't allowing damper to operate.Actuator Adjusted. Tests okay. Maximo service request #3557575.1/7/25
51012D-5-G-056Fire/SmokeRM 1012 By AHU 42 (AP). Vertical 10/12YesActiveXN/AFAOpenClosedOpenFail/PASSVertical 10x12 - Investigate actuator power to it when alarm
sent but does not function propelyDamper must be binding which isn't allowing damper to operate.Actuator Adjusted. Tests okay. Maximo service request #3557575.1/7/25
51012D-5-G-057Fire/SmokeRM 1012 By AHU 42 (AP). Vertical 40/42.YesActiveXN/AFAOpenClosedOpenFail/PASSVertical 40x42 - Investigate actuator power to it when alarm
sent but does not function properlyTests Okay -W/O 10245404911/20/19
51012D-5-G-058Fire/SmokeRM 1012 By AHU 42 (AP). Vertical 36/38. (AHU#3 RM A12 duct smokes control)YesActiveXN/AFAOpenClosedOpenPassVertical 36x38 - Control A12 no smokeN/A
51012D-5-G-059Fire/SmokeRM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 22/40YesActiveXN/AFAOpenClosedOpenPassVertical 22x40 - Activated by AHU-33N/A
51012D-5-G-060Fire/SmokeRM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 16/22 vertical.YesActiveXN/AFAOpenClosedOpenPassVertical 16x22 - Activated by AHU-33N/A
51012D-5-G-061Fire/SmokeRM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down)16/22 vertical.YesActiveXN/AFAOpenClosedOpenPassVertical 16x22 - Activated by AHU-33N/A
51012D-5-G-062Fire/SmokeRM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 18/24 vertical.YesActiveXN/AFAOpenClosedOpenPassVertical 18x34 - Activated by AHU-33N/A
51012D-5-G-063Fire/SmokeRM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 18/24 vertical.YesActiveXN/AFAOpenClosedOpenPassVertical 18x34 - Activated by AHU-33N/A
51030D-5-G-064Fire/SmokeRoom 1030 (NAP) 26/40 Supply Duct. Minimum access.YesActiveXN/AFAOpenClosedOpenPassMinumum accessN/A
51030D-5-G-065SmokeRoom 1030 (NAP) 70/26 return duct near chase.YesActiveXN/AFAOpenClosedOpenFail/PASSit's a smoke damper 10 feet from wall. -Access panel needed.It is in Mechanical Room. Dampers 065 and 065A are installed at locations identified on the construction documents. Access panel and test request under Maximo service request #3628565 1/28/2025.2/12/25
5G20AD-5-G-065AFireRoom G20A (AP) 70/30 Return ductYesActiveXFLN/AOpenClosedOpenPassJCI inspected and passed inspection Aug 2022.
51030D-5-G-065BSmokeRoom 1030 (NAP) 60/40 supply duct near AHUYesActiveXFLN/AOpenClosedOpenFail/PASSNeeds acces panel. Needs duct smoke by it, JCI to quote.Access panel and test request under Maximo service request #3628565 1/28/2025.2/15/25
5G20AD-5-G-065CFireRoom G20A (NAP) 12/20 exhaust ductYesActiveXFLN/AOpenClosedOpenFail/PASSNeeds access panelAccess panel and test request under Maximo service request #3628565 1/28/2025.2/12/25
5G20AD-5-G-066Fire/SmokeRoom G20A (AP in G20A) 62/30 Supply Duct Activate Duct smoke in RM 1030.YesActiveXN/AFAOpenClosedOpenPassGood accessN/A
5W08D-5-G-067FireRoom W08 (AP). Vertical 8/16. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 8x16N/A
5W08D-5-G-068FireRoom W08 (AP). Vertical 8" round. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 8" round - Ductwork sweating really badN/A
5W09D-5-G-069FireRoom W09 (AP). Vertical 12/18. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 12x18N/A
5W12D-5-G-070FireRoom W12 (AP). Vertical 6/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 6x10N/A
5W06D-5-G-071FireRoom W06 (AP). Vertical 10/12. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 10x12N/A
5E07D-5-G-072FireRoom E07 By South Exit (NAP)YesActiveX??NAPNAPNAPFail/PASSNo access door -Access panel needed.VA tested and damper passed Aug 2022.11/25/19
5E07D-5-G-073FireRoom E07 Ctr East Wall (NAP)YesActiveX??NAPNAPNAPFail/PASSNo access door - pneumatic damper installed in appears to be
welded stainless duct. Could not verify. -Access panel needed.VA tested and damper passed Aug 2022.11/25/19
5E01D-5-G-074FireRoom E01 West Wall. Vertical 24/24YesActiveXFLN/AOpenClosedOpenPassVertical 24x24 - Dynamic no duct to it.
5E19D-5-G-075FireOutside Room E19 Double Doors (AP). Vertical 6/6. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenOpenOpenPassVertical 6x6 - Very limited accessN/A
5E19D-5-G-076FireOutside Room E19 Double Doors (AP). Verticl 4/8. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 4x8 - Very limited accessN/A
5E15D-5-G-077FireRoom E15 (AP). Vertical 6/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 6x10 - Very limited accessN/A
5E15D-5-G-078FireRoom E15 (AP). Vertical 8/8. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 8x8 - Very limited accessN/A
5E15D-5-G-079FireRoom E15 (AP). Vertical 8/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files.NoActiveXFLN/AOpenClosedOpenPassVertical 8x10 - Very limited accessN/A
5E18D-5-G-080FireRoom E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper OpenNoActiveXFLN/AOpenClosedOpenPassN/A
5E18D-5-G-081FireRoom E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper OpenNoActiveXFLN/AOpenClosedOpenPassN/A
5E18D-5-G-082FireRoom E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper OpenNoActiveXFLN/AOpenClosedOpenPassN/A
5E18D-5-G-083FireRoom E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper OpenNoActiveXFLN/AOpenClosedOpenPassN/A
5E18D-5-G-084FireRoom E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper OpenNoActiveXFLN/AOpenClosedOpenFail/PassNo retaining angle on wall.Provide and install retaining angle.JCI inspected and passed inspection Aug 2022. Retaining angle under Maximo service request #3628565 1/28/2025. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required.