Attachment B Current Damper Inventory Tracker.xlsx
XLSX spreadsheet 5 MB Posted
- Solicitation number
- 36C26325Q1047
About this file
This document is an Excel spreadsheet tracking fire, smoke, and fire/smoke dampers for the Sioux Falls VA Healthcare System, containing an inventory of 571 total damper entries across multiple buildings. The comprehensive tracker details each damper's location, type, status, inspection results, and specific characteristics such as size, orientation, and testing outcomes, with most dampers categorized as active fire, smoke, or fire/smoke dampers.
The associated federal contract opportunity (Solicitation Number: 36C26325Q1047) seeks a service agreement for fire damper inspection and testing at the Sioux Falls VA Healthcare System. The pre-solicitation involves field verification, inspection, and testing of active and abandoned fire, smoke, and combination fire/smoke dampers according to NFPA 80 requirements. The contractor will be responsible for documenting findings, updating spreadsheets and drawings, installing access panels, and potentially performing repairs. The contract includes multiple contract line items (CLINs) for different services such as field verification, damper testing, access panel installation, and parts repair, with work to be performed Monday through Friday during business hours, excluding federal holidays.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachement A Fire Damper Location DWGs Sioux Falls Bldgs 1 and 5 and 54.pdf | ||
| 36C26325Q1047.docx | DOCX document | |
| Response Form to Sources Sought Notice.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Table 1
| Fire, Smoke, & Fire/Smoke Damper Testing, Tracking, and Inventory | Sum of All Damper Type Counts in table | 571 | TOTAL Damper Entries | 571 | ||
| Location: SFVAHCS | Damper Type Count (ALL Buildings) | 378 | Dampers that require inspection. | FL = Removal/Replace Fus. Link |
PDA = Removed Pwr at Damper FA = Via Fire Alarm Activation AP = Access Panel Available NAP = No Access Panel
| CR = Can't Reach | ACP = Accuator Closed Position CT = Can't Test | |
| AOP = Accuator Open Position Open = Damper Visibly Open Closed = Damper Visibly Closed Inspected By: Ryan Henglefelt DATEs of inspection 9/16/2019 Thur 9/20/2019 | Inspection: Fire & Fire/Smoke Damper Testing |
Frequency: 6 year Code REF: NFPA 80 Article 19.5 2019 Addition NFPA 80 Article 19.5.1.3 2019 Addition NFPA 105 Article 7.6 2019 Addition Inspection: Fire & Fire/Smoke Damper TestingFL = Removal/Replace Fus. LinkACP = Accuator Closed Position CT = Can't Test AOP = Accuator Open Position Open = Damper Visibly Open Closed = Damper Visibly Closed Inspected By: xxxxxxxxx DATEs of inspection PDA = Removed Pwr at Damper FA = Via Fire Alarm Activation AP = Access Panel Available NAP = No Access Panel CR = Can't Reach Frequency: 6 year Code REF: NFPA 80 Article 19.5 xxxx Addition NFPA 80 Article 19.5.1.3 xxxx Addition NFPA 105 Article 7.5.2 xxxx Addition
| Address: 2501 W. 22nd St. | Active Fire | 229 | Abandoned - Fire | 35 | Not Required Active Combination Fire/Smoke Dampers | 20 | |||||||||||||||
| City/State/Zip: SF, SD 57105 | Active Smoke | 16 | Not required Active Fire Damper | 95 | Not required Disabled Smoke Dampers | 2 | |||||||||||||||
| Contact: Sioux Falls | Active Fire/Smoke | 98 | Not Required Active Smoke Damper | 25 | Not required Disabled Fire/Smoke Dampers | 0 | |||||||||||||||
| Blanks (D, F, G) | 0 | Demolished - All Dampers | 51 | 0 | |||||||||||||||||
| Building | Room Number | Damper | |||||||||||||||||||
| Number | Damper | ||||||||||||||||||||
| Type | Description/Location: (Notes: AP, NAP, etc.) or Justification for Removal | Damper required? | Damper Status | Date Damper put into service | Added to "SFVA Dampers" dwg | Fusible Link | |||||||||||||||
| Test Method | Non-Fusible Link | ||||||||||||||||||||
| Test Method | Pre-Test | ||||||||||||||||||||
| Position (Open/Closed) | Test | ||||||||||||||||||||
| Position (Open/Closed) | Post-Test | ||||||||||||||||||||
| Position (Open/Closed) | Test | ||||||||||||||||||||
| Result | Deficiences | Corrective Action Taken | Date | ||||||||||||||||||
| Corrected | Test | ||||||||||||||||||||
| Result | Deficiences | Corrective Action Taken | Date | ||||||||||||||||||
| Corrected | ILSM IN Place? | ||||||||||||||||||||
| 1 | 307 | D-1-G-001 | Fire | 6" round horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307A | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round horizontal | N/A | ||||||
| 1 | 307 | D-1-G-002 | Fire | 6x6 horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307A | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 horizontal | N/A | ||||||
| 1 | 307 | D-1-G-003 | Fire | 6" round horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307A | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round horizontal | N/A | ||||||
| 1 | 307 | D-1-G-004 | Fire | 6" round horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307A | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round horizontal | N/A | ||||||
| 1 | 307 | D-1-G-005 | Fire | 6x6 horizontal. Room 307 (AP) *2 dampers listed w/ 307 need to move to 307A | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 horizontal | N/A | ||||||
| 1 | 307B | D-1-G-005A | Fire/Smoke | Room 307B (AP) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Activated key switch alarm sent but no reaction from | |||||||
| actuator used magnet alarm sent but no reaction from actuator | Tested Okay -W/O 102454049 | 11/8/19 | |||||||||||||||||||
| 1 | 307B | D-1-G-005B | Fire/Smoke | Room 307B (AP) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Activated key switch alarm sent but no reaction from actuator used magnet alarm sent but no reaction from | |||||||
| actuator | Tested Okay -W/O 102454049 | 11/8/19 | |||||||||||||||||||
| 1 | 307D | D-1-G-006 | Fire | 6" round. Room 307D (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 307D | D-1-G-007 | Fire | 6/6. Room 307D (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 307C | D-1-G-008 | Fire | 6/6. Room 307C (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 301 | D-1-G-009 | Fire | 6" round. Room 301 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 336 | D-1-G-010 | Fire | Room 336 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 336B | D-1-G-010A | Fire | 6" round. Room 336B (AP) *Update to 336A? | Yes | Active | X | FL | N/A | Open | Open | Open | Fail/PASS | 6" round Broken Links | Replaced Links & Tests Okay Now -W/O 102756589 | 12/9/19 | |||||
| 1 | 315 | D-1-G-011 | Fire | 6/6. Room 315 (AP) (access through vent cover) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 318 | D-1-G-012 | Fire | 6" round. Room 318 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 308 | D-1-G-013 | Fire | Room 308 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 308 | D-1-G-014 | Fire | Room 308 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 308 | D-1-G-014A | Fire/Smoke | Room 308 (AP) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Activated key switch alarm sent no reaction at actuator used magnet tripped alarm no reaction from actuator | Tested Okay -W/O 102454049 | 11/8/19 | |||||
| 1 | 308 | D-1-G-014B | Fire/Smoke | Room 308 (AP) | Yes | Active | X | N/A | FA | Open | Open | Open | Fail/PASS | Activated key switch alarm sent no reaction at actuator used magnet alarm no reaction from actuator | Tested Okay -W/O 102454049 | 11/8/19 | |||||
| 1 | 307C | D-1-G-015 | Fire | 6" round. Room 307C (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 306 | D-1-G-016 | Fire | 6/6. Room 306 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 306 | D-1-G-017 | Fire | 6" round. Room 306 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 304 | D-1-G-018 | Fire | 6" round. Room 304 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 304 | D-1-G-019 | Fire | Room 304 (AP) 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 309 | D-1-G-020 | Fire | Room 309 (AP). | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 309 | D-1-G-021 | Fire | Room 309 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see hard access door tight to grid | N/A | ||||||
| 1 | 302 | D-1-G-022 | Fire | Room 302 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 302 | D-1-G-023 | Fire | Room 302 (AP) 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Fail/PASS | 6x6 radiant link broke | Relaced Links and Tests Okay -W/O 0102454049 | 43805 | |||||
| 1 | 311 | D-1-G-024 | Fire | Room 311 (AP) (access through vent cover) 310? Don't see one in 311 on plans. Horizontal 6/6. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 6x6 | N/A | ||||||
| 1 | 318 | D-1-G-025 | Fire | Room 318 (AP) horizontal. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 333 | D-1-G-026 | Fire | Room 333 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 332 | D-1-G-027 | Fire | Room 332 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 332 | D-1-G-028 | Fire | Room 332 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 330 | D-1-G-029 | Fire | Room 330 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 330 | D-1-G-030 | Fire | Room 330 (AP). 6" ROUND | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 320 | D-1-G-031 | Fire | Room 320 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 320 | D-1-G-032 | Fire | Room 320 (AP) | Yes | Active | X | FL | N/A | Open | Closed | Open | Fail/PASS | Broken link radiant damper | Replaced Links & Tests Okay -W/O 102756589 | 12/9/19 | |||||
| 1 | 321 | D-1-G-033 | Fire | Room 321 (AP). Horizontal | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 321 | D-1-G-034 | Fire | Room 321 (AP). Use mirror. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 333 | D-1-G-035 | Fire | Room 333 (AP). Use mirror. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see hard access door tight to grid | N/A | ||||||
| 1 | 331 | D-1-G-036 | Fire | Room 331 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 327 | D-1-G-037 | Fire | Room 327 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round limited access | N/A | ||||||
| 1 | 327 | D-1-G-038 | Fire | Room 327 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 303 | D-1-G-039 | Fire | Room 303 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 329 | D-1-G-040 | Fire | Room 329 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round very limited access | N/A | ||||||
| 1 | 329 | D-1-G-041 | Fire | Room 329 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 331 | D-1-G-042 | Fire | Room 331 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 319 | D-1-G-043 | Fire | Room 319 (AP). Horizontal | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 319 | D-1-G-044 | Fire | Room 319 (AP). horizontal | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 326 | D-1-G-045 | Fire | Room 326 (AP). 8" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 8" round | N/A | ||||||
| 1 | 322 | D-1-G-046 | Fire | Room 322 (AP). Horizontal. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 322 | D-1-G-047 | Fire | Room 322 (AP). Use mirror. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 325 | D-1-G-048 | Fire | Room 325 (AP) *Only 2 dampers shown in 325 on dwg - need to locate 3rd in field. Horizontal | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 323 | D-1-G-049 | Fire | Room 323 (AP). Use mirror | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 323 | D-1-G-050 | Fire | Room 323 (AP). Horizontal. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 326 | D-1-G-051 | Fire | Room 326 (AP). 8" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 8" round | N/A | ||||||
| 1 | 325 | D-1-G-052 | Fire | Room 325 (AP) *Only 2 dampers shown in 325 on dwg - need to locate 3rd in field horizontal. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 325 | D-1-G-052A | Fire | Room 325 (AP) *Only 2 dampers shown in 325 on dwg - need to locate 3rd in field. Use mirror. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 324 | D-1-G-053 | Fire | Room 324 (AP). Horizontal | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal | N/A | ||||||
| 1 | 324 | D-1-G-054 | Fire | Room 324 (NAP) | Yes | Active | X | FL | N/A | Open | Closed | OP | Fail/PASS | No access panel -Access Panel Needed. Access panel is too far down from damper location needs moved to see damper or use camera in ductwork to see. There is damper access - HVAC noted that the screw holding the elbow can be removed which provides access. | Accessed from ductwork bottom side of damper. Maximo service request #3557575. | 1/7/25 | |||||
| 1 | 305 | D-1-G-055 | Fire | Room 305 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round limited access | N/A | ||||||
| 1 | 305 | D-1-G-056 | Fire | Room 305 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 328 | D-1-G-057 | Fire | Room 328 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 328 | D-1-G-058 | Fire | Room 328 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round limited access | N/A | ||||||
| 1 | 335 | D-1-G-059 | Fire | Room 335 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 335 | D-1-G-060 | Fire | Room 335 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 301 | D-1-G-061 | Fire | Room 301 (MH Check In) (AP). Use mirror. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Use mirror to see | N/A | ||||||
| 1 | 303 | D-1-G-062 | Fire | Room 303 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 334 | D-1-G-063 | Fire | Room 334 (AP). 6/6 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6x6 | N/A | ||||||
| 1 | 334 | D-1-G-064 | Fire | Room 334 (AP). 6" round | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | 6" round | N/A | ||||||
| 1 | 206 | D-1-G-065 | Fire/Smoke | Hall By Room 206 (NAP) Corr. 251A?. 8" round. | Yes | Active | X | N/A | FA | Open | Open | Open | Fail/PASS | 8" round - NAP - damper is in the middle of the hallway with flex going out one end to a RGD switch triggers alarm | |||||||
| but no movement from actuator | Tests Okay -W/O 102454049 | 11/8/19 | |||||||||||||||||||
| 1 | 209 | D-1-G-066 | Fire/Smoke | Hall By Room 209 (NAP) Corr. 251?. 8" round. | Yes | Active | X | N/A | FA | Open | Open | Open | Fail/PASS | 8" round - NAP - damper is completely on the outside of | |||||||
| the hallway 6" from the wall, key switch activates alarm but actuator does not move | Tests Okay -W/O 102454049 | 11/8/19 | |||||||||||||||||||
| 1 | 113 | D-1-G-067 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-068 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-069 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-070 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-071 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-072 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-073 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-074 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-075 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-076 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-077 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-078 | Fire | Floor south side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-079 | Fire | Floor south side - Return 12/12 | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-080 | Fire | Floor south side - Return 12/12 | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-081 | Fire | Floor south side - Return 12/12 | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-082 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-083 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-084 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-085 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-086 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-087 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-088 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-089 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-090 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-091 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-092 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-093 | Fire | Floor North Side | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-094 | Fire | Floor North Side - Return 12/12 | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-095 | Fire | Floor North Side - Return 12/12 | Yes | Active | X | Yes | |||||||||||||
| 1 | 113 | D-1-G-096 | Fire | Floor North Side - Return 12/12 | Yes | Active | X | Yes | |||||||||||||
| 1 | 009A | D-1-G-097 | Fire/Smoke | 6/6 OA duct. East wall. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 009A | D-1-G-098 | Fire/Smoke | 6/6 EA duct. East Wall | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 117 | D-1-G-099 | Fire/Smoke | 10/8 OA. Access panel in west wall. | Yes | Active | X | Fail | Tripped detector but didn't activate damper - alarm company to check wiring & programming | Yes | |||||||||||
| 1 | 117 | D-1-G-100 | Fire/Smoke | 12/8 EA duct. Access panel in west wall. | Yes | Active | X | Fail | Tripped detector but didn't activate damper - alarm company to check wiring & programming | Yes | |||||||||||
| 1 | 117 | D-1-G-101 | Fire/Smoke | 12/8 OA duct. West wall, south end. Ceiling light restricts accessibility. Dev 109 Triggers this damper. | Yes | Active | X | Fail | Tripped detector but didn't activate damper - alarm company to check wiring & programming. | Yes | |||||||||||
| 1 | 117 | D-1-G-102 | Fire/Smoke | 12/8 EA duct. West wall, north end. Ceiling light restricts accessibility. Dev 110 Triggers this damper. | Yes | Active | X | Fail | Tripped detector but didn't activate damper - alarm company to check wiring & programming. | Yes | |||||||||||
| 1 | 118 | D-1-G-103 | Fire/Smoke | 6/6 OA Duct. East wall. | Yes | Active | X | Fail | Not accessible | Yes | |||||||||||
| 1 | 118 | D-1-G-104 | Fire/Smoke | 6/6 EA duct. East Wall | Yes | Active | X | Fail | Not accessible | Yes | |||||||||||
| 1 | 244A | D-1-G-105 | Fire/Smoke | 6/6 OA duct. East wall. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 244A | D-1-G-106 | Fire/Smoke | 6/6 EA duct. East Wall. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 244 | D-1-G-107 | Fire/Smoke | 6/6 OA duct. West wall, south end. Dev 126 Triggers this damper. | Yes | Active | X | Pass | Yes | ||||||||||||
| 1 | 244 | D-1-G-108 | Fire/Smoke | 8/6 EA duct. West wall, north end.Dev 127 Triggers this damper | Yes | Active | X | Pass | Yes | ||||||||||||
| 1 | 360 | D-1-G-109 | Fire/Smoke | 6/6 EA duct. Access panel in east wall. | Yes | Active | X | Pass | Yes | ||||||||||||
| 1 | 360 | D-1-G-110 | Fire/Smoke | 6/6 OA duct. Access panel in east wall. | Yes | Active | X | Pass | Yes | ||||||||||||
| 1 | 312A | D-1-G-111 | Fire/Smoke | No damper at this location. Construction documents show 4th damper that does not exist. | No | Demolished | X | N/A | N/A | Yes | |||||||||||
| 1 | 312A | D-1-G-112 | Fire | Wall Transfer grille east. | Yes | Active | X | Fail | Not connected | Yes | |||||||||||
| 1 | 312A | D-1-G-113 | Fire | Wall Transfer grille east. | Yes | Active | X | Fail | Not connected | Yes | |||||||||||
| 1 | 312A | D-1-G-114 | Fire | Transfer fan. East wall. | Yes | Active | X | Fail | Not connected | Yes | |||||||||||
| 1 | 360 | D-1-G-115 | Fire/Smoke | 6/6 EA duct. East wall. Dev #139 or #140 Triggers this damper. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 360 | D-1-G-116 | Fire/Smoke | 6/6 OA duct. East wall. Dev #139 or #140 Triggers this damper. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 358A | D-1-G-117 | Fire/Smoke | 6/6 OA duct. East wall. Dev 132 Triggers this damper. | Yes | Active | X | Fail | Operated, but no accessibility. | Yes | |||||||||||
| 1 | 358A | D-1-G-118 | Fire/Smoke | 6/6 EA duct. East wall. Dev 133 Triggers this damper. | Yes | Active | X | Fail | Did not operate, no accessibility. | Yes | |||||||||||
| 1 | 355 | D-1-G-119 | Fire/Smoke | 6/6 OA duct. NW corner of room. | Yes | Active | X | Fail | No access, operated but no visual | Yes | |||||||||||
| 1 | 355 | D-1-G-120 | Fire/Smoke | 8/8 EA duct. NW corner of room. | Yes | Active | X | Fail | No access, operated but no visual | Yes | |||||||||||
| 1 | 407A | D-1-G-121 | Fire/Smoke | 6/6 OA duct. East wall. | Yes | Active | X | Fail | No access. Question of if these are required - is this a chase? | Yes | |||||||||||
| 1 | 407A | D-1-G-122 | Fire/Smoke | 6/6 EA duct. East wall. | Yes | Active | X | Fail | No access. Question of if these are required - is this a chase? | Yes | |||||||||||
| 1 | 411B | D-1-G-123 | Fire | Transfer. West wall. | Yes | Active | X | Fail | No way to actuate, no fusible link, not connected | Yes | |||||||||||
| 1 | 411B | D-1-G-124 | Fire | Transfer. North wall. | Yes | Active | X | Fail | No way to actuate, no fusible link, not connected | Yes | |||||||||||
| 1 | 404 | D-1-G-125 | Fire/Smoke | 28/12 OA duct. NW corner of room. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | 404 | D-1-G-126 | Fire/Smoke | 28/12 EA duct. NW corner of room. | Yes | Active | X | Fail | Inaccessible | Yes | |||||||||||
| 1 | ELEV-J | D-1-G-127 | Smoke | Smoke Damper not required evaluated by Vanguard contractor since no codes require them dated 2025/4/2. See RE: SIOUX FALLS VAMC – PRIORITY ONE PROJECTS: FIRE AND SMOKE DAMPER DECOMMISIONING report saved with JC files. | No | Active | X | Fail | Dampers not listed, not connected to power or alarm interface | Yes | |||||||||||
| 1 | 410 | D-1-G-128 | Fire/Smoke | 8/6 EA duct. East wall. | Yes | Active | X | Pass | Yes | ||||||||||||
| 1 | 410 | D-1-G-129 | Fire/Smoke | 8/6 OA duct. East wall. | Yes | Active | X | Pass | Yes | ||||||||||||
| 1 | ELEV-K | D-1-G-130 | Smoke | Smoke Damper not required evaluated by Vanguard contractor since no codes require them dated 2025/4/2. See RE: SIOUX FALLS VAMC – PRIORITY ONE PROJECTS: FIRE AND SMOKE DAMPER DECOMMISIONING report saved with JC files. | No | Active | X | Fail | Dampers not listed, not connected to power or alarm interface | Yes | |||||||||||
| 1 | ELEV-L | D-1-G-131 | Smoke | Smoke Damper not required evaluated by Vanguard contractor since no codes require them dated 2025/4/2. See RE: SIOUX FALLS VAMC – PRIORITY ONE PROJECTS: FIRE AND SMOKE DAMPER DECOMMISIONING report saved with JC files. | No | Active | X | Fail | Dampers not listed, not connected to power or alarm interface | Yes | |||||||||||
| 1 | 206 | D-1-G-132 | Fire | Yes | Active | X | Yes | ||||||||||||||
| 1 | 206 | D-1-G-133 | Fire | Yes | Active | X | Yes | ||||||||||||||
| 1 | 251 | D-1-G-134 | Fire | Yes | Active | X | Yes | ||||||||||||||
| 1 | 251 | D-1-G-135 | Fire | Yes | Active | X | Yes | ||||||||||||||
| 1 | 238 | D-1-G-136 | Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 237 | D-1-G-137 | Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 226 | D-1-G-138 | Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 226 | D-1-G-139 | Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 226 | D-1-G-140 | Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 349 | D-1-G-141 | Fire/Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 348 | D-1-G-142 | Fire/Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 324 | D-1-G-143 | Fire/Smoke | Yes | Active | X | Yes | ||||||||||||||
| 1 | 325 | D-1-G-144 | Fire/Smoke | Duct Chase into attic above room listed | Yes | Active | X | Yes | |||||||||||||
| 1 | 350 | D-1-G-145 | Fire/Smoke | Duct Chase into attic above room listed | Yes | Active | X | Yes | |||||||||||||
| 1 | 219B | D-1-G-146 | Fire | Abandoned. Closed 3/18/25. Duct is capped. 16/4. | Yes | Abandoned | X | Yes | |||||||||||||
| 1 | 219B | D-1-G-147 | Fire | Abandoned. Closed 3/18/25. Duct is capped. 27/7. | Yes | Abandoned | X | Yes | |||||||||||||
| 1 | 219B | D-1-G-148 | Fire | Abandoned. Closed 3/18/25. Duct is capped. 16/4. | Yes | Abandoned | X | Yes | |||||||||||||
| 1 | 250 | D-1-G-149 | Fire | Abandoned. Duct is capped. Access door on bottom of duct but inaccessible (it's above a hard deck). 31/8. | Yes | Abandoned | X | Yes | |||||||||||||
| 1 | 207 | D-1-G-150 | Fire | Demolished. 16/4. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 207 | D-1-G-151 | Fire | Demolished. 24/7. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 207 | D-1-G-152 | Fire | Demolished. 16/4. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 322B | D-1-G-153 | Fire | Demolished. 20/14. | No | Demolished | X | Yes | |||||||||||||
| 1 | 350 | D-1-G-154 | Fire | Damper in attic. Damper is open but inaccessible. Ductwork is capped & sealed at top. | Yes | Abandoned | X | Yes | |||||||||||||
| 1 | 350 | D-1-G-155 | Fire | Demolished. 16/12. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 317 | D-1-G-156 | Fire | Demolished. 22/18. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 317 | D-1-G-157 | Fire | Demolished. 32/8. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 348 | D-1-G-158 | Fire | Demolished. 20/14. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 307F | D-1-G-159 | Fire | Demolished. 14/17. Fire Duct capped at damper | No | Demolished | X | Yes | |||||||||||||
| 1 | 307E | D-1-G-160 | Fire | Demolished. 24/7. Fire | No | Demolished | X | Yes | |||||||||||||
| 1 | 351 | D-1-G-161 | Fire | Demolished. 14/14. Fire Duct capped at damper | No | Demolished | X | Yes | |||||||||||||
| 53 | 179A-53 | D-53-001 | Fire | Electrical closet removed. Unsure if damper remains.Damper Not required at this location | No | Active | X | ||||||||||||||
| 54 | 201 | D-54-G-001 | Fire | 22" dia SA duct. North of AHU. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 201 | D-54-G-002 | Fire | 20/18 RA duct. NE of AHU. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 201 | D-54-G-003 | Fire/Smoke | 12" dia SA duct. South of Elec 202-54 in truss space outside mechanical rooms. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 201 | D-54-G-004 | Fire/Smoke | 16/16 RA duct. South of Elec 202-54 in truss space outside mechanical rooms. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 201 | D-54-G-005 | Fire | 20/18 RA duct. SE of AHU. | Yes | Active | Jun-25 | ||||||||||||||
| 54 | 201 | D-54-G-006 | Fire | 22" dia duct. SW of AHU. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 201 | D-54-G-007 | Fire | 10/10 RA duct. SW of AHU. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 201 | D-54-G-008 | Smoke | 10/8 SA duct. Enters into stair 200. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 124A | D-54-G-009 | Fire/Smoke | 10/8 SA duct. Between bath 124 and den 121. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 100A | D-54-G-010 | Fire/Smoke | 16/12 SA duct. Between corridor 100A and walkway 100. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 111 | D-54-G-011 | Fire/Smoke | 8/8 RA duct. Betewen 109A and 111. | Yes | Active | Jun-25 | X | |||||||||||||
| 54 | 122 | D-54-G-012 | Fire | 14/10 EA Duct. Between 110 and 122. | Yes | Active | Jun-25 | X | |||||||||||||
| 5 | 435 | D-5-G-001 | Fire/Smoke | Room 435 Ceiling (AP) (test duct smoke on AHU 32 in attic) | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | N/A | |||||||
| 5 | 435 | D-5-G-002 | Fire/Smoke | Room 435 Ceiling (AP) (test duct smoke on AHU 32 in attic) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Used magnet alarm sent but no reaction from actuator | Tests Okay -See W/O 102454049 | 12/3/19 | |||||
| 5 | 337 | D-5-G-003 | Fire/Smoke | 20/14 EA Duct. West side of chase. Hall outside Room 337 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 337 | D-5-G-004 | Fire/Smoke | 20/14 EA Duct. North side of chase. Hall outside Room 337 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 336 | D-5-G-005 | Fire/Smoke | 28/14 SA west side chase. Hall outside Room 336 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 336 | D-5-G-006 | Fire/Smoke | SA duct. North side of Chase. Hall outside Room 336 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 334 | D-5-G-007 | Fire/Smoke | 46/16 RA duct. West side of chase. Hall outside Room 334 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Damper over hard lid -Access panel needed.Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 331E | D-5-G-008 | Fire/Smoke | Hall outside Room 331E (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Damper over hard lid -Access panel needed Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 309 | D-5-G-008A | Fire/Smoke | 20/20 SA Duct. Room 309 (AP) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Actuator not functioning (Noted on wrong floor) | Tests Okay -W/O 102454049 | 11/20/19 | |||||
| 5 | 309 | D-5-G-008B | Fire/Smoke | 18/12 RA Duct. Middle duct. Room 309 (AP) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Retaining angles not covering wall hole, damper actuator not | |||||||
| functioning (Noted on wrong floor). Duct work Needs Patch Work Around It. | Tests Okay -W/O 102454049. Confirmed patch work completed and retaining angles present 1/7/2025. | 11/20/19 | |||||||||||||||||||
| 5 | 309 | D-5-G-008C | Fire/Smoke | 18/12 RA Duct. East duct. Room 309 (AP) | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Actuator not functioning (Noted on wrong floor) | Tests Okay -W/O 102454049 | 11/20/19 | |||||
| 5 | 333 | D-5-G-008D | Fire/Smoke | Oxygen 333 | Yes | Active | X | N/A | Alarm | NAP | Fail/PASS | Found to be an extra. Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||||
| 5 | 228C | D-5-G-009 | Fire/Smoke | 16/16 EA Duct. Hall outside Room 228C (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel needed -See prints | Contractor installed access panels Aug. 2022, credit card PO PX2493. JCI inspected and passed inspection Aug. 2022. Tests okay. Maximo service request #3557575.1/7/2025 | 1/7/25 | |||||
| 5 | 233 | D-5-G-010 | Fire/Smoke | 28/18 SA duct. Hall outside Room 233 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 233 | D-5-G-011 | Fire/Smoke | 32/14 RA duct. Hall outside Room 233 (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 227D | D-5-G-011A | Fire/Smoke | Room 227D (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel or inspection opening needed at this location | Tests okay. Maximo service request #3557575. Installed access port for camera. | 1/7/25 | |||||
| 5 | 226A | D-5-G-012 | Fire/Smoke | Hall behind exit sign by 226A (NAP) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel needed. Damper requires repairs. Binding as tested on 1/7/2025. | Carpenter shop assigned service request to install access panel coordinating with HVAC 1/15/2025. | 1/28/25 | |||||
| 5 | 209 | D-5-G-012A | Fire/Smoke | Room 209 (AP but can't see louvers) | Yes | Active | X | N/A | FA | NAP | NAP | NAP | Fail/PASS | Access panel needed -See prints | Contractor installed access panels Aug. 2022, credit card PO PX2493. JCI inspected and passed inspection Aug. 2022. Tests okay. Maximo service request #3557575. | ||||||
| 5 | 145 | D-5-G-013 | Fire | Hall outside Room 147 (AP) Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | Demolision part of EHRM? Confirm | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x10 -Access panel needed | N/A | |||||
| 5 | 145 | D-5-G-014 | Fire | Hall outside Room 147 (AP)Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | Demolision part of EHRM? Confirm | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x10 | N/A | |||||
| 5 | 145 | D-5-G-015 | Fire | Hall outside Room 147 (AP). Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | Demolision part of EHRM? Confirm | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x10 | N/A | |||||
| 5 | 145 | D-5-G-016 | Fire | Room 145 (AP). Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | Demolision part of EHRM? Confirm | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x10 | N/A | |||||
| 5 | 175 | D-5-G-017 | Fire | Hall outside Room 175 (AP). Vertical. 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | Demolision part of EHRM? Confirm | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x10 | N/A | |||||
| 5 | 102 | D-5-G-018 | Fire | Hall outside Room 102 30/10 RA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | ? | ? | Open | Closed | Open | Pass | Vertical 10x30 - Very limited access | N/A | ||||||
| 5 | 134 | D-5-G-019 | Fire | Hall outside Room 134 (AP) (shut unit down) 48/10 RA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x48 - Small Access door | N/A | ||||||
| 5 | 133 | D-5-G-020 | Fire | Hall outside Room 133 (AP) (shut unit down) 36/18 RA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 18x36 | N/A | ||||||
| 5 | 133 | D-5-G-021 | Fire | Inside Room 133 (AP) (shut unit down) 24/14 SA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 14x24 - Very limited access | N/A | ||||||
| 5 | 110 | D-5-G-022 | Fire | Hall outside Room 110 (AP) (Shut unit down) 10" DIA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical round 12x12 | N/A | ||||||
| 5 | 110 | D-5-G-023 | Fire | Hall outside Room 110 (AP) (Shut unit down) 30/18 SA duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 18x24 | N/A | ||||||
| 5 | 109 | D-5-G-024 | Fire | Inside Room 109 (AP) 8" dia duct. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical round 8" | N/A | ||||||
| 5 | 105 | D-5-G-025 | Fire | Inside Room 105 (AP) (shut unit down). 6/12 vertical. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 6x12 | N/A | ||||||
| 5 | 105 | D-5-G-026 | Fire | Inside Room 105 (AP) (shut unit down). 6" round. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical round 6" | N/A | ||||||
| 5 | 105 | D-5-G-027 | Fire | Inside Room 105 (AP) (shut unit down). 8" round. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical round 8" | N/A | ||||||
| 5 | 105 | D-5-G-027A | Fire | Inside Room 105 (AP) (shut unit down). Vertical 10/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x10 | N/A | ||||||
| 5 | 126A | D-5-G-028 | Fire | Room 126A By AHU 9 (AP) (shut unit down) (lift up to reset) horizontal 16/20. | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 16x20 | N/A | ||||||
| 5 | 126A | D-5-G-029 | Fire | Room 126A By AHU 9 (AP) (shut unit down) (lift up to reset). Horizontal 16/20. | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 16x20 | N/A | ||||||
| 5 | 126A | D-5-G-030 | Fire | Room 126A By AHU 9 (AP) (shut unit down) (lift up to reset). Horizontal 16/20. | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 16x20 | N/A | ||||||
| 5 | 126A | D-5-G-031 | Fire | Room 126A By AHU 9 (AP) (shut unit down) (lift up to reset) | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 16x20 | N/A | ||||||
| 5 | 126A | D-5-G-032 | Fire | Room 126A By AHU 9 (AP) (shut unit down) (lift up to reset). Horizontal 14/20. | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 14x20 - Very limited access | N/A | ||||||
| 5 | 126A | D-5-G-033 | Fire | Room 126A By AHU 9 (AP) (shut unit down) (lift up to reset) horizontal 14/20 | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 14x20 - Very limited access | N/A | ||||||
| 5 | 126A | D-5-G-034 | Fire | Room 126A By AHU 9 (AP) (when shut unit down water floods flr) 18/24 | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x24 - Very limited access | N/A | ||||||
| 5 | 126A | D-5-G-035 | Fire | Room 126A By AHU 9 (AP) (when shut unit down water floods flr) 18/24 | No | Demolished | x | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x24 - Very limited access | N/A | ||||||
| 5 | 193A | D-5-G-036 | Fire | Room 193A (AP). 16/24 vertical.Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 16x24 - Very limited access | N/A | ||||||
| 5 | 193A | D-5-G-037 | Fire | Room 193A (AP). Vertical 16/26. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 16x26 | N/A | ||||||
| 5 | 193A | D-5-G-038 | Fire | Room 193A (AP). 10/12 vertical. Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x12 - Poor placement | N/A | ||||||
| 5 | 193A | D-5-G-039 | Fire | Room 193A (AP). 10/12 vertical. Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x12 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-040 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 10/10 limited access. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 10x10 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-041 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x20 - 8x8 Access Door | N/A | ||||||
| 5 | E124 | D-5-G-042 | Fire | Room E124 back wall behind AHU's (NAP) (shut unit down). Horizontal 18/20. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x20 - 8x8 Access Door | N/A | ||||||
| 5 | E124 | D-5-G-043 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/17. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x17 | N/A | ||||||
| 5 | E124 | D-5-G-044 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/17. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x17 | N/A | ||||||
| 5 | E124 | D-5-G-045 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/24 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x24 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-046 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x20 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-047 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x20 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-048 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/20. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x20 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-049 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/23. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x23 - Very limited access | N/A | ||||||
| 5 | E124 | D-5-G-050 | Fire | Room E124 back wall behind AHU's (AP) (shut unit down). Horizontal 18/23. | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Horizontal 18x23 - Very limited access | N/A | ||||||
| 5 | F02 | D-5-G-051 | Fire/Smoke | Corridor F02 By the exit sign in Oncology South (AP) (shut AHU off). Vertical. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Vertical - Used magnet alarm sent but no reaction from actuator used key switch alarm sent no reaction from actuator | Tests Okay -W/O 102454049 | 11/20/19 | |||||
| 5 | F02 | D-5-G-051A | Fire/Smoke | Corridor F02 By the exit sign in Oncology North (AP) (shut AHU off). Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Vertical - Used magnet alarm sent but no reaction from actuator used key switch alarm sent no reaction from actuator | Tests Okay-W/O 102454049 | 11/20/19 | |||||
| 5 | 2020B | D-5-G-052 | Fire/Smoke | Hall outside Room 2025 East Side (AP). 36/20. horizontal. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | N/A | FA | Open | ? | Open | Fail/PASS | Horizontal (main) 36X20 - No retaining angle nor reaction from actuator on magnet or key switch. -Air Handling Unit No Shut Down -Doesn't Stay Lit. Need to repair damper power and retest and install retaining angle. Damper requires repairs. Damper not moving. Working to get quote from JCI to correct1/7/2025. Work planned for week of 3/17/2025.- Johnson Controls fixed the programming and now the damper closes when duct smoke detector is activated and also shuts down AHU 42. 3-18-2025 VA Work Order #125662070 & PO: PA5828 | Fire caulk installed. Tests okay on 1/7/2025. Maximo service request #3557575. | 3/18/25 | |||||
| 5 | 2025 | D-5-G-053 | Fire/Smoke | Room 2025 West Side (AP). Vertical 18/28. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Vertical 18x28 - No retaining angle wrong - Damper didn’t close. Need Retaining angle installed at this location. | Tests Okay. Retaining angles present during observations 1/7/2025. Maximo service request #3557575. | 1/7/25 | |||||
| 5 | 2025 | D-5-G-053A | Fire/Smoke | Room 2025 East Side (AP). Horizontal 8/8.Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | N/A | FA | Open | Open | Open | Fail/PASS | Horizontal 8x8 - No retaining angles -No Duct Smoke. Need Retaining angle installed at this location. Damper does close when duct smoke in hallway alarms (Dev 121). Duct smoke is not required on exhaust duct per NFPA 90A, 2024 addition, 11.4.2.3. | Fire caulk installed. Tests okay on 1/7/2025. Maximo service request #3557575. | 1/23/25 | |||||
| 5 | 2020C | D-5-G-053B | Fire/Smoke | Hall 2020C North Side of Fire Doors (AP) (Shut unit down). E503. vertical. | No | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical - No retaining angles | N/A | ||||||
| 5 | 1012 | D-5-G-054 | Fire/Smoke | RM 1012 By AHU 42 (AP). Vertical 16/26. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 16x26 | N/A | ||||||
| 5 | 1012 | D-5-G-055 | Fire/Smoke | RM 1012 By AHU 42 (AP). Vertical 12/14. | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Vertical 12x14 - Investigate actuator power to it when alarm | |||||||
| sent but does not function properly. Damper must be binding which isn't allowing damper to operate. | Actuator Adjusted. Tests okay. Maximo service request #3557575. | 1/7/25 | |||||||||||||||||||
| 5 | 1012 | D-5-G-056 | Fire/Smoke | RM 1012 By AHU 42 (AP). Vertical 10/12 | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Vertical 10x12 - Investigate actuator power to it when alarm | |||||||
| sent but does not function propelyDamper must be binding which isn't allowing damper to operate. | Actuator Adjusted. Tests okay. Maximo service request #3557575. | 1/7/25 | |||||||||||||||||||
| 5 | 1012 | D-5-G-057 | Fire/Smoke | RM 1012 By AHU 42 (AP). Vertical 40/42. | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | Vertical 40x42 - Investigate actuator power to it when alarm | |||||||
| sent but does not function properly | Tests Okay -W/O 102454049 | 11/20/19 | |||||||||||||||||||
| 5 | 1012 | D-5-G-058 | Fire/Smoke | RM 1012 By AHU 42 (AP). Vertical 36/38. (AHU#3 RM A12 duct smokes control) | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 36x38 - Control A12 no smoke | N/A | ||||||
| 5 | 1012 | D-5-G-059 | Fire/Smoke | RM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 22/40 | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 22x40 - Activated by AHU-33 | N/A | ||||||
| 5 | 1012 | D-5-G-060 | Fire/Smoke | RM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 16/22 vertical. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 16x22 - Activated by AHU-33 | N/A | ||||||
| 5 | 1012 | D-5-G-061 | Fire/Smoke | RM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down)16/22 vertical. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 16x22 - Activated by AHU-33 | N/A | ||||||
| 5 | 1012 | D-5-G-062 | Fire/Smoke | RM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 18/24 vertical. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 18x34 - Activated by AHU-33 | N/A | ||||||
| 5 | 1012 | D-5-G-063 | Fire/Smoke | RM 1012 N. of Elev Fan Coil Units for Lobby (AP) (shut AHU down). 18/24 vertical. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Vertical 18x34 - Activated by AHU-33 | N/A | ||||||
| 5 | 1030 | D-5-G-064 | Fire/Smoke | Room 1030 (NAP) 26/40 Supply Duct. Minimum access. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Minumum access | N/A | ||||||
| 5 | 1030 | D-5-G-065 | Smoke | Room 1030 (NAP) 70/26 return duct near chase. | Yes | Active | X | N/A | FA | Open | Closed | Open | Fail/PASS | it's a smoke damper 10 feet from wall. -Access panel needed. | It is in Mechanical Room. Dampers 065 and 065A are installed at locations identified on the construction documents. Access panel and test request under Maximo service request #3628565 1/28/2025. | 2/12/25 | |||||
| 5 | G20A | D-5-G-065A | Fire | Room G20A (AP) 70/30 Return duct | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | JCI inspected and passed inspection Aug 2022. | |||||||
| 5 | 1030 | D-5-G-065B | Smoke | Room 1030 (NAP) 60/40 supply duct near AHU | Yes | Active | X | FL | N/A | Open | Closed | Open | Fail/PASS | Needs acces panel. Needs duct smoke by it, JCI to quote. | Access panel and test request under Maximo service request #3628565 1/28/2025. | 2/15/25 | |||||
| 5 | G20A | D-5-G-065C | Fire | Room G20A (NAP) 12/20 exhaust duct | Yes | Active | X | FL | N/A | Open | Closed | Open | Fail/PASS | Needs access panel | Access panel and test request under Maximo service request #3628565 1/28/2025. | 2/12/25 | |||||
| 5 | G20A | D-5-G-066 | Fire/Smoke | Room G20A (AP in G20A) 62/30 Supply Duct Activate Duct smoke in RM 1030. | Yes | Active | X | N/A | FA | Open | Closed | Open | Pass | Good access | N/A | ||||||
| 5 | W08 | D-5-G-067 | Fire | Room W08 (AP). Vertical 8/16. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 8x16 | N/A | ||||||
| 5 | W08 | D-5-G-068 | Fire | Room W08 (AP). Vertical 8" round. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 8" round - Ductwork sweating really bad | N/A | ||||||
| 5 | W09 | D-5-G-069 | Fire | Room W09 (AP). Vertical 12/18. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 12x18 | N/A | ||||||
| 5 | W12 | D-5-G-070 | Fire | Room W12 (AP). Vertical 6/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 6x10 | N/A | ||||||
| 5 | W06 | D-5-G-071 | Fire | Room W06 (AP). Vertical 10/12. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 10x12 | N/A | ||||||
| 5 | E07 | D-5-G-072 | Fire | Room E07 By South Exit (NAP) | Yes | Active | X | ? | ? | NAP | NAP | NAP | Fail/PASS | No access door -Access panel needed. | VA tested and damper passed Aug 2022. | 11/25/19 | |||||
| 5 | E07 | D-5-G-073 | Fire | Room E07 Ctr East Wall (NAP) | Yes | Active | X | ? | ? | NAP | NAP | NAP | Fail/PASS | No access door - pneumatic damper installed in appears to be | |||||||
| welded stainless duct. Could not verify. -Access panel needed. | VA tested and damper passed Aug 2022. | 11/25/19 | |||||||||||||||||||
| 5 | E01 | D-5-G-074 | Fire | Room E01 West Wall. Vertical 24/24 | Yes | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 24x24 - Dynamic no duct to it. | |||||||
| 5 | E19 | D-5-G-075 | Fire | Outside Room E19 Double Doors (AP). Vertical 6/6. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Open | Open | Pass | Vertical 6x6 - Very limited access | N/A | ||||||
| 5 | E19 | D-5-G-076 | Fire | Outside Room E19 Double Doors (AP). Verticl 4/8. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 4x8 - Very limited access | N/A | ||||||
| 5 | E15 | D-5-G-077 | Fire | Room E15 (AP). Vertical 6/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 6x10 - Very limited access | N/A | ||||||
| 5 | E15 | D-5-G-078 | Fire | Room E15 (AP). Vertical 8/8. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 8x8 - Very limited access | N/A | ||||||
| 5 | E15 | D-5-G-079 | Fire | Room E15 (AP). Vertical 8/10. Fire Damper not required evaluated by Vanguard contractor since the wall is no longer rated in report dated 2025/4/2. See report saved with JC files. | No | Active | X | FL | N/A | Open | Closed | Open | Pass | Vertical 8x10 - Very limited access | N/A | ||||||
| 5 | E18 | D-5-G-080 | Fire | Room E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper Open | No | Active | X | FL | N/A | Open | Closed | Open | Pass | N/A | |||||||
| 5 | E18 | D-5-G-081 | Fire | Room E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper Open | No | Active | X | FL | N/A | Open | Closed | Open | Pass | N/A | |||||||
| 5 | E18 | D-5-G-082 | Fire | Room E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper Open | No | Active | X | FL | N/A | Open | Closed | Open | Pass | N/A | |||||||
| 5 | E18 | D-5-G-083 | Fire | Room E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper Open | No | Active | X | FL | N/A | Open | Closed | Open | Pass | N/A | |||||||
| 5 | E18 | D-5-G-084 | Fire | Room E18 (AP) (shut EF3 unit down)(set up containment) Fire. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. Damper Open | No | Active | X | FL | N/A | Open | Closed | Open | Fail/Pass | No retaining angle on wall.Provide and install retaining angle. | JCI inspected and passed inspection Aug 2022. Retaining angle under Maximo service request #3628565 1/28/2025. 2025-01-31 Life Safety Contractor Jennifer O'Connell from Vanguard resources reviewed applicable codes and floor plans. Jennifer advised that the dampers located between the original building 5 and the SPS addition were not required. |